Air Systems 940 Remillard Court San Jose, California 95122 Phone: 408-280-1666 Fax: 408-280-1020 www.airsystemsinc.com
Re-Submittal Manualfor
CCCCD Project ADD ALT. 4A KINESIOLOGY BUILDING 11 (KIN)
Diablo Valley College321 Golf Club Road
Pleasant Hill, CA 94523 Direct Digital Control
ASI Job#: 18248-59
Engineered By:
Table of Contents Section I:
Section II:Section III:
Manufacturers Data Sheets Control DrawingsSequences of Operation
San Jose Office: 940 Remillard Ct., San Jose, California 95122 Phone: 408-280-1666 Fax: 408-280-1020 Website: www.airsystemsinc.com
Date:Air Systems Inc. April 1, 2019
DVC CADAVER LAB RENOVATIONFOR GENERAL REFERENCE ONLY
NOT PART OF CONTRACT
ASI Response to KIN ADD ALT. 4a Submittal Comments
Page 1 of 2
1. Drawing No. 1.1:
The enclosures for TCP-AH-1 and TCP-AH-4, as submitted under the D-1044 project, are NEMA Type 4.
2. Drawing No. 2.1:
Remote Start/Stop and Alarm/Fault points for both the Air-Cooled Chiller and Heating Hot Water Boiler are not currently points on the existing Andover system and therefore were not provided for on the ALC System. If required, they would constitute a Change Order Request; please advise. However, note that there did not appear to be an existing underground control conduit run to the Chiller Enclosure. Such a conduit would be necessary and quite costly.
Since there is no existing Status point for Exhaust Fan EF-1, no Remote Alarm Status point is provided. Again, if required, adding a Current Switch input point and alarm programming would constitute a Change Order Request. Please advise.
ALL existing (hardware) I/O points on the Andover System were picked up on the ALC System and an OSA lockout for both the Boiler and Chiller Systems is now provided for in the Sequence of Operation using (Global) OSA Temp. The Sequences of Operation also now include Manual Start/Stop (software points).
3. Drawing No. 2.3 and Page 3 of 3 of the Sequence of Operations:
All existing hardware points and the existing Sequence of Operation will be “replicated” and documented as part of the O&M Manual and As-Built Drawings. However, a detailed field survey was conducted subsequent to our original Submittal and revealed significant issues related to the current state of the Pool System Equipment and Pool Controller. Sixteen (16) of the twenty-three (23) existing automation points are NOT currently connected and/or operational, including ALL (5) of the OUTPUT points. Therefore, automatic control of any kind is not currently possible.
Air Systems Inc. 940 Remillard Court
San Jose, California 95122
Phone: 408-280-1666
ax: 408-280-1020 www.airsystemsinc.com
Section I
Manufacturers Data Sheets
San Jose Office: 940 Remillard Ct., San Jose, California 95122 Phone: 408-280-1666 Fax: 408-280-1020 Website: www.airsystemsinc.com
San Jose, CA 95122
T: 408-280-1666 F: 408-280-1020
Project Number:
Drawing Designation:
Project Name:
Drawing Date:
CCCCD PROJECT ADD ALT. 4A KIN BLDG. 11 18248-59
ADD ALT. 4A Re-Submittal4/1/2019
Manufacturer Part Number Part Description
Automated Logic EQT1-4-ALC Touch Screen Interface, Wall/Panel Mount w/Temp & Humidity, Rnet
Automated Logic ME812U Control Module, 8UO, 12UI, Supports 5 expanders
Automated Logic MEX48U Point Expander, 4UO, 8UI
Functional Devices TR100VA001 Xfmr 96VA,120:24,Ckt Brkr, Class 2
Functional Devices TR50VA005 Xfmr 50VA,120:24,Ckt Brkr, Class 2
Phoenix Contact RIF-1-RPT-LDP-24DC/1X21 - 2903342
SPDT Relay & Base, 24VDC Coil, 11A Switching Current
Veris V120 Enclosed Relay, SPDT, 24VAC/DC or 120VAC Coil, 20A
Veris VTD1P-UNI Time Delay Relay & Base, SPDT, 10 Functions, 24-240VAC/DC Coil, 15A
The Automated Logic® Equipment Touch Interface is an integral component of the WebCTRL® building automation system. It features an illuminated 4.3” color pixel touchscreen display and connects to a single equipment controller in the WebCTRL system. Designed for wall mounting, it provides building occupants, facility managers, and installers a powerful user interface for managing a single piece of equipment in a building.
Next level building automation engineered to help you make smart decisions.
1150 Roberts Boulevard, Kennesaw, Georgia 30144770-429-3000 Fax 770-429-3001 | www.automatedlogic.com © Automated Logic 2016
Equipment Touch InterfaceUnitary Equipment Control with Sensing
Occupant interface Equipment interface
Key Features and Benefits
• Illuminated 4.3”, 480 x 272 color pixel touchscreen display
• Built-in temperature and humidity sensing
• Connects to a single BACnet controller in the WebCTRLsystem using an Rnet connection
• Intuitive icon-driven / website-like screen navigation
• Default system screens such as scheduling and trendssupport international languages
• Ideal for single-zone rooftop applications such as officespaces and warehouses
• Multi-level password protection for security
• Intuitive equipment screen shows graphic and operatingstatus
• Easy access to equipment configuration, schedules, trends,and alarms
• Audible and visual alarm indication
For Building Occupants
The WebCTRL® building automation system gives you the ability to understand your building operations and analyze the results. The WebCTRL system integrates environmental, energy, security and safety systems into one powerful management tool that allows you to reduce energy consumption, increase occupant comfort, and achieve sustainable building operations. Our web-based platform allows building managers to control and access information about their HVAC, lighting, central plant and critical processes on premises or remotely at any time of day.
• View current space temperature
• View operating mode (heat / cool / economizer)
• Change setpoints easily
• Initiate timed local overrides
For Facility Managers
• Simple 4-wire installation
• Auto-discovers connected equipment controller
• Screen files can be auto-uploaded on select controllers,customized, or created from scratch
• Startup wizard and integrated help screens to assist withequipment startup and commissioning
For Installers Features
1150 Roberts Boulevard, Kennesaw, Georgia 30144770-429-3000 Fax 770-429-3001 | www.automatedlogic.com
Equipment Touch InterfaceSpecifications
Power Dedicated 24 Vac (±15%), 10 VA, 60 Hz, Class 2, isolated transformer, field supplied
Display 4.3 in. resistive touch screen color LCD display with backlighting (480x272 pixels)
Enclosure ABS plastic with polycarbonate bezel
Ports • Rnet: 2-wire EIA-485 port for connection to the Rnet network (115kbps)• USB port: for firmware upgrades
Microcontroller 32-bit
Memory • 16 MB flash memory to store screen file• 1.5 MB RAM to store variable data and LCD data• 4 KB Serial EEPROM to store non-volatile configuration data
Real-time clock 365-day real-time clock/calendar chip. The time and date is maintained for a minimum of 72 hours after loss of power (at room temperature).
Audible alarm A piezoeelectric sounder
Temperature sensor Range @ 95% RH: -4º F to 140º F (-20º C to 60º C)Range @ 20% RH: -4º F to 194º F (-20º C to 90º C)Accuracy @ 25º C: ±0.4º CAccuracy over 20º C to 30º C: ±0.5º CAccuracy over 10º C to 45º C: ±1.0º CAccuracy over full range: ±2.5º CResolution: 0.01º C
Humidity sensor Range: 0 to 100% RHAccuracy over 20 to 80% RH: ±3.0% RHAccuracy over full range: ±5.0% RHResolution: 0.05% RH
Environmental -4º F to 140º F (-20º C to 60º C), 10-90% RH, non-condensingoperating range
Mounting Wall or panel mounting
Overall dimensions Width: 5.4” (13.8 cm)Height: 4.5” (11.6 cm)Depth: 1.24” (3.2 cm)
Weight 8 oz. (0.23 kg)
Listed by UL-916 (PAZX), CE, FCC Part 15-Subpart B-Class AListed by UL-916 (PAZX), CE, FCC Part 15-Subpart B-Class A
width 5.440”
depth 1.242”
he
igh
t 4.5
50
”
All trademarks used herein are the property of their respective owners.
Next level building automation engineered to help you make smart decisions.
03242016
The Automated Logic® ME812 line of controllers
are integral components of the WebCTRL® building
automation system.
ME812u line controllers ave the speed, power, memory
and I/O flexibility to handle the most demanding control
applications in the industry. Capable of controlling
multiple pieces of HVAC equipment simultaneously,
this robust BACnet controller can support complex
control strategies with plenty of memory for trends,
and is capable of third-party integration using other
communication protocols.
Key Features and Benefits
Application Features
• Supports general HVAC applications including complex central plants
• Standard library of control programs available for most zoning applications
• Supports EIKON® graphical programming software, an object- oriented tool that provides complete flexibility for any custom control sequence that you need
• Supports Automated Logic® communicating sensors, which are available in a variety of zone sensing combinations and support setpoint adjustment and occupancy overrides
• Supports Automated Logic touchscreen interfaces for managing and troubleshooting the connected equipment easily
• Supports live, visual displays of control logic, which uses real time operational data and aids in optimizing and troubleshooting system operations
• Graphically programmed with self-documenting control sequences and a live view of all sequence components
• Fully graphically programmable, with full communications with other Automated Logic controllers
Hardware Features
• Controls 20 I/O points on the controller, and up to (6) MEx I/O expansion modules in panel configuration or remote mounted up to 100 ft away for scalable solutions (164 I/O points total)
• High-speed native BACnet communications to field devices over TCP/IP, Ethernet, high-speed ARCNET 156 Kbps or BACnet MS/TP networks
• Protocol translator package allows the ME controllers to serve as a gateway between BACnet and a wide range of open and proprietary networks
• Universal inputs and outputs, with HOA override switches and potentiometer adjustment available on all outputs
ME812u Controller Series Power ful, Multi-Equipment Controllers
Models: ME812u, ME812u-E, and ME812u-LGR
Next level building automation engineered to help you make smart decisions.
1150 Roberts Boulevard, Kennesaw, Georgia 30144770-429-3000 Fax 770-429-3001 | www.automatedlogic.com© Automated Logic 2018
The WebCTRL® building automation system gives you the ability
to understand your building operations and analyze the results.
The WebCTRL system integrates environmental, energy, security
and safety systems into one powerful management tool that
allows you to reduce energy consumption, increase occupant
comfort, and achieve sustainable building operations. Our web-
based platform allows building managers to control and access
information about their HVAC, lighting, central plant and critical
processes on premises or remotely at any time of day.
http://www.automatedlogic.com/pages/product-webctrl.aspxhttps://twitter.com/AutomatedLogic
1150 Roberts Boulevard, Kennesaw, Georgia 30144770-429-3000 Fax 770-429-3001 | www.automatedlogic.com
ME812u Controller Series Specifications
BACnet Support: Conforms to the BACnet Building Controller (B-BC) Standard Device as defined in BACnet 135-2001 Annex L. BTL Listing BACnet PICS
Communication Ports: ME812u Model EIA-485 port for ARCNET 156 Kbps or BACnet MS/TP (9600 baud to 76.8 Kbps) EIA-232/485 port* configurable port for BACnet PTP ME812u-E Model Ethernet port (10/100Mbps) only for BACnet/IP communications EIA-485 port for ARCNET 156 Kbps or BACnet MS/TP (9600 baud to 76.8 Kbps) EIA-232/485 port* configurable port for BACnet PTP ME812u-LGR Model Ethernet port* (10/100Mbps) for BACnet over Ethernet orBACnet/IP communications EIA-485 port for ARCNET 156 Kbps or BACnet MS/TP (9600 baud to 76.8 Kbps) EIA-232/485 port* configurable port for BACnet PTP *Third-Party integration drivers available through Ethernet and (1) EIA-232/485 configurable port All Models have Rnet port for Rnet communicating devices such as ZS room sensors and Touch interfaces. Xnet (500 Kbps) port for MEx I/O expansion modules. Local access port.
Universal Inputs: Twelve configurable universal inputs with 14-bit A/D resolution. Supported input types include: 0-5 V-dc, 0-10 V-dc, 0-20 mA, Thermistor (10k Ohm Type II), 1k Ohm RTD (Platinum, Nickel or Balco), and Dry Contact. All inputs support pulse counting up to 40 cycles per second (25mSec minimum pulse).
Universal Outputs Eight universal outputs are jumper configurable as 0-10V-dc, or 0-20mAdc with 12-bit A/D or 24V-dc @ 50mA relay drive. HOA (hand/off/auto) switches for all outputs, including potentiometer for manual adjustment of analog outputs
Expansion: Six MEx I/O expansion modules can be connected - one mounted directly on top of the controller, mounted locally in a stack configuration or remote-mounted up to 100ft away
Microprocessor: Powerful 32-bit Motorola Power PC microprocessor. High-performance 32-bit communication co-processor. I/O expansion CAN co-processor
Memory: 32-bit memory bus structure, 8 Mbyte flash memory, 16 Mbyte SDRAM battery-backed. Battery CR123A has life of 10 years with 720 hours of cumulative power outage
Real-time Clock: Battery-backed real-time clock
Status Indicators: LED status indicators for EIA-232/485 communication, and low battery status. Seven-segment status display for running, error, and power status
Module Addressing: Rotary dip switches for intuitive network addressing of modules
Protection: Built-in surge and transient protection circuitry for power, communications and I/O
Listed by: UL916 (Canadian Std C22.2 No. 205-M1983), CE, FCC Part 15 - Subpart B - Class A, BTL Listing
Environmental -20ºF to 140ºF (-29ºC to 60ºC); 10 to 90% relative humidity, non-condensingOperating Range:
Power Requirements: 24 V-ac ± 10%, 50-60Hz, 50VA, or 26 V-dc ± 10%, 23W. NOTE: Power consumption will increase when Equipment Touch or other accessories are attached.
Physical: Rugged aluminum cover. Removable screw terminal blocks
Weight: 1.4 lb. (0.635 kg)
Dimensions: Overall Mounting Holes Width: 7-1/2” (190mm) Width: 5” (127mm) Height: 11-5/16” (287mm) Height: 10-7/8” (276mm) Depth: 1-1/4” (32mm) min. panel depth
All trademarks used herein are the property of their respective owners.
Next level building automation engineered to help you make smart decisions.
08172018
https://www.bacnetinternational.net/btl/listings/automated%20logic/BTL_Listing_24054_ALC_WebCTRL.pdfhttps://www.bacnetinternational.net/catalog/manu/automated%20logic/ALC%20ME-LGR%20PICS.pdfhttps://www.bacnetinternational.net/btl/listings/automated%20logic/BTL_Listing_24054_ALC_WebCTRL.pdf
1150 Roberts BoulevardKennesaw, Georgia 30144770/429-3000Fax 770/429-3001www.automatedlogic.com
MEx I/O ExpanderSuperior Performance and Reliability
The MEx series of I/O expanders are designed for the powerful ME series of controllers, and for the most demanding control applications in the industry. The MEx I/O expanders can be remote mounted or directly mounted on the ME Controllers.
Key Features and Benefits
• High resolution Universal Inputs and Outputs for accuracy.• Easy expansion of I/O using up to five MEx I/O expansion modules in a stack panel configuration or remote
mounted up to 100ft away for scalable solutions.• First MEx I/O expander can be mounted directly on top of the ME812u controller, reducing control panel space.• Removable screw connectors for easy wiring, termination and service.• Tough construction delivers superior performance and reliability. Modules are constructed with a rugged
aluminum cover which provides optimum electrical protection and noise immunity.
Communication: Xnet I/O Expander bus for 500 Kbps communications between ME controller and I/O Expanders.
Universal Inputs: Configurable universal inputs with 14-bit A/D resolution. Supported input types include: 0-5 V-dc, 0-10 V-dc, 0-20 mA, Thermistor (10k Ohm Type II), 1k Ohm RTD (Platinum, Nickel or Balco), and Dry Contact. All inputs support pulse counting up to 40 cycles per second (12.5mSec minimum pulse duration).
Universal Outputs: Universal outputs that are jumper configurable as 0-10V-dc, or 0-20mAdc with 12-bit D/A or 24V-dc @ 50mA relay drive. HOA (hand/off/auto) switches for all outputs, including potentiometer for manual adjust-ment of analog outputs.
Expansion: Five MEx I/O expansion modules can be connected - one mounted directly on top of the controller, mounted locally in a stack configuration or remote mounted up to 100ft away. Compatible with legacy Mx I/O expanders using the 9-pin Sub-D connector only.
Status Indicators: LED status indicators for Power, Run, Error, Xnet TX and Xnet Rx.
Addressing: Rotary dip switches for intuitive network addressing of modules.
Protection: Built-in surge and transient protection circuitry for power, communications and I/O.
Listed by: UL916 (Canadian Std C22.2 No. 205-M1983), CE, FCC Part 15 - Subpart B - Class A.
Environmental Operating Range: -20ºF to 140ºF (-29ºC to 60ºC); 10 to 90% relative humidity, non-condensing.
Power Requirements: 24 V-ac ± 10%, 50-60Hz, 45VA, or 26 V-dc ± 10%, 21W. NOTE: Power consumption will increase when BACview6 or other accessories are attached.
Physical: Rugged aluminum cover. Removable screw terminal blocks.
Weight: 1.4 lb. (45.5 kg)
Dimensions:
MEx I/O ExpanderSpecif ications
OverallWidth: 4-3/4” (121mm)Height: 9” (229mm)Depth: 1-1/2” (38mm)
MountingWidth: 2-3/4” (70mm)Height: 8-1/2” (216mm)
Automated Logic Corporation . 1150 Roberts Boulevard . Kennesaw, Georgia 30144 . 770/429-3000 . Fax 770/429-3001 . www.automatedlogic.com
© United Technologies Corporation 2013. All rights reserved. Copyright Policy
BACnet is a registered trademark of ASHRAE. All other trademarks are the property of their respective owners. Specifications are subject to change without prior notice.
Automated Logic is a part of UTC Climate, Controls & Security, a unit of United Technologies Corp
MEX_CS_r4Made in the USA
Easy expansion of I/O using up to five MEx816u expanders.
Flexible Panel Configurations
Direct Mounting
Stack Panel Mounting Remote Panel Mounting
Product Universal Outputs Universal Inputs
MEx48u 4 8
MEx88u 8 8
MEx016u 0 16
MEx816u 8 16
2.00
0"
9.50"
4.000"
1.800"
Mounting Hole = .350" x .175"
.50"
2.500"
2.550"
3.00
0"
PRIMARY WIRES SECONDARY WIRES
Blk
Wht
Yel/Wht
Yel
Secondary Yel/Wht wire in phase with Primary Blk wire.
120V 60Hz 24Vac 100VA
VA Rating:Frequency:Mounting:
Over Current Protection:Dimensions:
Wire Length:Operating Temperature:
MTBF:Construction:
Weight:Approvals:
100 50/60 HzFoot & Single Threaded HubCircuit Breaker3.000˝ x 2.500˝ x 4.000˝ (w/ .500˝ NPT Hub)9.5˝ Typical w/ .5˝ Strip-30 to 140° F100,000 Hours @ 77° FSplit-Bobbin4.06 lbs.Class 2 UL5085-3 Listed, C-UL, CE, RoHS
TR100VA001 Transformer 100 VA, 120 to 24 Vac, Circuit Breaker, Foot and Single Threaded Hub Mount
Functional Devices, Inc. • p: 800.888.5538 • f: 765.883.7505 • www.functionaldevices.com • [email protected]
Transformer
Specifications
9.00" .50"
1.260"
2.00"
Mounting Hole = .350" x .175"
3.475"
1.950"
2.525"
3.000
"
PRIMARY WIRES SECONDARY WIRES
Blk
Wht
Yel/Wht
Yel
Secondary Yel/Wht wire in phase with Primary Blk wire.
120V 60Hz 24Vac 50VA
Class 2
VA Rating:Frequency:Mounting:
Over Current Protection:Dimensions:
Wire Length:Operating Temperature:
MTBF:Construction:
Weight:Approvals:
50 50/60 HzFoot & Single Threaded HubCircuit Breaker3.000˝ x 2.525˝ x 3.475˝ (w/ .500˝ NPT Hub)9˝ Typical w/ .5˝ Strip-30 to 140° F100,000 Hours @ 77° FSplit-Bobbin2.60 lbs.Class 2 UL5085-3 Listed, C-UL, CE, RoHS
SPECIFICATIONS
Transformer
TR50VA005 Transformer 50 VA, 120 to 24 Vac, Circuit Breaker, Foot and Single Threaded Hub Mount
Functional Devices, Inc.
310 South Union Street
Russiaville, IN 46979
Office
Sales
Fax
765.883.5538
800.888.5538
765.883.7505
Notes
www.FunctionalDevices.com
Industrial relay system
RIFLINE complete
2 PHOENIX CONTACT
You can carry out all standard relay
applications using the RIFLINE complete
industrial relay system. It doesn't matter
whether you want to isolate, multiply
or amplify signals.
The relay system, with a consistent plug-in
design, ensures high machine and system
availability. The area of application ranges
from coupling and timer relays through to
the small power contactor replacement.
Easy handling –RIFLINE complete relay system
Easy wiringthanks to push-in connection technology. This ensuresquick wiring without the need for any tools.
Easy potential distributionwith jumpers from the CLIPLINE complete system accessories.
Easy to extendusing the plug-in multifunctional timer module.
Three time functions can be selected in a time range from 0.5 seconds to 100 minutes.
Easy handling in detail
PHOENIX CONTACT 3
Complete relay familySwitch currents up to 16 A. From the coupling relay to the small power contactor replacement, the product range offers the right relay for every application.
High availability thanks to plug-in relays and function modulesRelays can be easily exchanged in the event of a service call. This, in turn, ensures a high machine and system availability.
Push-in technologyUtilize the proven push-in connection technology with RIFLINE complete. This ensures quick, tool-free wiring. The release button for releasing the conductor can be operated using a screwdriver or even a ballpoint pen.
4 PHOENIX CONTACT
Thanks to the diverse range of RIFLINE
complete products, a wide variety of
applications can be implemented using
the system. The relay can be extended
as desired using function modules.
Applications at a glance
Multifunctional timer moduleThe multifunctional plug-in timer module for 24 V transforms the relay module into a timer relay. The RIF-1 to RIF-4 bases can be fitted with this module.
Three time functions can be selected in a time range from 0.5 seconds to 100 minutes.
Switch-on delay
Passing make contact
Flasher unit
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
RUN-PRUN
STOPMRES
SF
BATF
DC5V
FRCE
RUN
STOP
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
PHOENIX CONTACT 5
Coupling relays between the controller and the field The RIF-0 and RIF-1 relay modules are used in particular to reliably couple signals between the controller and the field.As such, power is amplified, voltages are adjusted or signals are electrically isolated.
Relays for signal multiplicationThe RIF-2 relay modules are particularly suitable for applications in which a high number of contacts is required. A feedback signal to the controller can be switched in parallel with different loads.
From the power relay to the small power contactor replacementThe RIF-4 relay modules can be used in small power contactor applications thanks to their high switching capacity. The benefits in comparison with contactors are:• Easy maintenance thanks to
plug-in capability
• Operating indicator via status LED
• Inexpensive
• Quick installation thanks to bridgeability and push-in connection
From the coupling relay to the small power contactor replacement
6 PHOENIX CONTACT
You can decide for yourself whether you want to assemble RIFLINE complete individually – or order it ready assembled as a complete module. All components in the modular system
can be ordered individually depending on the application. This also includes relays that are available for a variety of voltages and applications.
RIFLINE complete – modular system1. Relay base2. Retaining bracket3. Relay4. Protective circuit5. Timer module (RIF-T3-24UC, Order No. 2902647) for RIF-1 to RIF-4 modules with 24 V input voltage
Standardized accessoriesRIFLINE complete uses the standardized accessories of the CLIPLINE complete modular terminal block system:
A: Bridging material B: Marking accessories such as zack marker strips and
marker carriersC: Test plugs
A
1B
2
C
3
45
Configuration made easy with CLIP PROJECT Configure the terminal strips and components for your control cabinet from Phoenix Contact easily using CLIP PROJECT – and prepare the corresponding markings at the same time. The planning software also supports you in selecting the correct accessories right through to ordering.
With CLIP PROJECT, you can benefit from a consistent process chain. This is achieved by way of the interaction with CAE systems.
Further information and download options can be found at:phoenixcontact.com
Modular relay system –for maximum flexibility and cost efficiency
PHOENIX CONTACT 7
Complete relay modules –RIFLINE complete order overview
Input voltage
Output contacts
Max.switching current 1) Type Order No.Switching voltage
RIF
-0
12 V DC 1 – 6 A 250 V AC/DC RIF-0-RPT-12DC/21 2903371
12 V DC 1 – 50 mA 2) 30 V AC/36 V DC RIF-0-RPT-12DC/21AU 2903369
12 V DC – 1 6 A 250 V AC/DC RIF-0-RPT-12DC/1 2903362
12 V DC – 1 50 mA 2) 30 V AC/36 V DC RIF-0-RPT-12DC/1AU 2903360
24 V DC 1 – 6 A 250 V AC/DC RIF-0-RPT-24DC/21 2903370
24 V DC 1 – 50 mA 2) 30 V AC/36 V DC RIF-0-RPT-24DC/21AU 2903368
24 V DC – 1 6 A 250 V AC/DC RIF-0-RPT-24DC/1 2903361
24 V DC – 1 50 mA 2) 30 V AC/36 V DC RIF-0-RPT-24DC/1AU 2903359
RIF
-1
24 V DC 1 – 11 A (13 A) 3) 250 V AC/DC RIF-1-RPT-LDP-24 DC/1x21 2903342
24 V DC 1 – 50 mA 2) 30 V AC/36 V DC RIF-1-RPT-LDP-24DC/1x21AU 2903338
24 V DC 2 – 8 A 250 V AC/DC RIF-1-RPT-LDP-24DC/2x21 2903334
24 V DC 2 – 50 mA 2) 30 V AC/36 V DC RIF-1-RPT-LDP-24DC/2x21AU 2903330
24 V AC 1 – 10 A (12 A) 3) 250 V AC/DC RIF-1-RPT-LV-24AC/1x21 2903341
24 V AC 1 – 50 mA 2) 30 V AC/36 V DC RIF-1-RPT-LV-24AC/1x21AU 2903337
24 V AC 2 – 8 A 250 V AC/DC RIF-1-RPT-LV-24AC/2x21 2903333
24 V AC 2 – 50 mA 2) 30 V AC/36 V DC RIF-1-RPT-LV-24AC/2x21AU 2903329
120 V AC 1 – 10 A (12 A) 3) 250 V AC/DC RIF-1-RPT-LV-120AC/1x21 2903340
120 V AC 1 – 50 mA 2) 30 V AC/36 V DC RIF-1-RPT-LV-120AC/1x21AU 2903336
120 V AC 2 – 8 A 250 V AC/DC RIF-1-RPT-LV-120AC/2x21 2903332
120 V AC 2 – 50 mA 2) 30 V AC/36 V DC RIF-1-RPT-LV-120AC/2x21AU 2903328
230 V AC 1 – 10 A (12 A) 3) 250 V AC/DC RIF-1-RPT-LV-230AC/1x21 2903339
230 V AC 1 – 50 mA 2) 30 V AC/36 V DC RIF-1-RPT-LV-230AC/1x21AU 2903335
230 V AC 2 – 8 A 250 V AC/DC RIF-1-RPT-LV-230AC/2x21 2903331
230 V AC 2 – 50 mA 2) 30 V AC/36 V DC RIF-1-RPT-LV-230AC/2x21AU 2903327
RIF
-2
24 V DC 2 – 10 A 250 V AC/DC RIF-2-RPT-LDP-24DC/2x21 2903315
24 V DC 4 – 6 A 250 V AC/DC RIF-2-RPT-LDP-24DC/4x21 2903308
24 V AC 2 – 8.5 A 250 V AC/DC RIF-2-RPT-LV-24AC/2x21 2903313
24 V AC 4 – 5 A 250 V AC/DC RIF-2-RPT-LV-24AC/4x21 2903306
120 V AC 2 – 8.5 A 250 V AC/DC RIF-2-RPT-LV-120AC/2x21 2903311
120 V AC 4 – 5 A 250 V AC/DC RIF-2-RPT-LV-120AC/4x21 2903305
230 V AC 2 – 8.5 A 250 V AC/DC RIF-2-RPT-LV-230AC/2x21 2903310
230 V AC 4 – 5 A 250 V AC/DC RIF-2-RPT-LV-230AC/4x21 2903304
RIF
-3
24 V DC 2 – 10 A 250 V AC/DC RIF-3-RPT-LDP-24DC/2x21 2903297
24 V DC 3 – 8.5 A 250 V AC/DC RIF-3-RPT-LDP-24DC/3x21 2903294
120 V AC 2 – 7 A 250 V AC/DC RIF-3-RPT-LV-120AC/2x21 2903296
120 V AC 3 – 6 A 250 V AC/DC RIF-3-RPT-LV-120AC/3x21 2903293
230 V AC 2 – 7 A 250 V AC/DC RIF-3-RPT-LV-230AC/2x21 2903295
230 V AC 3 – 6 A 250 V AC/DC RIF-3-RPT-LV-230AC/3x21 2903292
RIF
-4
24 V DC 2 – 11 A 440 V AC/250 V DC RIF-4-RPT-LDP-24DC/2x21 2903281
24 V DC 3 – 10 A 440 V AC/250 V DC RIF-4-RPT-LDP-24DC/3x21 2903278
24 V DC – 3 10 A 440 V AC/250 V DC RIF-4-RPT-LDP-24DC/3x1 2903275
120 V AC 2 – 9 A 440 V AC/250 V DC RIF-4-RPT-LV-120AC/2x21 2903280
120 V AC 3 – 8 A 440 V AC/250 V DC RIF-4-RPT-LV-120AC/3x21 2903277
120 V AC – 3 8 A 440 V AC/250 V DC RIF-4-RPT-LV-120AC/3x1 2903274
230 V AC 2 – 9 A 440 V AC/250 V DC RIF-4-RPT-LV-230AC/2x21 2903279
230 V AC 3 – 8 A 440 V AC/250 V DC RIF-4-RPT-LV-230AC/3x21 2903276
230 V AC – 3 8 A 440 V AC/250 V DC RIF-4-RPT-LV-230AC/3x1 2903273
1) Type dependent – please observe contact derating2) Due to multi-layer contact3) For use of the jumper between 11 and 21
43 mm
40 mm
6.2 mm
16 mm
31 mm
Always up-to-date, always available to you. Here you'll find everything on our products, solutions and service:
phoenixcontact.com
Product range
IF 0
6-14
.000
.L3
Pr
inte
d in
Ger
man
yM
NR
520
0362
8//2
014-
03-0
7/02
©
PH
OEN
IX C
ON
TAC
T 2
014
• Cables and wires• Connectors• Controllers• Electronics housing• Electronic switchgear and
motor control• Fieldbus components and systems• Functional safety• HMIs and industrial PCs• I/O systems
• Industrial communication technology• Industrial Ethernet• Installation and mounting material• Lighting and signaling• Marking and labeling • Measurement and control technology• Modular terminal blocks• Monitoring• PCB terminal blocks and
PCB connectors
• Power supply units and UPS• Protective devices• Relay modules• Sensor/actuator cabling• Software• Surge protection and interference filters• System cabling for controllers• Tools• Wireless data communication
PHOENIX CONTACT GmbH & Co. KG32825 Blomberg, GermanyPhone: +49 (0) 52 35 3-00Fax: +49 (0) 52 35 3-4 12 00phoenixcontact.com
RELAY
S
VERIS INDUSTRIES
800.354.8556 +1 503.598.4564 www.veris.com
Enclosed Victory Relays: 20A SPDT
FEATURES ● Sleek field enclosure reduces the need for panel space● The nipple mount feature allows the V120/220 Series to be mounted to any
electrical enclosure● HP Ratings make the V120/V220 ideal for control of fractional HP motors● Flexible tinned stranded wire...fits easily in tight spaces and provides secure
connections to wire nuts● UL508 Listed...designed and listed for field installation...makes electrical
inspection a snap
DESCRIPTIONThe Victory 120 and 220 20A SPDT enclosed relays combine a power duty relay with a high level of field-selectability and versatility. The device is quick and easy to install using the threaded nipple mount. With no need for a dedicated field enclosure, this series is ideal for retrofit projects.
APPLICATIONS● Command contactors● Control motors● Isolation● Device interlocking● Relay logic● Sense voltages for alarm conditions
SPECIFICATIONSOperating Temperature -34° to 55°C (-29° to 131°F)Operating Humidity 10-90% RH non-condensingExpected Relay Life Electrical (@ rated current) 100,000 cycles; Mechanical (unpowered) 10,000,000 cyclesRelay Status LED ON=energizedWire Specifications: Lead Length 14” (356 mm) min. Gauge UL1015; Coil: 18 AWG; Contacts: 12 AWGInsulation Class 600VAC RMSUL 508 enclosed device listing
Year Warranty5
Great For External Mount Applications V120 V220
Voltage Coil Current AC DC24V.......................................... 75mA 32mA120V........................................ 42mA -208V........................................ 36mA -277V........................................ 49mA -
TYPICAL COIL PERFORMANCE
CONTACT RATINGSResistive.............. 20A@277VAC, 28VDCMotor.................... 120VAC, 1HP 277VAC, 2HPPilot Duty............. A300Ballast.................. 277VAC, 20A N.O. 277VAC, 10A N.C.Tungsten............... 120VAC, 10A N.O. 120VAC, 2A N.C.
VICTORY 120 & 220
HQ0001840.A 01121
REL
AYS
800.354.8556 +1 503.598.4564 www.veris.com
DIMENSIONAL DRAWING
MODEL RELAY COIL AMPERAGE RATING RELAY POWER LED ULV120
SPDT24VAC/DC, 120VAC
20An n
V220 24VAC/DC, 208-277VAC n n
Some devices are plenum rated per UL 1995...see White Paper VWP01 at veris.com for details
Nipple mount to 4x electrical box
APPLICATION/WIRING EXAMPLES
Nipple mount directly to a panel
To ControlsPOWERSOURCE
FractionalHP Motor
To Load
To Controls
CONTACTS
COIL
WIRE COLOR CODES
1.6"(41 mm)
1.7"(43 mm)
1/2" NPT Nipple
1.8"(46 mm)
2.9"(74 mm)
2.8"(71 mm)
ORDERING INFORMATION
N.C.
Common
24VAC/DC
120VAC
HIwht/black
LOWwht/blue
COMMwht/yellow
Common
N.O.
CONTACT OUTPUTCONTROL SYSTEM INPUT
White
YELLOW
White
White
ORANGE
black
black
blue
blue
yellow
yellow
*Isolation…600VAC
*
208-277VAC
HIwht/brown White
brownbrown
or
HQ0001840.A 01121
RELAY
S
VERIS INDUSTRIES
800.354.8556 +1 503.598.4564 www.veris.com
DESCRIPTIONThe Veris VTD Series are multi-function time delay relays equipped with an external control switch input and designed for easy socket/DIN mounting. The VTD2P-F50 includes five functions shown at left, while the VTD1P-UNI and VTD2P-UNI include the same five as the VTD2P-F50 plus five more, for the most versatile relay available. Save inventory costs by purchasing one relay for all the functions you need.
FEATURES ● VTD2P-F50 has thumb wheel adjustment for function and timing...ensures
accuracy and eliminates mechanical deviation● VTD1P/2P-UNI models are made with solid state relays for greater reliability● Two different housings provide multiple mounting options
Multi-Function Time Delay Relays For A Variety Of Applications
Time Delay Relays
SPECIFICATIONSOperating Range 85% to 110% of nominal voltage Drop-Out Voltage Threshold 15% of nominal voltage Expected Relay Life Electrical (resistive @ rated current) 100,000 cycles; Mechanical (unpowered) 10,000,000 cyclesDielectric Strength 1000VAC RMSOperating Temperature -20°C to 55°C (-4 to 131°F)
Year Warranty5
Function Timing Chart
RE-TRIGGERABLE ONE SHOT
PULSEGENERATOR
ON/OFF DELAY(S Make/Break)
REPEAT CYCLE (Starting On)
MEMORY LATCH(S Make)
S
R
U
T T T
R
U
TPulse
T Pulse
R
UT T
T TT
S
R
U
SR
U
TT
TT
TT
U: Applied input voltage S: Control switch (open or closed) R: Relay contacts (on or off) T: Time delay
VTD2P-F50
VTD1P-UNI, VTD2P-UNI
Function Timing Chart
ON DELAY(Power On)
OFF DELAY (S Break)
REPEAT CYCLE(Starting Off)
INTERVAL (Power On)
ONE SHOT
R
UT T
S
R
U
T T
R
U
TT T
T TT
R
UT T T
SR
U
T T
TT
T
VTD2P-F50
VBD3P-C
VTD2P-UNI
Power Consumption AC ...................................................... 2.5VADC...................................................... 2W
TYPICAL COIL PERFORMANCE
(VTD2P-F50)Resistive ...........12A@240VAC, 30VDCPilot Duty..........B300 (VTD1P-UNI, VTD2P-UNI)Resistive ...........15A@240VAC, 24VDCMotor ...............1/2HP@120VAC; 1HP@240VACPilot Duty ......... B300
CONTACT RATINGS
VTD2P-F50 VTD1P-UNI, VTD2P-UNI
TIMING CHARACTERISTICS
Funtions Available 5 10Time Ranges 0.1 sec 0-999 1-10 sec 0-999 1-10 0.1 min 0-999 1-10 min 0-999 1-10 0.1 hr 0-999 1-10 hr 0-999 1-10 10 hr 0-999 --- 0.1 day --- 1-10 day --- 1-10Tolerance 0% 5% (mechanical setting)Repeatability 0.1% 0.2%Operate Time (max) 25ms no specReset Time (max) 150ms 150msTrigger Pulse Length (min) --- 50ms
VTD SERIES
HQ0001858.A 01121
REL
AYS
800.354.8556 +1 503.598.4564 www.veris.com
DIMENSIONAL DRAWINGS
RED LEDOUTPUT INDICATOR
Positive position thumb wheel adjustments A S 0 0 0
1.9"(48 mm)
1.8"(45 mm)
3.5"(89 mm)
1.8"(45 mm)
1.9"(48 mm)
PANEL CUTOUT FOR PANEL MOUNTING
5 6 789
1110
12
34
INPUT
EXTERNAL CONTROL SWITCH
2.1"(53 mm)
2.3"(58 mm)
1.0"(25 mm)
0.7”(18mm)
3.5”(90mm)
1.4”(36mm)
2.6” MAX(65mm)
MODEL RELAY STYLE No. of FUNCTIONS AMPERAGE RANGE COIL VOLTAGE MIN. SWITCHING CURRENT UL CEVTD2P-F50 DPDT 5 12 24-240VAC/DC
100mA@5VDCRecognized* n
VTD1P-UNI SPDT 10 15 24-240VAC/DC Listed nVTD2P-UNI DPDT 10 15 24-240VAC/DC Listed n
R
1615 18
U
R
2825 26
+n
-
SA1 A2
R
1615 18
U+
n-
SA1 A2
INPUTVOLTAGE
EXTERNALCONTROLSWITCH
15 - COMMON16 - NORMALLY CLOSED18 - NORMALLY OPEN
26 - NORMALLY CLOSED28 - NORMALLY OPEN
25 - COMMON
INPUTVOLTAGE
R
1615 18
R
2825 26
SA1 A2
R
1615 18
SA1 A2
CONTROLSWITCH
15 - COMMON16 - NORMALLY CLOSED18 - NORMALLY OPEN
26 - NORMALLY CLOSED28 - NORMALLY OPEN
25 - COMMON
MODEL AMPERAGE RATING VOLTAGE RATING UL CE
VBD3P-C 15A 300 n n
VTD2P-F50
VTD1P-UNI/VTD2P-UNI
VBD3P-C
VTD2P-F50
*Listed when used with Veris socket
APPLICATION/WIRING EXAMPLESVTD2P-UNIVTD1P-UNI
When relays and sockets are used together, the overall amperage rating is the lesser of the two ratings.
RELAY ORDERING INFORMATION
SOCKET ORDERING INFORMATION
E198454RoHSCompliant
HQ0001858.A 01121
Air Systems Inc. 940 Remillard Court
San Jose, California 95122
Phone: 408-280-1666
ax: 408-280-1020 www.airsystemsinc.com
Section II
Control Drawings
San Jose Office: 940 Remillard Ct., San Jose, California 95122 Phone: 408-280-1666 Fax: 408-280-1020 Website: www.airsystemsinc.com
000
DRAWING NAME:Cover
PROJECT:CCCCD PROJECT ADD ALT. 4A KIN BLDG. 11
321 Golf Club RoadPleasant Hill, CA 94523 CONTRACT NO: 18248-59
REV DESCRIPTION DATE BYFILENAME: -
DE: MW
Cover
SE:PY940 Remillard Ct
San Jose, CA 95122
A B C D E F G H
1
2
3
4
5
1
2
3
4
5
PR: TT
CCCCD PROJECT ADD ALT. 4A KIN BLDG. 11
321 Golf Club RoadPleasant Hill, CA 94523
As Prepared By:
940 Remillard Ct
Air Systems Inc.
T: 408-280-1666
ASI Design Engineer:
Project Number:Drawing Designation:
ASI Project Manager:
Drawing Date:
F: 408-280-1020San Jose, CA 95122
Mark Warren
18248-59Re-Submittal
Jason Whittington
4/1/2019
MW2/13/2019 MW4/1/2019Re-Submittal
ADD ALT. 4A Submittal01
DRAWING NO.: COVER
000
DRAWING NAME:Symbol Legend
PROJECT:CCCCD PROJECT ADD ALT. 4A KIN BLDG. 11
321 Golf Club RoadPleasant Hill, CA 94523 CONTRACT NO: 18248-59
REV DESCRIPTION DATE BYFILENAME: -
DE: MW
Symbol Legend
SE:PY940 Remillard Ct
San Jose, CA 95122
A B C D E F G H
1
2
3
4
5
1
2
3
4
5
PR: TT
DRAWING NO.: SYM.1
TAG DESCRIPTIONS
AA Remote Annunciator Module & Auto Dialer P Pressure ProbeALC Automated Logic Controller PDS Pressure Differential SwitchASA Smoke Detector PDT Pressure Differential TransmitterCR Control Relay PS Pressure Switch
ENC Enclosure PT Pressure TransmitterES Direct Current Power Supply QT Gas Transmitter
FCV Flow Control Valve / Damper Actuator ST Speed TransmitterFE Flow Element SUB Subpanel FS Flow Switch TE Temperature ElementFT Flow Transmitter TS Temperature SwitchG Generic Device TSH Temperature Switch HighIP Electro-Pneumatic Transducer TSL Temperature Switch LowIS Current Switch TT Temperature Transmitter
ISE Circuit Breaker TY Dew Pt./Enthaply/Wet Bulb TransducerIT Current Transducer V ValveJT BTU Meter VT Vibration Transmitter / SwitchJY Power Meter X UnclassifiedKS Electronic Timeclock XF TransformerLS Level Switch YKS Position TransmitterLT Level Transmitter YL Position TransmitterMS Humidistat YS Leak DetectorMT Humidity Transmitter YSE Emergency Stop
MTE Humidity Transmitter w/ Temperature Element YY TransducerMTT Humidity Transmitter w/ Temperature Transmitter ZS Position Indicating Switch
N Accessories ZT Position TransmitterNY Network Device
TE-# Field Mounted Instrument
LEGEND
Pneumatic Tubing
Line Voltage Wire
Miscellaneous Notations
FLP = Fails At Last PositionFC = Fails ClosedFO = Fails Open
L High Voltage Terminal
T1 Low Voltage Terminal
Wire Color
Shield Pigtail
Cable Masterto Controller
Cable Number and Location of Other End
Shield
Cable Slave to Field Device
Low Voltage ConnectionX1
Modbus
120 Ohm End of Line Resistor, 1/4 Watt, +/- 1%
BACNet MS/TP
Plug-In EOL Terminator & Bias Amplifier for ARC156 Network
Ethernet (Cat 6 RJ45 Cable)
ARC156
Fiber Optic Cable
120 Ώ
BT485
LEGEND
WH
T
BLK
(1.0,B1)C-2
WHT
BLK
(1.0,C1)C-2
MW2/13/2019 MW4/1/2019Re-Submittal
ADD ALT. 4A Submittal01
000
DRAWING NAME:Wire Specification
PROJECT:CCCCD PROJECT ADD ALT. 4A KIN BLDG. 11
321 Golf Club RoadPleasant Hill, CA 94523 CONTRACT NO: 18248-59
REV DESCRIPTION DATE BYFILENAME: -
DE: MW
Wire Specification
SE:PY940 Remillard Ct
San Jose, CA 95122
A B C D E F G H
1
2
3
4
5
1
2
3
4
5
PR: TT
DRAWING NO.: WIRE.1
WIRE COLOR LEGEND
GAUGE# OFCONDUCTORSTYPE REMARKSSUPPLIERPART NO. MANUFACTURERSUPPLIER
222MSTP(BACnet)Low Cap Twisted Shielded
(Purple Plenum) w221p-2227pb Lake CableConnect Air
222Generic Modbus Low Cap Twisted Shielded (Dark Blue Plenum) w181p-2040blrb Lake CableConnect Air
182Control Cable Twisted Shielded (White Plenum) w181p-2040bb/rt TappanConnect Air
222ARCnet(ALC)Low Cap Twisted Shielded
(Green Plenum) w221p-2227rib Lake CableConnect Air
222Liebert Comm Low Cap Twisted Shielded (Blue Plenum) w221p-2227blub Lake CableConnect Air
222Lighting Low Cap Twisted Shielded (Yellow Plenum) w221p-2227yb Lake CableConnect Air
222ABBnet(BACnet/Modbus)Low Cap Twisted Shielded
(Orange Plenum) w221p-2227snbt Lake CableConnect Air
182Legacy Trane(Tracer Comm Cable)Twisted Shielded (Purple Plenum) w181p-2040pbtc Lake CableConnect Air
182Daikin(Indoor Unit to Remote)Twisted Unshielded
(White Plenum) w181p-2051bb/rt TappanConnect Air
162Daikin(Indoor Unit to Remote)Twisted Unshielded
(White Plenum) w161p-2062b/rb General CableConnect Air
182Mitsubishi(Thermostats)Twisted Shielded(White Plenum) w181p-2040bb/rt TappanConnect Air
162Mitsubishi (City Multi)Twisted Shielded(White Plenum) w161p-2084rib Lake CableConnect Air
TAPPANPART NO.
M20015-15b
P40133-26b
P40133-1b
M20015-48b
M20015-26b
M20015-51b
M20015-12b
P40133-15b
P40020-1b
1680ab2/cmp
P40133-1b
1680ab2m/cmp
184Rnet Twisted Shielded (Black, White, Green, Red) w184c-2059bt Lake CableConnect Air 1880ab4/cmp
16224VAC(Power Cable)Twisted Unshielded
(White Plenum) W161p-2062b/rb General CableConnect Air 1680ab2/cmp
PRIMARY / ZONE LEVELMSTP / Subnet ARCnet
INTERMEDIATEBackbone ARCnet
SUPERVISORYEthernet 10/100
LGRME812u
LGR
30Devices
<30
Devices<
AAR 30Devices
000
DRAWING NAME:Table of Contents
PROJECT:CCCCD PROJECT ADD ALT. 4A KIN BLDG. 11
321 Golf Club RoadPleasant Hill, CA 94523 CONTRACT NO: 18248-59
REV DESCRIPTION DATE BYFILENAME: -
DE: MW
Table of Contents
SE:PY940 Remillard Ct
San Jose, CA 95122
A B C D E F G H
1
2
3
4
5
1
2
3
4
5
PR: TT
DRAWING NO.: TOC.1
DRAWING# DRAWING NAMESYM.1 Symbol LegendWIRE.1 Wire SpecificationTOC.1 Table of Contents1.1 NETWORK RISER1.2 Instrument List; TCP-LGR, Panel Layout2.1 TCP-CHW/HHW2.2 TCP-POOL2.3 POOL EQUIP GRAPHIC
MW2/13/2019 MW4/1/2019Re-Submittal
ADD ALT. 4A Submittal01
MWMWMWMW12/12/2018
12/28/20182/13/20194/1/2019
0Re-SubmittalADD ALT. 4A Submittal and UpdateUpdateSubmittal0
123
DRAWING NAME:NETWORK RISER
PROJECT:CCCCD PROJECT ADD ALT. 4A KIN BLDG. 11
321 Golf Club RoadPleasant Hill, CA 94523 CONTRACT NO: 18248-59
REV DESCRIPTION DATE BYFILENAME: #1 - D-1044 KIN RISER and LGR
DE: MW
NETWORK RISER
SE:PY940 Remillard Ct
San Jose, CA 95122
A B C D E F G H
1
2
3
4
5
1
2
3
4
5
PR: TT
DRAWING NO.: 1.1
TCP-LGR
TCP-AH-3
TCP-AH-2/-AH-5
DRAWING NO.: 1.1
1st Floor
2nd Floor
Roof
Ethernet
ARC156
Port S2 Port S1
IT Room 201
LGR250MAC: 4
IP: 10.23.4.216
CMnetBACnet
Xnet
Mech Room ___
ME812uMAC: 5
AH-5
CMnetBACnet
Xnet
Interstitial Space
ME812uMAC: 3
AH-3
CMnetBACnet
Xnet
ME812uMAC: 6
AH-2
Cable Reference
Modbus
120 Ohm End of Line Resistor, 1/4 Watt, +/- 1%
BACNet MS/TP
Plug-In EOL Terminator & Bias Amplifier for ARC156 Network
Ethernet (Cat 6 RJ45 Cable)
ARC156
Fiber Optic Cable
120 Ώ
BT485
CampusNetwork
ConnectionBy Others
Notes:1. The BMS Riser is intended only to provide
an overview of the system architecture. DDC devices are not intended to be wired in exactly the order shown. Optimal wiring runs to be determined in field.2. All devices are to be wired in a daisy chainconfiguration.
AH-1 in NEMA 4 Encl.
TCP-AH-1
AH-4 in NEMA4 Encl.
TCP-AH-4CMnetBACnet
Xnet
On AH-1
ME812uMAC: 1
AH-1
CMnetBACnet
Xnet
On AH-4
ME812uMAC: 2
AH-4
120 VACBy Others
ELEC. ROOM
TCP-CHW/HHW
Pool Equipment Room
TCP-POOL
120 VACBy Others
120 VACBy Others
BT485
CMnetBACnet
Xnet
ME812uMAC: 6
MEx48uMAC: 7
MEx48uMAC: 8
BT485
3
EXISTING; Part of D-1044 Project. BACnet changed from MS/TP to Arcnet.
NEW; Part of ADD ALT. 4A.
3
MWMWMWMW12/12/2018
12/28/20182/13/20194/1/2019
0Re-SubmittalADD ALT. 4A Submittal and UpdateUpdateSubmittal0
123
DRAWING NAME:Instrument List; TCP-LGR, Panel Layout
PROJECT:CCCCD PROJECT ADD ALT. 4A KIN BLDG. 11
321 Golf Club RoadPleasant Hill, CA 94523 CONTRACT NO: 18248-59
REV DESCRIPTION DATE BYFILENAME: #1 - D-1044 KIN RISER and LGR
DE: MW
Instrument List; TCP-LGR, Panel Layout
SE:PY940 Remillard Ct
San Jose, CA 95122
A B C D E F G H
1
2
3
4
5
1
2
3
4
5
PR: TT
DRAWING NO.: 1.2
24 VAC 120 VAC
XF-1
N LGCom24V
1122
TB-1L
N
G
TB-HV120 VAC By OthersPnl#:___Ckt#:___
G N L
TCP-LGR(Location: IT Room 201)
ENC-1
Ethernet ConnectionAs per Riser Diagram
By Others
LGR250CONTROL MODULE
MAC:4Shield
Net-
Net+
CMnet
BACnet
1
2
3
DTR
Rx
Tx
DCD
Gnd
n/c
Net-
Net+
n/c
Gnd
Port S2
232485
EIA
1
2
3
4
5
10/100 BaseTEthernet Port E1
Tx-
Rx+
Rx-
Tx+
Gnd
n/c
Net-
Net+
n/c
Gnd
Port S1
4 WIRE2 WIRE
5
4
3
2
1
DTR
Rx
Tx
DCD
Gnd
EIA232
OnOff
Power
2
1External Battery
2
1Ground
24V ac/dc
+3V
GND
Point Name Rnet, RNETRn+
Gnd
Rn-
1
2
+12V4
3
Rnet
ALC-1
Panel LayoutTCP-LGR
24"x24"x6.62" (NEMA-1)
1"1"
100VAC
1 82 3 4 5 6 7ON
485-2w
485-4w
Port S1
Ext. Batt.
Int. Batt.
DCDDTRRxTx
EIA-2324 wire
2 wire Signal
Ground
Rx-Rx+Tx-Tx+
n/cn/c
Net-Net+
External
Battery
Gnd+3V
Ground24V ac/dc
Power
On Off
ModuleStatus
3V Lithium BatteryCR-123A10/100 BaseT
Ethernet Port E1
100 LAN LINK
Cmnet transmitCmnet receive
Port S1 receivePort S1 transmit
Battery low
Blinking Dot = “Run”
Format
BACnetOver ARCNET156
KBaud LGR250Control Module
Without Keypad Display: 24Vac, 24VA, 1A, 50-60 Hz 26Vdc, 10W, 0.4A
Use Copper Conductors OnlyClass 2
®
Net +
Net -
Shield
CMnet
RnetLocal Access
GndRnet +Rnet -+12V
Rnet
Off
On
Enhanced Access
Port on S2 IP Addr
Module Address
10's 1's
BT485
Archive Valid
PowerLED
BT485
Port S2
BT485
Error Codes:
DCD
DTRRxTx
n/c
n/c
Net-Net+
EIA-485 232
EIA-232
EIA-485
EIA-232
EIA-485
Default
Assigned
0
+100
Disable
Enable
Disable
Enable
AddressMSTPon S1
PTPon S2
Tx
Rx
OptionComm
Signal Ground
Chase = OK0 = Download required1 = Control Program Error2 = RAM full3 = Comm setup error4 = System error8 = Formatting
Tag Manufacturer Part Number Product DescriptionALC-1 Automated Logic LGR250 BACnet Router, 250 Point GatewayENC-1 Hoffman A24N24ALP+A24N24MPP Hoffman Enclosure - 24in x 24in x 6.62 in, hinge, NEMA 1, w/back panel
XF-1 Functional Devices PSH100AB10 Enclosed Single Pwr Supply, 100VA
Instrument List
Wht
Blk
Arcnet Com. Bus IN/OUT Refer to Riser Diagram
EXISTING; Part of D-1044 Project
EXISTING; Part of D-1044 Project. BACnet changed from MS/TP to Arcnet.
MWMW2/13/2019
4/1/2019000
Re-SubmittalADD ALT. 4A Submittal0
1
DRAWING NAME:TCP-CHW/HHW
PROJECT:CCCCD PROJECT ADD ALT. 4A KIN BLDG. 11
321 Golf Club RoadPleasant Hill, CA 94523 CONTRACT NO: 18248-59
REV DESCRIPTION DATE BYFILENAME: #2 - ADD ALT. 4A KIN EQUIPMENT CONTROLS
DE: MW
TCP-CHW/HHW
SE:PY940 Remillard Ct
San Jose, CA 95122
A B C D E F G H
1
2
3
4
5
1
2
3
4
5
PR: TT
DRAWING NO.: 2.1
Exis
ting
208V
-3Ø
Pow
er
Exis
ting
208V
-3Ø
Pow
er
Air-Cooled Chiller
CHWPUMP
CHWS
CHWR
T T
10k-III
HHWS
HHWR
T T
10k-III
HHW BoilerHP-1
1
2
3
Drawing Notes:
Locate NEW Relays in Panel or Field, as necessary.
3
Field verify all EXISTING end devices and sensors. Reuse all existing wiring.
2
Remove EXISTING Andover Controllers PE_1 and PE_2 from Enclosure and replace with NEW ALC SE563a Controller.
1
CR-4
S+A1
15C
24-240Vac/dc
-A2
16NC
18NO
2 2
2
2
3
3
XF-1
Comm
on
24 V
AC
YelYel/Wht
Wht Blk
Neutr
al
120 V
AC
EXISTING 120 VAC
Wht
/Yel
24V 120VCOM
C NONC
CR-1
Wht
/Blk
Wht
/Blu
Blu Yel
Org
RIB
Wht
/Yel
24V 120VCOM
C NONC
CR-2
Wht
/Blk
Wht
/Blu
Blu Yel
Org
RIB
Located in CHILLER ENCLOSURE
Located in BOILER ROOM
Located in BOILER ROOM
T2T1
WHT
BLK (2.1,H2)C-8
WHT
BLK (2.1,E2)C-7
WHT
BLK (2.1,F2)C-6
WHT
BLK (2.1,B2)C-5
WHTBLK
(2.1,C2) C-1
WHTBLK
(2.1,E2) C-2
WHTBLK
(2.1,C1) C-3
WHTBLK
(2.1,E1) C-4
MAC:A
MEx48uCONTROL MODULE
Xnet -Xnet +
Gnd
123
Xnet
Aux Power Out(200 mA max)+ 24VDC
+ 24VDC12
OnOff
Power
Gnd24V ac/dc1
2
UO-1CHW PUMP START/STOP, Relay2
1Gnd
+
UO-2EF-1 START/STOP, Relay4
3Gnd
+
UO-3HHW PUMP START/STOP, Relay6
5Gnd
+
UO-4EXT. LIGHTING (PULSE), Relay8
7Gnd
+
IN-1 CHW PUMP STATUS, Th/DC/RTD12+
Gnd
IN-2 HHW PUMP STATUS, Th/DC/RTD34+
Gnd
IN-3 CHWS TEMP, Th/DC/RTD56+
Gnd
IN-4 HHWS TEMP, Th/DC/RTD78+
Gnd
IN-5 Spare, Th/DC/RTD12+
Gnd
IN-6 Spare, Th/DC/RTD34+
Gnd
IN-7 Spare, Th/DC/RTD56+
Gnd
IN-8 Spare, Th/DC/RTD78+
Gnd
ALC-1
mA Volts
Universal Output Mode Select
RelaySet Pot Full CW
mA Th/DC/RTD
Volts
Universal Input Mode Select
Wht
Blk
WHT
BLK(2.1,C5)
EXT. LIGHTING (PULSE)
C-8
WHTBLK
(2.1,C5)
HHW PUMP START/STOP
C-7W
HTBLK
(2.1,C5)
CHW PUMP START/STOP
C-5W
HT BLK
(2.1
,B3)
CHW
PUM
P ST
ATUS
C-1
WHT BLK
(2.1
,B4)
HHW
PUM
P ST
ATUS
C-2
WHTBLK
(2.1,B4)
CHWS TEMP
C-3
WHTBLK
(2.1,B4)
HHWS TEMP
C-4
24VAC Wired To All Points
Shown
T2T1
TCP-CHW/HHW Wiring Diagram(Location: ELEC. ROOM)
Xnet IN From TCP-POOL in
Pool Equip. Rm.
Tag Manufacturer Part Number Product DescriptionALC-1 Automated Logic MEX48U Point Expander, 4UO, 8UI
CR-1, -2, -3 Veris V120 Enclosed Relay, SPDT, 24VAC/DC or 120VAC Coil, 20A
CR-4 Veris VTD1P-UNI Time Delay Relay & Base, SPDT, 10 Functions, 24-240VAC/DC Coil, 15A
XF-1 Functional Devices TR100VA001 Xfmr 96VA,120:24,Ckt Brkr, Class 2
Instrument List
Exis
ting
208V
-3Ø
Pow
er
Exhaust AirEF-1Exhaust Air
2
3
Wht
/Yel
24V 120VCOM
C NONC
CR-3
Wht
/Blk
Wht
/Blu
Blu Yel
Org
RIB
Located in MECHANICAL ROOM
WHTBLK
(2.1,C5)
EF-1 START/STOP
C-6
EXISTING ANDOVER “Controllers PE_1 and PE_2” FOR REFERENCE.
1
1 Point moved to TCP-AH-2/AH-5 in Mech Room 207
Point moved to TCP-AH-2/AH-5 in Mech Room 207
MWMW2/13/2019
4/1/2019000
Re-SubmittalADD ALT. 4A Submittal0
1
DRAWING NAME:TCP-POOL
PROJECT:CCCCD PROJECT ADD ALT. 4A KIN BLDG. 11
321 Golf Club RoadPleasant Hill, CA 94523 CONTRACT NO: 18248-59
REV DESCRIPTION DATE BYFILENAME: #2 - ADD ALT. 4A KIN EQUIPMENT CONTROLS
DE: MW
TCP-POOL
SE:PY940 Remillard Ct
San Jose, CA 95122
A B C D E F G H
1
2
3
4
5
1
2
3
4
5
PR: TT
DRAWING NO.: 2.2
TCP-POOL Wiring Diagram(Location: Pool Equipment Room)
Arcnet Com. Bus
INAs per Riser
Diagram
WHTBLK
(2.3,E2) C-9
WHTBLK
(2.3,G5) C-10
WHTBLK
(2.3,C3) C-11
WHTBLK
(2.3,D3) C-12
WHTBLK
(2.3,E2) C-1
WHTBLK
(2.3,F3) C-2
WHTBLK
(2.3,F3) C-3
WHTBLK
(2.3,G3) C-4
WHTBLK
(2.3,G4) C-5
WHTBLK
(2.3,D2) C-6
WHTBLK
(2.3,D4) C-7
WHTBLK
(2.3,E2) C-8
WHTBLK (2.3,E2)C-17
WHT
BLK (2.3,E2)C-16
WHTBLK (2.3,F4)C-15
WHTBLK (2.3,E4)C-14
WHT
BLK (2.3,D2)C-13B
A
T2T1
ME812uCONTROL MODULE
MAC:A
BACnetShieldNet-Net+1
23
OnOff
Power
Gnd24V ac/dc1
2
ExternalBattery +3V
Gnd
1
2
UO-1BYPASS VALVE, 0-10V2
1Gnd
+
Xnet -Xnet +
Gnd
123
Xnet
UO-2BOILER 1 ENA/DIS, Relay4
3Gnd
+
UO-3BOILER 2 ENA/DIS, Relay6
5Gnd
+
UO-4SUPPLY PUMP VFD SPEED, 0-10V8
7Gnd
+
UO-5SUPPLY PUMP VFD S/S, Relay2
1Gnd
+
UO-6Spare, 0-10V4
3Gnd
+
UO-7Spare, 0-10V6
5Gnd
+
UO-8Spare, 0-10V8
7Gnd
+
IN-1 SUPPLY PUMP VFD AMPS, mA12+
Gnd
IN-2 CHEMTROL ORP (mV), mA34+
Gnd
IN-3 CHEMTROL pH, mA56+
Gnd
IN-4 CHEMTROL SANITIZER (ppm), mA78+
Gnd
IN-5 CHEMTROL TDS (ppm), mA12+
Gnd
IN-6 DISCHARGE PUMP PRESSURE, mA34+
Gnd
IN-7 ENABLE BUTTON, Th/DC/RTD56+
Gnd
IN-8 SUPPLY PUMP VFD FAULT, Th/DC/RTD78+
Gnd
IN-9 GPM, mA12+
Gnd
IN-10BOILER FLUE FAN STATUS, Th/DC/RTD34+
Gnd
IN-11SUCTION PUMP AMPS, mA56+
Gnd
IN-12TANK LEVEL, mA78+
Gnd
Equipment Touch, RNETRn+Gnd
Rn-
12
+12V43
Rnet
ALC-1
Aux Power Out(200 mA max)+ 24VDC
+ 24VDC
2
1
mA Volts
Universal Output Mode Select
RelaySet Pot Full CW
mA Th/DC/RTD
Volts
Universal Input Mode SelectWht
Blk
Xnet OUTTo TCP-
CHW/HHW in ELEC. RM.
Wht
Blk
T4T3
WHTBLK
(2.3,F4) C-18
WHTBLK
(2.3,F4) C-19
WHTBLK
(2.3,E4) C-20
WHTBLK
(2.3,F4) C-21
WHTBLK
(2.3,C2) C-22
WHTBLK
(2.3,E2) C-23
MAC:A
MEx48uCONTROL MODULE
Xnet -Xnet +
Gnd
123
Xnet
Aux Power Out(200 mA max)+ 24VDC
+ 24VDC12
OnOff
Power
Gnd24V ac/dc1
2
UO-1Spare, 0-10V2
1Gnd
+
UO-2Spare, 0-10V4
3Gnd
+
UO-3Spare, 0-10V6
5Gnd
+
UO-4Spare, 0-10V8
7Gnd
+
IN-1 TEMP HWR B1, Th/DC/RTD12+
Gnd
IN-2 TEMP HWR B2, Th/DC/RTD34+
Gnd
IN-3 TEMP HWS B1, Th/DC/RTD56+
Gnd
IN-4 TEMP HWS B2, Th/DC/RTD78+
Gnd
IN-5 TEMP RETURN WATER, Th/DC/RTD12+
Gnd
IN-6 TEMP SUPPLY WATER, Th/DC/RTD34+
Gnd
IN-7 Spare, Th/DC/RTD56+
Gnd
IN-8 Spare, Th/DC/RTD78+
Gnd
ALC-2
mA Volts
Universal Output Mode Select
RelaySet Pot Full CW
mA Th/DC/RTD
Volts
Universal Input Mode Select
Wht
Blk
B C DA S2S1
Rnet- Gnd 24V+
Rnet+ Sensor
ALC-3
WHTBLK
RED
GRN
(2.2,G5) C-24
WHT BLK
RED
GRN
(2.2,B3)
Spare
C-24
T5T6
Mount Equipment Touch on wall at 60" A.F.F.Coordinate location with Pool Equipment Supervisor.
BT485
XF-1
Comm
on
24 V
AC
YelYel/Wht
Wht Blk
Neutr
al
120 V
AC
EXISTING 120 VAC
XF-2
Comm
on
24 V
AC
YelYel/Wht
Wht Blk
Neutr
al
120 V
AC
XF-3
Comm
on
24 V
AC
YelYel/Wht
Wht Blk
Neutr
al
120 V
AC
24VAC Wired To All Points
Shown
T2T1
24VAC Wired To All Points
Shown
T4T3
24VAC Wired To All Points
Shown
T6T5
12A1A2 11
14CR-1
12A1A2 11
14CR-2
12A1A2 11
14CR-3
Tag Manufacturer Part Number Product DescriptionALC-1 Automated Logic ME812U Control Module, 8UO, 12UI, Supports 5 expanders
ALC-2 Automated Logic MEX48U Point Expander, 4UO, 8UI
ALC-3 Automated Logic EQT1-4-ALC Touch Screen Interface, Wall/Panel Mount w /Temp & Humidity, Rnet
CR-1, -2, -3 Phoenix Contact RIF-1-RPT-LDP-24DC/1X21 SPDT Relay & Base, 24VDC Coil, 11A Sw itching Current
XF-1, -2 Functional Devices TR100VA001 Xfmr 96VA,120:24,Ckt Brkr, Class 2
XF-3 Functional Devices TR50VA005 Xfmr 50VA,120:24,Ckt Brkr, Class 2
Instrument List
1 2
Drawing Notes:
Locate NEW Relays in Panel or Field, as necessary.
3
Field verify all EXISTING end devices and sensors are functional. Reuse all EXISTING wiring. See Drawing No. 2.3.
2
Remove EXISTING Andover Controller from Enclosure and replace with NEW ALC ME812u / MEx48u Controller / Expander.
1
3
EXISTING ANDOVER “Controller Pool” FOR REFERENCE.
1 Points shown “clouded” are NOT currentlyconnected and/or operational.
MWMW2/13/2019
4/1/2019000
Re-SubmittalADD ALT. 4A Submittal0
1
DRAWING NAME:POOL EQUIP GRAPHIC
PROJECT:CCCCD PROJECT ADD ALT. 4A KIN BLDG. 11
321 Golf Club RoadPleasant Hill, CA 94523 CONTRACT NO: 18248-59
REV DESCRIPTION DATE BYFILENAME: #2 - ADD ALT. 4A KIN EQUIPMENT CONTROLS
DE: MW
POOL EQUIP GRAPHIC
SE:PY940 Remillard Ct
San Jose, CA 95122
A B C D E F G H
1
2
3
4
5
1
2
3
4
5
PR: TT
DRAWING NO.: 2.3
EXISTING GRAPHIC FOR REFERENCE ONLY; NOT AN ACCURATE REPRESENTATION OF THE SYSTEM.
WHT
BLK (2.2,B4)
GPM
C-9
WHT
BLK
(2.2,B4)
BOILER FLUE FAN STATUS
C-10
WHT
BLK
(2.2,B5)
SUCTION PUMP AMPS
C-11
WHT
BLK(2.2,B5)
TANK LEVEL
C-12
WHT
BLK
(2.2,B4)
SUPPLY PUMP VFD AMPS
C-1
WHT
BLK
(2.2,B4)
CHEMTROL ORP (mV)
C-2
WHT
BLK
(2.2,B4)
CHEMTROL pH
C-3
WHT
BLK
(2.2,B4)
CHEMTROL SANITIZER (ppm)
C-4
WHT
BLK
(2.2,B4)
CHEMTROL TDS (ppm)
C-5
WHT
BLK
(2.2,B4)
DISCHARGE PUMP PRESSURE
C-6
WHT
BLK
(2.2,B4)
ENABLE BUTTON
C-7
WHT
BLK
(2.2,B4)
SUPPLY PUMP VFD FAULT
C-8
WHT
BLK
(2.2,D4)
SUPPLY PUMP VFD S/S
C-17
WHT
BLK
(2.2,D5)
SUPPLY PUMP VFD SPEED
C-16
WHTBLK (2.2,D5)
BOILER 2 ENA/DIS
C-15WHTBLK(2.2,D5)
BOILER 1 ENA/DIS
C-14
WHTBLK
(2.2
,D5)
BYPA
SS V
ALVE
C-13
WHT BLK
(2.2
,D3)
TEM
P HW
R B1
C-18
WHT BLK
(2.2
,D3)
TEM
P HW
R B2
C-19
WHT BLK
(2.2
,D3)
TEM
P HW
S B1
C-20
WHT BLK
(2.2
,D4)
TEM
P HW
S B2
C-21
WHT
BLK(2.2,D4)
TEMP RETURN WATER
C-22WHT
BLK (2.2,D4)
TEMP SUPPLY WATER
C-23
1 Points shown “clouded” are NOT currentlyconnected and/or operational.
Air Systems Inc. 940 Remillard Court
San Jose, California 95122
Phone: 408-280-1666
ax: 408-280-1020 www.airsystemsinc.com
Section III
Sequences of Operation
San Jose Office: 940 Remillard Ct., San Jose, California 95122 Phone: 408-280-1666 Fax: 408-280-1020 Website: www.airsystemsinc.com
CCCCD-DVC KINESIOLOGY BLDG. 11 ADD ALT. 4A
Page 1 of 3 ASI Job 18248-59 Rev. April 1, 2019
SEQUENCES OF OPERATION SINGLE AIR COOLED CHILLER Chiller - Run Conditions: The Chiller will run according to the following user-selectable modes:
- Off: The equipment will not run and all outputs will remain in their off position. - Manual Start/Stop: The equipment will run whenever the (software point) "Manual" Start/Stop is enabled. - (Global) Outside Air Temperature: The equipment will run whenever the (global) outside air temperature is greater than its user definable setpoint (adj.) of 54degF. - Schedule: The equipment will run whenever scheduled. - Cooling Requests & (Global) Outside Air Temperature: The equipment will run whenever; A definable number of chilled water coils need cooling; AND the (global) outside air temperature is greater than its user definable setpoint (adj.) of 54degF. - (Global) Outside Air Temperature and Schedule or Manual Start/Stop: The equipment will run whenever the (global) outside temperature is above its user definable setpoint (adj.) of 54degF and whenever it is scheduled. Both conditions must be true for the unit to run. The equipment will also run if the "Manual" Start/Stop is enabled.
Chilled Water Pump: The Chilled Water Pump will run anytime the Chiller is called to run.
The Chilled Water Pump will start prior to the Chiller being enabled via its flow switch. The Chilled Water Pump will have:
• A user adjustable minimum ON time.
• A user adjustable minimum OFF time.
Alarms will be provided as follows:
• Chilled Water Pump Failure: Commanded on, but the status is off.
• Chilled Water Pump Running in Hand: Commanded off, but the status is on.
• Chilled Water Pump Runtime Exceeded: Status runtime exceeds a user definable limit.
The Chiller will run subject to its own internal safeties and controls.
Chiller Chilled Water Supply Setpoint: The Chiller will maintain a Chilled Water Supply temperature setpoint as determined by its own internal controls.
Chilled Water Temperature Monitoring: The following temperatures will be monitored:
CCCCD-DVC KINESIOLOGY BLDG. 11 ADD ALT. 4A
Page 2 of 3 ASI Job 18248-59 Rev. April 1, 2019
• Chilled Water Supply.
Alarms will be provided as follows:
• High Chilled Water Supply Temp: If the Chilled Water Supply temperature is greater than 55°F (adj.).
• Low Chilled Water Supply Temp: If the Chilled Water Supply temperature is less than 38°F (adj.).
SINGLE HEATING HOT WATER BOILER SYSTEM Boiler System Run Conditions: The Boiler System will run according the following user-selectable modes:
- Off: The equipment will not run and all outputs will remain in their off position. - Manual Start/Stop: The equipment will run whenever the (software point) "Manual" Start/Stop is enabled. - (Global) Outside Air Temperature: The equipment will run whenever the (global) outside air temperature is less than its user definable setpoint (adj.) of 65degF. - Schedule: The equipment will run whenever scheduled. - Heating Requests & (Global) Outside Air Temperature: The equipment will run whenever; A definable number of heating hot water coils need heating; AND the (global) outside air temperature is less than its user definable setpoint (adj.) of 65degF. - (Global) Outside Air Temperature and Schedule or Manual Start/Stop: The equipment will run whenever the (global) outside temperature is below its user definable setpoint (adj.) of 65degF and whenever it is scheduled. Both conditions must be true for the unit to run. The equipment will also run if the "Manual" Start/Stop is enabled.
Heating Hot Water Pump: The Heating Hot Water Pump will run anytime the Boiler is called to run. The Heating Hot Water Pump will have:
• A user adjustable minimum ON time.
• A user adjustable minimum OFF time.
Alarms will be provided as follows:
• Heating Hot Water Pump Failure: Commanded on, but the status is off.
• Heating Hot Water Pump Running in Hand: Commanded off, but the status is on.
• Heating Hot Water Pump Runtime Exceeded: Status runtime exceeds a user definable limit.
CCCCD-DVC KINESIOLOGY BLDG. 11 ADD ALT. 4A
Page 3 of 3 ASI Job 18248-59 Rev. April 1, 2019
The Boiler will run subject to its own internal safeties and controls.
Heating Hot Water Supply Temperature Setpoint: The Boiler will maintain a Heating Hot Water Supply temperature setpoint as determined by its own internal controls.
Heating Hot Water Temperature Monitoring: The following temperatures will be monitored:
• Heating Hot Water Supply.
Alarms will be provided as follows:
• High Heating Hot Water Supply Temp: If greater than 200°F (adj.).
• Low Heating Hot Water Hot Water Supply Temp: If less than 100°F (adj.).
EXHAUST FAN EF-1 - ON/OFF Run Conditions - Scheduled: The Fan will run according to a user definable schedule.
Fan: The Fan will have a user definable (adj.) minimum runtime.
EXTERIOR LIGHTING Run Conditions: The (pulsed) lighting output will turn on and off based upon the local sunrise and sunset times and/or a user definable schedule.
POOL EQUIPMENT All existing hardware points and the existing Sequence of Operation will be “replicated” and documented as part of the O&M Manual and As-Built Drawings. However, a detailed field survey was conducted subsequent to our original Submittal and revealed significant issues related to the current state of the Pool System Equipment and Pool Controller. Sixteen (16) of the twenty-three (23) existing automation points are NOT currently connected and/or operational, including ALL (5) of the OUTPUT points. Therefore, automatic control of any kind is not currently possible.