Wiring systems Lighting Control ModulesThe marshalling box is designed for ease of installation and...

3
+44 (0) 1273 431600 +44 (0) 1273 439288 [email protected] 41 www.metway.co.uk Wiring systems Lighting Control Modules METWAY MARSHALLING BOX The marshalling box is designed for ease of installation and provides a simple cost effective solution as either a standalone product or part of a pre- fabricated wiring system. Features 8, 12 output 10A max load Industry standard 6-pole GST connectors 2 channel Dual fix Suitable for all dimming options (0v -10v, DSI & DALI) Emergency test Through wiring Dual channel dimming option Part numbers 8x output – MMB6-8 12x output – MMB6-12 PIR’s on/off MW1200PF/MB DSI – MW2000DF/MB DALI – MW2000DALIF/MB For all lead options – mains, emergency, dimming, see page 27. For all pluggable presence detector options/specifications, see pages 32 & 33.

Transcript of Wiring systems Lighting Control ModulesThe marshalling box is designed for ease of installation and...

  • +44 (0) 1273 431600 +44 (0) 1273 439288 [email protected] 41www.metway.co.uk

    Wiring systems

    Lighting Control Modules

    METWAY MARSHALLING BOX

    The marshalling box is designed for ease of installation and provides asimple cost effective solution as either a standalone product or part of a pre-fabricated wiring system.

    Features

    8, 12 output10A max loadIndustry standard 6-pole GST connectors2 channel Dual fix Suitable for all dimming options (0v -10v, DSI & DALI) Emergency test Through wiringDual channel dimming option

    Part numbers

    8x output – MMB6-8 12x output – MMB6-12

    PIR’son/off MW1200PF/MBDSI – MW2000DF/MBDALI – MW2000DALIF/MB

    For all lead options – mains, emergency, dimming, see page 27.For all pluggable presence detector options/specifications, see pages 32 & 33.

  • +44 (0) 1273 431600 +44 (0) 1273 439288 [email protected] www.metway.co.uk

    Wiring systems

    Lighting Control Modules

    METWAY MARSHALLING BOX

    INSTALLATION INSTRUCTIONS

    230

    190

    170 130

    M6/No.12 4 Positions

    Fixing Size Maximum

    68

    85

    20

    Input Mains Wiring

    Mechanical Fixing

    20

    42,5

    85

    D1

    D2

    L3

    NE

    L2

    L1

    Knock Out 20mm

    3 Positions

    L3 EN L1L2

    Switched Live

    Un-switched Live

    Earth

    Neutral

    *Factory Fitted LinkAll Outputs controlledby one switch

    Un-switched Live

    N EL3

    Neutral

    Earth

    L1L2

    Switched Live 1 Controls Outputs 1 to 6*Factory Fitted Link Removed

    Switched Live 2*

    Switched Live 1*

    Switched Live 2 Controls Outputs 7 to 12

    Link*

    Option 2Option 1

    Note: If Presence Detectors are fitted to Any Output Connector

    Switched Live Connections Must Not be made.

    D1 D2D1 D2

    Note: If presence detectors are fitted to any output connector

    switched live connections must not be made.

  • +44 (0) 1273 431600 +44 (0) 1273 439288 [email protected] 43www.metway.co.uk

    Wiring systems

    Lighting Control Modules

    METWAY MARSHALLING BOX

    Switched Live

    Earth

    Neutral

    Permanent Live

    Dimming 0V

    Dimming Line

    Output Connector Wiring

    NL1

    NL1

    L1L2L3 EN

    The Dimming Pair can be connected

    To a suitable Rotary Dimmer or Photocell

    Note this will control All Outputs.

    L3 EN L1L2

    17

    28

    39

    410

    511

    612

    Emergency

    Test

    Emergency Test Connector Wiring

    NL1 Factory Fitted Link

    NL1 For Emergency Test Purposes

    Remove Factory Fitted Link

    Connector Inserted - Maintained Live to All Outputs

    Connector Unplugged - No Maintained Live to All Outputs

    Wire to Keyswitch

    (Connector Supplied)

    Permanent Live

    NL1

    Presence Detector (PD) Connector Wiring

    NL1

    Neutral

    Earth

    Switched Live

    P

    Black

    Grey

    Black

    Grey

    Output Wiring

    Dimming Line

    L3 N L2E L1

    Dimming 0V

    Neutral

    Permanent Live

    Switched Live

    Earth

    PD

    Un-switched Live

    Switched LiveEarth

    Neutral

    (Controls All Outputs)

    Presence Detector with Override Switch OFF facility.

    addition of a second Presence Detector will give seperate

    * Duplication of this circuit by removal of Link and

    control of Outputs 1-6 and 7-12.

    *Link

    D1 D2

    D2D1D2D1

    The dimming pair can be connected

    to a suitable rotary dimmer or photocell.

    Note: this will control all outputs.

    Presence detector with override switch OFF facility -

    (controls all outputs).

    * Duplication of this circuit by removal of link and addition

    of a second presence detector will give separate control

    of outputs 1-6 and 7-12.

    Wiring systems Page 41Wiring systems Page 42Wiring systems Page 43