Site Survey Report - kplc.co.ke · A marshalling cubicle and a fiber optic terminal equipment to be...
Transcript of Site Survey Report - kplc.co.ke · A marshalling cubicle and a fiber optic terminal equipment to be...
Appr Project New Airport 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Resp. dept Projects Status
Doc. no. Lang. Rev. ind. Page 1 en 01 No. of p. 11
Site Survey Report
To: Projects Engineer
Station: New Airport 66/11kV
1. General: Information
Project Site survey
Site Survey Engineers Albert Kadala, Beatrice Muthoni
Survey Date 21st August 2014
Station Name & Contact New Airport 66/11 kV
Region &Town Nairobi South, Nairobi
Distance to Site(km) 13 km from Juja Control
Station Coordinates 1*20’34.9”S, 36*54’47.5”E, 5321ft
Access Road Airport South Road
Station Voltage 66/11 kV
Cable Trenches Available
Notes:
The substation is situated along Airport South Road. There is currently no communication to
Control center. There is a PLC at site but it is not in service. The station is proposed for last
mile fiber optic to be connected to Embakasi substation for onward routing to NCC using
existing communication equipment.
Appro Project New Airport 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 2 en 01 No. of p. 11
2. Drawings
3. Equipment Room
Location 11kV room
Room type and Floor Stone building, concrete floor
Ceiling type Iron Sheets
L x W x H in meters 9x6.5x4M
AC Power 240/415 VAC
DC Power 110V for protection, 48V for scada and communication
Rectifier Available
Batteries Available
Power Distribution Board Available
Grounding System Substation earthing
Security Guard at the gate, Room secured with standard padlock
Appro Project New Airport 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 3 en 01 No. of p. 11
4. RTU SIEMENS RTU available and in service. Station HMI for SAS is available but not powered.
5. Marshalling Cubicles Not Available
6. Communication Equipment Power line carrier available but out of service.
Proposed Adss fiber optic link to be installed to Embakasi sub station. New fiber optic terminal
equipment required to Embakasi for onward routing to NCC using existing equipment
7. Room layout
Communication room layout
.
Access Road Airport South road
RTU/SAS Available, Siemens RTU with station HMI available.
Marshalling Not Available
Cable Routes Available
Communication Eqpt PLC available but not powered. ADSS fiber optic proposed
Appro Project New Airport 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 4 en 01 No. of p. 11
8. AC Supply 240/415VAC available
9. DC Supply 110V protection, 48V Scada and telecomms
10. Plant Interface 10.1 Signals list
Attached
10.2 Installation and adaptation works A marshalling cubicle and a fiber optic terminal equipment to be installed at the station. Cabling
from all switch gear to the marshalling will need to be installed
11. Enclosures 9.1 Site Survey Report
9.2 Detailed plant drawings
9.3 Control Room layout
9.4 Equipment Room Layout
12. Notes distance from the site (km) 13 km from Juja Control Nearby buildings JKIA Nearby industries JKIA Type of soil Black Cotton Water availability Water available from borehole Special authority pass Permit to work Type of area Commercial Power supply 240VAC Pass issued by: Nairobi area control
Appro Project New Airport 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 5 en 01 No. of p. 11
13. Photographic Report Siemens RTU installed at New airport Power line Carrier. Out of service Station HMI not powered Battery and charger room AC distribution board
Signal list
Airport 66/11kV Signal list
OBJECT TYPE SIGNAL Indications Alarms Commands Measurands
Energy Meter Inputs
66kV LINE 1 DPI 1L1 E/S On/Off 1
1L3 ISO On/Off 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
LINE 2 DPI 2L1 E/S On/Off 1
2L3 ISO On/Off 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Appro Project New Airport 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 6 en 01 No. of p. 11
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
LINE 3 DPI 3L1 E/S On/Off 1
3L3 ISO On/Off 1
3L5 CB On/Off 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
DCO 3L5 CB Open/Close 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
Protection Faulty 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
LINE 4 DPI 4L1 E/S On/Off 1
4L3 ISO On/Off 1
4L5 CB On/Off 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
DCO 4L5 CB Open/Close 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
Protection Faulty 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
66kV Busbar DPI ISO BC On/Off 1
TX1 BAY DPI CB 1H5 On/Off 1
ISO 1H3 On/Off 1
SPI MPT‐Main Prot. Trip 1
Appro Project New Airport 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 7 en 01 No. of p. 11
BPT‐Backup Prot. Trip 1
Protection Faulty 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
DCO CB 1H5 Open/Close 1
AMI Volts, kV 1
Active Power, P 1
Reactive Power, Q 1
Amps 1
TX2 BAY DPI CB 2H5 On/Off 1
ISO 2H3 On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
Protection Faulty 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
DCO CB 2H5 Open/Close 1
AMI Volts, kV 1
Active Power, P 1
Reactive Power, Q 1
Amps 1
TX1 DPI TC Auto/Manual 1
TC Local/Remote 1
SPI TTA‐Temp Alarm 1
TTT TEMP TRIP 1
TBA BUCH AL 1
TBT BUCH TRIP 1
TOL OIL LEVEL ALARM 1
TGA TX GENERAL AL 1
TGT TX GEN TRIP 1
TBS TX OUT OF STEP 1
DCO TC Auto/Manual 1
RCO TC Raise/Lower 1
AMI Tap Position 1
TX2 DPI TC Auto/Manual 1
TC Local/Remote 1
Appro Project New Airport 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 8 en 01 No. of p. 11
SPI TTA‐Temp Alarm 1
TTT TEMP TRIP 1
TBA BUCH AL 1
TBT BUCH TRIP 1
TOL OIL LEVEL ALARM 1
TGA TX GENERAL AL 1
TGT TX GEN TRIP 1
TBS TX OUT OF STEP 1
DCO TC Auto/Manual 1
RCO TC Raise/Lower 1
AMI Tap Position 1
11 KV
INCOMER 1 DPI CB INC1 On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
Protection Faulty 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
DCO CB INC 1 Open/Close 1
AMI Volts, kV 1
Active Power, P 1
Reactive Power, Q 1
Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
INCOMER 2 DPI CB INC2 On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
BYF‐Bay Faulty 1
Protection Faulty 1
TCF‐Trip Circuit Faulty 1
Lockout relay operated 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
DCO CB INC 2 Open/Close 1
AMI Volts, kV 1
Appro Project New Airport 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 9 en 01 No. of p. 11
Active Power, P 1
Reactive Power, Q 1
Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
11kV BUSBAR DPI ISO BC On/Off 1
DCO ISO BC Open/Close 1
SPI Busbar protection 1
Busbar supervision 1
AMI Volts, kV 1
Frequency, F 1
11kV Feeders
Industrial DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Airport 1 DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
KPC DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
Appro Project New Airport 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 10 en 01 No. of p. 11
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
IMARA DAIMA DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
AIRPORT 2 DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
OSERIAN DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
ATHI DPI CB On/Off 1
Appro Project New Airport 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 11 en 01 No. of p. 11
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Station DPI Station Remote/Supervisory 1
SPI 48 DC Battery Alarm 1
48 DC Charger Alarm 1
48V Charger A Fail Alarm 1
48V Charger B Fail Alarm 1
RTU Alarm 1
Communications Alarm 1
110V DC Battery Alarm 1
110V DC Charger Alarm 1
110V DC Charger A Fail Alarm 1
110V DC Charger B Fail Alarm 1
Smoke in Control Room 1
AMI 48V DC1 1
48V DC2 1
110V DC1 1
110V DC2 1
Total 30 101 18 43 26
Appr Project DARA 11KV SUBSTATION Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Resp. dept Projects Status
Doc. no. Lang. Rev. ind. Page 1 en 01 No. of p. 9
Site Survey Report
To: Projects Engineer
Station: Dara 11 kV
1. General: Information
Project Site survey
Site Survey Engineers Albert Kadala, Beatrice Muthoni
Survey Date 20/08/2014
Station Name & Contact Dara 11 kV S/Stn
Region &Town Nairobi South
Distance to Site(km) 12.5km from Juja NCC
Station Coordinates 1*18’6.7”S, 36*49’54.9”E, 5444ft
Access Road Lusaka Road
Station Voltage 11 kV
Cable Trenches Available
Notes:
All the switchgear has been recovered from the station. New switch gear yet to be installed.
Appro Project DARA 11KV SUBSTATION Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 2 en 01 No. of p. 9
2. Drawings
DARA Substation SLD
3. Equipment Room
Location 11kV room
Room type and Floor Stone room and concrete floor
Ceiling type Concrete slab ceiling
L x W x H in meters 10.5 x 5 x 4
AC Power 240VAC
DC Power None
Rectifier None
Batteries None
Power Distribution Board 415VAC
Grounding System Substation earth
Security Secured with standard padlock and electric fence
Access Road Lusaka road
RTU/SAS None
Appro Project DARA 11KV SUBSTATION Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 3 en 01 No. of p. 9
4. RTU
No RTU at the station
.
5. Marshalling Cubicles
No marshalling cubicles at the station
6. Communication Equipment
No communication equipment at the station
7. Room layout
.
8. AC upply
415 VAC
Marshalling None
Cable Routes available
Communication Eqpt None, proposed radio to Ngong hills repeater
Appro Project DARA 11KV SUBSTATION Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 4 en 01 No. of p. 9
9. DC Supply
No DC supply
10. Plant Interface
10.1 Signals list
Attached
10.2 Installation and adaptation works
RTU, Marshalling cubicle and communication equipment need to be installed. Full wiring
to be done from the Panels to the Marshalling cubicle and to the RTU. Radio communication
to Ngong Hills repeater is proposed. If this is adapted a tower and antenna need to be
installed complete with radio and coax and configuration to Ngong repeater
11. Enclosures
9.1 Site Survey Report
9.2 Detailed plant drawings
9.3 Control Room layout
9.4 Equipment Room Layout
9.4
12. Notes
distance from the site (km) 12.5 km from NCC Nearby buildings Car and General Nearby industries Car and General Type of soil Cabro Water availability Not available Special authority pass Substation key, limitation of access Type of area Commercial Power supply 240VAC Pass issued by: Nairobi Area control
Appro Project DARA 11KV SUBSTATION Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 5 en 01 No. of p. 9
13. Photographic Report
Equipment room photos
Cable trenches
AC distribution board
Appro Project DARA 11KV SUBSTATION Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 6 en 01 No. of p. 9
DARA SIGNAL LIST
DARA 11kV Signal list
OBJECT TYPE SIGNAL Indications Alarms Commands Measurands
Energy Meter Inputs
LINE 1 DPI INC 1 CB On/Off 1
DCO INC 1 CB Open/Close 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
LINE 2 DPI INC 2 CB On/Off 1
DCO INC 2 CB Open/Close 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
11kV Feeders
NRBW2 DPI CB On/Off 1
Appro Project DARA 11KV SUBSTATION Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 7 en 01 No. of p. 9
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
KRWS2 DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
INDU2 DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
INDU1 DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Appro Project DARA 11KV SUBSTATION Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 8 en 01 No. of p. 9
Energy, KVARHR 1
BUS COUPLER DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
EAI DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
KRWS1 DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
CATH DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
Appro Project DARA 11KV SUBSTATION Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 9 en 01 No. of p. 9
ITI Energy, KWHR 1
Energy, KVARHR 1
GNGN DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Station DPI Station Remote/Supervisory 1
SPI 48 DC Battery Alarm 1
48 DC Charger Alarm 1
48V Charger A Fail Alarm 1
48V Charger B Fail Alarm 1
RTU Alarm 1
Communications Alarm 1
110V DC Battery Alarm 1
110V DC Charger Alarm 1
110V DC Charger A Fail Alarm 1
110V DC Charger B Fail Alarm 1
Smoke in Control Room 1
AMI 48V DC1 1
48V DC2 1
110V DC1 1
110V DC2 1
Total 12 55 11 19 20
Appr Project Industrial 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Resp. dept Projects Status
Doc. no. Lang. Rev. ind. Page 1 en 01 No. of p. 12
Site Survey Report
To: Projects Engineer
Station: Industrial 66/11 kV
1. General: Information
Project Site surveys
Site Survey Engineers Albert Kadala, Beatrice Muthoni
Survey Date 19th August 2014
Station Name & Contact Industrial 66/11 kV
Region &Town Nairobi South
Distance to Site(km) 14.7 km from Juja
Station Coordinates 1*18’50”S, 36*51’3.9”E
Access Road Enterprise Road
Station Voltage 66/11 kV
Cable Trenches Available, from switchyard to new station building
Notes:
New station building is under construction and far from completion. All equipment will be
transferred to the new building once complete. Survey was carried out on the existing system
and building. Cable trenches from the switchyard to the new building are constructed.
Appro Project Industrial 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 2 en 01 No. of p. 12
2. Drawings
66kV
66kV
W57 W58
1L7
1L1
1L5
2L7
2L1
2L5
TX123MVA
TX245MVA
Local TX
Local TX
VillaFranca
NewMSA rd
N/South1
N/South2
RollMills
PFC Kencell EAO Kampalard
PFCDara 1 Dara 2
Inc 1 Inc 2
Single Line Diagram
3. Equipment Room
Location Nairobi Industrial area
Room type and Floor Stone building, concrete floor
Ceiling type Iron sheet
L x W x H in meters New building under construction
AC Power 240VAC available
DC Power 30VDC available, 48VDC available but not in service
Rectifier Available
Batteries Available
Power Distribution Board Available
Grounding System Substation earthing
Security Security guard at the gate, room secured with standard padlock
Appro Project Industrial 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 3 en 01 No. of p. 12
4. RTU
RTU560 installed in old existing building but it is not in service. The RTU will need to be
migrated to the new equipment room when station building is complete
RTU available with following cards: 13No. 23BE23, 4No. 23AE23, 2No. 560PSU01, 1No.
560CMU05, 1No. 560RTC01, 1No. 23BA22, 48No. DC48V command relays
5. Marshalling Cubicles
Available with 80No. DC36V double pole and 126No. DC36V Single point indication relays
available in the marshalling.
6. Communication Equipment
Radio communication to Ngong Hills repeater site had been installed
The radio is not available at the station but radio cabinet is available.
36 ft tower complete with antenna and coax available. The coax will not be able to reach the new
building when equipments are migrated. Excavation work will be necessary and a longer coax
required.
A new radio and a coax from the tower to the new building will need to be installed to get
communication to Ngong Hills site which is connected to Juja Control
7. Room layout
.New station building is still under construction. There will be sufficient space to mount Scada
and communication cabinets in the new room.
Access Road Enterprise road
RTU/SAS RTU 560 installed
Marshalling Available
Cable Routes Available
Communication Eqpt Radio Not available, communication tower complete with
antenna and coax available
Appro Project Industrial 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 4 en 01 No. of p. 12
8. AC Supply
240VAC available
9. DC Supply
30VDC for protection available, 48VDC for communication available but not in use
10. Plant Interface
10.1 Signals list
Attached
10.2 Installation and adaptation works
New wiring will need to be done from the RTU to the relay panels to the switchyard as equipment
are to be moved from the old room to new building. Excavation may be required for coax path if the
existing Communication tower is to be used. It is situated further from the new building
Enclosures
9.1 Site Survey Report
9.2 Detailed plant drawings
9.3 Control Room layout
9.4 Equipment Room Layout
11. Notes
distance from the site (km) 14.7 km from Juja control Nearby buildings HEMA House Nearby industries Crown industries Type of soil Black cotton Water availability In process of installation Special authority pass Permit to work Type of area Industrial area Power supply 240VAC Pass issued by: Nairobi area control
Appro Project Industrial 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 5 en 01 No. of p. 12
12. Photographic Report
RTU 560 installed but not in service
Marshalling cubicle
Radio communication cabinet with radio missing
AC distribution board
30V DC supply
48V Dc supply out of service
Appro Project Industrial 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 6 en 01 No. of p. 12
Signal list
INDUSTRIAL 66/11kV Signal list
OBJECT TYPE SIGNAL Indications Alarms Commands Measurands
Energy Meter Inputs
66kV LINE DPI W57 On/Off 1
W58 On/Off 1
AMI Volts, kV W57 1
Volts, kV W58 1
Active Power, P W57 1
Active Power, P W58 1
Reactive Power, Q W57 1
Reactive Power, Q W58 1
ITI Energy, KWHR Imp W57 1
Energy, KWHR Imp W58 1
Energy, KVARHR Imp W57 1
Energy, KVARHR ImpW58 1
66kV Busbar DPI ISO BC 1H2 On/Off 1
TX1 BAY DPI ES 1L1 On/Off 1
CB 1L5 On/Off 1
ISO 1L7 On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
Protection Faulty 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
Appro Project Industrial 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 7 en 01 No. of p. 12
DCO CB 1L5 Open/Close 1
AMI Volts, kV 1
Active Power, P 1
Reactive Power, Q 1
Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
TX2 BAY DPI ES 2L1 On/Off 1
CB 2L5 On/Off 1
ISO 2L7 On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
Protection Faulty 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
DCO CB 2L5 Open/Close 1
AMI Volts, kV 1
Active Power, P 1
Reactive Power, Q 1
Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
TX1 DPI TC Auto/Manual 1
TC Local/Remote 1
SPI TTA‐Temp Alarm 1
TTT TEMP TRIP 1
TBA BUCH AL 1
TBT BUCH TRIP 1
TOL OIL LEVEL ALARM 1
TGA TX GENERAL AL 1
TGT TX GEN TRIP 1
TBS TX OUT OF STEP 1
DCO TC Auto/Manual 1
RCO TC Raise/Lower 1
AMI Tap Position 1
TX2 DPI TC Auto/Manual 1
TC Local/Remote 1
Appro Project Industrial 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 8 en 01 No. of p. 12
SPI TTA‐Temp Alarm 1
TTT TEMP TRIP 1
TBA BUCH AL 1
TBT BUCH TRIP 1
TOL OIL LEVEL ALARM 1
TGA TX GENERAL AL 1
TGT TX GEN TRIP 1
TBS TX OUT OF STEP 1
DCO TC Auto/Manual 1
RCO TC Raise/Lower 1
AMI Tap Position 1
11 KV
INCOMER 1 DPI CB INC1 On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
Protection Faulty 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
DCO CB INC 1 Open/Close 1
AMI Volts, kV 1
Active Power, P 1
Reactive Power, Q 1
Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
INCOMER 2 DPI CB INC2 On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
BYF‐Bay Faulty 1
Protection Faulty 1
TCF‐Trip Circuit Faulty 1
Lockout relay operated 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
DCO CB INC 2 Open/Close 1
Appro Project Industrial 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 9 en 01 No. of p. 12
AMI Volts, kV 1
Active Power, P 1
Reactive Power, Q 1
Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
11kV BUSBAR DPI ISO BC On/Off 1
DCO ISO BC Open/Close 1
SPI Busbar protection 1
Busbar supervision 1
AMI Volts, kV 1
Frequency, F 1
11kV Feeders
New Msa Rd DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Villa Franca DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
PFC1 DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Appro Project Industrial 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 10 en 01 No. of p. 12
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Nairobi south 1 DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Roll Mills DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Kencell DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Nairobi south 2 DPI CB On/Off 1
Appro Project Industrial 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 11 en 01 No. of p. 12
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
East Africa Oxygen DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Kampala rd DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Dara 1 DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
Appro Project Industrial 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 12 en 01 No. of p. 12
ITI Energy, KWHR 1
Energy, KVARHR 1
Dara 2 DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
PFC 2 DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Station DPI Station Remote/Supervisory 1
SPI 48 DC Battery Alarm 1
48 DC Charger Alarm 1
48V Charger A Fail Alarm 1
48V Charger B Fail Alarm 1
RTU Alarm 1
Communications Alarm 1
110V DC Battery Alarm 1
110V DC Charger Alarm 1
110V DC Charger A Fail Alarm 1
110V DC Charger B Fail Alarm 1
Smoke in Control Room 1
AMI 48V DC1 1
48V DC2 1
110V DC1 1
110V DC2 1
Total 29 107 21 42 36
Appr Project Substation NamePrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Resp. dept Projects Status
Doc. no. Lang. Rev. ind. Page 1 en 01 No. of p. 4
Site Survey Report
To: Projects Engineer
Station: KAREN 66/11KV SUBSTATION –
1. General: Information
Project Station Voltage 66/11kV
Site Survey Engineers Metrine Jelagat Cable Trenches
Survey Date 30/07/2014
Station Name & Contact Karen Substation
Region &Town Nairobi West
Distance to Site(km)
Station Coordinates
Access Road Ngong Rd
Notes:
Give a description of Substation and attach the SLD.
Station Voltage and general status of substation. Take pictures of station. Comment on
status of cable trenches etc.
Appro Project KAREN SUBSTATION Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. metrine Rev. ind. Page 2 en 01 No. of p. 4
2. Drawings
Comment on drawing(s) and collect copies of same. If station is new get station layout
drawings.
3. Equipment Room
4. RTU
Indicate if RTU/SAS exists and check model, and spare capacity.
.
5. Marshalling Cubicles
Indicate if Marshalling cubicles are available. Access cable routes and status of
Where possible, all signals shall be brought to the marshalling cubicle. Access need for
items like transducers etc.
Location 66kV panels
Room
RTU/SAS RTU560 – IEC103
Room type and Floor Blocks/stones Marshalling
Ceiling type none Cable Routes See Drawing/Photo
L x W x H in meters Communication Eqpt Radio
AC Power 415v/240v
DC Power 48VDC,110VDC
Rectifier
Batteries 48VDC Avail
Power Distribution Board
Grounding System
Security Room secure
Access Road
Appro Project KAREN SUBSTATION Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. metrine Rev. ind. Page 3 en 01 No. of p. 4
6. Communication Equipment
Indicate if any communication equipment exist in the station and necessary capacity installed and spare.
If no Equipment exists, indicate possible equipment and media. Since this shall be accessed on viability
give all the options possible and nearest terminal communication link. Limit to Fibre, Radio and
PLC(Least preferred)
Indicate if Tele-protection is required.
Indicate if fibre required length of fibre and line voltage.
7. Room layout
Get the room layout. Indicate if space is available for proposed new equipment.
8. AC Supply
Check the AC distribution board and available spare capacity.
9. DC Supply
Indicate if 48 VDC and 110 VDC is available in the status and spare capacity.
10. Plant Interface
10.1 Signals list
Make a table based on Standard Signal list to indicate no required
10.2 Installation and adaptation works
. Indicate any challenges expected
Appro Project KAREN SUBSTATION Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. metrine Rev. ind. Page 4 en 01 No. of p. 4
11. Enclosures
9.1 Site Survey Report
9.2 Detailed plant drawings
9.3 Control Room layout
9.4 Equipment Room Layout
9.4
12. Notes
distance from the site (km)
In town Type of area Urban
Nearby buildings Apartments, Slum Nearby industries Samsung, Heineken Power supply 240VAC Type of soil Loamy soil Water availability Special authority pass
Permit of work Pass issued by:
RCC
It is important to note if there other challenges expected in works. Also if available indicate any near
future rehabilitation works are planned.
Indicate strategic position of the sub-station and its importance to the region.
13. Photographic Report
Attach Relevant Photographs
Appr Project Kikuyu 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Resp. dept Projects Status
No. of p. 12
Site Survey Report
To: Projects Engineer
Station: Kikuyu Substation 66/11kV
1. General: Information
Project Site survey
Site Survey Engineers Metrine Jelagat/Tony Angatia
Survey Date 12th September 2014
Station Name & Contact Kikuyu S/S 66/11 kV
Region &Town Nairobi North, Nairobi
Distance to Site(km) 40 km from Juja Control via Waiyaki way
Station Coordinates 1.2326830S, 36.662070E
Access Road Waiyaki Way
Station Voltage 66/11 kV
Cable Trenches Available
Notes:
The substation is situated at Kikuyu town accessed via waiyaki way.
The substation has two 66/11KV, 23MVA transformers with an indoor 11kv switchboard. The 11kV switchboard has ABB type HD4 breakers with 2 incomers, 1 Bus Section switch and 6 feeders.
The control room accommodates the 11kV switchboard, the transformer and 66kV line protection panels and tap changer control panels.
There exists a SCADA equipment in the station but it is not terminated to the process, the cables have been done from the RTU/MC and lie in the trenches
Appro Project Kikuyu 66/11 kV Substation Prep. Date 12-09- Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 12
2. Drawings
Appro Project Kikuyu 66/11 kV Substation Prep. Date 12-09- Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 12
Appro Project Kikuyu 66/11 kV Substation Prep. Date 12-09- Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 12
3. Equipment Room
Location Scada room
Room type and Floor Stone building, concrete floor
Ceiling type Iron Sheets
L x W x H in meters 2.5x1.7x4M
AC Power 240/415 VAC
DC Power 30V for protection, 110V for Tap changer panel, 48V for scada
and communication
Rectifier Available
Batteries Available
Power Distribution Board Available
Grounding System Substation earthing
Security Guard at the gate, station controller
Access Road Waiyaki way to Kikuyu township
RTU/SAS Available, RTU560 installed but terminations to switchgear not
done
Marshalling Available
Cable Routes Available
Communication Eqpt Radio Mast available at the station, a radio cabinet available
but no radio, a coax from the mast to the radio cabinet
available
Appro Project Kikuyu 66/11 kV Substation Prep. Date 12-09- Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 12
4. RTU
It is proposed to use the existing RTU in the station. Average length of cables shall be 15 meters and shall all be for bottom entry. The existing transducers are mounted in the11kv panels and 66kv tap changer control panels. These are for local metering.
5. Marshalling Cubicles
The marshalling cabinet is located in the scada room as shown in the layout drawing and is of an average cable route of 15 meters from the switchgear.
6. Communication Equipment
There is no existing Telecommunication equipment for the SCADA Network.
A communication mast however exists and a UHF Radio is proposed for this station.
This would communicate with Ngong Hills UHF Repeater station as there is no direct propagation path to Juja Rd NCC.
The new radio equipment would be installed in the communications cabinet in the control room. See room layout drawing. The distance from the new RTU is about 5 meters.
7. Room layout (not to scale)
Communication room layout
.
8. AC Supply
Appro Project Kikuyu 66/11 kV Substation Prep. Date 12-09- Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 12
A 415V AC distribution board is located about 15meteres from the proposed RTU position Spare MCB way is available in the AC distribution board.
9. DC Supply
There exists a 48v DC system. This is located in the battery room as shown in the room layout. The system is located in the battery room shown in the room layout diagram
10. Plant Interface 10.1 Signals list
Attached
10.2 Installation and adaptation works There is an RTU 560 with a marshalling cubicle mounted in the scada room. The RTU has cables terminated but left in the trenches and not terminated to the process. It is proposed that in the implementation of the scada , the available materials shall be used
11. Enclosures Site Survey Report
Photographic represenation
Control Room/ Equipment room layout
12. Notes distance from the site (km) 40 km from Juja Control Nearby buildings Kikuyu Town Nearby industries Steel Rolling Mills Type of soil Red Soil Water availability Water available from a neighboring borehole Special authority pass Permit to work Type of area Commercial Power supply 240VAC Pass issued by: Nairobi area control
Appro Project Kikuyu 66/11 kV Substation Prep. Date 12-09- Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 12
13. Photographic Report
14. RTU & MC Radio cabinet and mast
Battery and charger room
AC distribution board
Signal list
Kikuyu 66/11kV Signal list
OBJECT TYPE SIGNAL Indications Alarms Commands Measurands
Energy Meter Inputs
66kV Karen DPI ISO 1L7 0N/OFF 1
CB 1L5 0N/Off 1
ISO 1L3 0N/OFF 1
ES 1L1 ON/OFF 1
DCO CB 1L5 Open/Close 1
ISO 1L7 Open/Close 1
ISO 1L3 Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
Appro Project Kikuyu 66/11 kV Substation Prep. Date 12-09- Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 12
Limuru DPI ISO 2L7 0N/OFF 1
CB 2L5 0N/Off 1
ISO 2L3 0N/OFF 1
ES 2L1 ON/OFF 1
DCO CB 2L5 Open/Close 1
ISO 2L7 Open/Close 1
ISO 2L3 Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
TX1 BAY DPI CB 1H5 On/Off 1
ISO 1H3 On/Off 1
SPI MPT-Main Prot. Trip 1
BPT-Backup Prot. Trip 1
Protection Faulty 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
DCO CB 1H5 Open/Close 1
AMI Volts, kV 1
Active Power, P 1
Reactive Power, Q 1
Amps 1
TX2 BAY DPI CB 2H5 On/Off 1
ISO 2H3 On/Off 1
SPI MPT-Main Prot. Trip 1
BPT-Backup Prot. Trip 1
Protection Faulty 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
DCO CB 2H5 Open/Close 1
AMI Volts, kV 1
Active Power, P 1
Reactive Power, Q 1
Amps 1
Appro Project Kikuyu 66/11 kV Substation Prep. Date 12-09- Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 12
TX1 DPI TC Auto/Manual 1
TC Local/Remote 1
SPI TTA-Temp Alarm 1
TTT TEMP TRIP 1
TBA BUCH AL 1
TBT BUCH TRIP 1
TOL OIL LEVEL ALARM 1
TGA TX GENERAL AL 1
TGT TX GEN TRIP 1
TBS TX OUT OF STEP 1
DCO TC Auto/Manual 1
RCO TC Raise/Lower 1
AMI Tap Position 1
TX2 DPI TC Auto/Manual 1
TC Local/Remote 1
SPI TTA-Temp Alarm 1
TTT TEMP TRIP 1
TBA BUCH AL 1
TBT BUCH TRIP 1
TOL OIL LEVEL ALARM 1
TGA TX GENERAL AL 1
TGT TX GEN TRIP 1
TBS TX OUT OF STEP 1
DCO TC Auto/Manual 1
RCO TC Raise/Lower 1
AMI Tap Position 1
11 KV
INCOMER 1 DPI CB INC1 On/Off 1
SPI MPT-Main Prot. Trip 1
BPT-Backup Prot. Trip 1
Protection Faulty 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
DCO CB INC 1 Open/Close 1
AMI Volts, kV 1
Active Power, P 1
Reactive Power, Q 1
Amps 1
Appro Project Kikuyu 66/11 kV Substation Prep. Date 12-09- Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 12
ITI Energy, KWHR 1
Energy, KVARHR 1
INCOMER 2 DPI CB INC2 On/Off 1
SPI MPT-Main Prot. Trip 1
BPT-Backup Prot. Trip 1
BYF-Bay Faulty 1
Protection Faulty 1
TCF-Trip Circuit Faulty 1
Lockout relay operated 1
SCF-Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
DCO CB INC 2 Open/Close 1
AMI Volts, kV 1
Active Power, P 1
Reactive Power, Q 1
Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
11kV BUSBAR DPI ISO BC On/Off 1
DCO ISO BC Open/Close 1
AMI Volts, kV 1
11kV Feeders
KABETE DPI CB On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
DPI CB On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
S PARE SCF-Spring Charge Fail 1
Appro Project Kikuyu 66/11 kV Substation Prep. Date 12-09- Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 12
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
UTHIRU DPI CB On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
KIKUYU DPI CB On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
MUGUGA DPI CB On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
STEEL MILLS DPI CB On/Off 1
Appro Project Kikuyu 66/11 kV Substation Prep. Date 12-09- Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 12
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Station DPI Station Remote/Supervisory 1
SPI 48 DC Battery Alarm 1
48 DC Charger Alarm 1
RTU Alarm 1
Communications Alarm 1
30V DC Battery Alarm 1
30V DC Charger Alarm 1
110V DC Chargerl Alarm 1
110V DC Battery 1
AMI 48V DC1 1
30V DC1 1
110V DC2 1
Total 26 78 21 43 20
Appr Project Limuru 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Resp. dept Projects Status
en 01 No. of p. 6
Site Survey Report
To: Projects Engineer
Station: Limuru Substation 66/11kV
General: Information
Project Site survey
Site Survey Engineers Metrine Jelagat
Survey Date 12th September 2014
Station Name & Contact Limuru S/S 66/11 kV
Region &Town Nairobi North, Nairobi
Distance to Site(km) 60 km from Juja Control
Station Coordinates 1.1109900S, 36.6458490E , 2254.5m ASL
Access Road Waiyaki Way
Station Voltage 66/11 kV
Cable Trenches Available
Notes:
The substation has 3no 66kV lines, 1 66kV bus-section switch, two 23MVA transformer with an indoor and one 5MVA transformer. All equipment is included in the siemens scada system, except one 23 MVA transformer which is still under construction with no scada .It has an 11kv switchgear board located in an adjacent control room. The board has Siemens type breakers with 3 incomers and 9 feeders.
There is a Siemens SCADA equipment in this station.
There is a PLC at site but it is not in service. An ADSS fiber optic cable is also under
installation to link Limuru S/S to Nairobi North S/S.
A fibre terminal equipment is proposed for the communication in this station.
Appro Project Limuru 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 6
Drawings
UPLANDS MUTHAIGA LOCAL TX2LIMURU TOWN
LOCAL TX 1 BATA
TX3 TX2
1L7
1L5
1L3
1L1
NGEMA/MAAI MAHIU KIKUYU
1H3
1H0
2L7
2L5
2L3
2L1
2H3
2H0
BC
WELBCK SPARE SPARE
BC
TX1
BC
INC3 INC1 INC2
3L7
3L5
3L3
3L1
NAIROBI NORTH
5 MVA
Under construction
Appro Project Limuru 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 6
quipment Room
RTU SIEMENS RTU available and in service. Station HMI for SAS is available but not powered.
Marshalling Cubicles Not Available
Communication Equipment Power line carrier available but out of service.
An Adss fiber optic link is being installed to Nairobi North sub station. New fiber optic terminal
equipment required to Nairobi North for onward routing to NCC using existing equipment
Room layout
Location Old control room
Room type and Floor Stone building, concrete floor
Ceiling type Iron Sheets
L x W x H in meters 9x6.5x4M
AC Power 240/415 VAC
DC Power 110V for protection, 48V for scada and communication
Rectifier Available
Batteries Available
Power Distribution Board Available
Grounding System Substation earthing
Security Guard at the gate, Room secured with standard padlock
Access Road Waiyaki way
RTU/SAS Available, Siemens RTU with station HMI available.
Marshalling Not Available
Cable Routes Available
Communication Eqpt PLC available but not powered. ADSS fiber optic proposed
Appro Project Limuru 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 6
Communication room layout
.
AC Supply 24all 0/415VAC available
DC Supply 110V protection, 48V Scada and telecomms
Plant Interface 1.1 Signals list
Except for a new transformer being installed in the station, the rest of the equipment is monitored
on the siemens scada platform. Details of the transformer not available
Appro Project Limuru 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 6
1.2 Installation and adaptation works
A new transformer is under construction, and it shall be required that it is added to the existing scada system via the siemens SCMS
A fiber optic terminal equipment is proposed to be installed at the station. The siemens Scada system
shall then be connected to NCC via Nairobi North s/s
Enclosures Site Survey Report
Photographs
Control Room layout
Equipment Room Layout
Notes distance from the site (km) 55 km from Juja Control Nearby buildings Limuru Shopping centre Nearby industries Bata Shoe Company Type of soil Red Soil Water availability Water available Special authority pass Permit to work Type of area Commercial Power supply 240VAC Pass issued by: Nairobi area control
Photographic Report Siemens RTU installed at Limuru
Appro Project Limuru 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 6
Power line Carrier. Out of service Station HMI not powered Battery and charger room
Appr Project Machakos 33/11 kV Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Resp. dept Projects Status
Doc. no. Lang. Rev. ind. Page 1 en 01 No. of p. 8
Site Survey Report
To: Projects Engineer
Station: Machakos 33/11 kV
1. General: Information Project Site surveys
Site Survey Engineers Albert Kadala, Beatrice Muthoni
Survey Date 22 August 2014
Station Name & Contact Machakos 33/11 kV
Region &Town Machakos
Distance to Site(km) 35 km from Nairobi
Station Coordinates Machakos town
Access Road Makutano - kitui road
Station Voltage 33/11 kV
Cable Trenches Available
Notes:
The station is undergoing renovation; a new station building is under construction.
Appro Project Machakos 33/11 kV Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 2 en 01 No. of p. 8
2. Drawings
3. Equipment Room
Location Building under construction
Room type and Floor Concrete
Ceiling type Concrete slab
L x W x H in meters 10.5 x 5 x 4 meters
AC Power Not yet available
DC Power Not yet available
Rectifier Not yet available
Batteries Not yet available
Power Distribution Board Not yet available
Grounding System Not yet available
Security Room is secured,
Access Road Makutano - kitui road
RTU/SAS Not available
Marshalling Not available
Appro Project Machakos 33/11 kV Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 3 en 01 No. of p. 8
4. RTU Not available
.
5. Marshalling Cubicles Not available
6. Communication Equipment Not available.
ADSS last mile fiber link to be installed to Embakasi substation. New FO terminal equipment
required to Embakasi for onward routing to NCC using existing communication equipment.
7. Room layout
.
8. AC Supply Not available
9. DC Supply Not available
Cable Routes Available
Communication Eqpt Not available
Appro Project Machakos 33/11 kV Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 4 en 01 No. of p. 8
10. Plant Interface 10.1 Signals list
Attached
10.2 Installation and adaptation works
A new RTU, Marshalling cabinet and Fiber optic terminal equipment will need to be installed.
Wiring from the panels yet to be installed to the Marshalling cubicle and from the
Marshalling to the RTU will be required.
11. Enclosures
9.1 Site Survey Report
9.2 Detailed plant drawings
9.3 Control Room layout
9.4 Equipment Room Layout
9.4
12. Notes
distance from the site (km) 35 km from nairobi
Nearby buildings Thika motor dealers
Nearby industries Thika motor dealers
Type of soil Clay soil
Water availability No water
Special authority pass LOA, PTW
Type of area Commercial
Power supply Not yet installed
Pass issued by: NRCC
Appro Project Machakos 33/11 kV Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 5 en 01 No. of p. 8
13. Photographic Report Substation building
Substation building
Communication room and Equipment rooms
SIGNAL LIST
Machakos 33/11kV Signal list
OBJECT TYPE SIGNAL Indications Alarms Commands Measurands
Energy Meter Inputs
33kV LINE 1 DPI X708 ISO On/Off 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
TX1 BAY DPI CB VPR1 On/Off 1
ISO X709 On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
Protection Faulty 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
Appro Project Machakos 33/11 kV Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 6 en 01 No. of p. 8
SF6 LOW second step 1
DCO CB VPR1 Open/Close 1
AMI Volts, kV 1
Active Power, P 1
Reactive Power, Q 1
Amps 1
TX2 BAY DPI CB VWVE13 On/Off 1
ISO X710 On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
Protection Faulty 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
DCO CB VWVE13 Open/Close 1
AMI Volts, kV 1
Active Power, P 1
Reactive Power, Q 1
Amps 1
TX1 DPI TC Auto/Manual 1
TC Local/Remote 1
SPI TTA‐Temp Alarm 1
TTT TEMP TRIP 1
TBA BUCH AL 1
TBT BUCH TRIP 1
TOL OIL LEVEL ALARM 1
TGA TX GENERAL AL 1
TGT TX GEN TRIP 1
TBS TX OUT OF STEP 1
DCO TC Auto/Manual 1
RCO TC Raise/Lower 1
AMI Tap Position 1
TX2 DPI TC Auto/Manual 1
TC Local/Remote 1
SPI TTA‐Temp Alarm 1
TTT TEMP TRIP 1
TBA BUCH AL 1
TBT BUCH TRIP 1
Appro Project Machakos 33/11 kV Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 7 en 01 No. of p. 8
TOL OIL LEVEL ALARM 1
TGA TX GENERAL AL 1
TGT TX GEN TRIP 1
TBS TX OUT OF STEP 1
DCO TC Auto/Manual 1
RCO TC Raise/Lower 1
AMI Tap Position 1
11 KV
FEEDER 1 DPI CB FTU110 On/Off 1
ISO Y6066 On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW second step 1
DCO CB FTU110 Open/Close 1
AMI Volts, kV 1
Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
FEEDER 2 DPI CB KFE13 On/Off 1
ISO Y6064 On/Off 1
CB OSM1 On/Off 1
ISO Y6065 On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW second step 1
DCO CB KFE13 Open/Close 1
AMI Volts, kV 1
Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Station DPI Station Remote/Supervisory 1
SPI 48 DC Battery Alarm 1
48 DC Charger Alarm 1
48V Charger A Fail Alarm 1
48V Charger B Fail Alarm 1
Appro Project Machakos 33/11 kV Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 8 en 01 No. of p. 8
RTU Alarm 1
Communications Alarm 1
110V DC Battery Alarm 1
110V DC Charger Alarm 1
110V DC Charger A Fail Alarm 1
110V DC Charger B Fail Alarm 1
Smoke in Control Room 1
AMI 48V DC1 1
48V DC2 1
110V DC1 1
110V DC2 1
Total 16 49 8 21 6
Appr Project Mombasa road substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Resp. dept Projects Status
Doc. no. Lang. Rev. ind. Page 1 en 01 No. of p. 10
Site Survey Report
To: Projects Engineer
Station: Mombasa Road Substation
1. General: Information
Project Site survey
Site Survey Engineers Albert Kadala, Beatrice Muthoni
Survey Date 21/08/2014
Station Name & Contact Mombasa road
Region &Town Nairobi South
Distance to Site(km) 18 km from Juja control
Station Coordinates 1*20’23.6”S, 36*52’26.9”E, 5403ft
Access Road Mombasa road
Station Voltage 66/11kV
Cable Trenches Available
Notes:
A new 11 kV board has been installed at the station. Installation works is in progress.
Appro Project Mombasa road substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 2 en 01 No. of p. 10
2. Drawings
Single line diagram
3. Equipment Room
Location 11kV room
Room type and Floor Concrete building
Ceiling type Galsheet mabati roof
L x W x H in meters 13.5 x 7.5 x 5meters
AC Power 415 VAC
DC Power 110VDC, 30VDC
Rectifier Available
Batteries Available
Power Distribution Board Available with spare capacity
Grounding System Substation earth
Security Room secured with standard paddlock
Access Road Mombasa road
RTU/SAS Available. To use existing Embakasi RTU
Marshalling Available, wiring in progress
Cable Routes Available
Communication Eqpt Available, with connection to Juja control
Appro Project Mombasa road substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 3 en 01 No. of p. 10
4. RTU
Available in Embakasi, wiring in progress
.
5. Marshalling Cubicles
Available. Wiring in progress
6. Communication Equipment
Fiber optic terminal available, fiber connection to Juja available
7. Room layout
.
8. AC Supply
415 VAC
Appro Project Mombasa road substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 4 en 01 No. of p. 10
9. DC Supply
110VDC, 48VDC, 30VDC
10. Plant Interface
10.1 Signals list
Attached
10.2 Installation and adaptation works
New 11kV panel installed. Wiring in progress
11. Enclosures 9.1 Site Survey Report
9.2 Detailed plant drawings
9.3 Control Room layout
9.4 Equipment Room Layout
9.4
12. Notes
distance from the site (km) 18 km from juja Nearby buildings Embakasi sub Nearby industries Lab and allied Type of soil Black cotton Water availability Water tank available Special authority pass Limitation of access Type of area Industrial Power supply Available Pass issued by: Nairobi area
Appro Project Mombasa road substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 5 en 01 No. of p. 10
13. Photographic Report
11kv board
Marshalling cubicle work in progress
AC distribution board
Appro Project Mombasa road substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 6 en 01 No. of p. 10
SIGNAL LIST
Mombasa Road 11kV Signal list
OBJECT TYPE SIGNAL Indications Alarms Commands Measurands
Energy Meter Inputs
LINE 1 DPI INC 1 CB On/Off 1
DCO INC 1 CB Open/Close 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
LINE 2 DPI INC 2 CB On/Off 1
DCO INC 2 CB Open/Close 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
11kV Feeders
SPARE DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
Appro Project Mombasa road substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 7 en 01 No. of p. 10
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
IMARA DAIMA DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
AIRPORT DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
NMG DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
MSA RD DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Appro Project Mombasa road substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 8 en 01 No. of p. 10
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
BUS COUPLER DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
LABELS DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
MASAI RD DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
LAB & ALLIED DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
Appro Project Mombasa road substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 9 en 01 No. of p. 10
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
POLYTHENE DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
SAFE PAK DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Station DPI Station Remote/Supervisory 1
SPI 48 DC Battery Alarm 1
48 DC Charger Alarm 1
48V Charger A Fail Alarm 1
48V Charger B Fail Alarm 1
RTU Alarm 1
Communications Alarm 1
110V DC Battery Alarm 1
110V DC Charger Alarm 1
110V DC Charger A Fail Alarm 1
110V DC Charger B Fail Alarm 1
Smoke in Control Room 1
Appro Project Mombasa road substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 10 en 01 No. of p. 10
AMI 48V DC1 1
48V DC2 1
110V DC1 1
110V DC2 1
Total 14 63 13 21 24
Appr Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Resp. dept Projects Status
Doc. no. Lang. Rev. ind. Page 1 en 01 No. of p. 17
Site Survey Report
To: Projects Engineer
Station: Muthurwa 66/11kV
1. General: Information
Project Site Survey
Site Survey Engineers Metrine Jelagat & Tony Angatia
Survey Date 17th September 2014
Station Name & Contact Muthurwa 66/11 kV
Region &Town Nairobi South, Nairobi
Distance to Site(km) 13.3 km from Juja rd NCC
Station Coordinates Latitude : 1.287117°S , 36.835619°E, 2389m
Access Road Landhies Road
Station Voltage 66/11 kV
Cable Trenches Available
Notes:
Muthurwa substation is a 66/11kV station with 3 No. 66 kV incomers from Juja and Nairobi
south. The station has 2 No. 45 MVA transformers with 15 No. feeders and 2 No. 11kV
incomers.
The station has already installed a Sicam (siemens) RTU but with no communication to the
control centres
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 2 en 01 No. of p. 17
2. Drawings
Single Line Diagram
NB: All isolators are motorised while CB are SF6
Station Layout
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 3 en 01 No. of p. 17
3. Equipment Room
Location 11kV room
Room type and Floor Stone building, concrete floor
Ceiling type Concrete
L x W x H in meters 25*6.6*4.46 m
AC Power 240/415 V ac
DC Power 110V
Rectifier Available
Batteries Available for protection panels
Power Distribution Board Available
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 4 en 01 No. of p. 17
4. RTU
Siemens SICAM 1703 ACP CP 6014 gateway available
5. Marshalling Cubicles
Available
Grounding System Substation earth mat
Security Guard at the gate, room secured with standard padlock
Access Road Landhies Rd
RTU/SAS Siemens SICAM 1703 ACP CP 6014 gateway available
Marshalling Available
Cable Routes Available
Communication Equipment Not Available
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 5 en 01 No. of p. 17
6. Communication Equipment
Not Available
7. Room layout
8. AC Supply
240/415V
9. DC Supply
110 V DC
10. Plant Interface
10.1 Signals list
Muthurwa 66/11kV Signal list
OBJECT TYPE SIGNAL Indications Alarms Commands Measurands
Energy Meter Inputs
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 6 en 01 No. of p. 17
66kV LINE 1 DPI 1L1 E/S On/Off 1
1L3 ISO On/Off 1
1L5 CB On/Off 1
1L7 ISO On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Back up Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW 1ST Step 1
SF6 LOW 2ND Step 1
Bay Faulty 1
Master Trip Operated 1
DC Source Fail 1
Remote/Local 1
Auto Reclose Operated 1
Auto Reclose Lockout 1
21 Relay Fail 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
DCO 1L3 ISO Open/Close 1
1L5 CB Open/Close 1
1L7 ISO Open/Close 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
LINE 2 DPI 2L1 E/S On/Off 1
2L3 ISO On/Off 1
2L5 CB On/Off 1
2L7 ISO On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Back up Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW 1ST Step 1
SF6 LOW 2ND Step 1
Bay Faulty 1
Master Trip Operated 1
DC Source Fail 1
Remote/Local 1
Auto Reclose Operated 1
Auto Reclose Lockout 1
21 Relay Fail 1
AMI Active Power, P 1
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 7 en 01 No. of p. 17
Reactive Power, Q 1
Voltage, U 1
Current, I 1
DCO 2L3 ISO Open/Close 1
2L5 CB Open/Close 1
2L7 ISO Open/Close 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
LINE 3 DPI 3L1 E/S On/Off 1
3L3 ISO On/Off 1
3L5 CB On/Off 1
3L7 ISO On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Back up Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW 1ST Step 1
SF6 LOW 2ND Step 1
Bay Faulty 1
Master Trip Operated 1
DC Source Fail 1
Remote/Local 1
Auto Reclose Operated 1
Auto Reclose Lockout 1
21 Relay Fail 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
DCO 3L3 ISO Open/Close 1
3L5 CB Open/Close 1
3L7 ISO Open/Close 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Tx 1 BAY DPI 1H3 ISO On/Off 1
1H0 CB On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Back up Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW 1ST Step 1
SF6 LOW 2ND Step 1
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 8 en 01 No. of p. 17
Bay Faulty 1
Master Trip Operated 1
DC Source Fail 1
Remote/Local 1
Auto Reclose Operated 1
Auto Reclose Lockout 1
Buchholz Trip 1
Winding Temperature Trip 1
Oil Temperature Trip 1
Oil Level Alarm 1
TC Manual/Auto 1
TC Master/Follower 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
DCO 1H3 ISO Open/Close 1
1H0 CB Open/Close 1
TC Raise/Lower 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
Tx 2 BAY DPI 2H3 ISO On/Off 1
2H0 CB On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Back up Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW 1ST Step 1
SF6 LOW 2ND Step 1
Bay Faulty 1
Master Trip Operated 1
DC Source Fail 1
Remote/Local 1
Auto Reclose Operated 1
Auto Reclose Lockout 1
Buchholz Trip 1
Winding Temperature Trip 1
Oil Temperature Trip 1
Oil Level Alarm 1
TC Manual/Auto 1
TC Master/Follower 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 9 en 01 No. of p. 17
DCO 2H3 ISO Open/Close 1
2H0 CB Open/Close 1
TC Raise/Lower 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
INCOMER 1 DPI INC 1 E/S On/Off 1
INC1 CB On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Back up Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW 1ST Step 1
SF6 LOW 2ND Step 1
Remote/Local 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
DCO INC1 CB Open/Close 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
INCOMER2 DPI INC 2 E/S On/Off 1
INC2 CB On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Back up Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW 1ST Step 1
SF6 LOW 2ND Step 1
Remote/Local 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
DCO INC2 CB Open/Close
ITI Energy, KWHR Imp
Energy, KVARHR Imp
CAPACITOR FDR1 DPI CB On/Off 1
E/S On/Off 1
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 10 en 01 No. of p. 17
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
OTC FDR DPI CB On/Off 1
E/S On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
TEMPLE 2 FDR DPI CB On/Off 1
E/S On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 11 en 01 No. of p. 17
ITI Energy, KWHR 1
Energy, KVARHR 1
DONHOLM FDR DPI CB On/Off 1
E/S On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
LOCAL TX 100KVA DPI CB On/Off 1
E/S On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
JEEVANJI 1 FDR DPI CB On/Off 1
E/S On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 12 en 01 No. of p. 17
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
RIVER RD FDR DPI CB On/Off 1
E/S On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
BUS SECTION DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Remote/Local 1
MUTHURWA FDR DPI CB On/Off 1
E/S On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 13 en 01 No. of p. 17
ITI Energy, KWHR 1
Energy, KVARHR 1
SPARE1 FDR DPI CB On/Off 1
E/S On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
JEEVANJI 2 FDR DPI CB On/Off 1
E/S On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
LOCAL TX 100KVA DPI CB On/Off 1
E/S On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 14 en 01 No. of p. 17
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
SPARE 1 DPI CB On/Off 1
E/S On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
KIKOMBA DPI CB On/Off 1
E/S On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
TEMPLE 1 DPI CB On/Off 1
E/S On/Off 1
SPI MPT‐Main Prot. Trip 1
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 15 en 01 No. of p. 17
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
CAPACITOR FDR2 DPI CB On/Off 1
E/S On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Station DPI Station Remote/Supervisory 1
SPI 48 DC Battery Alarm 1
48 DC Charger Alarm 1
48V Charger A Fail Alarm 1
48V Charger B Fail Alarm 1
RTU Alarm 1
Communications Alarm 1
110V DC Battery Alarm 1
110V DC Charger Alarm 1
110V DC Charger A Fail Alarm 1
110V DC Charger B Fail Alarm 1
Smoke in Control Room 1
AMI 48V DC1 1
48V DC2 1
110V DC1 1
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 16 en 01 No. of p. 17
110V DC2 1
Total 52 179 31 92 42
10.2 Installation and adaptation works
Siemens SICAM 1703 ACP CP 6014 gateway available but not yet connected to any
communication device.
It is expected to install and ADSS cable to the station through IT & T project. A multiplexer shall
therefore be required in this station for final connection to NCC
11. Enclosures
9.1 Site Survey Report
9.2 Detailed plant drawings
9.3 Control Room layout
9.4 Equipment Room Layout
9.4
12. Notes
distance from the site (km) 13.3 km from Juja rd NCC Nearby buildings Muthurwa Market & Machakos Country Bus Station Nearby industries Jua Kali light industries Type of soil Black cotton Soil Water availability Available Special authority pass Permit to work Type of area Urban Power supply 240V ac Pass issued by: Nairobi Area Regional Control
Appro Project Muthurwa 66/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 17 en 01 No. of p. 17
13. Photographic Report
Pic.1: RTU cabinet with Siemens SICAM 1703 ACP CP 6014 gateway but not yet connected to radio.
Pic.2: Battery room
Appr Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Resp. dept Projects Status
Doc. no. Lang. Rev. ind. Page 1 en 01 No. of p. 17
Site Survey Report
To: Projects Engineer
Station: Nairobi West 66/11kV
1. General: Information
Project Site survey
Site Survey Engineers Metrine Jelagat & Tony Angatia
Survey Date 17th September 2014
Station Name & Contact Nairobi West 66/11 kV
Region &Town Nairobi West, Nairobi
Distance to Site(km) 16.1 km from Juja Rd NCC
Station Coordinates 1.310715°S,36.828613°E, 2366m
Access Road Kiganjo Avenue off Mombasa Rd
Station Voltage 66/11 kV
Cable Trenches Available
Notes:
The substation is situated along Kiganjo Avenue off Mombasa Road. There is an existing FOX515
multiplexer which shares its cabinet with an ETL equipment for PLC. The equipment is currently
in the old control building.
There also exists an RTU 560 and its marshalling cubicle in the station but they are not installed
The station is a 66/11KV substation with 66kV equipment located outdoors. There is a new 11kV, indoor switchboard type ABB , currently being installed at the station. The control and protection equipment for the transformers and 66kV lines are located in the old control building. The 11kV breakers are as shown in the room layout drawing of the new control building There are four 66KV lines and fifteen 11KV feeders and two transformers.
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 2 en 01 No. of p. 17
2. Drawings Single Line Diagram
TX2
W33
1L5
1L3
1L1U/G Cable to RAGATI S/S NGONG RD
W37
1H0
2L7
2L5
2L3
2L1
2H3
2H0
BC
TX1
INC1 INC2
W39
OUT GOING FEEDERS
2H2W32
EMBAKASSI2EMBAKASSI1
To old Control room To old Control room
66/11kV 45MVA
11kV switchboard New Control room
66/11kV 45MVA
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 3 en 01 No. of p. 17
The 11kv feeder panels in the new building are not yet labelled.
Station Layout
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 4 en 01 No. of p. 17
3. Equipment Room
Location 1. New Control room
2. Old Control Room
Room type and Floor Stone building, concrete floor
Ceiling type Iron Sheets
L x W x H in meters 23.77x6.46x4.46m- new control room
AC Power 240/415 VAC
DC Power 110V for protection,
30V for protection of old 11kV switchboard- old control room
48V for scada and communication- old control Battery/charger
room
Rectifier Available
Batteries Available
Power Distribution Board Available
Grounding System Substation earthing
Security Guard at the gate, Room secured with non standard
contractor’s padlock
Access Road Kiganjo Avenue off Mombasa Rd
RTU/SAS RTU 560 in the old control room but not mounted
Marshalling Marshalling cubicle in the old control room but not mounted
Cable Routes Available
Communication Equipment Fox 515 equipment in the old control room
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 5 en 01 No. of p. 17
4. RTU Available but not installed
5. Marshalling Cubicles Available but not installed
6. Communication Equipment Fox 515 available
7. Room layout
.
8. AC Supply 240/415VAC available
9. DC Supply 110V protection, 48V Scada and telecoms in the old control room
10. Plant Interface 10.1 Signals list
Attached
10.2 Installation and adaptation works The 11kV switchboard has been entirely replaced. Station adaptation works shall be required for the
board to a new RTU under this contract. The 66kV line relay panels & Transformer Panels are
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 6 en 01 No. of p. 17
currently located in the old control building. Adaptation works for the same shall be required, these
are currently located in the old control building.
The distance between the two control buildings is approximately 50m
11. Enclosures 9.1 Site Survey Report
9.2 Detailed plant drawings
9.3 Control Room layout
9.4 Equipment Room Layout
12. Notes distance from the site (km) 16.1 km from Juja Rd NCC Nearby buildings Kongoni Primary School, Kenya Institute of Mass
Communication Nearby industries Industrial Area, CMC Type of soil Black Cotton Water availability Water available Special authority pass Permit to work Type of area Residential Power supply 240VAC Pass issued by: Nairobi Area Regional Control
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 7 en 01 No. of p. 17
13. Photographic Report
Pic.1: ODF in the new building is on the floor next to 110 DC charger & not yet fitted to the wall
Pic.2: The outgoing 11kV feeders under construction in the new control building
Pic.3: New control building Pic.4:
Signal list
Nairobi West 66/11kV Signal list
OBJECT TYPE SIGNAL Indications Alarms Commands Measurands
Energy Meter Inputs
66kV
LINE 1 DPI 1L1 E/S On/Off 1
1L3 ISO On/Off 1 1L5 CB On/Off
1 W33 ISO On/Off
1
SPI MPT-Main Prot. Trip 1
BPT-Back up Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1 SF6 LOW 1ST Step 1 SF6 LOW 2ND Step 1 Bay Faulty 1 Master Trip Operated 1 DC Source Fail 1 Remote/Local 1
Auto Reclose Operated 1
Auto Reclose Lockout 1
21 Relay Fail 1
DCO 1L5 CB Open/Close
1
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 8 en 01 No. of p. 17
1
LINE 2 DPI W39 ISO On/Off 1
SPI MPT-Main Prot. Trip 1
BPT-Back up Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1 SF6 LOW 1ST Step 1 SF6 LOW 2ND Step 1 Bay Faulty 1 Master Trip Operated 1 DC Source Fail 1 Remote/Local 1
Auto Reclose Operated 1
Auto Reclose Lockout 1
21 Relay Fail 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
DCO CB Open/Close 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
LINE 3 DPI 2L3 ISO On/Off 1
2L5 CB On/Off 1
W38 ISO On/Off 1
SPI MPT-Main Prot. Trip 1
BPT-Back up Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1 SF6 LOW 1ST Step 1 SF6 LOW 2ND Step 1 Bay Faulty 1 Master Trip Operated 1 DC Source Fail 1 Remote/Local 1
Auto Reclose Operated 1
Auto Reclose Lockout 1
21 Relay Fail 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current,I 1
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 9 en 01 No. of p. 17
DCO 2L5 CB Open/Close 1
ITI Energy, KWHR 1
Energy, KVARHR 1
BUSBAR SECTION DPI 2H2 ISO On/Off 1
LINE 4 DPI W32 ISO On/Off 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
DCO CB Open/Close 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
Tx 1 BAY DPI W37 ISO On/Off 1
1H0 CB On/Off 1
SPI MPT-Main Prot. Trip 1
BPT-Back up Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1 SF6 LOW 1ST Step 1 SF6 LOW 2ND Step 1 Bay Faulty 1 Master Trip Operated 1 DC Source Fail 1 Remote/Local 1
Auto Reclose Operated 1
Auto Reclose Lockout 1
Buchholz Trip 1
Winding Temperature Trip 1
Oil Temperature Trip 1
Oil Level Alarm 1
TC Manual/Auto 1
TC Master/Follower 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
DCO CB Open/Close 1
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 10 en 01 No. of p. 17
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
Tx 2 BAY DPI 2H3 ISO On/Off 1
2H0 CB On/Off 1
SPI MPT-Main Prot. Trip 1
BPT-Back up Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1 SF6 LOW 1ST Step 1 SF6 LOW 2ND Step 1 Bay Faulty 1 Master Trip Operated 1 DC Source Fail 1 Remote/Local 1
Auto Reclose Operated 1
Auto Reclose Lockout 1
Buchholz Trip 1
Winding Temperature Trip 1
Oil Temperature Trip 1
Oil Level Alarm 1
TC Manual/Auto 1
TC Master/Follower 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
DCO CB Open/Close 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
INCOMER 1 DPI INC 1 E/S On/Off 1
INC1 CB On/Off 1
SPI MPT-Main Prot. Trip 1
BPT-Back up Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1 SF6 LOW 1ST Step 1 SF6 LOW 2ND Step 1 Remote/Local 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 11 en 01 No. of p. 17
1
DCO INC1 CB Open/Close 1
ITI Energy, KWHR Imp 1
Energy, KVARHR Imp 1
INCOMER2 DPI INC 2 E/S On/Off 1
INC2 CB On/Off 1
SPI MPT-Main Prot. Trip 1
BPT-Back up Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1 SF6 LOW 1ST Step 1 SF6 LOW 2ND Step 1 Remote/Local 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
DCO INC2 CB Open/Close
ITI Energy, KWHR Imp
Energy, KVARHR Imp
K16 OUTGOING DPI CB On/Off 1
E/S On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
K15 OUTGOING DPI CB On/Off 1
E/S On/Off
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 12 en 01 No. of p. 17
1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
K14 OUTGOING DPI CB On/Off 1
E/S On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
K13 OUTGOING DPI CB On/Off 1
E/S On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 13 en 01 No. of p. 17
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
K12 OUTGOING DPI CB On/Off 1
E/S On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
K11 OUTGOING DPI CB On/Off 1
E/S On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
Auto Reclose Operated 1 Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
K10 OUTGOING DPI CB On/Off 1
E/S On/Off 1
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 14 en 01 No. of p. 17
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
BUS SECTION DPI CB On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1 Remote/Local 1
K07 OUTGOING DPI CB On/Off 1
E/S On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
Auto Reclose Operated 1 Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
K06 OUTGOING DPI CB On/Off 1
E/S On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 15 en 01 No. of p. 17
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
K05 OUTGOING DPI CB On/Off 1
E/S On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
K04 OUTGOING DPI CB On/Off 1
E/S On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 16 en 01 No. of p. 17
ITI Energy, KWHR 1
Energy, KVARHR 1
K03 OUTGOING DPI CB On/Off 1
E/S On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
Auto Reclose Operated 1 Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
K02 OUTGOING DPI CB On/Off 1
E/S On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
SCF-Spring Charge Fail 1
Auto Reclose Operated 1 Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
K01 OUTGOING DPI CB On/Off 1
E/S On/Off 1
SPI MPT-Main Prot. Trip 1
TCF-Trip Circuit Faulty 1
Appro Project Nairobi West 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 17 en 01 No. of p. 17
SCF-Spring Charge Fail 1
Auto Reclose Operated 1
Remote/Local 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Current, I 1
ITI Energy, KWHR 1
Energy, KVARHR 1
Station DPI Station Remote/Supervisory 1
SPI 48 DC Battery Alarm 1
48 DC Charger Alarm 1
48V Charger A Fail Alarm 1
48V Charger B Fail Alarm 1
RTU Alarm 1
Communications Alarm 1
110V DC Battery Alarm 1
110V DC Charger Alarm 1
110V DC Charger A Fail Alarm 1
110V DC Charger B Fail Alarm 1
Smoke in Control Room 1
AMI 48V DC1 1
48V DC2 1
110V DC1 1
110V DC2 1
Total 48 174 22 88 40
Appr Project Nyaga 33/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Resp. dept Projects Status
Doc. no. Lang. Rev. ind. Page 1 en 01 No. of p. 9
Site Survey Report
To: Projects Engineer
Station: Nyaga Substation 33/11kV
1. General: Information
Project Site survey
Site Survey Engineers Metrine Jelagat
Survey Date 10th September 2014
Station Name & Contact Nyaga S/S 33/11 kV
Region &Town Nairobi North, Nairobi
Distance to Site(km) 40 km from Juja Control, 14 km from Ruiru town
Station Coordinates 1.0881160S, 36.8628190 E, 1698m ASL
Access Road Githunguri Rd from Ruiru Town, tarmac
Station Voltage 33/11 kV
Cable Trenches Under Construction
Notes:
The substation is situated along Ruiru- Githunguri Road. The station is currently under
construction, to include a new transformer bay
The substation shall have two 33/11KV , 7.5MVA transformer with an outdoor 11kv switch gear. The 11kV side has 2 incomers which are 11kV autoreclosures and airbreak switches and 4 feeders all controlled from outdoor A/B switches and autoreclosures
The new control room shall accommodate, two transformers and 66kV line protection panels and tap changer control panels.
There exists no SCADA equipment for the station.
There is no existing RTU.
Appro Project Nyaga 33/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 2 en 01 No. of p. 9
2. Drawings
X113 1L3
33 kV A/B SW.
33KV VWVE
TX17.5MVA
TX27.5MVA
Local TX
1L1
Single Line Diagram
33 kV
33 kV A/B SW
33 kV A/B SW.
33 kV A/B SW
33 kV A/B SW.
New feeder New feederGithunguri feeder Ruiru Feeder
RuiruGatundu West
33 kV
33KV VWVE
Appro Project Nyaga 33/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 3 en 01 No. of p. 9
3. Equipment Room
4. RTU It is proposed to install a new RTU in the control room as indicated on the room layout. Average length of cables shall be 15 meters and shall all be for bottom entry.
5. Marshalling Cubicles Not Available
6. Communication Equipment No communication equipment available at the station.
Location Control Panel room
Room type and Floor Stone building, concrete floor
Ceiling type Iron Sheets
L x W x H in meters 10x4.5x4M
AC Power 240/415 VAC
DC Power 30V for protection
Rectifier Not Available
Batteries Available
Power Distribution Board Available
Grounding System Substation Under Construction
Security Guard at the gate, Room secured with standard padlock
Access Road Southern Bypass -Ruiru – Githunguri Rd
RTU/SAS Not Available
Marshalling Not Available
Cable Routes Under construction
Communication Eqpt No communication equipment
Appro Project Nyaga 33/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 4 en 01 No. of p. 9
The most probable solution for communication
i. Option 1 an ADSS could be run from Ruiru S/S (about 20 Km from Ruiru S/S) and a multiplex equipment installed
ii. Option 2, install a radio mast plus radio equipment
7. Room layout
Communication room layout.
Appro Project Nyaga 33/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 5 en 01 No. of p. 9
8. AC Supply The room is still under construction
9. DC Supply
New 48v DC system is required. There is a 30V system for protection. The new system shall be located in the battery room next to the 30V DC charger as shown in the room layout diagram.
10. Plant Interface 10.1 Signals list
Attached
10.2 Installation and adaptation works An RTU and marshalling cubicle and a fiber optic terminal equipment to be installed at the
station. Cabling from all switch gear to the marshalling will need to be installed
11. Enclosures 9.1 Site Survey Report
9.2 Detailed plant drawings
9.3 Control Room layout
9.4 Equipment Room Layout
Appro Project Nyaga 33/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 6 en 01 No. of p. 9
12. Notes distance from the site (km) 40 km from Juja Control Nearby buildings Kwa Maiko shopping Centre Nearby industries Kangaita Coffee farms Type of soil Red Soil Water availability Special authority pass Permit to work Type of area Farm land Power supply 240VAC Pass issued by: Nairobi area control
13. photographic Report
Battery Room Station under construction
Signal list
Airport 66/11kV Signal list
OBJECT TYPE SIGNAL Indications Alarms Commands Measurands
Energy Meter Inputs
33kV LINE 1 (Ruiru) DPI E/S On/Off 1
ISO On/Off 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
LINE 2 ( Gatundu West) DPI E/S On/Off 1
ISO On/Off 1
AMI Active Power, P 1
Reactive Power, Q 1
Appro Project Nyaga 33/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 7 en 01 No. of p. 9
Voltage, U 1
33kV Busbar DPI ISO On/Off 1
DCO ISO Close/Open 1
TX1 BAY DPI CB x114 On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
Protection Faulty 1
DCO CB x114 Open/Close 1
TX2 BAY DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
Protection Faulty 1
DCO CB Open/Close 1
TX1 DPI TC Auto/Manual 1
TC Local/Remote 1
SPI TTA‐Temp Alarm 1
TTT TEMP TRIP 1
TBA BUCH AL 1
TBT BUCH TRIP 1
TOL OIL LEVEL ALARM 1
TGA TX GENERAL AL 1
TGT TX GEN TRIP 1
TBS TX OUT OF STEP 1
DCO TC Auto/Manual 1
RCO TC Raise/Lower 1
AMI Tap Position 1
TX2 DPI TC Auto/Manual 1
TC Local/Remote 1
SPI TTA‐Temp Alarm 1
TTT TEMP TRIP 1
TBA BUCH AL 1
TBT BUCH TRIP 1
TOL OIL LEVEL ALARM 1
TGA TX GENERAL AL 1
TGT TX GEN TRIP 1
TBS TX OUT OF STEP 1
DCO TC Auto/Manual 1
Appro Project Nyaga 33/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 8 en 01 No. of p. 9
RCO TC Raise/Lower 1
AMI Tap Position 1
11 KV
INCOMER 1 DPI CB INC1 On/Off 1
DCO CB INC 1 Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
INCOMER 2 DPI CB INC2 On/Off 1
DCO CB INC 2 Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
11kV BUSBAR AMI Volts, kV 1
11kV Feeders
New feeder 1 DPI CB On/Off 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Ruiru DPI CB On/Off 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Githunguri DPI CB On/Off 1
DCO CB Open/Close 1
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
New Feeder 2 DPI CB On/Off 1
DCO CB Open/Close 1
Appro Project Nyaga 33/11 kV Substation Prep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
Doc. no. Lang. Rev. ind. Page 9 en 01 No. of p. 9
AMI Active Power, P 1
Reactive Power, Q 1
Voltage, U 1
Station DPI Station Remote/Supervisory 1
SPI 48 DC Battery Alarm 1
48 DC Charger Alarm 1
RTU Alarm 1
Communications Alarm 1
110V DC Battery Alarm 1
110V DC Charger Alarm 1
AMI 48V DC 1
110V DC 1
Total 18 28 13 30 2
Appr Project Steel Billets 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Resp. dept Projects Status
Doc. no. Lang. Rev. ind. Page 1 en 01 No. of p. 9
Site Survey Report
To: Projects Engineer
Station: Steel Billets Substation 66/11kV
1. General: Information
Project Site survey
Site Survey Engineers Metrine Jelagat
Survey Date 10th September 2014
Station Name & Contact Steel Billets S/S 33/11 kV
Region &Town Nairobi North, Nairobi
Distance to Site(km) 1.5 km from Juja Control
Station Coordinates
Access Road Juja Road
Station Voltage 66/11 kV
Cable Trenches Undergoing construction
Notes:
The substation consists of one 66KV line, two 23 MVA transformers, the 11kV board has been decommissioned to be constructed anew The substation is situated at a turn off from the Juja Rd near Tononoka steel mills.
There is no radio but there is a communication mast installed in the station
An RTU was installed at the station but has since been recovered and parts used for other
stations
A
P
T
Appro Prep. Title
Repo
2. Drawin
The 11
3. Equipm
Location
Room typ
Ceiling typ
L x W x H
AC Power
DC Power
Rectifier
Batteries
Power Dis
Grounding
ort on Site Vi
ngs
kV Board is
ment Room
e and Floo
pe
in meters
r
r
stribution B
g System
isit
s yet to be c
m
1
or S
I
N
N
A
Board N
S
Date
constructed
11kV room
Stone buildi
Iron Sheets
Not Availab
Not Availab
Available in
Available in
Not Availab
Station unde
Project
Customer
Dept
, the contro
ing, concret
ble
ble
n the decom
n the decom
ble
er construct
Steel B
Kenya P
Projects
ol room is em
te floor
missioned c
mmissioned
tion
illets 66/11 k
Power & Ligh
Sta
mpty
control room
control roo
kV Substatio
hting Co Ltd
atus
en 01
m
om
on
No. of p. 9
Appro Project Steel Billets 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 9
4. RTU
A vandalised RTU 560 with cables in the decommissioned control room
5. Marshalling Cubicles Available in the decommissioned control room
6. Communication Equipment A communication mast exists, but there is no radio
7. Room layout
Room still under construction
8. AC Supply Room still under construction
9. DC Supply 110V protection, 48V Scada and telecoms in the decommissioned control building
10. Plant Interface 10.1 Signals list
Attached
10.2 Installation and adaptation works It is required that a complete scada equipment is installed at the station once the 11 kV board is
replaced. Details of the 11kV board are yet to be availed.
The 66kV side is still existing and would also need to be rewired to a new scada equipment.
A communication mast exists at the station, a radio would be required at the station for
communication to Juja control site.
Security Guard at the gate, Room secured with standard padlock
Access Road Juja Rd
RTU/SAS Decommissioned RTU560 with parts vanadalised
Marshalling Available with parts vandalised
Cable Routes New control room under construction
Communication Eqpt Radio communication mast available but no radio
Appro Project Steel Billets 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 9
11. Enclosures 9.1 Site Survey Report
9.2 Detailed plant drawings
9.3 Control Room layout
9.4 Equipment Room Layout
12. Notes distance from the site (km) 1.5 km from Juja Control Nearby buildings Tononoka Steel Mills Nearby industries Tononoka Steel Mills Type of soil Black Cotton Water availability Water available from city council Special authority pass Permit to work Type of area Commercial Power supply 240VAC Pass issued by: Nairobi area control
13. Photographic Report RTU at site Marshalling Cubicle
Signal list as per original Station
Appro Project Steel Billets 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 9
Steel Billets 66/11kV Signal list
OBJECT TYPE SIGNAL Indications Alarms Commands Measurands
Energy Meter Inputs
66kV 66kV LINE DPI 1L7 ISO On/Off 1
1H5 ISO On/Off 1
1L5 CB On/Off 1
DCO 1L5 CB Open/Close 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
TX1 BAY
DPI ISO 3H3 On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
TX2 BAY
DPI ISO 2H3 On/Off 1
SPI MPT‐Main Prot. Trip 1
BPT‐Backup Prot. Trip 1
TX1 DPI TC Auto/Manual 1
TC Local/Remote 1
TC Master/Follower 1
SPI TTA‐Temp Alarm 1
TTT TEMP TRIP 1
TBA BUCH AL 1
TBT BUCH TRIP 1
TOL OIL LEVEL ALARM 1
TGA TX GENERAL AL 1
TGT TX GEN TRIP 1
TBS TX OUT OF STEP 1
RCO TC Raise/Lower 1
AMI Tap Position 1
Appro Project Steel Billets 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 9
TX2 DPI TC Auto/Manual 1
TC Local/Remote 1
TC Master/Follower 1
SPI TTA‐Temp Alarm 1
TTT TEMP TRIP 1
TBA BUCH AL 1
TBT BUCH TRIP 1
TOL OIL LEVEL ALARM 1
TGA TX GENERAL AL 1
TGT TX GEN TRIP 1
TBS TX OUT OF STEP 1
RCO TC Raise/Lower 1
AMI Tap Position 1
11 KV
INCOMER 1 DPI CB INC1 On/Off 1
SPI MPT‐Main Prot. Trip 1
Protection Faulty 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
DCO CB INC 1 Open/Close 1
AMI Volts, kV 1
Active Power, P 1
Reactive Power, Q 1
Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
INCOMER 2 DPI CB INC2 On/Off 1
SPI MPT‐Main Prot. Trip 1
BYF‐Bay Faulty 1
Protection Faulty 1
TCF‐Trip Circuit Faulty 1
Lockout relay operated 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
SF6 LOW second step 1
DCO CB INC 2 Open/Close 1
AMI Volts, kV 1
Active Power, P 1
Reactive Power, Q 1
Appro Project Steel Billets 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 9
Amps 1
ITI Energy, KWHR 1
Energy, KVARHR 1
11kV BUSBAR DPI ISO BC On/Off 1
DCO ISO BC Open/Close 1
AMI Volts, kV 1
Frequency, F 1
11kV Feeders
Jacaranda DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
Eastleigh DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
Sunrise DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
VOK DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
Appro Project Steel Billets 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 9
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
Tononoka DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
KCC DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
Kayole DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
Komarock DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
Appro Project Steel Billets 66/11 kV SubstationPrep. Date Customer Kenya Power & Lighting Co Ltd Title
Report on Site Visit Dept Projects Status
en 01 No. of p. 9
PFCF DPI CB On/Off 1
SPI MPT‐Main Prot. Trip 1
TCF‐Trip Circuit Faulty 1
SCF‐Spring Charge Fail 1
SF6 LOW first step 1
DCO CB Open/Close 1
AMI Amps 1
Station DPI Station Remote/Supervisory 1
SPI 48 DC Battery Alarm 1
48 DC Charger Alarm 1
RTU Alarm 1
Communications Alarm 1
110V DC Battery Alarm 1
110V DC Charger Alarm 1
AMI 48V DC1 1
48V DC2 1
110V DC1 1
110V DC2 1
Total 24 88 15 25 4