  • Wireless Data Acquisition

    System --

    Wireless GSM 3G RTU

    User Manual

    Ver 1.0

    S280

    Date Issued: 2016-11-08

    All rights reserved by

    www.GPRS-M2M.com

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    http://www.gprs-m2m.com/

  • S280 Wireless GSM 3G RTU User Manual Page 2 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    Table of contents

    1. Brief introduction -------------------------------------------------------------------------------------------------3

    2. Safety Directions ---------------------------------------------------------------------------------------------------6

    3. Physical Layout ----------------------------------------------------------------------------------------------------7

    4. Settings -------------------------------------------------------------------------------------------------------------9

    5. SMS commands -----------------------------------------------------------------------------------------21

    6. Communication Protocol--------------------------------------------------------------------------------------26

    7. Registers Assignment Table----------------------------------------------------------------------------------26

    8. Upgrade Firmware ----------------------------------------------------------------------------------------------26

    9. Warranty -----------------------------------------------------------------------------------------------------------26

    S280 Wireless GSM 3G RTU & Wireless DAM Table

    Model Master/

    Slave Precision DIN T/H DO Record Communication

    S280 Master 12bit 4 1 2 3500 USB/RS232/RS485

    433Hz/GSM/GPRS/3G/RJ45

    WT-01 Slave Wireless DTU(Data Transfer Unit) with RS485 Port

    WT-02 Slave Wireless Repeater, range 2~5Km

    WT-03 Slave Wireless DAM, supports 1 Temperature&Humidity Sensor.

    WT-05 Slave Wireless DAM, supports 1 Temperature&Humidity Sensor and 2 Analog

    input(0~5V)

    WT-06 Slave Wireless DAM, supports 4 Analog input(0~5V) and 4 Digital Inputs

    Notice

    1. For 3G Version, the model should plus C or W, C stands for inbuilt module is CDMA2000. W stands for inbuilt module is WCDMA;

    2. RS232/RS485 serial port default is RS485, optional is RS232.

    3. T/H: temperature & humidity input for environment monitoring, Range: -40~80C, 0~100%RH. 4. The standard package:

    1x RTU, 1x GSM Antenna, 1x AC/DC Adaptor, Android&IOS Apps, 1x PC Configuration Software,

    1x USB cable, 1x User Manual, 1x Backup battery inside, Terminals for Connection.

    5. The standard package not includes: SIMCard , Temperature+Humidity sensor AM2301.

    Warning Tips:

    Please Read the user manual firstly before any configurating and operating.

    This handbook has been designed as a guide to the installation and operation of Wireless GSM 3G RTU S280.

    Statements contained in the handbook are general guidelines only and in no way are designed to supersede the

    instructions contained with other products.

    We recommend that the advice of a registered electrician be sought before any Installation work commences.

    King Pigeon Communication.Co.,Limited. its employees and distributors, accept no liability for any loss or damage

    including consequential damage due to reliance on any material contained in this handbook.

    King Pigeon Communication.Co.,Limited. its employees and distributors, accept no liability for GSM/3G Network

    upgrading or SIMCard upgrading due to the technology specifications contained in this handbook.

  • S280 Wireless GSM 3G RTU User Manual Page 3 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    1. Brief Introduction

    The Wireless GSM 3G RTU(Remote Terminal Unit) S280 is a cost effective remote terminal unit. It inbuilt quad

    band GSM/GPRS module (Or WCDMA/CDMA2000) , ISM Band 433Mhz Radio Frequency module, and ARM

    Cortex 32 Bit RISC Core. It is a multi Isolation I/O port remote terminal unit and wireless data acquisition

    system.

    The Wireless GSM 3G RTU S280 can be used for monitoring maximum 400 distributed I/O endpoints though

    maximum 50 wireless Data Acquisition Modules by RF 433Mhz wireless network. Also it can be used as for

    converting the meters, transducers, Data Acquisition modules, PLC data via RS485 serial port to 433 MHz

    wireless network and then transmits it to GSM/SMS/GPRS/3G/Ethernet network. It performs as a wired

    wireless SMS/GPRS/ 3G/Ethernet/RS232/RS485 gateway. The range covers about 2~5Km, plus WT-02

    Wireless repeaters can increase the wireless distance.

    The Wireless GSM 3G RTU S280 equips 4 digital inputs, 2 solid relay outputs, power status detection moulde,

    and onsite temperature and humidity inputs. All of the inputs and outputs are isolation.

    The Wireless GSM 3G RTU S280 can be used as Wireless SMS Alarm, when the equipped I/O or 400

    distributed I/O alarm occurrence, it also can send pre-definition SMS to up to 10 mobile phone users.

    The Wireless GSM 3G RTU S280 is suitable for lots of applications, e.g.: Wireless data logging, BTS monitoring,

    remote data acquisition, telemetrically, farm, energy saving, agriculture, automatically meter reading system,

    weather station, storage, factory and other applications.

    The Wireless GSM 3G RTU S280 supports Modbus RTU Slave, Modbus TCP, TCP/UDP, SMS and data

    transparent transmission protocol through RS232/RS485/GSM/SMS/GPRS/3G./Ethernet.

    The Wireless GSM 3G RTU can be used as:

    A Wireless Data Acquisition System. Supports monitoring up to 50 wireless data acquisition module

    for maximum 400 endpoints by 433Mhz wireless network, the range covers about 2~5Km, plus WT-02

    Wireless repeaters can increase the wireless distance. Each endpoint can be setup threshold value or

    alarm conditions, once the value exceed threshold value or activated will send out SMS to alert the users

    immediately.

    A Wireless Gateway. Though the WT-01 wireless data transfer unit, it can convert the meters,

    transducers, Data Acquisition modules, PLC data via RS485 serial port to 433 MHz wireless network

    and then transmits it to GSM/SMS/GPRS/3G/Ethernet network. It performs as a wired wireless

    SMS/GPRS/ 3G/Ethernet/RS232/RS485 gateway.

    A SMS Alarm Controller. The IO activations or deactivations can be reported by SMS and optionally

    confirmed by phone calls. Each input can have its own message texts and the message can be

    programmed by users.

    A Switch with SMS Remote Control. SMS texts for switching particular terminals on/off or pulse output

    are configurable.

    A Timer-Switch which can be activated automatically. It can be setup when to performs preset logic

    events, e.g.: timer reports its status, timer switch on/off device or equipments automatically.

  • S280 Wireless GSM 3G RTU User Manual Page 4 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU A SMS reporter. The WIRELESS GSM 3G RTU can setup daily automatically report one or more times

    of its current status to users automatically.

    A Data Logger. The unit can save all of the events or acquisition data in internal memory storage, the

    historical data can export to CS format via USB port or upload to server by GPRS /3G network according

    to schedule, no distance limitation.

    1.1 Typically Applications

    Suitable Applications:

    1. Security Alarm System applications; 2. Supervision and monitoring alarm systems

    3. Automatic monitoring system; 4. Vending Machines;

    5. Pumping Stations; 6. Buildings and Real Estate;

    7. Weather Stations remote control and data logging; 8. River Monitoring and Flood Control remote control;

    9. Oil and gas pipelines remote control and data logging; 10. Corrosion protection

    11. Valve controls; 12. Wellheads;

    13. Energy saving,street lights control system; 14. Tanks, levels, temperatures,water leakage applications;

    15. Transformer stations; 16. Unmanned machine rooms;

    17. Control room application; 18. PLC and Automation System, M2M;

    19. GSM Access Control System, GSM Gate Opener, etc.

    System Schematic Diagram

  • S280 Wireless GSM 3G RTU User Manual Page 5 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    1.2 Mainly Features

    1) Inbuilt ARM Cortex-M4 32 Bit RISC Core MCU;

    2) Quadband 850/900/1800/1900Mhz GSM GPRS Module inside, WCDMA/CDMA2000 Modules are optional.

    3) Widely Rated voltage range, 9~36VDC, Inbuilt large capacity rechargeable backup battery;

    4) Large internal memory to save up to 3500 historical records, USB port for configuration, upgrade firmware

    and export records;

    5) Inbuilt industrial ISM Band 433Mhz Radio Frequency Half duplex communication module, distance up to

    2~5Km;

    6) Supports maximum 50 wireless Data Acquisition Modules, will alert users by SMS once the wireless DAM

    connect failure to ensure the monitoring working properly;

    7) Supports maximum 400 wireless distributed I/O endpoints;

    8) 2 solid relay outputs, rated capacity is 5A/30VDC,5A/250VAC;

    9) 4 digital inputs, compatible to dry contact or wet contact inputs. Logic level: 0~0. 5V or short circuit treated

    as close, +3~30V or open circuits treated as open;

    10) 1 temperature & humidity sensor input for monitoring onsite environment, the sensor model is AM2301,

    Measures temperatures from -40-80C,0.5C accuracy, Relative Humidity from 0-99RH%, accuracy is 3%;

    11) 1 RS485 serial port (Optional: RS232) for Modbus RTU Slave to SCADA or data transparent transmission;.

    12) I/O ports with opto-isolated, RS232/485/RJ45 with 15KV ESD protection;

    13) Supports Modbus TCP,TCP/IP protocol, Definition Protocol and transparent transmission over GPRS/3G/

    Ethernet network;

    14) Automatically resend the data while GPRS/3G/Ethernet communication interrupt or failure, GPRS/3G

    failure will alert by SMS text to users;

    15) Supports remotely restart the RTU, and configure& operate it by SMS commands remotely;

  • S280 Wireless GSM 3G RTU User Manual Page 6 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    16) Supports over voltage protection and phase-reversal protection, provide DC power sources for external

    device to save wiring cost;

    17) 10 SMS Alert and auto dial numbers for receiving alarm message, can program to receive specified alarm

    message.

    1.2 Specifications

    Item Reference Scope

    DC Power supply Standard adapter: DC 12V/1.5A Range 9-36VDC

    Power consumption Standby:12V/70mA; Working Max.: 12V/300mA

    GSM Frequency 850/900/1800/1900Mhz/ 3G WCDMA/3G CDMA2000

    Transmit power Class 4 (2W) at EGSM 900 and EGSM 850

    Class 1 (1W) at GSM 1800 and GSM 1900

    GPRS connectivity GPRS multi-slot class 10

    GPRS Data

    Transmission

    GPRS data downlink transfer: max. 85.6 kbps

    GPRS data uplink transfer: max. 42.8 kbps

    Coding scheme: CS-1, CS-2, CS-3 and CS-4

    TCP/IP stack TCP,UDP

    SIM interface Supporting 3V SIM Card

    External antenna SMA Antenna interface, 50 Ohm

    Program Interfaces 1 USB Port

    Protocols SMS, GPRS UDP,TCP, Modbus RTU Slave, Modbus TCP and more

    equipment protocols can be added according to requirements.

    RS232/485 1 RS485(Optional: RS232), Support Transparent transmission,

    definition protocol and Modbus RTU Slave.

    RF433Mhz

    Inbuilt RF433Mhz Half duplex communication module, wireless

    distance is 2~5Km, Max. receive sensitive: -148dBm,Max. transmit

    power: +27dBm.

    Max. Wireless DAM Supports Max. 50 wireless Data Acquisition Modules

    Max. Wireless I/O Supports Max. 400 wireless I/O

    RJ45 1 RJ45, support definition protocol and Modbus TCP protocol.

    Digital Inputs 4 Digital input, NC/NO/Level type

    Temp.&Hum Inputs Temperature range: -40C to +80C. Humidity Range: 0~100%RH;

    Relay Outputs 2, Rated: 5A/30VDC,5A/250VAC

    Power Outputs 1 Port, 9~36VDC output for external device;

    Memory Capacity Internal Memory inside, can save the data for 3500events.

    Backup Battery 3.7V 1200mAH

    Temperature range -10-+70 C

    Humidity range Relative humidity 95% (condensation free)

    Exterior dimension 168mm*113mm*32.3mm

    Net Weight 1000 g

    2.Safety Directions

    Safe Startup Do not use unit when using GSM/3G equipment is prohibited or might bring disturbance or danger.

    Interference

    All wireless equipment might interfere network signals of unit and influence its performance.

  • S280 Wireless GSM 3G RTU User Manual Page 7 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    Avoid Use at Gas Station

    Do not use unit at a gas station. Power off RTU when it near fuels or chemicals.

    Power it off near Blasting Places

    Please follow relevant restrictive regulations. Avoid using the device in blasting places.

    Reasonable Use

    Please install the product at suitable places as described in the product documentation. Avoid

    signal shielded by covering the mainframe.

    Use Qualified Maintenance Service

    Maintenance can be carried out only by qualified maintainer.

    3. Physical Layout

    LED Indicator Definition

    GSM/3G module indicator. Flicks quickly(less than 1second per time) stands for searching GSM/3G Network or no SIMCard inside or SIMCard connection is not good or cannot register to GSM/3G network successful. Flicks slowly (about 2senconds per time)stands for GSM/GPRS/3G stands for registered successful and GSM/3G Module standby.

    Relay indicator, any relay close stands for ON, otherwise will OFF;

    Alarm Indicator, alarm will ON and flick quickly. Normally is OFF;

    Arm/Disarmed Indicator, Arm is ON, disarmed is OFF.

    RF 433Mhz wireless transmit indicator, transmitting will flick, otherwise will OFF;

    RS232/RS485 Port indicator, transmitting data will flick, otherwise will OFF;

    RJ45 Ethernet indicator, connect successful will always ON, otherwise will OFF;

    Power indicator, powered on will ON, otherwise will OFF.

  • S280 Wireless GSM 3G RTU User Manual Page 8 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    Power Connectors Definition

    DC IN+ External DC Power input port, Connect to 1.5A@9~36V DC power, positive electrode.

    DC IN- External DC Power Input port, contact to negative electrode

    DC Out+ Power source output port, positive electrode. Provides power from RTU to external transducers or sensors or detectors. The output voltage and current is the same as the power from DC IN inputs.

    DC Out - Power source output port, Negative electrode.

    Digital Input Definition

    Dry contact or wet contact. Logic level: 0~0. 5V or short circuit treated as close, +3~30V or open circuits

    treated as open.

    1~4 The 1st~4th digital input, positive electrode.

    GND GND for digital inputs, negative electrode.

    ATN Port Connector Definition

    GSM ANT GSM/3G Antenna connector, 50Ohm, SMA female.(Grey color)

    RF ANT RF 433Mhz Antenna connector, 50Ohm, SMA female.(Black color)

    USB Port Connector Definition

    USB USB port, for configuration and upgrading firmware and exporting historical data;

    Temperature Humidity Sensor Port Definitions

    T/H Temperature & Humidity sensor AM2301 input. Measurement Range: Temperature: -40C to +80C, Humidity: 0~100%RH.

    Digital Solid Relay Output Connector Definition

    Solid Relay inside for outputs, Rated Capacity: 5A/30VDC,5A/250VAC.

    1+/1- The 1st Channel Solid Relay Output. + stands for positive electrode, - stands for negative electrode.

    2+/2- The 2

    nd Channel Solid Relay Output. + stands for positive electrode, - stands for

    negative electrode.

    RS232/RS485 Ports Definition

    A(R) RS485 A; RS232: RXD

    B(T) RS485 B; RS232: TXD

    GND Ground

  • S280 Wireless GSM 3G RTU User Manual Page 9 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    Backside Switch&Button Definition

    SIMCard Holder For SIMCard Installation, only supports 3V SIMCard, not supports 5V Simcard.

    Power Switch For switch ON or OFF the RTU.

    Load Button For upgrade firmware purpose only. Only when upgrade new firmware version will use it.

    4. Setting The WIRELESS GSM 3G RTU is user-friendly design. The user can setup it or export historic data by the PC

    Configurator through USB cable, and upgrade firmware by USB port. The WIRELESS GSM 3G RTU also can be

    configured some basically parameters by SMS Commands or Android APP and IOS APP, please refer to

    Chapter 5.

    Tips!

    1) Please insert the SIMCard firstly, and install the GSM Antenna, please power on to check the LEDs status

    according to abovementioned LED Definitions, then switch off it before you program it by PC Configurator.

    2) The PC Configurator in the CD, please click it to run it. Also can download from www.GPRS-M2M.com under

    S280 page directly.

    Below is the steps to setup the parameters by PC Configurator, please follow it step by step.

    Start to Configure the RTU :

    Step1: Run the WIRELESS GSM 3G RTU Configurator

    The WIRELESS GSM 3G RTU Configurator in the CD or download from www.GPRS-M2M.com, then run it

    on the computer, no need to installation.

    Step2: Connection

    Please insert the SIMCard, and install the GSM/3G Antenna.

    Step3: Connect the RTU to the PC by USB Cable. And connect the external DC Power to DC Power Ports,

    see below:

    Step4: Power On the RTU by the Backup side Power Switch.

    Step5: Install USB Drvier

    Please Contact the unit to the PC by USB Cable, and then install the USB Driver to the computer from the

    http://www.gprs-m2m.com/http://www.gprs-m2m.com/

  • S280 Wireless GSM 3G RTU User Manual Page 10 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    CD firstly. When successful, it can be found out at the device manager of the XP or Windows 7 or Win10,

    please see the below photo. Also, the driver for different OS can be downloaded from Silicon Laboratories,

    Inc. http://www.silabs.com , the model is CP210x.

    Tips: In some computer, if install the USB driver with problem, please try to get technical supports from technical

    support page of http://www.silabs.com directly.

    Step6: Run the WIRELESS GSM 3G RTU Configurator

    Click the to run the PC Configurator. And choose the correct Com port

    according to Step 5 displayed, as it shows COM 3, so should choose . Then click Open Com

    Port Button. If open successful, then the left corner of the windows will show

    ,otherwise, stands for connection failure. Enter the password, default is 1234.

    Then you can enter the configuration page as below:

    Step8: Configuration Parameters

    After above-mentioned operations, it is possible to program the parameters of the RTU. The details please

    see below instructions.

    Basic Settings

    http://www.silabs.com/http://www.silabs.com/

  • S280 Wireless GSM 3G RTU User Manual Page 11 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    Read Settings: Click it to read out the settings in the RTU;

    Save Settings: Click it to save all of the PC Configurator parameters to the RTU;

    Load Profile: Click it to load additional Profile to the PC Configurator;

    Export Profile: Click it to save the present configuration parameters as a profile for next RTU

    configurating or backup the parameter settings.

    Tips: The Load Profile and Export Profile is very useful while you need to program bulks of RTU with similar parameters.

    After programmed the first unit then you can export profile to save it, for the second RTU then you can load profile directly to

    save you time.

    Default: Click it to recovery the parameters to factory defaults.

    Reboot: Click it to restart the RTU.

    Parameter Settings

    Device ID: non-necessary. This is mainly for monitoring center to identify the RTU, if the application no

    needs to identify the RTU, and then no need to fill any thing in it.

    Device Description: This is the description of the RTU, can be included in daily reports and timer reports,

    e.g.: installation address, usage instructions and so on.

    Modify Password: this is for modifying the RTUs Password, default is 1234.

    Set Device Time: this is to setup the RTUs time for daily report or other timers. After click Set Device

    Time, the RTU will be synchronous the same time as the PC.

    Add Timestamp to Alarm SMS: Tick it stands for while alarm occurrence, the Alarm SMS will include the

    RTUS current time information at the SMS Content.

    Arm automatically when Power On: Tick it stands for once the RTU powered up, the RTU will enter into

    Arm Mode automatically.

    Auto Arm after Disarmed: Fill the timeout to enter into Armed Mode automatically after disarmed

    operation. This is usefully for security protection applications.

  • S280 Wireless GSM 3G RTU User Manual Page 12 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    Tips:

    Arm: Under this mode, any alarm occurrence will send SMS and dial the authorized numbers immediately. And execute the

    programmed I/O outputs.

    Disarmed: Under this mode, alarm occurrence will not send SMS & dial the authorized numbers.

    Enable Daily Report/Peridically report/Save Historical: Tick it stands for enable to automatically send

    SMS at specified time by daily/periodically or save historical data to internal memory.

    Number Settings

    This is to setup the Authorized User Telephone Numbers to receive the Alarm SMS or dial. Tick it stands

    for while the related event alarm occurrence will send SMS to this number.

    Alarm Tel Numbers: Set the alarm receiver numbers, please includes the country code, e.g. in China is

    0086, so input 8613570810254 neither +8613570810254 nor 008613570810254. Also, some

    GSM/3G Operators not required input country code, so please remove country code, e.g. in

    China is 0086, and China Mobile not required country code, so can set as 13570810254.

    Dial: Tick it stands for while the RTU own DIN/AIN alarm occurrence, will automatically dial this number.

    Timer Report: Tick it stands for Timer report SMS will send to this number.

    Arm/Disarm: Tick it stands for Arm or Disarm the RTU, will send SMS to this number.

    Alarm/Alarm Recovery: Tick it stands for while alarm or recovery, will send SMS to this number.

    Low Signal: Tick it stands for while GSM or 3G Network signal strength lower than 14 will send SMS to

    this number.

    External Power ON/OFF: Tick it stands for while external DC Power loss will send SMS to this number.

    GPRS Failure: Tick it stands for while GPRS/3G connection re-try 3 times and still failure will send SMS to

    this number.

    Relay ON/OFF: Tick it stands of while the Digital Solid Relay Output action will send SMS to this number.

    DIN Settings

    This page is for setting the digital input alarm conditions and usages.

  • S280 Wireless GSM 3G RTU User Manual Page 13 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    Channel Name: to setup the input channel name, e.g.: Pump or Motor and so on, in order to identify it in

    SMS Contents.

    Input Type: The user can choose the input type for related channel.

    1) Disabled: Not use this channel.

    2) NC: For connecting Normal close type detector, open will alarm.

    3) NO: For connecting normal open type detector, close will alarm.

    Current Status: Stands for inputs current status.

    Alarm Verify Time: Stands for when the digital input Close or Open last time more than this value, will be

    treated as a true alarm, if less than this value, then will not alarm.

    Alarm/Recovery SMS Content: fill it to define the SMS contents while alarm or recovery that will be sent

    to the authorized alarm telephone numbers;

    Enable Recovery Send SMS: Tick it stands for when the digital input recovery, will send SMS to the

    authorized numbers.

    Alarm Link DO1/DO2: Tick it stands for while this digital input triggering, the DO1/2 will response

    according to its configured parameters, e.g.: close or pulse output for xxxseconds.

    Temperature&Humidity Settings

    This page is to setup the temperature &Humidity Sensor AM230x parameters. The AM230x sensor is

    special for monitoring onsite environment temperature and humidity.

    Temperature and Humidity: Default is Enable. Only accept AMS230x series sensor;

    Channel Name: to setup the input channel name, e.g.:Room Temperature,in order to identify it in SMS

    Contents.

    Current Value: Stands for current temperature and humidity.

    Enable: Tick it stands for enable the related channel;

    Alarm Verify Time: Stands for when the analog input exceed the threshold value and last time more than

    this value, will be treated as a true alarm, if less than this value, then will not alarm.

    Threshold High: The higher value need to alarm, like 50Celsius degree. Temperature maximum value is

    80 Celsius degree, humidity maximum value is 100 for AM230x sensors;

    Threshold Low: The low value need to alarm, like -40Celsius degree.Temperature minimum value is -40

    Celsius degree, humidity minimum value is 0 for AM230x sensors;

    The other items are the same means as DIN settings.

    Digital Solid Relay Output (Dout) Settings

    This page is to setup the Output parameters and definite the output usages. The outputs will be used in the

    Interlock Page for programmable logic events.

  • S280 Wireless GSM 3G RTU User Manual Page 14 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    Channel Name: to setup the Output Channel name, e.g.: Pump or Motor and so on, in order to identify it in

    SMS Contents.

    Close Time: Stands for the relay close and last time.

    Open Description: Stands for when the Relay Open, send what SMS to the authorized numbers;

    Close Description: Stands for when the Relay Close, send what SMS to the authorized numbers.

    Manual Test By Click below ButtonThis is for manual test, click ON or OFF, the relay will close or open.

    Timer SettingDaily Timer

    This page is for setup daily timer, it is useful for scheduling when to execute what action automatically.

    Total can program 10 scheduling events. Tick it stands for enable this timer event:

    Weekly+Hour+Minute: Stands for what day and at what time does the RTU should execute the action.

    Action: Stands for what action does the RTU should to execute at the specified time.

    E.g.: as abovementioned,

    Every Sunday 06:00, RTU automatically Reboot.

    Every day 00:00, RTU upload data by GPRS to server.

    Every day 18:00, RTU armed automatically.

    Every Monday 08:00, RTU automatically send SMS reports to authorized numbers.

    GPRS Settings

    This Page is for setup the GPRS communication parameters, GPRS Transport data protocol and Server

  • S280 Wireless GSM 3G RTU User Manual Page 15 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    information. Only when you have Server or need to use GPRS to transmit data then need to setup these

    parameters. The GPRS Protocol details please refer to .

    GPRS Communication: To Enable or disabled GPRS/3G data communication function.

    APN: GPRS Access Point Name, provided by GSM/3G Operator.

    User Name: GPRS User Name, provided by GSM/3G Operator.

    Password: GPRS Password, provided by GSM/3G Operator.

    Communication Protocol: To choose which protocol will be used to transmit the data;

    Upload Data Interval Time:To setup the interval time to upload the data to server;

    Heart Beat Content: To setup the Heartbeat content;

    GPRS Protocol: Stands for the GPRS transmission using TCP or UDP protocol;

    Server Domain Name: The server DNS;

    Server IP Address: The server IP Address;

    Port: Stands for the servers port.

    Definition Protocol over GPRS: Tick it stands for the protocol via GPRS is KingPigeon RTU protocol.

    Modbus TCP Protocol over GPRS: Tick it stands for the protocol via GPRS is Modbus TCP protocol.

    Heartbeat Interval: GPRS keep online heartbeat interval time.

    Tips:

    1) The RTU only supports one of the IP Address and DNS as Server. Cannot use both of them at the same time.

    Ethernet Settings

    This page is for setup the Ethernet parameters. Over the RJ45 port, the S280 RTU can be used as slave

    to communication with the server. Please note, the connection must be started from the server. And only

    supports Ethernet LAN, not supports WAN.

    The protocol please refer to .

  • S280 Wireless GSM 3G RTU User Manual Page 16 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    RS232/485 Settings

    This page is for setup the serial port parameters. Over the RS232/485, the S280 RTU can be used as

    Modbus RTU Slave to DCS,SCADA,HMI.

    If use the S280 as a Modbus RTU slave, please refer to < S27X WIRELESS GSM 3G RTU Register

    Assignment Table> to get the registers information.

    Moreover, the RS232/485 supports transparent transmission to servers.

    Add Slave Settings

    This page is for adding wireless slaves to the RTU, only after consigned successful then the RTU can

    work properly with the wireless Slaves. Please understand how it works firstly by below:

    1) The S280 inbuilt a 433Mhz Half duplex communication module, it can transmit and receive data;

    2) The wireless slaves(WT-01/02/03/05/06 series) also inbuilt a a 433Mhz Half duplex

    communication module, it can transmit and receive data;

    3) The wireless salve includes 3 types for different purposes:

    WT-01: Wireless Data Transfer Unit, equips one RS485 Serial port for communication with with

    PLC,Meters,data acquisition modules, this model is special for transparent data transmission. If

    you use WT-01, then no need to setup other parameters. But at GPRS/Ethernet/RS232/485

    Settings, please choose the communication protocol as transparent data transmission type. This

    solution is special for the project that has Server already, and just want to covert the distributed

    PLC,Meters,Data Acquisition Modules to 433Mhz wireless network, then transmit to local server or

    remote servers. See below:

  • S280 Wireless GSM 3G RTU User Manual Page 17 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    WT-02: Wireless Repeater, it is a wireless amplifier special for expend the wireless signal transmit

    distance, the wireless distrance is up to 2~5Km.

    WT-03/05/06: Wireless Data Acquisition Module. These models equips I/O inputs for wired

    detectors, sensors and analog inputs. They are special for monitoring its I/O in distributed areas.

    see below:

    4) For WT-01 and WT-02, no need configure them in the PC configurator.

  • S280 Wireless GSM 3G RTU User Manual Page 18 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    5) For WT-03/05/06, in S280 RTU should assign the registers to save the data of each wireless

    salves IO parameters, means mapping address, E.g.: IO Channel Name, threshold value,trigger

    condition, alarm SMS content etc. and after configured, the RTU will polling the wireless slaves

    and read its present value, then compare the its preset value, if the reading value exceed the

    threshold value or active then will consider it as an alarm event, then process it according to the

    pre-set parameters, e.g.: send out SMS or close the DO1/2. The configuration please see below

    explanations.

    6) For adding slave operation, please refer to the PC Configurator Notice.

    Master-Slave Working Mode: to choose the RTU and Wireless slave working mode. Include 3 types.

    Disabled: Stands for will not use wireless slave;

    Slave Upload Period: Stands for the wireless slave will automatically upload the data to the RTU, this

    mode is reserved, if you application required this functions, please contact us for more details.

    Master Polling Mode: Stands for the RTU will periodically polling the wireless slaves.

    Slave Serial Number: Stands for the SN of the wireless slave, range 1~50, each wireless slave must

    use a unique serial number, and the serial number can not be the same with other wireless slave;

    Slave Model: Stands for wireless slaves WT-01/02/03/05/06. If choose WT-01/WT02 then no need to

    configure in the configurator.

    Notice:

    1) The S280 assigned 8channel for each wireless data acquisition module.

    2) For WT-03 and WT-05, the first channel is for temperature, the second channel is for humidity. And

    the temperature&humidity sensor must use AM230x sensor. Please dont change its usage. The

    unused channel is reserved.

    3) For WT-06, the 1st~4

    th channel is Analog input 1~4, and the 5~8

    th channel is digital input 1~4.

    Slave Mapping Address: Stands for this register in RTU related to which I/O in the Slave. The Slave

    mapping address was fixed, the relation is below:

  • S280 Wireless GSM 3G RTU User Manual Page 19 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    Slave Serial Number Mapping Address(Register in RTU)

    1 1~8

    2 9~16

    3 17~24

    4 25~32

    --- ---

    50 393~400

    The channel name, input type, and other items are the same as above-mentioned DIN Settings and

    AIN settings .

    Slave Manager

    This page is for reading out the wireless slave configuration from the RTU, and also can be used to read

    the wireless salve present values, click the Delete Device then can remove the wireless salves from the

    RTU.

    Historical Record

    This page is for manage and read out the historical record from the RTU, and can save as CS format for

    other purpose usage.

    For historical record, the PC Configurator can display max. 1000 records and the RTU can save maximum

    3500 records. If you need to read all of the records, please read out all records then export to Excel or

    CSV format to check it. Once the internal memory used over,, will automatically remove the earlier records

  • S280 Wireless GSM 3G RTU User Manual Page 20 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    for new records.

    The records only include alarm events, not includes power loss events, timer events.

    Register List

    This page is for monitoring the wireless slave present value, it is useful to check the I/O in the wireless

    data acquisition modules working status. and also can save as CS format for other purpose usage.

  • S280 Wireless GSM 3G RTU User Manual Page 21 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    Start to Work:

    Step1: In order to save you time to program it, please click Export Profile to save these configurations as a

    profile for future quickly configure the RTU.

    Step2: Exit the Configuration, and Switch OFF the RTU.

    Step3: This Step is for you first time to use this RTU, or youre not sure if the configurations are save

    successful. Run the PC Configurator, and Switch ON the RTU again, enter password and try to read

    out the previous settings. If can read out all of the settings, then stands for you previous settings are

    successful. And from Register list page you can check all of the wireless I/O present status.

    5. SMS commands.

    The SMS commands will be used for remote control the RTU are below, the SMS Commands must be CAP

    LOCKs:

    1) Commands error return SMS

    Event Return SMS Content

    Any incorrect Command SMS Format Error, Please check Caps Lock in Command!

    2) External DC Status

    Event Return SMS Content

    External DC goes off External DC Power Goes OFF

    External DC Power Goes ON External DC Power Goes ON

    3) External DC Power Lost Delay Time to Alarm

    SMS Command Return SMS Content

    Setup password+ACxxx

    xxx stands for delay time, range 000~999

    minutes. =000, stands for alarm

    immediately, =999 stands for DC power

    lost will not alarm. Default is 000.

    External DC Power Lost Delay time to Alarm: xxx minutes

    Inquiry password+AC External DC Power Lost Delay time to Alarm: xxx minutes

    4) Modify Password, 4digits, default is 1234

    SMS Command Return SMS Content

    Old PasswordPNew Password This is the New Password, please remember it carefully.

    5) Setup Device ID Number

    SMS Command Return SMS Content

    Setup password+ IDxxxxx

    xxxxx=1~65535. Default is 1.

    ID:XXXXX

    Inquiry password+IDE ID:XXXXX

    6) Arm/Disarm SMS Command

    SMS Command Return SMS Content

    Arm password+AA Armed

    Disarm password+BB Disarmed

    7) Set RTU time format is 2015-05-22 15:20:30W01, the W01 stands for Monday, W07 stands for Sunday.

    SMS Command Return SMS Content

    password+DxxxxxxxTxxxxxWxx xxxx(Y)XX(M)XX(D)xx(H)X(M)xx(W)

    8) Inquiry Current Status SMS Command

    SMS Command Return SMS Content

    password+EE Time

    Device ID:

  • S280 Wireless GSM 3G RTU User Manual Page 22 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    Armed/Disarmed

    GSM Signal Value:

    External DC Power Goes OFF/ON

    DIN 1 Channel Name: Close/Open, Normal/Alarm;

    DIN 2 Channel Name: Close/Open, Normal/Alarm;

    DIN 3 Channel Name: Close/Open, Normal/Alarm;

    DIN 4 Channel Name: Close/Open, Normal/Alarm;

    Temperature:Current Value, Normal/High Alarm/Low Alarm

    Humidity:Current Value, Normal/High Alarm/Low Alarm

    DO1 Channel Name: Close/Open

    DO2 Channel Name: Close/Open

    Model:

    Version:

    Device Description:

    9) Setup 10 User number(Alarm Number&Access Control Number), max 21digits. ( Return 1~5 or 6~10

    separately while setting.)

    SMS Command Return SMS Content

    Setup passwordAseries number+T+tel number

    Notice:

    Series number = 01~10

    Tel1: ---

    Tel2: ---

    Tel3: 008613570810254

    Tel4: ---

    Tel5: ---

    Inquiry password+A Return all numbers

    Delete password+A+series number Return 1~5 or 6~10 numbers.

    10) Setup Daily Report time

    SMS Command Return SMS Content

    Setup password+DRT+xx+yy

    Notice:

    xx =00~23, stands for hour. yy=00~59,stands for minutes. Default is 10:00

    Daily SMS Report at: xx:xx

    Inquiry password+DRT Daily SMS Report at: xx:xx

    Delete password+DRTDEL

    11) Setup Periodically SMS Report interval time

    SMS Command Return SMS Content

    Setup password+DTxxxxx

    Notice:

    xxxxx=0~65535minutes, 0=stands for disable, default is 0.

    Periodically SMS Report

    interval time is: xxxxx minutes

    Inquiry password+DT The same as above

    12) Setup save historical data periodically time

    SMS Command Return SMS Content

    Set password+HISSAVExxxxxxx

    Notice: xxxxxxx=0~65535 seconds, default is 0, stands for not

    save.

    save historical data periodically

    time is:xxxxxSeconds

    Inquiry password+HISSAVE

    13) Setup Master Polling Slave interval time

    SMS Command Return SMS Content

    Setup password+ MODxxxxxx Periodically Polling Slave

  • S280 Wireless GSM 3G RTU User Manual Page 23 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    Notice:

    xxxxxx=0~999999seconds, 0=stands for disable, default is 3.

    interval time is: xxxxx seconds

    Inquiry password+MODE The same as above

    14) Setup DIN Name

    SMS Command Return SMS Content

    Set DIN Name password+DIN+channel number+T+ DIN Name

    Notice: channel number= 1~4, DIN Name max 40 characters;

    E.g.: 1234DIN1TDoor alarm

    DINx:

    Inquiry DIN Name password+DIN+series number

    Notice: nnnn stands for channel number,e,g.:

    1234DIN123 to inquiry channel 123s name.

    DINx:

    Set DIN Alarm SMS

    Content

    password+DINA+channel number+T+SMS Content

    Notice: channel number= 1~4, DIN Name max 40 characters;

    DINx:

    Inquiry DIN Alarm

    SMS Content

    password+DINA+series number

    Notice: nnnn stands for channel number,e,g.:

    1234DIN123 to inquiry channel 123s name.

    DINx:

    Set DIN Recovery SMS

    Content

    password+DINR+channel number+T+ DIN Name

    Notice: channel number= 1~4, DIN Name max 40 characters;

    DINx:

    Inquiry DIN Alarm

    SMS Content

    password+DINR+series number

    Notice: nnnn stands for channel number,e,g.:

    1234DIN123 to inquiry channel 123s name.

    DINx:

    Inquiry Current Status password+DINE DIN1:Open/Close

    DIN2: Open/Close

    -----(If setup Channel name will use

    channel name to replace DINx)

    Set DIN Input Type password+DIN+channel number+NO to set as NO

    password+DIN+channel number+NC to set as NC

    Notice: channel number= 1~4

    DIN1:NO/NC

    DIN2:NO/NC

    Inquiry DIN Input Type password+DINR DIN1:NO/NC

    DIN2:NO/NC

    Set DIN Alarm Verify

    Time

    password+DIN+ channel number+Q+xxx

    Notice: channel number= 1~4, xxx=000~999seconds,stands for

    alarm verify time, =999 stands for not alarm. Default is

    2seconds.

    DINx: xxxseconds

    Inquiry DIN Alarm

    Verify Time

    password+DINQ DIN1~4: xxxseconds

    15) Setup AIN Name(AIN1 is temperature input, AIN2 is humidity input)

    SMS Command Return SMS Content

    Set AIN Name password+AIN+channel number+T+AIN Name

    Notice: channel number= 1~2, AIN Name max 40 characters;

    E.g.: 1234AIN1TTemperature

    AINx:xxxx

    Inquiry AIN Name password+AIN+ channel number

    Set Threshold password+AINR+channel number+Lxxx+Hxxx+#

    Notice: xxx must be 3 digits, e,g. 023 degree not 23.

    AINx: Low:xxx,High:xxx.

    Inquiry Threshold password+AINR+ channel number AINx: Low:xxx, High:xxx.

    AINy: Low:xxx, High:xxx.

  • S280 Wireless GSM 3G RTU User Manual Page 24 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    Set High Alarm SMS

    Content

    password+AINH+ channel number +T+ SMS Content

    Inquiry High Alarm

    SMS Content

    password+AINH+ channel number

    Set Low Alarm SMS

    Content

    password+AINL+ channel number +T+ SMS Content

    Inquiry Low Alarm

    SMS Content

    password+AINL+ channel number

    Set AIN Recovery SMS

    Content

    password+AINTHR+ channel number +T+ SMS

    Content

    Inquiry AIN Recovery

    SMS Content

    password+AINTHR+ channel number

    Set AIN Alarm Verify

    Time

    password+AIN+ channel number+Q+xxx

    Notice: channel number= 1~2, xxx=000~999seconds,stands

    for alarm verify time, =999 stands for not alarm. Default is

    2seconds.

    AINx: xxxseconds

    Inquiry DIN Alarm

    Verify Time

    password+AINQ AIN1: xxxseconds

    AIN2: xxxseconds

    Inquiry All AIN Current

    Value

    password+AINE AIN0xxxx ,+Normal/Higher/Lower

    AIN1xxxx ,+Normal/Higher/Lower

    ----

    16) SMS Control Digital Output

    SMS Command Return SMS Content

    Set DO Name password+DO+channel number+T+DO Name DOx:xxxx

    Inquiry DO Name password+DO+ channel number

    Set Close Description password+DOC+channel number+T+Description

    Inquiry Close

    Description

    password+DOCT+channel number

    Set Open Description password+DOO+channel number+T+Description

    Inquiry Open

    Description

    password+DOOT+channel number

    Switch ON(Close) password+DOC+ channel number DOx: ON

    DOy:ON

    Switch OFF(Open) password+DOO+ channel number DOx: OFF

    DOy:OFF

    Inquiry all DO Current

    Status

    password+DOE DO1: ON/OFF

    DO2:ON/OFF

    Set Pulse Output time password+DOP+ channel number +T+xxxx

    Notice: xxxx=9999seconds, =0 stands for always close

    DOx Pulse Output Time:xxxxS

    Inquiry pulse output

    time

    password+DOT Pulse Output Time:xxxS

    17) Reboot/Reset By SMS:

    SMS Command Return SMS Content

    Reboot password+Reboot Restart the RTU

    Reset password+Reset Recovery the settings of the RTU to

  • S280 Wireless GSM 3G RTU User Manual Page 25 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    factory default parameters.

    Delete Records password+HISDEL

    18) Read Register current value by SMS(Read wireless IO current value)

    SMS Command Return SMS Content

    Set password+RCU+register number

    Notice: register number=01~99. E.g. inquiry register 01 and 09

    current value, command is 1234RCU0109

    R1:XXXX(Y)

    R8:xxxx(N)

    Y stands for normal,

    N stands for alarm.

    19) Remove Slave by SMS(Remote wireless slave)

    SMS Command Return SMS Content

    Set password+DELDEV+Slave Serial number

    Notice: Slave Serial number =01~50. Each command can

    remove only 1 slave.

    Slave:xx, remove successful.

    20) Wireless Slave Monitoring SMS

    Event SMS Alarm Message

    Slave failure to communicate with Master Device ID: xx, yy, zz, --- fault Alarm

    Slave recovery to communicate with Master Device ID: xx, yy, zz, --- Recovery

    21) Set Server Parameter(Can not setup DNS by SMS)

    SMS Command Return SMS Content

    Set Server IP password+IP+ IPaddress+*+Server port Server:

    Port:

    Inquiry password+IP

    Delete password+IPDEL

    22) Set GPRS APN/USER NAME/PASSWORD

    SMS Command Return SMS Content

    Set password+AP+apn+#+username+#+userpassword APN:

    User Name:

    Password:

    Inquiry password+AP

    Delete password+APDEL

    23) Wakeup GPRS Online

    SMS Command Return SMS Content

    password+GPRSonline No SMS Return

    24) Read Current values by GPRS:

    GPRS Command Return Content

    Read data password+CEE

    Reset password+Reset Recovery the settings of the RTU to

    factory default parameters.

    Delete Records password+HISDEL

    25) Remote upload historic data via GPRS: Send this command, the unit will upload historic data via

    GPRS.

    GPRS Command Return Content

    Read All Historical

    Data

    password+HIS Automatically upload all historic

    data to server via GPRS.

    Read specified date

    Historical Data

    password+HIS+xxxxxxxxxx+yyyyyyyyyy

    Notice:

    xxxxxxxxxx: stands for start date,e.g.: 1601121200 means

    2016,Jan,12th,12:00 AM.

  • S280 Wireless GSM 3G RTU User Manual Page 26 of 26 Ver 1.0 WWW.GPRS-M2M.COM

    Wireless Data Acquisition System

    Wireless GSM 3G RTU

    yyyyyyyyyy: stands for end date.

    Delete Records password+HISDEL

    More other SMS Commands for special requirements please contact us.

    6. Communication Protocol

    The WIRELESS GSM 3G RTU supports TCP/IP communication via GPRS/3G. It is very useful for users to

    create remotely server. It inbuilt Modbus TCP protocol and definition protocol (KingPigeon RTU Protocol) and

    transparent transmission, the user can connect the WIRELESS GSM 3G RTU to the present HMI, OPC Server,

    SCADA directly.

    Also, the RS232/RS485 serial ports can be used as Modbus RTU Slave under Modbus RTU protocol integrated

    to DCS or other monitoring center.

    The RS232/485 also can be used as data transparent transmission.

    For GPRS Communication protocol, please refer to .

    7. Registers Assignment Table

    The registers assignment of the RTU and its IO will definite in the < S280 WIRELESS GSM 3G RTU Register

    Assignment Table>, please refer to it.

    8. Upgrade Firmware

    The WIRELESS GSM 3G RTU supports upgrade firmware via USB port directly. If we upgraded the

    firmware functions of the RTU, we will inform you to upgrade the firmware if you required. If there any new

    requirements of the present functions caused it should update the firmware, the user can upgrade them

    directly by USB port. If you required upgrade, please contact us to modify the firmware according to you

    requirements, and we will provide the upgraded firmware to you to upgrade them.

    9. Warranty

    1) The RTU was warranted to be free of defects in material and workmanship for one year from the date of

    purchase.

    2) This warranty does not extend to any defect, malfunction or failure caused by abuse or misuse by the

    Operating Instructions.