Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve...

15
Taco Presentation

Transcript of Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve...

Page 1: Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve Control valve Balance valve Balance valve.

Taco Presentation

Page 2: Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve Control valve Balance valve Balance valve.

LoadMatch

B-1

180°F315000 BTU/H

64.6 GPM

170°F

IHL-1

165.5°F

170.5°F

5000 BTU/H2.1 GPM

IHL-2

166.4°F

171.4°F

10000 BTU/H4.1 GPM

IHL-3

167.9°F

172.9°F

15000 BTU/H6.2 GPM

IHL-4

169.8°F

174.8°F

20000 BTU/H8.2 GPM

IHL-5

172.1°F

177.1°F

25000 BTU/H10.3 GPM

IHL-6

175°F

180°F

30000 BTU/H12.3 GPM

P-1

64.6 GPM31.1 FT

2.1 GPM10.5 FTHP-IHL-1

4.1 GPM10.5 FTHP-IHL-2

6.2 GPM11.1 FTHP-IHL-3

8.2 GPM10.5 FTHP-IHL-4

10.3 GPM10.7 FTHP-IHL-5

12.3 GPM11 FTHP-IHL-6

IHL-7

165.5°F

170.5°F

5000 BTU/H2.1 GPM

IHL-8

166.4°F

171.4°F

10000 BTU/H4.1 GPM

IHL-9

167.9°F

172.9°F

15000 BTU/H6.2 GPM

IHL-10

169.8°F

174.8°F

20000 BTU/H8.2 GPM

IHL-11

172.1°F

177.1°F

25000 BTU/H10.3 GPM

IHL-12

175°F

180°F

30000 BTU/H12.3 GPM

2.1 GPM10.5 FTHP-IHL-7

4.1 GPM10.5 FTHP-IHL-8

6.2 GPM11.1 FTHP-IHL-9

8.2 GPM10.5 FTHP-IHL-10

10.3 GPM10.7 FTHP-IHL-11

12.3 GPM11 FTHP-IHL-12

IHL-13

165.5°F

170.5°F

5000 BTU/H2.1 GPM

IHL-14

166.4°F

171.4°F

10000 BTU/H4.1 GPM

IHL-15

167.9°F

172.9°F

15000 BTU/H6.2 GPM

IHL-16

169.8°F

174.8°F

20000 BTU/H8.2 GPM

IHL-17

172.1°F

177.1°F

25000 BTU/H10.3 GPM

IHL-18

175°F

180°F

30000 BTU/H12.3 GPM

2.1 GPM10.5 FTHP-IHL-13

4.1 GPM10.5 FTHP-IHL-14

6.2 GPM11.1 FTHP-IHL-15

8.2 GPM10.5 FTHP-IHL-16

10.3 GPM10.7 FTHP-IHL-17

12.3 GPM11 FTHP-IHL-18

NAME: LOCATION:

Page 3: Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve Control valve Balance valve Balance valve.

Wet Rotor Circulating Pump

IHL-18

175°F

180°F

30000 BTU/H12.3 GPM 12.3 GPM

11 FTHP-IHL-18

Page 4: Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve Control valve Balance valve Balance valve.

Wet Rotor Circulating Pump

IHL-18

175°F

180°F

30000 BTU/H12.3 GPM 12.3 GPM

11 FTHP-IHL-18

Twin Tee

Page 5: Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve Control valve Balance valve Balance valve.

Wet Rotor Circulating Pump

IHL-18

175°F

180°F

30000 BTU/H12.3 GPM 12.3 GPM

11 FTHP-IHL-18

Twin Tee

Eliminate: Control valve Balance valve

Page 6: Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve Control valve Balance valve Balance valve.

Adjustments:Will have to either increase flow or coil area as you along the system.

Benefits: Saves on piping. Less pressure drop for circulator pump. Eliminates control valve leaks.

LoadMatch System

Page 7: Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve Control valve Balance valve Balance valve.

Pumps

Page 8: Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve Control valve Balance valve Balance valve.

Wet Rotor:

20 year life. Replacement cartridges cost around $150. No need to remove pump to replace cartridge. Can be variable speed. (300:1)

Page 9: Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve Control valve Balance valve Balance valve.

Self Sensing:

Drive comes with pre-programmed curves. Program can be edited in the field. Provide shut-off head for maximum efficiency. Standard dry run protection. Can only be lead/lag. Standard vibration isolation on drive.

Page 10: Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve Control valve Balance valve Balance valve.

Chilled Beams

Page 11: Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve Control valve Balance valve Balance valve.

Passive Beams

Page 12: Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve Control valve Balance valve Balance valve.

Active Beams

Page 13: Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve Control valve Balance valve Balance valve.

Design Considerations:

Chilled water should be between 55 and 60 deg. F. Handles sensible load only. Need DOAS system to handle latent load, ventilation requirements, and pressurization. Avoid openings to outdoors where using chilled beams. Provide dewpoint sensor in room and at ceiling for each space. Verify pressure in building stays positive.

Radiant cooling panels: 20-40 BTU/SF Passive chilled beams: 120-150 BTU/SF Active chilled beams: 400-750 BTU/SF

LoFlo with Chilled Beams

Page 14: Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve Control valve Balance valve Balance valve.

iWorx

Page 15: Wet Rotor Circulating Pump Twin Tee Wet Rotor Circulating Pump Twin Tee Eliminate: Control valve Control valve Balance valve Balance valve.

Features:

Pre-programmed controllers for standard equipment.Graphic control interface controller brings in other controllers and automatically creates graphics.Web-based.Uses NiagraAX framework.Can communicate with LonWorks, BACnet IP, BACnet MSTP, and Modbus.Only need to provide home screen graphics.Truly open protocol.Best used with light commercial and buildings with standard equipment.