Volt-VAR Control Implementation at Hydro Québec
Volt-VAR Control Implementation at Hydro Québec
Presented by Presented by HervHervéé DelmasDelmas
![Page 2: VVC implementation at Hydro Quebec - IEEE-SAgrouper.ieee.org/groups/td/dist/da/VVC implementation at... · 2010. 2. 1. · Actual Volt Control VAR Control Volt & VAR Control 123 V.](https://reader036.fdocuments.us/reader036/viewer/2022090610/606fd35f44c68834371d0f20/html5/thumbnails/2.jpg)
Projet CATVARProjet CATVAR 2
Outline
1. Context
2. Volt-VAR control overview
3. Volt-VAR control optimization
![Page 3: VVC implementation at Hydro Quebec - IEEE-SAgrouper.ieee.org/groups/td/dist/da/VVC implementation at... · 2010. 2. 1. · Actual Volt Control VAR Control Volt & VAR Control 123 V.](https://reader036.fdocuments.us/reader036/viewer/2022090610/606fd35f44c68834371d0f20/html5/thumbnails/3.jpg)
Projet CATVARProjet CATVAR 3
1. 1. HydroHydro--QuQuéébecbec’’ss VVC ProjectVVC Project
• By 2015, HQ wants to reduce energy consumption by 11 TWh (reduction of 6.4%)
• Lack of at least 1000 MVAR for Transmission needs
• Solution for 2 TWh energy reduction: Volt and Var Control
ContextContext
![Page 4: VVC implementation at Hydro Quebec - IEEE-SAgrouper.ieee.org/groups/td/dist/da/VVC implementation at... · 2010. 2. 1. · Actual Volt Control VAR Control Volt & VAR Control 123 V.](https://reader036.fdocuments.us/reader036/viewer/2022090610/606fd35f44c68834371d0f20/html5/thumbnails/4.jpg)
Projet CATVARProjet CATVAR 4
1. HQ VVC Project 1. HQ VVC Project –– ContextContext
• Volt and Var Control
– Addition of 2400 MVar on the distribution network. 2000 capacitor banks of 1.2 MVar. 3 installed for the demonstration project
– Addition of 1000 measurement points (volt.), 6 installed for the demonstration project
![Page 5: VVC implementation at Hydro Quebec - IEEE-SAgrouper.ieee.org/groups/td/dist/da/VVC implementation at... · 2010. 2. 1. · Actual Volt Control VAR Control Volt & VAR Control 123 V.](https://reader036.fdocuments.us/reader036/viewer/2022090610/606fd35f44c68834371d0f20/html5/thumbnails/5.jpg)
Projet CATVARProjet CATVAR 5
2. VVC 2. VVC overviewoverview -- EnergyEnergy SavingSaving
Minimum planning level to meet
CSA C235 = 115 V
Substation End of feeders
Actual
Volt Control
VAR Control
Volt & VAR Control
123 V
![Page 6: VVC implementation at Hydro Quebec - IEEE-SAgrouper.ieee.org/groups/td/dist/da/VVC implementation at... · 2010. 2. 1. · Actual Volt Control VAR Control Volt & VAR Control 123 V.](https://reader036.fdocuments.us/reader036/viewer/2022090610/606fd35f44c68834371d0f20/html5/thumbnails/6.jpg)
Projet CATVARProjet CATVAR 6
2. 2. VVC VVC overviewoverview –– Simple Volt ControlSimple Volt Control
Volt Meter
Communication network
Substation
End of Feeder
Regulationcontroller
A local regulation controller monitors the end of feeder’s voltage and sets the tap to maintain this voltage at 115V.
![Page 7: VVC implementation at Hydro Quebec - IEEE-SAgrouper.ieee.org/groups/td/dist/da/VVC implementation at... · 2010. 2. 1. · Actual Volt Control VAR Control Volt & VAR Control 123 V.](https://reader036.fdocuments.us/reader036/viewer/2022090610/606fd35f44c68834371d0f20/html5/thumbnails/7.jpg)
Projet CATVARProjet CATVAR 7
2. 2. VVC VVC overviewoverview –– Simple Volt controlSimple Volt control
• Simple but not fully effective. Demonstration project gained only 30% of the estimated energy consumption.
– Volt meters not really at the end of the feeders. Volt meters installed only on 3 phases circuits. Targets need to cover also the worst case voltage drop of the single phase networks.
– Network topology during the demonstration project (1 year average) was not in its normal state 40% of the time.
![Page 8: VVC implementation at Hydro Quebec - IEEE-SAgrouper.ieee.org/groups/td/dist/da/VVC implementation at... · 2010. 2. 1. · Actual Volt Control VAR Control Volt & VAR Control 123 V.](https://reader036.fdocuments.us/reader036/viewer/2022090610/606fd35f44c68834371d0f20/html5/thumbnails/8.jpg)
Projet CATVARProjet CATVAR 8
3. VVC Optimisation 3. VVC Optimisation -- Volt Volt MeterMeter PositionPosition
Substation End of feeders
123 V
115 V
Volt MeterTarget: 119V
3 Phases
Single phase
Volt MeterTarget: 116V
![Page 9: VVC implementation at Hydro Quebec - IEEE-SAgrouper.ieee.org/groups/td/dist/da/VVC implementation at... · 2010. 2. 1. · Actual Volt Control VAR Control Volt & VAR Control 123 V.](https://reader036.fdocuments.us/reader036/viewer/2022090610/606fd35f44c68834371d0f20/html5/thumbnails/9.jpg)
Projet CATVARProjet CATVAR 9
Volt meters can’t be moved as network topology changes
3. 3. VVC Optimisation VVC Optimisation –– Volt Volt MeterMeter PositionPosition
Volt Meter
Communication network
Substation
Volt Meter
Volt Meter
To anothersubstation
3 Phases
Single phase
Volt Meter
Volt Meter
Volt Meter
To anothersubstation Volt Meter
Regulationcontrol
Life is more complex
![Page 10: VVC implementation at Hydro Quebec - IEEE-SAgrouper.ieee.org/groups/td/dist/da/VVC implementation at... · 2010. 2. 1. · Actual Volt Control VAR Control Volt & VAR Control 123 V.](https://reader036.fdocuments.us/reader036/viewer/2022090610/606fd35f44c68834371d0f20/html5/thumbnails/10.jpg)
Projet CATVARProjet CATVAR 10
3. 3. VVC Optimisation VVC Optimisation –– DynamicDynamic Target Target CalculationCalculation
• For each measurement point, the voltage target is calculated using a network simulator:
– Target recalculation for any network topology change.
– Target recalculation following a load change.
![Page 11: VVC implementation at Hydro Quebec - IEEE-SAgrouper.ieee.org/groups/td/dist/da/VVC implementation at... · 2010. 2. 1. · Actual Volt Control VAR Control Volt & VAR Control 123 V.](https://reader036.fdocuments.us/reader036/viewer/2022090610/606fd35f44c68834371d0f20/html5/thumbnails/11.jpg)
Projet CATVARProjet CATVAR 11
3. 3. VVC Optimisation VVC Optimisation -- DynamicDynamicCalculationCalculation
Volt Meter
Substation
Volt Meter
Volt Meter
To anothersubstation
Volt Meter
Volt Meter
Volt Meter
To anothersubstation Volt Meter
Regulationcontrol
Communication network
DMSSetpoint
Volt/VAR simulator
![Page 12: VVC implementation at Hydro Quebec - IEEE-SAgrouper.ieee.org/groups/td/dist/da/VVC implementation at... · 2010. 2. 1. · Actual Volt Control VAR Control Volt & VAR Control 123 V.](https://reader036.fdocuments.us/reader036/viewer/2022090610/606fd35f44c68834371d0f20/html5/thumbnails/12.jpg)
Projet CATVARProjet CATVAR 12
3. VVC Optimisation 3. VVC Optimisation –– «« ManualManual »» proof of proof of ConceptConcept
• Manual hourly simulation launched during one week usingdynamic load and dynamic topology:
– 24h/24h Monday to Wednesday
– 8h/24h Thursday to Sunday
![Page 13: VVC implementation at Hydro Quebec - IEEE-SAgrouper.ieee.org/groups/td/dist/da/VVC implementation at... · 2010. 2. 1. · Actual Volt Control VAR Control Volt & VAR Control 123 V.](https://reader036.fdocuments.us/reader036/viewer/2022090610/606fd35f44c68834371d0f20/html5/thumbnails/13.jpg)
Projet CATVARProjet CATVAR 13
3. VVC Optimisation 3. VVC Optimisation -- manualmanualcalculationcalculation
Voltage reduction zone without dynamic target
Average hourly voltage reductionAverage voltage reduction
![Page 14: VVC implementation at Hydro Quebec - IEEE-SAgrouper.ieee.org/groups/td/dist/da/VVC implementation at... · 2010. 2. 1. · Actual Volt Control VAR Control Volt & VAR Control 123 V.](https://reader036.fdocuments.us/reader036/viewer/2022090610/606fd35f44c68834371d0f20/html5/thumbnails/14.jpg)
Projet CATVARProjet CATVAR 14
3. Real Time Network Simulation 3. Real Time Network Simulation
Challenges:
• Simulation robustness
– Missing settings – e.g.: substation transformer impedance, tap changer settings, …
– Missing measurements – e.g.: communication problem.
– Database inconsistency.
• Simulation accuracy
– Fixed load for commercial customer.
– Hourly load profile.
– Precision of measurements and dead band.
– Database inconsistency.