VRf PHV dxE H ˝, P-&) A$* C-*,˝$’ - Celsius Air Multi (VRF... · puhy / pury / pqhy / pqry vrf...
Transcript of VRf PHV dxE H ˝, P-&) A$* C-*,˝$’ - Celsius Air Multi (VRF... · puhy / pury / pqhy / pqry vrf...
VRf PHV dxE Heat Pump Air CurtainAir Curtain System
VRF PHV DXE - RECESSEDMOdEl REfERENCE
dIMENsIONs (mm) (WxdxH)
sUPPlY (50Hz)
HEAt OUtPUt (kW)
lOAdINg (amps)
VElOCItY (m/s)
AIR VOlUME (m3/h)
WEIgHt (kg)
NOIsE dB(A) @ 3m
MAx. MOUNtINg HEIgHt (m)
OUtdOOR UNIt MOdEl
VRF PHV1500R DXE HO
1650x436x296
415V*1
15.1
12.7*1
9
2600
67
58
3.5
PUMY / PUHY / PURY / PQHY / PQRY
VRF PHV2000R DXE LO
2240x436x296
415V*2
16.4
15.7*2
9.5
3300
85
59
3.5
PUMY / PUHY / PURY / PQHY / PQRY
Technical Information
VRF PHV DXE - FREE STANDINGMOdEl REfERENCE
dIMENsIONs (mm) (WxdxH)
sUPPlY (50Hz)
HEAt OUtPUt (kW)
lOAdINg (amps)
VElOCItY (m/s)
AIR VOlUME (m3/h)
WEIgHt (kg)
NOIsE dB(A) @ 3m
MAx. MOUNtINg HEIgHt (m)
OUtdOOR UNIt MOdEl
VRF PHV1500R DXE LO
1650x436x296
415V*1
10.6
12.7*1
9
2500
66
58
3.5
PUMY / PUHY / PURY / PQHY / PQRY
VRF PHV1000R DXE HO
1150x436x296
415V*1
9
7.8*1
9
1400
45
56
3.5
PUMY / PUHY / PURY / PQHY / PQRY
VRF PHV2000R DXE HO
2240x436x296
415V*2
21.4
15.7*2
9
3130
88
59
3.5
PUHY / PURY / PQHY / PQRY
VRF PHV1500 DXE HO
1746x377x255
415V*1
15.1
12.7*1
9
2600
60
58
3.75
PUMY / PUHY / PURY / PQHY / PQRY
VRF PHV2000 DXE LO
2296x377x255
415V*2
16.4
15.7*2
9.5
3300
78
59
3.75
PUMY / PUHY / PURY / PQHY / PQRY
VRF PHV1500 DXE LO
1746x377x255
415V*1
10.6
12.7*1
9
2500
59
58
3.75
PUMY / PUHY / PURY / PQHY / PQRY
VRF PHV1000 DXE HO
1196x377x255
415V*1
9
7.8*1
9
1400
39
56
3.75
PUMY / PUHY / PURY / PQHY / PQRY
VRF PHV2000 DXE HO
2296x377x255
415V*2
21.4
15.7*2
9
3130
80
59
3.75
PUHY / PURY / PQHY / PQRY
Notes: *1 for units with electric heaters disabled, 240v power supply 1.8 amp load (1.3 amp load for VRF PHV1000R DXE HO) *2 for units with electric heaters disabled, 240v power supply 2.7 amp load.
Notes: *1 for units with electric heaters disabled, 240v power supply 1.8 amp load (1.3 amp load for VRF PHV1000 DXE HO) *2 for units with electric heaters disabled, 240v power supply 2.7 amp load.
In collaboration with Thermoscreens, Mitsubishi Electric have developed a range of air curtains that are able to beconnected to our City Multi VRF systems, as opposed to the more traditional direct electric method associatedwith air curtains.
� Reduced CO2 emissions
� Reduced Running Costs
� Inverter technology (does not waste energy)
� Range of different sizes to suit every application
� Allows open door policy in retail outletswhilst being energy efficient
� Clean environment - protection from dust, fumes etc
� Comfortable climate for customers
� Easy to install and maintain
� Heat recovery possible, optimising energy use
Cit
y M
ult
iR
ange
VR
f PH
V d
xE
Air C
urt
ain
AIR CURTAIN VRf PHV1000/1500/2000R dxE
Dimensions
AIR CURTAIN VRf PHV1000/1500/2000 dxE
Rear View >
Upper View >
side View >
Rear View >
Upper View >
side View >