VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV...

132
AN ISO 9001 & 14001 COMPANY TENDER DOCUMENT TENDER No: DLI/CON/696/411 FOR ‘SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 11/0.433KV INDOOR/OUTDOOR ELECTRIC SUBSTATION AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K)’ VOLUME – III PRICE BID/ BILL OF QUANTITY

Transcript of VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV...

Page 1: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

AN ISO 9001 & 14001 COMPANY

TENDER DOCUMENT

TENDER No: DLI/CON/696/411

FOR

‘SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 11/0.433KV INDOOR/OUTDOOR ELECTRIC SUBSTATION AND OTHER ASSOCIATED

EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA,

DISTT. SAMBA (J&K)’

VOLUME – III

PRICE BID/ BILL OF QUANTITY

Page 2: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

In Figures In Words In Figures In Words1.0 A POWER SUPPLY PACKAGE FOR

SUBSTATION 11.1 POWER SUPPLY PACKAGE FOR

SUBSTATION 1 (As per DSR 2013) 1915100.00

1.2 POWER SUPPLY PACKAGE FORSUBSTATION 1 (As per Non DSRitems)

20243715.00

2.0 B POWER SUPPLY PACKAGE FOR SUBSTATION II TO VI & COMPACT TYPE SUBSTATION

2.1 POWER SUPPLY PACKAGE FORSUBSTATION II TO VI & COMPACTTYPE SUBSTATION (As per DSR2013)

18498560.00

2.2 POWER SUPPLY PACKAGE FORSUBSTATION II TO VI & COMPACTTYPE SUBSTATION (As per NonDSR 2013)

238497780.00

3.0 C EXTERNAL LIGHTING3.1 EXTERNAL LIGHTING WORK (As

per DSR 2013) 10661050.00

3.2 EXTERNAL LIGHTING WORK (Asper Non DSR 2013) 77807400.00

4.0 D CIVIL WORK4.1 CIVIL WORK (As per DSR 2013) 50158457.534.2 CIVIL WORK (As per Non DSR

2013) 1399200.00

I Total amount for DSR items 81233167.53II Total amount for Non DSR items 337948095.00III Total (I+II) 419181262.53

BIDDER FINANICIAL OFFER Rs:-( IN FIGURES)Rs:-( IN WORDS)

Note:- Bidder's has to quote their percentage rates including of all taxes & duties, octroi,Royalties, service tax,Labour cess, VAT/WCT/GST and Entry tax etc as applicable.

TENDER FOR SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 11/0.433KV INDOOR/OUTDOOR ELECTRIC SUBSTATION AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K)

Bidder's Price% Quote at Above/ PAR/ BelowS. No. Description Estimated Cost

(Rs.)

Amount in Rs. After adding Percentage at Above/ PAR/ BelowSection

PRICE BID FOR QUOTING SHEET

1 of 1

Page 3: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR-2013 MR TOTAL

I. A POWER SUPPLY PACKAGE FOR SUBSTATION - I 1,915,100.00 20,243,715.00 22,158,815.00

II. B POWER SUPPLY PACKAGE FOR SUBSTATION II TO VI & COMPACT TYPE SUBSTATIONS (CSS 1 TO CSS 10) 18,498,560.00 238,497,780.00 256,996,340.00

III. C EXTERNAL LIGHTING 10,661,050.00 77,807,400.00 88,468,450.00

IV D Civil Work 50,158,457.53 1,399,200.00 51,557,657.53

TOTAL 419,181,262.53

SAY 419,181,263.00(Rupees Fourty One Crore Ninety One lacs Eighty one Thousand Two Hundred Sixty Three only)

TENDER FOR SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 11/0.433KV INDOOR/OUTDOOR ELECTRIC SUBSTATION AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K)

GRAND SUMMARY OF POWER SUPPLY PACKAGE & EXTERNAL ELECTRICAL WORKS AND CIVIL WORK

SUB-HEAD SH. DESCRIPTIONESTIMATED COST IN RUPEES

SECTION

Page 4: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR-2013 MR TOTAL

I. H.T. CABLE & VACUUM CIRCUIT BREAKERS 375,384.00 5,036,600.00 5,411,984.00

II. DISTRIBUTION TRANSFORMER & BUS TRUNKING 330,345.00 3,254,000.00 3,584,345.00

III. DG SETS & ACCESSORIES 0.00 4,078,000.00 4,078,000.00

IV. MAIN L.T. PANELS, CAPACITOR BANK PANELS & SUB-DISTRIBUTION BOARDS 0.00 3,313,000.00 3,313,000.00

V. LT CABLES 887,371.00 4,562,115.00 5,449,486.00

VI. EARTHING 322,000.00 0.00 322,000.00

TOTAL AMOUNT (In Rs.) 1,915,100.00 20,243,715.00 22,158,815.00

SAY 22,158,815.00

TENDER FOR SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 11/0.433KV INDOOR/OUTDOOR ELECTRIC SUBSTATION AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE

BAGLA, DISTT. SAMBA (J&K)

SECTION - A: ABSTRACT COST FOR POWER SUPPLY PACKAGE FOR SUBSTATION - I

(POWER SUPPLY PACKAGE & EXTERNAL ELECTRICAL WORKS)

SUMMARY SHEET

SUB-HEAD SH. DESCRIPTIONESTIMATED COST IN RUPEES

Page 5: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

I. H.T. CABLE & VACUUM CIRCUIT BREAKERS

1.0 H.T. CABLE

Supply of following sizes 11KV XLPE aluminium conductorarmoured cable conforming to IS : 7098 complete as perspecification and as required.

i) 3 Core, 240 sq.mm 30 M 1,620.00 48,600.00 (MR)

ii) 3 Core, 400 sq.mm 1300 M 2,270.00 2,951,000.00 (MR)

2.0 Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 11KV grade of following sizes direct in groundincluding excavation, sand cushioning, protective covering andrefilling the trench etc. as required.

8.1(DSR-2013)

i) Above 120sqmm and upto 400 sqmm. 1250 M 256.00 320,000.00 8.1.2

3.0 Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 11 KV grade of following size in the existingRCC/HUME/ METAL pipe as required.

8.3(DSR-2013)

i) Above 120sqmm and upto 400 sqmm. 50 M 53.00 2,650.00 8.3.2

4.0 Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 11 KV grade of following size in the existingmasonry open duct as required.

8.4(DSR-2013)

i) Above 120sqmm and upto 400 sqmm. 30 M 45.00 1,350.00 8.4.2

DSR -2013 / MR

TENDER FOR SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 11/0.433KV INDOOR/OUTDOOR ELECTRIC SUBSTATION AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K)

SECTION - A: ABSTRACT COST FOR POWER SUPPLY PACKAGE FOR SUBSTATION - I

(POWER SUPPLY PACKAGE & EXTERNAL ELECTRICAL WORKS)

Item No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

Page 6: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

5.0 Supplying and making indoor cable end termination with heatshrinkable jointing kit complete with all accessories including lugssuitable for following size of 3 core, XLPE aluminium conductorcable of 11 KV grade as required :

10.4(DSR-2013)

i) 240 sq.mm 4 Set 7,007.00 28,028.00 10.4.3

ii) 400 sq.mm 2 Set 11,678.00 23,356.00 DR/DSR

6.0 11 KV H.T. FOUR (4) BREAKER SWITCHBOARD PANEL(SUBSTATION - 1)

Supplying, installation, testing & commissioning of indoor type floormounted metal clad, 11KV VCB panel with 4 No. VCBs, totallyenclosed and fully interlocked, horizontal drawout, horizontal /vertical isolation type breaker as per IS 13118, as amended up todate and additional specifications, having capacities as mentionedbelow, single break, trip free mechanism, motorised / manuallycharged and auto / manually closing breaker suitable for use on 11KV, 3 Phase, 50Hz A.C. supply with short circuit fault level of 350MVA, complete with self contained, fully interlocked, rack in andrack out mechanism, air insulated but encapsulated copper bus barsof 800 Amps capacity, breaker featured with mechanical ON/OFFindicator with hand trip device, spring release coil, shunt trip coiland auxiliary switch of 4 NO+4NC and equipped with followingswitchgears and accessories i/c connections suitable for 3 core 400sq.mm XLPE 11KV cable (cable entry from bottom / top / side), endtermination with heat shrinkable jointing material etc. and completeas per specification as required. (Note :- Cost of end termination notincluded in this item) (TOTAL OF A & B)

1 Set 2,037,000.00 2,037,000.00 (MR)

Page 7: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

A) INCOMING PANEL - 2 NO. (EACH CONSISTING OFFOLLOWING)

i) 1 No. 350 MVA, 630Amp 11KV, Vacuum Circuit Breaker withmotorised spring charged and manual closing mechanism. Shunt tripcoil shall operate in 110V DC voltage derived through a power pack.

ii) 3 No. Single Phase double core double ratio current transformer300/150/5/5Amp epoxy cast insulated class of insulation E.

Core 1-15VA burden class 0.5 for metering.

Core 2-15VA burden class 5P10 for protection.

iii) 3 Nos. Line PT 11KV/ √3, 110V/ √3, 100VA burden of class 0.5epoxy cast resin type with 1 No. voltmeter (0-15KV), analog / digitaltype, selector switch with voltmeter & protection mcb for H.T.Metering upto 12KV on incomer.

iv) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/Fprotection. (over load setting 20-200% and E/F setting 5-80%).

v) 1 No. Anti Pumping device.

vi) 1No.Circuit breaker control switch for electrical (T/N/C).

vii) 1No. limit switch for test & service position.

viii) 1 No. digital type Ammeter (0-300Amp) (96mm square) withselector switch.

ix) 1 No. electronic type digital energy analyser having minimum 30days memory and parameters of voltage, current, frequency, KW,KVA, KVAr, PF Power factor etc. shall be suitable for BMSoperation with 485 port MODBUS output protocol.

x) 1 Set of following indicating lamps.

- Red, Yellow & Blue for phase indication.

Page 8: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

- Amber for Trip indication.

- Red `ON' Green `OFF'

- Spring charge indication.

- Auto trip indication.

xi) 1 No. Power pack for trip coil operation.

xii) 1 No. control Transformer of 11KV/415-230Volts AC of 1KVAcapacity for auxillary supply for breaker closing coil, indicatinglamps, space heaters etc. control transformer shall be epoxy castresin dry type and the connection for control transformer shall betaken from the cable side before the circuit breaker tapping.

xiii) 1 No. hooter.

xiv) 1 No. master trip relay.

xv) 1 No. over voltage relay.

xvi) 1 Set of fuses, ferrules, wiring etc. as required.

xvii) Brass gland suitable for 1 No. 3 core 400Sq.mm. 11KV XLPEaluminium armoured cable.

B) OUTGOING PANEL - 2 NOS. (EACH CONSISTING OFFOLLOWING)

i) 1 No. 350MVA, 630Amp 11KV, Vacuum Circuit Breaker withmotorised spring charged and manual closing mechanism. Shunt tripcoil shall operate on 110V DC voltage derived through a powerpack.

ii) 3 No. Single Phase double core current transformer 50/5 Amp epoxycast insulated class of insulation E.

- Core 1-15VA burden class-1.0 for metering.

- Core 2-15VA burden class 5P10 for protection.

Page 9: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

iii) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/Fprotection. (Relay shall be for highset instantaneous protection forover current & earth fault).

iv) 1 No. Anti Pumping device.

v) 1 No. Auxiliary relay (VAA33) for transformer fault, alarm and tripsuitable for 230 V AC Supply.

vi) 1 No. Circuit breaker control switch for electrical (T/N/C).

vii) 1 No. limit switch for test & service position.

viii) 1 No. digital type Ammeter of range 0-50 Amp (96mm Square).

ix) 1 Set of following indicating lamps (LED Type).

- Red, Yellow & Blue for phase indication.

- Red 'ON' Green 'OFF'.

- Amber for trip indication.

- Spring charge indication.

- Auto trip indication.

x) 1 Set of fuses, ferrules, wiring etc. as required.

xi) 1 No. hooter.

xii) 1 No. master trip relay.

xiii) 1 No. power pack for trip coil operation.

xiv) Brass gland suitable for 1 No. 3 core 240sq.mm 11KV XLPEaluminium armoured cable.

- All metering and protection devices, interconnections, necessarycontrol wiring and all other accessories shall be provided as perspecifications, technical requirement of local electric supplyauthority.

TOTAL OF SUBHEAD I - HT CABLE & VACUUMCIRCUIT BREAKER CARRIED OVER TO THESUMMARY.

375,384.00 5,036,600.00

Page 10: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

II. DISTRIBUTION TRANSFORMER & BUS TRUNKING

1.0 DISTRIBUTION TRANSFORMER (OIL TYPE) (OLTCTYPE)

Supply, installation, testing & commissioning of 800 KVA11KV/433V, 3 phase 50 Hz outdoor copper wound oil typedistribution transformer with OLTC (On Load Tap Changer) withAVR and RTCC Panel. Vector group Dyn-11 ONAN cooled havingcable end box suitable for 3 core 240 sq.mm XLPE Aluminiumconductor 11KV cable on HV & multicore aluminium XLPE cableon L.T. side with all fittings & accessories, bucholtz relayalarm & trip, WTI alarm & trip and oil temperature alarm &trip control wiring, all civil work including foundation etc.complete as per specifications & conforming to IS 2026-1977and complying with specification and requirement of local electricsupply authority. 2 No. 1,557,000.00 3,114,000.00 (MR)

2.0 BUS TRUNKING

Supply, installation, testing & commissioning of following capacity /rating prefabricated Air insulated bus trunking / Bus Duct suitablefor 415 volts 3 phase, 4 wire 50Hz AC supply system (BetweenTransformer L.T. side and incomer of L.T. Panel side) of aluminiumbusbars complete with bends, expansion joints, fire barriers, copperfexible end connection at both ends, Earthing with 2 runs of copper /aluminium earth of size 25mm x 5mm strip etc. including necessarysupport etc. as per specification and as required.

3.5(DSR-2013)

a) Bus Trunking

i) 1250 Amp 27 M 12,235.00 330,345.00 3.5.3

Page 11: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

b) Copper Flexible for Bus Trunking (Average length 320mm)

i) 1250 Amp 4 Set 35,000.00 140,000.00 (MR)

(Note: The bus trunking shall be measured along the length ofenclosure. The aluminium/ copper strips which will go inside LTpanels & end termination box of transformers shall not be taken into measurement of bus trunking quantity).

TOTAL OF SUBHEAD II - DISTRIBUTIONTRANSFORMER & BUS TRUNKING CARRIED OVER TOSUMMARY.

330,345.00 3,254,000.00

Page 12: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

III. DG SETS & ACCESSORIES

1.0 Supply, installation, testing and commissioning of 200 KVA, 415Volt, 3 phase, 1500 R.P.M, 0.8 PF radiator with fan cooled, floormounted Diesel Generator set complete with Alternator of 200 KVA,415 Volt AC. Engine Coupled to Alternator housed in acousticenclosure conforming to latest environment protection regulationsfor emmission and noise levels complete with Diesel Enginedeveloping either 246 BHP at 1500 RPM or actual BHP calculatedconsidering de-rating factor if any whichever is higher Alternatorand all accessories including supply and installation of Enginecontrol panel with meters, CTs and transducers for all metering andprotection, AMF Panel suitable for auto start / stop of DG Set, Autochangeover of gird and DG supply, interlocking with requiredswitchgear, contactor (AC3 duty), Instrument, relay, timer etc.complete, antivibration mountings, hospital type silencer, flexiblepipe connections, exhaust piping with bends etc. (6 metre length)including 80mm thick glass wool insulation with aluminiumcladding 26 guage aluminium sheets, electric starter, batteries &battery charger, fuel tank of 990 ltrs.capacity with level indicator,radiator, control wiring, first fill of lubricating oil, and Diesel fortesting and commissioning and all spares and accessories as requiredcomplete with necessary civil work such as grouting, chipping,finishing etc.as required complete including foundation (Foundationto be paid and measured under separate item) (Foundation to be done by the Contractor based on DG Set manufacturer Shop Drawing).The work should be as per Central Electrical Inspectorate/ Pollutioncontrol board standards. (Refer Technical Specification)

1 No. 1,867,000.00 1,867,000.00 (MR)

Page 13: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

2.0 Supply, installation, testing and commissioning of 250 KVA, 415Volt, 3 phase, 1500 R.P.M, 0.8 PF water cooled, radiator type floormounted Diesel Generator set complete with Alternator of 250 KVA,415 Volt AC. Engine Coupled to Alternator housed in acousticenclosure conforming to latest environment protection regulationsfor emmission and noise levels complete with Diesel Enginedeveloping either 310 BHP at 1500 RPM or actual BHP calculatedconsidering de-rating factor if any whichever is higher alternatorconsidering de-rating factor if any whichever is higher alternator andall accessories including supply and installation of Engine controlpanel with meters, CTs and transducers for all metering andprotection, AMF Panel suitable for auto start / stop of DG Set, Autochangeover of gird and DG supply interlocking with requiredswitchgear, contactor (AC3 duty), Instrument, relay, timer etc.complete, antivibration mountings, hospital type silencer, flexiblepipe connections, exhaust piping with bends etc. (6 metre length)including 80mm thick glass wool insulation with aluminiumcladding 26 guage aluminium sheet, electric starter, batteries &battery charger, fuel tank of 990 ltrs. capacity with level indicator,radiator, control wiring, first fill of lubricating oil, and Diesel fortesting and commissioning and all spares and accessories as requiredcomplete with necessary civil work such as grouting, chipping,finishing etc.as required complete including foundation (Foundationto be paid and measured under separate item) (Foundation to be done by the Contractor based on DG Set manufacturer Shop Drawing).The work should be as per Central Electrical Inspectorate/ Pollutioncontrol board standards. (Refer Technical Specification)

1 No. 2,211,000.00 2,211,000.00 (MR)

TOTAL OF SUBHEAD III - DG SETS & ACCESSORIESCARRIED OVER TO THE SUMMARY. 0.00 4,078,000.00

Page 14: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

IV. MAIN L.T. PANELS, CAPACITOR BANK PANELS & SUB-DISTRIBUTION BOARDS

1.0 MAIN L.T. PANEL (NORMAL SUPPLY) (SS1/MLTP)

Supply, installation, testing & commissioning of Main L.T. Panelextensible type suitable for 415 volts (nominal) 3 phase 4 wire, 50Hz, A.C. Supply totally enclosed type with free standing floormounted dust and vermin proof compartmentalised indoor typefabricated from 2mm thick CRCA sheet steel complete with busbars,ammeter, ammeter selector switch, voltmeter, voltmeter selectorswitch, indicating lamps, protection relays, CT's, protection fuses,interconnections with suitable size of copper leads/solid aluminiumstrips/rod and having following incoming and outgoing Air CircuitBreakers, MCCB's as per the drawing and technical specificationscomplete as required. (TOTAL OF A TO D) 1 Set 1,825,000.00 1,825,000.00 (MR)

A) INCOMER BREAKERS

● 2 Nos. 1250Amp FP Manually operated horizontal drawout type(MDO) Air Circuit Breaker (50KA) with microprocessorrelease,O/L, S/C & E/F protection with communication port RS485port (Transformer Incomer).

B) BUSCOUPLER BREAKERS

● 1 No. 1250Amp FP Manually operated horizontal drawout type(MDO) Air Circuit Breaker (50KA) as buscoupler with interlockingarrangement with incomers ACB.

● 1 Set of indicating lamps for ON & OFF of buscoupler.

C) BUSBARS

● 1600 Amp TPN busbars of aluminium alloy (Bus-Section I & II).

Page 15: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

D) OUTGOING BREAKERS WITH INSTRUMENTS

● 6 Nos. 800 Amp Three Pole Manually operated horizontal drawouttype (MDO) Air Circuit Breaker (50KA) with thermal magneticrelease, with O/L, S/C & E/F protection & neutral link.

● 4 Nos. 630 Amp Three Pole Moulded Case Circuit Breaker (35KAIcs Value) with microprocessor release for O/L, S/C & E/Fprotection & neutral link.

● 2 No. 400 Amp Three Pole Moulded Case Circuit Breaker (35KAIcs Value) with microprocessor release for O/L, S/C & E/Fprotection & neutral link.

E) INSTRUMENTS & RELAYS ON INCOMER BREAKERS

● 2 Nos. 0 to 500 Volt digital voltmeter with selector switch (96mmsquare) (one for each incoming breaker).

● 2 Nos. 0 to 1250 Amp digital ammeter (96mm square) with CT's(one for each incoming breaker) and selector switch.

● 2 Sets of phase indicating lights (RYB) with protection mcb's (oneset for each incoming breaker).

● 2 Sets breaker 'ON' & 'OFF' indicating lamp (one set for eachincoming breaker).

● 2 Sets trip circuit healthy indicating lamp (one set for each incomingbreaker).

● 2 Sets auto trip indicating lamp (one set for each incoming breaker).

● 2 Nos. of Dual ratio CT's of 1250/300/5/5Amp ratio each for APFCRelay (one for each incoming breaker).

● 2 Nos. trip circuit supervision relay (one for each incoming breaker).

Page 16: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

● 2 Nos. electronic type Digital energy analyser having 30 daymemory and parameters of KW, KWH, power factor, frequency etc.(one for each incoming breaker).

● 2 Nos. Phase squence relay (one for each incoming breaker). ● 2 Nos. master trip relay (one for each incoming breaker). ● 2 Set of O/V & U/V relay (one for each incoming breaker).

2.0 CAPACITOR BANK PANEL (200 KVAR) Supply, installation, testing & commissioning of Capacitor Panelsuitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz, A.C. Supplytotally enclosed type with free standing floor mounted dust andvermin proof indoor type fabricated from 2mm thick CRCA sheetsteel complete with busbars, ammeter, ammeter selector switch,voltmeter, voltmeter selector switch, indicating lamps, protectionrelays, CT's protection fuses, interconnections with suitable size ofcopper leads/solid aluminium strips/rod auto / manual selectorswitch for operation of capacitor units, push buttons for manualoperation capacitor duty, contractors capacitor bank, APFC relay,power factor meter etc. complete and having following incoming andoutgoing Circuit Breakers etc. as per the drawing and specificationscomplete as required. (TOTAL OF A TO C)

2 Set 351,000.00 702,000.00

A) INCOMER ● 1 No. 630 Amp FP Moulded Case Circuit Breaker (35KA Ics Value)

with microprocessor release for O/L, S/C & E/F protection. ● 1 No. 0-630A. Ammeter with selector switch & CT's. ● 1 No. 0-500A. Voltmeter with selector switch.

● 1 Set of phase indicating lamps

Page 17: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

B) BUSBARS

● 700A TPN Aluminium busbars

C) OUTGOING

● 14 stepped Automatic Power Factor Correction relay (APFC relay).

● 4 Nos. 63 Amp TP Moulded Case Circuit Breaker (25KA Ics Value)with neutral link.

● 10 Nos. 32 Amp TP Moulded Case Circuit Breaker (25KA IcsValue) with neutral link.

● 14 Nos. Capacitor duty contactor (one for each 25KVAR /10KVAR) Capacitor unit.

● 4 Nos. 25 KVAR Capacitor Bank.

● 10 Nos. 10 KVAR Capacitor Bank.

● 14 sets of push button stations Red and Green for manual operationof capacitor units with auto/manual selector switches.

● 1 No. Indicating lamp for each 25 KVAR / 10 KVAR capacitor unitto indicate that the unit is 'ON'.

● 1 No. Toggle switch for changing automatic to manual operation ofcapacitor units.

● 1 No. Power factor meter.

3.0 MAIN L.T. PANEL (ESSENTIAL SUPPLY) (SS1/EMLTP)

Supply, installation, testing & commissioning of Main L.T. Panel(Essential Supply) extensible type suitable for 415 volts (nominal) 3phase 4 wire, 50 Hz, A.C. Supply totally enclosed type with freestanding floor mounted dust and vermin proof compartmentalisedindoor type fabricated from 2mm thick CRCA sheet steel completewith busbars, ammeter, ammeter selector switch, voltmeter,

Page 18: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

voltmeter selector switch, indicating lamps, protection relays, CT'sprotection fuses, interconnections with suitable size of copperleads/solid aluminium strips/rod. PLC shall be provided formonitering power supply on various bus section and closing /opening of incomer & bus coupler breakers and interlocking ofincomer and bus coupler breakers and having following incomingand outgoing Air Circuit Breakers, MCCB's as per the drawing andtechnical specifications complete as required. (TOTAL OF A TO E)

1 Set 679,000.00 679,000.00 (MR)

A) INCOMER BREAKERS

● 2 Nos. 400Amp FP Moulded Case Circuit Breaker (35KA IcsValue) with microprocessor release for O/L, S/C & E/F protection.

● 2 Nos. 400Amp FP contactor (AC 3 Duty) with timer switch.

B) AUTO OPERATION OF INCOMER / BUSCOUPLER ACB's.

i) Load management through Micro PLC shall be provided to achievethe following functions.

ii) Auto changeover between incomer breakers.

iii) Buscoupler switching.

iv) Signal to AMF Panel for status of 'Load' to ensure auto stop / autostart of DG Set by AMF Panel.

v) Interlocking of incomer and bus coupler breakers.

vi) Necessary hardware shall be provided to achieve above functionsincluding micro PLC with real time clock, digital inputs / outputs,MMI with 2 line display, power supply, auxillary relays, pushbuttons, LED indication lamp, window announciation facia etc. &software for the above. All items required for complete operationwhether or not list in BOQ shall deemed to be included in quotedrates.

Page 19: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

vii) Automatic system shall be user friendly and shall have manual override.

C) BUSCOUPLER BREAKERS

- 1 No. 400Amp FP Contactor as buscoupler.

- 1 Set of indicating lamps for ON & OFF of buscoupler.

D) BUSBARS

i) 600 Amp TPN busbars of aluminium alloy in Bus Section - I & II.

E) OUTGOING BREAKERS WITH INSTRUMENTS

i) 2 Nos. 250 Amp Three Pole Moulded Case Circuit Breaker (35KAIcs Value) with microprocessor release for O/L, S/C & E/Fprotection and neutral link.

ii) 2 Nos. 200 Amp Three Pole Moulded Case Circuit Breaker (35KAIcs Value) with thermal magnetic release, O/L, S/C & E/F protectionand neutral link.

iii) 2 Nos. 125 Amp Three Pole Moulded Case Circuit Breaker (35KAIcs Value) with thermal magnetic release, O/L, S/C & E/F protectionand neutral link.

iv) 2 Nos. 63 Amp Three Pole Moulded Case Circuit Breaker (25KAIcs Value) with thermal magnetic release, O/L, S/C & E/F protectionand neutral link.

F) INSTRUMENTS ON INCOMER BREAKERS

i) 2 Nos. 0 to 500 Volt digital voltmeter with selector switch (96mmsquare) (one for each incoming breaker).

ii) 2 Nos. 0 to 400 Amp digital ammeter (96mm square) with CT's andselector switch.

iii) 2 Sets of phase indicating lights (RYB) with protection mcb's (oneset for each incoming breaker).

Page 20: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

iv) 2 Sets breaker 'ON' & 'OFF' indicating lamp (one set for eachincoming breaker).

v) 2 Nos. electronic type Digital energy analyser having 30 daymemory and parameters of KW, KWH, power factor, frequency etc.(one for each incoming breaker).

4.0 SDB - DISTRIBUTION BOARDS

Supply, installation, testing & commissioning of cubicle type tollallyenclosure free standing type moistue, dust and vermin proof SubDistribution Boards (SDB) made out of 2mm thick CRCA sheetsteel complete with following equipments, including ammeter,ammeter selector switch, voltmeter, voltmeter selector switch,indicating lamps, CT's internal wiring with suitable size wires /cable, interconnection, pointing etc. as per drawing and specificationcomplete as required.

4.1 ESDB/SS1 (TOTAL OF A TO D) 1 Set 107,000.00 107,000.00 (MR)

A) INCOMING

● 1 No. 125Amp FP Moulded Case Circuit Breaker of (35KA IcsValue) with thermal magnetic release and O/L, S/C & E/Fprotection.

B) INSTRUMENTS

● 1 No. 0 to 500 Volt digital voltmeter (96mm square) with selectorswitch.

● 1 No. 0 to 125 Amp digital ammeter (96mm square) with selectorswitch & CT's.

● 1 Set of phase indicating lights (RYB) with protection MCB.

Page 21: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

C) BUSBARS

● 150Amp TPN busbars of aluminium alloy.

D) OUTGOING

● 2 Nos. 100 Amp TP Moulded Case Circuit Breaker of (25KA IcsValue) with thermal magnetic release, O/L & S/C protection andneutral link.

● 3 Nos. 32-63 Amp TP Moulded Case Circuit Breaker of (25KA IcsValue) with thermal magnetic release, O/L & S/C protection andneutral link.

TOTAL OF SUBHEAD IV - MAIN LT PANELS,CAPACITOR BANK PANELS & SUB-DISTRIBUTIONBOARDS CARRIED OVER TO THE SUMMARY.

0.00 3,313,000.00

Page 22: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

V. LT CABLES

1.0 Supply of following size of 1.1KV grade multicore aluminiumconductor XLPE / PVC insulated & PVC sheathed armoured cableas per IS: 7098 (Part-1) 1988 complete as per specification and asrequired.

i) 3.5 core, 400 Sq.mm. 90 M. 1,844.00 165,960.00 (MR)

ii) 3.5 core, 300 Sq.mm. 2630 M. 1,443.00 3,795,090.00 (MR)

iii) 3.5 core, 150 Sq.mm. 440 M. 759.00 333,960.00 (MR)

iv) 3.5 core, 120 Sq.mm. 50 M. 640.00 32,000.00 (MR)

v) 3.5 core, 50 Sq.mm. 25 M. 303.00 7,575.00 (MR)

vi) 3.5 core, 35 Sq.mm. 480 M. 235.00 112,800.00 (MR)

vii) 4 core, 16 Sq.mm. 770 M. 149.00 114,730.00 (MR)

2.0 Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 1.1 KV grade of following size direct in groundincluding excavation, sand cushioning, protective covering andrefilling the trench etc as required.

7.1(DSR-2013)

i) Upto 35 sq. mm 710 M. 181.00 128,510.00 7.1.1

ii) Above 95 sq. mm and upto 185 sq. mm 250 M. 195.00 48,750.00 7.1.3

iii) Above 185 sq. mm and upto 400 sq. mm 1390 M. 215.00 298,850.00 7.1.4

3.0 Laying of one number additional PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size direct inground in the same trench in one tier horizontal formation includingexcavation, sand cushioning, protective covering and refilling thetrench etc as required.

7.2(DSR-2013)

i) Upto 35 sq. mm 440 M. 124.00 54,560.00 7.2.1

Page 23: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

ii) Above 95 sq. mm and upto 185 sq. mm 180 M. 138.00 24,840.00 7.2.3

iii) Above 185 sq. mm and upto 400 sq. mm 1100 M. 159.00 174,900.00 7.2.4

4.0 Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 1.1 KV grade of following size in the existing RCC/HUME/ METAL pipe as required.

7.5(DSR-2013)

i) Upto 35 sq. mm 40 M. 15.00 600.00 7.5.1

ii) Above 95 sq. mm and upto 185 sq. mm 20 M. 30.00 600.00 7.5.3

iii) Above 185 sq. mm and upto 400 sq. mm 110 M. 53.00 5,830.00 7.5.4

5.0 Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 1.1 KV grade of following size in the existingmasonry open duct as required.

7.6(DSR-2013)

i) Upto 35 sq. mm 30 M. 11.00 330.00 7.6.1

ii) Above 35 sq. mm and upto 95 sq. mm 25 M. 18.00 450.00 7.6.2

iii) Above 95 sq. mm and upto 185 sq. mm 20 M. 25.00 500.00 7.6.3

iv) Above 185 sq. mm and upto 400 sq. mm 60 M. 45.00 2,700.00 7.6.4

6.0 Laying and fixing of one number PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size on wallsurface / cable Tray as required.

7.7(DSR-2013)

i) Upto 35 sq. mm (clamped with 1mm thick saddle) 30 M. 22.00 660.00 7.7.1

ii) Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) 20 M. 77.00 1,540.00 7.7.3

iii) Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) 60 M. 107.00 6,420.00 7.7.4

Page 24: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

7.0 Suppling and making indoor end termination with brass compressiongland and aluminium lugs for following size of PVC insulated andPVC sheathed / XLPE aluminium conductor cable of 1.1 KV gradeas required.

9.1(DSR-2013)

i) 3.5 core, 400 Sq.mm. 10 Set 1,203.00 12,030.00 9.1.31

ii) 3.5 core, 300 Sq.mm. 24 Set 940.00 22,560.00 9.1.30

iii) 3.5 core, 150 Sq.mm. 4 Set 501.00 2,004.00 9.1.26

iv) 3.5 core, 120 Sq.mm. 6 Set 417.00 2,502.00 9.1.25

v) 3.5 core, 50 Sq.mm. 2 Set 286.00 572.00 9.1.22

vi) 3.5 core, 35 Sq.mm. 2 Set 245.00 490.00 9.1.21

vii) 4 core, 16 Sq.mm. 6 Set 208.00 1,248.00 9.1.33

8.0 Supply and installing following size of perforated M.S. cable trayswith perforation not more than 17.5% in convenient sections, jointswith connectors suspended from the ceiling with M.S. suspendersand including bolts & nuts, painting suspenders etc. as perspecification and as required.

4.1(DSR-2013)

i) 150 mm width X 50 mm depth X 1.6 mm thickness 75 M. 523.00 39,225.00 4.1.2

ii) 300 mm width X 50 mm depth X 1.6 mm thickness 75 M. 756.00 56,700.00 4.1.4

TOTAL OF SUBHEAD V - LT CABLES CARRIED OVER TOTHE SUMMARY. 887,371.00 4,562,115.00

Page 25: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR -2013 / MRItem No. / Sub-Head Description Qty. Unit

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR(In Rs.)

Amount as per NON DSR

(In Rs.)

VI. EARTHING

1.0 Earthing with copper earth plate 600 mm X 600 mm X 3 mm thickincluding accessories, and providing masonry enclosure with coverplate having locking arrangement and watering pipe of 2.7 metrelong etc. with charcoal/ coke and salt as required. 8 Set 8,939.00 71,512.00

5.6(DSR-2013)

2.0 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thickincluding accessories, and providing masonry enclosure with coverplate having locking arrangement and watering pipe of 2.7 metrelong etc. with charcoal/ coke and salt as required. 14 Set 4,367.00 61,138.00

5.4(DSR-2013)

3.0 Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I.pipe from earth electrode including connection with brass nut, bolt,spring, washer excavation and re-filling etc. as required. 80 M. 1,019.00 81,520.00

5.10(DSR-2013)

4.0 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I.pipe from earth electrode including connection with G.I. nut, bolt,spring, washer excavation and re-filling etc. as required. 150 M. 391.00 58,650.00

5.11(DSR-2013)

5.0 Providing and fixing 25 mm X 5 mm copper strip on surface or inrecess for connections etc. as required. 40 M. 812.00 32,480.00

5.14(DSR-2013)

6.0 Providing and fixing 25 mm X 5 mm G.I. strip on surface or inrecess for connections etc. as required. 100 M. 133.00 13,300.00

5.15(DSR-2013)

7.0 Providing and fixing 6 SWG dia G.I. wire on surface or in recess forloop earthing as required. 100 M. 34.00 3,400.00

5.16(DSR-2013)

TOTAL OF SUBHEAD VI - EARTHING CARRIED OVERTO THE SUMMARY. 322,000.00 0.00

Page 26: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR-2013 MR TOTAL

I. H.T. CABLE & VACUUM CIRCUIT BREAKERS 3,077,390.00 38,359,100.00 41,436,490.00

II. DISTRIBUTION TRANSFORMER & BUS TRUNKING 183,516.00 25,602,000.00 25,785,516.00

III. DG SETS & ACCESSORIES 0.00 30,062,000.00 30,062,000.00

IV. MAIN L.T. PANELS, CAPACITOR BANK PANELS & SUB-DISTRIBUTION BOARDS 0.00 20,047,000.00 20,047,000.00

V. COMPACT TYPE SUBSTATION & DISTRIBUTION FEEDER PILLARS 0.00 23,998,000.00 23,998,000.00

VI. L.T. CABLES 12,882,860.00 100,429,680.00 113,312,540.00

VII. EARTHING 2354794.00 0.00 2,354,794.00

TOTAL 18,498,560.00 238,497,780.00 256,996,340.00

SAY 256,996,340.00

TENDER FOR SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 11/0.433KV INDOOR/OUTDOOR ELECTRIC SUBSTATION AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE

BAGLA, DISTT. SAMBA (J&K)

SECTION - B: ABSTRACT COST FOR POWER SUPPLY PACKAGE FOR SUBSTATION II TO VI & COMPACT TYPE SUBSTATIONS (CSS 1 TO CSS 10)

(POWER SUPPLY PACKAGE & EXTERNAL ELECTRICAL WORKS)

SUMMARY SHEET

SUB-HEAD SH. DESCRIPTIONESTIMATED COST IN RUPEES

Page 27: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

I. H.T. CABLE & VACUUM CIRCUIT BREAKERS

1.0 H.T. CABLE

Supply of following sizes 11KV XLPE aluminium conductor armouredcable conforming to IS : 7098 complete as per specification and asrequired.

i) 3 Core, 240 sq.mm 150 M 1,620.00 243,000.00 (MR)

ii) 3 Core, 400 sq.mm 12130 M 2,270.00 27,535,100.00 (MR)

2.0 Laying of one number PVC insulated and PVC sheathed / XLPE powercable of 11KV grade of following sizes direct in ground includingexcavation, sand cushioning, protective covering and refilling the trenchetc. as required.

8.1(DSR-2013)

i) Above 120sqmm and upto 400 sqmm. 6500 M 256.00 1,664,000.00 8.1.2

3.0 Laying of one number additional PVC insulated and PVC sheathed /XLPE power cable of 11 KV grade of following size direct in ground inthe same trench in one tier horizontal formation including excavation,sand cushioning, protective covering and refilling the trench etc asrequired.

8.2(DSR-2013)

i) Above 120sqmm and upto 400 sqmm. 4200 M 182.00 764,400.00 8.2.2

4.0 Laying of one number PVC insulated and PVC sheathed / XLPE powercable of 11 KV grade of following size in the existing RCC/HUME/METAL pipe as required.

8.3(DSR-2013)

i) Above 120sqmm and upto 400 sqmm. 1000 M 53.00 53,000.00 8.3.2

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

TENDER FOR SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 11/0.433KV INDOOR/OUTDOOR ELECTRIC SUBSTATION AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA

(J&K)

SECTION - B: ABSTRACT COST FOR POWER SUPPLY PACKAGE FOR SUBSTATION II TO VI & COMPACT TYPE SUBSTATIONS (CSS 1 TO CSS 10)

(POWER SUPPLY PACKAGE & EXTERNAL ELECTRICAL WORKS)

Item No. /Sub-Head Description Qty. Unit

Page 28: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

5.0 Laying of one number PVC insulated and PVC sheathed / XLPE powercable of 11 KV grade of following size in the existing masonry openduct as required.

8.4(DSR-2013)

i) Above 120sqmm and upto 400 sqmm. 580 M 45.00 26,100.00 8.4.2

6.0 Supplying and making indoor cable end termination with heat shrinkablejointing kit complete with all accessories including lugs suitable forfollowing size of 3 core, XLPE aluminium conductor cable of 11 KVgrade as required :

10.4(DSR-2013)

i) 240 sq.mm 18 Set 7,007.00 126,126.00 10.4.3

ii) 400 sq.mm 38 Set 11,678.00 443,764.00 DR/DSR

7.0 11 KV H.T. FOUR (4) BREAKER SWITCHBOARD PANEL(SUBSTATION - 2)

Supplying, installation, testing & commissioning of indoor type floormounted metal clad, 11KV VCB panel with 4 No. VCBs, totallyenclosed and fully interlocked, horizontal drawout, horizontal / verticalisolation type breaker as per IS 13118, as amended up to date andadditional specifications, having capacities as mentioned below, singlebreak, trip free mechanism, motorised / manually charged and auto /manually closing breaker suitable for use on 11 KV, 3 Phase, 50Hz A.C.supply with short circuit fault level of 350 MVA, complete with selfcontained, fully interlocked, rack in and rack out mechanism, airinsulated but encapsulated copper bus bars of 800 Amps capacity,breaker featured with mechanical ON/OFF indicator with hand tripdevice, spring release coil, shunt trip coil and auxiliary switch of 4NO+4NC and equipped with following switchgears and accessories i/cconnections suitable for 3 core 400 sq.mm XLPE 11KV cable (cableentry from bottom / top / side), end termination with heat shrinkablejointing material etc. and complete as per specification as required. (Note:- Cost of end termination not included in this item) (TOTAL OF A &B) 1 Set 2,029,000.00 2,029,000.00 (MR)

Page 29: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

A) INCOMING PANEL - 2 NO. (EACH CONSISTING OFFOLLOWING)

i) 1 No. 350 MVA, 630Amp 11KV, Vacuum Circuit Breaker withmotorised spring charged and manual closing mechanism. Shunt tripcoil shall operate in 110V DC voltage derived through a power pack.

ii) 3 No. Single Phase double core double ratio current transformer300/150/5/5Amp epoxy cast insulated class of insulation E.

Core 1-15VA burden class 0.5 for metering.

Core 2-15VA burden class 5P10 for protection.

iii) 3 Nos. Line PT 11KV/ √3, 110V/ √3, 100VA burden of class 0.5 epoxycast resin type with 1 No. voltmeter (0-15KV), analog / digital type,selector switch with voltmeter & protection mcb for H.T. Metering upto12KV on incomer.

iv) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/Fprotection. (over load setting 20-200% and E/F setting 5-80%).

v) 1 No. Anti Pumping device.

vi) 1No.Circuit breaker control switch for electrical (T/N/C).

vii) 1No. limit switch for test & service position.

viii) 1 No. digital type Ammeter (0-300Amp) (96mm square) with selectorswitch.

ix) 1 No. electronic type digital energy analyser having minimum 30 daysmemory and parameters of voltage, current, frequency, KW, KVA,KVAr, PF Power factor etc. shall be suitable for BMS operation with485 port MODBUS output protocol.

x) 1 Set of following indicating lamps.

- Red, Yellow & Blue for phase indication.

Page 30: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

- Amber for Trip indication.

- Red `ON' Green `OFF'

- Spring charge indication.

- Auto trip indication.

xi) 1 No. Power pack for trip coil operation.

xii) 1 No. control Transformer of 11KV/415-230Volts AC of 1KVAcapacity for auxillary supply for breaker closing coil, indicating lamps,space heaters etc. control transformer shall be epoxy cast resin dry typeand the connection for control transformer shall be taken from the cableside before the circuit breaker tapping.

xiii) 1 No. hooter.

xiv) 1 No. master trip relay.

xv) 1 No. over voltage relay.

xvi) 1 Set of fuses, ferrules, wiring etc. as required.

xvii) Brass gland suitable for 1 No. 3 core 400Sq.mm. 11KV XLPEaluminium armoured cable.

B) OUTGOING PANEL - 2 NOS. (EACH CONSISTING OFFOLLOWING)

i) 1 No. 350MVA, 630Amp 11KV, Vacuum Circuit Breaker withmotorised spring charged and manual closing mechanism. Shunt tripcoil shall operate on 110V DC voltage derived through a power pack.

ii) 3 No. Single Phase double core current transformer 90/5 Amp epoxycast insulated class of insulation E.

- Core 1-15VA burden class-1.0 for metering.

- Core 2-15VA burden class 5P10 for protection.

Page 31: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

iii) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/Fprotection. (Relay shall be for highset instantaneous protection for overcurrent & earth fault).

iv) 1 No. Anti Pumping device.

v) 1 No. auxiliary relay (VAA33) for transformer fault, alarm and tripsuitable for 230 V AC Supply.

vi) 1 No. Circuit breaker control switch for electrical (T/N/C).

vii) 1 No. limit switch for test & service position.

viii) 1 No. digital type Ammeter of range 0-100 Amp (96mm Square).

ix) 1 Set of following indicating lamps (LED Type).

- Red, Yellow & Blue for phase indication.

- Red 'ON' Green 'OFF'.

- Amber for trip indication.

- Spring charge indication.

- Auto trip indication.

xi) 1 Set of fuses, ferrules, wiring etc. as required.

xii) 1 No. hooter.

xiii) 1 No. master trip relay.

xiv) 1 No. power pack for trip coil operation.

xv) Brass gland suitable for 1 No. 3 core 240sq.mm 11KV XLPE aluminiumarmoured cable.

- All metering and protection devices, interconnections, necessary controlwiring and all other accessories shall be provided as per specifications,technical requirement of local electic supply authority.

Page 32: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

8.0 11 KV H.T. FIVE (5) BREAKER SWITCHBOARD PANEL(SUBSTATION - 3)

Supplying, installation, testing & commissioning of indoor type floormounted metal clad, 11KV VCB panel with 5 No. VCBs, totallyenclosed and fully interlocked, horizontal drawout, horizontal / verticalisolation type breaker as per IS 13118, as amended up to date andadditional specifications, having capacities as mentioned below, singlebreak, trip free mechanism, motorised / manually charged and auto /manually closing breaker suitable for use on 11 KV, 3 Phase, 50Hz A.C.supply with short circuit fault level of 350 MVA, complete with selfcontained, fully interlocked, rack in and rack out mechanism, airinsulated but encapsulated copper bus bars of 800 Amps capacity,breaker featured with mechanical ON/OFF indicator with hand tripdevice, spring release coil, shunt trip coil and auxiliary switch of 4NO+4NC and equipped with following switchgears and accessories i/cconnections suitable for 3 core 400 sq.mm XLPE 11KV cable (cableentry from bottom / top / side), end termination with heat shrinkablejointing material etc. and complete as per specification as required. (Note:- Cost of end termination not included in this item) (TOTAL OF A &B) 1 Set 2,453,000.00 2,453,000.00 (MR)

A) INCOMING PANEL - 2 NO. (EACH CONSISTING OFFOLLOWING)

i) 1 No. 350 MVA, 630Amp 11KV, Vacuum Circuit Breaker withmotorised spring charged and manual closing mechanism. Shunt tripcoil shall operate in 110V DC voltage derived through a power pack.

ii) 3 No. Single Phase double core double ratio current transformer400/200/5/5Amp epoxy cast insulated class of insulation E.

Core 1-15VA burden class 0.5 for metering.

Core 2-15VA burden class 5P10 for protection.

Page 33: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

iii) 3 Nos. Line PT 11KV/ √3, 110V/ √3, 100VA burden of class 0.5 epoxycast resin type with 1 No. voltmeter (0-15KV), analog / digital type,selector switch with voltmeter & protection mcb for H.T. Metering upto12KV on incomer.

iv) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/Fprotection. (over load setting 20-200% and E/F setting 5-80%).

v) 1 No. Anti Pumping device.

vi) 1No.Circuit breaker control switch for electrical (T/N/C).

vii) 1No. limit switch for test & service position.

viii) 1 No. digital type Ammeter (0-400Amp) (96mm square) with selectorswitch.

ix) 1 No. electronic type digital energy analyser having minimum 30 daysmemory and parameters of voltage, current, frequency, KW, KVA,KVAr, PF Power factor etc. shall be suitable for BMS operation with485 port MODBUS output protocol.

x) 1 Set of following indicating lamps.

- Red, Yellow & Blue for phase indication.

- Amber for Trip indication.

- Red `ON' Green `OFF'

- Spring charge indication.

- Auto trip indication.

xi) 1 No. Power pack for trip coil operation.

xii) 1 No. control Transformer of 11KV/415-230Volts AC of 1KVAcapacity for auxillary supply for breaker closing coil, indicating lamps,space heaters etc. control transformer shall be epoxy cast resin dry typeand the connection for control transformer shall be taken from the cableside before the circuit breaker tapping.

Page 34: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

xiii) 1 No. hooter.

xiv) 1 No. master trip relay.

xv) 1 No. over voltage relay.

xvi) 1 Set of fuses, ferrules, wiring etc. as required.

xvii) Brass gland suitable for 1 No. 3 core 400Sq.mm. 11KV XLPEaluminium armoured cable.

B) OUTGOING PANEL - 3 NOS. (EACH CONSISTING OFFOLLOWING)

i) 1 No. 350MVA, 630Amp 11KV, Vacuum Circuit Breaker withmotorised spring charged and manual closing mechanism. Shunt tripcoil shall operate on 110V DC voltage derived through a power pack.

ii) 3 No. Single Phase double core current transformer 90/5 Amp epoxycast insulated class of insulation E.

- Core 1-15VA burden class-1.0 for metering.

- Core 2-15VA burden class 5P10 for protection.

iii) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/Fprotection. (Relay shall be for highset instantaneous protection for overcurrent & earth fault).

iv) 1 No. Anti Pumping device.

v) 1 No. auxiliary relay (VAA33) for transformer fault, alarm and tripsuitable for 230 V AC Supply.

vi) 1 No. Circuit breaker control switch for electrical (T/N/C).

vii) 1 No. limit switch for test & service position.

viii) 1 No. digital type Ammeter of range 0-100 Amp (96mm Square).

ix) 1 Set of following indicating lamps (LED Type).

Page 35: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

- Red, Yellow & Blue for phase indication.

- Red 'ON' Green 'OFF'.

- Amber for trip indication.

- Spring charge indication.

- Auto trip indication.

xi) 1 Set of fuses, ferrules, wiring etc. as required.

xii) 1 No. hooter.

xiii) 1 No. master trip relay.

xiv) 1 No. power pack for trip coil operation.

xv) Brass gland suitable for 1 No. 3 core 240sq.mm 11KV XLPE aluminiumarmoured cable.

- All metering and protection devices, interconnections, necessary controlwiring and all other accessories shall be provided specifications,technical requirement of local electic supply authority.

9.0 11 KV H.T. FOUR (4) BREAKER SWITCHBOARD PANEL(SUBSTATION - 4)

Supplying, installation, testing & commissioning of indoor type floormounted metal clad, 11KV VCB panel with 4 No. VCBs, totallyenclosed and fully interlocked, horizontal drawout, horizontal / verticalisolation type breaker as per IS 13118, as amended up to date andadditional specifications, having capacities as mentioned below, singlebreak, trip free mechanism, motorised / manually charged and auto /manually closing breaker suitable for use on 11 KV, 3 Phase, 50Hz A.C.supply with short circuit fault level of 350 MVA, complete with selfcontained, fully interlocked, rack in and rack out mechanism, airinsulated but encapsulated copper bus bars of 800 Amps capacity,breaker featured with mechanical ON/OFF indicator with hand trip

Page 36: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

device, spring release coil, shunt trip coil and auxiliary switch of 4NO+4NC and equipped with following switchgears and accessories i/cconnections suitable for 3 core 400 sq.mm XLPE 11KV cable (cableentry from bottom / top / side) end termination with heat shrinkablejointing material etc. complete as per specification and as required. (Note:- Cost of end termination not included in this item) (TOTAL OF A &B) 1 Set 2,033,000.00 2,033,000.00 (MR)

A) INCOMING PANEL - 2 NO. (EACH CONSISTING OFFOLLOWING)

i) 1 No. 350 MVA, 630Amp 11KV, Vacuum Circuit Breaker withmotorised spring charged and manual closing mechanism. Shunt tripcoil shall operate in 110V DC voltage derived through a power pack.

ii) 3 No. Single Phase double core double ratio current transformer400/200/5/5Amp epoxy cast insulated class of insulation E.

Core 1-15VA burden class 0.5 for metering.

Core 2-15VA burden class 5P10 for protection.

iii) 3 Nos. Line PT 11KV/ √3, 110V/ √3, 100VA burden of class 0.5 epoxycast resin type with 1 No. voltmeter (0-15KV), analog / digital type,selector switch with voltmeter & protection mcb for H.T. Metering upto12KV on incomer.

iv) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/Fprotection. (over load setting 20-200% and E/F setting 5-80%).

v) 1 No. Anti Pumping device.

vi) 1No.Circuit breaker control switch for electrical (T/N/C).

vii) 1No. limit switch for test & service position.

viii) 1 No. digital type Ammeter (0-400Amp) (96mm square) with selectorswitch.

Page 37: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

ix) 1 No. electronic type digital energy analyser having minimum 30 daysmemory and parameters of voltage, current, frequency, KW, KVA,KVAr, PF Power factor etc. shall be suitable for BMS operation with485 port MODBUS output protocol.

x) 1 Set of following indicating lamps.

- Red, Yellow & Blue for phase indication.

- Amber for Trip indication.

- Red `ON' Green `OFF'

- Spring charge indication.

- Auto trip indication.

xi) 1 No. Power pack for trip coil operation.

xii) 1 No. control Transformer of 11KV/415-230Volts AC of 1KVAcapacity for auxillary supply for breaker closing coil, indicating lamps,space heaters etc. control transformer shall be epoxy cast resin dry typeand the connection for control transformer shall be taken from the cableside before the circuit breaker tapping.

xiii) 1 No. hooter.

xiv) 1 No. master trip relay.

xv) 1 No. over voltage relay.

xvi) 1 Set of fuses, ferrules, wiring etc. as required.

xvii) Brass gland suitable for 1 No. 3 core 400Sq.mm. 11KV XLPEaluminium armoured cable.

B) OUTGOING PANEL - 2 NOS. (EACH CONSISTING OFFOLLOWING)

i) 1 No. 350MVA, 630Amp 11KV, Vacuum Circuit Breaker withmotorised spring charged and manual closing mechanism. Shunt tripcoil shall operate on 110V DC voltage derived through a power pack.

Page 38: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

ii) 3 No. Single Phase double core current transformer 90/5 Amp epoxycast insulated class of insulation E.

- Core 1-15VA burden class-1.0 for metering.

- Core 2-15VA burden class 5P10 for protection.

iii) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/Fprotection. (Relay shall be for highset instantaneous protection for overcurrent & earth fault).

iv) 1 No. Anti Pumping device.

v) 1 No. auxiliary relay (VAA33) for transformer fault, alarm and tripsuitable for 230 V AC Supply.

vi) 1 No. Circuit breaker control switch for electrical (T/N/C).

vii) 1 No. limit switch for test & service position.

viii) 1 No. digital type Ammeter of range 0-100 Amp (96mm Square).

ix) 1 Set of following indicating lamps (LED Type).

- Red, Yellow & Blue for phase indication.

- Red 'ON' Green 'OFF'.

- Amber for trip indication.

- Spring charge indication.

- Auto trip indication.

xi) 1 Set of fuses, ferrules, wiring etc. as required.

xii) 1 No. hooter.

xiii) 1 No. master trip relay.

xiv) 1 No. power pack for trip coil operation.

xv) Brass gland suitable for 1 No. 3 core 240sq.mm 11KV XLPE aluminiumarmoured cable.

Page 39: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

- All metering and protection devices, interconnections, necessary controlwiring and all other accessories shall be provided as per specifications,technical requirement of local electric supply authority.

10.0 11 KV H.T. FOUR (4) BREAKER SWITCHBOARD PANEL(SUBSTATION - 5)

Supplying, installation, testing & commissioning of indoor type floormounted metal clad, 11KV VCB panel with 4 No. VCBs, totallyenclosed and fully interlocked, horizontal drawout, horizontal / verticalisolation type breaker as per IS 13118, as amended up to date andadditional specifications, having capacities as mentioned below, singlebreak, trip free mechanism, motorised / manually charged and auto /manually closing breaker suitable for use on 11 KV, 3 Phase, 50Hz A.C.supply with short circuit fault level of 350 MVA, complete with selfcontained, fully interlocked, rack in and rack out mechanism, airinsulated but encapsulated copper bus bars of 800 Amps capacity,breaker featured with mechanical ON/OFF indicator with hand tripdevice, spring release coil, shunt trip coil and auxiliary switch of 4NO+4NC and equipped with following switchgears and accessories i/cconnections suitable for 3 core 400 sq.mm XLPE 11KV cable (cableentry from bottom / top / side) end termination with heat shrinkablejointiing material etc. and complete as per specification as required.(Note :- Cost of end termination not included in this item) (TOTAL OFA & B 1 Set 2,033,000.00 2,033,000.00 (MR)

A) INCOMING PANEL - 2 NO. (EACH CONSISTING OFFOLLOWING)

i) 1 No. 350 MVA, 630Amp 11KV, Vacuum Circuit Breaker withmotorised spring charged and manual closing mechanism. Shunt tripcoil shall operate in 110V DC voltage derived through a power pack.

ii) 3 No. Single Phase double core double ratio current transformer400/200/5/5Amp epoxy cast insulated class of insulation E.

Page 40: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

Core 1-15VA burden class 0.5 for metering.

Core 2-15VA burden class 5P10 for protection.

iii) 3 Nos. Line PT 11KV/ √3, 110V/ √3, 100VA burden of class 0.5 epoxycast resin type with 1 No. voltmeter (0-15KV), analog / digital type,selector switch with voltmeter & protection mcb for H.T. Metering upto12KV on incomer.

iv) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/Fprotection. (over load setting 20-200% and E/F setting 5-80%).

v) 1 No. Anti Pumping device.

vi) 1No.Circuit breaker control switch for electrical (T/N/C).

vii) 1No. limit switch for test & service position.

viii) 1 No. digital type Ammeter (0-400Amp) (96mm square) with selectorswitch.

ix) 1 No. electronic type digital energy analyser having minimum 30 daysmemory and parameters of voltage, current, frequency, KW, KVA,KVAr, PF Power factor etc. shall be suitable for BMS operation with485 port MODBUS output protocol.

x) 1 Set of following indicating lamps.

- Red, Yellow & Blue for phase indication.

- Amber for Trip indication.

- Red `ON' Green `OFF'

- Spring charge indication.

- Auto trip indication.

xi) 1 No. Power pack for trip coil operation.

Page 41: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

xii) 1 No. control Transformer of 11KV/415-230Volts AC of 1KVAcapacity for auxillary supply for breaker closing coil, indicating lamps,space heaters etc. control transformer shall be epoxy cast resin dry typeand the connection for control transformer shall be taken from the cableside before the circuit breaker tapping.

xiii) 1 No. hooter.

xiv) 1 No. master trip relay.

xv) 1 No. over voltage relay.

xvi) 1 Set of fuses, ferrules, wiring etc. as required.

xvii) Brass gland suitable for 1 No. 3 core 400Sq.mm. 11KV XLPEaluminium armoured cable.

B) OUTGOING PANEL - 2 NOS. (EACH CONSISTING OFFOLLOWING)

i) 1 No. 350MVA, 630Amp 11KV, Vacuum Circuit Breaker withmotorised spring charged and manual closing mechanism. Shunt tripcoil shall operate on 110V DC voltage derived through a power pack.

ii) 3 No. Single Phase double core current transformer 70/5 Amp epoxycast insulated class of insulation E.

- Core 1-15VA burden class-1.0 for metering.

- Core 2-15VA burden class 5P10 for protection.

iii) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/Fprotection. (Relay shall be for highset instantaneous protection for overcurrent & earth fault).

iv) 1 No. Anti Pumping device.

v) 1 No. auxiliary relay (VAA33) for transformer fault, alarm and tripsuitable for 230 V AC Supply.

Page 42: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

vi) 1 No. Circuit breaker control switch for electrical (T/N/C).

vii) 1 No. limit switch for test & service position.

viii) 1 No. digital type Ammeter of range 0-100 Amp (96mm Square).

ix) 1 Set of following indicating lamps (LED Type).

- Red, Yellow & Blue for phase indication.

- Red 'ON' Green 'OFF'.

- Amber for trip indication.

- Spring charge indication.

- Auto trip indication.

xi) 1 Set of fuses, ferrules, wiring etc. as required.

xii) 1 No. hooter.

xiii) 1 No. master trip relay.

xiv) 1 No. power pack for trip coil operation.

xv) Brass gland suitable for 1 No. 3 core 240sq.mm 11KV XLPE aluminiumarmoured cable.

- All metering and protection devices, interconnections, necessary controlwiring and all other accessories shall be provided as per specifications,technical requirement of local electric supply authority.

11.0 11 KV H.T. FOUR (4) BREAKER SWITCHBOARD PANEL(SUBSTATION - 6)

Supplying, installation, testing & commissioning of indoor type floormounted metal clad, 11KV VCB panel with 4 No. VCBs, totallyenclosed and fully interlocked, horizontal drawout, horizontal / verticalisolation type breaker as per IS 13118, as amended up to date andadditional specifications, having capacities as mentioned below,

Page 43: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

single break, trip free mechanism, motorised / manually charged andauto / manually closing breaker suitable for use on 11 KV, 3 Phase,50Hz A.C. supply with short circuit fault level of 350 MVA, completewith self contained, fully interlocked, rack in and rack out mechanism,air insulated but encapsulated copper bus bars of 800 Amps capacity,breaker featured with mechanical ON/OFF indicator with hand tripdevice, spring release coil, shunt trip coil and auxiliary switch of 4NO+4NC and equipped with following switchgears and accessories i/cconnections suitable for 3 core 400 sq.mm XLPE 11KV cable (cableentry from bottom / top / side) end termination with heat shrinkablejointing material etc. complete as per specification and as required. (Note:- Cost of end termination not included in this item) (TOTAL OF A &B) 1 Set 2,033,000.00 2,033,000.00 (MR)

A) INCOMING PANEL - 2 NO. (EACH CONSISTING OFFOLLOWING)

i) 1 No. 350 MVA, 630Amp 11KV, Vacuum Circuit Breaker withmotorised spring charged and manual closing mechanism. Shunt tripcoil shall operate in 110V DC voltage derived through a power pack.

ii) 3 No. Single Phase double core double ratio current transformer400/100/5/5Amp epoxy cast insulated class of insulation E.

Core 1-15VA burden class 0.5 for metering.

Core 2-15VA burden class 5P10 for protection.

iii) 3 Nos. Line PT 11KV/ √3, 110V/ √3, 100VA burden of class 0.5 epoxycast resin type with 1 No. voltmeter (0-15KV), analog / digital type,selector switch with voltmeter & protection mcb for H.T. Metering upto12KV on incomer.

iv) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/Fprotection. (over load setting 20-200% and E/F setting 5-80%).

v) 1 No. Anti Pumping device.

Page 44: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

vi) 1No.Circuit breaker control switch for electrical (T/N/C).

vii) 1No. limit switch for test & service position.

viii) 1 No. digital type Ammeter (0-400Amp) (96mm square) with selectorswitch.

ix) 1 No. electronic type digital energy analyser having minimum 30 daysmemory and parameters of voltage, current, frequency, KW, KVA,KVAr, PF Power factor etc. shall be suitable for BMS operation with485 port MODBUS output protocol.

x) 1 Set of following indicating lamps.

- Red, Yellow & Blue for phase indication.

- Amber for Trip indication.

- Red `ON' Green `OFF'

- Spring charge indication.

- Auto trip indication.

xi) 1 No. Power pack for trip coil operation.

xii) 1 No. control Transformer of 11KV/415-230Volts AC of 1KVAcapacity for auxillary supply for breaker closing coil, indicating lamps,space heaters etc. control transformer shall be epoxy cast resin dry typeand the connection for control transformer shall be taken from the cableside before the circuit breaker tapping.

xiii) 1 No. hooter.

xiv) 1 No. master trip relay.

xv) 1 No. over voltage relay.

xvi) 1 Set of fuses, ferrules, wiring etc. as required.

xvii) Brass gland suitable for 1 No. 3 core 400Sq.mm. 11KV XLPEaluminium armoured cable.

Page 45: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

B) OUTGOING PANEL - 2 NOS. (EACH CONSISTING OFFOLLOWING)

i) 1 No. 350MVA, 630Amp 11KV, Vacuum Circuit Breaker withmotorised spring charged and manual closing mechanism. Shunt tripcoil shall operate on 110V DC voltage derived through a power pack.

ii) 3 No. Single Phase double core current transformer 60/5 Amp epoxycast insulated class of insulation E.

- Core 1-15VA burden class-1.0 for metering.

- Core 2-15VA burden class 5P10 for protection.

iii) 1 No. Microprocessor based Numerical relay with O/L, S/C & E/Fprotection. (Relay shall be for highset instantaneous protection for overcurrent & earth fault).

iv) 1 No. Anti Pumping device.

v) 1 No. auxiliary relay (VAA33) for transformer fault, alarm and tripsuitable for 230 V AC Supply.

vi) 1 No. Circuit breaker control switch for electrical (T/N/C).

vii) 1 No. limit switch for test & service position.

viii) 1 No. digital type Ammeter of range 0-100 Amp (96mm Square).

ix) 1 Set of following indicating lamps (LED Type).

- Red, Yellow & Blue for phase indication.

- Red 'ON' Green 'OFF'.

- Amber for trip indication.

- Spring charge indication.

- Auto trip indication.

xi) 1 Set of fuses, ferrules, wiring etc. as required.

Page 46: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

xii) 1 No. hooter.

xiii) 1 No. master trip relay.

xiv) 1 No. power pack for trip coil operation.

xv) Brass gland suitable for 1 No. 3 core 240sq.mm 11KV XLPE aluminiumarmoured cable.

- All metering and protection devices, interconnections, necessary controlwiring and all other accessories shall be provided as per specifications,technical requirement of local electric supply authority.

TOTAL OF SUBHEAD I - HT CABLE & VACUUM CIRCUITBREAKER CARRIED OVER TO THE SUMMARY. 3,077,390.00 38,359,100.00

Page 47: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

II. DISTRIBUTION TRANSFORMER & BUS TRUNKING

DISTRIBUTION TRANSFORMER (OIL TYPE) (OLTC TYPE)

1.0 Supply, installation, testing & commissioning of 1000 KVA11KV/433V, 3 phase 50 Hz indoor copper wound oil type distributiontransformer with OLTC (On Load Tap Changer) with AVR and RTCCPanel. Vector group Dyn-11 ONAN cooled having cable end boxsuitable for 3 core 240 sq.mm XLPE Aluminium conductor 11KV cableon HV & Aluminium Bus Trunding / Bus Duct on L.T side with allfittings & accessories, bucholtz relay alarm & trip, WTI alarm &trip and oil temperature alarm & trip control wiring, all civil workincluding foundation etc. complete as per specifications &conforming to IS 2026-1977 and complying with specification andrequirement of local electric supply authority. 1 No. 1,799,000.00 1,799,000.00

2.0 Supply, installation, testing & commissioning of 1250 KVA

11KV/433V, 3 phase 50 Hz indoor copper wound oil type distributiontransformer with OLTC (On Load Tap Changer) with AVR and RTCCPanel. Vector group Dyn-11 ONAN cooled having cable end boxsuitable for 3 core 240 sq.mm XLPE Aluminium conductor 11KV cableon HV & Aluminium Bus Trunding / Bus Duct on L.T side with allfittings & accessories, bucholtz relay alarm & trip, WTI alarm &trip and oil temperature alarm & trip control wiring, all civil workincluding foundation etc. complete as per specifications &conforming to IS 2026-1977 and complying with specification andrequirement of local electric supply authority.

1 No. 2,003,000.00 2,003,000.00 (MR)

Page 48: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

3.0 Supply, installation, testing & commissioning of 1600 KVA11KV/433V, 3 phase 50 Hz indoor copper wound oil type distributiontransformer with OLTC (On Load Tap Changer) with AVR and RTCCPanel. Vector group Dyn-11 ONAN cooled having cable end boxsuitable for 3 core 240 sq.mm XLPE Aluminium conductor 11KV cableon HV & Aluminium Bus Trunding / Bus Duct on L.T side with allfittings & accessories, bucholtz relay alarm & trip, WTI alarm &trip and oil temperature alarm & trip control wiring, all civil workincluding foundation etc. complete as per specifications &conforming to IS 2026-1977 and complying with specification andrequirement of local electric supply authority.

7 No. 2,302,000.00 16,114,000.00 (MR)

4.0 BUS TRUNKING

Supply, installation, testing & commissioning of following capacity /rating prefabricated Air insulated bus trunking / Bus Duct suitable for415 volts 3 phase, 4 wire 50Hz AC supply system (BetweenTransformer L.T. side and incomer of L.T. Panel side) of aluminiumbusbars complete with bends, expansion joints, fire barriers, copperfexible end connection at both ends, Earthing with 2 runs of copper /aluminium earth of size 25mm x 5mm strip etc. including necessarysupport etc. as per specification and as required. 3.5

(DSR-2013)

a) Bus Trunking

i) 1600 Amp 12 M 15,293.00 183,516.00 3.5.5

ii) 2000 Amp 12 M 24,000.00 288,000.00 (MR)

iii) 2500 Amp 125 M 32,000.00 4,000,000.00 (MR)

b) Copper Flexible for Bus Trunking (Average length 320mm)

i) 1600 Amp 2 Set 42,000.00 84,000.00 (MR)

ii) 2000 Amp 2 Set 69,000.00 138,000.00 (MR)

iii) 2500 Amp 14 Set 84,000.00 1,176,000.00 (MR)

Page 49: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

(Note: The bus trunking shall be measured along the length ofenclosure. The aluminium/ copper strips which will go inside LTpanels & end termination box of transformers shall not be takeninto measurement of bus trunking quantity).

TOTAL OF SUBHEAD II - DISTRIBUTION TRANSFORMER &BUS TRUNKING CARRIED OVER TO SUMMARY. 183,516.00 25,602,000.00

III. DG SETS & ACCESSORIES

1.0 Supply, installation, testing and commissioning of 200 KVA, 415 Volt,3 phase, 1500 R.P.M, 0.8 PF radiator with fan cooled, floor mountedDiesel Generator set complete with Alternator of 200 KVA, 415 VoltAC. Engine Coupled to Alternator housed in acoustic enclosureconforming to latest environment protection regulations for emmissionand noise levels complete with Diesel Engine developing either 246BHP at 1500 RPM or actual BHP calculated considering de-rating factorif any whichever is higher Alternator and all accessories includingsupply and installation of Engine control panel with meters, CTs andtransducers for all metering and protection, AMF Panel suitable for autostart / stop of DG Set, Auto changeover of gird and DG supply,interlocking with required switchgear, contactor (AC3 duty), Instrument,relay, timer etc. complete, antivibration mountings, hospital typesilencer, flexible pipe connections, exhaust piping with bends etc. (6metre length) including 80mm thick glass wool insulation withaluminium cladding 26 guage aluminium sheets, electric starter, batteries& battery charger, fuel tank of 990 ltrs. capacity with level indicator,radiator, control wiring, first fill of lubricating oil, and Diesel for testingand commissioning and all spares and accessories as required completewith necessary civil work such as grouting, chipping, finishing etc.asrequired complete including foundation (Foundation to be paid andmeasured under separate item) (Foundation to be done by the Contractorbased on DG Set manufacturer Shop Drawing). The work should be asper Central Electrical Inspectorate/ Pollution control board standards.(Refer Technical Specification)

1 No. 1,867,000.00 1,867,000.00 (MR)

Page 50: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

2.0 Supply, installation, testing and commissioning of 250 KVA, 415 Volt,3 phase, 1500 R.P.M, 0.8 PF radiator with fan cooled, floor mountedDiesel Generator set complete with Alternator of 250 KVA, 415 VoltAC. Engine Coupled to Alternator housed in acoustic enclosureconforming to latest environment protection regulations for emmissionand noise levels complete with Diesel Engine developing either 310BHP at 1500 RPM or actual BHP calculated considering de-rating factorif any whichever is higher Alternator and all accessories includingsupply and installation of Engine control panel with meters, CTs andtransducers for all metering and protection, AMF Panel suitable for autostart / stop of DG Set, Auto changeover of gird and DG supply,interlocking with required switchgear, contactor (AC3 duty), Instrument,relay, timer etc. complete, antivibration mountings, hospital typesilencer, flexible pipe connections, exhaust piping with bends etc. (6metre length) including 80mm thick glass wool insulation withaluminium cladding 26 guage aluminium sheets, electric starter, batteries& battery charger, fuel tank of 990 ltrs. capacity with level indicator,radiator, control wiring, first fill of lubricating oil, and Diesel for testingand commissioning and all spares and accessories as required completewith necessary civil work such as grouting, chipping, finishing etc.asrequired complete including foundation (Foundation to be paid andmeasured under separate item) (Foundation to be done by the Contractorbased on DG Set manufacturer Shop Drawing). The work should be asper Central Electrical Inspectorate/ Pollution control board standards.(Refer Technical Specification)

5 No. 2,211,000.00 11,055,000.00 (MR)

Page 51: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

3.0 Supply, installation, testing and commissioning of 380 KVA, 415 Volt,3 phase, 1500 R.P.M, 0.8 PF radiator with fan cooled, floor mountedDiesel Generator set complete with Alternator of 380 KVA, 415 VoltAC. Engine Coupled to Alternator housed in acoustic enclosureconforming to latest environment protection regulations for emmissionand noise levels complete with Diesel Engine developing either 510BHP at 1500 RPM or actual BHP calculated considering de-rating factorif any whichever is higher Alternator and all accessories includingsupply and installation of Engine control panel with meters, CTs andtransducers for all metering and protection, AMF Panel suitable for autostart / stop of DG Set, Auto changeover of gird and DG supply,interlocking with required switchgear, contactor (AC3 duty), Instrument,relay, timer etc. complete, antivibration mountings, hospital typesilencer, flexible pipe connections, exhaust piping with bends etc. (6metre length) including 80mm thick glass wool insulation withaluminium cladding 26 guage aluminium sheets, electric starter, batteries& battery charger, fuel tank of 990 ltrs. capacity with level indicator,radiator, control wiring, first fill of lubricating oil, and Diesel for testingand commissioning and all spares and accessories as required completewith necessary civil work such as grouting, chipping, finishing etc.asrequired complete including foundation (Foundation to be paid andmeasured under separate item) (Foundation to be done by the Contractorbased on DG Set manufacturer Shop Drawing). The work should be asper Central Electrical Inspectorate/ Pollution control board standards.(Refer Technical Specification)

5 No. 3,428,000.00 17,140,000.00 (MR)

TOTAL OF SUBHEAD III - DG SETS & ACCESSORIESCARRIED OVER TO THE SUMMARY. 0.00 30,062,000.00

Page 52: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

IV. MAIN L.T. PANELS, CAPACITOR BANK PANELS & SUB-DISTRIBUTION BOARDS

1.0 MAIN L.T. PANEL (NORMAL SUPPLY) (SS2/MLTP-1)

Supply, installation, testing & commissioning of Main L.T. Panelextensible type suitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz,A.C. Supply totally enclosed type with free standing floor mounted dustand vermin proof compartmentalised indoor type fabricated from 2mmthick CRCA sheet steel complete with busbars, ammeter, ammeterselector switch, voltmeter, voltmeter selector switch, indicating lamps,protection relays, CT's, protection mcb's, interconnections with suitablesize of copper leads/solid aluminium strips/rod having followingincoming and outgoing Air Circuit Breakers, MCCB's as per thedrawing and technical specifications complete as required. (TOTAL OFA TO E) 1 Set 2,586,000.00 2,586,000.00 (MR)

A) INCOMER BREAKERS

● 2 No. 2500Amp FP Manually operated horizontal drawout type (MDO)Air Circuit Breaker (50KA) with microprocessor release, O/L, S/C &E/F protection with communication port RS485 port (TransformerIncomer).

B) BUSCOUPLER BREAKERS

● 1 No. 2500Amp FP Manually operated horizontal drawout type (MDO)Air Circuit Breaker (50KA) as buscoupler with interlocking arrangementwith incomers.

● 1 Set of indicating lamps for ON & OFF of buscoupler.

C) BUSBARS

● 3000 Amp TPN busbars of aluminium alloy (Bus-Section I & II).

Page 53: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

D) OUTGOING BREAKERS WITH INSTRUMENTS

i) 8 Nos. 1250 Amp Three Pole Manually operated horizontal drawouttype (MDO) Air Circuit Breaker (50KA) complete with thermalmagnetic release, O/L, S/C & E/F protection & neutral link.

ii) 2 Nos. 800 Amp Three Pole Manually operated horizontal drawout type(MDO) Air Circuit Breaker with thermal magnetic release, O/L, S/C &E/F protection & neutral link.

iii) 2 Nos. 400 Amp Three Pole Moulded Case Circuit Breaker (50KA)complete with microprocessor release, O/L, S/C & E/F protection &neutral link.

E) INSTRUMENTS ON INCOMER BREAKERS

● 2 Nos. 0 to 500 Volt digital voltmeter with selector switch (96mmsquare) (one for each incoming breaker).

● 2 Nos. 0 to 2500 Amp digital ammeter (96mm square) with CT's (onefor each incoming breaker) and selector switch.

● 2 Sets of phase indicating lights (RYB) with protection mcb's (one setfor each incoming breaker).

● 2 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incomingbreaker).

● 2 Sets trip circuit healthy indicating lamp (one set for each incomingbreaker).

● 2 Sets auto trip indicating lamp (one set for each incoming breaker).

● 2 No. of Dual ratio CT's of 2500/500/5/5Amp ratio for APFC Relay(one for each incomer breaker).

● 2 Nos. trip circuit supervision relay (one for each incoming breaker).

Page 54: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

● 2 Nos. electronic type Digital energy analyser having 30 day memoryand parameters of KW, KWH, power factor, frequency etc. (one for eachincoming breaker).

● 2 Nos. master trip relay (one for each incoming breaker).

● 2 Set of O/V & U/V relay (one for each incoming breaker).

● 2 Nos. Phase squence relay (one for each incoming breaker).

2.0 CAPACITOR BANK PANEL (SS-2)

Supply, installation, testing & commissioning of Capacitor Panelsuitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz, A.C. Supplytotally enclosed type with free standing floor mounted dust and verminproof indoor type fabricated from 2mm thick CRCA sheet steel completewith busbars, ammeter, ammeter selector switch, voltmeter, voltmeterselector switch, indicating lamps, protection relays, CT's protectionfuses, interconnections with suitable size of copper leads/solidaluminium strips/rod, auto / manual selector switch for operation ofcapacitor units, push buttons for manual operation, capacitor dutycontractors, capacitor bank, APFC relay, power factor meter etc.complete and having following incoming and outgoing Circuit Breakersetc. as per the drawing and specifications complete as required.

2.1 Capacitor Bank Panel (400 KVAR) 2 Set 518,000.00 1,036,000.00 (MR)

A) INCOMER

● 1 No. 1250 Amp FP Moulded Case Circuit Breaker (50KA Ics Value)with microprocessor release for O/L, S/C & E/F protection.

● 1 No. 0-1250A. Ammeter with selector switch & CT's.

● 1 No. 0-500A. Voltmeter with selector switch

● 1 Set of phase indicating lamps

Page 55: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

B) BUSBARS

● 1500A TPN Aluminium busbars

C) OUTGOING

● 14 stepped Automatic Power Factor Correction relay (APFC relay).

● 4 Nos. 100 Amp TP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release and neutral link.

● 6 Nos. 63 Amp TP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release and neutral link.

● 4 Nos. 40 Amp TP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release and neutral link.

● 14 Nos. Capacitor duty contactor (one for each 50KVAR /25KVAR/12.5KVAR) Capacitor unit.

● 4 Nos. 12.5 KVAR Capacitor Bank.

● 4 Nos. 50 KVAR Capacitor Bank.

● 6 Nos. 25 KVAR Capacitor Bank.

● 14 Sets of push button stations Red and Green for manual operation ofcapacitor units with auto/manual selector switches.

● 1 No. Indicating lamp for each 50 KVAR / 25 KVAR / 12.5KVARcapacitor unit to indicate that the unit is 'ON'.

● 1 No. Toggle switch for changing automatic to manual operation ofcapacitor units.

● 1 No. Power factor meter.

Page 56: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

3.0 MAIN L.T. PANEL (ESSENTIAL SUPPLY) (SS2/EMLTP-1)

Supply, installation, testing & commissioning of Main L.T. Panel(Essential Supply) extensible type suitable for 415 volts (nominal) 3phase 4 wire, 50 Hz, A.C. Supply totally enclosed type with freestanding floor mounted dust and vermin proof compartmentalised indoortype fabricated from 2mm thick CRCA sheet steel complete withbusbars, ammeter, ammeter selector switch, voltmeter, voltmeter selectorswitch, indicating lamps, protection relays, CT's protection fuses,interconnections with suitable size of copper leads/solid aluminiumstrips/rod . PLC shall be provided for monitering power supply onvarious bus section and closing / opening of incomer & bus couplerbreakers and interlocking, auto / manual selector switch, and havingfollowing incoming and outgoing Air Circuit Breakers, MCCB's as perthe drawing and technical specifications complete as required. (TOTALOF A TO F) 1 Set 634,000.00 634,000.00 (MR)

A) INCOMER BREAKERS

● 1 No. 800Amp FP Electrical operated horizontal drawout type (EDO)Air Circuit Breaker (50KA) with microprocessor release, O/L, S/C &E/F protection.

● 1 No. 400Amp FP Moulded Case Circuit Breaker (35KA Ics Value)with microprocessor release for O/L, S/C & E/F protection.

● 1 No. 400Amp FP contactor (AC 3 Duty) with timer switch.

B) AUTO OPERATION OF INCOMER / BUSCOUPLER ACB's.

● Load management through Micro PLC shall be provided to achieve thefollowing functions.

● Auto changeover closing & opening incomer breakers.

● Buscoupler switching.

Page 57: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

● Signal to AMF Panel for status of load to ensure Auto stop / Auto startof DG Sets by AMF Panel. (Both DG Set)

● Interlocking.

● Necessary hardware shall be provided to achieve above functionsincluding PLC with real time clock, digital inputs / outputs, MMI with 2line display, power supply, auxillary relays, push buttons, LEDindication lamp etc. and software for the above. All items required forcomplete operation whether or not list in BOQ shall deemed to beincluded in quoted rates.

● Automatic system shall be user friendly and shall have manual over ride.

C) BUSCOUPLER BREAKERS

● 1 No. 400Amp FP Contactor (AC 3 Duty) for closing & openingthrough PLC.

● 1 Set of indicating lamps for ON & OFF of buscoupler.

D) BUSBARS

● 1000 Amp TPN busbars of aluminium alloy in Bus Section - I.

● 500 Amp TPN busbars of aluminium alloy in Bus Section - II.

E) OUTGOING BREAKERS WITH INSTRUMENTS

● 2 Nos. 500 Amp Three Pole Moulded Case Circuit Breaker (35KA IcsValue) with microprocessor release for O/L, S/C & E/F protection andneutral link.

● 3 Nos. 250 Amp Three Pole Moulded Case Circuit Breaker (35KA IcsValue) with microprocessor release for O/L, S/C & E/F protection andneutral link.

● 2 Nos. 100 Amp Three Pole Moulded Case Circuit Breaker (25KA IcsValue) with thermal magnetic release for O/L, S/C & E/F protection andneutral link.

Page 58: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

F) INSTRUMENTS ON INCOMER BREAKERS

● 2 Nos. 0 to 500 Volt digital voltmeter with selector switch (96mmsquare) (three for each incoming breaker).

● 1 No. 0 to 800 Amp digital ammeter (96mm square) with CT's (for DGincoming breaker) and selector switch.

● 1 No. 0 to 400 Amp digital ammeter (96mm square) with CT's (for DGincoming breaker) and selector switch.

● 2 Sets of phase indicating lights (RYB) with protection mcb's (one setfor each incoming breaker).

● 2 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incomingbreaker).

● 2 Set trip circuit healthy indicating lamp (for incomer ACB Breaker).

● 2 Set auto trip indicating lamp (for incomer ACB Breaker).

● 2 No. electronic type Digital energy analyser having 30 day memory andparameters of KW, KWH, power factor, frequency etc. (for eachincomer).

● 2 No. master trip relay (for incomer ACB Breaker).

● 2 No. O/V & U/V relay (for incomer ACB Breaker).

● 2 No. of reverse power relay (for incomer ACB Breaker).

4.0 MAIN L.T. PANEL (NORMAL SUPPLY) (SS3/MLTP-1)

Supply, installation, testing & commissioning of Main L.T. Panelextensible type suitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz,A.C. Supply totally enclosed type with free standing floor mounted dustand vermin proof compartmentalised indoor type fabricated from 2mmthick CRCA sheet steel complete with busbars, ammeter, ammeterselector switch, voltmeter, voltmeter selector switch,

Page 59: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

indicating lamps, protection relays, CT's, protection fuses,interconnections with suitable size of copper leads/solid aluminiumstrips/rod and having following incoming and outgoing Air CircuitBreakers, MCCB's as per the drawing and technical specificationscomplete as required. (TOTAL OF A TO E) 1 Set 4,722,000.00 4,722,000.00 (MR)

A) INCOMER BREAKERS

● 3 Nos. 2500Amp FP Manually operated horizontal drawout type (MDO)Air Circuit Breaker (50KA) with microprocessor release,O/L, S/C & E/Fprotection with communication port RS485 port (Transformer Incomer).

B) BUSCOUPLER BREAKERS

● 2 Nos. 2500Amp FP Electrically operated horizontal drawout type(EDO) Air Circuit Breaker (50KA) as buscoupler with interlockingarrangement with incomers with communication port RS485 port.

● 1 Set of indicating lamps for ON & OFF of buscoupler.

C) BUSBARS

● 3000 Amp TPN busbars of aluminium alloy (Bus-Section I, II & II).

D) OUTGOING BREAKERS WITH INSTRUMENTS

● 3 Nos. 1600 Amp Three Pole Manually operated horizontal type (MDO)Air Circuit Breaker (50KA) with thermal magnetic release, O/L, S/C &E/F protection & neutral link.

● 12 Nos. 1250 Amp Three Pole Manually operated horizontal type(MDO) Air Circuit Breaker (50KA) with thermal magnetic release, O/L,S/C & E/F protection & neutral link.

● 6 Nos. 800 Amp Three Pole Manually operated horizontal type (MDO)Air Circuit Breaker (50KA) with thermal magnetic release, O/L, S/C &E/F protection & neutral link.

Page 60: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

E) INSTRUMENTS ON INCOMER BREAKERS

● 3 Nos. 0 to 500 Volt digital voltmeter with selector switch (96mmsquare) (two for each incoming breaker).

● 3 Nos. 0 to 2500 Amp digital ammeter (96mm square) with CT's (onefor each incoming breaker) and selector switch.

● 3 Sets of phase indicating lights (RYB) with protection mcb's (one setfor each incoming breaker).

● 3 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incomingbreaker).

● 3 Sets trip circuit healthy indicating lamp (one set for each incomingbreaker).

● 3 Sets auto trip indicating lamp (one set for each incoming breaker).

● 3 Nos. of Dual ratio CT's of 2500/500/5/5Amp ratio for APFC Relay(For each incoming supply).

● 3 Nos. trip circuit supervision relay (one for each incoming breaker).

● 3 Nos. electronic type Digital energy analyser having 30 day memoryand parameters of KW, KWH, power factor, frequency etc. (one for eachincoming breaker).

● 3 Nos. master trip relay (one for each incoming breaker).

● 3 Set of O/V & U/V relay (one for each incoming breaker).

● 3 Nos. Phase squence relay (one for each incoming breaker).

5.0 CAPACITOR BANK PANEL (400KVAR) 3 Sets 518,000.00 1,554,000.00 (MR)

Supply, installation, testing & commissioning of Capacitor Panelsuitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz, A.C. Supplytotally enclosed type with free standing floor mounted dust and verminproof indoor type fabricated from 2mm thick CRCA sheet steel

Page 61: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

complete with busbars, ammeter, ammeter selector switch, voltmeter,voltmeter selector switch, indicating lamps, protection relays, CT'sprotection fuses, interconnections with suitable size of copper leads/solidaluminium strips/rod auto / manual selector switch for operation ofcapacitor units, push buttons for manual operation capacitor duty,contractors capacitor bank, APFC relay, power factor meter etc.complete and having following incoming and outgoing Circuit Breakersetc. as per the drawing and specifications complete as required.

A) INCOMER

● 1 No. 1250 Amp FP Moulded Case Circuit Breaker (50KA Ics Value)with microprocessor release for O/L, S/C & E/F protection.

● 1 No. 0-1250A. Ammeter with selector switch & CT's.

● 1 No. 0-500A. Voltmeter with selector switch

● 1 Set of phase indicating lamps

B) BUSBARS

● 1500A TPN Aluminium busbars

C) OUTGOING

● 14 stepped Automatic Power Factor Correction relay (APFC relay).

● 4 Nos. 100 Amp TP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release and neutral link.

● 6 Nos. 63 Amp TP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release and neutral link.

● 4 Nos. 40 Amp TP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release and neutral link.

● 14 Nos. Capacitor duty contactor (one for each 50 KVAR / 25KVAR /12.5KVAR) Capacitor unit.

Page 62: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

● 4 Nos. 50 KVAR Capacitor Bank.

● 6 Nos. 25 KVAR Capacitor Bank.

● 4 Nos. 12.5 KVAR Capacitor Bank.

● 14 Sets of push button stations Red and Green for manual operation ofcapacitor units with auto/manual selector switches.

● 1 No. Indicating lamp for each 50KVAR / 25 KVAR / 12.5 KVARcapacitor unit to indicate that the unit is 'ON'.

● 1 No. Toggle switch for changing automatic to manual operation ofcapacitor units.

● 1 No. Power factor meter.

6.0 MAIN L.T. PANEL (ESSENTIAL SUPPLY) (SS3/EMLTP-1)

Supply, installation, testing & commissioning of Main L.T. Panel(Essential Supply) extensible type suitable for 415 volts (nominal) 3phase 4 wire, 50 Hz, A.C. Supply totally enclosed type with freestanding floor mounted dust and vermin proof compartmentalised indoortype fabricated from 2mm thick CRCA sheet steel complete withbusbars, ammeter, ammeter selector switch, voltmeter, voltmeter selectorswitch, indicating lamps, protection relays, CT's protection fuses,interconnections with suitable size of copper leads/solid aluminiumstrips/rod . PLC shall be provided for monitering power supply onvarious bus section and closing / opening of incomer & bus couplerbreakers and interlocking, auto / manual selector switch, and havingfollowing incoming and outgoing Air Circuit Breakers, MCCB's as perthe drawing and technical specifications complete as required. (TOTALOF A TO F) 1 Set 1,246,000.00 1,246,000.00 (MR)

A) INCOMER BREAKERS

● 3 Nos. 800Amp FP Electrical operated horizontal drawout type (EDO)Air Circuit Breaker (50KA) with microprocessor release for O/L, S/C &E/F protection with communication port RS485 port.

Page 63: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

B) AUTO OPERATION OF INCOMER / BUSCOUPLER ACB's.

● Load management through Micro PLC shall be provided to achieve thefollowing functions.

● Auto changeover incomer breaker.

● Buscoupler switching.

● Signal to AMF Panel for status of load to ensure auto start / auto stop ofDG Sets by AMF Panel.

● Interlocking.

● Necessary hardware shall be provided to achieve above functionsincluding micro PLC with real time clock, digital inputs / outputs, MMIwith 2 line display, power supply, auxillary relays, push buttons, LEDindication lamp, window announciation facia etc. & software for theabove. All items required for complete operation whether or not list inBOQ shall deemed to be included in quoted rates.

● Automatic system shall be user friendly and shall have manual over ride.

C) BUSCOUPLER BREAKERS

● 2 Nos. 800Amp FP Electrically operated horizontal drawout type (EDO)Air Circuit Breaker (50KA) as buscoupler with interlocking arrangementwith incomers through PLC with communication port RS485 port.

● 1 Set of indicating lamps for ON & OFF of buscoupler.

D) BUSBARS

● 1000 Amp TPN busbars of aluminium alloy in Bus Section - I, II & III.

Page 64: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

E) OUTGOING BREAKERS WITH INSTRUMENTS

● 6 Nos. 630 Amp Three Pole Manually operated horizontal drawout type(MDO) Air Circuit Breaker (50KA) with thermal magnetic release, O/L,S/C & E/F protection & neutral link.

● 2 Nos. 250 Amp Three Pole Moulded Case Circuit Breaker (35KA IcsValue) with microprocessor release for O/L, S/C & E/F protection andneutral link.

● 1 No. 125 Amp Three Pole Moulded Case Circuit Breaker (35KA IcsValue) with microprocessor release for O/L, S/C & E/F protection andneutral link.

F) INSTRUMENTS ON INCOMER BREAKERS

● 3 Nos. 0 to 500 Volt digital voltmeter with selector switch (96mmsquare) (one for each incoming breaker).

● 3 Nos. 0 to 800 Amp digital ammeter (96mm square) with CT's (for800Amp incomer breaker) and selector switch.

● 3 Sets of phase indicating lights (RYB) with protection mcb's (one setfor each incoming breaker).

● 3 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incomingbreaker).

● 3 Set trip circuit healthy indicating lamp (one set for each incomingbreaker).

● 3 Set auto trip indicating lamp (one set for each incoming breaker).

● 3 Nos. trip circuit supervision relay (one for each incoming breaker).

● 3 Nos. electronic type Digital energy analyser having 30 day memoryand parameters of KW, KWH, power factor, frequency etc. (one for eachincoming breaker).

● 3 Nos. master trip relay (one for each incoming breaker).

Page 65: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

● 3 Nos. O/V & U/V relay (one for each incoming breaker).

● 3 Nos. reverse power relay (one for each incoming breaker).

7.0 MAIN L.T. PANEL (NORMAL SUPPLY) (SS4/MLTP-1)

Supply, installation, testing & commissioning of Main L.T. Panelextensible type suitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz,A.C. Supply totally enclosed type with free standing floor mounted dustand vermin proof compartmentalised indoor type fabricated from 2mmthick CRCA sheet steel complete with busbars, ammeter, ammeterselector switch, voltmeter, voltmeter selector switch, indicating lamps,protection relays, CT's, protection fuses, interconnections with suitablesize of copper leads/solid aluminium strips/rod and having followingincoming and outgoing Air Circuit Breakers, MCCB's as per thedrawing and technical specifications complete as required. (TOTAL OFA TO D) 1 Set 2,617,000.00 2,617,000.00 (MR)

A) INCOMER BREAKERS

● 2 Nos. 2500Amp FP Manually operated horizontal drawout type (MDO)Air Circuit Breaker (50KA) with microprocessor release,O/L, S/C & E/Fprotection with communication port RS485 port (Transformer Incomer).

B) BUSCOUPLER BREAKERS

● 1 No. 2500Amp FP Manually operated horizontal drawout type (MDO)Air Circuit Breaker (50KA) as buscoupler with interlocking arrangementwith incomers with communication port RS485 port.

● 1 Set of indicating lamps for ON & OFF of buscoupler.

C) BUSBARS

● 3000 Amp TPN busbars of aluminium alloy (Bus-Section I & II).

Page 66: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

D) OUTGOING BREAKERS WITH INSTRUMENTS

● 2 Nos. 1600 Amp Three Pole Manually operated horizontal drawouttype (MDO) Air Circuit Breaker (50KA) with thermal magnetic release,O/L, S/C & E/F protection & neutral link.

● 6 Nos. 1250 Amp Three Pole Manually operated horizontal drawouttype (MDO) Air Circuit Breaker (50KA) with thermal magnetic release,O/L, S/C & E/F protection & neutral link.

● 2 Nos. 800 Amp Three Pole Manually operated horizontal drawout type(MDO) Air Circuit Breaker (50KA) with thermal magnetic release, O/L,S/C & E/F protection & neutral link.

● 2 Nos. 400 Amp Three Pole Moulded Case Circuit Breaker (35KA IcsValue) with microprocessor release for O/L, S/C & E/F protection andneutral link.

E) INSTRUMENTS ON INCOMER BREAKERS

● 2 Nos. 0 to 500 Volt digital voltmeter with selector switch (96mmsquare) (one for each incoming breaker).

● 2 Nos. 0 to 2500 Amp digital ammeter (96mm square) with CT's (onefor each incoming breaker) and selector switch.

● 2 Sets of phase indicating lights (RYB) with protection mcb's (one setfor each incoming breaker).

● 2 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incomingbreaker).

● 2 Sets trip circuit healthy indicating lamp (one set for each incomingbreaker).

● 2 Sets auto trip indicating lamp (one set for each incoming breaker).

● 2 Nos. of Dual ratio CT's of 2500/500/5/5Amp ratio for APFC Relay(one for each incomer breaker).

Page 67: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

● 2 Nos. trip circuit supervision relay (one for each incoming breaker).

● 2 Nos. electronic type Digital energy analyser having 30 day memoryand parameters of KW, KWH, power factor, frequency etc. (one for eachincoming breaker).

● 2 Nos. master trip relay (one for each incoming breaker).

● 2 Nos. of O/V & U/V relay (one for each incoming breaker).

● 2 Nos. Phase squence relay (one for each incoming breaker).

8.0 CAPACITOR BANK PANEL (SUBSTATION NO. 4) (400KVARCAPACITY) 2 Sets 518,000.00 1,036,000.00 (MR)

Supply, installation, testing & commissioning of Capacitor Panelsuitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz, A.C. Supplytotally enclosed type with free standing floor mounted dust and verminproof indoor type fabricated from 2mm thick CRCA sheet steel completewith busbars, ammeter, ammeter selector switch, voltmeter, voltmeterselector switch, indicating lamps, protection relays, CT's protectionfuses, interconnections with suitable size of copper leads/solidaluminium strips/rod auto / manual selector switch for operation ofcapacitor units, push buttons for manual operation, capacitor dutycontactors, capacitor bank, APFC relay, power factor meter etc.complete and having following incoming and outgoing Circuit Breakersetc. as per the drawing and specifications complete as required. (TOTALOF A TO C)

A) INCOMER

● 1 No. 1250 Amp Four Pole Moulded Case Circuit Breaker (50KA IcsValue) with microprocessor release for O/L, S/C & E/F protection.

● 1 No. 0-1250A. Ammeter with selector switch & CT's.

● 1 No. 0-500A. Voltmeter with selector switch

● 1 Set of phase indicating lamps

Page 68: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

B) BUSBARS

● 1250A TPN Aluminium busbars

C) OUTGOING

● 14 stepped Automatic Power Factor Correction relay (APFC relay).

● 4 Nos. 40 Amp Three Pole Moulded Case Circuit Breaker (25KA IcsValue) with thermal magnetic release for O/L, S/C & E/F protection andneutral link.

● 4 Nos. 100 Amp Three Pole Moulded Case Circuit Breaker (25KA IcsValue) with thermal magnetic release for O/L, S/C & E/F protection andneutral link.

● 6 Nos. 63 Amp Three Pole Moulded Case Circuit Breaker (25KA IcsValue) with thermal magnetic release for O/L, S/C & E/F protection andneutral link.

● 14 Nos. Capacitor duty contactor (one for each 50KVAR / 25KVAR /12.5KVAR) Capacitor unit.

● 4 Nos. 50 KVAR Capacitor Bank.

● 6 Nos. 25 KVAR Capacitor Bank.

● 4 Nos. 12.5 KVAR Capacitor Bank.

● 14 Sets of push button stations Red and Green for manual operation ofcapacitor units with auto/manual selector switches.

● 1 No. Indicating lamp for each 50KVAR / 25KVAR /12.5KVARcapacitor unit to indicate that the unit is 'ON'.

● 1 No. Toggle switch for changing automatic to manual operation ofcapacitor units.

● 1 No. Power factor meter.

Page 69: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

9.0 MAIN L.T. PANEL (ESSENTIAL SUPPLY) (SS4/EMLTP-1)

Supply, installation, testing & commissioning of Main L.T. Panel(Essential Supply) extensible type suitable for 415 volts (nominal) 3phase 4 wire, 50 Hz, A.C. Supply totally enclosed type with freestanding floor mounted dust and vermin proof compartmentalised indoortype fabricated from 2mm thick CRCA sheet steel complete withbusbars, ammeter, ammeter selector switch, voltmeter, voltmeter selectorswitch, indicating lamps, protection relays, CT's protection fuses,interconnections with suitable size of copper leads/solid aluminiumstrips/rod. PLC shall be provided for monitering power supply onvarious bus section and closing / opening of incomer & bus couplerbreakers and interlocking, auto / manual selector switch, and havingfollowing incoming and outgoing Air Circuit Breakers, MCCB's as perthe drawing and technical specifications complete as required. (TOTALOF A TO F) 1 Set 534,000.00 534,000.00 (MR)

A) INCOMER BREAKERS

● 1 No. 800Amp FP Electrical operated horizontal drawout type (EDO)Air Circuit Breaker (50KA) with microprocessor release,O/L, S/C & E/Fprotection with communication port RS485 port.

● 1 No. 400Amp FP Moulded Case Circuit Breaker (35KA Ics Value) forO/L, S/C & E/F protection.

● 1 No. 400Amp FP contactor (AC 3 Duty) with timer switch.

B) AUTO OPERATION OF INCOMER / BUSCOUPLER ACB's.

● Load management through Micro PLC shall be provided to achieve thefollowing functions.

● Auto changeover closing and opening incomer breakers.

● Buscoupler switching.

Page 70: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

● Signal to AMF Panel for status of load to ensure auto start / auto stop ofDG Sets by AMF Panel.

● Interlocking.

● Necessary hardware shall be provided to achieve above functionsincluding micro PLC with real time clock, digital inputs / outputs, MMIwith 2 line display, power supply, auxillary relays, push buttons, LEDindication lamp, window announciation facia etc. & software for theabove. All items required for complete operation whether or not list inBOQ shall deemed to be included in quoted rates.

● Automatic system shall be user friendly and shall have manual over ride.

C) BUSCOUPLER BREAKERS

● 1 No. 400Amp FP Contactor (AC 3 Duty) for closing and openingthrough PLC.

● 1 Set of indicating lamps for ON & OFF of buscoupler.

D) BUSBARS

● 1000 Amp TPN busbars of aluminium alloy in Bus Section - I.

● 500 Amp TPN busbars of aluminium alloy in Bus Section - II.

E) OUTGOING BREAKERS WITH INSTRUMENTS

● 2 Nos. 400 Amp Three Pole Moulded Case Circuit Breaker (35KA IcsValue) with microprocessor release for O/L, S/C & E/F protection andneutral link.

● 2 Nos. 300 Amp Three Pole Moulded Case Circuit Breaker (35KA IcsValue) with microprocessor release for O/L, S/C & E/F protection andneutral link.

Page 71: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

● 2 Nos. 250 Amp Three Pole Moulded Case Circuit Breaker (35KA IcsValue) with microprocessor release for O/L, S/C & E/F protection andneutral link.

● 2 Nos. 100 Amp Three Pole Moulded Case Circuit Breaker (25KA IcsValue) with microprocessor release for O/L, S/C & E/F protection andneutral link.

F) INSTRUMENTS ON INCOMER BREAKERS

● 2 Nos. 0 to 500 Volt digital voltmeter with selector switch (96mmsquare) (one for each incoming breaker).

● 1 No. 0 to 630 Amp digital ammeter (96mm square) with CT's (for 630incoming breaker) and selector switch.

● 1 No. 0 to 400 Amp digital ammeter (96mm square) with CT's (for 400incoming breaker) and selector switch.

● 2 Sets of phase indicating lights (RYB) with protection mcb's (one setfor each incoming breaker).

● 2 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incomingbreaker).

● 2 Set trip circuit healthy indicating lamp (for 630 ACB incoming

● 2 Set auto trip indicating lamp (for 630 ACB incoming breaker).

● 2 Nos. trip circuit supervision relay (for 630 Amp incomer breaker).

● 2 Nos. electronic type Digital energy analyser having 30 day memoryand parameters of KW, KWH, power factor, frequency etc. (one forincomer breaker).

● 2 Nos. master trip relay (one for each incomer breaker).

● 2 Set of O/V & U/V relay (one for each incomer breaker).

● 2 Set of reverse power relay (one for each incomer breaker).

Page 72: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

10.0 MAIN L.T. PANEL (NORMAL SUPPLY) (SS5/MLTP-1)

Supply, installation, testing & commissioning of Main L.T. Panelextensible type suitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz,A.C. Supply totally enclosed type with free standing floor mounted dustand vermin proof compartmentalised indoor type fabricated from 2mmthick CRCA sheet steel complete with busbars, ammeter, ammeterselector switch, voltmeter, voltmeter selector switch, indicating lamps,protection relays, CT's, protection fuses, interconnections with suitablesize of copper leads/solid aluminium strips/rod and having followingincoming and outgoing Air Circuit Breakers, MCCB's as per thedrawing and technical specifications complete as required. (TOTAL OFA TO D) 1 Set 1,004,000.00 1,004,000.00 (MR)

A) INCOMER BREAKERS

● 1 No. 2000Amp FP Manually operated horizontal drawout type (MDO)Air Circuit Breaker (50KA) with microprocessor release,O/L, S/C & E/Fprotection with communication port RS485 port (Transformer Incomer).

B) BUSBARS

● 2500 Amp TPN busbars of aluminium alloy.

C) OUTGOING BREAKERS WITH INSTRUMENTS

● 2 Nos. 800 Amp Three Pole Manually operated horizontal drawout type(MDO) Air Circuit Breaker (50KA) with thermal magnetic release, withO/L, S/C & E/F protection and neutral link.

● 9 Nos. 400 Amp Three Pole Moulded Case Circuit Breaker (35KA IcsValue) with microprocessor release for O/L, S/C & E/F protection andneutral link.

Page 73: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

D) INSTRUMENTS ON INCOMER BREAKERS

● 1 No. 0 to 500 Volt digital voltmeter with selector switch (96mmsquare).

● 1 No. 0 to 2000 Amp digital ammeter (96mm square) with CT's andselector switch.

● 1 Set of phase indicating lights (RYB) with protection mcb's

● 1 Set breaker 'ON' & 'OFF' indicating lamp.

● 1 Set trip circuit healthy indicating lamp.

● 1 Set auto trip indicating lamp.

● 1 No. of Dual ratio CT's of 2000/500/5/5Amp ratio each for APFCRelay (for Transformer Incomer).

● 1 No. trip circuit supervision relay.

● 1 No. electronic type Digital energy analyser having 30 day memory andparameters of KW, KWH, power factor, frequency etc. (one for eachincoming breaker).

● 1 No. master trip relay.

● 1 No. of O/V & U/V relay.

● 1 No. Phase squence relay.

11.0 CAPACITOR BANK PANEL -SS5 (300KVAR)

Supply, installation, testing & commissioning of Capacitor Panelsuitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz, A.C. Supplytotally enclosed type with free standing floor mounted dust and verminproof indoor type fabricated from 2mm thick CRCA sheet steel completewith busbars, ammeter, ammeter selector switch, voltmeter, voltmeterselector switch, indicating lamps, protection relays, CT's protectionfuses, interconnections with suitable size of copper

Page 74: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

leads/solid aluminium strips/rod auto / manual selector switch foroperation of capacitor units, push buttons for manual operation capacitorduty, contractors capacitor bank, APFC relay, power factor meter etc.complete and having following incoming and outgoing Circuit Breakersetc. as per the drawing and specifications complete as required. (TOTALOF A TO C) 1 Set 377,000.00 377,000.00 (MR)

A) INCOMER

● 1 No. 800 Amp Four Pole Moulded Case Circuit Breaker (50KA IcsValue) with microprocessor release for O/L, S/C & E/F protection.

● 1 No. 0-800A. Ammeter with selector switch & CT's.

● 1 No. 0-500A. Voltmeter with selector switch

● 1 Set of phase indicating lamps

B) BUSBARS

● 1000A TPN Aluminium busbars

C) OUTGOING

● 14 stepped Automatic Power Factor Correction relay (APFC relay).

● 2 Nos. 100 Amp FP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release and neutral link.

● 6 Nos. 63 Amp FP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release and neutral link.

● 4 Nos. 40 Amp FP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release and neutral link.

● 12 Nos. Capacitor duty contactor (one for each 50KVAR / 25KVAR /12.5KVAR) Capacitor unit.

● 2 Nos. 50 KVAR Capacitor Bank.

● 6 Nos. 25 KVAR Capacitor Bank.

Page 75: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

● 4 Nos. 12.5 KVAR Capacitor Bank.

● 12 Sets of push button stations Red and Green for manual operation ofcapacitor units with auto/manual selector switches.

● 1 No. Indicating lamp for each 50KVAR / 25KVAR / 12.5KVARcapacitor unit to indicate that the unit is 'ON'.

● 1 No. Toggle switch for changing automatic to manual operation ofcapacitor units.

● 1 No. Power factor meter.

12.0 MAIN L.T. PANEL (ESSENTIAL SUPPLY) (SS5/EMLTP-1)

Supply, installation, testing & commissioning of Main L.T. Panel(Essential Supply) extensible type suitable for 415 volts (nominal) 3phase 4 wire, 50 Hz, A.C. Supply totally enclosed type with freestanding floor mounted dust and vermin proof compartmentalised indoortype fabricated from 2mm thick CRCA sheet steel complete withbusbars, ammeter, ammeter selector switch, voltmeter, voltmeter selectorswitch, indicating lamps, protection relays, CT's protection fuses,interconnections with suitable size of copper leads/solid aluminiumstrips/rod. PLC shall be provided for monitering power supply onvarious bus section and closing / opening of incomer & bus couplerbreakers and interlocking, auto / manual selector switch and havingfollowing incoming and outgoing Air Circuit Breakers, MCCB's as perthe drawing and technical specifications complete as required. (TOTALOF A TO F) 1 Set 446,000.00 446,000.00 (MR)

A) INCOMER BREAKERS

● 2 Nos. 400Amp FP Moulded Case Circuit Breaker with microprocessorrelease for O/L, S/C & E/F protection with communication RS485 port.

● 2 Nos. 400Amp FP contactor (AC 3 Duty) with timer switch.

Page 76: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

B) AUTO OPERATION OF INCOMER / BUSCOUPLER ACB's.

● Load management through Micro PLC shall be provided to achieve thefollowing functions.

● Auto closing and opening of incomer power contactor.

● Buscoupler switching.

● Signal to AMF Panel for status of "Load" to ensure auto stop / auto startof DG Set by AMF Panel.

● Interlocking.

● Necessary hardware shall be provided to achieve above functionsincluding micro PLC with real time clock, digital inputs / outputs, MMIwith 2 line display, power supply, auxillary relays, push buttons, LEDindication lamp, window announciation facia etc. & software for theabove. All items required for complete operation whether or not list inBOQ shall deemed to be included in quoted rates.

● Automatic system shall be user friendly and shall have manual over ride.

C) BUSCOUPLER BREAKERS

● 1 No. 400Amp FP Contactor (AC 3 Duty)

● 1 Set of indicating lamps for ON & OFF of buscoupler.

D) BUSBARS

● 600 Amp TPN busbars of aluminium alloy in Bus Section - I & II

E) OUTGOING BREAKERS WITH INSTRUMENTS

● 5 Nos. 200 Amp Three Pole Moulded Case Circuit Breaker (35KA IcsValue) with thermal magnetic release for O/L, S/C & E/F protection andneutral link.

Page 77: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

● 2 Nos. 160 Amp Three Pole Moulded Case Circuit Breaker (35KA IcsValue) with thermal magnetic release for O/L, S/C & E/F protection andneutral link.

● 2 Nos. 100 Amp Three Pole Moulded Case Circuit Breaker (25KA IcsValue) with microprocessor release for O/L, S/C & E/F protection andneutral link.

F) INSTRUMENTS ON INCOMER BREAKERS

● 2 Nos. 0 to 500 Volt digital voltmeter with selector switch (96mmsquare) (for each incoming breaker).

● 2 Nos. 0 to 400 Amp digital ammeter (96mm square) with CT's (for 400incomer breaker) and selector switch. (one for each incoming breaker).

● 2 Sets of phase indicating lights (RYB) with protection mcb's (one setfor each incoming breaker).

● 2 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incomingbreaker).

● 2 Sets trip circuit healthy indicating lamp (one set for each incomingbreaker).

● 2 Sets auto trip indicating lamp (one set for each incoming breaker).

● 2 Nos. trip circuit supervision relay (one set for each incoming breaker).

● 2 Nos. electronic type Digital energy analyser having 30 day memoryand parameters of KW, KWH, power factor, frequency etc. (one for eachincoming breaker).

● 2 Nos. master trip relay (one for each incoming breaker).

● 2 Sets of O/V & U/V relay (one for each incoming breaker).

● 2 Nos. of reverse power relay (one for each incoming breaker).

Page 78: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

13.0 MAIN L.T. PANEL (NORMAL SUPPLY) (SS6/MLTP-1)

Supply, installation, testing & commissioning of Main L.T. Panelextensible type suitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz,A.C. Supply totally enclosed type with free standing floor mounted dustand vermin proof compartmentalised indoor type fabricated from 2mmthick CRCA sheet steel complete with busbars, ammeter, ammeterselector switch, voltmeter, voltmeter selector switch, indicating lamps,protection relays, CT's, protection fuses, interconnections with suitablesize of copper leads/solid aluminium strips/rod and having followingincoming and outgoing Air Circuit Breakers, MCCB's as per thedrawing and technical specifications complete as required. (TOTAL OFA TO D) 1 Set 894,000.00 894,000.00 (MR)

A) INCOMER BREAKERS

● 1 No. 1600Amp FP Manually operated horizontal drawout type (MDO)Air Circuit Breaker (50KA) with microprocessor release,O/L, S/C & E/Fprotection with communication port RS485 port (Transformer Incomer).

B) BUSBARS

● 2000 Amp TPN busbars of aluminium alloy.

C) OUTGOING BREAKERS WITH INSTRUMENTS

● 2 Nos. 800 Amp Three Pole Manually operated horizontal drawout type(MDO) Air Circuit Breaker (50KA) with thermal magnetic release, O/L,S/C & E/F protection and neutral link.

● 7 Nos. 400 Amp Three Pole Moulded Case Circuit Breaker (35KA IcsValue) with microprocessor release for O/L, S/C & E/F protection andneutral link.

D) INSTRUMENTS ON INCOMER BREAKERS

● 1 No. 0 to 500 Volt digital voltmeter with selector switch (96mmsquare).

Page 79: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

● 1 No. 0 to 1600 Amp digital ammeter (96mm square) with CT's andselector switch.

● 1 Set of phase indicating lights (RYB) with protection mcb's

● 1 Set breaker 'ON' & 'OFF' indicating lamp.

● 1 Set trip circuit healthy indicating lamp.

● 1 Set auto trip indicating lamp.

● 1 No. of Dual ratio CT's of 1600/400/5/5Amp ratio each for APFCRelay.

● 1 No. trip circuit supervision relay.

● 1 No. electronic type Digital energy analyser having 30 day memory andparameters of KW, KWH, power factor, frequency etc.

● 1 No. master trip relay.

● 1 No. of O/V & U/V relay.

● 1 No. Phase squence relay.

14.0 CAPACITOR BANK PANEL -SS6 (300KVAR)

Supply, installation, testing & commissioning of Capacitor Panelsuitable for 415 volts (nominal) 3 phase 4 wire, 50 Hz, A.C. Supplytotally enclosed type with free standing floor mounted dust and verminproof indoor type fabricated from 2mm thick CRCA sheet steel completewith busbars, ammeter, ammeter selector switch, voltmeter, voltmeterselector switch, indicating lamps, protection relays, CT's protectionfuses, interconnections with suitable size of copper leads/solidaluminium strips/rod auto / manual selector switch for operation ofcapacitor units, push buttons for manual operation capacitor duty,contractors capacitor bank, APFC relay, power factor meter etc.complete and having following incoming and outgoing Circuit Breakersetc. as per the drawing and specifications complete as required. (TOTALA TO C) 1 Set 377,000.00 377,000.00 (MR)

Page 80: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

A) INCOMER

● 1 No. 800 Amp Four Pole Moulded Case Circuit Breaker (50KA IcsValue) with microprocessor release for O/L, S/C & E/F protection andneutral link.

● 1 No. 0-800A. Ammeter with selector switch & CT's.

● 1 No. 0-500A. Voltmeter with selector switch

● 1 Set of phase indicating lamps

B) BUSBARS

● 1000A TPN Aluminium busbars

C) OUTGOING

● 14 stepped Automatic Power Factor Correction relay (APFC relay).

● 2 Nos. 100 Amp FP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release and neutral link.

● 6 Nos. 63 Amp TP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release, O/L, S/C & E/F protection and neutrallink.

● 4 Nos. 40 Amp TP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release, O/L, S/C & E/F protection and neutrallink.

● 12 Nos. Capacitor duty contactor (one for each 50KVAR / 25KVAR /12.5KVAR) Capacitor unit.

● 2 Nos. 50 KVAR Capacitor Bank.

● 6 Nos. 25 KVAR Capacitor Bank.

● 4 Nos. 12.5 KVAR Capacitor Bank.

● 12 Sets of push button stations Red and Green for manual operation ofcapacitor units with auto/manual selector switches.

Page 81: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

● 1 No. Indicating lamp for each 50KVAR / 25KVAR / 12.5KVARcapacitor unit to indicate that the unit is 'ON'.

● 1 No. Toggle switch for changing automatic to manual operation ofcapacitor units.

● 1 No. Power factor meter.

15.0 MAIN L.T. PANEL (ESSENTIAL SUPPLY) (SS6/EMLTP-1)

Supply, installation, testing & commissioning of Main L.T. Panel(Essential Supply) extensible type suitable for 415 volts (nominal) 3phase 4 wire, 50 Hz, A.C. Supply totally enclosed type with freestanding floor mounted dust and vermin proof compartmentalised indoortype fabricated from 2mm thick CRCA sheet steel complete withbusbars, ammeter, ammeter selector switch, voltmeter, voltmeter selectorswitch, indicating lamps, protection relays, CT's protection fuses,interconnections with suitable size of copper leads/solid aluminiumstrips/rod. PLC shall be provided for monitering power supply onvarious bus section and closing / opening of incomer & bus couplerbreakers and interlocking, auto / manual selector switch, and havingfollowing incoming and outgoing Air Circuit Breakers, MCCB's as perthe drawing and technical specifications complete as required. (TOTALOF A TO F) 1 Set 455,000.00 455,000.00 (MR)

A) INCOMER BREAKERS

● 2 Nos. 400Amp FP Moulded Case Circuit Breaker (35KA Ics Value)with microprocessor release for O/L, S/C & E/F protection withcommunication RS485 port.

● 2 Nos. 400Amp FP contactor (AC3 Duty) with timer switch.

B) AUTO OPERATION OF INCOMER / BUSCOUPLER ACB's.

● Load management through Micro PLC shall be provided to achieve thefollowing functions.

Page 82: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

● Auto closing and opening of incomer power contactor.

● Buscoupler switching.

● Signal to AMF Panel for status of "Load" to ensure auto stop / auto startof DG Set by AMF Panel.

● Interlocking.

● Necessary hardware shall be provided to achieve above functionsincluding micro PLC with real time clock, digital inputs / outputs, MMIwith 2 line display, power supply, auxillary relays, push buttons, LEDindication lamp, window announciation facia etc. & software for theabove. All items required for complete operation whether or not list inBOQ shall deemed to be included in quoted rates.

● Automatic system shall be user friendly and shall have manual over ride.

C) BUSCOUPLER BREAKERS

● 1 No. 400Amp FP Contactor (AC3 Duty)

● 1 Set of indicating lamps for ON & OFF of buscoupler.

D) BUSBARS

● 600 Amp TPN busbars of aluminium alloy in Bus Section - I & II.

E) OUTGOING BREAKERS WITH INSTRUMENTS

● 7 Nos. 200 Amp Three Pole Moulded Case Circuit Breaker (35KA IcsValue) with thermal release for O/L, S/C & E/F protection and neutrallink.

● 2 Nos. 100 Amp Three Pole Moulded Case Circuit Breaker (25KA IcsValue) with thermal release for O/L, S/C & E/F protection and neutrallink.

Page 83: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

F) INSTRUMENTS ON INCOMER BREAKERS

● 2 Nos. 0 to 500 Volt digital voltmeter with selector switch (96mmsquare) (for each incoming breaker).

● 2 Nos. 0 to 400 Amp digital ammeter (96mm square) with CT's (for400Amp incomer breaker) and selector switch.

● 2 Sets of phase indicating lights (RYB) with protection mcb's (one setfor each incoming breaker).

● 2 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incomingbreaker).

● 2 Sets trip circuit healthy indicating lamp (one for each incomerbreaker).

● 2 Sets auto trip indicating lamp (one for each incomer breaker).

● 2 Nos. trip circuit supervision relay (one for each incomer).

● 2 Nos. electronic type Digital energy analyser having 30 day memoryand parameters of KW, KWH, power factor, frequency etc. (one for eachincomer).

● 2 Nos. master trip relay (one for each incomer).

● 2 Sets. of O/V & U/V relay (one for each incomer).

● 2 Nos. of reverse power relay (one for each incomer).

16.0 SDB - DISTRIBUTION BOARDS

Supply, installation, testing & commissioning of cubicle type tollallyenclosure free standing type moistue, dust and vermin proof SubDistribution Boards (SDB) made out of 2mm thick CRCA sheet steelcomplete with following equipments, including ammeter, ammeterselector switch, voltmeter, voltmeter selector switch, indicating lamps,CT's internal wiring with suitable size wires / cable, interconnection,pointing etc. as per drawing and specification complete as required.

Page 84: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

16.1 ESDB/SS2 TYPICAL FOR ESDB/SS4, ESDB/SS6 (TOTAL OF A TO D) 3 Set 105,000.00 315,000.00 (MR)

A) INCOMING

● 1 No. 100Amp FP Moulded Case Circuit Breaker of (25KA Ics Value)with thermal magnetic release and O/L, S/C & E/F protection.

B) INSTRUMENTS

● 1 No. 0 to 500 Volt digital voltmeter (96mm square) with selectorswitch.

● 1 No. 0 to 100 Amp digital ammeter (96mm square) with selector switch& CT's.

● 1 Set of phase indicating lights (RYB) with protection MCB.

C) BUSBARS

● 150Amp TPN busbars of aluminium alloy.

D) OUTGOING

● 5 Nos. 32-63 Amp TP Moulded Case Circuit Breaker of (25KA IcsValue) with thermal magnetic release, O/L, S/C & E/F protection andneutral link.

16.2 ESDB/SS3 TYPICAL FOR ESDB/SS5 (TOTAL OF A TO D) 2 Set 107,000.00 214,000.00 (MR)

A) INCOMING

● 1 No. 125Amp FP Moulded Case Circuit Breaker of (35KA Ics Value)with thermal magnetic release and O/L, S/C & E/F protection.

B) INSTRUMENTS

● 1 No. 0 to 500 Volt digital voltmeter (96mm square) with selectorswitch.

Page 85: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

● 1 No. 0 to 125 Amp digital ammeter (96mm square) with selector switch& CT's.

● 1 Set of phase indicating lights (RYB) with protection MCB.

C) BUSBARS

● 150Amp TPN busbars of aluminium alloy.

D) OUTGOING

● 2 Nos. 100 Amp TP Moulded Case Circuit Breaker of (25KA Ics Value)with thermal magnetic release, O/L, S/C & E/F protection and neutrallink.

● 3 Nos. 32-63 Amp TP Moulded Case Circuit Breaker of (25KA IcsValue) with thermal magnetic release, O/L, S/C & E/F protection andneutral link.

TOTAL OF SUBHEAD IV - MAIN LT PANELS, CAPACITORBANK PANELS & SUB-DISTRIBUTION BOARDS CARRIEDOVER TO THE SUMMARY.

0.00 20,047,000.00

V. COMPACT TYPE SUBSTATION & DISTRIBUTION FEEDERPILLARS

1.0 COMPACT TYPE SUBSTATIONS (CSS - 1) [TYPICAL FORCSS2]

Page 86: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

Supply, Installation, Testing & Commissioning of Compact typesubstation consisting of following equipments mounted in outdoorenclosure fabricated out of galvanised sheet steel complete as perspecifications complete as required. (TOTAL OF A TO C): 2 Set 2,149,000.00 4,298,000.00 (MR)

A) THREE WAY 11KV RING MAIN UNIT

1 No. 200Amp 11KV, TP Vacuum Circuit Breaker encapsulated insteel vessel with SF6 Gas Insulated with self powered IDMT relay typeVIP 35 for protection against phase to phase & phase to earth protectionand 2 Nos. 630 Amp TP Load Break Switch with earth switch completeas required (Three Way RMU with One No. VCB for transformerProtection & 2 Nos. Load break switches).

B) TRANSFORMER (OIL TYPE)

1 No. 400 KVA, 11KV/433V, 3 phase 50Hz. Vector group Dyn-11 Oiltype, ONAN cooled, hermitically sealed, copper wound Distributiontransformer with off load tap changer of range +5% to -5% insteps of2.5%, cable end boxes on HV & LT side with all fittings & accessories,WTI alarm & trip and oil temperature alarm & trip control wiring,complete as per specifications & conforming to IS 2026-1977.

Page 87: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

C) LT PANEL

L.T. Panel suitable for 415 volt (nominal) 3 phase 4 wire 50 Hz ACsupply, cubicle type dust and vermin proof compartmentalised indoortype febricated from 2mm thick CRCA sheet steel complete withbusbars, Ammeter, Ammeter selector switch, voltmeter, voltmeterselector switch, indicating lamp, interconnection and having follwingincoming and outgoing breakers as per drawing and specification.

i) INCOMING

● 1 No. 630 Amp FP manually operated Fixed type (MF) Air CircuitBreaker (50KA) with microprocessor release, with O/L, S/C & EFprotection and ON/ OFF Indicating LED lights complete as perspecifications.

ii) INSTRUMENTS

● 1 No. 0 to 630 Amp Ammeter with Ammeter selector switch & CT's.

● 1 No. 0 to 500 Volt Voltmeter with Voltmeter selector switch.

● 1 Set of RYB indicating lamps with protection MCB.

iii) BUSBARS

● 800Amp TPN aluminium busbar.

iv) TIE BREAKER

● 1 No. 250 Amp FP Moulded Case Circuit Breakers (35KA Ics Value)with microprocessor release for O/L, S/C & EF protection and ON/ OFFIndicating LED lights complete as per specifications.

v) OUTGOING

● 2 Nos. 300Amp TP Moulded Case Circuit Breaker (35KA Ics Value)with microprocessor release and neutral link.

● 2 Nos. 200Amp TP Moulded Case Circuit Breaker (35KA Ics Value)with thermal magnetic release and neutral link.

Page 88: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

2.0 COMPACT TYPE SUBSTATION (CSS - 5)

Supply, Installation, Testing & Commissioning of Compact typesubstation consisting of following equipments mounted in outdoorenclosure fabricated out of galvanised sheet steel complete as perspecifications complete as required. (TOTAL OF A TO C): 1 Set 2,149,000.00 2,149,000.00 (MR)

A) THREE WAY 11KV RING MAIN UNIT

1 No. 200Amp 11KV, TP Vacuum Circuit Breaker encapsulated insteel vessel with SF6 Gas Insulated with self powered IDMT relay typeVIP 35 for protection against phase to phase & phase to earth protectionand 2 Nos. 630 Amp TP Load Break Switch with earth switch completeas required (Three Way RMU with One No. VCB for transformerProtection & 2 Nos. Load break switches).

B) TRANSFORMER (OIL TYPE)

1 No. 400 KVA, 11KV/433V, 3 phase 50Hz. Vector group Dyn-11 Oiltype, ONAN cooled, hermitically sealed, copper wound Distributiontransformer with off load tap changer of range +5% to -5% insteps of2.5%, cable end boxes on HV & LT side with all fittings & accessories,WTI alarm & trip and oil temperature alarm & trip control wiring,complete as per specifications & conforming to IS 2026-1977.

C) LT BREAKER PANEL

L.T. Panel suitable for 415 volt (nominal) 3 phase 4 wire 50 Hz ACsupply, cubicle type dust and vermin proof compartmentalised indoortype febricated from 2mm thick CRCA sheet steel complete withbusbars, Ammeter, Ammeter Selector switch, voltmeter, voltmeterselector switch, indicating lamp, interconnection and having follwingincoming and outgoing breakers as per drawing and specification.

Page 89: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

i) INCOMING

● 1 No. 630 Amp FP manually operated Fixed type (MF) Air CircuitBreaker (50KA) with microprocessor release, with O/L, S/C & EFprotection and ON/ OFF Indicating LED lights complete as perspecifications.

ii) INSTRUMENTS

● 1 No. 0 to 630 Amp Ammeter with Ammeter selector switch & CT's.

● 1 No. 0 to 500 Volt Voltmeter with Voltmeter selector switch.

● 1 Set of RYB indicating lamps with protection MCB.

iii) BUSBARS

● 800Amp TPN aluminium busbar.

iv) TIE BREAKER

● 1 No. 250 Amp FP Moulded Case Circuit Breakers (35KA Ics Value)with microprocessor release for O/L, S/C & EF protection and ON/ OFFIndicating LED lights complete as per specifications.

v) OUTGOING

● 3 Nos. 160Amp TP Moulded Case Circuit Breaker (35KA Ics Value)with thermal magnetic release and neutral link.

● 2 Nos. 63-80Amp TP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release and neutral link.

3.0 COMPACT TYPE SUBSTATIONS (CSS - 9)

Supply, Installation, Testing & Commissioning of Compact typesubstation consisting of following equipments mounted in outdoorenclosure fabricated out of galvanised sheet steel complete as perspecifications complete as required. (TOTAL OF A TO D): 1 Set 2,149,000.00 2,149,000.00 (MR)

Page 90: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

A) THREE WAY 11KV RING MAIN UNIT

1 No. 200Amp 11KV, TP Vacuum Circuit Breaker encapsulated insteel vessel with SF6 Gas Insulated with self powered IDMT relay typeVIP 35 for protection against phase to phase & phase to earth protectionand 2 Nos. 630 Amp TP Load Break Switch with earth switch completeas required (Three Way RMU with One No. VCB for transformerProtection & 2 Nos. Load break switches).

B) TRANSFORMER (OIL TYPE)

1 No. 400 KVA, 11KV/433V, 3 phase 50Hz. Vector group Dyn-11 Oiltype, ONAN cooled, hermitically sealed, copper wound Distributiontransformer with off load tap changer of range +5% to -5% insteps of2.5%, cable end boxes on HV & LT side with all fittings & accessories,WTI alarm & trip and oil temperature alarm & trip control wiring,complete as per specifications & conforming to IS 2026-1977.

C) LT BREAKER PANEL

L.T. Panel suitable for 415 volt (nominal) 3 phase 4 wire 50 Hz ACsupply, cubicle type dust and vermin proof compartmentalised indoortype febricated from 2mm thick CRCA sheet steel complete withbusbars, Ammeter, Ammeter Selector switch, voltmeter, voltmeterselector switch, indicating lamp, interconnection and having follwingincoming and outgoing breakers as per drawing and specification.

i) INCOMING

● 1 Nos. 630 Amp FP manually operated Fixed type (MF) Air CircuitBreaker (50KA) with microprocessor release, with O/L, S/C & EFprotection and ON/ OFF Indicating LED lights complete as perspecifications.

Page 91: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

ii) INSTRUMENTS

● 1 No. 0 to 630 Amp Ammeter with Ammeter selector switch & CT's.

● 1 No. 0 to 500 Volt Voltmeter with Voltmeter selector switch.

● 1 Set of RYB indicating lamps with protection MCB.

iii) BUSBARS

● 800Amp TPN aluminium busbar.

iv) TIE BREAKER

● 1 No. 500 Amp FP Moulded Case Circuit Breakers (35KA Ics Value)with microprocessor release for O/L, S/C & EF protection and ON/ OFFIndicating LED lights complete as per specifications.

v) OUTGOING

● 5 Nos. 160Amp TP Moulded Case Circuit Breaker (35KA Ics Value)with thermal magnetic release and neutral link.

● 2 Nos. 100Amp TP Moulded Case Circuit Breaker (35KA Ics Value)with thermal magnetic release and neutral link.

4.0 COMPACT TYPE SUBSTATIONS (CSS - 3)

Supply, Installation, Testing & Commissioning of Compact typesubstation consisting of following equipments mounted in outdoorenclosure fabricated out of galvanised sheet steel complete as perspecifications complete as required. (TOTAL OF A TO C): 1 Set 2,149,000.00 2,149,000.00 (MR)

A) THREE WAY 11KV RING MAIN UNIT

1 No. 200Amp 11KV, TP Vacuum Circuit Breaker encapsulated insteel vessel with SF6 Gas Insulated with self powered IDMT relay typeVIP 35 for protection against phase to phase & phase to earth protectionand 2 Nos. 630 Amp TP Load Break Switch with earth switch completeas required (Three Way RMU with One No. VCB for transformerProtection & 2 Nos. Load break switches).

Page 92: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

B) TRANSFORMER (OIL TYPE)

1 No. 400 KVA, 11KV/433V, 3 phase 50Hz. Vector group Dyn-11 Oiltype, ONAN cooled, hermitically sealed, copper wound Distributiontransformer with off load tap changer of range +5% to -5% insteps of2.5%, cable end boxes on HV & LT side with all fittings & accessories,WTI alarm & trip and oil temperature alarm & trip control wiring,complete as per specifications & conforming to IS 2026-1977.

C) LT BREAKER PANEL

L.T. Panel suitable for 415 volt (nominal) 3 phase 4 wire 50 Hz ACsupply, cubicle type dust and vermin proof compartmentalised indoortype febricated from 2mm thick CRCA sheet steel complete withbusbars, Ammeter, Ammeter Selector switch, voltmeter, voltmeterselector switch, indicating lamp, interconnection and having follwingincoming and outgoing breakers as per drawing and specification.

i) INCOMING

● 1 No. 630 Amp FP manually operated Fixed type (MF) Air CircuitBreaker (50KA) with thermal magnetic release, with O/L, S/C & EFprotection and ON/ OFF Indicating LED lights complete as perspecifications.

ii) INSTRUMENTS

● 1 No. 0 to 800 Amp Ammeter with Ammeter selector switch & CT's.

● 1 No. 0 to 500 Volt Voltmeter with Voltmeter selector switch.

● 1 Set of RYB indicating lamps with protection MCB.

iii) BUSBARS

● 1000Amp TPN aluminium busbar.

Page 93: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

iv) TIE BREAKER

● 1 No. 500 Amp FP Moulded Case Circuit Breakers (35KA Ics Value)with microprocessor release for O/L, S/C & EF protection and ON/ OFFIndicating LED lights complete as per specifications.

v) OUTGOING

● 6 Nos. 160Amp TP Moulded Case Circuit Breaker (35KA Ics Value)with thermal magnetic release and neutral link.

● 2 Nos. 100Amp TP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release and neutral link.

5.0 COMPACT TYPE SUBSTATIONS (CSS-6)

Supply, Installation, Testing & Commissioning of Compact typesubstation consisting of following equipments mounted in outdoorenclosure fabricated out of galvanised sheet steel complete as perspecifications complete as required. (TOTAL OF A TO C): 1 Set 2,196,000.00 2,196,000.00 (MR)

A) THREE WAY 11KV RING MAIN UNIT

1 No. 200Amp 11KV, TP Vacuum Circuit Breaker encapsulated insteel vessel with SF6 Gas Insulated with self powered IDMT relay typeVIP 35 for protection against phase to phase & phase to earth protectionand 2 Nos. 630 Amp TP Load Break Switch with earth switch completeas required (Three Way RMU with One No. VCB for transformerProtection & 2 Nos. Load break switches).

B) TRANSFORMER (OIL TYPE)

1 No. 500 KVA, 11KV/433V, 3 phase 50Hz. Vector group Dyn-11 Oiltype, ONAN cooled, hermitically sealed, copper wound Distributiontransformer with off load tap changer of range +5% to -5% insteps of2.5%, cable end boxes on HV & LT side with all fittings & accessories,WTI alarm & trip and oil temperature alarm & trip control wiring,complete as per specifications & conforming to IS 2026-1977.

Page 94: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

C) LT BREAKER PANEL

L.T. Panel suitable for 415 volt (nominal) 3 phase 4 wire 50 Hz ACsupply, cubicle type dust and vermin proof compartmentalised indoortype febricated from 2mm thick CRCA sheet steel complete withbusbars, Ammeter, Ammeter Selector switch, voltmeter, voltmeterselector switch, indicating lamp, interconnection and having follwingincoming and outgoing breakers as per drawing and specification.

i) INCOMING

● 1 No. 800 Amp FP manually operated Fixed type (MF) Air CircuitBreaker (50KA) with thermal magnetic release, with O/L, S/C & EFprotection and ON/ OFF Indicating LED lights complete as perspecifications.

ii) INSTRUMENTS

● 1 No. 0 to 800 Amp Ammeter with Ammeter selector switch & CT's.

● 1 No. 0 to 500 Volt Voltmeter with Voltmeter selector switch.

● 1 Set of RYB indicating lamps with protection MCB.

iii) BUSBARS

● 1000Amp TPN aluminium busbar.

iv) TIE BREAKER

● 1 No. 250 Amp FP Moulded Case Circuit Breakers (35KA Ics Value)with microprocessor release for O/L, S/C & EF protection and ON/ OFFIndicating LED lights complete as per specifications.

v) OUTGOING

● 6 Nos. 160Amp TP Moulded Case Circuit Breaker (35KA Ics Value)with thermal magnetic release and neutral link.

● 2 Nos. 100Amp TP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release and neutral link.

Page 95: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

6.0 COMPACT TYPE SUBSTATIONS (CSS - 10)

Supply, Installation, Testing & Commissioning of Compact typesubstation consisting of following equipments mounted in outdoorenclosure fabricated out of galvanised sheet steel complete as perspecifications complete as required. (TOTAL OF A TO C): 1 Set 2,196,000.00 2,196,000.00 (MR)

A) THREE WAY 11KV RING MAIN UNIT

1 No. 200Amp 11KV, TP Vacuum Circuit Breaker encapsulated insteel vessel with SF6 Gas Insulated with self powered IDMT relay typeVIP 35 for protection against phase to phase & phase to earth protectionand 2 Nos. 630 Amp TP Load Break Switch with earth switch completeas required (Three Way RMU with One No. VCB for transformerProtection & 2 Nos. Load break switches).

B) TRANSFORMER (OIL TYPE)

1 No. 500 KVA, 11KV/433V, 3 phase 50Hz. Vector group Dyn-11 Oiltype, ONAN cooled, hermitically sealed, copper wound Distributiontransformer with off load tap changer of range +5% to -5% insteps of2.5%, cable end boxes on HV & LT side with all fittings & accessories,WTI alarm & trip and oil temperature alarm & trip control wiring,complete as per specifications & conforming to IS 2026-1977.

C) LT BREAKER PANEL

L.T. Panel suitable for 415 volt (nominal) 3 phase 4 wire 50 Hz ACsupply, cubicle type dust and vermin proof compartmentalised indoortype febricated from 2mm thick CRCA sheet steel complete withbusbars, Ammeter, Ammeter Selector switch, voltmeter, voltmeterselector switch, indicating lamp, interconnection and having follwingincoming and outgoing breakers as per drawing and specification.

Page 96: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

i) INCOMING

● 1 No. 800 Amp FP manually operated Fixed type (MF) Air CircuitBreaker (50KA) with thermal magnetic release, with O/L, S/C & EFprotection and ON/ OFF Indicating LED lights complete as perspecifications.

ii) INSTRUMENTS

● 1 No. 0 to 800 Amp Ammeter with Ammeter selector switch & CT's.

● 1 No. 0 to 500 Volt Voltmeter with Voltmeter selector switch.

● 1 Set of RYB indicating lamps with protection MCB.

iii) BUSBARS

● 1000Amp TPN aluminium busbar.

iv) TIE BREAKER

● 1 No. 500 Amp FP Moulded Case Circuit Breakers (35KA Ics Value)with microprocessor release for O/L, S/C & EF protection and ON/ OFFIndicating LED lights complete as per specifications.

v) OUTGOING

● 6 Nos. 160Amp TP Moulded Case Circuit Breaker (35KA Ics Value)with thermal magnetic release and neutral link.

● 2 Nos. 100Amp TP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release and neutral link.

7.0 COMPACT TYPE SUBSTATIONS (CSS- 7) [TYPICAL FOR CSS-8]

Supply, Installation, Testing & Commissioning of Compact typesubstation consisting of following equipments mounted in outdoorenclosure fabricated out of galvanised sheet steel complete as perspecifications complete as required. (TOTAL OF A TO C): 2 Set 2,374,000.00 4,748,000.00 (MR)

Page 97: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

A) THREE WAY 11KV RING MAIN UNIT

1 No. 200Amp 11KV, TP Vacuum Circuit Breaker encapsulated insteel vessel with SF6 Gas Insulated with self powered IDMT relay typeVIP 35 for protection against phase to phase & phase to earth protectionand 2 Nos. 630 Amp TP Load Break Switch with earth switch completeas required (Three Way RMU with One No. VCB for transformerProtection & 2 Nos. Load break switches).

B) TRANSFORMER (OIL TYPE)

1 No. 630 KVA, 11KV/433V, 3 phase 50Hz. Vector group Dyn-11 Oiltype, ONAN cooled, hermitically sealed, copper wound Distributiontransformer with off load tap changer of range +5% to -5% insteps of2.5%, cable end boxes on HV & LT side with all fittings & accessories,WTI alarm & trip and oil temperature alarm & trip control wiring,complete as per specifications & conforming to IS 2026-1977.

C) LT BREAKER PANEL

L.T. Panel suitable for 415 volt (nominal) 3 phase 4 wire 50 Hz ACsupply, cubicle type dust and vermin proof compartmentalised indoortype febricated from 2mm thick CRCA sheet steel complete withbusbars, Ammeter, Ammeter Selector switch, voltmeter, voltmeterselector switch, indicating lamp, interconnection and having follwingincoming and outgoing breakers as per drawing and specification.

i) INCOMING

● 1 Nos. 1000 Amp FP manually operated Fixed type (MF) Air CircuitBreaker (50KA) with thermal magnetic release, with O/L, S/C & EFprotection and ON/ OFF Indicating LED lights complete as perspecifications.

Page 98: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

ii) INSTRUMENTS

● 1 No. 0 to 1000 Amp Ammeter with Ammeter selector switch & CT's.

● 1 No. 0 to 500 Volt Voltmeter with Voltmeter selector switch.

● 1 Set of RYB indicating lamps with protection MCB.

iii) BUSBARS

● 1250Amp TPN aluminium busbar.

iv) TIE BREAKER

● 1 No. 500 Amp FP Moulded Case Circuit Breakers (35KA Ics Value)with microprocessor release for O/L, S/C & EF protection and ON/ OFFIndicating LED lights complete as per specifications.

v) OUTGOING

● 8 Nos. 160Amp TP Moulded Case Circuit Breaker (35KA Ics Value)with microprocessor release and neutral link.

8.0 COMPACT TYPE SUBSTATIONS (CSS- 4)

Supply, Installation, Testing & Commissioning of Compact typesubstation consisting of following equipments mounted in outdoorenclosure fabricated out of galvanised sheet steel complete as perspecifications complete as required. (TOTAL OF A TO C): 1 Set 2,388,000.00 2,388,000.00 (MR)

A) THREE WAY 11KV RING MAIN UNIT

1 No. 200Amp 11KV, TP Vacuum Circuit Breaker encapsulated insteel vessel with SF6 Gas Insulated with self powered IDMT relay typeVIP 35 for protection against phase to phase & phase to earth protectionand 2 Nos. 630 Amp TP Load Break Switch with earth switch completeas required (Three Way RMU with One No. VCB for transformerProtection & 2 Nos. Load break switches).

Page 99: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

B) TRANSFORMER (OIL TYPE)

1 No. 630 KVA, 11KV/433V, 3 phase 50Hz. Vector group Dyn-11 Oiltype, ONAN cooled, hermitically sealed, copper wound Distributiontransformer with off load tap changer of range +5% to -5% insteps of2.5%, cable end boxes on HV & LT side with all fittings & accessories,WTI alarm & trip and oil temperature alarm & trip control wiring,complete as per specifications & conforming to IS 2026-1977.

C) LT BREAKER PANEL

L.T. Panel suitable for 415 volt (nominal) 3 phase 4 wire 50 Hz ACsupply, cubicle type dust and vermin proof compartmentalised indoortype febricated from 2mm thick CRCA sheet steel complete withbusbars, Ammeter, Ammeter Selector switch, voltmeter, voltmeterselector switch, indicating lamp, interconnection and having follwingincoming and outgoing breakers as per drawing and specification.

i) INCOMING

● 1 Nos. 1000 Amp FP manually operated Fixed type (MF) Air CircuitBreaker (50KA) with thermal magnetic release, with O/L, S/C & EFprotection and ON/ OFF Indicating LED lights complete as perspecifications.

ii) INSTRUMENTS

● 1 No. 0 to 1000 Amp Ammeter with Ammeter selector switch & CT's.

● 1 No. 0 to 500 Volt Voltmeter with Voltmeter selector switch.

● 1 Set of RYB indicating lamps with protection MCB.

iii) BUSBARS

● 1250Amp TPN aluminium busbar.

Page 100: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

iv) TIE BREAKER

● 1 No. 400 Amp FP Moulded Case Circuit Breakers (35KA Ics Value)with microprocessor release for O/L, S/C & EF protection and ON/ OFFIndicating LED lights complete as per specifications.

v) OUTGOING

● 2 Nos. 300Amp TP Moulded Case Circuit Breaker (35KA Ics Value)with microprocessor release and neutral link.

● 5 Nos. 200Amp TP Moulded Case Circuit Breaker (25KA Ics Value)with thermal magnetic release and neutral link.

9.0 DISTRIBUTION FEEDER PILLAR

Supply, installation, testing & commissioning of Double door type withslanting top dust, damp, vermin proof, weather proof type DistributionFeeder Pillars fabricated from 2mm thick CRCA sheet including opening handle,locking arrangement complete with incomer MCCB, busbar,indicating lights, protection mcbs, including all civil works likeexcavation, PCC, bricks work, plastering, refilling, providing PVCsleeves in foundation (Feeder Pillar foundation shall be of brick workminimum 600mm above from Ground level) etc. including epoxypainting of feeder pillar, interconnection etc complete as perspecifications as required.

10.1 I/FP-1 TYPICAL FOR III/FP-1, III/FP-2, IV/FP-1, IV/FP-2, IV/FP-3, IV/FP-4 (TOTAL A TO D). 7 Set 180,000.00 1,260,000.00 (MR)

A) INCOMING

● 1 No. 200Amp Four Pole Moulded Case Circuit Breaker of (35KA IcsValue) with thermal magnetic release, O/L, S/C & E/F protection.

B) INSTRUMENTS

● 1No. 0-200 Ammeter with selector switch and CT's.

Page 101: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

● 1No. 0 -500 Volt voltmeter with selector switch.

● 1Set of phase indicating lamps with SP MCB.

C) BUSBARS

● 250Amp TPN busbars of aluminium alloy.

D) OUTGOING

● 9 Nos. 40-63Amp Three Pole Moulded Case Circuit Breaker (25KA IcsValue) with thermal magnetic release, O/L, S/C & E/F protection andneutral link.

10.2 I/FP-2 (TOTAL A TO D). 1 Set 207,000.00 207,000.00 (MR)

A) INCOMING

● 1 No. 300Amp Four Pole Moulded Case Circuit Breaker of (35KA IcsValue) with microprocessor release, O/L, S/C & E/F protection.

B) INSTRUMENTS

● 1No. 0-300 Ammeter with selector switch and CT's.

● 1No. 0 -500 Volt voltmeter with selector switch.

● 1Set of phase indicating lamps with SP MCB.

C) BUSBARS

● 400Amp TPN busbars of aluminium alloy.

D) OUTGOING

● 10 Nos. 40-63Amp Three Pole Moulded Case Circuit Breaker (25KAIcs Value) with thermal magnetic release, O/L, S/C & E/F protection andneutral link.

Page 102: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

10.3 IV/FP-5 (TOTAL A TO D). 1 Set 258,000.00 258,000.00 (MR)

A) INCOMING

● 1 No. 300Amp Four Pole Moulded Case Circuit Breaker of (35KA IcsValue) with microprocessor release, O/L, S/C & E/F protection.

B) INSTRUMENTS

● 1No. 0-300 Ammeter with selector switch and CT's.

● 1No. 0 -500 Volt voltmeter with selector switch.

● 1Set of phase indicating lamps with SP MCB.

C) BUSBARS

● 400Amp TPN busbars of aluminium alloy.

D) OUTGOING

● 2 Nos. 100Amp Three Pole Moulded Case Circuit Breaker (25KA IcsValue) with thermal magnetic release, O/L, S/C & E/F protection andneutral link.

● 10 Nos. 40-63Amp Three Pole Moulded Case Circuit Breaker (25KAIcs Value) with thermal magnetic release, O/L, S/C & E/F protection andneutral link.

TOTAL OF SUBHEAD V - COMPACT TYPE SUBSTATION &DISTRIBUTION FEEDER PILLARS CARRIED OVER TO THESUMMARY.

0.00 23,998,000.00

Page 103: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

VI. L.T. CABLES

1.0 Supply of following size of 1.1KV grade multicore aluminiumconductor XLPE / PVC insulated & PVC sheathed armoured cable asper IS: 7098 (Part-1) 1988 complete as required.

i) 3.5 core, 400 Sq.mm. 39130 M. 1,844.00 72,155,720.00 (MR)

ii) 3.5 core, 300 Sq.mm. 7410 M. 1,443.00 10,692,630.00 (MR)

iii) 3.5 core, 240 Sq.mm. 2240 M. 1,185.00 2,654,400.00 (MR)

iv) 3.5 core, 185 Sq.mm. 490 M. 938.00 459,620.00 (MR)

v) 3.5 core, 150 Sq.mm. 2330 M. 759.00 1,768,470.00 (MR)

vi) 3.5 core, 120 Sq.mm. 9670 M. 640.00 6,188,800.00 (MR)

vii) 3.5 core, 95 Sq.mm. 360 M. 510.00 183,600.00 (MR)

viii) 3.5 core, 50 Sq.mm. 50 M. 303.00 15,150.00 (MR)

ix) 3.5 core, 35 Sq.mm. 3160 M. 235.00 742,600.00 (MR)

x) 4 core, 400 Sq.mm. 1860 M. 2,065.00 3,840,900.00 (MR)

xi) 4 core, 25 Sq.mm. 7040 M. 205.00 1,443,200.00 (MR)

xii) 4 core, 16 Sq.mm. 1910 M. 149.00 284,590.00 (MR)

2.0 Laying of one number PVC insulated and PVC sheathed / XLPE powercable of 1.1 KV grade of following size direct in ground includingexcavation, sand cushioning, protective covering and refilling the trenchetc as required.

7.1(DSR-2013)

i) Upto 35 sq. mm 6010 M. 181.00 1,087,810.00 7.1.1

ii) Above 35 sq. mm and upto 95 sq. mm 290 M. 188.00 54,520.00 7.1.2

iii) Above 95 sq. mm and upto 185 sq. mm 6000 M. 195.00 1,170,000.00 7.1.3

iv) Above 185 sq. mm and upto 400 sq. mm 23600 M. 215.00 5,074,000.00 7.1.4

Page 104: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

3.0 Laying of one number additional PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size direct in ground inthe same trench in one tier horizontal formation including excavation,sand cushioning, protective covering and refilling the trench etc asrequired.

7.2(DSR-2013)

i) Upto 35 sq. mm 4700 M. 124.00 582,800.00 7.2.1

iii) Above 95 sq. mm and upto 185 sq. mm 4750 M. 138.00 655,500.00 7.2.3

iv) Above 185 sq. mm and upto 400 sq. mm 15940 M. 159.00 2,534,460.00 7.2.4

4.0 Laying of one number PVC insulated and PVC sheathed / XLPE powercable of 1.1 KV grade of following size in the existing RCC/ HUME/METAL pipe as required.

7.5(DSR-2013)

i) Upto 35 sq. mm 1000 M. 15.00 15,000.00 7.5.1

ii) Above 35 sq. mm and upto 95 sq. mm 40 M. 23.00 920.00 7.5.2

iii) Above 95 sq. mm and upto 185 sq. mm 1120 M. 30.00 33,600.00 7.5.3

iv) Above 185 sq. mm and upto 400 sq. mm 4000 M. 53.00 212,000.00 7.5.4

5.0 Laying of one number PVC insulated and PVC sheathed / XLPE powercable of 1.1 KV grade of following size in the existing masonry openduct as required.

7.6(DSR-2013)

i) Upto 35 sq. mm 200 M. 11.00 2,200.00 7.6.1

ii) Above 35 sq. mm and upto 95 sq. mm 40 M. 18.00 720.00 7.6.2

iii) Above 95 sq. mm and upto 185 sq. mm 320 M. 25.00 8,000.00 7.6.3

iv) Above 185 sq. mm and upto 400 sq. mm 1600 M. 45.00 72,000.00 7.6.4

6.0 Laying and fixing of one number PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size on cable Tray asrequired.

7.8(DSR-2013)

i) Upto 35 sq. mm (clamped with 1mm thick saddle) 200 M. 19.00 3,800.00 7.8.1

Page 105: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

ii) Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) 40 M. 44.00 1,760.00 7.8.2

iii) Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) 300 M. 54.00 16,200.00 7.8.3

iv) Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) 5500 M. 84.00 462,000.00 7.8.4

7.0 Suppling and making indoor end termination with brass compressiongland and aluminium lugs for following size of PVC insulated and PVCsheathed / XLPE aluminium conductor cable of 1.1 KV grade asrequired.

9.1(DSR-2013)

i) 3.5 core, 400 Sq.mm. 304 Set 1,203.00 365,712.00 9.1.31

ii) 3.5 core, 300 Sq.mm. 156 Set 940.00 146,640.00 9.1.30

iii) 3.5 core, 240 Sq.mm. 26 Set 824.00 21,424.00 9.1.29

iv) 3.5 core, 185 Sq.mm. 4 Set 671.00 2,684.00 9.1.27

v) 3.5 core, 150 Sq.mm. 24 Set 501.00 12,024.00 9.1.26

vi) 3.5 core, 120 Sq.mm. 128 Set 417.00 53,376.00 9.1.25

vii) 3.5 core, 95 Sq.mm. 2 Set 401.00 802.00 9.1.24

viii) 3.5 core, 50 Sq.mm. 4 Set 286.00 1,144.00 9.1.22

ix) 3.5 core, 35 Sq.mm. 30 Set 245.00 7,350.00 9.1.21

x) 4 core, 400 Sq.mm. 12 Set 1,203.00 14,436.00 9.1.31

xi) 4 core, 25 Sq.mm. 122 Set 211.00 25,742.00 9.1.34

xii) 4 core, 16 Sq.mm. 42 Set 208.00 8,736.00 9.1.33

8.0 Supply and installing following size of perforated M.S. cable trays withperforation not more than 17.5% in convenient sections, joints withconnectors suspended from the ceiling with M.S. suspenders andincluding bolts & nuts, painting suspenders etc. as required.

4.1(DSR-2013)

i) 150 mm width X 50 mm depth X 1.6 mm thickness 150 M. 523.00 78,450.00 4.1.2

ii) 300 mm width X 50 mm depth X 1.6 mm thickness 75 M. 756.00 56,700.00 4.1.4

iii) 600 mm width X 50 mm depth X 2.0 mm thickness 75 M. 1,338.00 100,350.00 4.1.7

Page 106: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Rate as per DSR

(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.)

DSR -2013 / MR

Item No. /Sub-Head Description Qty. Unit

TOTAL OF SUBHEAD VI - SUBMAIN CABLES CARRIEDOVER TO THE SUMMARY. 12,882,860.00 100,429,680.00

VII. EARTHING

1.0 Earthing with copper earth plate 600 mm X 600 mm X 3 mm thickincluding accessories, and providing masonry enclosure with cover platehaving locking arrangement and watering pipe of 2.7 metre long etc.with charcoal/ coke and salt as required. 60 Set 8,939.00 536,340.00

5.6(DSR-2013)

2.0 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thickincluding accessories, and providing masonry enclosure with cover platehaving locking arrangement and watering pipe of 2.7 metre long etc.with charcoal/ coke and salt as required. 112 Set 4,367.00 489,104.00

5.4(DSR-2013)

3.0 Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipefrom earth electrode including connection with brass nut, bolt, spring,washer excavation and re-filling etc. as required. 600 M. 1,019.00 611,400.00

5.10(DSR-2013)

4.0 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipefrom earth electrode including connection with G.I. nut, bolt, spring,washer excavation and re-filling etc. as required. 1250 M. 391.00 488,750.00

5.11(DSR-2013)

5.0 Providing and fixing 25 mm X 5 mm copper strip on surface or in recessfor connections etc. as required. 200 M. 812.00 162,400.00

5.14(DSR-2013)

6.0 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess forconnections etc. as required. 400 M. 133.00 53,200.00

5.15(DSR-2013)

7.0 Providing and fixing 6 SWG dia G.I. wire on surface or in recess forloop earthing as required. 400 M. 34.00 13,600.00

5.16(DSR-2013)

TOTAL OF SUBHEAD VII - EARTHING CARRIED OVER TOTHE SUMMARY. 2,354,794.00 0.00

Page 107: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

DSR-2013 MR TOTAL

I. EXTERNAL LIGHTING WORKS 10,661,050.00 77,807,400.00 88,468,450.00

TOTAL OF EXTERNAL ELECTRICAL WORKS 88,468,450.00

SAY 88,468,450.00

TENDER FOR SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 11/0.433KV INDOOR/OUTDOOR ELECTRIC SUBSTATION AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE

BAGLA, DISTT. SAMBA (J&K)

SECTION - C: ABSTRACT COST FOR EXTERNAL ELECTRICAL WORKS

(POWER SUPPLY PACKAGE & EXTERNAL ELECTRICAL WORKS)

SUMMARY SHEET

SUB-HEAD SH. DESCRIPTIONESTIMATED COST IN RUPEES

Page 108: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

1.0 FEEDER PILLARS (EXTERNAL LIGHTING)

Supply, installation, testing & commissioning of dust, damp, verminproof, weather proof type fabricated from 2mm thick CRCA sheetsteel including locking arrangement complete with incomer MCCB,busbar, ammeter, ammeter selector switch, voltmeter, voltmeterselector switch, CT's, indicator lights, protection mcb including allcivil works (Feeder Pillar foundation) like excavation, PCC, brickswork, plastering, refilling, providing PVC sleeves in foundation etc.including epoxy painting of feeder pillar, interconnection etccomplete as per specifications as required. (Note : Feeder Pillar-I -Not in scope of this contract)

1.1 FEEDER PILLAR-(EXTERNAL LIGHTING - 2) TYPICALFOR [FEEDER PILLAR EXT/L4, EXT/L-5, EXT/L-10] 4 Set 94,000.00 376,000.00 (MR)

A) INCOMING

● 1 No. 63 Amp FP Moulded Case circuit Breaker of 25KA (IcsValue) with O/L, S/C & E/F protection.

● 1 Set of 3 pole 70Amp power contactor , Astronomical Timer switchDIN mounting & Toggle switch for auto / manual operation of Roadlighting complete as required.

B) INSTRUMENTS WITH INCOMER

● 1 No. 0 to 500Volt voltmeter with selector switch.

● 1No. 0 to 63Amp ammeter with selector switch & CT's.

● 1 Sets of ON / OFF indicating lamps

● 1 Sets of RYB indicating lamps with SP MCB.

Qty. UnitRate as per

DSR(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

TENDER FOR SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 11/0.433KV INDOOR/OUTDOOR ELECTRIC SUBSTATION AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE

BAGLA, DISTT. SAMBA (J&K)

SECTION - C: ABSTRACT COST FOR EXTERNAL ELECTRICAL WORKS

(POWER SUPPLY PACKAGE & EXTERNAL ELECTRICAL WORKS)

Amount as per NON DSR

(In Rs.) DSR -2013 / MR

Item No. /Sub-Head Description

Page 109: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Qty. UnitRate as per

DSR(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.) DSR -2013 / MR

Item No. /Sub-Head Description

C) BUSBARS

● 1 Set of 100Amp TPN busbars of aluminium alloy.

D) OUTGOING

● 12 Nos. 10-32 Amp four pole Miniature Circuit Breaker (10KA).

● 9 Nos. 10-32 Amp double pole Miniature Circuit Breaker (10KA).

1.2 FEEDER PILLAR (EXTERNAL LIGHTING - 6) TYPICALFOR FEEDER PILLAR EXT/L-7, EXT/L-8, EXT/L-9 4 Set 230,000.00 920,000.00 (MR)

A) INCOMING

● 1 No. 100 Amp FP Moulded Case circuit Breaker of 25KA (IcsValue) with O/L, S/C & E/F protection.

● 1 Set of 3 pole 110Amp power contactor , Astronomical Timerswitch DIN mounting & Toggle switch for auto / manual operationof Road lighting complete as required.

B) INSTRUMENTS WITH INCOMER

● 1 No. 0 to 500Volt voltmeter with selector switch.

● 1No. 0 to 100Amp ammeter with selector switch & CT's.

● 1 Sets of ON / OFF indicating lamps

● 1 Sets of RYB indicating lamps with SP MCB.

C) BUSBARS

● 1 Set of 150Amp TPN busbars of aluminium alloy ( For Bus Section-I)

● 1 Set of 100Amp TPN busbars of aluminium alloy ( For Bus Section-II)

D) OUTGOING

● 9 No. 40-63 Amp FP Moulded Case circuit Breaker of 25KA (IcsValue).

Page 110: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Qty. UnitRate as per

DSR(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.) DSR -2013 / MR

Item No. /Sub-Head Description

● 15 Nos. 10-32 Amp Four pole Miniature Circuit Breaker (10KA).

● 9 Nos. 10-32 Amp double pole Miniature Circuit Breaker (10KA).

1.3 FEEDER PILLAR (EXTERNAL LIGHTING - 3) TYPICALFOR FEEDER PILLAR EXT/L-11, EXT/L-12, EXT/L-13 4 Set 281,000.00 1,124,000.00 (MR)

A) INCOMING

● 1 No. 100 Amp FP Moulded Case circuit Breaker of 25KA (IcsValue) with O/L, S/C & E/F protection.

● 1 Set of 3 pole 110Amp power contactor , Astronomical Timerswitch DIN mounting & Toggle switch for auto / manual operationof Road lighting complete as required.

B) INSTRUMENTS WITH INCOMER

● 1 No. 0 to 500Volt voltmeter with selector switch.

● 1No. 0 to 100Amp ammeter with selector switch & CT's.

● 1 Sets of ON / OFF indicating lamps

● 1 Sets of RYB indicating lamps with SP MCB.

C) BUSBARS

● 1 Set of 150Amp TPN busbars of aluminium alloy ( For Bus Section-I)

● 1 Set of 100Amp TPN busbars of aluminium alloy ( For Bus Section-II)

D) OUTGOING

● 12 Nos. 40-63 Amp FP Moulded Case circuit Breaker of 25KA (IcsValue).

● 18 Nos. 10-32 Amp Four pole Miniature Circuit Breaker (10KA).

● 9 Nos. 10-32 Amp double pole Miniature Circuit Breaker (10KA).

Page 111: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Qty. UnitRate as per

DSR(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.) DSR -2013 / MR

Item No. /Sub-Head Description

2.0 POLES

2.1 Design, Manufacture, Supply, installation, testing & commissioningof 20mtr high mast complete in all respects including electricallyoperated raising and lowering gears double drum winch with steelwire ropes, integral power tool, lantern carriage, top pulleyarrangement complete with hot dip galvanised finished, civil RCCfoundation with excavation in soil, foundation bolts, anchor plates,nuts, washers including multicore copper conductor cable (Trailingcable) in two circuits ( one for HPSV fixtures and other for halogenfixtures) of suitable current carrying capacity between top carriageand the base terminal (inside mast) including provision of out doortype double doors feeder pillar made out of 2mm thick CRCA sheetwith powder coated paint comprising of suitable rating one numberincomer TP MCCB of 25KA and two numbers out going circuitswith TP MCB(s) of 10KA , Auto ON / OFF with Astronomicalswitch, contactor(s) , timer for switching off of halogen fixtures after5min when power supply ON by day time switch, toggle switche(s),interconnecting copper cables, etc as required suitable for operationon 415 V, 3 phase, 50 Hz, AC power supply. Each mast shall becomplete with 1 nos. 1000W halogen fixtures of Schreder Cata ref.RT4, 4 nos. 2x250 W HPSV and 4 nos. 1x250 W HPSV of SchrederCata ref. RT3 therefore Lantern carriage, switch gears and cablesizes shall be designed/ selected accordingly including wiring withsuitable size 3 core cable in flexible GI conduit, connectioncomplete as required. The scope of work also covers provision oflightning arrester. One No. LED obstruction light fixtures erectedwith lantern carriage & connected in two separate wiring/connections from mast control board, extending earth strip fromfeeder pillar to mast body, connections, interconnections, completeas required and as specified.

10 Set 626,900.00 6,269,000.00 (MR)NOTE :-

a) Provision of earth pits & earth strip interconnections from earth pitto feeder pillar not included in above item. This shall be paid underseparate items.

Page 112: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Qty. UnitRate as per

DSR(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.) DSR -2013 / MR

Item No. /Sub-Head Description

b) Barricade for the entire high mast & feeder pillar shall be paid underseparate item.

2.2 Design, Manufacture, Supply, installation, testing & commissioningof 16mtr high mast complete in all respects including electricallyoperated raising and lowering gears double drum winch with steelwire ropes, integral power tool, lantern carriage, top pulleyarrangement complete with hot dip galvanised finished, civil RCCfoundation with excavation in soil, foundation bolts, anchor plates,nuts, washers including multicore copper conductor cable (Trailingcable) in two circuits ( one for HPSV fixtures and other for halogenfixtures) of suitable current carrying capacity between top carriageand the base terminal (inside mast) including provision of out doortype double doors feeder pillar made out of 2mm thick, CRCA sheetsteel with powder coated paint comprising of suitable rating onenumber incomer TP MCCB of 25KA and two numbers out goingcircuits with TP MCB(s) of 10KA , Auto ON / OFF with day timeswitch, contactor(s) , timer for switching off of halogen fixtures after5min when power supply ON by day time switch, toggle switche(s),interconnecting copper cables, etc as required suitable for operationon 415 V, 3 phase, 50 Hz, AC power supply. Each mast shall becomplete with 1 nos. 1000W halogen fixtures of Schreder Cata ref.RT4, 4 nos. 2x250 W HPSV and 4 nos. 1x250 W HPSV of SchrederCata ref. RT3 therefore Lantern carriage, switch gears and cablesizes shall be designed/ selected accordingly including wiring withsuitable size 3 core cable in flexible GI conduit, connectioncomplete as required. The scope of work also covers provision oflightning arrester. two Nos. LED obstruction light fixtures erectedwith lantern carriage & connected in two separate wiring/connections from mast control board, extending earth strip fromfeeder pillar to mast body, connections, interconnections, completeas required and as specified.

24 Set 556,500.00 13,356,000.00 (MR)

Page 113: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Qty. UnitRate as per

DSR(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.) DSR -2013 / MR

Item No. /Sub-Head Description

NOTE :-

a) Provision of earth pits & earth strip interconnections from earth pitto feeder pillar not included in above item. This shall be paid underseparate items.

b) Barricade for the entire high mast & feeder pillar coverd undercivil scope of work.

2.3 Design, manufacture & supply of 6 Metre long MS Pole with Baseplate of minimum 300mm x 300mm duly weld at bottom of pole andpole diameter of 140mm at bottom & 76mm at top. Pole shall becomplete with in built cable loop in box and pole shall be as perfollowing specifications :- 735 No. 27,300.00 20,065,500.00 (MR)

● Steel pole shall be made out of MS pipe section with die-castaluminium embellishments.

● Base made of die cast MS with holes suitable for minimum 12mmfoundation bolts

● Pole are painted with multiple coats of weather resistantpolyurethane paint.

● Coutout at the lower part of the pole suitable for cable looping,MCB, connectors etc. shall be provided.

2.4 Design, manufacture & supply of 4 Metre long MS Pole with Baseplate of minimum 300mm x 300mm duly weld at bottom of pole andpole diameter of 140mm at bottom & 76mm at top. Pole shall becomplete with in built cable loop in box and pole shall be as perfollowing specifications :- 300 No. 25,600.00 7,680,000.00 (MR)

● Steel pole shall be made out of MS pipe section with die-castaluminium embellishments.

● Base made of die cast MS with holes suitable for minimum 12mmfoundation bolts

Page 114: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Qty. UnitRate as per

DSR(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.) DSR -2013 / MR

Item No. /Sub-Head Description

● Pole are painted with multiple coats of weather resistantpolyurethane paint.

● Coutout at the lower part of the pole suitable for cable looping,MCB, connectors etc. shall be provided.

3.0 Erection of metallic pole of following length in cement concrete1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mmnominal size) foundation including excavation and refilling etc. asrequired.

11.3(DSR-2013)

i) Above 4.0 metre and upto 6.5 metre 1035 No. 2,311.00 2,391,885.00 11.3.1

4.0 Supply of Road lighting LED light fixtures made out of Extrudedaluminium with moulded poly carbonate cover, optical compartmentIP 66, a separate IP 66 controlgear compartment, a toughened glassprotector premanently sealed mounting Spigot suitable for horizontalmounting (dia 32 to 42mm) with tilt flexibility of + 10 Degree, withlensoflex2 technology, PMMA lenses for wider photometry withsurge protection of 10KV, power factor > 0.90, colour renderingindex 65 & of neutral white light (4100OK). Manufacturer toguarantee minimum life of LED of 50000 hours. complete asrequired.

a) 27Watt LED Light Fixture with 0.5mtr. Single arm bracket ofSchereder Cata Ref. BRIKA or approved equivalent. 340 No. 14,200.00 4,828,000.00 (MR)

b) 42Watt LED Light Fixture with 0.5mtr. Single arm bracket ofSchereder Cata Ref. BRIKA or approved equivalent. 335 No. 18,200.00 6,097,000.00 (MR)

5.0 Supply of Post top lantern type LED light fixtures of 53 watt withbase section & cover made out of die cast aluminium alloy,protectors made of SLX plycarbonate, minimum impact resistenceIK 10 (anti UV) optical complartment IP 66, Light fixture withlensoflex 2 technology for wider light distribution and sitereplacement lenso flex module, manufacture to confirm life timeguarantee of 50000 hours for LEDs complete as required. ofSchereder cata ref. HAPILED or approved equivalent. 300 No. 36,600.00 10,980,000.00 (MR)

Page 115: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Qty. UnitRate as per

DSR(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.) DSR -2013 / MR

Item No. /Sub-Head Description

6.0 Supply of 1 x 150 watt metal halide Flood light fixture consisting oftwo parts made of painted , die cast Aluminium Alloy complete with150 watt metal halide lamp, control gear & all accessories asrequired similar to Keselec Schreder Cata Ref. RT3 –NB-150-83complete or approved equivalent.

30 No. 17,900.00 537,000.00 (MR)

7.0 Supply of 1 x 250 watt metal halide Flood light fixture consisting oftwo parts made of painted , die cast Aluminium Alloy complete with250 watt metal halide lamp, control gear & all accessories asrequired similar to Keselec Schreder Cata Ref. RT3 –NB-250-83 complete or approved equivalent. 30 No. 18,700.00 561,000.00 (MR)

8.0 Installation, testing & commissioning of LED Road Light Fixtureon existing 6 Meter high Pole including connection as required. 675 M 300.00 202,500.00 (MR)

9.0 Installation, testing & commissioning of LED outdoor Light Fixture(Post top Lantern) on existing 4 Meter high Pole includingconnection as required. 300 No. 300.00 90,000.00 (MR)

10.0 Supply of following size of 1.1KV grade multicore aluminiumconductor XLPE insulated & PVC sheathed armoured cable as perIS:7098 (Part-I) 1988.

i) 4 Core 10 Sq.mm. 31,200 M 137.00 4,274,400.00 (MR)

ii) 4 Core 16 Sq.mm. 3,000 M 149.00 447,000.00 (MR)

11.0 Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 1.1 KV grade of following size direct in groundincluding excavation, sand cushioning, protective covering andrefilling the trench etc as required. 7.1

(DSR-2013)

i) Upto 35 sq.mm 19,600 M 181.00 3,547,600.00 7.1.1

Page 116: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Qty. UnitRate as per

DSR(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.) DSR -2013 / MR

Item No. /Sub-Head Description

12.0 Laying of one number additional PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size direct inground in the same trench in one tier horizontal formation includingexcavation, sand cushioning, protective covering and refilling thetrench etc as required.

7.2(DSR-2013)

i) Upto 35 sq. mm 12,600 M 124.00 1,562,400.00 7.2.1

13.0 Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 1.1 KV grade of following size in the existing RCC/HUME/ METAL pipe as required.

7.5(DSR-2013)

i) Upto 35 sq. mm 2,000 M 15.00 30,000.00 7.5.1

14.0 Providing, laying and fixing following dia RCC pipe NP2 class(light duty) in ground complete with RCC collars, jointing withcement mortar 1:2 (1 cement : 2 fine sand) including trenching (75cm deep) and refilling etc as required.

14.14(DSR-2013)

i) 150 mm dia 1000 M 357.00 357,000.00 14.14.2

15.0 Supply & making end termination with brass compression gland &aluminium lugs for following size of PVC insulated and PVCsheathed / XLPE aluminium conductor cable of 1.1KV grade asrequired.

9.1(DSR-2013)

i) 4 Core 10 Sq.mm. 2,326 Set 163.00 379,138.00 9.1.32

ii) 4 Core 16 Sq.mm. 128 Set 208.00 26,624.00 9.1.33

16.0 Supplying and drawing following sizes of FR PVC insulated copperconductor, single core cable in the existing surface/ recessed steel/PVC conduit as required. (Wiring for Cable loop in box upto Lightfixture mounted on pole)

1.17(DSR-2013)

i) 3 x 2.5 Sq.mm. 7,000 M. 77.00 539,000.00 1.17.12

Page 117: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

Qty. UnitRate as per

DSR(In Rs.)

Rate as per NON-DSR

(In Rs.)

Amount as per DSR

(In Rs.)

Amount as per NON DSR

(In Rs.) DSR -2013 / MR

Item No. /Sub-Head Description

17.0 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thickincluding accessories, and providing masonry enclosure with coverplate having locking arrangement and watering pipe of 2.7 metrelong etc. with charcoal/ coke and salt as required. 84 Set 4,367.00 366,828.00

5.4(DSR-2013)

18.0 Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia includingaccessories, and providing masonry enclosure with cover platehaving locking arrangement and watering pipe etc. with charcoal/coke and salt as required.

120 Set 3,753.00 450,360.005.2

(DSR-2013)

19.0 Supplying and laying 6 SWG G.I. wire at 0.50 metre below groundlevel for conductor earth electrode, including connection/termination with GI thimble etc. as required (from pole to pole) 33,000 M 25.00 825,000.00

5.7(DSR-2013)

20.0 Providing and laying earth connection from earth electrode with 6SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrodeincluding connection with G.I. thimble excavation and re-fillingrequired. 330 M 136.00 44,880.00

5.12(DSR-2013)

21.0 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I.pipe from earth electrode including connection with G.I. nut, bolt,spring, washer excavation and re-filling etc. as required. 330 M 391.00 129,030.00

5.11(DSR-2013)

22.0 Providing and fixing 25 mm X 5 mm G.I. strip on surface or inrecess for connections etc. as required. 85 M 133.00 11,305.00

5.15(DSR-2013)

TOTAL OF EXTERNAL ELECTRICAL WORKS CARRIED OVER TO THE SUMMARY. 10,661,050.00 77,807,400.00

Page 118: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

S.No. Sub Head DSR Amount ( Rs) Non DSR Amount ( Rs) )

1 EARTH WORK : Rs. 2344017.13 1392000.00

2 CONCRETE WORK : Rs. 3506114.70 0.00

3 REINFORCEMENT CEMENT CONCRETE : Rs. 26485125.00 0.00

4 BRICK WORK : Rs. 6436116.00 0.00

5 FLOORING : Rs. 3617814.00 0.00

6 FINISHING : Rs. 3324034.20 7200.00

7 STEEL WORK : Rs. 3286910.10 0.00

8 ROOFING : Rs. 63605.70 0.00

9 WATERPROOFING WORK : Rs. 1094720.70 0.00

Sub Total : Rs. 50158457.53 1399200.00

Amount of DSR items 50158457.53

say : Rs. 50158458.00Amount of Non DSR items 1399200.00

say : Rs. 1399200.00

Grand Total (DSR + Non DSR) Say Rs. 51557658.00

TENDER FOR SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 11/0.433KV INDOOR/OUTDOOR ELECTRIC SUBSTATION AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ)

AT VILLAGE BAGLA, DISTT. SAMBA (J&K)

SECTION D: ABSTRACT COST FOR CIVIL WORK

(CIVIL WORKS)

SUMMARY SHEET

Page 119: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

S.No. Description.

Qty.for one sub station

block

Qty.for six sub station

block

Unit. Rate in Figures (in Rs.) DSR

Rate in Figures (in

Rs.) NON DSR

DSR Amount ( in Rs.)

NON DSR/ MR Amount (

in Rs.)

Ref DSR -2013 Item

no

1 2 3 4 5 6 7 8 9Note: This BOQ to be read in conjunction with generel

conditions, special conditions, LEED/ GRIHA conditions and

other tender document.1.00 SUB-HEAD : I : EARTH WORK :-

1.01 Earth work in excavation by mechanical means (Hydraulic

excavator) / manual means over areas (exceeding 30cm in

depth. 1.5m in width as well as 10 sqm on plan) including

disposal of excavated earth, lead upto 50m and lift upto 1.5m,

disposed earth to be levelled and neatly dressed.All kinds of soil

including river pebbles. 919.0 5514 Cum 146.5 807801.00 2.6.1

1.02 Filling available excavated earth (excluding rock) in trenches,

plinth, sides of foundations etc. in layers not exceeding 20 cm in

depth, consolidating each deposited layer by ramming and

watering, lead up to 50 m & lift upto 1.5 m. 306.0 1836 Cum 101.50 186354.00 2.25

1.03 Supplying and filling in plinth with river sand under floorsincluding, watering, ramming consolidating and dressingcomplete. 74.0 444 Cum 843.65 374580.60 2.27

1.04 Extra for every additional lift of 1.5 m or part thereof in.a) All kinds of soil including river pebbles. 315.0 1890 Cum 41.75 78907.50 2.26.1

TENDER FOR SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 11/0.433KV INDOOR/OUTDOOR ELECTRIC SUBSTATION AND OTHER ASSOCIATED EXTERNAL ELECTRICAL WORKS FOR THE PERMANENT CAMPUS OF THE CENTRAL UNIVERSITY OF JAMMU (CUJ) AT VILLAGE BAGLA, DISTT. SAMBA (J&K)

SECTION D: ABSTRACT COST FOR CIVIL WORK

(CIVIL WORKS)

Page 120: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

S.No. Description.

Qty.for one sub station

block

Qty.for six sub station

block

Unit. Rate in Figures (in Rs.) DSR

Rate in Figures (in

Rs.) NON DSR

DSR Amount ( in Rs.)

NON DSR/ MR Amount (

in Rs.)

Ref DSR -2013 Item

no

1 2 3 4 5 6 7 8 91.05 Carriage of materials by mechanical transport inclluding loading &

unloading and dressing complete for a lead of 5 KM including

the initial lead of 50 mtr out side the site premises as per

direction by Engineer-in-Charge.(a) Earth including river pebbles. 613.0 3678 Cum 153.30 563837.40 1.1.2

1.06 Excavating trenches of required width for pipes, cables, etc.,

including excavation for sockets and dressing of sides, ramming

of bottoms, depth upto 1.5m including taking out the excavated

soil and then returning the soil as required in layers, not

exceeding 20cm in depth including consolidating each deposited

layer by ramming, watering, etc., and disposing of surplus

excavated soil as directed within a lead of 50m.All kind of soils a) Pipes, cables etc not exceeding 80mm dia . 20.0 120 metre 118.00 14160.00 2.10.1.1

b) Pipes, cables etc exceeding 80mm dia but not exceeding300mm dia. 50.0 300 metre 414.75 124425.00 2.13.1.2

c) Pipes, cables etc exceeding 300mm dia but not exceeding600mm dia. 50.0 300 metre 477.30 143190.00 2.13.1.3

1.07 Clearing jungle including uprooting of rank vegetation grass,

brush wood, trees and saplings of girth upto 30cm measured at a

height of 1m above ground level and removal of rubbish inclusive

of uprooted items upto a distance of 50m outside the periphery

of the area cleared: 473.0 2838 100 sqm 579.55 16447.63 2.31

Page 121: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

S.No. Description.

Qty.for one sub station

block

Qty.for six sub station

block

Unit. Rate in Figures (in Rs.) DSR

Rate in Figures (in

Rs.) NON DSR

DSR Amount ( in Rs.)

NON DSR/ MR Amount (

in Rs.)

Ref DSR -2013 Item

no

1 2 3 4 5 6 7 8 91.08 Providing and injecting chemical emulsion chlorophyriphos 20 %

emulsifiable concentrates with 1% concentration or Lindane 20

% emulsifiable concentrates with 1 % concentration as IS 6313

pre-constructional anti -termite treatment and creating a

contineous chemical barrier under and alround the column pits,

wall trenches, basements excavation, top surface of plinth filling,

junction of wall and floor along the external perimeter of the of

the building, expansion joints over the top surface of

consolidated earth on which apron is to be laid, surroundings of

pipes and conduits etc. complete as per specifications . The work

shall be carried out by a specialised agency and shall carry a

performance guarantee on stamp paper for 10 years ((Plinth

area at ground floor level to be measured and paid for ) ) 315.0 1890 sqm 550.00 1039500.00 MR

1.09 Earth work in excavation by mechanical means (Hydraulic

excavator) / manual means over areas (exceeding 30cm in

depth. 1.5m in width as well as 10 sqm on plan) including

disposal of excavated earth, lead upto 50m and lift upto 1.5m,

disposed earth to be levelled and neatly dressed. Hard rock (

blasting prohibited ) 10.0 60 Cum 571.90 34314.00 2.7.3

1.10 Providing & Laying of rubble stone soling shall be hand packed

by wedging and packing with 80 mm metal in the joints of the

soling and driving them by hammers in place so as to fill the

voids as completely as possible. This operation of hand packing

shall closely follow the rubble laying. The soling shall be laid and

hand packed true to grade and section and these shall be often

checked by boning rods,template boards, fish line, etc. The

grades, sections, etc. of soling shall correspond 47.0 282 Cum 1250 352500.00 MR

Page 122: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

S.No. Description.

Qty.for one sub station

block

Qty.for six sub station

block

Unit. Rate in Figures (in Rs.) DSR

Rate in Figures (in

Rs.) NON DSR

DSR Amount ( in Rs.)

NON DSR/ MR Amount (

in Rs.)

Ref DSR -2013 Item

no

1 2 3 4 5 6 7 8 9

Total :- 2344017.13 1392000.00

2.00 SUB-HEAD : II : CONCRETE WORK :-

2.01 Providing and laying in position cement concrete of specific grade

excluding the cost of centring and shuttering-All work upto plinth

level

a) 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate20 mm nominal size) 63.0 378 cum 4921.70 1860402.60 4.1.3

b) 1:4:8 ( 1 cement: 4 coarse sand:8 graded stone aggregate40mm nominal size ) 63.0 378 cum 3920.65 1482005.70 4.1.8

2.02 Making plinth protection 50mm thick of cement concrete 1:3:6 (

1 cement: 3 coarse sand : 6 graded stone aggregate 20 mm

nominal size ) over 75mm thick bed of dry brick ballast 40 mm

nominal size,well rammed and consolidated and grouted with fine

sand,including finishing th etop smooth. 72.0 432 sqm 378.95 163706.40 4.17

Total :- 3506114.70 0.00

3.00 SUB-HEAD : III : REINFORCEMENT CEMENT CONCRETE :-

Page 123: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

S.No. Description.

Qty.for one sub station

block

Qty.for six sub station

block

Unit. Rate in Figures (in Rs.) DSR

Rate in Figures (in

Rs.) NON DSR

DSR Amount ( in Rs.)

NON DSR/ MR Amount (

in Rs.)

Ref DSR -2013 Item

no

1 2 3 4 5 6 7 8 9

3.01 Providing and laying in position machine bayched and machine

mixed design mix M-25 grade cement concrete for reinforced

cement concrete work,using cement content as per approved

design mix,including pumping of ceonctrete to site of laying but

excluding the cost of centring,shuttering,finishing and

reinforcement,includingadmixtures in recommednded proportions

as per IS: 9103 to accelerate , retard setting of concrete,improve

workability without impairing strenth andduability as per direction

of Engineer-in-Charge.( Note: Cement content considered in this item is 330Kg/cum.Excess/less cement used as per design mix is payable/recoverable seperately )a) All works upto plinth level. 195.0 1170 cum 5704.45 6674206.50 5.33.1

b) All works above plinth level upto floor V level. 83.0 498 cum 6353.00 3163794.00 5.33.2

3.02 Extra for providing richer mixes at all floor levels.

Note: Excess /less cement over the specified cement content

used is payable/recoverable seperately )a) Providing M-30 grade concrete instead of M-25 grade

BMC/RMC. ( Note ; Cement content cosidered in M-30 is @ 340

Kg/cum ) 19.0 114 cum 64.15 7313.10 5.34.1

3.03 Centring and shuttering including strutting,propping etc. and

removal of form for:

a) Foundation ,footing,bases of columns ,etc. for mass concrete.535.0 3210 sqm 186.40 598344.00 5.9.1

b) Walls ( Any thickness ) including attached

pilasters,butteresses,plinth and string courses etc. 132.0 792 sqm 334.50 264924.00 5.9.2

c) Suspended floors,roofs,landings,balconies and access platform.335.0 2010 sqm 371.80 747318.00 5.9.3

Page 124: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

S.No. Description.

Qty.for one sub station

block

Qty.for six sub station

block

Unit. Rate in Figures (in Rs.) DSR

Rate in Figures (in

Rs.) NON DSR

DSR Amount ( in Rs.)

NON DSR/ MR Amount (

in Rs.)

Ref DSR -2013 Item

no

1 2 3 4 5 6 7 8 9d) Lintels, beams, plinth beams, girders, bressuners andcantilevers. 298.0 1788 sqm 309.8 553922.40 5.9.5

e) Columns,Pillars,Piers,Abutments,Posts and struts. 183.0 1098 sqm 423.00 464454.00 5.9.6

g) Edges of slab and breaks in floors and walls

i) Under 20cm wide. 10.0 60 metre 111.70 6702.00 5.9.16.1ii) Above 20cm wide.

10.0 60sqm 490.40

29424.00 5.9.16.2

3.04 Steel reinforcement for RCC work includng

straightening,cutting,bending,placing in position and binding all

complete for all works i.e below /above plinth level.Thermo-Mechanically Treated bars 33645.0 201870 Kilogram 66.50 13424355.00 5.22.6

3.05 Extra for additional height in centering, shuttering wherever

required with adequate bracing, propping etc. including cost of

de-shuttering & de-centring at all levels over a height of 3.5 m,

for every additional height of 1 m, or part thereof (Plan area to

be measured).

(a) Suspended floors, roofs, landing, beams and balconies (Plan

area to be measured). 630.0 3780 sqm 145.6 550368.00 5.11.1

Total :- 26485125.00 0.00

4.00 SUB-HEAD : IV : BRICK WORK :-

4.01 Brick work with common burnt clay F.P.S (non modular) bricks of

class designation 7.5 foundations and plinth in :-

a) Cement mortar 1:6 ( 1 cement: 6 coarse sand ) 40.0 240 cum 4646.50 1115160.00 6.1.2

Page 125: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

S.No. Description.

Qty.for one sub station

block

Qty.for six sub station

block

Unit. Rate in Figures (in Rs.) DSR

Rate in Figures (in

Rs.) NON DSR

DSR Amount ( in Rs.)

NON DSR/ MR Amount (

in Rs.)

Ref DSR -2013 Item

no

1 2 3 4 5 6 7 8 94.02 Brick work with non modular fly ash lime bricks ( FALG Bricks )

conforming to IS: 12894,class designation 10 average

compressive strength in super structure above plinth level upto

floor V level in :

a) Cement mortar 1:4 ( 1 cement: 4 coarse sand ) 152.0 912 cum 5301.25 4834740.00 6.34.1

4.03 Half brick masonry with non modular fly ash lime Gypsum bricks

(FALG Bricks ) of class designation 10,conforming to IS: 12894,in

super structure above plinth and upto floor V level.

a) Cement mortar 1:4 ( 1 cement: 4 coarse sand ) 20.0 120 sqm 641.30 76956.00 6.45.2

4.04 Rnadom rubble masonary with hard stone in foundations and plith

including levelling up with cement concrete 1:6:12( 1 cement: 6

coarse sand: 12 graded stone aggregate 20mm nominal size)

upto plinth level with a) cement mortar 1:6 ( 1cement : 6coarse

sand) 20.0 120 cum 3410.50 409260.00 7.1.1

Total :- 6436116.00 0.00

5.00 SUB-HEAD: VIII: FLOORING:-

5.01 62 mm thick cement concrete flooring with concrete hardener

topping under layer 50 mm thick cement concrete 1:2:4 (1 Cement

: 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)

and top layer 12 mm thick Hardcrete cement hardener consisting

of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate

6mm nominal size) by volume hardening compound is mixed @

2 litre per 50 kg of cement or as per manufacturers

specificationss. This included cost of cement slurry, but excluding

the cost of nosing of steps etc. complete. 212.0 1272 sqm 528.25 671934.00 11.5

Page 126: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

S.No. Description.

Qty.for one sub station

block

Qty.for six sub station

block

Unit. Rate in Figures (in Rs.) DSR

Rate in Figures (in

Rs.) NON DSR

DSR Amount ( in Rs.)

NON DSR/ MR Amount (

in Rs.)

Ref DSR -2013 Item

no

1 2 3 4 5 6 7 8 9

5.02 Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4

graded stone aggregate) finished with floating coat of neat cement

including cement slurry, but excluding the cost of nosing of steps

etc. complete.

a) 40mm thick with 20mm nominal size stone aggregate 20.0 120 sqm 316.80 38016.00 11.3.1

5.03 Cement plaster skirting upto 30 cm height with cement mortar

1:3 (1 Cement: 3 coarse sand) finished with a floating coat of

neat cement.a) 18 mm thick 21.0 126 sqm 299.20 37699.20 11.6.1

5.04 Kota stone slab flooring over 20mm (average) thick base laid

over and jointed with grey cement slurry mixed with pigment to

match the shade of the slab including rubbing and polishing

complete with base of cement mortar 1 : 4 ( 1 cement : 4 coarse

sand) : 29.0 174 sqm 1071.70 186475.80 11.26.125 mm thick

5.05 Kota stone slabs 20 mm thick in risers of steps, skirting, dado

and pillars laid on 12 mm (average) thick cement mortar 1:3 (1

cement 3 coarse sand) and jointed with grey cement slurry mixed

with pigment to match the shade of the slabs, including rubbing

and polishing complete. 4.0 24 sqm 1100.85 26420.40 11.27

5.06 Providing and fixing Ist quality ceramic glazed wall tiles

conforming to IS : 15622 (thickness to be specified by the

manufacture ) of approved make in all colours, shades except

burgundy, bottle green, black of any size as approved by

Engineer-in-Charge in skirting, risers of steps and dados over 12

mm thick bed of cement Mortar 1:3 (1 cement : 3 coarse sand)

and jointing with grey cement slurry @ 3.3kg per sum including

pointing in white cement mixed with pigment of matching shade

complete. 22.0 132 sqm 793.60 104755.20 11.36

Page 127: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

S.No. Description.

Qty.for one sub station

block

Qty.for six sub station

block

Unit. Rate in Figures (in Rs.) DSR

Rate in Figures (in

Rs.) NON DSR

DSR Amount ( in Rs.)

NON DSR/ MR Amount (

in Rs.)

Ref DSR -2013 Item

no

1 2 3 4 5 6 7 8 9

5.07 Providing and laying Ceramic glazed floor tiles 300x300 mm

(thickness to be specified by the manufacturer) of 1st quality

conforming to IS : 15622 of approved make in colours such as

White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick

Cement Mortar 1:4 (1 Cement : 4 Coarse sand) including pointing

the joints with white cement and matching pigment etc.,

complete. 6.0 36 sqm 822.10 29595.60 11.37

5.08 Providing and fixing Heat resistant terrace tile ( 300x 300mm x

20mm ) with SRI ( solar refractive index )>78, solar reflection >

0.70 and initial emmitance > 0.75 on waterproof and sloped

roofed surface of terrace,laid on 20mm thick cement sand mortar

in theratio of 1: 4 ( 1 cement: coarse sand ) and grouting the

joints with mix of white cement & marble powder in ratio of 1:

1,including rubbing and polishing of the surface upto 3 cuts

complete,including providing skirting upto 150 mm heights along

the parapet walls in the same manner. 347.0 2082 sqm 1108.70 2308313.40 12.55

5.09 Stone work,plain in copings,cornices,string courses and plinth

courses,upto 75 mm thick in Cement mortar 1:6 (1 cement

: 6 coarse sand),including pointing with white cement mortar 1:2

(1 white cement :2 stone dust) with an admixture of pigment

matching the stone shade.

Red sand stone 1.00 6 cum 35767.40 214604.40 7.32

Total :- 3617814.00 0.00

6.00 SUB-HEAD: IX : FINISHING:-

6.01 12mm cement plaster of mix :-

a) 1:4 ( 1 cement : 4 coarse sand) 807.0 4842 sqm 153.85 744941.70 13.4.1

Page 128: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

S.No. Description.

Qty.for one sub station

block

Qty.for six sub station

block

Unit. Rate in Figures (in Rs.) DSR

Rate in Figures (in

Rs.) NON DSR

DSR Amount ( in Rs.)

NON DSR/ MR Amount (

in Rs.)

Ref DSR -2013 Item

no

1 2 3 4 5 6 7 8 9

6.02 15mm cement plaster on the rough side of single or half brick wallof mix

a) 1:4 (1 cement : 4 coarse sand) 807.0 4842 sqm 178.60 864781.20 13.5.1

6.03 6mm cement plaster to ceiling of mix :-

a) 1:3 (1 cement : 3 fine sand) 335.0 2010 sqm 120.35 241903.50 13.16.1

6.04 White washing with lime to give an even shadea) New work ( three or more coats ) 335.0 2010 sqm 14.35 28843.50 13.37.1

6.05 Finishing walls with textured exterior paint of required shade:

a) New work ( two or more coats allpied @ 3.28 ltr/10 sqm) over

and including priming coat of exterior primer applied 2.20 kg/10

sqm 451.0 2706 sqm 127.10 343932.60 13.45.1

6.06 18 mm cement plaster in two coats under layer 12mm thickcement plaster 1:5 ( 1cement : 5 coarse sand) and a top layer6mm thick cement plaster 1:3 (1 cement : 3 coarse sand) finishedwith rough with sponge. 451.0 2706 sqm 231.20 625627.20 13.12

6.07 Distempering with 1st quality acrylic distemper,having VOC (

Volatile Organic Compound ) Content less than 50grams/litre,of

approved brand and manufacture,including applying additional

coats wherever required,to achieve even shade and colour

a) Two or more coats 1613.0 9678 sqm 41.75 404056.50 13.81.2

6.08 Painting with synthetic enamel paint ,having VOC ( Volatile

Organic Compound ) content less than 150 gms/litre,of approved

brand and manufacture,including applying additional coats

wherever required to achieve even shade colour.Two or more coats 174.0 1044 sqm 67.00 69948.00 13.84.2

Page 129: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

S.No. Description.

Qty.for one sub station

block

Qty.for six sub station

block

Unit. Rate in Figures (in Rs.) DSR

Rate in Figures (in

Rs.) NON DSR

DSR Amount ( in Rs.)

NON DSR/ MR Amount (

in Rs.)

Ref DSR -2013 Item

no

1 2 3 4 5 6 7 8 96.09 Extra for Making 15 x 15 mm grooves in the plastering work as

shown in the drawing or as directed by the Engineer-in-Charge. 100.0 600 metre 12.00 7200.00 MR

Total :- 3324034.20 7200.00 7.00 SUB-HEAD: X : STEEL WORK :-

7.01 Steel work welded in built up sections/framed ,including

cutting,hopisting,fixing in position and applying a priming coat of

approved steel primer using structural steel etc. as required.

In gratings, frames, guard bar, ladders, railings,louvers, brackets,

gates & similar works. 4950.0 29700 Kg 86.50 2569050.00 10.25.2

7.02 Supplying and fixing rolling shutters of approved make, made of

required size M.S. laths interlocked together through their entire

length and jointed together at the end by end locks mounted on

specially designed pipe shaft with brackets, side guides and

arrangements for inside and outside locking with push and pull

operation complete including the cost of providing and fixing

necessary 27.5cm long wire springs grade No. 2 and M.S. top

cover of required thickness for rolling shutters.

a) 80 x 1.20mm M.S. laths with 1.20mm thick top cover 41.00 246 sqm 1831.20 450475.20 10.6.2

7.03 Providing and fixing ball bearing for rolling shutters. 15.00 90 each 436.45 39280.50 10.7

7.04 Extra for providing grilled rolling shutters manufactured out of

8mm dia M.S. Bar instead of laths as per design approved by

Engineer-in-Charge (Area of grill to be measured). 14.00 84 sqm 313.60 26342.40 10.9

7.05 Extra for providing mechnical device chain and cranks operation

for operating rolling shutters

Page 130: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

S.No. Description.

Qty.for one sub station

block

Qty.for six sub station

block

Unit. Rate in Figures (in Rs.) DSR

Rate in Figures (in

Rs.) NON DSR

DSR Amount ( in Rs.)

NON DSR/ MR Amount (

in Rs.)

Ref DSR -2013 Item

no

1 2 3 4 5 6 7 8 9a) Excedding 10 sqm and upto 16.80 sqm in the area 14.00 84 sqm 665.50 55902.00 10.8.1

7.06 Providing and fixing 1mm thick M.S. sheet door with frame of

40x40x6mm angle iron and 3mm M.S. gusset plates at the

junction and corners , all necessary fittings complete, including

applying a priming coat of approved steel primer.Using M.S angles 40x40x6mm for diagonal braces.

8.00 48 sqm 2942.00 141216.00 10.5.1

7.07 Fencing with angle iron post placed at required distance

embedded in cement concrete blocks, every 15th post, last but

one end post and corner post shall be strutted on both sides and

end post on one side only and provided with horizontal lines and

two diagonals interwoven with horizontal wires, of barbed wire

weighing 9.38 kg per 100 m (minimum), between the two posts

fitted and fixed with G.I. staples, turn buckles etc. complete.

(Cost of posts, struts, earth work and concrete work to be paid

for separately). 30 180 sqm 25.80 4644.00 16.20

Total :- 3286910.10 .00

8.00 SUB-HEAD: XI: ROOFING :-

8.01 Providing gola 75 x 75 mm in cement concrete 1: 2 :4 (1 cement:2

coarse sand:4 stone aggregate 10mm and down gauge) ,including

finishing with cement mortar 1: 3 ( 1 cement: 3 fine sand) as

perstandard design.a) 75 x 75mm deep chase. 75.0 450 metre 127.95 57577.50 12.21.1

Page 131: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

S.No. Description.

Qty.for one sub station

block

Qty.for six sub station

block

Unit. Rate in Figures (in Rs.) DSR

Rate in Figures (in

Rs.) NON DSR

DSR Amount ( in Rs.)

NON DSR/ MR Amount (

in Rs.)

Ref DSR -2013 Item

no

1 2 3 4 5 6 7 8 98.02 Making khurras 45 x 45 cm with average minimum thickness of

5cm cement concrete 1: 2 :4 ( 1 cement:2 coarse sand:4 graded

stone aggregate of 20mm nominal size ) overP.V.C. sheet 1mx

1mx 400 micron,finished with 12mm cement plaster 1;3 ( 1

cement: 3 coarse sand) and a coat of neat cement,rounding the

edges and making and finishing the outlet complete 6.0 36 each 167.45 6028.20 12.22

Total :- 63605.70 .00

9.00 SUB-HEAD: XIII: WATERPROOFING WORKS :-

9.01 Providing and laying water proofing treatment to vertical andhorizontal surfaces of depressed portions of W.C ,kitchen and thelike consisiting of :i) 1st course of applying cement slurry @ 4.4 kg/sqm mixed withwaterproofing compound conforming to IS:2645 in recommendedproportions including rounding off junction of vertical andhorizontal surface.ii) 2nd course of 20mm cement plaster 1:3 ( 1 cement: 3 coarsesand) mixed with water rpoofing compound in recommendedproportion including rounding off junctionsof vertical andhorizontal surface.iii) 3rd surface of applying blown or residual bitumen applied hot

at 1.7 kgper sqm of area.iv) 4th course of 400 micron thick PVC sheet ( Overlaps at joints

of PVC sheet should be 100mm wide and pasted to each other

with bitumen @ 1.7 kg/sqm. 10.0 60 sqm 449.45 26967.00 22.3

Page 132: VOLUME – IIIengineeringprojects.com/Tender/UploadFiles/2119_VOL-III.pdf · power cable of 11 KV grade of following size in the existing masonry open duct as required. 8.4 ... Brass

S.No. Description.

Qty.for one sub station

block

Qty.for six sub station

block

Unit. Rate in Figures (in Rs.) DSR

Rate in Figures (in

Rs.) NON DSR

DSR Amount ( in Rs.)

NON DSR/ MR Amount (

in Rs.)

Ref DSR -2013 Item

no

1 2 3 4 5 6 7 8 99.02 Providing and laying APP ( Atactic Polypropylene Polymer )

modified prefabricated five layer 3mm thick waterproofing

mambrane,black finished reinforced with non woven polyster

matt consisting of a coat of bitumen primer for bitumen

membrane @ 0.40 litre/sqm by the same membrane manufacture

of density at 250 C,0.87 - 0.89 kg/litre and viscocity 70-160

cps.Over the primer coat the layer of membrane shall be laid

using butane torch and sealing all joints etc, and preparing the

surface complete.The cital physical and chemical parametres of

the membrane shall be as under:Joint strength in longitudinal and

trensverse direction at 230 C as 650/450 N/5 cm.Tear strength in

longitudinal and transverse direction as 300/250 N. Softening

point of membrane not lessthan 1500 C.Cold flexibility shall be

upto -20 C when tested in accordance with ASTM, D-5147.The

laying of membrane shall be got done through the authorised

applicator of the manufacture of membrane:3mm thick 347.0 2082 sqm 448.30 933360.60 22.20.1

9.03 Extra for covering top of membrane with geotextile,120 gsm non

woven,100% polyster of thickness 1 to 1.25mm bonded to th

emembrane with intermittent touch by heating the membrane by

butane torch as per manyfacture recommendations. 347.0 2082 sqm 64.55 134393.10 22.21