Ventilation installation web

36
Planlægnings- og installationsvejledning VENTILATIONSSYSTEM 04 I 2010 31701

description

https://www.uponor.dk/~/media/countryspecific/denmark-bld/download-centre/current/ventilation/ventilation-installation-web.pdf?version=3

Transcript of Ventilation installation web

Page 1: Ventilation installation web

Planlægnings- og installationsvejledning

V E N T I L AT I O N S S Y S T E M

04 I 201031701

Page 2: Ventilation installation web

Indhold

Uponor PP plast ventilationskanaler og -komponenter ...................................................................4

Materialedata ......................................................................................................................................4

Tekniske data for kanaler .....................................................................................................................4

Tekniske data for kanalisolering ...........................................................................................................5

Kvalitet ................................................................................................................................................5

Mål og tolerancer.................................................................................................................................5

Kanalernes tæthed ...............................................................................................................................5

Emballage ............................................................................................................................................5

Opbevaring ..........................................................................................................................................5

Ventilationskanaler og -komponenter ................................................................................................6

Ventilationskanaler ....................................................................................................................................6

Ventilationskomponenter .....................................................................................................................6

Præ-isolerede ventilationskanaler ........................................................................................................8

Præ-isolerede ventilationskomponenter ..............................................................................................8

Armaturer og ventiler ........................................................................................................................10

Konstruktion af ventilationssystem .............................................................................................12

Defi nitioner .......................................................................................................................................12

Anvendelser for Uponor ventilationskanaler ......................................................................................12

Køkken emhætte/ventilator kanaler ..................................................................................................12

Placering af kanaler ...........................................................................................................................12

Offentlige regler ................................................................................................................................12

Isolering af kanalerne ........................................................................................................................12

Ventilation af saunarum .....................................................................................................................12

Dimensionering af kanaler og lyddæmpere .................................................................................15

Lyddæmpernes lyddæmpning pr oktav, ISO 7235:2003 .....................................................................19

Lyddæmpernes tryktab, ISO 7235:2003 ............................................................................................19

Lyddæmpernes tryktab, ISO 7235:2003

USI-125-300, USI-125-650 og USI-125-1000 .............................................................................20

USI-160-650 og USI-160-1000 ...................................................................................................20

2 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 3: Ventilation installation web

Installation ............................................................................................................................................21

Oversigt .............................................................................................................................................21

Kanalføring ........................................................................................................................................21

Kanalføring gennem dampspærrer .....................................................................................................22

Kanalføring af præ-isolerede kanaler gennem dampspærrer ..............................................................22

Understøtninger ................................................................................................................................23

Understøtning af præ-isolerede kanaler ............................................................................................23

Isolering ........................................................................................................................................24

Installation og indstilling af luftarmaturer ...............................................................................................26

Oversigt .............................................................................................................................................26

Tilslutning af luftarmaturer til kanalerne ............................................................................................26

Friskluftrist ........................................................................................................................................27

Friskluftsarmatur til vægmontage ......................................................................................................27

Friskluftsarmatur til ventilationshul ...................................................................................................27

Spalteventil ........................................................................................................................................28

Friskluftsarmatur ...............................................................................................................................28

Justering af armaturer .......................................................................................................................28

Tabeller over armatur fabriksindstillinger, trykdifferens 20 Pa ..................................................29

Luftstrøm, trykdifferens og støjniveau .......................................................................................30

Luftstrøm og trykdifferens ..........................................................................................................32

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 3

Page 4: Ventilation installation web

Uponor PP plast ventilationskanaler og -komponenter

• Alle kanaler og komponenter

er rene og beskyttede fra pro-

duktion til installation.

• Vores produktudvalg indehol-

der fabriksfærdige, præ-iso-

lerede kanaler og kanalsek-

tioner.

• Opsamler ikke støv eller snavs:

Antistatisk PP materiale mod-

står enhver forurening.

• Hurtig og nem installation.

• Let bearbejdelige materialer.

• Kanalerne kan installeres uden

separat forsegling og låsning.

Materialespecifi kationer

Råmaterialer: polypropylen;

lugtfri og ugiftig

Farve: blå

Massefylde: ≈ 900 kg/m3

Brudstyrke: 30 MPa

Varmeudvidelse: 0,06 mm/m °C

Tekniske data for kanaler

Den indvendige overfl ade på kana-

ler er ren og fri for ujævnheder.

Modstandsdygtighed mod slag:

Opfylder kraven angivet i

SFS-EN 1411.

Korrosionsbestandighed:

Kemisk modstandsdygtighed som

beskrevet i standarden ISO/TR

10358

Antistatiske egenskaber:

Antistatiske produkter. De antista-

tiske egenskaber af kanalernes og

komponenternes indre overfl ader

måles under produktionen i over-

ensstemmelse med testproceduren i

ANSI/EOS/ESD-S11.11.

Varmebestandighed:

Kontinuerlig –50°C...+85°C,

kortvarigt +100 °C.

Kuldebestandighed:

Den lavest anbefalede temperatur

er -15°C. Kuldebestandigheden ve-

rifi ceres gennem konstant kvalitets-

kontrol i fl g. testmetoderne i SFS/

EN 1411.

Renhedsklassifi kation:

Renhedsklasse M1. Udviklet i sam-

arbejde med det fi nske Astma- og

Allergiforbund.

Tekniske data for kanalisolering

Råmaterialer: polyætylen skum

Farve: Blå

Massefylde: 30 kg/m3, isolering

tykkelse 15 mm

U-værdi 0,037 W/ m x K

Brandsikkerhed: Ingen brandklas-

sifi cering.

VTT studier:

- En fabriksisoleret ventilationska-

nal til 1 – 2 familiehuse eller ræk-

kehuse

Laboratorietest for overfl ade

temperatur

Dato 6. november 2006

En computerberegning af den

nødvendige isolerings tyk-

kelse for at hindre kondens og

begrænse produktets varmetab

udviklings- og laboratoriums- af-

prøvning

Dato 10. maj 2006

Instruktionerne i denne manual er

udarbejdet til brug for implemente-

ring af lejligheds-adskilte ventilati-

onssystemer i fritliggende huse, ter-

rassehuse eller rækkehuse. I terras-

sehuse og rækkehuse skal der være

fuldstændig strukturel brandadskil-

lelse af boligenes loftsrum.

Uponors produktsortiment er blevet

opdateret, og vi introducerer nu

præ-isolerede ventilationskanaler

og -kanalsektioner på markedet. Et

isoleret kanalsystem tillader en sik-

rere køling af indsugningsluften, og

der mistes ikke energi i strukturen.

På den anden side er fabriksisolere-

de kanaler i den øverste tagisolering

"sikre", og det gør det lettere at

undgå kondens og risici pga. instal-

lationsfejl.

������������ ������ ���������� �� �������� � � �����������������������������

���� �!� "�#� $ � �� %�& ����'

� %!�'��'( �#

� %!�'��'()#'�##*�& #

" ' �+,%�' ��-)+,#'),�

Kanalmærkning

• Teknisk excellent struktur for

luftgennemstrømning

• Ingen korrosionsproblemer

• Ingen lugtproblemer

• Garanteret ren indeluft i hele

hjemmet

• Patenterede struktur- og sam-

lingsløsninger

4 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 5: Ventilation installation web

Lyddæmpere

Lyddæmperne er udført i PE plast.

Lyddæmperne er testet af

VTT Technical Research Centre of

Finland, Certifi kat

Nr. VTT-S-03839-07

Dato 24.04.2007

- Firkantede lyddæmpere med

runde kanaltilslutninger

- Lille vægt og lette at håndtere

- Fremragende lyddæmpende

egenskaber

- Modstandsdygtige mod slag og

korrosion

- Sort farve

- Det indvendige lyddæmpende

materiale er Dacron

- Ingen løse fi bre eller fugtabsorp-

tion

- Ingen irritation af hud eller ån-

dedræt

- Ingen lugt eller støbeproblemer

Kanalernes tæthed

Kanalerne opfylder lufttæthedsklas-

se D. Kanalerne skal tilsluttes i over-

ensstemmelse med instruktionerne i

denne manual.

Forbindelserne kan ikke limes sam-

men, fordi opløsningsmidlerne ikke

virker på polypropylen.

Emballage

Kanalerne leveres lukkede i begge

ender for at holde dem rene. Kanal-

komponenterne leveres i plastposer

og papkasser.

Opbevaring

Modstår udendørs oplagring i cen-

traleuropæisk klima. Kanalerne er

UV-beskyttede. Højst 2 lag oven på

hinanden.

Kvalitet

Uponors plast ventilationssystem

kanaler er blevet tildelt et VTT pro-

duktcertifi kat.

Mål og tolerancer

Kanalstørrelserne er ø 100 (+0.5)

mm, ø 125 (+0.5) mm, ø 160 (+0.6)

mm

og ø 200 (+0.7) mm.

Tolerancerne opfylder kanalstandar-

den SFS 3282.

Tolerancerne for de sprøjtestøbte

komponenter er bedre end standar-

den kræver.

Uponors ventilationskanaler og

-komponenter er kompatible med

kanalkomponenter, der opfylder

standarden SFS 3282.

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 5

Page 6: Ventilation installation web

Ventilationskanaler og -komponenter

Ventilationskanaler Materiale: Polypropylen. Farve: blå.

Ventilationskanal Leveres i længder på 3 meter.

di x l Uponor nr. VVS nr. s

100 x 3000 1046152 35.3500.100 2,1

125 x 3000 1046153 35.3500.125 2,1

160 x 3000 1046154 35.3500.160 2,5

200 x 3000 1046155 35.3500.200 3,0

Ventilationskomponenter Materiale: Polypropylen. Farve: Blå.

Bøjning 45°

do x α Uponor nr. VVS nr l1 l2

100 x 45° 1046172 35.3502.100 46 40

125 x 45° 1046173 35.3502.125 36 50

160 x 45° 1046174 35.3502.160 45 50

200 x 45° 1046171 35.3502.200 54 50

Bøjning 90°

do x α Uponor nr. VVS nr. l1 l2

100 x 90° 1046168 35.3501.100 81 40

125 x 90° 1046169 35.3501.125 84 50

160 x 90° 1046170 35.3501.160 160 50

200 x 90° 1046167 35.3501.200 130 50

T-stykker

do1/do2 Uponor nr. VVS nr. l1 l2 l3

100/100 1046175 35.3503.100 142 40 71

125/100 1046179 35.3503.124 144 50 81

125/125 1046176 35.3503.125 168 50 81

160/100 1046180 35.3503.158 144 50 98

160/125 1046177 35.3503.159 168 50 101

160/160 1046178 35.3503.160 196 50 100

200/160 1046181 35.3503.199 202 50 118

%

�.

'

α

%� %�

% �% �

%�

% �

%�%� %�

��

% �

α

% �

% �

% ��

% �

6 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 7: Ventilation installation web

Ventilationskomponenter Materiale: Polypropylen. Farve: Blå.

%�

%�%�

%�

%�

%�

Samlenippel

do Uponor nr. VVS nr. l1 l2

100 1046164 35.3508.100 83 40

125 1046165 35.3508.125 103 50

160 1046166 35.3508.160 103 50

200 1046163 35.3508.200 103 50

Prop

do1/do2 Uponor nr. VVS nr. do3 l1 l2

100 1046182 35.3506.100 120 43 40

125 1046183 35.3506.125 145 33 30

125/160 1046184 35.3506.159 180 53 50

Reduktionsstykke

do1/do2 Uponor nr. VVS nr. l2 l3 l4

100/125 1046185 35.3504.124 50 20 40

125/160 1046186 35.3504.159 51 30 50

160/200 1046187 35.3504.199 51 40 50

% �% �

��

��

% �% �

��

��

��

% �% �

��

��100

125

125/160

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 7

Page 8: Ventilation installation web

Præ-isolerede ventilationskanaler Kanalmateriale: Polypropen. Farve: Blå.

Isoleringsmateriale: Polyætylen skum Farve: Blå

Isoleringstykkelse: 15 mm

VentilationskanalLeveres i længder på 3 meter.

di x l Uponor nr. VVS nr.

100 x 3000 1046156 35.3510.100

125 x 3000 1046157 35.3510.125

160 x 3000 1046158 35.3510.160

200 x 3000 1046159 35.3510.200

Præ-isolerede ventilationskomponenter Kanalmateriale: Polypropen. Farve: Blå.

Isoleringsmateriale: Polyætylen skum Farve: Blå

Isoleringstykkelse: 15 mm

Bøjning 45°

do x α Uponor nr. VVS nr.

100 x 45° 1046197 35.3512.100

125 x 45° 1046198 35.3512.125

160 x 45° 1046199 35.3512.160

200 x 45° 1046196 35.3512.200

Bøjning 90°

do x α Uponor nr. VVS nr.

100 x 90° 1046193 35.3511.100

125 x 90° 1046194 35.3511.125

160 x 90° 1046195 35.3511.160

200 x 90° 1046192 35.3511.200

T-stykker

do1/do2 Uponor nr. VVS nr.

100/100 1046200 35.3513.100

125/100 1046204 35.3513.124

125/125 1046201 35.3513.125

160/100 1046205 35.3513.158

160/125 1046202 35.3513.159

160/160 1046206 35.3513.160

200/160 1046203 35.3513.199

l

di

s

l

di

s

8 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 9: Ventilation installation web

Samlenippel

do Uponor nr. VVS nr.

100 1046189 35.3518.100

125 1046190 35.3518.125

160 1046191 35.3518.160

200 1046188 35.3518.200

Prop

do1/do2 Uponor nr. VVS nr.

100 1046207 35.3516.100

125 1046208 35.3516.125

125/160 1046209 35.3516.159

Reduktionsstykke

do1/do2 Uponor nr. VVS nr.

100/125 1046210 35.3514.124

125/160 1046211 35.3514.159

160/200 1046212 35.3514.199

Aluminiumsspændbånd

Produkt Uponor nr. VVS nr.

Aluminiumsspændbånd 5 stk. / pose 1046258 35.3529.800

��

��

��

��100

125

125/160

Kanalføring gennem dampspærre

Selvklæbende PE-plast.

Mål d1 Uponor nr. VVS nr. l1 l2 tykkelse

100 1046252 35.3529.010 240 240 10

125 1046251 35.3529.012 240 240 10

Lyddæmper Firkantet, indvendigt lyddæmpene materiale er Dacron

Tilslutningsdiameter og model Uponor nr. VVS nr. l1 l2 l3

USI - 125 - 300 1046253 35.3529.123 300 190 270

USI - 125 - 650 1046254 35.3529.126 650 190 270

USI - 125 - 1000 1046255 35.3529.120 1000 190 270

USI - 160 - 650 1046256 35.3529.166 650 225 300

USI - 160 - 1000 1046257 35.3529.160 1000 225 300

%�

% �

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 9

Page 10: Ventilation installation web

Armaturer og ventiler Standardfarve: Hvid.

Indblæsningsarmaturer (mekanisk ventilation)

Lofts-monterede armaturer Tilslutningsdiameter og model Uponor nr. VVS nr. D D1 H

UTK-100 1046266 35.3520.110 140 98 60

UTK-C-100, krom 1046267 35.3520.114 140 98 60

UTK-B-100, messing 1046268 35.3520.116 140 98 60

* UTK-S-100, sauna 1046269 35.3520.210 140 98 60

* UTK-S-B-100, sauna messing 1046270 35.3520.216 140 98 60

UTK-125 1046271 35.3520.120 175 115 67Vægmonterede armaturer

UTK-C-125, krom 1046272 35.3520.124 175 115 67

UTK-B-125, messing 1046273 35.3520.126 175 115 67

* UTK-S-125, sauna 1046274 35.3520.220 175 115 67

* UTK-S-B-125, sauna messing 1046275 35.3520.226 175 115 67

UKK-125, armaturkrave 1046227 35.3520.820 166 135 55

Armaturkrave UTS-100 1046226 35.3520.410 Mål i billedet

UTS-125 1046218 35.3520.420 Mål i billedet

* Varmebestandigt op til 200°C. Ved brug af saunaarmaturet, brug altid kraven i emballagen.

Udsugningsarmaturer (mekanisk ventilation)

Loftsmonterede armaturer Tilslutningsdiameter og model Uponor nr. VVS nr. D D1 H

UPK-100 1046214 35.3521.110 138 72 50

UPK-C-100, krom 1046228 35.3521.114 138 72 50

UPK-M-100, messing 1046229 35.3521.116 138 72 50

UPK-125 1046213 35.3521.120 168 90 60

UPK-C-125, krom 1046230 35.3521.124 168 90 60

UPK-M-125, messing 1046231 35.3521.126 168 90 60

* UPK-S-100 med træknop 1046232 35.3521.210 138 72 50

* UPK-S-125, med træknop 1046233 35.3521.220 168 90 60

* UPK-S-M-100, messing, med træknop 1046234 35.3521.216 138 72 50

* UPK-S-M-125, messing, med træknop 1046235 35.3521.226 168 90 60

* Varmebestandigt op til 200°C. Ved brug af saunaarmaturet, brug altid kraven i emballagen.

Tallerkenventiler (naturlig ventilation)

Tilslutningsdiameter og model Uponor nr. VVS nr. D D1 H

ULV-100 1046236 35.35211.10 138 72 58

ULV-125 1046237 35.3522.120 168 90 66

/

0 0�

/

0 0�

/

0 0�

/

0 0�

10 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 11: Ventilation installation web

Armaturer og ventiler Standardfarve: Hvid.

Friskluftsriste

Tilslutningsdiameter og model Uponor nr. VVS nr. A D H

USS-100 med insektnet 1046238 35.3525.110 143 123 57

USS-125 med insektnet 1046239 35.3525.120 143 123 57

USS-160 med aftagelig netkassette 1046240 35.3525.160 235 160 74

USS-200 med aftagelig netkassette 1046241 35.3525.200 235 200 74

160/200 Netkassette til friskluftrist 1046242 35.3525.620

Friskluftsarmatur

Tilslutningsdiameter og model Uponor nr. VVS nr.

URS-100 1046243 35.3523.100

Friskluftsarmatur til ventilationshul

Tilslutningsdiameter og model Uponor nr. VVS nr.

UKS-100, vægmonteret 1046244 35.3523.200

UKTL-100, ventilationshul 1046245 35.3523.300

Spalteventil

Tilslutningsdiameter og model Uponor nr. VVS nr.

URV-18, 18 x 245 x 340 1046246 35.3523.618

1��

��

���

1��

2

1��

1��

�1��

�2���

1��

���

�3

���

��

��

��3 ��4�

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 11

Page 12: Ventilation installation web

Konstruktion af ventilationssystem

Defi nitioner

- Friskluftkanalen tilfører frisk

udeluft til ventilatoren.

- Indblæsningskanalerne fordeler

den friske luft fra ventilationsenhe-

den til rummene.

- Udsugningskanalerne fører

indeluften til ventilationsenheden,

som overfører varmen fra udblæs-

ningsluften til at opvarme den ind-

kommende friske luft, om nødven-

digt.

- Afkastluftkanalen overfører

udblæsningsluften fra ventilations-

enheden til udblæsningsrøret på

taget.

- Mineraluld refererer til både

glasuld og stenuld (fx Rockwool).

Mineraluld kan hverken brænde el-

ler rådne.

Ved design af luftkanalerne og di-

mensionering af kanalerne anbefa-

les det som udgangspunkt at bruge

en relativt lav lufthastighed (under

3 m/s) i kanalerne.

Anvendelser for Uponor

ventilationskanaler

Uponor ventilationskanaler bruges i

overensstemmelse med kapitel 6.3.1

i det danske bygningsreglement til

individuel ventilation af beboelses-

bygninger og andre bygninger end

beboelsesbygninger..

Køkken emhætte / emfang med

ekstern ventilator

Udsugningskanalerne fra køkken-

ventilatorer og emhætter tilslut-

tes ikke til ventilationssystem, men

føres ud til taget separat og har sin

egen udsugningsventilator.

Placering af kanaler

Indblæsnings- og udsugnings-kana-

lerne installeres normalt

- Nede i loftsisoleringen over loftet

- I loftsrummene

- Inde i gulv/loftsadskillelser

- Over et forsænket loft, eller

- Under loftet i huset.

Indblæsningsarmaturerne installeres

især i opholdsrum og soverum for at

tilføre frisk udeluft. Fordi udsug-

ningsarmaturerne er konstrueret til

affugtning og fjernelse af dårlige

lugt i tillæg til luftcirkulation, an-

bringes de i baderum, saunaer,

og nytterum (fyrrum, hobbyrum,

bryggers), skabsrum, køkkener og

toiletter. Den brugte luft fl yder

gennem døråbninger fra rummene

med indblæsning til rummene med

udsugning.

Myndighedernes bestemmelser

I designet af luftkanalerne og deres

installation skal regler og instruk-

tionerne, der står i det danske

bygningsreglement kapitel 6 over-

holdes. Ventilationskanalerne skal

beskyttes af et nedhængt loft eller

konstruktion mod opholdsrum..

Isolering af kanalerne

Forholdene vedr. opvarmning, kon-

dens og brandisolering af kanalerne

er specifi ceret i ventilationsplanen.

Isolering kan vises på tegningerne

fx med følgende markeringer:

- HI1: Varmeisolering, mineraluld

50 mm uden overfl adeafslutning.

- HI2: Varmeisolering, mineraluld

50 + 50 mm uden overfl ade-

afslutning.

- HI2: Varmeisolering, mineraluld

50 mm uden overfl adeafslutning

+ indblæst løs isolering eller til-

svarende mindst 100 mm oven på

den isolerede kanal.

- HI4: I opvarmede områder iso-

lering mod varme og kondens

med ekspanderet polystyren 15

mm. Inde i den øverste loftspla-

des isolering: Mindst 100 mm

løst indblæst mineraluld oven på

kanalerne, der er isoleret med 15

mm ekspanderet polystyren.

- HI5: Isolering mod varme og kon-

dens med ekspanderet polystyren

15 mm + mineraluld 50 mm uden

overfl adeafslutning.

Uanset ovenstående forslag skal

ventilationsrør som minimum iso-

leres mod energitab jf. DS 452,

klasse 1.

Brugen af præ-isolerede

indendørs luftprodukter letter

isoleringsarbejdet, især på

vanskeligt tilgængelige steder.

Ventilation af saunarum

Ved design af kanaler til saunaer skal

temperaturbegrænsningerne over-

holdes. Kanalerne skal enten indsæt-

tes i saunaens isolering eller installe-

ret over isoleringen. I andre tilfælde,

fx hvor den skal anbringes direkte

bag panelerne, skal rørene isoleres

termisk. Kanalerne og rammerne til

de loftsmonterede armaturer skal

fastgøres til loftsstrukturerne på for-

svarlig vis med skruer.

Bemærk venligst: Brug kun anbefale-

de varmebestandige saunaarmaturer

ved loftet i saunaer. Indblæsnings-

armaturerne er markeret med en rød

etiket, og udsugningsarmaturerne

har en træknop. Saunaarmaturer skal

altid installeres i en armaturkrave.

Armaturkraven skal fastgøres til sau-

naloftets træ med skruer, hvorefter

saunaarmaturet indsættes. Undgå at

installere saunaarmaturet lige over

saunaens ovn.

Tuloilma

katosta kiukaan

l heisyydest

Poisto-

ilma

lattian

l helt

0,5—1,0 m/s

Ventilation af saunarum

Tilluft fra taget i nærheden

af ventilationsaggregatet

Fraluft

ved

gulv

12 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 13: Ventilation installation web

RE

GU

LA

TO

R F

OR

PE

ISA

VT

RE

KK

SAUNA

FUGTSENSOR

VÆRELSE

VÆRELSE

VÆRELSE

UDHUS

TERRASSE

STUE

KØKKEN

EMHÆTTE

LYD-

DÆMPER

LYD-

DÆMPER

KLÆDESKAB

BRYGGERS

VENTILATIONSREGULATOR

(UDEN INSEKTNET)

FR

ALU

FT

VE

NT

IL

MO

NT

ER

ES 4

00

MM

OV

ER

GU

LV,

RE

KTA

NG

ULÆ

R K

AN

AL

I V

ÆG

GE

N 4

0 X

14

0

Ø1

60

TIL

TA

GE

T

+A

FK

AST

TT

E

UN

DE

RTA

GSN

IVE

AU

Eksempel på ventilationssystem design for et fritliggende hus. Materialelisten fi ndes på næste side.

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 13

Page 14: Ventilation installation web

Materialeliste for ventilations-plan for et een-familiehus som det vist på forrige side

Uponor Størrelse Produkt Producent stk m nr /kode

1046158 Ø 160 Kanal, præ-isoleret Uponor 13 36

1046157 Ø 125 Kanal, præ-isoleret Uponor 18 48

1046195 Ø 160 Bøjning 90°, præ-isoleret Uponor 3

1046194 Ø 125 Bøjning 90°, præ-isoleret Uponor 12

1046202 Ø 160/125 T-stykke, præ-isoleret Uponor 11

1046201 Ø 125/125 T-stykke, præ-isoleret Uponor 12

1046206 Ø 160/160 T-stykke, præ-isoleret Uponor 1

1046191 Ø 160 Samlenippel, præ-isoleret Uponor 8

1046190 Ø 125 Samlenippel, præ-isoleret Uponor 9

1046209 Ø 125/160 Prop, præ-isoleret Uponor 1

1046208 Ø 125 Prop, præ-isoleret Uponor 8

1046211 Ø 125/160 Reduktion, præ-isoleret Uponor 2

1046251 Ø 125 Dampspærre gennemføring Uponor 21

1046271 UTK-125 Indblæsningsarmatur Uponor 8

1046213 UPK-125 Udsugningsarmatur Uponor 9

1046237 ULV-125 Tallerkenventil Uponor 4

1046241 USS-200 Friskluftrist m/aftagelig netkassette Uponor 2

1046239 USS-125 Friskluftrist m/insektnet Uponor 4

1046253 USI-125-300 Lyddæmper Uponor 3

1046255 USI-125-1000 Lyddæmper Uponor 2

Tillægsliste over produkter, der ikke fi ndes i Uponors produkt-sortiment

Størrelse Produkt Producent stk m2 /kode

Mineraluld isolering 50 mm 7

40x140 Rektangulær kanalpakke for badstue 1

Ø 160 Taggennemføring med hætte og inddækning for afkastluft 2

Ø 160 Tallerkenventil 1

Ø 200 Tallerkenventil 1

Bemærk at der ikke indgår produkter til emhætte/emfang i ovenstående materialeliste.

14 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 15: Ventilation installation web

�3

2

��

��

��

��

��

3�

�� �� �� �� �� 3� 2� ��� ��� ��� ����%! ���% +��'+��� �5!��'6

� �

-,+

�*4��

������7

����8�7

",)�,��������7�& �����8�7��

�3

2

��

��

��

��

��

3�

�� �� �� �� �� 3� 2� ��� ��� ��� ����%! ���% +��'+��� �5!��'6

� �

-,+

�*4��

��9�'��'�����3�

: & �'�3�����

$����%����;���9�'��'������3��& �% & �'��3�����

���%! ���- )'��4���#<�!�

����%! ���% +��'+��� �5!��'6

���������2�3������������4�

�4�

�4�

�4��4��43

�42�

��32

��

��

� �

-,+

�*4��

5� �

!6

1��� 1�3�3�!�'

��!�'

��!�'

��!�'

" + ��1����4�1����4�1��3��& �1����

1���

��!�'

��!�'

1���

�3�2

��

��

��

��

��3���

�� �� �� �� �� 3� 2� ��� ��� ��� ���

�%! ���% +��'+��� �5!��'6

� �

-

,+�*

4��

��9�'��'�3�����

: & �'�����3�

$����%����;���9�'��#' ���������4��3�����4& �% & �#' ����������& ������3�

: & �'���������9�'��'

�������

2�8�

���

Tryk

tab

, P

a

Luftstrøm (l/s)

Reduktionsstykke: Reduktionsstykker 125/100,

160/125, 100/125 og 125/160

Reduktion

Reduktion

Ekspansion

Ekspansion

10

20

30

40

50

60

70

0 20 30 40 50 60 80 100Ilman tilavuusvirta haarakanavassa q

3 [dm3/s]

Kok

onai

spai

ne-e

ro Δ

p 1-3

[Pa]

2

T-kappale 100/100Poisto sivulta. Kokonaispaine-ero Δp1-3

80

90100

0

-10

-20

-30

-40

-50

-6010 70 90 110 120 130

4

6

8

10

V1 m/s

1

3

2

Tota

l tr

ykd

iffe

ren

s Δp

1-3

, (P

a)

Luftstrøm i kanalgrenen q3 (l/s)

T-stykke 100/100

Side udsugning Total trykdifferens Δp1-3

3�28

��

3�

� �� �� �� �� 3� 2� ���

�%! ���% +��'+��� �- � # + '' �N��5!��'6

"�#

� �

'9 �

(

���O

9 �(��

5� 6

�(# 99 % ����������%��'�+�%% Q�"�#� �'9 � ( ���O9�(�

��2�8�

�� �� 8� ��� ��� ���

3

2

��

��

��

��

��

���!�'

Tota

l tr

ykd

iffe

ren

s Δp

1-3

, (P

a)

Luftstrøm i kanalgrenen q3 (l/s)

T-stykke 100/100

Side udsugning Total trykdifferens Δp1-3

6789

10

20

0 20 30 40 50 60 80 100

Ilman tilavuusvirta haarakanavassa q2 [dm3/s]

Kok

onai

spai

ne-e

ro Δ

p 1-2

[Pa]

2

T-kappale 100/100Poisto sivulta. Kokonaispaine-ero Δp1-2

30

40

50

0,90,80,70,60,50,4

10 70 90 110 120 130

4

6

8

10

V1 m/s

140 150

54

3

2

1

0,3

0,2

0,1

1

3

2

Luftstrøm i kanalgrenen q2 (l/s)

T-stykke 100/100

Side udsugning Total trykdifferens Δp1-2

Tota

l tr

ykd

iffe

ren

s Δp

1-2

, (P

a)

Dimensionering af kanaler og

lyddæmpere

Hoved indblæsnings- og udsug-

nings-kanalerne skal så vidt muligt

være store (ø 160) for at mindske

tryktabet i kanalerne mest muligt.

Indblæsningsarmaturerne skal til-

sluttes til hovedkanalen med for-

greninger.

Luftstrøm (l/s)

Tryk

tab

, P

a

Kanaler ø 100, ø 125, ø 160 og ø 200

Luftstrøm (l/s)

Tryk

tab

, P

a

Reduktionsstykke: Reduktionsstykker 200/160,

160/200

Reduktion

Ekspansion

Luftstrøm (l/s)

Tryk

tab

, P

a

Bøjning 200/45° og 200/90°Luft massefylde 1,20 kg/m³

Tryk

tab

, P

a

Luftstrøm l/s

Bøjninger 100/45°, 100/90°, 125/45°, 2x125/45°,

125/90°, 160/45° og 160/90°

og

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 15

Page 16: Ventilation installation web

Ilman tilavuusvirta haarakanavassa q3 [dm3/s]0 10 20 30 40 50 60 70 80 90 100 110 120130

10

8

6

4

21

3

2

v1 [m/s]

5060

80

1

2

3

456

20

30

40

100

810

Tota

l tr

ykd

iffe

ren

s Δp

1-3

, (P

a)

Luftstrøm i kanalgrenen q3 (l/s)

T-stykke 125/125

Side indsugning Total trykdifferens Δp1-3

�%! ���% +��'+��� ���#�# + '' �N��5!��'6

"�

#�

�'9

( �

��O

9�S

��5�

6

S��

��

��

��

��

��

� �� �� �� �� �� 3� �� 2� 8� ��� ��� ������

��2

3��

+��5!�'6

S�

�(# 99 % ����������%��'�+�%% Q�"�#� �'9 � ( ���O9�S�

��

��

��

��

��

3�

��

� �� �� �� �� 3� 2� ����%! ���% +��'+��� �- � # + '' �N

��5!��'6

"�#�

�'

9 �

( �

��O9

�(��

5� 6

�(# 99 % �����������'���'�+�%� Q�"�#� �'9 � ( ���O9�(�

2�

8����

(��

(��

(��

(��

(��

(3��� �� 8� ��� ��� ���

�32

��

���!�'

3

2��

��

� �� �� �� �� 3� 2� ���

�%! ���% +��'+��� �- � # + '' �N��5!��'6

"�#�

�'

9 �

( �

��O

9 �(��

5� 6

�(# 99 % �����������'���'�+�%� Q�"�#� �'9 � ( ���O9�(�

��

����

�42�43�4��4�

�� �� 8� ��� ��� ���

3

2

��

���!�'

��� ���

��

�4�

�4�

�4�

�%! ���% +��'+��� �- � # + '' �N��5!��'6

"�

#�

�'9

( �

��O

9�S

��5�

6

� �� �� �� �� �� 3� �� 2� 8� ��� ��� ������

��

2

3

+��5!�'6

��3�

2�

��3

��

��

��

���

2��

�(# 99 % ����������%��'�+�%% Q�"�#� �'9 � ( ���O9�S�

��

��

� �� �� �� �� 3� 2� ���

�%! ���% +��'+��� �- � # + '' �N��5!��'6

"�#�

�'

9 �

( �

��O

9 �(��

5� 6

�(# 99 % ����������%��'�+�%% Q�"�#� �'9 � ( ���O9�(�

��

��

�� �� 8� ��� ��� ���

�3

2

�����!�'

��� ���

��

(�

(��

��

��

� �� �� �� �� 3� 2� ���

�%! ���% +��'+��� �- � # + '' �N��5!��'6

"�#

� �

'9 �

(

���O

9 �(��

5� 6

�(# 99 % ����������%��'�+�%% Q�"�#� �'9 � ( ���O9�(�

��

��

�� �� 8� ��� ��� ���

�3

2

��

���!�'

��� ���

��

(�

(��

Tota

l tr

ykd

iffe

ren

s Δp

1-2

, (P

a)

Luftstrøm i kanalgrenen q2 (l/s)

T-stykke 100/100

Side udsugning Total trykdifferens Δp1-3

-60

-50

-40

-30

-20

-10

0

10

20

30

40

50

60

70

80

90

100

0 10 20 30 40 50 60 70 80 90 100 110120 130

Ko

kon

aisp

ain

e-er

o Δ

p1–

3 [P

a]

10

8

6

42 v1 [m/s]

1

3

2

T-kappale 125/125Poisto sivulta. Kokonaispaine-ero Δp1–3

Luftstrøm i kanalgrenen q3 (l/s)

T-stykke 125/125

Side udsugning Total trykdifferens Δp1-3

Tota

l tr

ykd

iffe

ren

s Δp

1-3

, (P

a)

Ilman tilavuusvirta runkokanavassa q2 [dm3/s]

Ko

kon

aisp

ain

e-er

o Δ

p1–

2 [P

a]

0,1

0,2

0,30,40,50,60,8

1

2

34568

10

20

304050

0 10 20 30 40 50 60 70 80 90 100 120 140150

10

8

6

4

2

v1 [m/s]

1

3

2

T-kappale 125/125Poisto sivulta. Kokonaispaine-ero Δp1–2

Tota

l tr

ykd

iffe

ren

s Δp

1-2

, (P

a)

Luftstrøm i kanalgrenen q2 (l/s)

T-stykke 125/125

Side udsugning Total trykdifferens Δp1-2

Luftstrøm i kanalgrenen q2 (l/s)

T-stykke 125/125

Side indblæsning Total trykdifferens Δp1-2

Tota

l tr

ykd

iffe

ren

s Δp

1-2

, (P

a)

Luftstrøm i kanalgrenen q3 (l/s)

T-stykke 125/100

Side udsugning Total trykdifferens Δp1-3

Tota

l tr

ykd

iffe

ren

s Δp

1-3

, (P

a)

Luftstrøm i kanalgrenen q3 (l/s)

T-stykke 125/100

Side udsugning Total trykdifferens Δp1-2

Tota

l tr

ykd

iffe

ren

s Δp

1-2

, (P

a)

Luftstrøm i kanalgrenen q3 (l/s)

T-stykke 125/100

Side indblæsning Total trykdifferens Δp1-3

Tota

l tr

ykd

iffe

ren

s Δp

1-3

, (P

a)

Luftstrøm i kanalgrenen q2 (l/s)

T-stykke 125/100

Side udsugning Total trykdifferens Δp1-3

Tota

l tr

ykd

iffe

ren

s Δp

1-3

, (P

a)

16 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 17: Ventilation installation web

��23��

� �� �� 3� 2� ��� ��� ��� �3� �2� ��� ���

+��5!�'6

99

��

8�

S��

��

��

��

��

��

2�

���

���

��

���

3�

99

��

56

� �� �� �� �� �� 3� �� 2� 8� ��� ��� ������

��2

3

+��5!�'6

��3�

2�

��3

��

��

��

���

2��

��

2

3

��

"�

#�

�'9

( �

��O

��(

��5�

6

�3��8�7+��5!�'6

� �� �� 3� 2� ��� ��� ��� �3� �2� ��� ���S3�

S��

S��

S��

S��

S��

��

��

��

��

��

3�

��

2�

8�

���

�%! ���% +��'+��� �- � # + '' �N��5!��'6

��

2

3

S��

S��

S��

S��

S��

��

��

��

��

��

3�

��

2�

8�

���

� �� �� �� �� �� 3� �� 2� 8� ��� ��� ������

+��5!�'6

��

2

3

��3�

2�

��3

��

��

��

���

2��

� �� �� 3� 2� ��� ��� ��� �3� �2� ��� ���

+��5!�'6

(3�

(��

(��

(��

(��

(��

��

��

��

��

��

3�

��

2�

8�

���

� �� �� �� �� �� 3� �� 2� 8� ��� ������ ����%! ���% +��'+��� �- � # + '' �N��5!��'6

"�

#�

�'9

( �

��O

9�S

��5�

6

��

2

3

� +��5!�'6

�(# 99 % ��3��������'���'�+�%� Q�"�#� �'9 � ( ���O9�S�

3

2��

��

�� �� �� �� 3� 2� ���

�%! ���% +��'+��� �- � # + '' �N��5!��'6

"�#

� �

'9 �

(

���O

9 �(��

5� 6

�(# 99 % ��3��������'���'�+�%� Q�"�#� �'9 � ( ���O9�(�

��

����

�42

�43�4��4�

�� �� 8� ���������

3 2

��

���!�'

������

��

�4�

�4�

�4��3�����2��8�

�4�

�48

�%! ���% +��'+��� �- � # + '' �N��5!��'6

"�

#�

�'9

( �

��O

9�S

��5�

6

� �� �� �� �� �� 3� �� 2� 8� ��� ��� ������

��

2

3

+��5!�'6

��3�

2�

��3

��

��

��

���

2��

�(# 99 % ��3�������%��'�+�%% Q�"�#� �'9 � ( ���O9�S�

�%! ���% +��'+��� ���#�# + '' �N��5!��'6

"�

#�

�'9

( �

��O

9�S

��5�

6

S��

��

��

��

��

��

�� �� �� �� �� 3� �� 2� 8� ��� ��� ��� �2�

��

2

3��

+��5!�'6

S�

�(# 99 % ��3�������%��'�+�%% Q�"�#� �'9 � ( ���O9�S�

�3�

Tota

l tr

ykd

iffe

ren

s Δp

1-3

, (P

a)

Luftstrøm i kanalgrenen q3 (l/s)

T-stykke 160/125

Side udsugning Total trykdifferens Δp1-3

Tota

l tr

ykd

iffe

ren

s Δp

1-2

, (P

a)

Luftstrøm i kanalgrenen q2 (l/s)

T-stykke 160/125

Side udsugning Total trykdifferens Δp1-2

Luftstrøm i kanalgrenen q3 (l/s)

T-stykke 160/125

Side indblæsning Total trykdifferens Δp1-3

Tota

l tr

ykd

iffe

ren

s Δp

1-2

, (P

a)

Luftstrøm i kanalgrenen q2 (l/s)

T-stykke 160/125

Side indblæsning Total trykdifferens Δp1-2

Tota

l tr

ykd

iffe

ren

s Δp

1-3

, (P

a)

Luftstrøm i kanalgrenen q3 (l/s)

T-stykke 160/160

Side udsugning Total trykdifferens Δp1-3

Tota

l tr

ykd

iffe

ren

s Δp

1-3

, (P

a)

Luftstrøm i kanalgrenen q3 (l/s)

T-stykke 160/100

Side udsugning Total trykdifferens Δp1-3

Tota

l tr

ykd

iffe

ren

s Δp

1-3

, (P

a)

Luftstrøm i kanalgrenen q2 (l/s)

T-stykke 160/100

Side udsugning Total trykdifferens Δp1-2

Tota

l tr

ykd

iffe

ren

s Δp

1-2

, (P

a)

Luftstrøm i kanalgrenen q3 (l/s)

T-stykke 160/100

Side indblæsning Total trykdifferens Δp1-3

Tota

l tr

ykd

iffe

ren

s Δp

1-3

, (P

a)

Luftstrøm i kanalgrenen q2 (l/s)

T-stykke 160/100

Side indblæsning Total trykdifferens Δp1-2

Tota

l tr

ykd

iffe

ren

s Δp

1-2

, (P

a)

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 17

Page 18: Ventilation installation web

��

2

3

� �� �� 3� 2� ��� ��� ��� �3� �2� ��� ����%! ���% +��'+��� �- � # + '' �N��5!��'6

"�

#�

�'9

( �

��O

��(

��5�

6

3

��

2

��

��

��

3�

���

��

2�

+��5!�'6

�(# 99 % ��3���3���%��'�+�%% Q�"�#� �'9 � ( ���O9�S�

��

2

3�

� �� �� 3� 2� ��� ��� ��� �3� �2� ��� ����%! ���% +��'+��� ���#�# + '' �N��5!��'6

"�

#�

�'9

( �

��O

��(

��5�

6

S��

��

��

��

��

S�

��

+��5!�'6

�(# 99 % ��3���3���%��'�+�%% Q�"�#� �'9 � ( ���O9�S�

��

2

3

� �� �� 3� 2� ��� ��� ��� �3� �2� ��� ����%! ���% +��'+��� ���#�# + '' �N��5!��'6

�4�

"�

#�

�'9

( �

��O

��(

��5�

6

�4�

�4��4�

�43

�4�

�42

��

3

��

2

��

������

�3��8�7+��5!�'6

�(# 99 % ��3���3����'���'�+�%� Q�"�#� �'9 � ( ���O9�S�

(3�

(��

(��

(��

(��

(��

��

��

��

��

��

3�

��

2�

8�

���

� �� �� �� �� �� 3� �� 2� 8� ��� ��� �3� ����%! ���% +��'+��� �- � # + '' �N��5!��'6

"�

#�

�'9

( �

��O

9�S

��5�

6

��

2

3

�+��5!�'6

�(# 99 % ������3����'���'�+�%� Q�"�#� �'9 � ( ���O9�S�

���

��

23

�� �� �� 3� 2� ��� ��� ��� �3� �2� ��� ����%! ���% +��'+��� ���#�# + '' �N��5!��'6

"�

#�

�'9

( �

��O

��(

��5�

6

�4�

�4��4�

�43

�4�

�42

��

3

��

2

��

������

�3��8�7+��5!�'6

�(# 99 % ������3����'���'�+�%� Q�"�#� �'9 � ( ���O9�S�

�4���� �3�

�%! ���% +��'+��� �- � # + '' �N��5!��'6

"�

#�

�'9

( �

��O

9�S

��5�

6

� �� �� �� �� �� 3� �� 2� 8� ��� ��� ������

��

2

3

+��5!�'6

��3�

2�

��3

��

��

��

���

2��

�(# 99 % ������3���%��'�+�%% Q�"�#� �'9 � ( ���O9�S�

��

23�

3� 2� ��� ��� ��� �3� �2� ��� ��� ��� �3� �2��%! ���% +��'+��� ���#�# + '' �N��5!��'6

"�

#�

�'9

( �

��O

��(

��5�

6

S��

��

��

��

��

S�

��

+��5!�'6

�(# 99 % ������3���%��'�+�%% Q�"�#� �'9 � ( ���O9�S�

Luftstrøm i kanalgrenen q2 (l/s)

T-stykke 160/160

Side udsugning Total trykdifferens Δp1-2

Tota

l tr

ykd

iffe

ren

s Δp

1-3

, (P

a)

Luftstrøm i kanalgrenen q3 (l/s)

T-stykke 160/160

Side indblæsning Total trykdifferens Δp1-3

Tota

l tr

ykd

iffe

ren

s Δp

1-2

, (P

a)

Luftstrøm i kanalgrenen q2 (l/s)

T-stykke 160/160

Side indblæsning Total trykdifferens Δp1-2

Tota

l tr

ykd

iffe

ren

s Δp

1-2

, (P

a)

Luftstrøm i kanalgrenen q3 (l/s)

T-stykke 200/160

Side udsugning Total trykdifferens Δp1-3

Tota

l tr

ykd

iffe

ren

s Δp

1-3

, (P

a)

Luftstrøm i kanalgrenen q2 (l/s)

T-stykke 200/160

Side udsugning Total trykdifferens Δp1-2

Tota

l tr

ykd

iffe

ren

s Δp

1-2

, (P

a)

Luftstrøm i kanalgrenen q3 (l/s)

T-stykke 200/160

Side indblæsning Total trykdifferens Δp1-3

Tota

l tr

ykd

iffe

ren

s Δp

1-3

, (P

a)

Luftstrøm i kanalgrenen q2 (l/s)

T-stykke 200/160

Side indblæsning Total trykdifferens Δp1-2

Tota

l tr

ykd

iffe

ren

s Δp

1-2

, (P

a)

18 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 19: Ventilation installation web

qVD = Luftstrøm, l/s

Val = Lufthastighed, m/s

PtD = Totalt tryktab for luft, Pa

ζτ = Total tryk træk koeffi cient, −

Lyddæmpernes lyddæmpning pr. oktav, ISO 7235:2003

STØJREDUKTION ΔL (dB)

Oktavbånd centerfrekvens (Hz)

Mål 63 125 250 500 1000 2000 4000 8000

125x300 2,0 6,5 9,5 15,5 11,0 7,5 8,0 6,0

125x650 5,0 14,5 15,5 23,5 33,0 24,5 22,0 15,5

125x1000 10,5 18,0 20,5 29,0 37,0 36,0 36,5 26,5

160x650 6,0 12,5 12,0 21,0 29,5 18,0 14,5 11,5

160x1000 10,5 17,0 16,0 25,0 30,5 27,5 23,0 16,5

Lyddæmperens tryktab, ISO 7235:2003

125x300 1 2 3 4 5

qVD / l/s 43,7 51,4 65,4 77,5 100,4

Val / m/s 3,6 4,2 5,3 6,3 8,2

PtD / Pa 2,5 3,5 5,6 7,9 13,2

ζτ / − 0,32 0,33 0,33 0,33 0,33

125x650 1 2 3 4 5

qVD / l/s 43,1 49,6 62,4 76,1 93,9

Val / m/s 3,5 4,0 5,1 6,2 7,7

PtD / Pa 5,2 6,9 10,3 15,0 22,3

ζτ / − 0,70 0,71 0,667 0,651 0,634

125x1000 1 2 3 4 5

qVD / l/s 39,4 51,9 66,4 77,5 98,4

Val / m/s 3,2 4,2 5,4 6,3 8,0

PtD / Pa 7,2 12,4 19,3 26,2 40,8

ζτ / − 1,17 1,15 1,10 1,09 1,06

160x650 1 2 3 4 5

qVD / l/s 71,1 86,6 104 127 157

Val / m/s 3,5 4,3 5,2 6,3 7,8

PtD / Pa 5,2 7,9 11,1 16,4 25,2

ζτ / − 0,70 0,71 0,696 0,686 0,689

160x1000 1 2 3 4 5

qVD / l/s 74,1 95,2 116 144 180

Val / m/s 3,7 4,7 5,8 7,2 8,9

PtD / Pa 9,2 15,0 22,6 34,8 55,4

ζτ / − 1,13 1,11 1,13 1,13 1,15

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 19

Page 20: Ventilation installation web

Lyddæmpernes tryktab, ISO 7235:2003

USI-125-300, USI-125-650 og USI-125-1000

USI-160-650 og USI-160-1000

Kanal lufthastighed, m/s

Tota

lt t

ryk, P

a

Luftstrøm, l/s

Luft massefylde 1,2 kg/m³

Kana lufthastighed, m/s

Tota

lt t

ryk,

Pa

Luftstrøm, l/s

Luft massefylde 1,2 kg/m³

20 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 21: Ventilation installation web

Installation

Oversigt

Uponors ventilationskanaler og

-komponenter er lavet af polypro-

pylen plast. De har derfor lille vægt

og er lette at håndtere.

Kanalinstallationen må ikke udsæt-

tes for temperaturer under -15°C.

Kanalerne må ikke kastes, trækkes,

bules eller på anden vis beskadiges.

Kanalerne leveres fra fabrikken med

begge ender tillukkede og pakket

i plastposer og papkasser for har

holde dem rene. Kanalerne og kom-

ponenterne skal beskyttes ved at

holde kanalenderne lukkede og ved

at opbevare komponenterne i deres

respektive emballager, når de op-

bevares på arbejdspladsen. De skal

beskyttes mod lang tids påvirkning

af direkte sollys.

Fjern først endelukningen og

de beskyttende poser, når de

installeres. Åbne ender af præ-

installerede kanaler skal be-

skyttes med endepropper, som

skal forblive på plads, indtil

armaturerne er installerede og

justerede.

Monter passende anbragte rense

lemme i kanalerne for at befordre

rensning.

Kanalmontage

Skæring og samling af kanaler

Uponor kanalerne skal afskæres

vinkelret med en fi ntandet (1-2

mm) sav . Fjern savsmuld fra både

de ydre og de indre overfl ader, og

affas de indre kanter af skærefl aden

for at lette indsættelsen af samle-

stykkerne.

Kanalsamlinger, retningsændrin-

ger og forgreninger må kun udføres

med kanalkomponenter. Kompo-

nenterne er forsynet med paknings-

false i komponentmaterialet. Kana-

lerne har ingen false.

Udfør samlingen ved at skubbe ka-

nalen ind på samlestykket, indtil det

når samlestykkets stopkant. Udfør

samlingerne manuelt; komponen-

terne kan smøres med rent vand

eller vand tilsat lidt opvaskemiddel.

Samlingerne udføres uden skruer

eller nitter.

Dog skal lodrette sektioner un-

derstøttes, så deres vægt ikke

hviler på samlestykket. Hvis

man ikke kan bruge vinkelbeslag,

kan samlingen sikres med 8-10 mm

popnitter, hvis det er nødvendigt.

Skæring og samling af præ-

isolerede kanaler og kanalsek-

tioner

Præisolerede kanaler skæres sam-

men med isoleringen og samles på

samme måde som ikke-isolerede

kanaler og kanalsektioner. I nogle

tilfælde kan det være nødvendigt at

fjerne noget af isoleringen.

Fx ved gennemføring gennem en

dampspærre, skal varmeisoleringen

fjernes på den varme side af fl angen

gennem dampspærren, hvis der ikke

er behov for kondensisolering.

Tip!

Lav et installationsmærke 5 cm fra

kanalens åbning. Det sikrer, at røret

er skubbet helt ind, og at samlingen

er tæt.

Præ-isoleret rørStopkant

Læbering

Aluminumsspændbånd

Stopkant Læbering

Samlekomponent

Aluminiumsspændbånd

Præ-isoleret samlekomponent

Ekstra isolering

Ekstra isolering

Præ-isoleret prop

Præ-isoleret rørPræ-isoleret komponent

Rør

Samlekomponent

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 21

Page 22: Ventilation installation web

1 = Flangepakning

2 = Dampspærre

3 = Kanal

1 = Flangepakning

2 = Dampspærre

3 = Kanal

Kanalføring gennem

dampspærre

Når en kanal skal føres gennem en

struktur med en dampspærre (fx

et tag), skal gennemføringshul-

let forsegles med en dampspærre

fl angepakning. Den ene side af

dampspærre fl angepakningen er

selvklæbende.

Flangepakningen installeres normalt

over dampspærren, så der er tæt

mellem den termiske isolering og

dampspærren.

• Rens fugtspærren for støv m.m.

Fjern den beskyttende plast fra

fl angepakningen og tryk den

hårdt mod fugtspærren ovenfra/

udefra (A).

• Med en skarp kniv, lav en åbning

i dampspærren, der svarer til stør-

relsen af fl angepakningens hul

(B). Sørg for at fl angepakningen

er trykket ind mod dampspærren

på begge sider.

• Skub/træk forsigtigt kanalen

gennem fl angepakningens hul

mens kanalen roteres (C).

• Før kanalen ind på sin endelige

plads, og forbind den til de øvrige

kanaler (D).

Kanalføring af præ-isolerede

kanaler gennem dampspærre

Ved afskæring af præ-isolerede ka-

naler, bemærk at isoleringsmateria-

let skal skæres et andet sted en den

aktuelle kanal.

Varmeisoleringen skal slutte på den

kolde side af dampspærrens fl an-

gepakning. Kanalsektionen på den

varme side af dampspærren kan

efterlades uisoleret, med mindre ka-

nalerne kræver installation af kon-

densisolering.

På den varme side af dampspærren,

fx i et forsænket loft, skal indblæs-

ningskanalen være polystyren-iso-

leret, hvis indblæsningsluften er af-

kølet eller kold, eller hvis luften ikke

er forvarmet om vinteren. I dette

tilfælde afskær polystyren-isolerin-

gen ved fl angepakningen, og for-

segl den lufttæt til dampspærrens

fl angepakning.

22 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 23: Ventilation installation web

Understøttelse

Understøttelse skal udføres med

støtter, der er konstrueret til venti-

lationskanaler.

Den største afstand mellem støt-

ter på vandrette kanaler er 1.500

mm. Der skal (desuden) installeres

en støtte ved hver samling/kom-

ponent.

Lodrette sektioner skal understøt-

tes, så deres vægt ikke hviler på

samlestykket. Også skråtstillede ka-

naler skal understøttes for at hindre

bevægelser under installationen af

armaturer eller ved rengøringen af

kanaler/armaturer.

Støtterne kan fx monteres på støt-

tepælen under kanalen.

Kanalerne skal også fastgøres øverst

på loftsstrukturen for at hindre det i

at fl ytte sig under rengøring.

Understøttelse af præ-isolerede

kanaler

Præ-isolerede kanaler understøt-

tes på nøjagtig samme måde som

uisolerede kanaler. Bemærk dog,

at isoleringen ikke må skæres ved

støttepunktet. I stedet skal støtten

placeres udenpå isoleringen. I dette

tilfælde skal der benyttes støtter

med en større diameter.

1 = Støtte ved nedre

tagafstivning

2 = Isoleret (50 mm) kanal

3 = T-stykke

4 = Støttepæl (hvis støtten

ikke er monteret på tag

afstivningen)

5 = Støtte

Eksempel på understøttelse af en loftsmonte-

ret kanal og et T-stykke.

1 = Kanal

2 = Støtte

3 = Nedre tagafstivning

4 = Nedsænket loft

Eksempel på understøttelse af en kanal over

et forsænket loft.

1 = Kanal + termisk isolering

LE5 (15+50)

2 = Støtte

3 = Støtte ved øvre tagafstiv-

ning

Eksempel på understøttelse af en isoleret kanal

på et loft. Mellemrum mellem støtter maks.

1.500 mm.

1 = Kanal + termisk isolering

2 = Støtte

3 = Nedre tagafstivning

4 = Nedsænket loft

Eksempel på understøttelse af en kanal over

et forsænket loft.

Næstestøttepunktmax. 1500 mm

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 23

Page 24: Ventilation installation web

Isolering

Isoleringens tykkelse er specifi ceret

i ventilationsplanen. Normale isole-

ringstykkelser er som følger:

Varme rum (indenfor damp-

spærren):

• Indblæsnings og udsugnings

luftkanaler har ikke behov for

isolering undtagen kanaler inde i

saunalofter, som skal termisk iso-

leres med 50 mm mineraluld uden

overfl adeafslutning. Hvis indblæs-

ningsluften kan være afkølet, skal

indblæsningsluftkanalerne være

isoleret med ekspanderet PE plast.

Hvis indblæsningsluften ikke er for-

varmet om vinteren, skal kanalerne

være isoleret med ekspanderet PE-

plast.

• Udendørs og afkastluftkana-

ler skal installeres med ekspanderet

PE plast isolering, der fungerer som

kondensisolering.

Uopvarmede områder (udenfor

dampspærren)

• Indsugnings- og afkastluft-

kanaler samt friskluft- og ud-

sugningskanaler, som er anbragt

indenfor den yderste tagisolering,

hvor der er mindst 100 mm løst mi-

neraluldsfyld, skal kondens- og var-

meisoleres med 15 mm ekspande-

ret polystyren. Bemærk, at i dette

tilfælde skal indblæst mineraluld

være anbragt i den øverste del af

tagkonstruktionen.

• Alternativt skal der bruges 50 mm

mineraluld uden overfl adeafslutning

som kanalisolering af udsugnings-,

indsugnings- og afkast-kana-

ler, som er anbragt indenfor den

yderste tag-varmeisolering, hvor

der er mindst 100 mm indblæst løs

isolering.

• Indsugnings- og afkast-luftar-

maturer, der er placeret over den

yderste loftsisolering, skal varme-

isoleres med 15 mm ekspanderet

polystyren + 50 mm mineraluld

uden overfl adeafslutning eller 50 +

50 mm mineraluld uden overfl ade-

afslutning.

• Udsugnings-luftarmaturer, der er

placeret over den yderste loftsiso-

lering, kan varmeisoleres med 50

mm mineraluld uden overfl adeaf-

slutning.

• Friskluftsarmaturer, der er placeret

over den yderste loftsisolering, kan

varmeisoleres med 50 mm mineral-

uld uden overfl adeafslutning.

Når man isolerer kanaler på kolde

steder indenfor loftets termiske

isolering med ekspanderet PE plast,

skal loftets termiske isolering være

altid være baseret på mineraluld.

Men hvis den termiske isolering af

kanalerne er med mineraluld, må

loftet være isoleret med et vilkårligt

lovligt isoleringsmateriale på mar-

kedet.

Isoleringen er svøbt tæt rund om

kanalerne og fastgjort med ståltråd,

strips eller lignende.

Kondensisoleringen af kanalerne er

implementeret med 15 mm ekspan-

deret PE plast, som er ført ind over

kanalen.

Isoleringen kan også være åbnet

lodret, viklet rundt om kanalen og

samlet med limning. Luk de tværgå-

ende og lodrette samlinger tæt med

kontaktlim.

Isoleringen af præ-isolerede kanaler

er tæt, når enden af den præ-iso-

lerede kanal med intern samling

er forbundet meden anden intern

samling. Samlingens tæthed sikres

med to aluminiumsspændbånd.

Præisolerede samlinger, kanaler og

sektioner er installeret korrekt når

de præ-isolerede kanaler er skub-

bet ind, indtil det når stopkanten.

Samlingens tæthed sikres med et

aluminiumsspændbånd.

24 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 25: Ventilation installation web

Kanal isoleringsmuligheder

Kanaler i et varmt rum, i nedsænket

loft eller i en kasse

Lufttemperaturen i kanalen er over + 10 grader

• Udsugningskanal

• Luftforsyningskanal

Ingen isolering Dampspærre

Lufttemperaturen i kanalen er under + 10 grader

• Udeluftkanal til ventilationsenhed• Udsugningskanal fra ventilationsenhed• Luftforsyningskanal

Dampspærre

15 mm ekspanderet isolering LE4

Kanaler i kolde rum

(loft, forsænket loftisolering eller over den)

• Luftforsyningskanal

• Udsugningskanal

• Udeluft til ventilationsenhed

• Udsugningsluft fra

ventilationsenhed

Dampspærre Dampspærre

Dampspærre

Tagbjælke Tagbjælke

Kanaler i løs mineraluld eller tilsvarende Isoleringsmaterialet er PE ekspanderet polystyren LE 4 eller 50 mm mineraluld uden overfl adeafslutning LE3.

Dampspærre

I et koldt rum over lofts-isoleringen er kanalerne isoleret med 15 mm ekspanderet polystyren+ 50 mm mineraluld uden overfl adeafslutning LE5 eller 50 + 50 mm mineral-uld uden overfl adeafslutning LE2.

Dampspærre Dampspærre

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 25

Page 26: Ventilation installation web

Installation og indstilling af luftarmaturer

Oversigt

Installer og indstil først armaturerne

efter den afsluttende rengøring af

arbejdspladsen.

Ventilationssystemet må først ta-

ges i brug, når bygningen er helt

færdig.

Tilslutning af luftarmaturer til kanalerne

1 = Kanal

2 = Dampspærre fl angepakning3 = Kanalsektion til afskæring

4 = Det endelige loft

5 = Armatur

6 = Monteringsskrue

A. Afskær kanalen til niveauet for

det endelige loft med en fi ntandet

sav eller end kanal skæretang. Fast-

gør kanalen indefra med to monte-

ringsskruer.

B. Indsæt armaturet i kanalen. Ar-

maturet låser selv til kanalen, og

montageproceduren er færdig. Be-

mærk venligst: Hvis det loftsmon-

terede armatur er monteret på en

komponent i stedet for en kanal,

skal kanalpakningen skæres tættere

på langs den punkterede linje med

en saks eller en skarp kniv.

C. Indblæsnings- og udsug-

ningsarmaturer er i saunaer for

loftsmontage er forsynet med mon-

teringsrammer, der skal fastgøres til

loftsstrukturen med skruer. Installer

armaturet i rammen ved at dreje

det. Loftsmonterede rammer, der

er installeret over saunaovnen, skal

altid være sikret med skruer.

D. Det loftsmonterede armaturs

(ø 125) krave er en ophøjet ring,

som fører den udgående luft gen-

nem loftet. Dette forhindrer støv i

indeluften i at komme op, og det

holder loftet rent. Den ophøjede

krave er velegnet til både nye byg-

ninger og renovering.

Installation af kraven

Afskær kanalen 50 mm under lof-

tets underside. Installer kraven på

ventilen. Skub ventilen op på kana-

len, så kraven tætter mellem venti-

len og loftet.

Hvis kanalen er afskåret til overfl a-

dens niveau, skal kanalen forlæn-

ges. Skær kanalpakningen tættere

på langs den punkterede linje, og

installer armaturet og kraven som

angivet i trin B.

Diameter 125

Produktkode 1046218

E. Installer det vægmonterede

armatur ved at skubbe det ind i

kanalen, som er afskåret i niveau

med væggens overfl ade. Armaturets

dæksel kan fjernes ved at vride det

af med en skruetrækker. Basispla-

den er forsynet med huller til mon-

teringsskruerne.

"����)'� �,�

Uponors ventilationssystemarma-

turer er klar til brug som indblæs-

nings- eller udsugningsarmaturer

med Uponor kanaler.

Udvidelse

Krave

Armatur

A. B. C.

� 3 �

� 3 �

� 3 �

Fastgørelseshuller

26 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 27: Ventilation installation web

Friskluftrist

Friskluftsristene er forsynet med

let udtagelig netkassette eller in-

sektnet.

Netkassetten skal renses regelmæs-

sigt, op til én gang om måneden på

de varme årstider (april-oktober).

Behovet for rensning kan variere

stærkt afhængig af bygningens

placering.

Det hvide ABS plastgitter kan males

med fx sprøjtemaling, og grunding

er normalt ikke nødvendig. Kon-

troller altid først, om malingen kan

bruges på ABS plast. Før malingen,

rens overfl aden med fx acetone.

Friskluftsventil til vægmontage

(udendørs luftarmatur med fi lter i

ventilation med mekanisk udblæs-

ning)

Armaturet installeres i et hul,

ø 106 mm, boret eller udsavet over

vinduet. Armaturet åbnes og lukkes

med træksnoren.

Installation

Åbn det indvendige armatur med

træksnoren, og skru dækslet af. Ro-

ter friskluftristen lidt mod uret, og

træk det af. Afkort kanalforlængel-

sen, så den passer til murens tykkel-

se. Installer kanalen og selve arma-

turet, og fastgør dem med skruer.

Skru friskluftristen og dækslet på

igen, og juster armaturåbningen.

Fastgør friskluftristens holder med

skruer. Installer friskluftristen ved

at presse det ind på friskluftristens

holder.

Vedligeholdelse

Rens fi lteret to gange om året med

varmt vand.

Friskluftsventil til ventilationshul

(udendørs luftarmatur med fi lter i

ventilation med mekanisk udblæs-

ning)

Installer armaturet i et hul,

ø 106 mm, boret eller udsavet over

ventilhullet.

Installation

Åbn den indvendige ventil med

træksnoren, og skru dækslet af. Ro-

ter friskluftristen lidt mod uret, og

træk det af.

Installer selve armaturet og det løse

bunddæksel med skruer. Hvis muren

ved ventilhullet er over 90 mm tyk,

forlæng armaturet med den medle-

verede forhøjelsesring.

Skru friskluftristen og dækslet på

igen, og juster armaturåbningen ved

at dreje dækslet.

Luftføring

Luftføringen kan rettes opad, mod

venstre eller mod højre. Hvis der fx

er en radiator til venstre rettes luft-

føringen mod venstre.

Luftføringen kan trækkes ud for at

drejes ved først at åbne armatu-

ret ved træksnoren og derpå skrue

dækslet af.

Vedligeholdelse

Rens fi lteret to gange om året med

varmt vand.

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 27

Page 28: Ventilation installation web

Spalteventil

(Friskluftventil med fi lter til luftind-

tag ved mekanisk ventilation med

afkast.)

Installer armaturet enten i en 19 x

250 mm spalte i toppen af vindues-

rammen eller mellem vinduesram-

men og muren. Hvis spalteventilen

er monteret over en radiator, skal

den indre kant vende opad og den

ydre kant vende nedad.

Vedligeholdelse

Rens fi lteret to gange om året med

varmt vand. Træk fi lteret i armatu-

rets rørsektion ud, efter at lukkela-

mellerne er fjernet ved at løsne de

to monteringsskruer.

Justering af armaturer

Juster armaturerne som vist i juste-

ringskurverne på side 24-25 ved at

rotere armaturskiven (loftsmonte-

rede armaturer) eller ved at åbne

nogle rækker huller (vægmonterede

armaturer). Trykdifferensen måles

på de punkter, der er vist på de til-

hørende tegninger. Efter justerin-

gen lås armaturernes position med

låseskruerne.

Et manometer kan også bruges til

at justere og kontrollere justerin-

gen af armaturerne. I dette tilfælde

er armaturets lukkede tilstand, dvs.

armaturets 0-niveau, følgende:

- Luftindblæsning, loft, ø 125:

+10 mm

- Luftindblæsning, loft, ø 100:

+10 mm

- Luftudsugning, loft, ø 125:

-3 mm

- Luftudsugning, loft, ø 100:

-1 mm

- Saunaarmatur, loft, ø 125:

+8 mm

Armaturerne præ-justeres før den

endelige justering og måling. De

præ-justerede værdier ved et tryk-

tab over armaturet på 20 Pa ses i

tabellerne på næste side.

Efter installationen af luftindblæs-

ningsarmaturerne, kan lukkelamel-

lerne fjernes fra rammen med en

skarp kniv.

- Mål trykdifferensen på punkterne

vist i tegningen.

- Juster ved at rotere ventilspind-

len, stigning 1 mm/omdrejning.

- 0-niveau = lukket armatur.

- Sidehuller åbne/lukkede.

- Åbn det nødvendige antal huller

med en saks eller kniv.

- Geninstaller lukkelamellerne ved

at trykke dem på plads.

� � !��� �'

� � !��� ��

��%#��' �

Friskluftsventil

(Friskluftventil med fi lter til luftind-

tag ved mekanisk ventilation med

afkast.)

Armaturet installeres i et hul,

ø 106 mm, boret eller udsavet midt

over vinduet.

Trykmåling

Lukkelameller

Manometer

28 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 29: Ventilation installation web

Tabeller over armatur fabriksindstillinger, trykdifferens 20 Pa

Luftindblæsningsarmaturer

Udsugningsarmaturer

Udsugningsluft

l/s

Udsugningsarma-

tur 125

Omdr. åben

Udsugningsarma-

tur 100

Omdr. åben

Udsugningsluft

l/s

Udsugningsarma-

tur 125

Omdr. åben

Udsugningsarma-

tur 100

Omdr. åben

3 3 4 11 14 20

4 4 6 12 15

5 6 8 13 16

6 7 10 14 18

7 8 12 15 20

8 10 14 16 22

9 11 16 17 23

10 13 18 18 24

Indblæsningsluft l/s

Loft-monteret/sauna armaturer 125

Omdrejninger åben

Loft-monteret/sauna armaturer 100

Omdrejninger åben

Vægmonterede armaturer100 & 125

Sidehuller åben

Rækker af åbne huller

Vægmonterede armaturer100 & 125

Sidehuller luk-kede.

Rækker af lukkede huller

6 3 4 2 3

7 4 4 3 3

8 4 5 3 4

9 5 6 4 5

10 5 6 4 5

11 6 5 6

12 6 6 6

13 7 7 7

14 8 8 8

15 9 9 9

16 10 9 10

17 11 10 10

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 29

Page 30: Ventilation installation web

"� ���#'� �,,�* ' ���!!

���

���

���

��

��

��

��

���UW�X

$���

�'9

( �

���

�������������������������3��8������

���UW�X���UW�X

���UW�X

"Y�

48

"Y�

43

"Y�

4�"

Y�48

"Y�

4�"

Y�4�

"� ���#'� �,,�* ' ���!!

���

���

���

��

��

��

��

���UW�X

$���

�'9

( �

���

�������������������������3��8������

���UW�X���UW�X

���UW�X

"Y�

48

"Y�

43

"Y�

4�"

Y�48

"Y�

4�"

Y�4�

"� ���#'� �,,�* ' ���!!

���

���

���

��

��

��

��$���

�'9

( �

���

��������������������������3���8������

���UW�X

���UW�X

���UW�X

���UW�X

"Y�

48

"Y�

4�

"Y�

4�"

Y�43

"Y�

4�"

Y�4�

"� ���#'� �,,�* ' ���!!

���

���

���

��

��

��

��$���

�'9

( �

���

��������������������������3���8������

���UW�X

���UW�X

���UW�X

���UW�X

"Y�

48

"Y�

4�

"Y�

4�"

Y�43

"Y�

4�"

Y�4�

Luftstrøm, trykdifferens og støjniveau

Luftindblæsning loftsarmaturer Ø100

OmdrejningerJusteringsposition mm

Mål

t tr

ykd

iffe

ren

s P

a

Luftindblæsning loftsarmaturer Ø125

OmdrejningerJusteringsposition mm

Mål

t tr

ykd

iffe

ren

s P

a

Sauna luftindblæsningsarmaturer Ø100

OmdrejningerJusteringsposition mm

Mål

t tr

ykd

iffe

ren

s P

a

Sauna luftindblæsningsarmaturer Ø125

OmdrejningerJusteringsposition mm

Mål

t tr

ykd

iffe

ren

s P

a

Udsugningsarmaturer Ø100

OmdrejningerJusteringsposition mm

Mål

t tr

ykd

iffe

ren

s P

a

Udsugningsarmaturer Ø125

OmdrejningerJusteringsposition mm

Mål

t tr

ykd

iffe

ren

s P

a

30 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 31: Ventilation installation web

Luftindblæsning vægarmaturer Ø100 med lukkede

sidehuller

Justeringsposition, rækker med åbne huller

Mål

t tr

ykd

iffe

ren

s P

a

Luftindblæsning vægarmaturer Ø125 med lukkede

sidehuller

Justeringsposition, rækker med åbne huller

Mål

t tr

ykd

iffe

ren

s P

a

Luftindblæsning vægarmaturer Ø100 med åbne

sidehuller

Mål

t tr

ykd

iffe

ren

s P

a

Luftindblæsning vægarmaturer Ø125 med åbne

sidehuller

Mål

t tr

ykd

iffe

ren

s P

a

Justeringsposition, rækker med åbne huller

Justeringsposition, rækker med åbne huller

Luftstrøm, trykdifferens og støjniveau

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 31

Page 32: Ventilation installation web

Luftstrøm og trykdifferens

Friskluftsarmatur ø100 Spalteventil 18x245x340

Tryk

fors

kel, P

a

Tryk

fors

kel, P

a

Uden fi lter

Med fi lter

Friskluftsriste

Mål

t tr

ykfo

rskel P

a

Mål

t tr

ykfo

rskel P

a

Mål

t tr

ykfo

rskel P

a

32 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 33: Ventilation installation web

Bemærkninger

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 33

Page 34: Ventilation installation web

Bemærkninger

34 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0

Page 35: Ventilation installation web

Bemærkninger

U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 35

Page 36: Ventilation installation web

Uponor A/S

Uponor VVS

Banemarksvej 2A

2600 Glostrup

T 4326 3400

F 4343 1011

E [email protected]

W www.uponor.dk

KAIKKI KANAVATUponor Suomi OyNastola - Forssa

01

.06

.20

07

SE

NE

WA

OY