Ventilation in Sewers Quantified
from Measurements of CO2
Presenter: Emil D. Fuglsang
Co-authors: Asbjørn H. Nielsen, Jes Vollertsen
Department of Civil Engineering
Aalborg University, Denmark
![Page 2: Ventilation in Sewers Quantified from Measurements of COhikom.grf.bg.ac.rs/stari-sajt/9UDM/Presentations/012_PPT.pdf · Ventilation in Sewers Quantified from Measurements of CO 2](https://reader034.fdocuments.us/reader034/viewer/2022042804/5f55caebb0c3d815b723e8e9/html5/thumbnails/2.jpg)
Conveyer of water
Conveyer of gas
Biological and chemical reactor
WHAT IS A SEWER?
Gas flow
Water flow
![Page 3: Ventilation in Sewers Quantified from Measurements of COhikom.grf.bg.ac.rs/stari-sajt/9UDM/Presentations/012_PPT.pdf · Ventilation in Sewers Quantified from Measurements of CO 2](https://reader034.fdocuments.us/reader034/viewer/2022042804/5f55caebb0c3d815b723e8e9/html5/thumbnails/3.jpg)
Odor problems
- As long as the smelly sewer gas stays in the sewer – why
care?
Asset corrosion
- Corrosive hydrogen sulfide attacks concrete and metals
Safety issues
- Hydrogen sulfide is highly toxic
WHY STUDY VENTILATION?
![Page 4: Ventilation in Sewers Quantified from Measurements of COhikom.grf.bg.ac.rs/stari-sajt/9UDM/Presentations/012_PPT.pdf · Ventilation in Sewers Quantified from Measurements of CO 2](https://reader034.fdocuments.us/reader034/viewer/2022042804/5f55caebb0c3d815b723e8e9/html5/thumbnails/4.jpg)
Sewer gas is transported by means of:
- Drag effects
- Wind at surface
- Barometric pressure gradients
- Temperature gradients
- Changes in water level – pumps starting and stopping
WHAT DO WE KNOW ABOUT SEWER
VENTILATION?
![Page 5: Ventilation in Sewers Quantified from Measurements of COhikom.grf.bg.ac.rs/stari-sajt/9UDM/Presentations/012_PPT.pdf · Ventilation in Sewers Quantified from Measurements of CO 2](https://reader034.fdocuments.us/reader034/viewer/2022042804/5f55caebb0c3d815b723e8e9/html5/thumbnails/5.jpg)
Measuring methods typically used:
- Anemometers
- Tracer gas experiments
- Pressure transducers
- Physical models
Ventilation is a dynamic
phenomenon changing in time and
space
Tracer measurements and
velocities are labour intensive and
do seldom give us the full
dynamics of the process
HOW IS VENTILATION MEASURED?
Madsen H I, Hvitved-Jacobsen T, Vollertsen J (2006).
Gas Phase Transport in Gravity Sewers – A methodology for determination of
horizontal gas transport and ventilation.
Water Environment Research, 78(11), 2203-2209
![Page 6: Ventilation in Sewers Quantified from Measurements of COhikom.grf.bg.ac.rs/stari-sajt/9UDM/Presentations/012_PPT.pdf · Ventilation in Sewers Quantified from Measurements of CO 2](https://reader034.fdocuments.us/reader034/viewer/2022042804/5f55caebb0c3d815b723e8e9/html5/thumbnails/6.jpg)
We test if CO2 can be used as a naturally occuring tracer –
overcomming those issues
OBJECTIVES
![Page 7: Ventilation in Sewers Quantified from Measurements of COhikom.grf.bg.ac.rs/stari-sajt/9UDM/Presentations/012_PPT.pdf · Ventilation in Sewers Quantified from Measurements of CO 2](https://reader034.fdocuments.us/reader034/viewer/2022042804/5f55caebb0c3d815b723e8e9/html5/thumbnails/7.jpg)
CONCEPTUAL IDEA
High CO2 concentrations in water
Caused by biodegradation and
potable water CO2 contents
Easily measurable
Low CO2 concentrations in atmosphere
Constant
CO2 is released at a known rate from
water to gas
Release rates depend on hydraulic
conditions in the pipe
![Page 8: Ventilation in Sewers Quantified from Measurements of COhikom.grf.bg.ac.rs/stari-sajt/9UDM/Presentations/012_PPT.pdf · Ventilation in Sewers Quantified from Measurements of CO 2](https://reader034.fdocuments.us/reader034/viewer/2022042804/5f55caebb0c3d815b723e8e9/html5/thumbnails/8.jpg)
CONCEPTUAL IDEA
In a completely closed system the partial
pressure of CO2 is the same in the water
as in the gas
In a completely ventilated system, the
partial pressure of CO2 in the sewer gas
is the same as in the atmosphere
In a partly open system, the CO2
concentration in the gas tells us how fast
the sewer gas is ventilated out
![Page 9: Ventilation in Sewers Quantified from Measurements of COhikom.grf.bg.ac.rs/stari-sajt/9UDM/Presentations/012_PPT.pdf · Ventilation in Sewers Quantified from Measurements of CO 2](https://reader034.fdocuments.us/reader034/viewer/2022042804/5f55caebb0c3d815b723e8e9/html5/thumbnails/9.jpg)
We have tested this at an intercepting sewer in Denmark
PROJECT SITE
![Page 10: Ventilation in Sewers Quantified from Measurements of COhikom.grf.bg.ac.rs/stari-sajt/9UDM/Presentations/012_PPT.pdf · Ventilation in Sewers Quantified from Measurements of CO 2](https://reader034.fdocuments.us/reader034/viewer/2022042804/5f55caebb0c3d815b723e8e9/html5/thumbnails/10.jpg)
Installation of equipment in the sewer
MEASUREMENT CAMPAIGN
![Page 11: Ventilation in Sewers Quantified from Measurements of COhikom.grf.bg.ac.rs/stari-sajt/9UDM/Presentations/012_PPT.pdf · Ventilation in Sewers Quantified from Measurements of CO 2](https://reader034.fdocuments.us/reader034/viewer/2022042804/5f55caebb0c3d815b723e8e9/html5/thumbnails/11.jpg)
Data from January 2012
RESULTS
Time Jan 13-14 2012
17:00 21:00 01:00 05:00 09:00
pH
[-]
7.0
7.5
8.0
8.5
9.0
Concentr
ation o
f C
O2 [ppm
]
0
2000
4000
6000
8000
10000
12000
14000
pH
CO2
Background CO2
Equilibrium concentration
![Page 12: Ventilation in Sewers Quantified from Measurements of COhikom.grf.bg.ac.rs/stari-sajt/9UDM/Presentations/012_PPT.pdf · Ventilation in Sewers Quantified from Measurements of CO 2](https://reader034.fdocuments.us/reader034/viewer/2022042804/5f55caebb0c3d815b723e8e9/html5/thumbnails/12.jpg)
CONCEPTUAL IDEA
Known
Known
Known
Calculated
![Page 13: Ventilation in Sewers Quantified from Measurements of COhikom.grf.bg.ac.rs/stari-sajt/9UDM/Presentations/012_PPT.pdf · Ventilation in Sewers Quantified from Measurements of CO 2](https://reader034.fdocuments.us/reader034/viewer/2022042804/5f55caebb0c3d815b723e8e9/html5/thumbnails/13.jpg)
WHAT WILL THE RETENTION TIME BE?
Calculated sewer gas retention time [hours]
0 1 2 3 4 5 6
Pro
ba
bili
ty [%
]
10
30
50
70
90Jan 13-14, 2012
Feb 3-4, 2012
![Page 14: Ventilation in Sewers Quantified from Measurements of COhikom.grf.bg.ac.rs/stari-sajt/9UDM/Presentations/012_PPT.pdf · Ventilation in Sewers Quantified from Measurements of CO 2](https://reader034.fdocuments.us/reader034/viewer/2022042804/5f55caebb0c3d815b723e8e9/html5/thumbnails/14.jpg)
To release CO2 from the water to the air, pH must be below ~8
A sufficient amount of alkalinity must be present in the
wastewater
LIMITATIONS OF THE METHOD
![Page 15: Ventilation in Sewers Quantified from Measurements of COhikom.grf.bg.ac.rs/stari-sajt/9UDM/Presentations/012_PPT.pdf · Ventilation in Sewers Quantified from Measurements of CO 2](https://reader034.fdocuments.us/reader034/viewer/2022042804/5f55caebb0c3d815b723e8e9/html5/thumbnails/15.jpg)
A new approach to the sewer air ventilation has been
suggested
In this case study sewer-air retention times around 1.5-2.5
hours were found
The method should be addaptable to other systems as long as
the pH is not too high and when a certain amount of alkalinity
is present
CONCLUSIONS
![Page 16: Ventilation in Sewers Quantified from Measurements of COhikom.grf.bg.ac.rs/stari-sajt/9UDM/Presentations/012_PPT.pdf · Ventilation in Sewers Quantified from Measurements of CO 2](https://reader034.fdocuments.us/reader034/viewer/2022042804/5f55caebb0c3d815b723e8e9/html5/thumbnails/16.jpg)
Questions?