vacon - Danfoss · 2019. 12. 10. · The OPTBJ option board together with VACON® 100 family...

47
safety manual sto and atex option board optbj ac drives vacon ® 100 hvac vacon ® 100 flow vacon ® 100 industrial

Transcript of vacon - Danfoss · 2019. 12. 10. · The OPTBJ option board together with VACON® 100 family...

  • safety manualsto and atex option board

    optbj

    ac drivesvacon® 100 hvacvacon® 100 flow

    vacon® 100 industrial

  • vacon • 3

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

    TABLE OF CONTENTS Document: DPD00470E

    Release date : 24092018

    1. Approvals.........................................................................................................42. General ..........................................................................................................102.1 References .......................................................................................................................113. Installation of OPTBJ board ...........................................................................124. OPTBJ board layout........................................................................................154.1 Identifying board revision.................................................................................................154.2 OPTBJ board jumpers......................................................................................................164.3 STO jumper on the VACON® 100 family AC drive ...........................................................174.4 Cuttable jumper to separate control ground from PE ....................................................185. STO and SS1 safety functions .........................................................................195.1 Safe Torque Off (STO) principle .......................................................................................205.2 Safe Stop 1 (SS1) Principle ..............................................................................................225.3 Technical details ..............................................................................................................245.3.1 Response times................................................................................................................245.3.2 Input voltage levels ..........................................................................................................245.3.3 External dark test pulse filtering capability ....................................................................245.3.4 External light test pulse filtering capability ....................................................................255.3.5 Connections......................................................................................................................255.3.6 Relay output .....................................................................................................................265.3.7 Safety-related data according to the standard ...............................................................276. Commissioning ..............................................................................................296.1 General wiring instructions .............................................................................................296.2 Wiring examples ..............................................................................................................326.3 Parameterization of STO functionality.............................................................................366.4 Checklist for commissioning the OPTBJ board...............................................................376.5 Testing the Safe Torque Off (STO) or Safe Stop 1 (SS1) safety functions .......................387. Maintenance...................................................................................................397.1 Faults related to the Safe Torque Off (STO) or Safe Stop 1 (SS1) safety functions ........398. Thermistor function (ATEX) ...........................................................................418.1 Technical data ..................................................................................................................458.1.1 Functional description .....................................................................................................458.1.2 Hardware and connections ..............................................................................................458.1.3 Atex function ....................................................................................................................458.1.4 Short circuit monitoring...................................................................................................468.2 Commissioning ................................................................................................................468.2.1 General wiring instructions .............................................................................................468.2.2 Fault diagnosis of thermistor function ............................................................................46

    NOTE! You can download the English and French product manuals with applicable safety, warning and caution information from https://www.danfoss.com/en/service-and-support/.

    REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit contenant l’ensemble des informations de sécurité, avertissements et mises en garde applicables sur le site https://www.danfoss.com/en/service-and-support/.

    http://www.vacon.com/downloads

  • 1

    vacon • 4 Approvals

    1. APPROVALS

    Date Issued by Date Approved by15-04-2016 Signature

    Name: Antti Vuola Title: Head of Standard Drives

    15-04-2016 Signature Name: Timo Kasi Title: VP, Design Center Finland and Italy

    Danfoss only vouches for the correctness of the English version of this declaration. In the event of the declaration being translated into any other language, the translator concerned shall be liable for the correctness of the translation. ID No: DPD01856 Revision No: A Page 1 of 1

    Danfoss A/SDK-6430 Nordborg Denmark CVR nr.: 20 16 57 15 Telephone: +45 7488 2222 Fax: +45 7449 0949

    EU DECLARATION OF CONFORMITY Danfoss A/S

    Vacon Ltd declares under our sole responsibility that the Product name Vacon OPTBJ option board to be used with Vacon 100 family products Product identification 70CVB01380 Product Safety Functions Safe Torque Off (Specified in EN 61800-5-2) fulfils all of the relevant safety component requirements of EC Machinery Directive 2006/42/EC. Notified body that carried out the EC type examination:

    TÜV Rheinland Industrie Service GmbH (NB0035) Am Grauen Stein, 51105 Köln, Germany

    The following standards and/or technical specifications referenced below were used: - EN 61800-5-2:2007

    Adjustable speed electrical power drive systems, Part 5-2: Safety requirements – Functional - EN 61800-5-1:2007 (only for LV Directive compliance)

    Adjustable speed electrical power drive systems, Part 5-2: Safety requirements - Electrical, thermal and energy

    - EN 61800-3:2004/A1:2012 (only for EMC Directive compliance) Adjustable speed electrical power drive systems, Part 3: EMC requirements and specific test methods

    - EN ISO 13849-1:2008 + AC:2009 Safety of machinery - Safety-related parts of control systems –, Part 1: General principles for design

    - EN 62061:2005 + AC:2010 Safety of machinery - Functional safety of safety-related electrical, electronic and programmable electronic control systems

    - IEC 61508 Parts 1-7:2010 Functional safety of electrical/electronic/programmable electronic safety-related systems

    - EN 60204-1:2006 + A1:2009 + AC:2010 (in extracts) Safety of machinery – Electrical equipment of machines – Part 1: General requirements

    - EN 61326-3-1:2008 Electrical equipment for measurement, control and laboratory use – EMC, Part 3-1: Immunity requirements for safety-related systems and for equipment intended to perform safety-related functions (functional safety).

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • Approvals vacon • 5

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 1

  • 1

    vacon • 6 Approvals

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • Approvals vacon • 7

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 1

  • 1

    vacon • 8 Approvals

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • Approvals vacon • 9

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 1

  • 2

    vacon • 10 General

    2. GENERALThis document covers OPTBJ option board 70CVB01380D (or newer).

    NOTE! Designing of safety-related systems requires special knowledge and skills. Only qualified persons are permitted to install and set up the OPTBJ board.

    This document covers the OPTBJ option board 70CVB01380 functionality together with VACON® 100 family Control board 70CVB01582.

    The OPTBJ option board together with VACON® 100 family control board provides the following safety functions with VACON® 100 family products.

    The following safety-related abbreviations and expressions have been used in this manual:

    Table 1. Version history of the manual

    Date Revision Updates

    09/2018 E

    • Updated ATEX certificate • Updated EC declaration• Corrected option board graphics

    and slot coding information in chapter 3

    • Added new chapters: 4.1, 4.4, 5.3.2, 5.3.3 and 5.3.4

    • Added wiring examples in chapter 6.1

    • Changed cable recommendation information in chapter 6.1

    • Added new chapter 6.3• Corrected the notes related to

    edge sensitive start command in chapter 6.2 (the chapter was moved here from end of chapter 5)

    • Discrepancy time of STO inputs increased from 50 ms to 500 ms for board revision D. Change affects chapters 5.3.2, 5.3.5 and 7.1.

    • Other minor updates.Throughout the manual.

    SIL Safety Integrity LevelPL Performance LevelPFH Probability of a dangerous random hardware Failure per HourCategory Designated architecture for a safety function (from EN ISO 13849-1:2006)MTTFd Mean time to dangerous failureDCavg Average diagnostic coveragePFDavg Average probability of (random hardware) failure on demandTM Mission timeSafety actuator

    Device that controls the safety-related signal lines. Can be, for example, emergency button, safety PLC, safety relay.

    OSSD Output Signal Switching Device, i.e. switch that controls the signal lines between actuator and the drive's signal input.

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • General vacon • 11

    Safe Torque Off (STO)The hardware based 'Safe Torque Off' safety function prevents the drive from generating torque on the motor shaft. The STO safety function has been designed for use in accordance with the following standards:

    • EN 61800-5-2 Safe Torque Off (STO) SIL3• EN ISO 13849-1 PL"e" Category 3• EN 62061: SILCL3• IEC 61508: SIL3• The function also corresponds to an uncontrolled stop in accordance with the stop category 0, EN

    60204-1.• The STO safety function has been certified by TÜV Rheinland

    NOTE! The STO function is not the same as a prevention of unexpected start-up function. For fulfilling those requirements, additional external components are required according to appropriate standards and applica-tion requirements. Required external components may be for example:

    • Appropriate lockable switch• A safety relay providing a reset function

    NOTE! The safety functions of OPTBJ do not comply with Emergency Switching Off according to EN 60204-1.

    NOTE! Do not use the STO function as a standard stop function of the drive.

    NOTE! In an IGBT fault situation, the shaft of a permanent magnet motor can rotate up to 180 degrees around the pole of the motor.

    NOTE! If the pollution degree 2 cannot be guaranteed, use the IP54 protection class.

    Safe Stop 1 (SS1)The SS1 safety function is realized in compliance with type C of the drives safety standard EN 61800-5-2 (Type C: "The PDS(SR) initiates the motor deceleration and initiates the STO function after an application specific time delay").

    The SS1 safety function has been designed for use in accordance with the following standards:• EN 61800-5-2 Safe Stop 1 (SS1) SIL2• EN ISO 13849-1 PL"d" Category 3• EN 62061: SILCL2• IEC 61508: SIL2• The function also corresponds to a controlled stop in accordance with the stop cat. 1, EN 60204-1.

    Motor Thermistor Over temperature protection (according to ATEX)Overtemperature detection using thermistor. It can be used as a tripping device for ATEX certified motors.

    The thermistor tripping function is certified by VTT* according to ATEX directive 94/9/EC.

    All safety functions of the OPTBJ board are described in this manual.* VTT = Technical Research Centre of Finland

    2.1 ReferencesVACON® 100 family Installation and Application manuals are downloadable at https://www.dan-foss.com/en/service-and-support/.

    CAUTION! The OPTBJ board and its safety functions do not electrically isolate the drive output from the mains supply. If electrical work is to be carried out on the drive, the motor or the motor cabling, the drive has to be completely isolated from the mains supply, for example, using an external supply disconnecting switch. See, for example, EN60204-1 Chapter 6.5.

    13006.emf

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 2

    http://www.vacon.com/downloads

  • 3

    vacon • 12 Installation of OPTBJ board

    3. INSTALLATION OF OPTBJ BOARD

    1

    Open the cover of the AC drive.

    The relay outputs and other I/O-terminals may have a dangerous control voltage present even when VACON® 100 family AC drive is disconnected from mains.

    2

    NOTE: Incompatible boards cannot be installed on VACON® 100 family AC drives. Boards that are compatible for VACON® 100 family AC drives have two codings that enable the placing of the board (see above): one for VACON® 100 family compatibility (A), and another for the slot-specific placing (B).

    M4x55

    11573_00

    9000.emf

    3040A_00A B

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • Installation of OPTBJ board vacon • 13

    3

    Open the inner cover to reveal the option board slots and install the OPTBJ board into slot E. Close the inner cover.NOTE! See Chapter 4.2 for the jumper settings!

    4

    If shielded cable is used, ground the shield of the OPTBJ cable to the frame of the drive by using the grounding clamp for control cable included in the delivery of the drive.NOTE! If shielded cable is used, grounding must be done according to best prac-tice.

    E

    3041A_00

    11574A_uk

    Grounding clamp for control cable

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 3

  • 3

    vacon • 14 Installation of OPTBJ board

    5

    Unless already done for the other control cables, cut free the opening on the AC drive cover for the OPTBJ cable (protection class IP21). NOTE: Cut the opening on the side of the slot E!

    6

    Remount the AC drive cover and run the cable as shown in picture.NOTE: When planning the cable runs, remember to keep the distance between OPTBJ cables and the motor cable at a minimum of 30 cm. It is rec-ommended to route the OPTBJ cables away from the power cables as shown in the picture.

    11576_00

    11572_uk

    OPTBJ cables

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • OPTBJ board layout vacon • 15

    4. OPTBJ BOARD LAYOUT

    Figure 1. OPTBJ board layout

    4.1 Identifying board revisionThe revision of OPTBJ board can be identified by checking the revision letter on the matrix bar code sticker. Revision letter is written after the board type code. For example, '70CVB01380 D' indicates that the board is of revision D. Some features may be introduced or changed during board updates.

    Figure 2. The board identification sticker on the OPTBJ board

    1234

    2526

    2829

    3038A_uk

    X23

    X10STO JMP

    Thermistor shortcircuit supervision

    On Off

    Jumper for selectingthermistor short circuitsupervision

    Jumper for STO boardactivation. Place here the3-pin jumper fromthe control board.

    STO inputs

    Relay outputfor STO function

    Thermistor Input:Thermistor active > 4000 ohm.After being active, the fault canbe reset if resistance is < 2000 ohm

    STO1+STO1-STO2+STO2-

    TI1+

    TI1-

    11855_00

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 4

  • 4

    vacon • 16 OPTBJ board layout

    4.2 OPTBJ board jumpersThere are two pin headers for jumpers on the OPTBJ option board. The jumper settings are de-scribed below:

    Figure 3. OPTBJ board jumpers

    To activate the OPTBJ board, you must take the three-pin jumper from the drive control board and place it to the OPTBJ board jumper X10. See the next chapter for more information.

    NOTE! If there are problems with the jumpers, see chapter 7.1!

    Jumper X23, short circuit supervision

    3039A_uk

    Jumper X10, STO board activation

    STO board activated. Jumper has to be placed here when OPTBJ is installed in the drive. Take the jumper from the control board.

    Short circuit supervision ON

    Short circuit supervision OFF

    STO board not activated

    = Factory default

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • OPTBJ board layout vacon • 17

    4.3 STO jumper on the VACON® 100 family AC drive

    Figure 4. STO jumper location on VACON® 100 family AC drive. Open the main cover and the inner cover to reveal the jumper.

    3049A_00

    STO JMP

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 4

  • 4

    vacon • 18 OPTBJ board layout

    4.4 Cuttable jumper to separate control ground from PE

    Figure 5.Location of cuttable jumper X15

    Normally when the OPTBJ board is installed on the drive, the AC drive's control ground is connected to PE (Protective Earth, drive's frame) through the OPTBJ board. Without the OPTBJ board, the con-trol ground is connected to PE through high impedance. In some systems, the control ground may need to be separated from PE when the OPTBJ board is installed. Do not do this before consulting the Danfoss support personnel (contact the Danfoss local contacts at http://drives.danfoss.com/danfoss-drives/local-contacts/). If the jumper is cut, at least 1 mm of wire from X15 needs to be re-moved to ensure isolation.

    CAUTION! Cutting this jumper should be done only when it is required by the sys-tem. After the jumper is cut, the drive's internal +24VDC can be used for external safety devices if fault exclusion in wiring 'Short circuit of any conductor to an exposed conductive part or earth or to the protective bonding conductor' accord-ing to EN ISO 13849-2 can be achieved.

    11856_00

    X15

    13006.emf

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • STO and SS1 safety functions vacon • 19

    5. STO AND SS1 SAFETY FUNCTIONSThe safety functions of the OPTBJ board, such as the technical principle and data, wiring examples and commissioning, will be described in this chapter.

    NOTE! The use of STO, SS1 or other safety functions does not itself ensure safety. An overall risk evaluation is required in order to make sure that the commissioned system is safe. Safety devices like the OPTBJ board must be correctly incorporated into the entire system. The entire system must be designed in compliance with all relevant standards within the field of industry.Standards such as EN12100 Part 1, Part 2, & ISO 14121-1 provide methods for designing safe ma-chinery and for carrying out a risk assessment.

    CAUTION! The information in this manual provides guidance on the use of the safety functions that OPTBJ option board provides together with VACON® 100 family control board. This information is in compliance with accepted practice and regulations at the time of writing. However, the end product/system designer is responsible for ensuring that the system is safe and in compliance with relevant regulations.

    13006.emf

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 5

  • 5

    vacon • 20 STO and SS1 safety functions

    5.1 Safe Torque Off (STO) principleThe STO safety function of the OPTBJ board allows the drive output to be disabled so that the drive cannot generate torque in the motor shaft. For STO, the OPTBJ board has two separate, galvanically isolated inputs STO1 and STO2.

    NOTE! To allow the drive to go to ready state, a voltage of +24V must be connected between the in-put terminals for both STO input channels. See chapter 5.3.5 for details.

    The STO safety function is achieved by disabling the drive modulation. The drive modulation is dis-abled through two independent paths controlled by STO1 and STO2 so that a single fault in any of the safety related parts will not lead to the loss of the safety function. This is done by disabling the gate driver signal outputs to the driver electronics. The gate drive output signals control the IGBT module. When gate drive output signals are disabled, the drive will not generate torque in the motor shaft. See Figures 6 and 7.

    Figure 6.STO principle with OPTBJ board and VACON® 100 family control board MR4-10

    STO1

    +

    STO2

    -

    RO

    =

    3~

    VACON 100 CONTROL UNIT

    Control boardOPTBJ board, slot E

    POWER UNIT

    ThermistorAtex Safety Function

    Atex Safety Function

    Hardware STO 1

    Hardware STO 2

    11575B_uk

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • STO and SS1 safety functions vacon • 21

    Figure 7.STO principle with OPTBJ board and VACON® 100 family control board MR12

    STO1

    +

    STO2

    -

    RO

    =

    3~

    =

    3~

    VACON 100 CONTROL UNIT

    Control boardOPTBJ board, slot E

    MASTERPOWER UNIT

    SLAVEPOWER UNIT

    ThermistorAtex Safety Function

    Atex Safety Function

    Hardware STO 1

    Hardware STO 2

    Hardware STO 1

    Hardware STO 2

    11654A_uk

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 5

  • 5

    vacon • 22 STO and SS1 safety functions

    5.2 Safe Stop 1 (SS1) PrincipleAfter a safe stop command the motor starts decelerating and SS1 safety function initiates the STO after a user set time delay.

    Figure 8. The principle of Safe Stop 1 (EN 61800-5-2, SS1 type c)

    The Safe Stop 1 (SS1) safety function consists of two safety related subsystems, an external time delayed safety relay and the STO safety function. These two subsystems combined compose the Safe Stop 1 safety function as shown in Figure 9.

    Figure 9. Safe Stop 1 (SS1) safety function

    Time0

    StopMotordeceleration

    Frequency

    factual

    Time delay

    Safe Torque Off (STO)

    11578_uk

    Safe Stop 1 (SS1)

    Time Delayed Safety Relay Vacon 100 Safe Torque Off (STO)

    +Subsystem Safety Relay Subsystem STO

    11579_uk

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • STO and SS1 safety functions vacon • 23

    Figure 10 shows the connection principle of Safe Stop 1 safety function, as specified in figure 8.

    • The time delayed safety relay outputs are connected to the STO inputs.• A separate digital output from the safety relay is connected to a general digital input of the

    VACON® 100 family AC drive. The general digital input must be programmed to execute the drive stop command and initiates the drive stop function without a time delay (must be set to "stop by ramp") and causes motor deceleration. If the SS1 behavior of Figure 8 is required then it must be ensured that the ramp stop is activated when the stop signal is received. It is the responsibility of the system designer to verify this. See Chapter 6.2 for the wiring and parametrization of Safe Stop 1.

    Figure 10. The connection principle of Safe Stop 1 (SS1)

    CAUTION! The system designer/user is responsible for understanding and setting the time delay of the safety relay, as it is process/machine dependent.

    • The time delay must be set to a greater value than the deceleration time of the drive*. The motor deceleration time is process/machine dependent.

    • The stop function of the drive needs to be correctly set for the process/machine. Activating the SS1 safety function must execute the configured stop in the drive. In the VACON® 100 default application software it is rec-ommended to use the "Quick Stop" functionality for this purpose.

    * In case of a single fault the drive may not ramp down but is only put to STO mode after the config-ured time delay.

    CAUTION! The control place must be set according to the application require-ments.

    M

    Switch

    Safety Relay with timer

    Vacon 100control

    Basic I/O

    Digital input

    OPTBJ board

    STO channel 1STO channel 2

    Timedelay

    Power Unit

    Ramp stop

    STO1

    STO2

    11577A_uk

    13006.emf

    13006.emf

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 5

  • 5

    vacon • 24 STO and SS1 safety functions

    5.3 Technical details

    5.3.1 Response times

    5.3.2 Input voltage levelsSTO inputs fulfill the requirements for standard operating ranges for Type 2 digital inputs (current sinking), defined by IEC 61131-2 (2007). Reversed polarity applied on STO input terminals does not cause disabling of STO function.

    The STO inputs of OPTBJ are OSSD tolerant. The operation of OPTBJ is not interfered by test pulses that are generated to the STO lines by the connected safety actuator as long as the test pulses fulfill certain requirements. See chapters 5.3.3 and 5.3.4 for details.

    5.3.3 External dark test pulse filtering capabilityTo recognize the short circuits from STO lines to power supplies or ground, some safety PLCs test their outputs by pulsing the output from high to low level for short periods of time when STO is dis-abled. The pulses are known as 'dark test pulses'. To prevent these test pulses from causing false fault indications, these dark test pulses are filtered out by STO inputs on OPTBJ. If the input voltage-specific values for dark test pulse durations are exceeded, the drive may indicate STO diagnostics fault or STO may be activated. The used dark test pulse duration should always be shorter than the specified minimum pulse withstanding duration. Limits for the test pulse duration, frequency and period are given in Table 5. The filtering time is hardware-based and cannot be adjusted. External dark test pulse filtering is included on OPTBJ boards from revision D onwards. See chapter 4.1 for identifying the board revision.

    Table 2. STO response times

    Safety function Activation time

    De-activation

    time

    Safe Torque Off (STO) < 20 ms 500 ms

    Table 3. Safe input data

    Technical item or function Minimum Typical Maximum

    Input Voltage (logic 1) 11 V 24 V 30 V

    Input Voltage (logic 0) -3 V 0 V 5 V

    Input Current (logic 1) 4.5 mA 7.5 mA 8 mA

    Input Current (logic 0) 2.0 mA

    Input Resistance 2.5 kΩGalvanic Isolation Yes

    Short circuit protected Yes

    Active -> Inactive Debounce time 4 ms 9 ms

    Allowed discrepancy time of physical inputs 500 ms

    Table 4. External dark test pulse filtering capability

    Dark test pulse filtering capability Minimum Typical Maximum

    STO input voltage: 11 V 0 ms 0 ms 1 ms

    STO input voltage: 24 V 4 ms 4 ms 7 ms

    STO input voltage: 30 V 5 ms 6 ms 9 ms

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • STO and SS1 safety functions vacon • 25

    5.3.4 External light test pulse filtering capabilityTo verify the switching capabilities of STO lines' switches, some safety actuators test their outputs by pulsing the output from low to high level for short periods of time when STO is enabled. The puls-es are known as 'light test pulses'. Allowed pulse characteristics are introduced in Table 5 in Chap-ter 5.3.3.

    To prevent the test pulses from causing false STO disactivation commands or false fault indications, the used connection must not create current path through STO inputs. Only connection example 1 is allowed. See the connection examples in chapter 6.1. Only one switch is allowed to be tested at a time.

    5.3.5 ConnectionsIn addition to the STO inputs, the board contains also a thermistor input. If the thermistor input is not used, it must be disabled. The thermistor input is disabled by making a short circuit to the ter-minals and setting the jumper X23 in "OFF" state. The thermistor input operation and instructions are presented in chapter 8.1.

    * If 230VAC is used as control voltage from the output relays, the control circuitry must be powered with a separate isolation transformer to limit short circuit current and overvoltage spikes. This is to prevent the welding on the relay contacts.

    Table 5. Pulse characteristics

    Pulse characteristics Dark test pulse Light test pulse

    Test pulse length < 4 ms (24 V) < 4 ms (24 V)

    Period > 20 ms > 20 ms

    Frequency < 50 Hz < 50 Hz

    CAUTION! When using other connection than "Connection example 1" with light test pulse function, forbidden pulse structure or by testing both switches (SW P & SW M) simultaneously, the drive may enter ready state even if STO should be ac-tivated. This may cause unintentional rotation of the motor shaft. See the connec-tion examples in chapter 6.1.

    Table 6. OPTBJ I/O terminals

    Terminal Technical information

    1 STO1+ Isolated STO input 1, +24V

    2 STO1- Virtual GND 1

    3 STO2+ Isolated STO input 2, +24V

    4 STO2- Virtual GND 2

    25 RO1 Relay output 1 (NO) *Switching capacity:

    • 24VDC/8A• 250VAC/8A• 125VDC/0.4A

    Min. switching load: 5V/10mA

    26 RO2

    28 TI1+Thermistor input; Rtrip > 4.0 kΩ (PTC)29 TI1-

    13006.emf

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 5

  • 5

    vacon • 26 STO and SS1 safety functions

    5.3.6 Relay outputWhen the STO function is active, the relay output is closed. When the STO function is inactive the relay output is open. When STO function has detected a non-resettable diagnostics fault the relay output toggles at a frequency of one hertz.

    NOTE! The ATEX input has no effect on the relay output.

    Table 7. STO function truth table

    VSTO1+ - VSTO1- VSTO2+ - VSTO2- STO state

    0VDC 0VDC STO active

    24VDC 0VDCSTO diagnostic fault and STO activation. Fault is activated after inputs have been in different states for >500 ms.

    0VDC 24VDCSTO diagnostic fault and STO activation. Fault is activated after inputs have been in different states for >500 ms.

    24VDC 24VDC STO inactive

    CAUTION! The relay output is intended only for diagnostics of the STO function.

    CAUTION! The relay output is a non-safety-related functionality.

    13006.emf

    13006.emf

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • STO and SS1 safety functions vacon • 27

    5.3.7 Safety-related data according to the standard

    * The values in the table above are worst case values and they are fulfilled with all board revisions.

    If more detailed information is needed, contact Danfoss local contacts (http://drives.danfoss.com/danfoss-drives/local-contacts/) for support and details.

    Table 8. Safe Torque Off (STO) safety-related data *

    MR4 - MR10 MR12

    EN 61800-5-2:2007

    SIL 3PFH = 4.12x10-10 /hour

    HFT = 1

    SIL 3PFH = 4.30x10-10 /hour

    HFT = 1

    EN 62061:2005

    SIL CL 3PFH = 4.12x10-10 /hour

    HFT = 1

    SIL CL 3PFH = 4.30x10-10 /hour

    HFT = 1

    EN/ISO 13849-1:2006

    PL eMTTFd =1700 years

    DCavg = medium

    Category 3

    PL eMTTFd =700 years

    DCavg = medium

    Category 3

    IEC 61508:2010, High Demand Mode

    SIL 3PFH = 4.12x10-10 /hour

    HFT = 1

    SIL 3PFH = 4.30x10-10 /hour

    HFT = 1

    IEC 61508:2010, Low Demand Mode

    SIL 3PFDAVG (TM)= 3.59x10

    -5 TM = 20 years

    HFT = 1

    SIL 3PFDAVG (TM)= 3.76x10

    -5 TM = 20 years

    HFT = 1

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 5

  • 5

    vacon • 28 STO and SS1 safety functions

    Safe Stop (SS1) safety-related dataNOTE! The following chapter is only an informative example of combining products.The SS1 safety function consists of two subsystems with different safety-related data.The subsys-tem consisting of the time delayed safety relay is manufactured, for example, by PHOENIX CON-TACT. The following types are available from this manufacturer:

    • PSR-SCP-24DC/ESD/5X1/1X2/300 or • PSR-SPP-24DC/ESD/5X1/1X2/300

    See manufacturer user manual for more information regarding the time delayed safety relay.

    PSR-SC/PP-24DC/ESD/5X1/1X2/300 safety-related data from user manual and certificate: VACON® 100 STO safety-related data (MR4-MR10):

    SubsystemSafetyRelay SubsystemVACON100STO

    Safe Stop 1 (SS1) safety-related data:

    When the two subsystems are combined, the maximum safety integrity level or performance level reached is the level of the lower subsystem.

    • SIL 2 and PL dThe PFH value for a safety function of combined subsystems is the sum of all subsystems PFH values.PFHSS1 = PFHSafety Relay + PFHVACON100 STO = 1.89•10

    -9 /hour + 4.12•10-10 /hour = 2.31•10-9 /hour

    • The result is within the requirements for SIL 2 and PL d.

    IEC 61 508 SIL 2

    +

    EN 61800-5-2 SIL 3

    EN 62061 SIL CL 2 EN 62061 SIL CL 3

    DIN EN/ISO 13849-1 PL dCategory 3 IEC 61508 SIL 3

    PFH 1.89•10-9 /hourDIN EN/ISO 13849-1 PL eCategory 3PFH 4.12•10-10 /hour

    EN 61800-5-2 SIL 2

    EN 62061 SIL CL 2

    IEC 61508 SIL 2

    DIN EN/ISO 13849-1 PL dCategory 3PFH 2.31•10-9 /hour

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • Commissioning vacon • 29

    6. COMMISSIONINGNOTE! The use of STO, SS1 or other safety functions does not itself ensure safety. Always make sure that the safety of the entire system is confirmed.

    NOTE! The user is responsible for excluding faults in the external wiring.

    6.1 General wiring instructions• The wiring should be done according to the general wiring instructions for the specific prod-

    uct where OPTBJ is installed. See wiring examples in the figures 11, 12 and 13.• If shielded cable is used, the shield must be connected to the drive's lid (PE) using a ground-

    ing clamp. • EN 60204-1 part 13.5: The voltage drop from supply point to load must not exceed 5%.• In practice, due to electromagnetic disturbances, the cable length should be limited to to

    max. 200 m when using shielded cable and to max. 50 m when using unshielded cable. In a noisy environment, the length of the cable could still be less in order to avoid unwanted trip-ping.

    • Using unshielded cables is not allowed with some STO input configurations. Also some STO input connection options are not allowed to be used with certain safety actuator types. See Table 9 for details.

    • The +24V power supply used for safety actuators may come from control board (e.g. drive's control connector pins 6 & 7) or it may also be external, earth fault and short circuit pro-tected power supply.

    Figure 11. STO connection example 1

    SAFETY ACTUATOR OPTBJCHANNEL 1

    SW P+24V

    OVSW M

    STO1+

    STO1-

    OPTBJCHANNEL 2

    STO2+

    STO2-11851_uk

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 6

  • 6

    vacon • 30 Commissioning

    Figure 12. STO connection example 2

    Figure 13. STO connection example 3

    Cable recommendation:

    See Table 9 for connections where shielded cable is required. In cases where the shield is marked as being required, use the shield to separate the STO input channels from each other as shown in Figure 14.

    Type

    For example one of the following:

    • 2x2x0.75mm2 (18 AWG) low voltage cable with two individually shielded twisted pairs

    • 2x2x0.75mm2 (18 AWG) low voltage, unshielded, twisted pair cable

    • two separate 2x0.75mm2 (18 AWG) shielded or unshielded twisted pair cables.

    SAFETY ACTUATOR OPTBJCHANNEL 1

    SW P+24V

    +24VOV

    OVSW M

    STO1+

    STO1-

    OPTBJCHANNEL 2

    STO2+

    STO2-

    11852_uk

    SAFETY ACTUATOR OPTBJCHANNEL 1

    SW P+24V

    +24VSW P

    STO1+

    STO1-

    OPTBJCHANNEL 2

    STO2+

    STO2-

    OV11853_uk

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • Commissioning vacon • 31

    Figure 14. Structure of cable with two individually shielded twisted pairs

    X = Not recommended due to causes of electromagnetic disturbances, safety actuator configuration or behavior in failure situations.

    Table 9. Recommended maximum cable lengths

    Safety actuator type Diagnostics on safety actuator

    Cable type

    Used STO input connection

    STO connection example 1

    STO connection example 2

    STO connection example 3

    Undiagnosed safety actuator(i.e. emergency stop button or

    relay contact)No diagnostics

    Shielded X 200 m 200 m

    Unshielded X 30 m X

    Safety actuator with diagnosed outputs (i.e. safety PLC)

    Outputs diagnosed using e.g. dark test pulse,

    light test pulse not used

    Shielded 200 m 200 m 200 m

    Unshielded 30 m 30 m X

    Outputs diagnosed using light test pulse

    Shielded 200 m X X

    Unshielded 30 m X X

    Individual pair Overall shield (Optional)

    Pair shield

    Cable jacket

    11860_uk

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 6

  • 6

    vacon • 32 Commissioning

    6.2 Wiring examplesThe examples in this chapter show the basic principles for wiring OPTBJ board. Local standards and regulations should be always followed in the final design.

    Example 1: OPTBJ board without reset for Safe Torque Off (STO)

    The figure above shows a connection example of OPTBJ board for Safe Torque Off safety function without reset. The switch S1 is connected with 4 wires to the OPTBJ board as shown above.

    When the switch S1 is activated (contacts open), the drive goes to STO state and motor (if running) will stop by coasting. If STO fault action is parameterized as "Alarm", the drive indicates: "30 Safe torque off". Regardless of the parameterization, activation of STO function causes a coasting stop for motor.

    To allow the returning of the drive to ready state without a reset after S1 is deactivated (contacts closed), STO Fault action must be parameterized as "Alarm". See application manual for related pa-rameters.

    To start the motor operation again, the following sequence is performed.• Release the switch S1 (contacts closed). The hardware is now enabled and the drive returns to ready

    state.• Giving a valid start command starts running the motor.

    NOTE! According to EN 60204-1 (Safety of machinery - Electrical equipment of machines), the re-setting of the emergency stop request (e.g. releasing of emergency stop button) must not restart the drive.

    NOTE! The VACON® 100 default application software uses edge-sensitive start as a default start command. With the edge-sensitive start command, disactivating the STO does not cause immediate start.

    F1

    1

    2

    3

    4

    5

    6

    L1 L2

    MAIN CIRCUIT

    L3

    PE

    PE

    L1 L2 L3

    U V WPE

    2

    7

    PEPE

    PE

    W1

    M1

    M3~

    U1

    1

    V1 W1

    2

    PE

    R1

    SPEED REFERENCE

    S

    CCW

    CW

    W12 1sh 1r 2sh 2p 2s

    Basic I/O

    1

    +10Vref

    1

    2

    AI1+

    2

    3

    AI1

    3

    OPTBJSLOT E1

    STO1+

    2

    STO1

    S111

    12

    W10 1r 2r1b 2b

    S6

    START

    13

    14

    4

    AI2+

    4

    5

    AI2

    5

    6

    24Vout

    6

    7

    GND

    7

    3

    STO2+

    4

    STO2

    21

    22

    S7

    STOP

    11

    12

    8

    DI1

    8

    9

    DI2

    9

    10

    DI3

    10

    11

    CM

    11

    25

    RO1 C

    26

    RO1 NO

    28

    TI1+

    12

    24Vout

    12

    13

    GND

    13

    14

    DI4

    14

    15

    DI5

    15

    X23OFF

    29

    TI1

    16

    DI6

    16

    17

    CM

    17

    18

    AO1+

    18

    19

    AO/GND

    19

    30

    +24Vin

    20

    PE

    Safe torque off

    +24V

    0V

    A

    RS485

    B

    RS485

    21 22

    AO1RS485

    UUU

    ON OFFIII

    AI2AI1

    Short circuit and earthfault protected supply

    ON OFF DGND

    X10Installed

    3044B_UK.eps

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • Commissioning vacon • 33

    Example 2: OPTBJ board with reset for Safe Torque Off or EN 60204-1 stop category 0.

    The figure above presents a connection example of OPTBJ board for STO safety function with reset. The switch S1 is connected with 4 wires to the OPTBJ board as shown above. The digital input 3 (DIN3), for example, is wired for the fault reset function. The reset function (not part of any safety function) can be programmed to any of the available digital inputs.

    To prevent starting the motor without reset, STO fault action has to be parameterized as "Fault". See application manual for related parameters.

    When the switch S1 is activated (contacts open), the drive goes to STO state and motor (if running) stops by coasting. The drive indicates: "30 SafeTorqueOff".

    To start the motor operation again, the following sequence is performed.• Release the switch S1 (contacts closed). The hardware is now enabled but the drive continues to dis-

    play the fault "30 SafeTorqueOff".• Acknowledge the releasing of switch by edge sensitive reset function. The drive returns to the ready

    state.• Giving a valid start command starts running the motor.

    NOTE! According to EN 60204-1 (Safety of machinery - Electrical equipment of machines), the re-setting of the emergency stop request (e.g. releasing of emergency stop button) must not restart the drive.

    NOTE! The VACON® 100 default application software uses edge-sensitive start as a default start command. With the edge-sensitive start command, disactivating the STO does not cause immediate start.

    NOTE! For EN 60204-1 emergency stop according to stop category 0, use the emergency stop but-ton.

    F1

    1

    2

    3

    4

    5

    6

    L1 L2

    MAIN CIRCUIT

    L3

    PE

    PE

    L1 L2 L3

    U V WPE

    2

    7

    PEPE

    PE

    W1

    M1

    M3~

    U1

    1

    V1 W1

    2

    PE

    R1

    SPEED REFERENCE

    S

    CCW

    CW

    W12 1sh 1r 2sh 2p 2s

    Basic I/O

    1

    +10Vref

    1

    2

    AI1+

    2

    3

    AI1

    3

    OPTBJSLOT E1

    STO1+

    2

    STO1

    S111

    12

    W10 1r 2r1b 2b

    S6

    START

    13

    14

    4

    AI2+

    4

    5

    AI2

    5

    6

    24Vout

    6

    7

    GND

    7

    3

    STO2+

    4

    STO2

    21

    22

    S7

    STOP

    11

    12

    S8

    RESET

    13

    14

    8

    DI1

    8

    9

    DI2

    9

    10

    DI3

    10

    11

    CM

    11

    25

    RO1 C

    26

    RO1 NO

    28

    TI1+

    12

    24Vout

    12

    13

    GND

    13

    14

    DI4

    14

    15

    DI5

    15

    X23OFF

    29

    TI1

    16

    DI6

    16

    17

    CM

    17

    18

    AO1+

    18

    19

    AO/GND

    19

    30

    +24Vin

    20

    PE

    +24V

    0V

    Safe torque off

    A

    RS485

    B

    RS485

    21 22

    Short circuit and earthfault protected supply

    X10Installed

    3045B_UK

    AO1RS485

    UUU

    ON OFFIII

    AI2AI1

    ON OFF DGND

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 6

  • 6

    vacon • 34 Commissioning

    Example 3: OPTBJ board with SS1 and safety reset or EN 60204-1 stop category 1.

    The figure above presents a connection example of OPTBJ board for SS1 safety function with ex-ternal safety relay module and with safety reset.

    The external safety relay module is connected to the switch S1. The used power supply to switch S1 is 230 VAC as an example. The safety relay module is connected to OPTBJ board with 4 wires as shown in Figure above.

    To configure the drive to perform the fast deceleration with a ramp, it is recommended to use Quick Stop -function that is activated by digital input, for example DI6 as in Example 3 above. See the ap-plication manual for correct parametrization of Quick Stop -function.

    When the switch S1 is activated (contacts open), the drive starts ramping down the output frequency until the delay of the safety relay has passed. After safety relay time delay, the drive goes to STO state. If the motor is still running, it stops by coasting. If STO fault action is parameterized as "Alarm", the drive indicates: "30 Safe torque off". Regardless of the parameterization, activation of STO function causes a coasting stop for motor.

    To allow the returning of the drive to ready state after S1 is deactivated (contacts closed) and safety relay is resetted, STO Fault action needs to be parameterized as "Alarm". If STO Fault action is pa-rameterized as "Fault", also the drive needs to be reset to allow ready state. See application manual for related parameters.

    To start the motor operation again, following sequence is performed.• Release the switch S1 (contacts closed). The hardware is now enabled and the drive returns to ready

    state. An alarm indication for STO actiavation is displayed if STO Fault action is parameterized as "Alarm".

    • Acknowledge the releasing of switch by resetting the safety relay. The drive returns to the ready state.• Giving a valid start command starts running the motor

    F1

    1

    2

    3

    4

    5

    6

    L1 L2

    MAIN CIRCUIT

    L3

    PE

    PE

    L1 L2 L3

    U V WPE

    2

    7

    PEPE

    PE

    W1

    M1

    M3~

    U1

    1

    V1 W1

    2

    PE

    R1

    SPEED REFERENCE

    S

    CCW

    CW

    W12 1sh 1r 2sh 2p 2s

    Basic I/O

    1

    +10Vref

    1

    2

    AI1+

    2

    3

    AI1

    3

    OPTBJSLOT E1

    STO1+

    2

    STO1

    S6

    START

    13

    14

    4

    AI2+

    4

    5

    AI2

    5

    6

    24Vout

    6

    7

    GND

    7

    3

    STO2+

    4

    STO2

    S7

    STOP

    11

    12

    8

    DI1

    8

    9

    DI2

    9

    10

    DI3

    10

    11

    CM

    11

    25

    RO1 C

    26

    RO1 NO

    28

    TI1+

    12

    24Vout

    12

    13

    GND

    13

    14

    DI4

    14

    15

    DI5

    15

    X23

    29

    TI1

    16

    DI6

    16

    17

    CM

    17

    18

    AO1+

    18

    19

    AO/GND

    19

    30

    +24Vin

    20

    PE

    OFF

    A

    RS485

    B

    RS485

    21 22

    X10Installed

    PE

    Short circuit and earthfault protected supply

    0V

    PE

    PE

    A10

    W3 1r 2r

    57

    58

    +24V

    67

    68

    PE

    13

    14

    23

    24

    33

    34

    41

    42

    24VDC

    A1

    A2

    0VDC

    +S10

    S111

    12

    S11 S12 S21

    21

    22

    PHOENIX CONTACT

    S22 S33

    PSRSCP24DC/ESD/5X1/1X2/300

    RESET

    S34 S35

    Bridge between S33/S35 for automatic reset.(Not allowed with emergency stop)

    RS1

    RS2

    RS1

    RS2

    RAMP STOP

    3046A_UK

    AO1RS485

    UUU

    ON OFFIII

    AI2AI1

    ON OFF DGND

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • Commissioning vacon • 35

    More information on the safety relay module may be found in the safety relay documentation.

    NOTE! According to EN 60204-1 (Safety of machinery - Electrical equipment of machines), the re-setting of the emergency stop request (e.g. releasing of emergency stop button) must not restart the drive.

    NOTE! The VACON® 100 default application software uses edge-sensitive start as a default start command. With the edge-sensitive start command, disactivating the STO does not cause immediate start.

    NOTE! For EN 60204-1 emergency stop according to stop category1, use emergency stop button.

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 6

  • 6

    vacon • 36 Commissioning

    6.3 Parameterization of STO functionalitySTO functionality is based on hardware, and cannot be bypassed by parameterization. Activating ei-ther or both of STO input channels by applying logical '0' causes a coasting stop for the motor and prevents the restart. The additional actions such as generating fault or alarm from STO activation or driving the STO state to an output can be parameterized. See application manual for the related parameters.

    Table 10. Parameter description for STO fault parameter

    Index Parameter Min Max Default ID Description

    P3.9.1.14 (INDUS-TRIAL / FLOW)

    STO Fault No ActionFault,Coast

    Fault, Coast

    775

    • No Action: Activating STO causes motor to stop by coasting and 'Not ready' state. Drive returns to 'Ready' state as soon as STO is deactivated. No indication of STO activation is displayed.

    • Alarm: Activating STO causes motor to stop by coasting and 'Not ready' state. Alarm is displayed, but drive returns to 'Ready' state as soon as STO is deactivated.

    • Fault, Coast: Activating STO causes motor to stop by coasting and 'Fault' state. STO needs to be deactivated and fault reset before drive returns to 'Ready' state.

    P3.9.29 (HVAC)

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • Commissioning vacon • 37

    6.4 Checklist for commissioning the OPTBJ board

    Nr Step Yes No

    1Has a risk assessment of the system been carried out to ensure that us-ing the OPTBJ board Safe Torque Off (STO) or Safe Stop 1 (SS1) safety function is safe and according to the local regulations ?

    2 Does the assessment include an examination of whether using external devices such as a mechanical brake is required ?3 Has the switch S1 been chosen according to the required safety perfor-mance target (SIL or PL) set during the risk evaluation?4 Is the switch S1 required to be lockable or otherwise secured in the OFF position?5 Is it ensured that color coding and marking of the switch S1 is in accor-dance with the intended use?6 Is the external power of the switch S1 protected (according to EN 60204-1) against supply earth fault and short circuit?

    7The shaft of a permanent magnet motor might in an IGBT fault situation rotate up to 180 degrees around the pole of the motor. Has it been en-sured that the system is designed in such a way that the this can be ac-cepted?

    8 Has the STO jumper configuration been done according to the instruc-tions in this manual?9 Has the STO input wiring been done according to examples?

    10Have process requirements (including deceleration time) been consid-ered for correct execution of Safe Stop 1 (SS1) safety function and are the corresponding settings done?

    11 Is there a risk of conductive contamination (e.g. conductive dust) in the environment?12 If pollution degree 2 cannot be guaranteed, IP54 protection class must be used.13 Have the User's Manual instructions for the specific product been fol-lowed?14 Does the system need a safety certified prevention of unexpected start-up? The safety function has to be provided by an external safety relay.

    15Has the system been designed in such a way that activating (enabling) the drive through STO inputs will not lead to an unexpected start of the drive?

    16 Have only approved units and parts been used?

    17Is the VACON® 100 family control board 70CVB01582? (See the sticker on the VACON® 100 family control board, or “Drive Info” in VACON® Live)

    18 Is the VACON® 100 system software version FW0072V002, or newer?

    (Check the system software version on the keypad or in VACON® Live)

    19 Has a routine been set up to ensure that the functionality of the safety functions is being checked at regular intervals?20 Has this manual been read, understood and followed carefully?

    21 Have the STO and SS1 safety functions been tested properly according to Chapter 6.5?

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 6

  • 6

    vacon • 38 Commissioning

    6.5 Testing the Safe Torque Off (STO) or Safe Stop 1 (SS1) safety functionsNOTE! Before testing the STO or SS1 safety functions, make sure that the checklist (Chapter 6.2) is inspected and completed.

    NOTE! After connecting the board ALWAYS make sure that the STO or SS1 safety functions are working properly by testing them before operating the system.

    NOTE! Concerning the SS1 safety function, make sure by testing that the drive's stop by ramp func-tion is working in accordance with the process requirements.

    NOTE! If the STO safety function is used in a low-demand operating mode, it must be tested period-ically at least once a year.

    When the STO safety function is activated, a code: Fault 30 "SafeTorqueOff " appears on the control keypad display. This indicates that the STO safety function is active. After STO has been deactivated, the fault remains active until the fault is acknowledged.

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • Maintenance vacon • 39

    7. MAINTENANCE

    7.1 Faults related to the Safe Torque Off (STO) or Safe Stop 1 (SS1) safety functionsThe table below shows the normal fault, generated when STO safety function is active:

    The table below shows faults that may be generated from the software part that monitors the hard-ware related to the STO safety function. If some of the faults listed below occur, DO NOT reset the fault:

    CAUTION! If any service or repair is to be conducted on the drive installed with OPTBJ board please follow the check list given in Chapter 6.2.

    CAUTION! During maintenance breaks, or in case of service/repair, the OPTBJ board might have to be removed from its slot. After reconnecting the board, ALWAYS make sure that the STO or SS1 safety functions are active and fully func-tional by testing them. See Chapter 6.5.

    Fault code Fault ID Explanation Correcting measures

    30 SafeTorqueOff 530STO activated through the

    OPTBJ option boardSTO function activated. Drive is in safe state

    Fault code Fault ID Explanation Correcting measures

    30 Safety configuration 500STO jumper is installed on the

    control board.

    • Remove the STO jumper from the control board. See ch. 3.1 and 3.1.1

    30 Safety configuration 501More than one OPTBJ option board detected in the drive.

    • Only one OPTBJ board is sup-ported by the drive. Remove other OPTBJ boards from the drive, except from slot E.

    30 Safety configuration 502OPTBJ option board installed to

    a wrong slot.

    • OPTBJ option board can only be installed to slot E. Install the board to slot E.

    30 Safety configuration 503STO jumper missing from the

    control board.

    • Install the STO jumper to the control board, when the OPTBJ board has been removed from the drive. See ch. 3.1 and 3.1.1

    30 Safety configuration 504Problem detected in STO

    jumper installation on the con-trol board.

    • Check the installation of the STO jumper on the control board. See ch. 3.1 and 3.1.1.

    30 Safety configuration 505Problem detected in STO jumper installation on the

    OPTBJ board.

    • Check the installation of STO jumper switch on the OPTBJ board. See ch. 3.1 and 3.1.1

    30 Safety configuration 506Communication has been failed between the control board and

    OPTBJ option board.

    • Check the installation of the OPTBJ board.

    • Restart the drive.• Change the OPTBJ board if nec-

    essary.• Should the fault re-occur, con-

    tact the distributor near to you.

    13006.emf

    13006.emf

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 7

  • 7

    vacon • 40 Maintenance

    30 Safety configuration 507The hardware does not support

    the OPTBJ board.

    • Restart the drive.• Should the fault re-occur, con-

    tact the distributor near to you.

    30 Safety diagnostics 520

    There is a diagnostic failure in the STO safety function. This

    fault occurs when the STO inputs are in a different state for

    more than 500 ms.

    • Restart the drive.• If the restart does not help,

    check the wiring: Both STO input channels of OPTBJ need to be on the same state, i.e. safety device controlling the inputs needs to feed or cut power from both STO1 and STO2 channels simultaneously.

    • If the inputs are on the same state and the fault re-occurs, replace the OPTBJ board.

    • Should the fault re-occur, con-tact the distributor near to you. Deliver the fault report to the distributor, see fault details for more information.

    30 Safety diagnostics 521Atex-thermistor diagnostic

    fault.

    • Restart the drive.• If the restart does not help,

    change the OPTBJ board.• Should the fault re-occur, con-

    tact the distributor near to you

    30 Safety diagnostics 522 Atex-thermistor short-circuit.

    • Check the connection of the Atex-thermistor

    • Check the thermistor• Restart the drive.• If the restart does not help,

    change the OPTBJ board.• Should the fault re-occur, con-

    tact the distributor near to you

    30 Safety diagnostics 523Problem occured in internal

    safety circuit

    • Reset the drive and restart. If the fault reoccurs contact your nearest distributor.

    30 Safety diagnostics 524Overvoltage detected in safety

    option board

    • Reset the drive and restart. If the fault reoccurs contact your nearest distributor.

    30 Safety diagnostics 525Undervoltage detected in safety

    option board

    • Reset the drive and restart. If the fault reoccurs contact your nearest distributor.

    30 Safety diagnostics 526Internal failure detected in safety option board CPU or

    memory handling

    • Reset the drive and restart. If the fault reoccurs contact your nearest distributor.

    30 Safety diagnostics 527Internal failure detected in

    safety function

    • Reset the drive and restart. If the fault reoccurs contact your nearest distributor.

    Fault code Fault ID Explanation Correcting measures

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • Thermistor function (ATEX) vacon • 41

    8. THERMISTOR FUNCTION (ATEX)The thermistor overtemperature supervision is designed in accordance with ATEX directive 94/9/EC. It is approved by VTT Finland for group II (certificate nr. VTT 06 ATEX 048X), category (2) in the 'G' area (area in which potentially explosive gas, vapor, mist or air mixtures are present) and 'D' area (area with combustible dust). The "X" in the certificate number refers to special conditions for safe use. See the conditions in the last note in this page.

    It can be used as an overtemperature tripping device for motors in explosive area (EX motors).

    NOTE! The OPTBJ board also contains the Safe Torque Off (STO) safety function. When STO is not intended to be used, inputs STO1+(OPTBJ:1), STO2+(OPTBJ:3) are to be connected to +24V (for ex-ample, pin 6 in VACON® 100 family control board). STO1-(OPTBJ:2). STO2- (OPTBJ:4) are to be con-nected to GND (for example, pin 7 or 13 on VACON® 100 family control board).

    NOTE! Safety devices like the OPTBJ board must be correctly incorporated into the entire system. The functionality of the OPTBJ board is not necessarily suitable for all systems. The entire system must be designed in compliance with all relevant standards within the field of industry.

    NOTE! The special conditions required for safe use (X in the certificate number): This function can be used with Exe-, Exd-, and ExnA- type of motors. In case of Exe-, and ExnA- motors, the end user has to confirm that the installation of the measurement circuit is done according to area classification. For example, in the Exe- and ExnA- motors, the PTC sensors must be certified together with the motor according to the require-ments of the type of protection. The allowed ambient temperature range for the drive is -10ºC…+50ºC.

    0537 II (2) GD

    CAUTION! The information in this manual provides guidance on the use of therm-istor function for protecting overheating of motors in explosive atmosphere. How-ever, the end product/system designer is responsible for ensuring that the system is safe and in compliance with relevant regulations.

    CAUTION! During maintenance breaks, or in case of service/repair the OPTBJ board might have to be removed from its slot. After reconnecting the board ALWAYS make sure that the thermistor function is working correctly by testing it.

    CAUTION! The thermistor function on OPTBJ board with VACON® 100 family con-trol is used to protect the overheating of motors in explosive atmosphere. The drive itself including OPTBJ board can not be installed in explosive atmosphere.

    13006.emf

    13006.emf

    13006.emf

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 8

  • 8

    vacon • 42 Thermistor function (ATEX)

    Date Issued by Date Approved by15-04-2016 Signature

    Name: Antti Vuola Title: Head of Standard drives

    15-04-2016 Signature Name: Timo Kasi Title: VP, Design Center Finland and Italy

    Danfoss only vouches for the correctness of the English version of this declaration. In the event of the declaration being translated into any other language, the translator concerned shall be liable for the correctness of the translation. ID No: DPD01855 Revision No: A Page 1 of 1

    Danfoss A/SDK-6430 Nordborg Denmark CVR nr.: 20 16 57 15 Telephone: +45 7488 2222 Fax: +45 7449 0949

    EU DECLARATION OF CONFORMITY

    Danfoss A/S Vacon Ltd

    declares under our sole responsibility that the Product name Vacon OPTBJ option board to be used with Vacon 100 family products Product identification 70CVB01380

    Marking of the equipment has been designed in conformity with the requirements of the Council directive for explosive atmospheres, 94/9/EC of March 1994 (until April 19th, 2016), 2014/34/EU (from April 20th, 2016) according to following standards.

    - EN ISO 13849-1 (2006) Safety of machinery – safety-related parts of the control systems. Part 1: General principles for design

    - EN ISO 13849-2 (2003) Safety of machinery – safety-related parts of the control systems. Part 2: Validation

    - EN 60079-14 (2007) Electrical apparatus for explosive gas atmospheres. Part 14: Electrical installations in hazardous area (other than mines).

    - EN 61508-3(2010) Functional safety of electrical/electronic/programmable electronic safety- related systems – Part3: Software requirements

    - EN ISO/IEC 80079-34 (2011) Explosive atmospheres – Part 34: Application of quality systems for equipment manufacture.

    - EN 50495 (2010) Safety devices for ignition prevention.

    VTT Industrial Systems, Electrical Ex apparatus, the Notified Body having identification number 0537, has assessed the conformity of thermal motor protection system and has issued the certificate VTT 06 ATEX 048X. It is ensured through internal measures and quality control that the product conforms at all times to the requirements of the current Directive and the relevant standards.

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • Thermistor function (ATEX) vacon • 43

    Figure 15. Thermistor function principle in VACON® 100 family AC drive with the OPTBJ board, MR4-10

    STO1

    +

    STO2

    -

    RO

    =

    3~

    VACON 100 CONTROL UNIT

    Control boardOPTBJ board, slot E

    POWER UNIT

    ThermistorAtex Safety Function

    Atex Safety Function

    Hardware STO 1

    Hardware STO 2

    11575B uk

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 8

  • 8

    vacon • 44 Thermistor function (ATEX)

    Figure 16.STO principle with OPTBJ board and VACON® 100 family control board MR12

    STO1

    +

    STO2

    -

    RO

    =

    3~

    =

    3~

    VACON 100 CONTROL UNIT

    Control boardOPTBJ board, slot E

    MASTERPOWER UNIT

    SLAVEPOWER UNIT

    ThermistorAtex Safety Function

    Atex Safety Function

    Hardware STO 1

    Hardware STO 2

    Hardware STO 1

    Hardware STO 2

    11654A_uk

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • Thermistor function (ATEX) vacon • 45

    8.1 Technical data

    8.1.1 Functional descriptionThe thermistor supervision circuit of the OPTBJ board is designed to provide a reliable way of dis-abling the drive modulation in case there is an overtemperature at the motor thermistor(s).

    By disabling the drive modulation, the feeding of the energy to the motor is prevented and a further heating up of the motor due to this is avoided.

    The thermistor supervision circuit meets the requirements in the ATEX directive by directly activat-ing the "STO" safety function of the VACON® 100 family (See Figure 15) and thus provides a reliable, software and parameter independent way of preventing the energy supply to the motor.

    8.1.2 Hardware and connectionsSee Chapter 5.3.5.

    The thermistor (PTC) is connected between the terminals 28(TI1+) and 29(TI1-) of the OPTBJ board. The optocoupler isolates the thermistor inputs from the control board potential* If 230VAC is used as control voltage from the output relays, the control circuitry must be powered with a separate isolation transformer to limit short circuit current and overvoltage spikes. This is to prevent the welding on the relay contacts.

    Figure 17. Typical characteristics of a motor-protection sensor as specified in DIN 44081/DIN 440

    8.1.3 Atex functionWhen drive is connected to the main power and if the motor temperature is below overtemperature limits (see Figure 17), the drive goes to ready state. The motor may start after a valid start com-mand.

    If the motor temperature is above the overtemperature limits (see Figure 17), fault 29 (Atex therm-istor) is activated.

    When the resistance of the thermistor(s) mounted in the motor goes above 4 kOhm due to motor overheating, the drive modulation is disabled within 20ms.

    According to Figure 17, when the temperature falls below 2 kOhm, the thermistor function allows fault reset and entering to ready state.

    OPTBJ:OPTBJ:

    OPTBJ

    11580_uk

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/ 8

  • 8

    vacon • 46 Thermistor function (ATEX)

    8.1.4 Short circuit monitoringThe thermistor inputs TI1+ and TI1- are monitored for short circuit. If a short circuit is detected, the drive modulation is disabled within 20ms, Fault 30, Safety diagnostic (subcode 522) is generated. When the short circuit has been removed, the drive can be reset only after restarting the drive.

    The short circuit monitoring can be enabled or disabled using the jumper X23 in ON or OFF position respectively. The jumper is set in ON position by factory default.

    8.2 CommissioningNOTE! Installation, testing and service work on the OPTBJ board can be performed only by qualified persons.

    NOTE! It is not allowed to perform any repair work on the OPTBJ board. Return faulty boards to the manufacturer for analysis.

    NOTE! It is recommended to test the ATEX functionality using thermistor input on OPTBJ board pe-riodically (typically once a year). For testing, activate the thermistor functionality (e.g. remove Atex-thermistor plug from the OPTBJ board). The drive enters to fault state and indicates fault 29 (Atex-thermistor fault, subcode 280).

    8.2.1 General wiring instructionsThe thermistor connection must be done using a separate control cable. It is not allowed to use wires belonging the motor supply cables or any other main circuit cables. A shielded control cable must be used. See also Chapter 3.

    8.2.2 Fault diagnosis of thermistor functionThe table below shows the normal fault / warning, generated when thermistor input is active

    See the fault table in chapter 7.1.

    Maximum cable length without short circuit monitoring. Shield must be connected to the drive's lid (PE).

    X23 : OFF

    Maximum cable length with short cir-cuit monitoring.

    X23 : ON

    >= 1.5 sq mm 1500 meters 250 meters

    Fault code Fault ID Explanation Correcting measures

    29 Atex-thermistor 280Atex-thermistor has detected

    overtemperature.

    The resistance of thermistor input must go below 2 kΩ to be able to restart the drive.

    Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

  • Document ID:

    DPD00470ERev. E

    Sales code: DOC-OPTBJ+DLUK

    Vacon LtdMember of the Danfoss GroupRunsorintie 765380 VaasaFinland

    www.danfoss.com

    1. Approvals2. General2.1 References

    3. Installation of OPTBJ board4. OPTBJ board layout4.1 Identifying board revision4.2 OPTBJ board jumpers4.3 STO jumper on the VACON® 100 family AC drive4.4 Cuttable jumper to separate control ground from PE

    5. STO and SS1 safety functions5.1 Safe Torque Off (STO) principle5.2 Safe Stop 1 (SS1) Principle5.3 Technical details5.3.1 Response times5.3.2 Input voltage levels5.3.3 External dark test pulse filtering capability5.3.4 External light test pulse filtering capability5.3.5 Connections5.3.6 Relay output5.3.7 Safety-related data according to the standard

    6. Commissioning6.1 General wiring instructions6.2 Wiring examples6.3 Parameterization of STO functionality6.4 Checklist for commissioning the OPTBJ board6.5 Testing the Safe Torque Off (STO) or Safe Stop 1 (SS1) safety functions

    7. Maintenance7.1 Faults related to the Safe Torque Off (STO) or Safe Stop 1 (SS1) safety functions

    8. Thermistor function (ATEX)8.1 Technical data8.1.1 Functional description8.1.2 Hardware and connections8.1.3 Atex function8.1.4 Short circuit monitoring

    8.2 Commissioning8.2.1 General wiring instructions8.2.2 Fault diagnosis of thermistor function