University Hall Fire Sprinkler System Upgrade
Transcript of University Hall Fire Sprinkler System Upgrade
GENERAL NOTES1. THIS PROJECT INCLUDES THE DESIGN AND PROVISION OF A NEW WET−PIPE SPRINKLER SYSTEM THROUGHOUT THE
UNSPRINKLERED PORTIONS OF THE BUILDING INDICATED ON THE FOLLOWING DRAWINGS.
2. THE ARCHITECTURAL BACKGROUND PROVIDED ON THESE SHEETS IS FOR GENERAL REFERENCE ONLY. CONTRACTOR SHALLVERIFY ALL BACKGROUNDS WITH ARCHITECTURAL SHEETS AND SITE VISIT.
3. SYSTEM DESIGN TO BE PER NFPA−13, 2010 EDITION AND THESE DRAWINGS AND SPECIFICATIONS.
4. CONTRACTOR SHALL OBTAIN SIGNED OWNER’S CERTIFICATE AS PER NFPA−13 AND SPECIFICATIONS.
5. REFER TO SPECIFICATIONS SECTION 21 1300 FOR ADDITIONAL INFORMATION REGARDING THE FIRE PROTECTION SYSTEM.
6. SEE PROJECT SPECIFICATIONS FOR SYSTEM TESTING REQUIREMENTS (HYDROSTATIC, TRIP TESTING ETC.).
7. PIPING:7.1. SPRINKLER CONTRACTOR SHALL COORDINATE LOCATION OF ALL PIPING AND SPRINKLERS WITH OTHER TRADES, HVAC
SYSTEMS IN PARTICULAR. COORDINATION SHALL OCCUR DURING DESIGN AND LAYOUT, AS WELL AS IN THE FIELD.7.2. SPRINKLER PIPING SHALL BE ROUGHED−IN PRIOR TO OR CONCURRENTLY WITH THE INSTALLATION OF MAJOR DUCTWORK.
INSTALLATION OF SPRINKLERS BELOW OBSTRUCTING DUCTWORK MAY OCCUR LATER.7.3. SIZING AND ACTUAL ROUTING OF ALL NEW SPRINKLER SYSTEM PIPING IS THE RESPONSIBILITY OF THE CONTRACTOR AND
SUBJECT TO APPROVAL BY THE ENGINEER.7.4. WET SYSTEM PIPING AND FITTINGS SHALL MEET THE REQUIREMENTS OF NFPA−13, EXCEPT THAT PRESS−FIT AND POZ−LOK
SYSTEMS ARE NOT APPROVED FOR THIS PROJECT.7.5. ALL PIPING 4 INCH AND LARGER TO BE SCHEDULE 40 STEEL; ALL PIPING 3 INCH AND SMALLER TO BE CPVC EXCEPT AS NOTED
BELOW:7.5.1. ALL EXPOSED PIPING TO BE SCHEDULE 40 STEEL.7.5.2. ALL LOCATIONS NOT LISTED FOR CPVC SHALL BE SCHEDULE 40 STEEL.7.5.3. WHERE SUNLIGHT, CHEMICALS, OR PHYSICAL ABUSE COULD BE EXPECTED, ONLY SCHEDULE 40 STEEL PIPE SHALL BE USED.
7.6. PIPING PENETRATIONS THROUGH RATED WALLS SHALL BE SEALED IN ACCORDANCE WITH SPECIFICATIONS (SEE ALSO DETAIL3/F100).
7.7. PAINTING OF PIPE TO BE BY DIVISION 9.
8. HANGERS:8.1. HANGERS, HANGER RODS, CLAMPS, AND INSERTS SHALL BE IN ACCORDANCE WITH NFPA−13, 2010 EDITION.8.2. CPVC HANGERS SHALL BE IN ACCORDANCE WITH MANUFACTURER’S GUIDELINES. SEE DETAIL 4/F100.8.3. TRAPEZE−STYLE HANGING ASSEMBLIES MAY BE USED, BUT ONLY WITH DOCUMENTATION ON THE SHOP DRAWINGS VALIDATING
THE SIZING OF THE TRAPEZE MEMBERS. WHEN A TRAPEZE MEMBER IS NOT EXPLICITLY LISTED IN NFPA−13 (E.G. UNISTRUT),DOCUMENTATION MUST BE PROVIDED THAT INDICATES ADEQUATE SECTION MODULUS AND OTHER PERTINENT PARAMETERSARE BEING MET.
9. SPRINKLERS:9.1. PROTECTION OF SPRINKLERS DURING PAINTING, AND REMOVAL THEREAFTER, SHALL BE BY DIVISION 9.9.2. UNLESS INDICATED OTHERWISE, ALL AUTOMATIC SPRINKLERS LOCATED WITHIN SUSPENDED TILE CEILINGS SHALL BE CHROME,
RECESSED TO MATCH EXISTING SPRINKLERS. UNLESS OTHERWISE NOTED, REMAINING EXPOSED SPRINKLERS SHALL BEBRASS. SEE SPRINKLER LEGEND FOR SPRINKLER TYPE DETAILS.
9.3. SPRINKLERS SHALL BE LOCATED IN THE CENTER OF TILE. SEE DETAIL 2/F100.9.4. HEAD GUARDS LISTED FOR USE WITH THE RESPECTIVE SPRINKLERS SHALL BE INSTALLED ANYWHERE EXPOSED SPRINKLERS
ARE LOCATED BELOW 7’−0" AFF.9.5. ELECTRICAL AND MECHANICAL ROOMS SHALL UTILIZE INTERMEDIATE TEMPERATURE RATED SPRINKLERS.
10. WATER SUPPLY DATA: CONTRACTOR SHALL BASE HYDRAULIC CALCULATIONS ON THE FOLLOWING WATER SUPPLY INFORMATION:10.1. STATIC: 160 PSI RESIDUAL: 150 PSI FLOWING: 1186 GPM10.2. TEST CONDUCTED BY : WESTERN STATES FIRE PROTECTION DATE: 06/04/1010.3. EFFECTIVE POINT: WHERE 6 INCH UNDERGROUND CONNECTS TO 8 INCH UNDERGROUND MAIN. SEE SITE PLAN 1/F100.10.4. HOSE ALLOWANCES SHALL BE TAKEN AT THIS SAME EFFECTIVE POINT.
RISER
VERTICAL PIPE
EXISTING SPRINKLER PIPING
NEW SPRINKLER PIPING
UNDERGROUND WATER MAIN PIPING
CAP
PIPE BREAK
ORDINARY HAZARD GROUP I AREA
ORDINARY HAZARD GROUP II AREA
PLAN NOTE
FIRE DEPARTMENT CONNECTION(FLUSH TYPE)
FIRE DEPARTMENT CONNECTION(SIAMESE TYPE)
BACKFLOW TEST OUTLET
UNDERGROUND GATE VALVE
HYDRANT
EXISTING REMOTE YARD FDC
CHECK VALVE
BUTTERFLY CONTROL VALVE
CEILING HEIGHT ABOVE FINISHED FLOOR
1
FIRE PROTECTION SYMBOLS LEGEND
OH2
OH1
DESIGN NOTES:
1. ALL AREAS WITH THIS SYMBOL: SHALL BE DESIGNEDTO ORDINARY HAZARD GROUP II PARAMETERS AS PERNFPA−13.
2. ALL AREAS WITH THIS SYMBOL: SHALL BE DESIGNEDTO ORDINARY HAZARD GROUP I PARAMETERS AS PERNFPA−13.
3. ALL AREAS WITH THIS SYMBOL: SHALL BE DESIGNEDTO FLOW 20 SPRINKLERS OR ENTIRE ROOM WITHMINIMUM END HEAD PRESSURE OF 7 PSI. SPRINKLERS TOBE 11.2K.
4. ALL REMAINING AREAS TO BE DESIGNED TO LIGHTHAZARD PARAMETERS PER NFPA−13.
5. ALL HYDRAULIC CALCULATIONS SHALL INCLUDE AMINIMUM 10 PSI SAFETY FACTOR.
6. IN ACCORDANCE WITH FM GLOBAL GUIDELINES, AREAREDUCTIONS FOR QUICK RESPONSE SPRINKLERS, AND"SMALL ROOM RULE", SHALL NOT BE USED.
OH2
OH1
SP1
2x4 TILES
24"
12" 12"
48"
24"
24"
24"
24"
2x2BLANK TILES
2x2SCORED TILES
12"
12"6"
6"
6" 6"12"
LOCATE SPRINKLER AT CENTER OR 12 INCHESFROM THE TWO ADJACENT GRID LINES
LOCATE SPRINKLER ATCENTER OF TILE
LOCATE SPRINKLER6 INCHES FROMTWO GRID LINES
OF HANGERS REQUIRED
SEE TABLE BELOW FOR NUMBER
ASTM F442 CPVCBRANCHLINE *
*
20’−1" TO 30’−0"
18’−1" TO 27’−0"
16’−1" TO 24’−0"
13’−1" TO 19’−6"
14’−1" TO 21’−0"
12’−1" TO 18’−0"6’−1" TO 12’−0"
7’−1" TO 14’−0"
6’−7" TO 13’−0"
8’−1" TO 16’−0"
9’−1" TO 18’−0"
10’−1" TO 20’−0"0’−0" TO 10’−0"
0’−0" TO 9’−0"
0’−0" TO 8’−0"
0’−0" TO 6’−6"
0’−0" TO 7’−0"
0’−0" TO 6’−0"
3 Hangers2 Hangers1 Hanger
PIPE SIZE
inches
1"
1¼"
1½"
2"
2½"
3"
Pipe Length
MINIMUM ALLOWABLE HANGERSPER LENGTH OF CPVC PIPE
NSF INTERNATIONAL APPROVED FOR USE WITH POTABLE WATER
NOTE:THE MAXIMUM DISTANCE BETWEEN HANGERS FOR LISTED NONMETALLIC PIPE SHALL BEMODIFIED AS SPECIFIED IN THE INDIVIDUAL PRODUCT LISTINGS.
PIPE
WALLESCUTCHEON
WALLESCUTCHEON
PACK ANNULARSPACE WITHMINERAL WOOL
SEAL WITHAPPROVED FIRECAULKING (SEESPECIFICATIONS)
NOTE:HOLES THROUGH WALLS SHALL BE A MINIMUM OF 1 IN. LARGER, AND MAXIMUMOF 2 IN. LARGER IN DIAMETER THAN THE OUTSIDE DIAMETER OF THE PIPEPASSING THRU THE RATED WALL. THIS SPACE SHALL BE FILLED WITH MINERALWOOL AND SEALED WITH AN APPROVED LISTED FIRE CAULK OR SEALANT. ALLPENETRATIONS OF FIRE RATED WALLS AND ASSEMBLIES SHALL BE UL LISTEDFOR THAT PURPOSE, FOR BOTH THE TYPE OF PIPE MATERIAL AND WALL ORCEILING/FLOOR CONSTRUCTION. LISTED ALTERNATE METHODS WILL BEACCEPTED.
APPROX. 60 FT OFEXISTING 6 IN. UGWATER MAIN
EFFECTIVE POINT
EXISTING HYDRANT
EXISTING GATE VALVEEXISTING 8 IN. UGWATER MAIN
EXISTING REMOTE YARD FDC
EXISTING HYDRANTELEVATION = 92’−0"
FLOOR ELEVATION @SPRINKLER CONTROLS = 72’−0"
EXISTINGGATE VALVE
FLOW TEST INFO:STATIC: 160 PSIRESIDUAL: 150 PSIFLOWING: 1186 GPM
CONCRETE
FLOOR SLAB
CLIP
ANGLE
POST- INSTALLED
ANCHOR
ALL THREAD
ROD
HANGER
RINGPIPE
CONCRETE
TEE
POST- INSTALLED
ANCHOR
ALL THREAD
ROD
HANGER
RINGPIPE
NOTE:ALL ANCHORS AND HANGERS TO BE LISTED FORUSE IN CONCRETE IN ACCORDANCE WITH NFPA 13,2010 EDITION.
5’−0"
2’−6"
CEILING SPACECEILING SPACE
STEEL STUD
ROOF
LIGHT COVE
GYP BOARD
SKYLIGHT
GRID CEILING
USER\PW: REED.ROISUM\M4500-3755 O:\PROJECTS\2010\10.01833\2.0 PROJECT EXECUTION\2.2 DESIGN - ENGINEERING\DRAWINGS\10.01833 F100.DWG 28 FEB 2011 - 3:52PM XREFS:
19 SOUTH TEJON ST., SUITE 300COLORADO SPRINGS, CO. 80903
TELE.: 719−471−7566 FAX: 719−471−1174www.rtaarchitects.com
SHEET NO.
ISSUED FOR:
BID SET
02-28-11
REVISION
DATE
RTA PROJECT NUMBER
10070.00
SHEET TITLE
COPYRIGHT RTA, INC.c
3955 CRAGWOOD DRIVE, COLORADO SPRINGS, COLORADO 80907
University Hall
Fire Sprinkler System Upgrade
DRAWN BY:
CHECKED BY:
UEI PROJECT NUMBER
10.01833
Web: www.ulteig.com
9777 Pyramid Court, Suite 200
Phone: 720.873.5700
Englewood, CO 80112
Fax: 720.873.5701
0’ 50’25’ 100’
RAR
MAS
F100
DETAILS − FIRE PRO
SITE PLAN −
OH1
OH1 OH1
OH1
OH2OH2
OH2
OH1
6
2
OH2 OH2
OH2
OH1
OH2
OH2
DN TO LEVEL 2
LEVEL 2FEED MAIN
LEVEL 2FEED MAIN
LEVEL 2FEED MAIN
LEVEL 2FEED MAIN
1
1
15
3
3
3
444
9
3
3
3
45
5
5
7 7 710
131313
13
13
13
13
13 1313
13
THIS LEVELFEED MAIN
14
14
16 16
12
12
12
12
12 12
OH1
OH2 OH2
OH2
13
OH2
EXISTING HOSECONNECTION
INSPECTOR’STEST OUTLET
removehead??
OH1
OH2
13
16
16
16
16
16
16
16
16
SP1SP1
SP1
SP1
PLAN NOTES
1. PROVIDE AND INSTALL HORIZONTAL SIDEWALL SPRINKLER UNDER OPEN GARAGEDOOR.
2. PROVIDE INTERMEDIATE OR HIGH TEMPERATURE RATED SPRINKLERS NEAR UNITHEATER BASED ON NFPA 13 GUIDELINES.
3. PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE RATED BRASS UPRIGHTSPRINKLERS IN SKYLIGHTS. SEE 6/F100 FOR DETAILS.
4. PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE HORIZONTAL SIDEWALLSPRINKLER POINTING DOWN THE SLOPE IN THE APPROXIMATE LOCATION SHOWN.PIPING TO BE ROUTED AS HIGH AND TIGHT TO WALL AS POSSIBLE. ALL EXPOSEDPIPING TO BE SCHEDULE 40 STEEL IN THIS AREA.
5. PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE RATED CONCEALEDSPRINKLER WITH BRUSHED BRASS COVER PLATE IN DISPLAY CASE AS SHOWN.
6. PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE RATED RECESSED PENDANTSPRINKLER IN APPROXIMATE LOCATION SHOWN. SPRINKLER PROTECTION NOTREQUIRED IN SKYLIGHT.
7. PROVIDE AND INSTALL EXTENDED COVERAGE RECESSED HORIZONTAL SIDEWALLSPRINKLER IN APPROXIMATE LOCATION SHOWN. FINISH AND ESCUTCHEON FINISHTO BE CHROME.
8. NO WORK IN THIS AREA. EXISTING SPRINKLERS.
9. PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE HORIZONTAL SIDEWALLSPRINKLER POINTING DOWN THE SLOPE IN THE APPROXIMATE LOCATION SHOWN.ALL EXPOSED PIPING TO BE SCHEDULE 40 STEEL IN THIS AREA.
10. ROUTE LEVEL 2 FEED MAIN DOWN IN CHASE IN THIS APPROXIMATE LOCATION.
11. NOT USED.
12. NO SPRINKLER PROTECTION REQUIRED BELOW NON−COMBUSTIBLE EXTERIOROVERHANG.
13. CPVC PIPING NOT ALLOWED IN OR ABOVE THIS ROOM.
14. COORDINATE CROSS MAIN ROUTING WITH EXISTING CONDITIONS.
15. PROVIDE AND INSTALL CONCEALED SPRINKLER WITH BRUSHED BRASS COVERPLATE AS SHOWN.
16. NO SPRINKLER PROTECTION REQUIRED WITHIN CEILING POCKET.
#
TYPEMFR.THDSZ
TEMP.RTG.
SPRNKFINISH
VIKING RECESSED PENDANT 12"
KFCTR
5.6 200° CHROME
SYMB.
SPRINKLER LEGEND
S.I.N.NO.
ESCUT.FINISH
CHROMEVK302
RSPNS
QUICK
VIKING FLAT CONCEALED PENDANT − "MIRAGE" 12"5.6 200° BRASS
BRUSHEDBRASS
VK462 QUICK
VIKING HORIZONTAL SIDEWALL 12"5.6 155° BRASS N/AVK305 QUICK
VIKING RECESSED PENDANT 12"5.6 155° CHROME CHROMEVK302 QUICK
VIKING RECESSED HORIZONTAL SIDEWALL 12"5.6 155° CHROME CHROMEVK305 QUICK
VIKING RECESSED HORIZONTAL SIDEWALL 12"5.6 200° CHROME CHROMEVK305 QUICK
VIKING UPRIGHT 12"5.6 200° BRASS N/AVK300 QUICK
VIKING EXTENDED COVERAGE REC. HORIZ. SIDEWALL 34"8.0 155° CHROMEVK606 QUICK CHROME
UPRIGHT 34 "11.2 155° BRASS N/AVK531 QUICKVIKING
DESIGN NOTES:
1. ALL AREAS WITH THIS SYMBOL: SHALL BE DESIGNEDTO ORDINARY HAZARD GROUP II PARAMETERS AS PERNFPA−13.
2. ALL AREAS WITH THIS SYMBOL: SHALL BE DESIGNEDTO ORDINARY HAZARD GROUP I PARAMETERS AS PERNFPA−13.
3. ALL AREAS WITH THIS SYMBOL: SHALL BE DESIGNEDTO FLOW 20 SPRINKLERS OR ENTIRE ROOM WITHMINIMUM END HEAD PRESSURE OF 7 PSI. SPRINKLERS TOBE 11.2K.
4. ALL REMAINING AREAS TO BE DESIGNED TO LIGHTHAZARD PARAMETERS PER NFPA−13.
5. ALL HYDRAULIC CALCULATIONS SHALL INCLUDE AMINIMUM 10 PSI SAFETY FACTOR.
6. IN ACCORDANCE WITH FM GLOBAL GUIDELINES, AREAREDUCTIONS FOR QUICK RESPONSE SPRINKLERS, AND"SMALL ROOM RULE", SHALL NOT BE USED.
OH2
OH1
SP1
USER\PW: REED.ROISUM\M4500-3755 O:\PROJECTS\2010\10.01833\2.0 PROJECT EXECUTION\2.2 DESIGN - ENGINEERING\DRAWINGS\10.01833 F110.DWG 28 FEB 2011 - 3:47PM XREFS:
19 SOUTH TEJON ST., SUITE 300COLORADO SPRINGS, CO. 80903
TELE.: 719−471−7566 FAX: 719−471−1174www.rtaarchitects.com
SHEET NO.
ISSUED FOR:
BID SET
02-28-11
REVISION
DATE
RTA PROJECT NUMBER
10070.00
SHEET TITLE
COPYRIGHT RTA, INC.c
3955 CRAGWOOD DRIVE, COLORADO SPRINGS, COLORADO 80907
University Hall
Fire Sprinkler System Upgrade
DRAWN BY:
CHECKED BY:
UEI PROJECT NUMBER
10.01833
Web: www.ulteig.com
9777 Pyramid Court, Suite 200
Phone: 720.873.5700
Englewood, CO 80112
Fax: 720.873.5701
KEY PLANN.T.S. NORTH
UNIVERSITY HALL BUILDING
0’ 8’4’ 16’
SEE 1/F120 FOR CONTINUATION
RAR
MAS
F110
FIRE PROTECTION
FLOOR PLAN
PARTIAL MAIN LEVEL
PLAN NOTES
1. SPRINKLER CONTROLS. SEE DETAIL 2/F200.
2. PROVIDE AND INSTALL (2) NEW SPARE HEAD CABINETS. ONE 12HEAD SPARE CABINET TO HOLD THE REQUIRED SPARESPRINKLERS AND ONE (6) HEAD CABINET TO HOUSE SPARECOVER PLATES AS SPECIFIED.
3. PROVIDE HORIZONTAL SIDEWALL SPRINKLER IN ELEVATOR PITLOCATED NO MORE THAN 2 FT UP FROM PIT FLOOR. PROVIDEFLOW SWITCH WITH VALVE ABOVE CEILING, OUTSIDE ELEVATORSHAFT. ROUTE TEST/DRAIN PIPING TO EXTERIOR WALL ANDOUT. PROVIDE SPLASH BLOCK AT EXTERIOR.
4. NO SPRINKLERS OR SPRINKLER PIPING ALLOWED IN ELEVATOREQUIPMENT ROOM.
5. PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE RATEDCONCEALED SPRINKLER WITH BRUSHED BRASS COVER PLATEIN DISPLAY CASE AS SHOWN.
6. LEVEL 2 FLOOR CONTROLS LOCATED ABOVE CEILING. SEE3/F200 FOR DETAILS.
7. ROUTE DRAIN PIPING TO EXTERIOR WALL IN APPROXIMATELOCATION SHOWN. PROVIDE SPLASH BLOCK AT EXTERIOR.
8. NO WORK IN THIS AREA. EXISTING SPRINKLERS.
9. FEED MAIN FROM LEVEL 1. ROUTE MAIN ABOVE CEILING TOFLOOR CONTROLS LOCATION SHOWN.
10. FEED MAIN UP FROM LEVEL 2.
11. LEVEL 1 FLOOR CONTROLS. SEE 4/F200 FOR DETAILS.
12. NO SPRINKLER PROTECTION REQUIRED BELOWNON−COMBUSTIBLE EXTERIOR OVERHANG.
13. CPVC PIPING NOT ALLOWED IN OR ABOVE THIS ROOM.
#
4
DN FROM LEVEL 1
OH1
3
OH1
6
7
9
SPRINKLEREDFROM ABOVE
OH2
13
13
OH2
LEVEL 2FEED MAIN
LEVEL 1FEED MAIN
LEVEL 2FEED MAIN
11
8
8
8
10
5
5
5
7
12
ALL ROOMS WITHIN THIS PORTIONOF THE FLOOR PROVIDED WITHEXISTING SPRINKLER PROTECTION.
OH2
ROUTE FEED MAINUP TO LEVEL 2
SEE SITE PLAN 1/F100FOR CONTINUATION
EXISTING 6 IN. UGWATER MAIN
1
2
ALL ROOMS WITHIN THIS PORTIONOF THE FLOOR PROVIDED WITHEXISTING SPRINKLER PROTECTION.
TYPEMFR.THDSZ
TEMP.RTG.
SPRNKFINISH
VIKING RECESSED PENDANT 12"
KFCTR
5.6 200° CHROME
SYMB.
SPRINKLER LEGEND
S.I.N.NO.
ESCUT.FINISH
CHROMEVK302
RSPNS
QUICK
VIKING FLAT CONCEALED PENDANT − "MIRAGE" 12"5.6 200° BRASS
BRUSHEDBRASS
VK462 QUICK
VIKING HORIZONTAL SIDEWALL 12"5.6 155° BRASS N/AVK305 QUICK
VIKING RECESSED PENDANT 12"5.6 155° CHROME CHROMEVK302 QUICK
VIKING RECESSED HORIZONTAL SIDEWALL 12"5.6 155° CHROME CHROMEVK305 QUICK
VIKING RECESSED HORIZONTAL SIDEWALL 12"5.6 200° CHROME CHROMEVK305 QUICK
VIKING UPRIGHT 12"5.6 200° BRASS N/AVK300 QUICK
VIKING EXTENDED COVERAGE REC. HORIZ. SIDEWALL 34"8.0 155° CHROMEVK606 QUICK CHROME
UPRIGHT 34 "11.2 155° BRASS N/AVK531 QUICKVIKING
DESIGN NOTES:
1. ALL AREAS WITH THIS SYMBOL: SHALL BE DESIGNEDTO ORDINARY HAZARD GROUP II PARAMETERS AS PERNFPA−13.
2. ALL AREAS WITH THIS SYMBOL: SHALL BE DESIGNEDTO ORDINARY HAZARD GROUP I PARAMETERS AS PERNFPA−13.
3. ALL AREAS WITH THIS SYMBOL: SHALL BE DESIGNEDTO FLOW 20 SPRINKLERS OR ENTIRE ROOM WITHMINIMUM END HEAD PRESSURE OF 7 PSI. SPRINKLERS TOBE 11.2K.
4. ALL REMAINING AREAS TO BE DESIGNED TO LIGHTHAZARD PARAMETERS PER NFPA−13.
5. ALL HYDRAULIC CALCULATIONS SHALL INCLUDE AMINIMUM 10 PSI SAFETY FACTOR.
6. IN ACCORDANCE WITH FM GLOBAL GUIDELINES, AREAREDUCTIONS FOR QUICK RESPONSE SPRINKLERS, AND"SMALL ROOM RULE", SHALL NOT BE USED.
OH2
OH1
SP1
FEED MAIN UPFROM LEVEL 3(LOWER LEVEL)
FEED MAIN UP TO LEVEL 1(MAIN/GARDEN LEVEL)
ALL ROOMS WITHIN THIS PORTIONOF THE FLOOR PROVIDED WITHEXISTING SPRINKLER PROTECTION.
USER\PW: REED.ROISUM\M4500-3755 O:\PROJECTS\2010\10.01833\2.0 PROJECT EXECUTION\2.2 DESIGN - ENGINEERING\DRAWINGS\10.01833 F120.DWG 28 FEB 2011 - 3:42PM XREFS:
19 SOUTH TEJON ST., SUITE 300COLORADO SPRINGS, CO. 80903
TELE.: 719−471−7566 FAX: 719−471−1174www.rtaarchitects.com
SHEET NO.
ISSUED FOR:
BID SET
02-28-11
REVISION
DATE
RTA PROJECT NUMBER
10070.00
SHEET TITLE
COPYRIGHT RTA, INC.c
3955 CRAGWOOD DRIVE, COLORADO SPRINGS, COLORADO 80907
University Hall
Fire Sprinkler System Upgrade
DRAWN BY:
CHECKED BY:
UEI PROJECT NUMBER
10.01833
Web: www.ulteig.com
9777 Pyramid Court, Suite 200
Phone: 720.873.5700
Englewood, CO 80112
Fax: 720.873.5701
KEY PLANN.T.S. NORTH
UNIVERSITY HALL BUILDING
0’ 8’4’ 16’
0’ 8’4’ 16’
0’ 8’4’ 16’
0’ 8’4’ 16’
SE
E 1
/F1
10 F
OR
CO
NT
INU
AT
ION
RAR
MAS
F120
FIRE PROTECTION
PARTIAL FLOOR PLANS
7 8654321
USER\PW: REED.ROISUM\M4500-3755 O:\PROJECTS\2010\10.01833\2.0 PROJECT EXECUTION\2.2 DESIGN - ENGINEERING\DRAWINGS\10.01833 F200.DWG 28 FEB 2011 - 3:57PM XREFS:
19 SOUTH TEJON ST., SUITE 300COLORADO SPRINGS, CO. 80903
TELE.: 719−471−7566 FAX: 719−471−1174www.rtaarchitects.com
SHEET NO.
ISSUED FOR:
BID SET
02-28-11
REVISION
DATE
RTA PROJECT NUMBER
10070.00
SHEET TITLE
COPYRIGHT RTA, INC.c
3955 CRAGWOOD DRIVE, COLORADO SPRINGS, COLORADO 80907
University Hall
Fire Sprinkler System Upgrade
DRAWN BY:
CHECKED BY:
UEI PROJECT NUMBER
10.01833
Web: www.ulteig.com
9777 Pyramid Court, Suite 200
Phone: 720.873.5700
Englewood, CO 80112
Fax: 720.873.5701
0’ 2’1’ 4’
1 BUTTERFLY VALVE WITH TAMPER SWITCH.
CHECK VALVE
FLOOR CONTROL VALVE ASSEMBLY INCLUDING:
FLOW SWITCH
PRESSURE RELIEF VALVE
PRESSURE GAUGE WITH 3−WAY VALVE
DRAIN TO OUTSIDE WALL
TO LEVEL 2 SPRINKLER SYSTEM
TO LEVEL 1 SPRINKLER SYSTEM
FEED MAIN FROM BELOW
2
3
4
5
3a
3b
3c
3d
3
1
2
3a
3b
3c
3d
3d
4 5
6
6
1
2
3
4
5
6
1 EXISTING 6 IN. UNDERGROUND WATER LEAD−IN.
EXISTING 4 IN. MAIN.
EXISTING 4 IN. 2000SS AMES BACKFLOW ASSEMBLY
EXISTING MAIN DRAIN
EXISTING FLOW SWITCH
EXISTING PRESSURE GAUGE
EXISTING SYSTEM BUTTERFLY CONTROL VALVE
EXISTING WET SYSTEM
EXISTING FDC PIPING
EXISTING FDC CHECK VALVE
EXISTING STANDPIPE PIPING
2
3
4
5
6
7
8
9
10
11
1
1
2
2
3
3
4
44
4
45
5
5
6
6
6
7
88
99
10
10
11 11
1 EXISTING 6 IN. UNDERGROUND WATER LEAD−IN.
EXISTING 4 IN. MAIN.
EXISTING 4 IN. 2000SS AMES BACKFLOW ASSEMBLY
EXISTING MAIN DRAIN
EXISTING FLOW SWITCH
EXISTING PRESSURE GAUGE
EXISTING SYSTEM BUTTERFLY CONTROL VALVE
EXISTING WET SYSTEM
EXISTING FDC PIPING
EXISTING FDC CHECK VALVE
EXISTING STANDPIPE PIPING
NEW BUTTERFLY VALVE WITH TAMPER SWITCH
NEW WET SYSTEM
2
3
4
5
6
7
8
9
10
11
1
2
3 4
4
5
6
9
10
11
1
2
3
4
4
4
5
5
6
6
7
8
9
10
11
12
13
12
12
13
13
13
13
5
5
1
3
4
4
6
7
8
9
1 BUTTERFLY VALVE WITH TAMPER SWITCH.
CHECK VALVE
FLOOR CONTROL VALVE ASSEMBLY INCLUDING:
FLOW SWITCH
PRESSURE RELIEF VALVE
PRESSURE GAUGE WITH 3−WAY VALVE
DRAIN TO OUTSIDE WALL
TO LEVEL 2 SPRINKLER SYSTEM
FEED MAIN
2
3
4
5
3a
3b
3c
3d
3
1
2
3a
3b
3c
3d
5
ABOVE CEILING SPACE
ABOVE CEILING SPACE
OFFICE 208
OFFICE 208
LIGHT FIXTURE (TYP.)
4
LIGHT FIXTURE (TYP.)
CEILING
1
2
3
4
5
0’ 8’4’ 16’
RAR
MAS
F200
DETAILS − FIRE PRO
3d
3d
3d
3d
3d
3d
1. PROVIDE AND INSTALL (2) NEW SPARE HEADCABINETS ON WALL NEAR SPRINKLER CONTROLS.ONE 12 HEAD SPARE CABINET TO HOLD THEREQUIRED SPARE SPRINKLERS AND ONE (6) HEADCABINET TO HOUSE SPARE COVER PLATES ASSPECIFIED.