ÇUKUROVA UNIVERSITY INSTITUTE OF NATURAL AND …Endüksiyon Fırını, Pasif Filtreler, Melez Aktif...
Transcript of ÇUKUROVA UNIVERSITY INSTITUTE OF NATURAL AND …Endüksiyon Fırını, Pasif Filtreler, Melez Aktif...
ÇUKUROVA UNIVERSITY
INSTITUTE OF NATURAL AND APPLIED SCIENCES
MSc THESIS
Adnan TAN
MODELING AND ANALYSIS OF POWER QUALITY COMPENSATION
SYSTEMS FOR CURRENT SOURCE INVERTER BASED INDUCTION
FURNACE
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING
ADANA, 2011
ÇUKUROVA UNIVERSITY
INSTITUTE OF NATURAL AND APPLIED SCIENCES
MODELING AND ANALYSIS OF POWER QUALITY COMPENSATION
SYSTEMS FOR CURRENT SOURCE INVERTER BASED INDUCTION
FURNACE
Adnan TAN
MSc THESIS
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING
We certify that the thesis titled above was reviewed and approved for the award of degree
of the Master of Science by the board of jury on 09/08/2011.
Asst. Prof. Dr. K. Çağatay BAYINDIR
SUPERVISOR
Prof. Dr. Mehmet TÜMAY
MEMBER
Assoc. Prof. Dr. Zekeriya TÜFEKÇĠ
MEMBER
This MSc Thesis is written at the Department of Institute of Natural And Applied Sciences
of Çukurova University.
Registration Number:
Prof. Dr. İlhami YEĞİNGİL
Director
Institute of Natural and Applied Sciences
Note: The usage of the presented specific declarations, tables, figures, and photographs either in this thesis
or in any other reference without citation is subject to "The law of Arts and Intellectual Products"
number of 5846 of Turkish Republic.
To My Brother Levent TAN
Who Passed Away in October 2010
I
ABSTRACT
MSc THESIS
MODELING AND ANALYSIS OF POWER QUALITY COMPENSATION
SYSTEMS FOR CURRENT SOURCE INVERTER BASED INDUCTION
FURNACE
Adnan TAN
ÇUKUROVA UNIVERSITY
INSTITUTE OF NATURAL AND APPLIED SCIENCES
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING
Supervisor : Asst. Prof. Dr. K. Çağatay BAYINDIR
Year : 2011, Pages: 193
Jury : Asst. Prof. Dr. K. Çağatay BAYINDIR
: Prof. Dr. Mehmet TÜMAY
: Assoc. Prof. Dr. Zekeriya TÜFEKÇĠ
With the developments in the power electronics technology, high-power converters
have become available in many of industrial applications. High-power converters provide
efficient electric energy utilizing and advance control of process in many of industrial
applications. Besides the advantages of these power converters, they show nonlinear load
characteristic which causes various power quality (PQ) problems in electric power systems.
Induction steel scrap melting furnaces are one of the examples of industrial
applications which use high power converters in power supplies. In high power induction
furnaces, power supply is commonly formed from 12-pulse or higher pulse fully controlled
rectifier, current source inverter and parallel resonant tank circuit. Besides the advantages of
current source inverter based induction furnaces (CSI-IF) in melting process, CSI-IFs causes
serious PQ problems such as; time varying harmonics and interharmonics. Moreover, when
these high power furnaces are supplied from weak power systems, voltage fluctuations and
flicker problems occur in the power system.
In this thesis, the CSI-IF is modeled in PSCAD/EMTDC simulation program in
order to investigate the time varying harmonics and interharmonics of CSI-IF and find
solutions to these PQ problems. For the solution of PQ problems of CSI-IF, passive filtering
and active filtering methods are investigated. In passive filtering methods; single tuned filter,
C-type filter and broad band filter are designed for the PQ problems of CSI-IF. In active
filtering methods, hybrid active power filters (HAPF) which use shunt active power filter
(APF) - shunt passive filter topology and APF in series with shunt passive filters topology
are designed for the PQ problems of CSI-IF. The compensation performances of these
passive filters and HAPFs are investigated by modeling in PSCAD/EMTDC simulation
program.
Key Words: Harmonics, Interharmonics, Current Source Inverters, Induction Furnace,
Passive Filters, Hybrid Active Power Filters
II
ÖZ
YÜKSEK LİSANS TEZİ
AKIM KAYNAKLI ÇEVİRGECE DAYALI ENDÜKSİYON FIRINI İÇİN
GÜÇ KALİTESİ KOMPANZASYON SİSTEMLERİNİN MODELLENMESİ
VE ANALİZİ
Adnan TAN
ÇUKUROVA ÜNİVERSİTESİ
FEN BİLİMLERİ ENSTİTÜSÜ
ELEKTRİK ELEKTRONİK MÜHENDİSLİĞİ ANABİLİM DALI
Danışman : Yrd. Doç. Dr. K. Çağatay BAYINDIR
Yıl :2011, Pages 193
Jüri : Yrd. Doç. Dr. K. Çağatay BAYINDIR
: Prof. Dr. Mehmet TÜMAY
: Doç. Dr. Zekeriya TÜFEKÇĠ
Güç elektroniği teknolojisindeki gelişmelerle birlikte yüksek güçlü çevirgeçler
birçok endüstriyel uygulamada kullanılmaktadır. Bu yüksek güçlü çevirgeçler, birçok
endüstriyel uygulamada elektrik enerjisinin verimli kullanılmasını ve önemli proses kontrol
özellikleri sağlamaktadırlar. Çevirgeçlerin bu avantajlarının yanında, bu çevirgeçler elektrik
güç sistemlerinde çeşitli güç kalitesi problemlerine yol açan lineer olmayan yük
karakteristiği göstermektedirler.
Endüksiyonla hurda çelik eritme fırınları yüksek güçlü çevirgeçlerin kullanıldığı
endüstriyel uygulamalara bir örnektir. Yüksek güçlü endüksiyon fırınlarında kullanılan güç
ünitesi genellikle 12 veya daha yüksek darbeli tam kontrollü doğrultucudan, akım kaynaklı
çevirgeçten ve paralel bağlı rezonans tank devresinden oluşmaktadır. Akım kaynaklı
çevirgece dayalı endüksiyon fırının (AKÇ-EF) avantajlarının yanında bu fırınlar zamanla
değişen harmonik ve araharmonik gibi güç kalitesi sorunlarına yol açmaktadır. Ayrıca bu
yüksek güçlü fırınlar zayıf elektrik şebekelerine bağlandıklarında, elektrik şebekesinde
gerilim dalgalanmalarına ve kırpışma sorunlarına sebep olmaktadırlar.
Bu tez çalışmasında, AKÇ-EF’ nin zamanla değişen harmoniklerini ve
araharmoniklerini incelemek ve bu güç kalitesi problemlerine çözüm bulmak için fırının
PSCAD/EMTDC simülasyon programında modeli oluşturulmuştur. Fırının güç kalitesi
problemlerinin çözümü için pasif ve aktif filtreleme yöntemleri incelenmiştir. Pasif
filtreleme yöntemlerinde, AKÇ-EF’ nin güç kalitesi problemlerinin çözümü için tek frekansa
ayarlanmış pasif filtre, C-Tipi filtre ve geniş band geçiren filtre tasarlanmıştır. Aktif
filtreleme yöntemlerinde ise AKÇ-EF’ nin güç kalitesi problemlerinin çözümü için paralel
aktif güç filtresi (AGF)-paralel pasif filtre topolojisi ve paralel pasif filtre ile seri bağlanmış
AGF topolojisi kullanan melez AGF’ leri tasarlanmıştır. Bu pasif filtrelerin ve melez
AGF’ lerinin kompanzasyon performansları PSCAD/EMTDC simülasyon programında
modellenerek incelenmiştir.
Anahtar Kelimeler: Harmonikler, Araharmonikler, Akım Kaynaklı Çevirgeçler,
Endüksiyon Fırını, Pasif Filtreler, Melez Aktif Güç Filtreleri
III
ACKNOWLEDGEMENTS
I would like to express my deepest gratitude to my supervisor Asst. Prof. Dr.
K. Çağatay BAYINDIR for his guidance, advice, criticism, encouragements and
insight throughout this research.
I am also grateful to Prof. Dr. Mehmet TÜMAY, head of the Department, for
his help and support during my study.
I am also grateful to Dr. Ahmet TEKE, Dr. M. Uğraş CUMA, Lütfü
SARIBULUT, Murat FURAT, Tahsin KÖROĞLU and M. Mustafa SAVRUN for
their support and friendship.
I wish to express my special thanks to Dr. Alper TERCĠYANLI and Ġlker
YILMAZ for sharing their knowledge and experience on power quality analysis and
active power filters.
I also wish to express my deepest gratitude to my mother Dilber TAN, my
brother Mehmet Serkan TAN and my extended family for their endless support,
encouragement and patience.
Finally, I owe my deepest gratitude to my lovely wife for her love, persistent
confidence in me, patience and endless support during this heavy work.
IV
CONTENTS PAGE
ABSTRACT .................................................................................................................. I
ÖZ ................................................................................................................................ II
ACKNOWLEDGEMENTS ....................................................................................... III
CONTENTS ............................................................................................................... IV
LIST OF TABLES ............................................................................................................. VI
LIST OF FIGURES ........................................................................................................ VIII
LIST OF SYMBOLS .............................................................................................. XVI
LIST OF ABBREVATIONS ............................................................................... XXIV
1. INTRODUCTION .................................................................................................... 1
1.1. Background and Research Motivation .............................................................. 1
1.2. Scope of Thesis .................................................................................................. 2
1.3. Outline of Thesis ............................................................................................... 6
2. INDUCTION HEATING ......................................................................................... 7
2.1. History of Induction Heating ............................................................................. 7
2.2. Basic Principles of Induction Heating ............................................................... 8
2.3. Applications of Induction Heating .................................................................. 10
2.3.1. Heating ................................................................................................... 10
2.3.2. Heat Treating .......................................................................................... 11
2.3.3. Melting ................................................................................................... 14
2.3.4. Welding, Brazing and Soldering ............................................................ 18
2.3.5. Other Applications ................................................................................. 19
2.4. Power Supplies of Induction Furnaces ............................................................ 20
3. HARMONICS AND INTERHARMONICS ......................................................... 29
3.1. Harmonics ........................................................................................................ 29
3.2. Interharmonics ................................................................................................. 37
3.3. Harmonic and Interharmonic Mitigation Techniques ..................................... 39
3.3.1. Passive Filters ......................................................................................... 40
3.3.2. Active Power Filters ............................................................................... 44
3.4. Harmonic and Interharmonic Extraction Methods .......................................... 51
V
4. MODELING AND ANALYSIS OF CSI-IF .......................................................... 53
4.1. Operating Principles of CSI – IF Power Supply ............................................. 54
4.1.1. Parallel Resonant Tank Circuit ............................................................... 54
4.1.2. CSI .......................................................................................................... 63
4.1.3. 12-Pulse Fully Controlled Rectifier ....................................................... 66
4.2. Power Quality Problems of CSI-IF ................................................................. 68
4.3. Modeling of Current Source Induction Furnace .............................................. 71
4.3.1. Power Circuit Parameters ....................................................................... 71
4.3.2. Controller of CSI-IF ............................................................................... 72
4.3.3. Simulation Results of CSI-IF ................................................................. 75
4.3.4. Comparison of Simulation Results with Real Power Quality
Measurements of Induction Furnace ...................................................... 92
5. MODELING AND ANALYSIS OF PQ COMPENSATION SYSTEMS FOR CSI-
IF ............................................................................................................................ 95
5.1. Passive Filters .................................................................................................. 95
5.1.1. Single Tuned Passive Filters .................................................................. 95
5.1.2. C - Type Passive Filters ........................................................................ 107
5.1.3. Broad - Band Passive Filters ................................................................ 119
5.2. Hybrid Active Power Filters .......................................................................... 134
5.2.1. Shunt Active Power Filter and Parallel Passive Filter Combination .... 134
5.2.1.1. Power Circuit Configuration of Proposed HAPF System ........ 134
5.2.1.2. Control Method of APF Modules in Proposed HAPF System 137
5.2.1.3. Simulation Results of Proposed HAPF System ....................... 143
5.2.2. Active Power Filter Series with Passive Filter Combination: SHAPF 157
5.2.2.1. Power Circuit Configuration of Proposed SHAPF System ..... 157
5.2.2.2. Control Method of SHAPF Modules in Proposed SHAPF System
.................................................................................................. 162
5.2.2.3. Simulation Results of Proposed SHAPF System ..................... 165
6. CONCLUSIONS .................................................................................................. 179
REFERENCES ......................................................................................................... 185
BIOGRAPHY .......................................................................................................... 193
VI
LIST OF TABLES PAGE
Table 3.1. Harmonic Extraction Methods ........................................................... 51
Table 4.1. Power Circuit Parameters of CSI-IF Model ....................................... 72
Table 5.1. Power Circuit Parameters of Single Tuned Passive Filter Model ...... 99
Table 5.2. Power Circuit Parameters of C-Type Filter Model .......................... 109
Table 5.3. Initial Values for Power Circuit Parameters of LLCL Type Broad-
Band Filter Model............................................................................. 122
Table 5.4. Final Values for Power Circuit Parameters of LLCL Type Broad-Band
Filter Model ...................................................................................... 123
Table 5.5. Power Circuit Parameters of HAPF System ..................................... 145
Table 5.6. Power Circuit Parameters of SHAPF System .................................. 167
Table 6.1. Comparison of Investigated Compensation Systems ....................... 183
VII
VIII
LIST OF FIGURES PAGE
Figure 1.1. General Block Diagram of Induction Furnaces .................................... 1
Figure 1.2. 3-D Drawing of a High Power Induction Melting Furnace .................. 4
Figure 2.1. Principles of Induction Heating ............................................................ 9
Figure 2.2. Steel Billet Heating Induction Furnace .............................................. 11
Figure 2.3. Variety of Induction Hardening Patterns Obtained Using Variations in
Frequency, Heat Time, and Coil Power ............................................. 12
Figure 2.4. Induction Spin Hardening Process ..................................................... 13
Figure 2.5. Gap by Gap Hardening Operation of Gears ....................................... 13
Figure 2.6. Cross - Section View of Channel Type Induction Furnace ................ 16
Figure 2.7. Cross - Section View of Coreless Induction Furnace ......................... 17
Figure 2.8. Induction Welding of Tubular Products ............................................. 18
Figure 2.9. Power - Frequency Diagram of Induction Heating Applications ....... 22
Figure 2.10. Three Phase Uncontrolled Rectifier ................................................... 22
Figure 2.11. Three Phase Fully Controlled Rectifier .............................................. 23
Figure 2.12. Three Phase Uncontrolled Rectifier with SMR .................................. 23
Figure 2.13. Power-Frequency Diagram of Solid State Devices Used in Inverters of
Induction Heating Power Supplies ..................................................... 25
Figure 2.14. VSI with Series Resonance Load ....................................................... 26
Figure 2.15. VSI with Series Resonant Circuit Connected to Parallel Resonant
Tank .................................................................................................... 27
Figure 2.16. VSI with Parallel Resonance Load ..................................................... 28
Figure 3.1. Single Line Diagram of Power System with Potential Parallel
Resonance Problems ........................................................................... 33
Figure 3.2. Equivalent Circuit of Power System with Potential Parallel Resonance
Problems ............................................................................................. 33
Figure 3.3. Power System Impedance in Parallel Resonance Problems ............... 33
Figure 3.4. Single Line Diagram of Power System with Potential Parallel and
Series Resonance Problem ................................................................. 34
IX
Figure 3.5. Equivalent Circuit of Power System with Potential Parallel and Series
Resonance Problems ........................................................................... 35
Figure 3.6. Power System Impedance in Parallel and Series Resonance Problems .
............................................................................................................ 35
Figure 3.7. Single Line Diagram of Power System with Linear, Nonlinear and
Compensation Loads .......................................................................... 36
Figure 3.8. Equivalent Circuit of Power System with Linear, Nonlinear and
Compensation Loads .......................................................................... 36
Figure 3.9. Effects of Resistive Loads on Parallel Resonance ............................. 36
Figure 3.10. Series Passive Filter ............................................................................ 41
Figure 3.11. Shunt Passive Filter Topologies ......................................................... 42
Figure 3.12. Shunt Passive filters Impedance - Frequency Curves ......................... 43
Figure 3.13. Broad-Band Passive Filter .................................................................. 43
Figure 3.14. Block Diagram of Power Circuit of APF ........................................... 45
Figure 3.15. Block Diagram of Shunt APF ............................................................. 46
Figure 3.16. Block Diagram of Series APF ............................................................ 47
Figure 3.17. Block Diagram of UPQC.................................................................... 48
Figure 3.18. Hybrid APF Topologies ..................................................................... 49
Figure 3.19. Converter Based on Classification of APFs ....................................... 50
Figure 4.1. Power Circuit Topology of the Coreless CSI-IF in The Steel Mill .... 53
Figure 4.2. Equivalent Circuit of Transformer ..................................................... 55
Figure 4.3. Equivalent Circuit of Coreless Induction Furnace ............................. 55
Figure 4.4. Coreless Induction Furnace Equivalent Circuit Referred to Primary
Side ..................................................................................................... 56
Figure 4.5. Ideal Parallel Resonant Circuit ........................................................... 56
Figure 4.6. Impedance-Frequency Curve of Ideal Parallel Resonant Circuit ....... 57
Figure 4.7. Practical Parallel Resonant Circuit ..................................................... 58
Figure 4.8. Practical Parallel Resonant Circuit Converted To Ideal Parallel
Resonant Circuit Form ....................................................................... 58
Figure 4.9. CSI of IF with Parallel Resonant Tank Circuit .................................. 64
X
Figure 4.10. Voltage and Current Waveforms of Parallel Resonant Tank Circuit
Operating Above the Resonance Frequency ...................................... 64
Figure 4.11. Operation of Load Commutated CSI .................................................. 65
Figure 4.12. Load Commutation of CSI ................................................................. 65
Figure 4.13. Circuit Diagram of 12-Pulse Rectifier ................................................ 67
Figure 4.14. Generated Harmonics Related with Operating Frequency of CSI-IF 70
Figure 4.15. Power Circuit Model of CSI-IF .......................................................... 71
Figure 4.16. Block Diagram of DC Link Controller of CSI-IF .............................. 73
Figure 4.17. Block Diagram of CSI of CSI-IF........................................................ 74
Figure 4.18. Frequency Trend of Modeled Induction Furnace According To
Operating Scenario ............................................................................. 76
Figure 4.19. Trend of Phase Difference between Voltage and Current of Resonant
Load .................................................................................................... 77
Figure 4.20. Trend of CSI Angular Operating Frequency ...................................... 77
Figure 4.21. Trend of Phase Difference between Voltage and Current of Resonant
Load during Entire Simulation ........................................................... 78
Figure 4.22. Trend of CSI Angular Operating Frequency during Entire Simulation .
............................................................................................................ 78
Figure 4.23. Phase of the Operating Frequency of CSI .......................................... 79
Figure 4.24. Thyristor Gate Pulses of CSI .............................................................. 79
Figure 4.25. Current and Voltage Waveform between Terminals of Parallel
Resonant Tank Circuit ........................................................................ 80
Figure 4.26. Current Waveform of Furnace Coil .................................................... 80
Figure 4.27. Trend of Firing Angle of 12-Pulse Rectifier ...................................... 81
Figure 4.28. Trend of DC Link Voltage of CSI-IF ................................................. 82
Figure 4.29. Trend of DC Link Current of CSI-IF ................................................. 82
Figure 4.30. Trend of DC Link Voltage of CSI-IF during Entire Simulation ........ 83
Figure 4.31. Trend of DC Link Current of CSI-IF during Entire Simulation ......... 83
Figure 4.32. Ripple on DC Link Current of CSI-IF ................................................ 84
Figure 4.33. Supply Current Waveform of CSI-IF ................................................. 84
Figure 4.34. Supply Voltage Waveform of CSI-IF................................................. 85
XI
Figure 4.35. Trend of Active and Reactive Power of CSI-IF ................................. 85
Figure 4.36. Angular Operating Frequency at the 1st Second of the Simulation .... 86
Figure 4.37. Generated Harmonics When CSI-IF Operates at 175 Hz ................... 87
Figure 4.38. Harmonic Spectrum of CSI-IF Current when CSI-IF operates at 175
Hz ....................................................................................................... 88
Figure 4.39. Angular Operating Frequency at the 5th
Second of the Simulation .... 89
Figure 4.40. Generated Harmonics When CSI-IF Operates at 235 Hz ................... 90
Figure 4.41. Harmonic Spectrum of CSI-IF Current when CSI-IF operates at 235
Hz ....................................................................................................... 91
Figure 4.42. Harmonic Spectrum Obtained by the PQ Measurements in the Steel
Mill ..................................................................................................... 93
Figure 4.43. Interharmonic Spectrum Obtained by the PQ Measurements in the
Steel Mill ............................................................................................ 93
Figure 5.1. Single Tuned Passive Filter ................................................................ 96
Figure 5.2. Impedance Frequency Curve of Single Tuned Filter ......................... 96
Figure 5.3. Impedance-Frequency Curve of 5th
, 7th
, 11th
and 13th
Harmonic Single
Tuned Filters ....................................................................................... 98
Figure 5.4. Single Line Diagram and Equivalent Circuit of CSI-IF with Single
Tuned Passive Filter ........................................................................... 99
Figure 5.5. Impedance-Frequency Curve of Single Tuned Filter Designed for CSI-
IF....................................................................................................... 100
Figure 5.6. Power Circuit Model of Single Tuned Filter .................................... 101
Figure 5.7. CSI-IF Current Waveform in Single Tuned Filter Simulation ......... 102
Figure 5.8. Source Current Waveform in Single Tuned Filter Simulation ......... 102
Figure 5.9. Single Tuned Filter Current Waveform in Single Tuned Filter
Simulation......................................................................................... 103
Figure 5.10. Reactive Powers Drawn From source, Drawn By CSI-IF and Drawn
by Single Tuned Filter in Single Tuned Filter Simulation ............... 103
Figure 5.11. Harmonic Spectrum of Lower Order Harmonics of CSI-IF Current
and Source Current in Single Tuned Filter Simulation .................... 105
XII
Figure 5.12. Harmonic Spectrum of Higher Order Harmonics of CSI-IF Current
and Source Current in Single Tuned Filter Simulation .................... 106
Figure 5.13. Power Circuit Topology of C-Type Filter ........................................ 107
Figure 5.14. Single Line Diagram and Equivalent Circuit of CSI-IF with C-Type
Filter ................................................................................................. 109
Figure 5.15. Impedance-Frequency Curve of C-Type Filter Designed for CSI-IF ....
.......................................................................................................... 110
Figure 5.16. Impedance-Frequency Curve of C-Type Filter with Different Quality
Factor ................................................................................................ 111
Figure 5.17. Impedance-Frequency Curve of C-Type Filter with Different Reactive
Power Ratings ................................................................................... 112
Figure 5.18. Power Circuit Model of C-Type Filter ............................................. 113
Figure 5.19. CSI-IF Current Waveform in C-Type Filter Simulation .................. 114
Figure 5.20. Source Current Waveform in C-Type Filter Simulation .................. 114
Figure 5.21. C-Type Filter Current Waveform in C-Type Filter Simulation ....... 115
Figure 5.22. Reactive Powers Drawn From source, Drawn By CSI-IF and Drawn
by C-Type Filter in C-Type Filter Simulation .................................. 115
Figure 5.23. Harmonic Spectrum of Lower Order Harmonics of CSI-IF Current
and Source Current in C-Type Filter Simulation ............................. 117
Figure 5.24. Harmonic Spectrum of Higher Order Harmonics of CSI-IF Current
and Source Current in C-Type Filter Simulation ............................. 118
Figure 5.25. Broad Band Passive Filter Topologies ............................................. 119
Figure 5.26. Single Line Diagram and Equivalent Circuit of CSI-IF with LLCL
Type Broad Band Filter .................................................................... 123
Figure 5.27. Impedance-Frequency Curve of LLCL Type Broad-Band Filter
Designed for CSI-IF ......................................................................... 124
Figure 5.28. Filtering Characteristic of LLCL Type Broad-Band Filter Designed
for CSI-IF ......................................................................................... 125
Figure 5.29. Power Circuit Model of LLCL Type Broad-Band Filter.................. 125
Figure 5.30. CSI-IF Current Waveform in LLCL-Type BBF Filter Simulation .. 126
Figure 5.31. Source Current Waveform in LLCL-Type BBF Filter Simulation .. 127
XIII
Figure 5.32. Current Waveform of Shunt Branch of LLCL Type Filter in LLCL-
Type BBF Filter Simulation ............................................................. 127
Figure 5.33. Source Voltage Waveform in LLCL-Type BBF Filter Simulation .. 128
Figure 5.34. CSI-IF Voltage Waveform in LLCL-Type BBF Filter Simulation .. 128
Figure 5.35. Reactive Powers Drawn From source and Drawn By CSI-IF in LLCL
Type Filter Simulation ...................................................................... 129
Figure 5.36. Harmonic Spectrum of Lower Order Harmonics of CSI-IF Current
and Source Current in LLCL Type Broad-Band Passive Filter ....... 131
Figure 5.37. Harmonic Spectrum of Higher Order Harmonics of CSI-IF Current
and Source Current in LLCL Type Broad-Band Passive Filter
Simulation......................................................................................... 132
Figure 5.38. Harmonic Spectrum of CSI-IF Voltage LLCL Type Broad-Band
Passive Filter Simulation .................................................................. 133
Figure 5.39. Proposed HAPF System for CSI-IF ................................................. 135
Figure 5.40. Power Circuit Configuration of APF Modules ................................. 136
Figure 5.41. Control Method of Shunt APF Modules in Proposed HAPF System137
Figure 5.42. Harmonic Extraction Method in Shunt APF Modules ..................... 138
Figure 5.43. Structure of EPLL............................................................................. 139
Figure 5.44. Distorted Input signal, Extracted Fundamnetal Signal and Extracted
Harmonics of EPLL .......................................................................... 140
Figure 5.45. DC Link Voltage Control of Shunt APF Modules ........................... 142
Figure 5.46. Current Control of Shunt APF Modules ........................................... 143
Figure 5.47. Power Circuit Model of Proposed HAPF System ............................ 144
Figure 5.48. CSI-IF Current Waveform in Proposed HAPF Simulation .............. 146
Figure 5.49. CSI-IF and STF Current Waveform in Proposed HAPF Simulation .....
.......................................................................................................... 146
Figure 5.50. Source Current Waveform in Proposed HAPF Simulation .............. 147
Figure 5.51. STF Currents in Proposed HAPF Simulation ................................... 147
Figure 5.52. High Voltage Side APFs Currents in Proposed HAPF Simulation .. 148
Figure 5.53. Harmonic Spectrum of Lower Order Harmonics of CSI-IF Current
and Source Current in Proposed HAPF Simulation ......................... 149
XIV
Figure 5.54. Harmonic Spectrum of Higher Order Harmonics of CSI-IF Current
and Source Current in Proposed HAPF Simulation ......................... 150
Figure 5.55. CSI-IF Voltage Waveform in Proposed HAPF Simulation ............. 151
Figure 5.56. Reactive Powers Drawn From source, Drawn By CSI-IF and Drawn
By Single Tuned Filter in HAPF Simulation ................................... 152
Figure 5.57. Injected Current Waveform of APF1 in Proposed HAPF Simulation ...
.......................................................................................................... 153
Figure 5.58. Injected Current Waveform of APF2 in Proposed HAPF Simulation ...
.......................................................................................................... 154
Figure 5.59. DC Link Voltage Waveform of APF1 in Proposed HAPF Simulation ..
.......................................................................................................... 155
Figure 5.60. DC Link Voltage Waveform of APF2 in Proposed HAPF Simulation ..
.......................................................................................................... 155
Figure 5.61. Reference Current and Injected Current Waveforms of APF1 in
Proposed HAPF Simulation ............................................................. 156
Figure 5.62. Reference Current and Injected Current Waveforms of APF2 in
Proposed HAPF Simulation ............................................................. 156
Figure 5.63. Proposed SHAPF System for CSI-IF ............................................... 158
Figure 5.64. Single Line Equivalent Circuit of SHAPF ....................................... 159
Figure 5.65. Power Circuit Configuration of SHAPF Modules............................ 161
Figure 5.66. Filtering Characteristics of a Single SHAPF Module with Different
SHAPFK Values .................................................................................. 162
Figure 5.67. Filtering Characteristics of Proposed SHAPF System with Different
SHAPFK Values ................................................................................... 162
Figure 5.68. Control Method of Shunt APF Modules in Proposed SHAPF System ..
.......................................................................................................... 163
Figure 5.69. DC Link Voltage Control of SHAPF Modules ................................ 164
Figure 5.70. Voltage Control of SHAPF Modules ............................................... 165
Figure 5.71. Power Circuit Model of Proposed SHAPF System .......................... 166
Figure 5.72. CSI-IF Current Waveform in Proposed SHAPF Simulation ............ 168
Figure 5.73. Source Current Waveform in Proposed SHAPF Simulation ............ 168
XV
Figure 5.74. High Voltage Side APFs Currents in Proposed SHAPF Simulation ......
.......................................................................................................... 169
Figure 5.75. Harmonic Spectrum of Lower Order Harmonics of CSI-IF Current
and Source Current in Proposed SHAPF Simulation ....................... 171
Figure 5.76. Harmonic Spectrum of Lower Order Harmonics of CSI-IF Current
and Source Current in Proposed SHAPF Simulation ....................... 172
Figure 5.77. CSI-IF Voltage Waveform in Proposed SHAPF Simulation ........... 173
Figure 5.78. Reactive Powers Drawn From Source, Drawn By CSI-IF and Drawn
By SHAPF Modules in SHAPF Simulation ..................................... 174
Figure 5.79. Injected Current Waveform of SAPF1 in Proposed SHAPF Simulation
.......................................................................................................... 175
Figure 5.80. Injected Current Waveform of SAPF2 in Proposed SHAPF Simulation
.......................................................................................................... 175
Figure 5.81. DC Link Voltage Waveform of SHAPF1 in Proposed SHAPF
Simulation......................................................................................... 176
Figure 5.82. DC Link Voltage Waveform of SHAPF2 in Proposed SHAPF
Simulation......................................................................................... 176
Figure 5.83. Reference Voltages and Triangular Wave Waveforms of SHAPF1
Controller in Proposed SHAPF Simulation ...................................... 177
Figure 5.84. Reference Voltages and Triangular Wave Waveforms of SHAPF2
Controller in Proposed SHAPF Simulation ...................................... 177
XVI
LIST OF SYMBOLS
fA : Amplitude of fundamental component
C : Capacitance
BBFC : Capacitance of LC type broad band passive filter capacitor
,BBF Y sC : Capacitance of wye connected capacitors of LLCL type broad
band passive filter
,BBF sC : Capacitance of delta connected capacitors of LLCL type broad
band passive filter
,1CtypeC : Capacitance of auxiliary capacitor of C-type passive filter
,2CtypeC : Capacitance of main capacitor of C-type passive filter
DCC : DC link capacitance
,dc APFC : DC link capacitance of active power filter
,dc SHAPFC : DC link capacitance of shunt hybrid active power filter
fC : Induction furnace resonant tank circuit capacitance
PC : Capacitance of parallel resonant load
SHAPFC : Capacitance of series connected capacitor of shunt hybrid active
power filter
,STF YC : Capacitance of wye connected capacitors of single tuned passive
filter
,STFC : Capacitance of delta connected capacitors of single tuned passive
filter
f : Frequency
if : Generated harmonics and interharmonics frequency
pf : Parallel resonance frequency
,p BBFf : Parallel resonance tuning frequency of LLCL type broad band
passive filter
XVII
PFf : Tuning frequency of passive filter
rf : Resonance frequency
sf : Series resonance frequency
,s BBFf : Series resonance tuning frequency of LLCL type broad band
passive filter
STFf : Tuning frequency of single tuned passive filter
Ctypef : Tuning frequency of C-type passive filter
mf : Maximum frequency of practical parallel resonant load
of : Operating frequency of the inverter
uf : Unity power factor frequency of practical parallel resonant load
1f : Fundamental supply frequency
h : Order of harmonics
I : Current
( , , )a b cI : Phase a, b, c currents
( , , ),a b c APFI : Phase a, b, c currents pf active power filter
( , , )_ ,a b c capref APFI : Generated three phase current references of DC link capacitor of
active power filter
( , , ),a b c CSI IFI : Phase a, b, c currents of CSI-IF
( , , ),a b c CtypeI : Phase a, b, c currents of C-type passive filter
( , , )_ ,a b c ref APFI : Generated three phase current references of active power filter
( , , ),a b c sourceI : Phase a, b, c currents of source
( , , ),a b c hI : Phase a, b, c harmonic currents
( , , ),a b c STFI : Phase a, b, c currents of single tuned passive filter
APFI : Injected current of active power filter
PCI : Current flow from the capacitance of parallel resonant load
XVIII
,capref APFI : Generated current reference of DC link capacitor of active power
filter
CSI IFI : CSI-IF current
,CSI IF harI : Harmonic components of CSI-IF current
DCI : DC link current
,DC setI : Set value of DC link current
fI : Fundamental component of current
fur coilI : Induction furnace coil current
hI : Harmonic component of current
,h pI : Magnified current harmonic components caused by parallel
resonance
,h sI : Voltage harmonics caused by series resonance
iI : Input current signal of EPLL
loadI : Load current
,load hI : Harmonic components of load current
PLI : Current flow from the inductance of parallel resonant load
PFI : Current drawn by passive filter
PFI : Harmonic components of current drawn by passive filter
,ref APFI : Reference current of active power filter
res tankI : Resonant tank circuit current
SHAPFI : Current of shunt hybrid active power filter
sourceI : Source current
,source hI : Harmonic components of source current
AK : Peak detector gain of EPLL
APFK : Feedback gain of active power filter
IK : Low-pass filter integrator gain of EPLL
XIX
PK : Low-pass filter proportional gain of EPLL
SHAPFK : Feedback gain of shunt hybrid active power filter
L : Inductance
APFL : Inductance of smoothing inductor of active power filter
SHAPFL : Inductance of series connected inductor of shunt hybrid active
power filter
BBFL : Inductance of LC type broad band passive filter
,BBF sL : Inductance of shunt branch inductor of LLCL type broad band
passive filter
,1CtypeL : Inductance of C-type passive filter
DCL : DC link inductance
,i BBFL : Inductance of input inductor of LLCL type broad band passive
filter
LL : Inductance of practical parallel resonant load
PL : Inductance of parallel resonant load
,o BBFL : Inductance of output inductor of broad band passive filter
STFL : Inductance of single tuned passive filter
strayL : Stray Inductance
sysL : Power system inductance
coilN : Turn number of induction furnace coil
PN : Primary winding turn number of transformer
SN : Secondary winding turn number of transformer
1p
: Pulse number of the rectifier
2p
: Pulse number of the inverter
Q : Reactive power
BBFQ : Reactive power rating of broad band passive filter
XX
CtypeQ : Reactive power rating of single tuned passive filter
PFQ : Reactive power rating of passive filter
STFQ : Reactive power rating of single tuned passive filter
BBFQF : Quality factor of broad band passive filter
CtypeQF : Quality factor of C-type passive filter
PQF : Quality factor of parallel resonant load
PFQF : Quality factor of passive filter
STFQF : Quality factor of single tuned passive filter
R : Resistance
,BBF sR : Resistance of shunt branch resistor of LLCL type broad band
filter
CR : Core resistance of transformer
chR : Resistance of charge metal of induction furnace
,ch refR : Resistance of charge metal of induction furnace referred to
primary side
CtypeR : Resistance of C-type filter
fR : Equivalent induction furnace resistance
fcR : Resistance of induction furnace coil
LR : Resistance of practical parallel resonant load
LoadR : Load resistance
PR : Resistance of parallel resonant load
PrR : Resistance of primary winding of transformer
SR : Resistance of secondary winding of transformer
STFR : Resistance of single tuned filter
LoadS : Apparent Power Rating of Load
SCS : Short circuit power of power system
XXI
( , , )a b cV : Phase a, b, c voltages
( , , )_ ,a b c capref SHAPFV : Generated three phase voltage references of DC link capacitor of
shunt hybrid active power filter
( , , )_ ,a b c ref SHAPFV : Generated three phase voltage references of shunt hybrid active
power filter
( , , ),a b c sourceV : Phase a, b, c source voltages
APFV : Injected voltage of active power filter
,cap APFV : DC link capacitor voltage of active power filter
,cap SHAPFV : DC link capacitor voltage of shunt hybrid active power filter
,capref SHAPFV : Generated voltage reference of DC link capacitor of shunt hybrid
active power filter
,capset APFV : DC link capacitor voltage set value of active power filter
,capset SHAPFV : DC link capacitor voltage set value of shunt hybrid active power
filter
,cappi APFV : PI controller output signal of DC link controller of active power
filter
,cappi SHAPFV : PI controller output signal of DC link controller of shunt hybrid
active power filter
DCV : DC link voltage
fV : Fundamental component of voltage
hV : Harmonic component of voltage
,h pV : Magnified voltage harmonic components caused by parallel
resonance
,h sV : Voltage harmonics caused by series resonance
,L L rmsV : Line to line RMS value of power system voltage
mV : Peak value of supply voltage rectifier
XXII
meanV : Mean value of DC link voltage of rectifier
PV : Voltage across the terminals of parallel resonant load
res tankV : Voltage between terminals of resonant tank circuit
,ref SHAPFV : Generated reference voltage of shunt hybrid active power filter
%SCV : Short circuit voltage of transformer in percentage
SHAPFV : Shunt hybrid active power filter voltage
sourceV : Source voltage
CX : Reactance of capacitor
chX : Reactance of charge metal of induction furnace
,ch refX : Reactance of charge metal of induction furnace referred to
primary side
fX : Equivalent induction furnace reactance
fcX : Reactance of induction furnace coil
gapX : Reactance of insulation material and gap between induction
furnace coil and inside of induction furnace crucible
,gap refX : Referred reactance of insulation material and gap between
induction furnace coil and inside of induction furnace crucible
LLX : Reactance of practical parallel resonant load inductance
PLX : Reactance of parallel resonant load inductance
PCX : Reactance of parallel resonant load capacitance
LoadX : Load reactance
MX : Magnetizing reactance of transformer
PrX : Leakage reactance of primary winding of transformer
SX : Leakage reactance of secondary winding of transformer
sourceX : Reactance of source
TRX : Total leakage reactance of transformer
XXIII
PY : Admittance of parallel resonant load
Z : Impedance
EqZ : Equivalent impedance
Filter SystemZ : Equivalent impedance of passive filter and system impendance
PZ : Impedance of parallel resonant load
PmZ : Maximum impedance of parallel resonant load
PFZ : Impedance of passive filter
sysZ : Impedance of power system
: firing angle of rectifier
: Phase angle between voltage and current of parallel resonant tank
circuit of induction furnace
error : Phase angle error between voltage and current of parallel resonant
tank circuit of induction furnace
set : Phase angle set value between voltage and current of parallel
resonant tank circuit of induction furnace
a : Phase of phase A voltage
CSI : Operating phase of current source inverter of induction furnace
f : Phase of fundamental component
_a sourceV : Phase of phase a voltage of source
CSI : Angular operating frequency of current source inverter of
induction furnace
,CSI i : Initial angular operating frequency of current source inverter of
induction furnace
XXIV
LIST OF ABBREVATIONS
AC : Alternating Current
APF : Active Power Filter
ASD : Adjustable Speed Drive
BBF : Broad-Band Filter
CSI : Current Source Inverter
CSI-APF : Current Source Inverter Based Active Power Filter
CSI-IF : Current Source Inverter Based Induction Furnace
DC : Direct Current
DFT : Discrete Fourier Transform
EAF : Electric Arc Furnace
EHV : Extra High Voltage
FFT : Fast Fourier Transform
GTO : Gate Turn off Thyristor
HAPF : Hybrid Active Power Filter
HV : High Voltage
HVDC : High Voltage Direct Current
IEC : International Electrotechnical Commission
IEEE : Institute of Electrical and Electronics Engineers
IF : Induction Furnace
IHD : Individual Harmonic Distortion
IGBT : Insulated Gate Bipolar Transistor
IGCT : Integrated Gate Commutated Thyristor
GTO : Gate Turn-off Thyristor
LV : Low Voltage
MOSFET : Metal Oxide Semiconductor Field Effect Transistor
MV : Medium Voltage
PI : Proportional Integral
PLL : Phase Lock Loop
PQ : Power Quality
XXV
PSCAD/EMTDC : Power System Computer Aided Design / Electromagnetic
Transient DC Program
PU : Per Unit
PWM : Pulse Width Modulation
RDFT : Recursive Discrete Fourier Transform
RMS : Root Mean Square
SCR : Silicon Controlled Rectifier
SHAPF : Shunt Hybrid Active Power Filter
SMPS : Switched Mode Power Supply
SMR : Switched Mode Regulator
SRF : Synchronous Reference Frame
STF : Single Tuned Filter
TDD : Total Demand Distortion
THD : Total Harmonic Distortion
UPQC : Unified Power Quality Conditioner
UPS : Uninterruptible Power Supply
VSI : Voltage Source Inverter
VSI-APF : Voltage Source Inverter Based Active Power Filter
VSI-IF : Voltage Source Inverter Based-Induction Furnace
1. INTRODUCTION Adnan TAN
1
1. INTRODUCTION
1.1. Background and Research Motivation
Induction furnaces (IFs) are used in many of mill and foundry processes such
as; heating, melting, hardening, tempering and welding. With the development of
power electronics technology, the capacity and the efficiency of IFs get higher and
become an alternative technology to electric arc furnaces (EAFs) in scrap steel
melting process. Although EAFs have major advantages in high capacity production
and melting speed, IFs are preferred in low production capacity mills because of the
low installation and operating cost and high heating efficiency.
The power supplies of IFs are formed from four main parts; rectifier, dc link,
inverter and resonance tank as shown in Figure 1.1. According to the inverter and the
resonance tank of IFs, they are divided into two type of IFs; voltage source inverter
based induction furnace (VSI-IF) which uses a series resonant circuit and current
source inverter based induction furnace (CSI-IF) which uses a parallel resonant
circuit.
3 PHASE SUPPLY
RECTIFIER DC LINK INVERTER RESONANCE TANK
Figure 1.1. General Block Diagram of Induction Furnaces
Besides the advantages of IFs in the installation and operating cost and
efficiency, IFs cause power quality problems because of the power supplies. Both
VSI-IFs and CSI-IFs generate harmonics related to pulse number of rectifier circuit
but, CSI-IFs generate specific power quality problems. Because of the current source
inverter, CSI-IFs generate time varying harmonics and interharmonics in addition to
their rectifier harmonics. In high power applications such as metal melting, current
source inverter (CSI) and parallel resonant tank circuit configuration are preferred in
1. INTRODUCTION Adnan TAN
2
IFs because of the advantages of parallel resonant circuit in high power applications.
High power CSI-IFs are commonly connected to distribution network through a
power transformer. Commonly, the power ratings of CSI-IFs are relatively large
compared to the distribution network so, the time varying harmonics and
interharmonics generated by CSI-IFs cause other power quality problems such as;
voltage harmonics, flicker and resonance problems in distribution networks.
To overcome harmonics, passive filters and APFs have been proposed in
literature. Passive filters are the economical way of reducing the harmonics and
meeting the reactive power requirements of nonlinear loads but, they have limited
performance on suppressing harmonics and cause resonance problems with system
impedance. The drawbacks of passive filters have led to the development of APFs.
Since 1970s, various type APF configurations have been proposed in literature to
achieve harmonic filtering, damping, isolation and termination, reactive-power
control for power factor correction and voltage regulation, load balancing, voltage-
flicker reduction, and/or their combinations (Akagi, 2005).
In recent years, the usage of high power coreless melting CSI-IFs become
widespread in steel mills. In order to prevent the effects of nonlinear load
characteristics of these CSI-IFs on power systems, appropriate compensation systems
must be applied to the CSI-IFs.
1.2. Scope of Thesis
The developments in power electronics technology perform the use of high
power converters in many of industrial applications. Besides the advantages in
efficient electric energy utilizing of these power electronics based converters, they
show nonlinear load characteristic which causes various power quality problems in
electric power systems. Induction steel scrap melting furnaces is one of the examples
of industrial applications which use high power converters in power supplies.
Induction melting is a well-known process and it has been used in many of mills
since the beginning of 1900s. Early induction melting furnaces used transformers and
motor-generator sets in the power supplies. These type power supplies cannot
1. INTRODUCTION Adnan TAN
3
completely meet the requirements of furnaces and cause inefficient melting operation
especially in high power melting applications. With the developments in solid state
technology, high power converters are developed and used in the power supplies of
induction melting furnaces. These power electronics based power converters provide
efficient and controllable melting operation. When these advantages of induction
power supplies are combined with the advantages of induction melting process in
high production quality, low environmental contamination and, low initial and
operating costs, induction melting furnaces become popular in metal melting process.
Today, the capacity of induction melting furnaces is reached to 50 tons and power of
these furnaces exceeds 25 MVA. With these specifications, induction melting
furnaces become a rival to electric arc furnaces in steel scrap melting process.
The 3-D drawing of a high power induction melting furnace is shown in
Figure 1.2. As shown in Figure 1.2, the power supply of high power induction
furnace is formed from transformer, rectifier, DC link, inverter and resonance tank
circuit which is formed from capacitor banks and furnace coil in the crucible. In the
power supplies of high power induction melting furnaces, the combination of 12 or
higher pulse rectifiers, current source inverters and parallel resonant tank circuits
which are formed from parallel connected capacitor bank with furnace coil are
preferred. The reason of preferring the 12-pulse or higher pulse rectifier is to
decrease the harmonic content of current drawn by the furnace. The cause of
preferring current source inverter with parallel resonance tank circuit is advantages
of parallel resonant tank circuit. When the parallel resonant tank circuit is operated at
the resonance frequency by the current source inverter, the current source inverter
supplies only the small percentage of excessive coil current of parallel resonant
circuit which is necessary for creating eddy currents in the workpieces. The coil
current is produced by the capacitors of resonant circuit in operation under resonance
frequencies. Besides the advantages of current source inverter based power supplies
of induction melting furnaces, these power supplies create unusual power quality
problems such as time varying harmonics and interharmonics. Moreover, these time
varying harmonics and interharmonics cause resonance problems and other power
1. INTRODUCTION Adnan TAN
4
quality problems such as voltage fluctuations and flicker in weak transmission and
distribution networks.
FURNACE
CRUCIBLE
SCRAP
METAL
POWER
CONVERTERRECTIFIER
DC LINK
INVERTER
TRANSFORMER
RESONANT TANK
CIRCUIT
CAPACITORS
WATER
COOLING
SYSTEM
Figure 1.2. 3-D Drawing of a High Power Induction Melting Furnace
(Otto-Junker GmhB)
These power quality problems of CSI-IF are investigated in a steel mill which
is located in Payas Industrial Zone in Turkey. This steel mill has two 10 MVA
coreless steel melting CSI-IFs and these furnaces are directly connected to 31.5kV
busbar which also supplies other industrial plants and domestic loads in Payas Town.
After the commissioning of CSI-IFs in the steel mill, power quality (PQ) problems
such as; voltage fluctuations, flicker and resonance problems began to appear in
power system which the steel mill is connected. These PQ problems caused damage
in reactive power compensation systems, microprocessor based controllers and
adjustable speed drives (ASD) of some other industrial plants which were supplied
from the same busbar with the steel mill. Moreover, many of home appliances
supplied from the line of domestic loads in Payas Town suffered from these PQ
problems. In order to find the source of these problems, power quality measurements
are performed at the substation which supplies the steel mill, other industrial plants
1. INTRODUCTION Adnan TAN
5
and domestic loads. When the power quality measurements are investigated, it is
observed that the CSI-IFs in the steel mill draw time varying harmonics and
interharmonics in wide frequency spectrum. After the detailed investigations of
power quality measurements, power supply of CSI-IFs and installed passive filtering
system at 31.5kV for CSI-IF which is formed from 5th
,7th
,11th
and 13th
harmonic
filters, it is seen that time varying harmonics and interharmonics of CSI-IFs cause
parallel resonance between the installed passive filtering system and the system
impedance. Because of the improper passive filtering compensation system, high
voltage distortion occurs in the 31.5kV busbar. Moreover, these time varying
harmonics and interharmonics of CSI-IF causes resonance problems with reactive
power compensation systems of other industrial plants and, voltage fluctuations and
flicker problems because of the weak power system. Because of these, design and
implementation of an appropriate compensation system is necessary for CSI-IFs in
order to prevent these PQ problems of CSI-IFs.
In this thesis, a CSI-IF is modeled in PSCAD/EMTDC simulation program by
using the power circuit parameters of CSI-IFs in the steel mill and knowledge
obtained during the power quality measurements of CSI-IFs. In the simulation model
of the CSI-IF, the PQ problems of CSI-IF are investigated and the simulation results
are compared with power quality measurements of CSI-IFs in the steel mill. In order
to find solutions to the PQ problems of CSI-IF, passive and active filtering methods
are modeled and investigated in PSCAD/EMTDC. In the passive filtering methods,
the characteristics of single tuned filter, C-type filter and LLCL type broadband filter
are investigated and performances of these filters on compensating PQ problems of
CSI-IF are demonstrated in PSCAD/EMTDC. In the active filtering methods, HAPF
which use shunt APF - shunt passive filter topology and APF in series with shunt
passive filters topology are proposed for the PQ problems of CSI-IF and
performances of these HAPFs on compensating PQ problems of CSI-IF are
demonstrated in PSCAD/EMTDC.
1. INTRODUCTION Adnan TAN
6
1.3. Outline of Thesis
After the introduction section, outline of the thesis is organized as follows;
The second chapter introduces general information about induction heating.
In this chapter, history, basic principles and applications of induction heating are
presented and general power supply topologies of induction furnaces are described.
In the third chapter, the general definitions about harmonics and
interharmonics are presented and their impacts on power systems are discussed. In
addition, harmonic and interharmonic mitigation techniques and extraction methods
are introduced.
In the fourth chapter, firstly the operating principles of CSI-IF are
investigated. Secondly, power quality problems of CSI-IF are presented and finally
the model of CSI-IF is introduced and the power quality problems of CSI-IF are
demonstrated by simulation results.
The fifth chapter presents probable passive and active filter based
compensation systems for the power quality problems of CSI-IF. In this chapter
firstly passive filtering methods are investigated and their compensation
performances on the PQ problems of CSI-IF are demonstrated in simulation results.
Afterwards, HAPF systems are proposed for the power quality problems of CSI-IF.
Their power circuit configurations and control methods are presented in detail.
Finally, the compensation performances of proposed HAPF systems on the PQ
problems of CSI-IF is demonstrated by the simulation results.
In the sixth chapter, conclusions of the thesis are given and future work
studies are discussed.
Finally all references used in this thesis study are presented.
2. INDUCTION HEATING Adnan TAN
7
2. INDUCTION HEATING
Induction heating has very important roles in many of mill and foundry
applications. The reason of popularity of induction heating is to have advanced
control in heating operation and fast heating feature in many of metalworking
processes. These features of induction heating can be achieved by application
specific coil design and applying necessary power and frequency to these specific
coils. Before several decades from today, the precision control of electric power
could not be implemented and capabilities of induction furnaces were limited.
However today, induction furnaces work under wide power and frequency range by
the help of static power converter based power supplies.
2.1. History of Induction Heating
In the beginning of 1900s, induction furnaces were firstly used in the metal
melting applications. The first induction furnace was formed from cylindrical
crucible and spark gap power supply. However, extensive application of first
induction furnaces was limited by the power attainable from spark-gap generators
(Zinn et al., 2002). In the beginning of 1920s, the motor-generator type power
supplies were invented for induction furnaces. After the development of motor-
generator based power supplies of induction furnaces, the induction furnaces were
widely used in metal melting and alloy production applications. At the motor-
generator type furnaces, a motor is connected to utility and rotates a generator which
is connected to the same shaft with motor. The generator output voltage frequency is
related to motor rotation speed and pole number of generator. When a constant
furnace frequency is employed, as is the case with motor-generators, the inductance
of the secondary circuit varies throughout the melting period, resulting in wide
changes of power factor. To prevent excessive current being drawn from the motor-
generator, switched capacitor banks are placed in parallel with the furnace coil
(Sieveking, 1940). The drawback of motor-generator type power supply is that the
desired operating conditions could not be reached by switching capacitors so the
2. INDUCTION HEATING Adnan TAN
8
efficient operating of these furnaces could not be obtained. After induction furnaces
proved themselves in metal melting processes, the attention of scientists and
engineers turned in another direction. Since the depth of the current penetration in a
given metal varies with the material electric resistivity, magnetic permeability, and
frequency, it is possible to heat specific areas of a piece of metal without heating
others. The first use of this knowledge shows itself in hardening applications of
steels (Rudnev et al., 2003).
After 1970s, the development of solid state power devices influenced to
change the motor-generator power supplies to solid state power supplies. This
change causes major advantages in induction heating technology. Today induction
heating has very wide application area by the help of solid state technology.
2.2. Basic Principles of Induction Heating
The principles of induction heating can be explained easily by the
electromagnetic theory. When the alternating voltage is applied to the coil of the
induction furnace, alternating current flows from coil. According to Ampere’s Law, a
conductor that carries a time varying current creates a time varying magnetic field so
the furnace coil produces a magnetic field at the same frequency with current passes
through coil as shown at Fig. 2(a). Moreover, a time varying magnetic field can
create an electric field with respect to Faraday’s Law. This electric field created in
the furnace coil produces eddy currents on the work pieces at shown at Fig. 2(b). As
a result, these eddy currents pieces heat up the work pieces according to Joule effect
(Rudnev et al., 2003; Zinn et al., 2002).
2. INDUCTION HEATING Adnan TAN
9
MagneticFlux
i
tEddyCurren
ii
i
(a) (b)
MagneticFlux
Figure 2.1. Principles of Induction Heating
(a) Effect of Current Carrying Conductor - Ampere's Law
(b) Effect of Magnetic Field on Metal Piece
In practice the magnetic field in the crucible and the current distribution in the
work piece are not uniform because of the several electromagnetic phenomena such
as skin effect, proximity effect and ring effect. These electromagnetic phenomena
influence directly the furnace coil design and furnace operating frequency related to
type of work pieces (Rudnev et al., 2003).
Induction heating has advantages over other type heating techniques such as
(Zinn et al.,2002; EPRI,1993);
Quick heating.
Fast start up.
Less scale loss.
High production rate.
Ease of automation and control.
Reduced floor space requirements.
Quite, safe and clean working conditions.
Low installation cost.
Low operation and maintenance requirements.
2. INDUCTION HEATING Adnan TAN
10
2.3. Applications of Induction Heating
As introduced in the history of induction heating, induction heating was
firstly used in metal melting applications. After the invention of specific area and
volume heating properties of induction heating, it was taking place in heat treatment
applications. Today, induction furnaces can work in wide power and frequency
ranges with advanced controls of power and frequency by the help of power
electronics based power supplies so induction furnaces take place in most of the mill
and foundry applications such as heating, hardening, annealing, coating, welding and
melting processes. Also induction furnaces find places in special applications in
paper industry, wood industry, wool industry, food industry, semiconductor
production. The major applications of induction furnaces are described in below
sections.
2.3.1. Heating
Induction heating is used to heat various metals to temperatures that will
allow hot or warm forming applications such as forging, rolling, extrusion and
heading. It is readily adapted to through heating of steels, aluminum alloys, and
specialty metals such as titanium and nickel-base alloys. Frequently, the workpieces
in these types of applications consist of round, square, or round-cornered square bar
stock (Zinn et al.,2002). Induction heating is also used for coating applications such
as; curing of points and vanishes, thermal spraying and galvanizing. Induction
heating has great advantage in raising the workpieces to the specified temperature
with required uniform temperature distribution. Besides the temperature uniformity,
the other advantage of induction heating is to provide the maximum production rate
at which the metal can be processed. High powers from hundreds kilowatts to several
megawatts and relatively low frequencies typically in the range of 200 Hz to 30 kHz
are most commonly used for induction heating applications (Rudnev et al., 2003).
The steel billet preheating induction furnaces are shown in Figure 2.2(a) and 2.2(b).
2. INDUCTION HEATING Adnan TAN
11
(a) (b) Figure 2.2. Steel Billet Heating Induction Furnace
(a) Short Billet Heating Induction Furnace (Rudnev, 2011)
(b) Long Billet Heating Induction Furnace (Rudnev, 2008)
2.3.2. Heat Treating
In physical metallurgy, the three main variables that are considered chemical
composition of the metal, any mechanical prior treatment and prior thermal
treatment. Any of these variables can be changed in order to produce a metal with
certain desired properties such as hardness, strength, ductility, toughness, corrosion
and wear resistance. Heat treatment deals with the effect of temperature and the rate
of heating and cooling of the metal in order to arrive at a specific microstructure and
properties (Rudnev et al., 2003). In heat treating applications, the primary advantage
of induction furnaces is the ability to control the area of material that is heat treated.
The most common heat treating applications are hardening, tempering, and
annealing.
Hardening is the most common induction heat treating operation that
improves the strength, wear resistance and fatigue properties of metals. Hardening
operation is divided into through hardening and surface hardening. The goal in
through hardening is to harden the workpiece throughout its entire cross-section. It
2. INDUCTION HEATING Adnan TAN
12
can be achieved by heating the workpiece as uniformly as possible to above the
transformation temperature and then to quench it to ambient temperature. Selection
of the correct induction heating frequency is very important to achieve uniform
“surface to core” temperature in the shortest time with the highest heating efficiency.
Through hardening may be needed for parts requiring high strength such as springs,
chain links, truck bed frames, certain fasteners, gears etc. By the help of skin effect
and some other electromagnetic phenomena, it is possible to induce power in
selected areas of the workpiece where the hardening is required. The goal in surface
hardening is to provide hardness and wear resistance on the specific outer areas of
work piece while allow the remainder of the part to be soft and ductile. Surface
hardening may be needed for parts such as gears, shafts, valves etc. The different
hardening patterns of gears which are obtained by induction hardening with different
frequencies and power is shown in Figure 2.3 and hardening operation of a gear is
shown in Figure 2.4. In Figure 2.4(a), narrow surface of gear is hardened and in
Figure 2.4(b) wide surface of gear is hardened. In some applications, tooth and holes
of gear can be separately hardened. In gap hardening of gears, special designed coils
which are coated by ceramic plates are converged with gaps between teeth of gear
and heat is applied to gaps by induction as shown in Figure 2.5. The tooth hardening
process is the same with gap hardening. This time, special design coils apply heat
treatment to each tooth (Rudnev et al., 2003; Zinn et al.,2002).
Figure 2.3. Variety of Induction Hardening Patterns Obtained Using Variations in
Frequency, Heat Time, and Coil Power (Rudnev, 2009)
2. INDUCTION HEATING Adnan TAN
13
(a) (b)
Figure 2.4. Induction Spin Hardening Process
(a) Narrow Surface Hardening Inductotherm (Rudnev et al., 2008)
(b) Wide Surface Hardening (Rudnev, 2007)
(a) (b)
Figure 2.5. Gap by Gap Hardening Operation of Gears
(a) (Rudnev et al., 2008)
(b) (Inductoheat Inc., 2011)
Tempering is often confused with annealing and sometimes referred to as
stress relieving. Tempering is a lower temperature process used to increase the
toughness and ductility of material to relieve the internal stress and eliminate the
2. INDUCTION HEATING Adnan TAN
14
brittleness caused by cold working or hardening. For example in surface hardening
only the surface layer of the workpiece is heated. The surface is raised to relatively
high temperature in a short period of time. A significant surface to core temperature
difference and the metal’s transformation phenomena upon quenching result in the
buildup of the internal residual stresses. Reheating the steel for tempering after
hardening and quenching leads to decrease or relaxation of these internal stresses. In
other words, because of tempering it is possible to improve the mechanical properties
of the workpiece and to reduce the stresses caused by the previous heat treatment
stage without losing too much of the hardness. For a particular application,
tempering can provide the optimal combination of hardness, strength and toughness.
(Rudnev et al., 2003; Zinn et al.,2002)
Annealing is the process of heating a metal and providing slow controlled
cooling to soften the metal. There are two basic types of annealing; full annealing
and process annealing. The purpose of full annealing is to decrease the hardness of
material, to maintain the full ductility of material and to create the material’s
homogenization and uniform structure. In full annealing, the material is allowed to
cool very slowly. It can take one day or longer. Process annealing is a short heat
treatment cycle than full annealing, that restores some of the ductility to a workpiece
allowing it to be worked further without breaking. Full annealing is generally
processed in gas fired or electric furnaces, induction furnaces are frequently used in
process annealing processes. (Rudnev et al., 2003; Zinn et al.,2002)
2.3.3. Melting
Electric furnaces have wide application area in various type metals melting
process. Electric furnaces which are used in metal melting process are induction
furnaces, electric arc furnaces and electric resistance furnaces. Electric resistance
furnaces have very narrow application area in metal melting process and they are
generally used in low temperature melting processes such as glass, plastic, etc.
Electric arc furnaces which heat/melt the metals by means of electric arc are mostly
preferred in steel production processes. Induction furnaces are commonly used in
2. INDUCTION HEATING Adnan TAN
15
melting of metals and production of high quality metal alloys. There are three type
induction furnaces; channel type induction furnace, coreless induction furnace and
vacuum induction furnace.
The channel type induction furnaces are used mainly for holding molten
metals as storage vessel for supplying process continuously and pouring of molten
metals which are melted previously other type furnaces such as electric arc furnaces
and coreless induction furnaces. If the channel type induction furnace is used as
melting furnace, pre-melted metal will be required for the start-up of furnace. As
shown in Figure 2.6, channel type induction furnace has a small channel of molten
metal passing through the magnetic core which has a coil wound around it. This
channel of molten metal act as like the secondary of a short circuited transformer
causing current to flow through the metal in the channel and heat the metal by the
Joule effect (Rudnev et al., 2003). The channel of furnace forms a continuous loop
with the molten metal in the main part of the furnace body. By convection, the hot
molten metal in the channel circulates into the main body of the charge in the furnace
envelope to be replaced by colder molten metal (Zinn et al.,2002). The channel type
induction furnaces are high efficiency furnaces and they work commonly under the
line frequency (Bakee, 2011). They are suitable for when high metal volumes are
desired, power outages are not expected and temperature uniformity is not critical in
the furnace vessel (Zinn et al.,2002). When channel type furnaces are compared to
the coreless furnaces; the power density of channel type furnaces are low, mixing
property of channel type furnace is weak, channel furnace cannot be started easily
when it is used as primary melting furnace, accurate input power does not necessarily
mean accurate metal temperature control throughout furnace vessel in the channel
type furnaces because of the poorer mixing (Zinn et al.,2002)..
2. INDUCTION HEATING Adnan TAN
16
Crucible
Refractory
Coil
Magnetic
Core
Channel
Figure 2.6. Cross - Section View of Channel Type Induction Furnace (Bakee, 2011)
The cross - section view of coreless induction furnace is shown in Figure 2.7.
The charge is melted inside a crucible formed from refractory lining. A cylindrical
water-cooled copper coil surrounds the outside of the refractory and produces a
magnetic field pulsating in the vertical direction when supplied with power. Outside
the coil, there are packets of magnetic laminations which provide return paths for the
flux, improving the power factor and reducing the risk of the flux linking with
surrounding metalwork to cause stray heating. The main use of the coreless furnace
is melting of metals and production of high quality alloys. The coreless induction
furnaces allow a wide range of different alloys to treat in the same foundry. It is
capable of taking a wide variety of charge material and heating it to the correct
temperature with correct composition with little or no contamination. Since the melt
is fluid, there will be hydrodynamic forces set up by the interaction of the fluxes and
currents which produce vigorous stirring; while this stirring takes place in all
induction melting. This allows a wide range of charge materials to be melted
2. INDUCTION HEATING Adnan TAN
17
economically with minimal loss of expensive alloying additions. The final mix is
homogeneous and the composition can be measured and changed quickly and easily
(Davies, 1990). The stirring action in a coreless induction furnace is directly
proportional to the power and inversely proportional to the square root of the applied
frequency (Rudnev et al., 2003). Coreless induction furnaces work commonly under
frequencies between 50 Hz to 5000 Hz. In some special small power applications,
they are designed to work under several tens of kHz. Today the power of coreless
induction furnaces reaches up to several tens of MWs and the molten metal capacity
exceeds 50 tons by the help of developments in power electronics technology.
Magnetic Yoke
Furnace
Coil
Refractory
Lining
Figure 2.7. Cross - Section View of Coreless Induction Furnace (Otto-Junker GmhB)
Vacuum induction furnaces are used for producing special metal alloys. The
melting process in vacuum induction furnace is carried out in a vacuum in order to
eliminate concerns about oxidation and metal purity during the melting and casting
processes (Rudnev et al., 2003).
2. INDUCTION HEATING Adnan TAN
18
2.3.4. Welding, Brazing and Soldering
Induction heating is also utilized in welding, brazing and soldering
applications. Induction welding, brazing and soldering provide serious energy
savings by the advantage of advance heat and heating area control. The most
common application of induction welding is tube or pipe making process which
involves the heating of a sheet of metal that has been formed into a tubular shape and
constrained in a such way that eddy currents in the workpiece cause the two open
ends of the sheet to be welded together producing the seam as shown in Figure 2.8.
Induction welding is usually a continuous operation. After welding, the seams are
then subsequently annealed with a seam annealing that follows the welding system in
a continuous line (Rudnev et al., 2003). Induction brazing and soldering which rely
on the local heating capability of induction heating are frequently used in joining of
metal workpieces. Induction welding, brazing and soldering applications operate
under high frequencies in the range of 10 kHz to 1000 kHz and relatively low power
when compared to other induction heating applications.
Figure 2.8. Induction Welding of Tubular Products (Zinn et al.,2002)
2. INDUCTION HEATING Adnan TAN
19
2.3.5. Other Applications
Besides the metalworking applications, induction heating is used in various
type applications. Some of these applications are listed and described below.
Adhesive Bonding: Induction heating is used in bonding metal to nonmetal
workpieces such as clutch plates and brake shoes, as it is used in joining
metal to metal workpieces. Induction heating of the metal parts to curing
temperatures can be an excellent means of achieving rapid bonding (Zinn et
al.,2002).
Semiconductor Fabrication: The growing of single crystals of germanium
and silicon often relies on induction heating. Zone refining, zone leveling,
doping, and epitaxial deposition of semiconductor materials also make use of
the induction process (Zinn et al.,2002).
Sintering: Induction heating is widely used in sintering of carbide preforms
because it can provide the necessary high temperature (2550 °C, or 4620 °F)
in a graphite retort or susceptor with atmosphere control. Other preforms of
ferrous and nonferrous metals can be sintered in a similar manner with or
without atmosphere protection (Zinn et al.,2002).
Cap Sealing: Cap sealing is a very important application in the food and
pharmaceutical industries. This technology provides a way that consumers
can be sure that the product is coming to them in exactly the same form and
purity in which it was packages at the factory. With this process, a small layer
of aluminum foil is placed on the top of a container that has been filled and
inspected. The container with the foil is passed under an induction coil, which
heats the foil to a sufficient temperature to bond it to top of container. The
contents are thus seal and virtually guaranteed safe at the point of final use
(Rudnev et al., 2003).
Food Industry: A variety of applications of induction heating is found in the
food industry. Many systems utilize susceptor that are heated by the induction
which in turn heat the food by conduction. Many induction food warmers and
induction stoves work by this principle. Induction extruders are used to
2. INDUCTION HEATING Adnan TAN
20
produce many types of grain transformation and confectionery products.
Large cauldrons are used for cooking caramel and other similar products and
there are also fluid heating systems used in the production of milk. One of the
final application in the food industry is the heating of rollers used to make
thin products such as pizza dough and cookies (Rudnev et al., 2003).
Papermaking: In the papermaking industry the primary application is in the
heating of calendar rolls to accurately control the thickness and quality of the
paper produced. A variety of individual coils spaced along the length of the
calendar roll. The roll temperature and paper quality are continually
monitored and the power levels are adjusted accordingly to provide the
desired temperature at each point along the length of the roll (Rudnev et al.,
2003).
Wool and Wood Processing: It is possible to utilize induction heating in
industries that require the drying of materials as they pass along a production
line or batches offline. The induction coil is used to heat a metal plate, which
in turn may contact the material and heat it by conduction and/or convection
(Rudnev et al., 2003).
Chemical Industry: In the chemical industry, induction heating is used to
heat various types of reactors and distillation equipment, which is used in the
production of the pharmaceutical products. In most industrial systems, the
heat that must be transferred to water in an induction system is an undesirable
byproduct of the heating process. In the chemical and food industry it may
itself be the desired end product. Some of the benefits of using induction as
opposed to open flame heating are ease of control, safety and efficiency
(Rudnev et al., 2003).
2.4. Power Supplies of Induction Furnaces
As mentioned in previous section, induction furnaces have very wide
application area. The effective power and frequency control of IFs in heating process
2. INDUCTION HEATING Adnan TAN
21
plays important role in finding such a wide application area. The advanced control
capability of IFs is achieved by the help of solid state based power supplies.
The induction furnaces can be classified into three groups according to
operating frequencies; low frequency furnaces, medium frequency furnaces and high
frequency furnaces. Low frequency IFs generally operate under constant line
frequencies. Medium frequency IFs operate frequency range from 100 Hz to several
tens of kHz and high frequency IFs operate frequency range between several tens of
kHz and several MHz. The power - frequency diagram of induction heating
applications is shown in Figure 2.9. Low frequency IFs are generally used in high
power applications such as melting operations. The power supply of low frequency
induction furnace is formed from a transformer, a furnace coil and compensation
capacitors. The power control of these type furnaces is achieved by the changing the
secondary voltage of transformer by tap changers. The medium and high frequency
IFs use power electronics based power supplies. These power electronic based power
supplies are frequency changers that convert the available utility line frequency
power to the desired single phase power at the frequency required by the induction
heating process (Loveless, 1995). These power supplies are commonly formed from
AC to DC converters which are named as rectifiers and DC to AC converters which
are named as inverters. Many different power supply topologies formed from the
different type rectifier and inverter circuits are used to meet the heating requirements
of a nearly endless variety of induction heating applications (Loveless, 1995).
The rectifier section of induction heating power supply is specified according
to the fixed or variable voltage requirements of inverter section. Generally,
uncontrolled rectifier, fully controlled rectifier and uncontrolled rectifier with
switched mode regulator topologies are used to supply DC power to inverters in
induction heating power supplies available on the market.
The three phase uncontrolled rectifier shown in Figure 2.10 is formed from
diodes. It produces fixed output voltage relative to the input voltage, so the power
control of induction heating must be achieved by the inverter circuit.
2. INDUCTION HEATING Adnan TAN
22
1000 MW
100 MW
10 MW
1 MW
100 KW
10 KW
Po
we
r
100 Hz 1 KHz 10 KHz 100 KHz 1 MHz 10 MHz
Frequency
MELTING
HEATING
HEAT TREATMENT
WELDING,BRAZING,SOLDERING
SPECIAL APPLICATIONS
SUPPLY
FREQUENCY
SYSTEM
SOLID STATE
POWER
SUPPLIES
VACUUM TUBE
BASED
SYSTEMS
Figure 2.9. Power - Frequency Diagram of Induction Heating Applications
3 Phase
Supply
Voltage
-
+
Constant
DC Output
Voltage
Figure 2.10. Three Phase Uncontrolled Rectifier
When the variable DC output voltage is necessary, the fully controlled
rectifier or the uncontrolled rectifier with switched mode regulator is used. The three
phase fully controlled rectifier is formed from silicon controlled rectifiers (SCRs) as
shown in Figure 2.11. It produces a variable DC output voltage by firing SCRs at
appropriate angles so the power delivered by inverter can be adjusted.
2. INDUCTION HEATING Adnan TAN
23
-
+
Variable
DC Output
Voltage
3 Phase
Supply
Voltage
Figure 2.11. Three Phase Fully Controlled Rectifier
In the uncontrolled rectifier with switched mode regulator topology, switched
mode regulator is connected to the output of uncontrolled rectifier as shown in Figure
2.11. Thanks to the switched mode regulator (SMR), the fixed output DC voltage
produced by uncontrolled rectifier can be converted to the variable DC voltage and
the power supplied to the inverter can be controlled as fully controlled rectifier. This
topology is commonly suitable for low power applications.
-
+
Variable
DC Output
Voltage
Switched
Mode
Regulator
3 Phase
Supply
Voltage
Figure 2.12. Three Phase Uncontrolled Rectifier with SMR
In high power applications above the megawatts, the rectifier section of
induction heating power supply becomes a thread for the utility because of harmonic
phenomenon. Due to the high harmonic content of six pulse rectifiers, the twelve
pulse or higher pulse rectifiers are preferred in high power induction heating power
supplies.
2. INDUCTION HEATING Adnan TAN
24
Inverters used in induction heating power supplies on the market can be
generally divided into VSI and CSI according to behavior of the load of inverter.
Basically, the load of an induction heating generator is an inductor in which there is a
workpiece to be heated. A direct feed of the heating coil would result in apparent to
real power ratio too high; therefore compensation of the heating coil is required.
Compensation of the power factor is carried out by a capacitor designed so that this
factor will be close to the unity at the working frequency. The compensation
capacitor can be placed in series or in parallel with the inductor. In the series
connection of coil and capacitor, the load acts like a current source and therefore it
has to be fed by voltage source (VSI). In the parallel connection of coil and
capacitor, when the load is a parallel resonant circuit, it will react like a voltage
source and therefore it has to be fed by a current source (CSI) (Dede et al., 1991). In
the both of VSI and CSI topologies, the single phase half bridge inverters and single
phase full bridge (H - Bridge) inverters can be used but full bridge inverters are more
commonly used than half bridge inverters in induction heating power supplies. Half
bridge inverters can be preferred to decrease the costs in low power applications.
Although the frequency and power are the significant parameters in induction
heating applications, these parameters are also very important in the design of
induction heating power supplies because the power components must be rated to
operate at the specified power and frequency. Especially, solid state power devices
used in VSIs and CSIs show variety according to operating frequency and power.
The operating power – frequency of solid state devices used in inverters of induction
heating power supplies are shown in Figure 2.13. In high power and up to 10 kHz
frequency induction heating applications, thyristor group of solid state devices can be
used in the inverters. Generally, SCRs are preferred in most of induction heating
power supplies but in some of the studies in literature gate turn - off thyristors
(GTOs) and newly integrated gate commutated thyristors (IGCTs) are used (Mertens
et al., 1991; Weber et al., 2002). Insulated gate bipolar transistors (IGBTs) are
preferred in medium power and both low and medium frequency induction heating
applications. In low power and high frequency induction applications, Metal Oxide
2. INDUCTION HEATING Adnan TAN
25
Semiconductor Field Effect Transistors (MOSFETs) are used. In the overlapped
areas shown in Figure 2.13, either type of solid state devices can be used effectively.
100 MW
10 MW
1 MW
100 KW
10 KW
Po
we
r
100 Hz 1 KHz 10 KHz 100 KHz 1 MHz 10 MHz
Frequency
IGCT
GTO
IGBT
MOSFET
SCR
Figure 2.13. Power-Frequency Diagram of Solid State Devices Used in Inverters of
Induction Heating Power Supplies
Single phase full bridge VSIs are distinguished by the use of a filter capacitor
at the input of the inverter and a series connected output circuit as shown in
Figure 2.14 (Rudnev et al., 2003). When driving a series resonant load by inverter
there will always be a phase shift between output voltage and current except
resonance frequency ideally. In the case of a series load it results that in some time
intervals, the current will flow from the load to the power source. This implies that in
an inverter with series resonant load, the switches must be bidirectional in current
and unidirectional in voltage (Dede et al., 1991). Because of this, anti-parallel diodes
are connected to the terminals of switches as shown in Figure 2.14. There are two
methods for the heating power control of VSI with series connected resonant load.
The first method is the changing of switching frequency of VSI below or above the
resonance frequency of load. When the inverter switching frequency is set to the
resonant frequency of load, the impedance of resonant load get lower value and
2. INDUCTION HEATING Adnan TAN
26
seems like resistance so the output power factor becomes unity and maximum power
is transferred to the load. By changing the switching frequency of inverter below or
above the resonance frequency of load, the impedance of series resonant load can be
increased as shown in Figure 2.14 so the power delivered to induction heating coil
can be decreased. In this method power control is achieved by inverter so it is
sufficient to use rectifier which produce fixed DC voltage. In the second method, the
switching frequency of inverter is set to resonant frequency of load. By using
variable DC voltage output rectifier, the power supplied to the VSI can be changed
because the VSI is continuously operating under resonant frequency and the
maximum power is transmitted to the load. When SCRs are used as solid state switch
at the VSI in high power applications, inverter must operate below the resonant
frequency of the load because of the commutation of inverter. The first method is
commonly used in induction heating power supplies available on the market because
only controlling the inverter heating power control can be achieved. In VSI, solid
state switches conduct the whole load current so if any short circuit condition is
occurred in the heating coil, solid state devices can be damaged.
+
-
DC
Furnace
Coil
Z
frf
Resonant Tank
Circuit
Figure 2.14. VSI with Series Resonance Load
Another load type used in VSI is series resonant circuit connected to parallel
resonant tank circuit as shown in Figure 2.15. The values of the series inductor and
capacitor are selected to be resonant above the operating or firing frequency of the
inverter with an impedance at this firing frequency that will allow sufficient current
to flow from the bridge to permit full power operation. A very important feature of
2. INDUCTION HEATING Adnan TAN
27
this style of the inverter is that the internal series circuit isolates the bridge from the
load. This protects the inverter from load faults caused by shorting or arcing and
from badly tuned loads. A second feature of this load configuration is that VSI is
capable of developing full power into the parallel resonant tank circuit tuned to either
the fundamental resonant frequency or third harmonic frequency by tuning the series
resonant circuit to the third harmonic of the resonant frequency of parallel resonant
tank circuit (Rudnev et al., 2003).
+
-
DC
Furnace
Coil
Resonant Tank
Circuit
Figure 2.15. VSI with Series Resonant Circuit Connected to Parallel Resonant Tank
The CSIs are distinguished by the use of a variable voltage DC source
followed by a large inductor at the input of the inverter bridge and a parallel resonant
load circuit at the output as shown in Figure 2.16 (Rudnev et al., 2003). In CSI with
parallel resonant load, there will be some intervals in which the output voltage is
opposite to the output current. In this case, solid state switches must be bidirectional
in voltage and unidirectional in current (Dede et al., 1991). Thyristor group solid
state devices have either high forward or reverse voltage blocking capabilities but
IGBTs and MOSFET have high forward and low reverse voltage blocking
capabilities. Thus, when the IGBTs or MOSFETs are used in CSI with parallel
resonant circuit, series connected diode is used with IGBTs or MOSFETs to increase
the reverse blocking capabilities. When SCRs are used as solid state switch at the
CSI in high power applications, the starting circuit is necessary for starting CSI and
CSI must operate above the resonant frequency of the parallel resonant load because
of the commutation of inverter (Rudnev et al., 2003; Zinn et al.,2002). The heating
2. INDUCTION HEATING Adnan TAN
28
power control is managed by variable DC voltage output rectifiers in CSI based
induction heating power supplies. The only mission of CSI is applying AC power at
resonant frequency of parallel resonant load to keep the parallel resonant load at
unity power factor and transmit the maximum power to the load. The CSI is exposed
to the full furnace voltage. However, it only sees about 10% of resonant current
because the reactive component of the coil current bypasses the inverter via the
parallel tuning capacitor (Rudnev et al., 1999).
+
-
DC
Furnace
Coil
Resonant Tank
Circuit Z
frf
Figure 2.16. VSI with Parallel Resonance Load
3. HARMONICS & INTERHARMONICS Adnan TAN
29
3. HARMONICS AND INTERHARMONICS
Advances in solid state power devices allow effective utilizing of electrical
energy using power converters in many of industrial, commercial and domestic
applications. On the other hand, developments in power electronics technology
increase the usage of power converters which have non-linear characteristics in the
power systems designed for linear loads. This contradiction causes power quality
problems in power systems. Power quality problems can be defined as any power
problem manifested in voltage, current, or frequency deviations that results of in
failure or misoperation in equipment (Dugan et al., 1996).The most suffering power
quality problems of power converters and other nonlinear loads are harmonics and
interharmonics. These nonlinear loads change the sinusoidal nature of AC current
and voltage because of the voltage drop in system impedances. These distorted
current and voltage cause the flow of harmonic and interharmonic currents in the ac
power system that can cause interference with other equipment (IEEE Std. 519,
1992).
3.1. Harmonics
Harmonics are more encountered power quality problem than interharmonics
and can be defined as the spectral components at frequencies that are integer
multiples of the ac system fundamental frequency (Testa et al., 2007). The most
common harmonic current drawn nonlinear loads are all single and three phase
power converters which contains rectifiers such as DC motor drives, adjustable speed
drives (ASD), uninterruptable power supplies (UPS), switched mode power supplies
(SMPS) etc.; cycloconverters, fluorescent lighting, electrical heating furnaces,
welding machines, arc furnaces. Besides these nonlinear loads, AC generators, AC
motors and transformers also produce harmonic currents. However; besides poor
design or fault conditions of these devices, harmonic currents of them are negligible
when compared to their fundamental currents.
3. HARMONICS & INTERHARMONICS Adnan TAN
30
In order to understand the amount of harmonic distortion in non-sinusoidal
voltage or current waveforms and set the limits related with harmonic distortion,
some indices are defined in IEEE and IEC standards. These most used indices in
harmonic limits defined IEEE and IEC standards are individual harmonic distortion
(IHD), total harmonic distortion (THD) and total demand distortion (TDD).
IHD is used either voltage or current harmonics and defined as the ratio of
root mean square (rms) value of each harmonic to the rms value of the fundamental
component as given in Eq. 3.1.
hV
f
hI
f
VIHD
V
IIHD
I
(3.1)
THD is also used either voltage or current harmonics and defined as the ratio
of the root-mean-square (rms) value of the harmonic components to the rms value of
the fundamental component and expressed in percent as given in Eq. 3.2. This index
is used to measure the deviation of a periodic waveform containing harmonics from a
perfect sine wave. For a perfect sine wave at fundamental frequency, the THD is zero
(Chang et al., 1998).
2
2
2
2
.100%
.100%
h
h
V
f
h
h
I
f
V
THDV
I
THDI
(3.2)
The THD of voltage is used to define the effect of harmonics on power
system voltage (IEEE Std. 519, 1992). The voltage distortion limits in low voltage,
medium voltage and high voltage power systems are defined in IEEE Std. 519, IEC
61000-2-2, IEC 61000-2-12 and IEC 61000-3-6. When the IEEE and IEC standards
3. HARMONICS & INTERHARMONICS Adnan TAN
31
related with voltage harmonic limits are compared, it is seen that both standards
provide voltage harmonic limits but the IEEE voltage harmonic limits are constant
across all frequencies whereas the permissible voltage harmonic magnitudes decrease
with frequency in the IEC (Halpin, 2005).
Current distortion levels can be characterized by a THD value but this can
often be misleading. A small current may have a high THD but not be a significant
threat to the system. For example, many adjustable-speed drives will exhibit high
THD values for the input current when they are operating at very light loads. This is
not necessarily a significant concern because the magnitude of harmonic current is
low, even though its relative current distortion is high (Dugan et al., 1996). Because
of these, TDD is used for characterizing current distortion limits. TDD is defined as
the ratio of the rms value of the current harmonic components to the rms value of the
maximum load (demand) current fundamental component drawn from point of
common coupling (PCC) and expressed in percent as given in Eq. 3.3. PCC in the
definition of TDD is a point of metering, or any point as long as both the utility and
the consumer can either access the point for direct measurement of the harmonic
indices (IEEE Std. 519, 1992).
2
2.100%
h
h
L
I
TDDI
(3.3)
The current distortion limits are defined both in IEEE and IEC standards.
IEEE Std. 519-1992 specify current harmonic limits for low voltage (LV), medium
voltage (MV), high voltage (HV) and extra high voltage (EHV) power systems with
respect to proportion between the demand of the load and capacity of the power
system. The capacity of the utility is defined by the short circuit current at PCC, and
the size of the load is the maximum demand load current calculated by the average of
the last twelve monthly peak demand. Therefore, according to IEEE Std. 519-1992,
the load can inject harmonic current to the utility at higher percentages as the size of
the load decreases with respect to the capacity of the system (Uçak, 2010). IEC
3. HARMONICS & INTERHARMONICS Adnan TAN
32
Standards for controlling harmonic distortion levels on the power system fall into
two categories. IEC 61000-3-2 and IEC 61000-3-12 outline limits for harmonic
emissions from individual equipment. These standards apply for equipment up to 75
amps on LV systems. IEC 61000-3-6 avoids giving current harmonic limits in a
general sense, preferring that these limits be more rigorously derived based on
voltage limits and system impedance characteristics for MV, HV and EHV systems
(McGranaghan et al., 2006).
Power system infrastructure and linear loads in the power systems can be
represented and modeled with resistors, inductors and capacitors. Basically; motors,
transformers, short transmission lines and system impedances can be represented as
series connection of resistors and inductors; and pure reactive power factor
compensation systems can be represented as capacitors. When a nonlinear load is
connected to power system formed from linear loads and large compensation systems
there will be created some interaction between nonlinear load and power system in
certain harmonic frequencies produced by nonlinear loads. This interaction is called
as resonance. There will occur two type resonances of in power systems; parallel
resonance and series resonance.
When the nonlinear load and compensation capacitors are connected parallel
in the same busbar as shown in Figure 3.1, the equivalent circuit of power system is
formed basically as in Figure 3.2 for harmonic frequencies. In this condition, parallel
resonance can occur so parallel connected system impedance and compensation
capacitors show high impedance as shown in Figure 3.3. Thus, the harmonic voltages
are magnified in the common busbar and high harmonic currents flows from the
compensation capacitors to system.
3. HARMONICS & INTERHARMONICS Adnan TAN
33
Substation
Transfomer
3 Phase
Supply
Voltage
Compensation
Capacitors
Nonlinear
Load
Common
Busbar
Figure 3.1. Single Line Diagram of Power System with Potential Parallel Resonance
Problems
Nonlinear
Load
sourceX TRX
CX
hI
Parallel Resonant
Circuit
Magnified
Current Harmonics
Caused By
Parallel Resonance
,h pI
,h pV
Magnified
Voltage Harmonics
Caused By
Parallel Resonance
EqZ
Figure 3.2. Equivalent Circuit of Power System with Potential Parallel Resonance
Problems
EqZ
fpf
Capacitor +Network Impedance
Only Network Impedance
Figure 3.3. Power System Impedance in Parallel Resonance Problems
3. HARMONICS & INTERHARMONICS Adnan TAN
34
When the compensation capacitors are placed under the transformer and the
transformer is connected in parallel with nonlinear harmonic producing load as
shown in Figure 3.4, the equivalent circuit of power system in shown in Figure 3.4 is
formed basically as in Figure 3.5 for harmonic frequencies. In this condition, series
connection of transformer and compensation system impedances create series
resonance in addition to parallel resonance caused by parallel connection of system
impedances and series connected transformer impedance with compensation system
impedance. Because of the series resonance, low impedance path is created to
harmonics and harmonics flow from this path. In Figure 3.6, frequency impedance
curve of power system shown in Figure 3.4 is given. High impedance point of curve
occurs in the parallel resonance frequency of the system and low impedance point of
curve occurs in the series resonance frequency of the system. Not only series
connection transformer, but also compensation system impedances and series
connection of any reactance of equipment such as power cables with capacitors can
create series resonance.
Substation
Transfomer
3 Phase
Supply
Voltage
Compensation
Capacitors
Nonlinear
Load
Common
Busbar
Transformer
Figure 3.4. Single Line Diagram of Power System with Potential Parallel and Series
Resonance Problem
3. HARMONICS & INTERHARMONICS Adnan TAN
35
Nonlinear
Load
sourceX TRX
CX
TRX
hI
Parallel Resonant
Circuit
Series Resonant
Circuit
Magnified
Current Harmonics
Caused By
Parallel Resonance
,h pI
,h pV
Magnified
Voltage Harmonics
Caused By
Parallel Resonance
,h sI
Current
Harmonics
Caused By
Series
Resonance
,h sVHigh Voltage
Distortion
Caused By
Series
ResonanceEqZ
Figure 3.5. Equivalent Circuit of Power System with Potential Parallel and Series
Resonance Problems
EqZ
fpf
sf
Figure 3.6. Power System Impedance in Parallel and Series Resonance Problems
Besides nonlinear loads and compensation systems, linear loads are also
connected to the power systems as shown in Figure 3.7. These loads can be modeled
as series connected resistor and inductor. These linear loads create damping affects to
parallel resonances occurring in the power system. The impedance frequency curve
of power system in Figure 3.8 is shown in Figure 3.9. With increasing ratio of
resistive load, the damping effect is increased. Not only linear loads but also power
lines, transformers and reactors have resistance. These resistances of equipment also
show damping effect on parallel and series resonance conditions.
3. HARMONICS & INTERHARMONICS Adnan TAN
36
Substation
Transfomer
3 Phase
Supply
Voltage
Compensation
Capacitors
Nonlinear
Load
Common
Busbar
R-L Loads
R-L Loads
Figure 3.7. Single Line Diagram of Power System with Linear, Nonlinear and
Compensation Loads
Common
Busbar
R-L Loads
R-L Loads
Nonlinear
Load
sourceX TRX
CX
TRX
hI
EqZ
Figure 3.8. Equivalent Circuit of Power System with Linear, Nonlinear and
Compensation Loads
EqZ
f
100% Resistive Load
50% Resistive Load
20% Resistive Load
Figure 3.9. Effects of Resistive Loads on Parallel Resonance
3. HARMONICS & INTERHARMONICS Adnan TAN
37
The effects of harmonics on equipment can be classified into short term
effects and long term effects. Short term effects are instantaneous effects that causes
generally failure, malfunctions or downgraded performance of power converters and
computer based devices through displacement of zero crossing of the voltage wave
because of the harmonics in voltage wave. Long term effects are related with
thermal losses in cables, transformers, motors, capacitors, etc. and mechanical stress
and losses in motors and generators. These problems cause excessive aging or even
damage in equipment (IEC 61000-2-2, 2002; IEEE Std. 519, 1992).
3.2. Interharmonics
Interharmonics are spectral components at frequencies that are not integer
multiples of the system fundamental frequency. Interharmonics can be observed in
an increasing number of loads in addition to harmonics. The main sources of
interharmonics are static frequency converters, cycloconverters, high voltage direct
current (HVDC) transmission systems, subsynchronous converter cascades,
adjustable speed drives, induction motors, welding machines, arc furnaces, and all
loads not pulsating synchronously with the fundamental power system frequency
(Tayjasanant et al., 2005; Yacamini, 1996)
The power converters which convert the AC input power to another AC
output power are the most suffering interharmonic sources. In these type converters,
two AC systems running at different frequencies are joined together through some
form of DC link. The problem arises if the systems are not perfectly decoupled
through the DC link. The DC voltage or current is modulated by the output frequency
of the converter and as a result interharmonic currents appear in the input current,
causing interharmonic voltages to be generated in the mains voltage. The
interharmonics are not only found in the input system also present in output AC
system. The harmonics and interharmonics produced by power converters can be
identified by the following equation; (Yacamini, 1996; IEC 61000-2-1, 1990)
3. HARMONICS & INTERHARMONICS Adnan TAN
38
1 1 21i of p m f p n f (3.4)
where
if : is the produces harmonics and interharmonics
1f : is the fundamental supply frequency
of : is the output frequency of the inverter
1p : is the pulse number of the rectifier
2p : is the pulse number of the inverter
m : are 0, 1, 2, 3 … (integers)
n : are 0, 1, 2, 3 … (integers)
m and n are not simultaneously equal to 0
The part formed from 1p , m and 1f in Eq. 3.4 gives the harmonic components. These
harmonic components in combination with the part formed from 2p , n and if in Eq.
3.4 give the interharmonic components. The interharmonic sources can generate
interharmonics below the fundamental frequency of power system in addition to high
frequency components. These interharmonics are named as sub – harmonics in many
of studies in literature however there is not any official definition in related
standards.
Interharmonics can create the all effects of harmonics on power systems and
equipment. In addition to these problems, interharmonics cause other power quality
problems such as subsynchronous oscillations, voltage fluctuations, and flickers.
Flickers and interharmonics have an inherent relationship. When a voltage waveform
contains interharmonics, the rms and peak magnitudes of the waveform will fluctuate
because the periods of the interharmonic components are not synchronous with the
fundamental frequency cycle. This fluctuating magnitude is essentially a form of
voltage flicker. If the magnitude is sufficiently large and the fluctuation frequency is
in a range perceptible by human eyes, a light flicker will occur. As a result, devices
that produce interharmonics have been considered as a major source of light flicker
(Testa et al., 2007; Tayjasanant et al., 2005). The only limitations about
3. HARMONICS & INTERHARMONICS Adnan TAN
39
interharmonics are recommended by IEC 61000-3-6 standard. IEC 61000-3-6
addresses interharmonic voltage limits by recommending a frequency-independent
limit of 0.2% so as to avoid problems with lamp flicker and ripple control, signaling,
and communications equipment (Halpin, 2005).
3.3. Harmonic and Interharmonic Mitigation Techniques
In order to mitigate harmonics and interharmonics, there are two main
approaches. The first approach is to make modifications in the power circuits of the
nonlinear loads and the second approach is to design compensation systems for
nonlinear loads.
In order to solve the harmonic problems of power converters, the most
preferred method is using higher pulse rectifiers in the rectifier section of power
converters with phase multiplication method. Another method is using pulse with
modulation (PWM) rectifiers which are able to provide variable DC link voltage with
generating low harmonic current content. The main drawback of both of these
methods is high costs. Using high pulse rectifiers with phase multiplication method is
preferred in most of the high power applications. However, although the harmonic
content of currents drawn from power systems is decreased seriously, the harmonics
of converters will be still over the limits. In PWM rectifiers, IGBTs or MOSFETs are
used instead of diodes or thyristors in classical rectifiers. Thanks to this difference,
the harmonic content of power converter can be decreased under limits by
controlling the current generated by power converter. There is a limited number of
PWM rectifier based products in market and these products are produced for low
voltage applications. The PWM rectifier based power converters are not preferred
and they are unpractical in many of applications because of the extremely high costs
and complex power circuit and control systems configurations.
Harmonic compensations systems are the most preferred approach in practical
harmonic mitigation applications. There are two main methods; passive filters and
active filters to compensate the harmonics and interharmonic. In order to control the
harmonic and interharmonic distortion generated by nonlinear loads, passive filters
3. HARMONICS & INTERHARMONICS Adnan TAN
40
have been used over many years. Passive filters are very popular because of the low
installation cost and meeting the reactive power requirements of nonlinear loads
while filtering the harmonics. However, the increasing use of nonlinear loads cause
complicated load characteristics shown in power systems and passive filters become
insufficient because of the drawbacks in the system impedance dependent filtering
performance and the resonance problems. This limited performance of passive filters
causes the development of active filters. The active filters are power electronics
based harmonic compensation systems and they are superior in harmonic filtering
performance, smaller in physical size, and more flexible in application compared to
traditional passive harmonic filters. The main purpose of the usage of APF is the
harmonic filtering but APF can be developed as a power conditioning device that can
solve simultaneously serious power quality problems such as unbalance loading,
reactive power and flicker additional to harmonics (Akagi, 2005).
3.3.1. Passive Filters
Passive filters which are formed from the various connections of capacitors,
inductors, and/or resistors have been used to overcome harmonic currents for a long
time. The passive filters can be classified into series passive filters, shunt passive
filters and broadband passive filters. The series passive filters are connected in series
with nonlinear loads and they create series high impedance to block the harmonic
currents. The shunt passive filters are connected in parallel with nonlinear loads and
they provide low-impedance paths for harmonic frequencies, thus resulting in
absorbing the dominant harmonic currents flowing out of the load current. The
broadband filters are formed from the series and parallel connection of passive
devices and they are used to block multiple or widespread harmonic frequencies
(Akagi, 2005; Dugan et al., 1996; Uçak, 2010).
Series passive filters are formed from parallel connection of inductor capacitor
as shown in Figure 3.10. The series passive filters are tuned to provide high
impedance at a selected harmonic frequency. The use of the series filters is limited in
blocking multiple harmonic currents. Each harmonic current requires a series filter
3. HARMONICS & INTERHARMONICS Adnan TAN
41
tuned to that harmonic. As all the series components, series filters are subjected to
full line current while shunt connected passive filters carry only a fraction of line
current. Moreover, the reactive power compensation capability of shunt connected
passive filters and the lower installation cost of shunt filters make series passive
filters non preferable (Dugan et al., 1996; Uçak, 2010).
L
C
3 Phase
Supply
Voltage
Nonlinear
Load
Figure 3.10. Series Passive Filter
Shunt passive filters can be classified into tuned filters, high pass filters and
C-type filters. The power circuit topologies and impedance frequency curves of the
most common type filters are shown in Figure 3.11. Single tuned filters are the most
commonly used type of the shunt passive filters. Single tuned filters are also named
as band-pass filters or notch filter in literature. This type filters tuned to a specific
frequency to present low impedance to a particular harmonic current. Thus, harmonic
currents are diverted from their normal flow path on the line through the filter. This
filter type is the most economical type and is frequently sufficient for the application
(Dugan et al., 1996). Single tuned filters are generally used for power factor
compensation in addition to harmonic compensation. In fact in many cases, single
tuned passive filters are used primarily for power factor correction instead of
compensation capacitors to avoid the resonance problems. High pass filters are also
named as damped filters. These filters provide low impedance for a wide spectrum of
harmonics without the need for subdivision of parallel branches with increased
switching and maintenance problems. The main drawback of high pass filters is
higher losses in the resistors and reactors. Another drawback is to achieve a similar
level of filtering performance as single tuned filters, high pass filters must be
3. HARMONICS & INTERHARMONICS Adnan TAN
42
designed for higher fundamental volt-ampere (VA) ratings. In many of cases it is
impossible to get sufficient filtering performance as single tuned filters with not
exceeding the reactive power compensation requirements. Because of these, high
pass filters are generally designed in low power ratings to damp the high order
harmonics. The three types of high pass filters and their characteristic as shown in
Figure 3.12. First order high pass filter is not preferred in many of applications,
because it has not sufficient filtering performance and it has excessive loss at the
fundamental frequency. The second order filter high pass filter has better
performance on filtering but higher losses with compared to third order high pass
filter (Arrillaga, 1985). The C-type filters are also type of damped filters, the filtering
performance of this type filter is between the second order and third order high pass
filters as shown in Figure 3.12. In C-type filter, C2 and L are tuned to fundament
frequency so in the fundamental frequency series connected C2 - L branch is short
circuited and resistor R is bypassed. Because of these, C-type filters get significant
advantage in fundamental frequency losses. C-type filters are generally tuned
frequencies between 2nd
and 6th
order harmonics and used in arc furnace and HVDC
compensation systems (Nassif et al., 2009).
R
L
C
R
CR
C
L
R
2C
L
1C
R
2C
L
1C
(a) (b) (c) (d) (e)
Figure 3.11. Shunt Passive Filter Topologies (a) Single Tuned (b) First Order (c)
Second Order (d)Third Order (e) C-Type
3. HARMONICS & INTERHARMONICS Adnan TAN
43
Figure 3.12. Shunt Passive filters Impedance - Frequency Curves (Nassif et al., 2009)
The basic circuit topology of broadband passive filter is shown in Figure
3.13. In many of practical applications, multiple stage shunt or series passive filters
must be used for reducing the different order harmonics under the limits. Unlike the
shunt and series filters that have a narrow band of harmonic suppression, broadband
filters have a wider range of harmonics suppression property. Broadband filters
employ a combination of the two passive techniques, with a high series impedance to
block the undesired current harmonics (from flowing through the grid) and a low
shunt impedance path to divert their flow through the shunt filter (Dugan et al., 1996;
Win, 2008).
L
C
3 Phase
Supply
Voltage
Nonlinear
Load
Figure 3.13. Broad-Band Passive Filter
3. HARMONICS & INTERHARMONICS Adnan TAN
44
Besides the advantages of passive filters in wide application area, passive
filters have significant drawbacks such as (Das, 2004; Fujita et al., 1991);
The power system impedance has considerable effect on filtering
performance of passive filter. It is difficult to anticipate the changes in the
power system impedance in the design stage.
Parallel resonance may be formed between a source and a passive filter and
causes amplification of harmonic currents on the source side at specific
frequencies.
Passive filters may fall into series resonance with a source so that voltage
distortion produces excessive harmonic currents flowing into the passive
filter.
Passive filters are not suitable for changing system conditions. Once installed,
these are rigidly in place. Neither the tuned frequency nor the size of the filter
can be changed so easily.
The aging, overloading and temperature can change the values of components
in passive filter so these effects can change the tuning frequency of passive
filter.
3.3.2. Active Power Filters
The limited performance of passive filters enforces to find the new solutions
for harmonic mitigation and provide the invention of APFs. In the beginning of
1970s, the basic principle of shunt APFs was originally presented by H. Sasaki and
T. Machida by using linear amplifiers. In 1976, L. Gyugyi and E. C. Strycula
presented a family of shunt and series active filters, and established the concept of
the active filters consisting of PWM inverters using power transistors (Peng et al.,
1990). For over 40 years, the scientists and engineers have been working on APFs
and by the help of developments in power electronics and microprocessor
technology, various type APFs have been developed to solve many of power quality
problems. Today APFs not only achieve harmonic filtering but also solve the various
3. HARMONICS & INTERHARMONICS Adnan TAN
45
type power quality problems such as reactive power, unbalanced loading, voltage
fluctuation and voltage flicker.
The block diagram of basic power circuit configuration of active power filter
is shown in Figure 3.14. The power circuit of APFs is mainly formed from three part;
output filter, inverter and DC link. Output filter is used for linking the inverter to the
power system and eliminating the switching ripples created by the inverter. The
inverter is main part of the power circuit and various type inverter topologies are
used for generating compensation currents or voltages. The switching devices used in
inverters are selected according to the power ratings of APF. The most common
switching devices used in inverters are MOSFETs and IGBTs. MOSFETs are low
power devices and they have high switching frequency capabilities. Adversely
IGBTs can work under higher powers but their switching frequency is lower than
MOSFETs. DC link of active power filter is formed from inductor or capacitor
depending on the type of inverter. DC link is used as energy storage device. APF
eliminates harmonics and/or other power quality problems by supplying reactive
energy to DC link and/or consuming reactive energy from DC link and additional DC
supply is not necessary. The only active power requirement of active power filter is
for losses of its power circuit.
INVERTEROUTPUT FILTER DC LINK
Figure 3.14. Block Diagram of Power Circuit of APF
The APFs can be classified based on topology, converter type and supply
system. In the topology based on classification, APFs can be classified into shunt
(parallel) APFs, series APFs, combination of both series and shunt APFs and HAPFs.
The shunt APFs is the most preferred type active filter in practical applications. The
shunt APF is connected in parallel with nonlinear load as shown in Figure 3.15. The
3. HARMONICS & INTERHARMONICS Adnan TAN
46
basic operating principle of shunt APF is to detect the harmonics from the distorted
current drawn by nonlinear load and then inject the reverse of harmonic currents to
the power system to eliminate the harmonic currents from the source current. Shunt
APFs can also achieve reactive-power compensation, balancing of three-phase
currents and voltage fluctuation and flicker reduction caused by nonlinear load
current.
Isource Iload
IAPF
APF
NonlinearLoad
Utility
Figure 3.15. Block Diagram of Shunt APF
The series APF is connected in series with the power system using a
transformer as shown in Figure 3.16. The main operating principle of series APF is
to inject a harmonic voltage in series with the line to render the supply current
sinusoidal (Bhattacharya et al., 2010).The approach is based on a principle of
harmonic isolation by controlling output voltage of the series APF. In other words,
the series APF is to present high impedance to harmonic current, therefore blocking
harmonic current flow from the load to the ac source and from the ac source to the
load side (Peng ,1998). The main drawback of series active power filter is to handle
3. HARMONICS & INTERHARMONICS Adnan TAN
47
the high load currents which increase their current ratings and losses (Habrouk et al.,
2000).
VAPF
APF
NonlinearLoad
Utility
+ -Isource Iload
Figure 3.16. Block Diagram of Series APF
The combination of shunt and series active filter which is called unified
power quality conditioner (UPQC) is shown in Figure 3.17. UPQC is formed by
connecting the series APF and the shunt APF using the same DC link. UPQC is
advanced power quality compensation device and it can solve voltage sag and swell
in addition to the power quality problems solved by both of series and parallel active
power filters. Its main drawbacks are its large cost and control complexity because of
the large number of solid-state devices involved (Singh, 1999).
3. HARMONICS & INTERHARMONICS Adnan TAN
48
VAPF
Utility
+ -
IAPF
NonlinearLoad
DC Link
Series APF Shunt APF
Isource Iload
Figure 3.17. Block Diagram of UPQC
HAPFs are formed using active power filters and passive filters are together.
The most popular hybrid power topologies are shown in Figure 3.18. In Figure
3.18(a), the series active power filter and shunt passive filter combination is shown.
In this configuration, while series active power filter compensated voltage
harmonics, it also constitutes a high impedance to increase the harmonic filtering
performance of the parallel passive filter. The drawbacks of series active power filter
constraint the use of this topology. In Figure 3.18(b), the shunt active power filter
and shunt passive filter combination is shown. In this topology shunt passive filter is
used to achieve reactive power compensation and eliminate the part of the harmonics
for reducing the ratings of active power filter. Another popular hybrid active power
filter topology is shown in Figure 3.18(c). In this topology active power filter is
connected to shunt passive filter in series with transformer. In low and medium
voltage applications, transformer can be removed and active filter can be connected
to passive filters directly. This combination of active power filter and passive filter is
significantly important for medium and high voltage applications because series
connection with passive filter reduces the voltage stress applied to the switches in the
active power filter. This specification reduces the rating of the active filter up to tenth
of the ratings of conventional active power filters and provides the ability of
compensation in high voltage applications. filters The operation principle of this type
3. HARMONICS & INTERHARMONICS Adnan TAN
49
hybrid is slightly different from conventional shunt connected passive filters. The
task of these hybrid active power filter are not to compensate for harmonic currents
produced nonlinear loads, but to achieve “harmonic isolation” between the supply
and the load. As a result, no harmonic resonance occurs, and no harmonic current
flows in the supply (Habrouk et al., 2000; Singh, 1999; Akagi, 2005).
VAPF
Utility
+ -
Nonlinear
Load
Series APF Passive Filter
Utility
+
Nonlinear
Load
Passive Filter
IAPF
Shunt APF
IPF IPF
Utility
Nonlinear
Load
Passive Filter
IPF
VAPF
+
-
Series APF
(a) (b)
(c)
Isource Iload Isource Iload
Isource Iload
Figure 3.18. Hybrid APF Topologies
(a) Series APF and Shunt Passive Filter Topology
(b) Shunt APF and Shunt Passive Filter Topology
(b) APF Series with Shunt Passive Filter Topology
In the converter based on classification, active power filters can be classified
into voltage source inverter based active power filter (VSI-APF) and current source
inverter based active power filter (CSI-APF). In CSI-APF, inductors are used as DC
link energy storage device and series connected diodes are used with switching
devices to maintain the reverse voltage blocking capability as shown in Figure
3.19(a). In VSI-APF, capacitors are used as DC link energy storage device and anti-
3. HARMONICS & INTERHARMONICS Adnan TAN
50
parallel diodes is connected to switching devices for allowing reverse current flow as
shown in Figure 3.19(b). Both topologies can achieve the sufficient harmonic
filtering performance. Although CSI-APF has faster dynamic response than VSI-
APF in current harmonic compensation, VSI-APF is more preferred in practical
applications because of the disadvantages of CSI-APF in high losses caused by DC
link inductor and necessity of large place for bulky DC link inductor and also the
advantages of VSI-APF in high efficiency, smaller size and the low initial costs
(Benchaita et al., 1999; Routimo et al., 2007; Akagi, 2005).
IAPF
NonlinearLoad
Utility
IAPF
NonlinearLoad
CDCLDC
(a) (b)
Isource Iload Isource IloadUtility
Figure 3.19. Converter Based on Classification of APFs (a) CSI-APF (b) VSI-APF
In the supply system based on classification, APFs can be classified into
single phase active power filters, three phase three wire active power filters and three
phase four wire active power filters. Most of commercial and domestic single phase
loads show nonlinear load characteristics and produce harmonics including third
order harmonics. In small commercial and domestic buildings, single phase active
power filters can be used for eliminating harmonics. The large domestic or
commercial plants such as hospitals, shopping centers etc. are generally supplied
from three phase four wire systems. Because of third harmonic currents of the single
phase nonlinear loads and unbalanced loading in three phase four wire systems, there
3. HARMONICS & INTERHARMONICS Adnan TAN
51
will occur overcurrent in the neutral conductor. Theoretically, third harmonics cannot
be eliminated by three phase three wire active power filters so, in order to solve these
problems in three phases four wire systems, four wire active power filters are widely
used. In industrial applications, loads are generally formed from balanced three phase
loads and third harmonic problems are rarely encountered. Thus, in industrial
applications three phase three wire active power filters are commonly used.
3.4. Harmonic and Interharmonic Extraction Methods
Harmonic extraction methods have significant importance in active power
filter performance. In order to achieve effective harmonic compensation, the
reference harmonic currents must be calculated as possible as accurate and fast.
Moreover the calculation complexity of harmonic extraction methods must be low
for the efficient use of resources of active power filter controllers. In literature,
various type harmonic extraction methods are proposed. These methods can be
mainly classified into time domain methods and frequency domain methods. In Table
3.1, the classification of most popular harmonic extraction methods are presented.
Table 3.1. Harmonic Extraction Methods
Time Domain
Methods
PQ Theory
Synchronous Reference Frame (SRF)
Filtering Methods; Band pass filters
Adaptive Filters
Neural Networks
Frequency Domain
Methods
Fast Fourier Transform (FFT)
Recursive Discrete Fourier Transform (RDFT)
Wavelet Transform
Kalman Filters
3. HARMONICS & INTERHARMONICS Adnan TAN
52
The time domain methods offer increased speed and fewer calculations
compared to the frequency-domain methods. PQ Theory and SRF methods are the
most popular time domain harmonic extraction methods. Both of these methods need
voltage and current measurements and they suffer from non-sinusoidal supply
voltage. Non-sinusoidal voltage supply directly affects the performances of these
methods. In literature, some improvements are proposed to improve PQ theory and
SRF methods. In SRF method, selective harmonic extraction can be achieved by the
help of PLL used in method. The most common frequency based methods are
Fourier based methods and wavelet method. The limitations of the frequency domain
approaches are that the designer has to consider the effect of aliasing. The
antialiasing filter used for this purpose is required to be very accurate; otherwise, the
whole calculation will be erroneous. Sampling instant and zero crossing of
fundamental are required to be synchronized. Otherwise, phase estimation by this
process will be erroneous. If number of samples is not a power of two, then zero
padding is required. Moreover, this method of analysis is very susceptible to noise
and transients (Asiminoaei et al., 2007; Bhattacharya et al., 2009).
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
53
4. MODELING AND ANALYSIS OF CSI-IF
In the modeling studies of CSI-IF, the coreless CSI-IF in the steel mill
mentioned in the introduction section is taken as a base model and CSI-IF is modeled
by using the power circuit and operating parameters of the coreless CSI-IF in the
steel mill. The modeling purpose of this CSI-IF is to show and analyze the power
quality problems of furnace. Thus, the furnace coil analysis and the effect of furnace
coil in the melting process do not take place in this thesis content. The power circuit
topology of the coreless CSI-IF in the steel mill is shown in Figure 4.1. The furnace
is formed from 12 MVA three phase double secondary transformer which is
connected to 31.5 kV busbar, twelve pulse fully controlled rectifier, DC link
inductors, H-bridge inverter and parallel resonant tank circuit. This furnace has 10
MVA power converter and the current source inverter works between 150 and 250
Hz frequencies to perform melting process at rated power. In this section of thesis the
operating principles and power quality problems of CSI-IF power supply and
modeling studies of CSI-IF is presented.
3 PHASE
DOUBLE SECONDARY
TRANSFORMER
12 MVA
31.5 kV/1.2 kV -1.2kV
Δ/ Δ-Y
FULLY CONTROLLED
12 – PULSE RECTIFIER
DC LINK
CURRENT
SOURCE
H – BRIDGE
INVERTER
PARALLEL
TUNING
CAPACITOR FURNACE COIL
PARALLEL
RESONANT TANK
CIRCUIT
31.5kV BUSBAR
Ssc = 335MVA
Figure 4.1. Power Circuit Topology of the Coreless CSI-IF in The Steel Mill
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
54
4.1. Operating Principles of CSI – IF Power Supply
The power circuit of CSI-IF shown in Figure 4.1 is mainly formed from three
parts; parallel resonant tank circuit, current source H bridge inverter, and 12-pulse
fully controlled rectifier. The general operating principle of CSI-IF is described in
Section 2.4. The heating power control in CSI-IF is performed by the variable DC
voltage output rectifier and CSI keep the parallel resonant tank circuit in the
resonance in order to maintain the flow of resonance current to the furnace coil.
These operating principle of CSI-IF is analyzed by investigating the main parts of
power supply of CSI-IF individually.
4.1.1. Parallel Resonant Tank Circuit
The parallel resonance circuit tank circuit of coreless CSI-IF is formed from
furnace coil and parallel connected capacitors. Before proposing the characteristic of
parallel resonant circuit, the electrical characteristics of furnace coil must be known.
The coreless induction furnaces are electrically analogous to the transformers. The
equivalent circuit approximation of transformer is used for furnace coil of coreless
CSI-IF (Tremayne, 1983). The equivalent circuit of a transformer is shown in Figure
4.2. PrR and PrX are the primary winding resistance and leakage reactance of
transformer. CR is the core resistance and MX is the magnetizing reactance of
transformer. PN is the primary winding turn number and SN is the secondary
winding turn number. SR and SX are the secondary winding resistance and leakage
reactance of transformer. LR and LX are the load resistance and load reactance.
When this transformer model is applied to coreless induction furnace, PR and PX
are the coil resistance fcR and reactance
fcX of furnace. CR and MX can be
neglected in the furnace model. Because of the coreless structure, their effects are
very less. PN is equal to coil turn number coilN and SN is equal to 1. SR and SX are
not used in furnace model because the secondary winding is absent in the coreless
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
55
furnace. gapX is the reactance of insulation material and gap between coil and inside
of crucible. The load resistance LoadR and reactance LoadX are equal to the metal
charge resistance chR and reactance chX of coreless induction furnace. The
resistance chR and inductance chX of the charge changes depending on the type of
metal charge, temperature of charge and amount of charge in the furnace. The
approximate equivalent circuit of coreless induction furnace is shown in Figure 4.3
and the equivalent circuit of furnace referred to primary side is shown at the Figure
4.4. fR is the equivalent furnace coil resistance which is equal to the sum of coil
resistance fcR and charge resistance referred to primary side
,ch refR . fX is the
equivalent furnace coil reactance which is equal to the sum of furnace coil reactance
fcX , gap reactance referred to primary side ,gap refX and load reactance referred to
primary side,ch refX . Also,
fR and fX are variable depending on the chR and chX
(Tremayne, 1983; Tokunç, 2010).
+ +
PrR
PrX
PrV CR MX
:P S
N NSR
SX
SVLoadR
LoadX--
Figure 4.2. Equivalent Circuit of Transformer
:1coil
N
+
PV
-
+
SV
-
fcR fcX
chR
chX
gapX
Figure 4.3. Equivalent Circuit of Coreless Induction Furnace
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
56
+
PV
-
, , f fc gap ref ch refX X X X,f fc ch ref
R R R
Figure 4.4. Coreless Induction Furnace Equivalent Circuit Referred to Primary Side
The parallel connected furnace coil and capacitors form a parallel resonance
circuit. If the resonance occurs in the electric circuits, the energy absorbed by one
reactive element is the same as that released by another reactive element within the
system. In other words, energy pulsates from one reactive element to the other.
Therefore, once an ideal system has reached a state of resonance, it requires no
further reactive power and they only deliver active power (Boylestad, 2007). Ideal
parallel resonance circuit is formed parallel connected resistance, inductance and
capacitance in parallel with a current source as shown in Figure 4.5.
PR PL PCI
,P PZ Y
PV
-
+
Figure 4.5. Ideal Parallel Resonant Circuit
The impedance-frequency curve of parallel RLC circuit is shown in Figure
4.6. In the resonance conditions of ideal parallel RLC circuit, the impedance of RLC
circuit reaches its maximum value and the reactance of PL is equal to the reactance
of PC so the resonance frequency of parallel RLC circuit is found as;
P PL CX X (4.1)
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
57
12
2P P
p P
f Lf C
(4.2)
1
2P
P P
fL C
(4.3)
PZ
mPZ
Pf
CapacitiveInductive
Figure 4.6. Impedance-Frequency Curve of Ideal Parallel Resonant Circuit
However, in practical applications as in the parallel resonant tank circuit
which is formed from parallel connected capacitor group with the furnace coil,
inductor has initial resistance and connected series with the inductance of inductor as
shown in Figure 4.7. If this circuit is converted to the parallel network equivalent
shown in Figure 4.8, the PR and PLX is equal to
2 2
LL L
P
L
R XR
R
(4.4)
2 2
L
P
L
L L
L
L
R XX
X
(4.5)
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
58
LL
PCI
LR
Figure 4.7. Practical Parallel Resonant Circuit
2 2
L
L
L L
P
L
R XR
R
2 2
L
P
L
L L
L
L
R XX
X
PCXI PV
-
+
Figure 4.8. Practical Parallel Resonant Circuit Converted To Ideal Parallel Resonant
Circuit Form
In the ideal parallel resonance circuit, the resonant frequency is the frequency
at which the impedance was a maximum, the current a minimum, and the input
impedance purely resistive, and the network have a unity power factor. However, for
the practical parallel circuits, since the resistance PR in our equivalent model is
frequency dependent, the frequency at which maximum PV is obtained is not the
same as required for the unity-power-factor characteristic (Boylestad, 2007).
For unity power factor, the power must be zero so; the inductive reactance
must be equal to capacitive reactance as in Eq 4.6.
P PL CX X (4.6)
With using Eq. 4.5, Eq.4.6 can be written as;
2 2
L
P
L
L L
C
L
R XX
X
(4.7)
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
59
From Eq. 4.7 unity power factor frequency uf is;
211
2
L Pu
LL P
R Cf
LL C (4.8)
The maximum impedance frequency of practical parallel resonant circuit can
be calculated as differentiating the impedance of parallel resonant circuit and then
determining the frequency at which the resulting equation is equal to zero. From
using this way, the maximum impedance frequency can be expressed as (Boylestad,
2007);
21 11
42
L Pm
LL P
R Cf
LL C
(4.9)
When Eq. 4.8 is compared to Eq. 4.9., it is seen that;
m uf f (4.10)
The quality factor of resonant circuit is equal to the ratio of reactive power to
the active power at resonance frequency. For practical parallel resonant circuit
quality factor is calculated as;
2 22
2 2 2
L
P
L
L
L LP
L LP
P L L
PL
R XVX R
QFV R X
R X
(4.11)
so that
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
60
LL
P
L
XQF
R (4.12)
The quality factor of parallel resonant tank circuit of coreless induction
furnace is considerably high (Chudnovsky et al., 1997; Rudnev et al., 2003). If the
quality factor of practical parallel resonant load PQF is larger than 10, the following
approximation can be done. If Eq. 4.4 is reorganized as (Boylestad, 2007).,
21P P LR QF R (4.13)
then, for 10PQF , 2 21 P PQF QF so
2
P P LR QF R (4.14)
If Eq. 4.5 is reorganized as,
2P
LL L
P
XX X
QF (4.15)
then, for 10PQF , 2 0L PX QF so
PL LX X (4.16)
If Eq 4.8 is reorganized with using Eq. 4.14 (Boylestad, 2007),
2
1 11
2u
PL P
fQFL C
(4.17)
then, for 10PQF , 21 0PQF so
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
61
1
2u
L P
fL C
(4.18)
,If Eq 4.9 is reorganized with using Eq. 4.14 (Boylestad, 2007),
2
1 1 11
42m
PL P
fQFL C
(4.19)
then, for 10PQF , 21 0PQF so
1
2m
L P
fL C
(4.20)
When the quality factor of practical parallel resonant load PQF is larger than
10, the capacitor current and inductor current is investigated by the following
equations. When the practical parallel resonant circuit in resonance, by using Eq. 4.6
and Eq. 4.16 the capacitive reactance of circuit is defined as;
P P LC L LX X X (4.21)
so the total impedance of practical parallel resonant circuit is calculated as,
1 1 1
P P
p
P L C
ZR jX jX
(4.22)
By using Eq. 4.14 and Eq. 4.21, At the resonance frequency maximum value of PZ is
found from Eq. 4.22 (Boylestad, 2007),
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
62
2
P P LZ QF R (4.23)
For 10PQF , from Ohm’s Law the voltage between the terminals of practical
parallel resonant circuit at the resonance frequency is calculated as;
2
P P LV IQF R (4.24)
and the capacitor and inductor current is calculated as;
2
P
P P
P P LC
C C
V IQF RI
X X (4.25)
2
P
P P
P P LL
L L
V IQF RI
X X (4.26)
For 10PQ , by using Eq. 4.12 and Eq. 4.21, Eq. 4.25 and 4. 26 can be organized as;
PC PI QF I (4.27)
PL PI QF I (4.28)
These approximations show that if the quality factor of practical parallel
resonant circuit is equal or larger than 10, this parallel resonant circuit is approved as
ideal parallel resonant circuit. Thus, the maximum impedance frequency and unity
power factor frequency of practical parallel resonance circuit can be accepted as
equal. Also from Eq. 4.27 and Eq. 4.28, it is shown that at the resonant frequency,
approximately while current source produce constant value of current, the quality
factor times of current of source flows from inductor and capacitor.
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
63
The parallel resonant tank circuit of coreless melting furnace is accepted as
ideal parallel resonance circuit, because of the high quality factor of parallel resonant
tank circuits. Hence these approximations are valid for the resonant tank circuit of
coreless melting CSI-IF. The advantage of parallel resonant tank circuit is shown in
Eq. 4.28. By using parallel resonant tank circuit with high quality factor excessive
high current can be drawn by the furnace coil while the switching devices used in the
CSI see only the constant value source current.
4.1.2. CSI
In order to keep the parallel resonant tank circuit in resonance, CSI must be
used. In low and medium power applications, IGBTs or MOSFETs can be used as
switching devices in inverters. However in high power applications, the capabilities
of IGBTs and MOSFETs are inadequate so SCRs are preferred in high power
applications as the high power melting CSI-IFs. When SCRs are used as power
switched in the inverters, load commutation must be maintained. In the load
commutation, the proper operation of these switches requires that a reverse voltage
be maintained across the switch, in order to turn off the SCRs. The reverse voltage
across the power switches can be provided with leading power factor load (Dawson
et al., 1991; Bose, 1986). The parallel resonant tank circuit of coreless CSI-IF can act
as both inductive load and capacitive load according to the operating frequency as
mentioned in previous section. The operating principles of CSI with SCRs and why
the capacitive load is necessary for the load commutation are proposed by giving the
capacitive mode operation waveforms of parallel resonant tank circuit.
The CSI with the parallel resonant tank circuit of IF is shown in Figure 4.9.
As mentioned in previous section; if the ideal or high quality factor parallel resonant
load operates below the resonant frequency of the parallel resonant load, it acts as
inductive load and if it operates in above the resonant frequency of the parallel
resonant load, it acts as capacitive load. In Figure 4.10, the waveforms of parallel
resonant operating above the resonant frequency are shown. If the current source is
accepted as an ideal source, the current waveform is formed from square wave and
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
64
voltage across the parallel resonant load is formed from sinusoidal wave in the
parallel resonant circuit. And also current leads the voltage because parallel load acts
as capacitive load above the resonant frequency.
LL
PC
LR
+
-
DCV
I
PV -+1Q
3Q
4Q
2Q
Figure 4.9. CSI of IF with Parallel Resonant Tank Circuit
I
PV
st
rf f Capacitive
Figure 4.10. Voltage and Current Waveforms of Parallel Resonant Tank Circuit
Operating Above the Resonance Frequency
The SCRs in the CSI are switched alternately for 180° to form a square
current wave. During the positive cycle of current 1Q and 2Q are switched on as
shown in Figure 4.11. When at the st time 3Q and 4Q are triggered and the voltages
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
65
are formed instantaneously for the upper switches as shown in Figure 4.12(a) and
lower switches as shown in Figure 4.12(b).
LL
PC
LR
PV -+
I
+
-
DCV
1Q
3Q
4Q
2Q
Figure 4.11. Operation of Load Commutated CSI
LL
PC
LR
+
DCVPV -+1
Q3
QLLLR
-DCV 4
Q2
Q
PC
PV -+
(a) (b)
Figure 4.12. Load Commutation of CSI
(a) Top Switches
(b) Bottom Switches
From the Kirchhoff’s Mesh Law, the voltage shown between the anode and
the cathode terminals of 1Q and 2Q is expressed as;
1Q PV V (4.29)
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
66
2Q PV V (4.30)
As shown in Figure 4.12 at time st , the magnitude of
PV is positive and
negative voltage is formed across the between the anode and the cathode terminals of
1Q and 2Q so that the 1Q and 2Q are closed and 3Q and 4Q is getting on. If the load is
inductive at the switching time of 3Q and 4Q , the voltage across the terminals of
load is negative and positive voltage is seen across the anode - cathode voltage of 1Q
and 2Q so that the 1Q and 2Q are not closed and the CSI cannot operate. Because of
these, in order to operate the CSI with using SCRs, the load must be capacitive.
Besides requirement of capacitive load for load commutation of CSI, CSI
requires an initial pre-charge on the parallel capacitor in order to initiate oscillations
in the parallel resonant circuit and built up sufficient voltage across the terminals of
the parallel resonance load circuit. Because of these problems, various type starting
circuit topologies are developed (Dawson et al., 1991; Bonert et al., 1994). Starting
circuits are used only in several cycles of inverter and then detached from the
inverter.
In the CSI-IF, the furnace coil is varied dependent to the temperature and the
amount of the charge material and fixed value capacitor is used to form parallel
resonant tank circuit. CSI of coreless melting IF provides the high current flow from
the furnace coil and load commutation for switching of SCRs by operating
continuously slightly above the resonance frequency of varying load.
4.1.3. 12-Pulse Fully Controlled Rectifier
The heating power in CSI-IF is related with the value of current flow from the
furnace coil. The value of furnace coil current is dependent on DC link current while
the CSI operates in resonance frequency as represented in previous sections. The DC
link current of CSI-IF is provided by the output DC voltage rectifier so the DC link
current is changed by varying rectifier output DC voltage. Therefore the control of
heating power can be performed by the rectifier of CSI-IF.
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
67
In high power CSI-IF, 12-pulse or higher pulse rectifiers are preferred
because of the lower demand for current harmonic content as in the base model CSI-
IF. The CSI-IF in the steel mill used as a base model in this thesis study has a series
connected 12-pulse fully controlled rectifier. The series connected 12-pulse fully
controlled rectifier is formed from two series connected 6-pulse rectifier which are
supplied from one of double secondary transformer as shown in Figure 4.13. The star
and delta connected secondaries have an inherent 6-phase which have 60° phase
difference.
6-Pulse Fully Controlled Rectifier
Double SecondaryTransformer
6-Pulse Fully Controlled Rectifier
Figure 4.13. Circuit Diagram of 12-Pulse Rectifier
The variable output of 12 pulse fully controlled rectifier is performed by
firing thyristor with delay/firing angle. When the thyristors are triggering at the zero
crossing point of each phase voltage signals, the firing angles of thyristors are equal
to zero and maximum DC voltage can be obtained from the output of the rectifier. If
the firing angle of rectifier is increased the voltage across the output of rectifier is
decreased. The mean value of the output DC voltage of rectifier is calculated as;
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
68
712
512
12sinmean mV V d
(4.31)
where
: firing angle
mV : input line to line voltage peak value of rectifier
From this equation meanV is equal to
1.977 cosmean mV V (4.32)
4.2. Power Quality Problems of CSI-IF
The CSI-IF in the steel mill used as a base model in this thesis study is a type
of AC to AC converter and formed from basically rectifier, DC link and inverter. As
introduced in Section 3.2, the harmonics and interharmonics created by the static
power converters can be derived from the equation;
1 1 21i of p m f p n f (4.33)
where
if : is the generated harmonics and interharmonics
1f : is the fundamental supply frequency
of : is the output frequency of the inverter
1p : is the pulse number of the rectifier
2p : is the pulse number of the inverter
m : are 0, 1, 2, 3 … (integers)
n : are 0, 1, 2, 3 … (integers)
The first part of this equation which contains 1p , m and 1f represents the
harmonics produced by the rectifiers. The second part of equation contains 2p , n
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
69
and of represents the effects of inverters and combination with first part gives the
interharmonics produced by power converter. If the rectifier and the inverter of
power converter can be decoupled perfectly with DC link, the second part of the
equation can be cancelled and only rectifier harmonics is seen in the current of power
converters. However if good decoupling cannot be provided between the rectifier and
the inverter of converter the interharmonics components are seen in the current of
power converter.
Generally when DC link of power converter is formed from only inductors,
the good isolation cannot be provided and inverter operating frequency affects the
input currents of the power converter. The coreless CSI-IF in the steel mill is an
example of such systems because the inductor is used in the DC link of power
converter of furnace. The CSI-IF in steel mill is connected to 50 Hz system voltage
and it has a 12 pulse rectifier. The inverter of this CSI-IF is a single phase H-bridge
CSI and operates between 150 Hz and 250 Hz. When the parameters are placed in
Eq. 4.33 if is obtained as;
12 1 50 2i of m nf (4.34)
When the values of variables m and n are increased in the Eq. 4.34, the amplitudes
of the harmonics and interharmonics decrease. Also, the amplitudes of the harmonics
and interharmonics decrease in the higher frequencies of of . By giving values of m
and n in Eq. 4.34 up to 2, the most dominant harmonics related with the operating
frequency of CSI-IF are shown in Figure 4.14. In this figure, the lines of most
dominant harmonics are colored with darker colors. In Figure 4.14, it is shown that
besides 11th
, 13th
, 23rd
and 25th
harmonics created by rectifier, the harmonic and
interharmonic frequencies at 1 2 of f and 1 4 of f are shown as dominant.
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
70
150
250
350
450
550
650
750
850
950
1050
1150
1250
50
1350
15
0
16
0
17
0
18
0
19
0
20
0
21
0
22
0
23
0
24
0
25
0
f1+2fo
-f1+2fo
f1+4fo
-f1+4fo
13f111f1
25f123f1
13f1-2fo
11f1-2fo
13f1+2fo11f1+2fo
25f1-2fo
23f1-2fo
CSI-IF Operating Frequency
fo
Ge
ne
rate
d H
arm
on
ics
by
CS
I-IF
f i
Figure 4.14. Generated Harmonics Related with Operating Frequency of CSI-IF
It is shown clearly in the Figure 4.14 that harmonic and interharmonic content
of furnace current is varying with the operating frequency of furnace and cover wide
harmonic and interharmonic spectrum. Moreover the high harmonic and
interharmonic content of CSI-IF current can cause serious voltage harmonics and
interharmonics especially in weak power systems. The voltage interharmonics cause
voltage fluctuations and flicker problems because of the interaction of non-
synchronous interharmonic components with the fundamental frequency (Dugan et
al., 1999).
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
71
4.3. Modeling of Current Source Induction Furnace
4.3.1. Power Circuit Parameters
The power circuit model of CSI-IF in PSCAD/EMTDC. shown in Figure 4.15
DCI
DCV
DCL
DCL
res-tankI
res-tankV
fur coilI
stray
L
fL
fC
fR
sysL
sysL
sysL
aI
bI
cI
aV
bV
cV
3 PHASE
DOUBLE SECONDARY
TRANSFORMER
12 MVA
31.5 kV/1.2 kV -1.2kV
Δ/ Δ-Y
3 PHASE
POWER SUPPLY
31.5kV
Ssc = 335MVA
Figure 4.15. Power Circuit Model of CSI-IF
The CSI-IF is connected to 31.5kV busbar which has 335 MVA short circuit
power. The system impedance is calculated from Eq. 4.35 and found as 9.4 mH.
2
,
100
L L rms
sys
sc
VL
S
(4.35)
The power circuit parameters of CSI-IF is determined by using the coreless
melting CSI-IF in the steel mill. Except the furnace coil parameters, all other
parameters are taken from the CSI-IF in steel mill. The furnace coil inductance
values are calculated using the fixed capacitor values of resonant tank circuit and
operating frequency of furnace by using Eq. 4.18. The furnace coil resistance values
are determined by quality factor of parallel resonant tank circuit and calculated
furnace inductance values. According to Eq. 4.28, quality factor of parallel resonant
tank circuit is determined by using current measurements of DC link current and
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
72
furnace coil current. When the measurements of DC-link current and furnace coil
current are investigated, the quality factor of parallel resonant tank circuit has lower
values during charging period of furnace. When the furnace crucible is full, quality
factor of parallel resonant tank circuit reaches higher values. By using this
information about quality factor and furnace coil inductance values, the furnace
resistance values are determined by using Eq. 4.12. The power circuit parameters of
CSI-IF modeled in PSCAD/EMTDC are given in Table 4.1.
Table 4.1. Power Circuit Parameters of CSI-IF Model
Transformer 12 MVA, 31.5 kV/1.2 kV -1.2kV, Δ/ Δ-Y
VSC,1-2, VSC,1-3=12%, VSC,2-3=30%,
LDC 1 mH
LStray 12.5 µH
Cf 5.28 mF
Rf 0.011 – 2 mΩ
Lf 0.076 – 0.213 mH
In proposed model of CSI-IF, starting circuit is not used for CSI. Initial
voltage of furnace capacitor is given by an external voltage source at start-up of
furnace.
4.3.2. Controller of CSI-IF
The controller of CSI-IF applied in simulation study is formed from two parts
as DC link current controller and CSI controller. DC link current controller controls
the firing angles of thyristor in order to maintain constant DC link current value. The
DC link controller is formed from basic PI controller and firing pulse generator as
shown in Figure 4.16. The PI controller produces the firing angle according to error
signal between the set value and measurement value of DC link current. Firing pulse
generator generates appropriate firing angles for SCRs of 12-pulse rectifier by using
PLL. PLL gives the phase information of voltage of phase A. Firing angles of each
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
73
thyristor produced by comparing firing angle and the phase value of voltage by firing
pulse generator.
DCI
aV
PI
CONTROLLER
PLL
FIRING
PULSE
GENERATOR
12
DCI
aV
,DC setI
a
12-Pulse
Rectifier
-
+
Figure 4.16. Block Diagram of DC Link Controller of CSI-IF
By changing set value of DC link current, DC link current is changed by 12-
pulse rectifier so, the heating power control can be adjusted. Also at the starting of
CSI-IF, CSI cannot determine the resonant frequency immediately. Because of these
at the starting of furnace, the impedance of parallel resonant circuit is low. Until the
CSI of furnace catches the operation frequency of parallel resonant tank circuit, the
rectifier must decrease DC link voltage to prevent excessive current flow from the
power switches of CSI.
In order to control the CSI of IF, many controllers are proposed in literature
and also the most of these controllers are PLL based controllers. The main idea of
these PLL controllers is to keep the parallel resonant load in resonance with reducing
the phase shift between current and voltage across the terminals of parallel resonant
circuit to approximately zero by increasing or decreasing the CSI operating
frequency. The proposed controller of CSI-IF shown in Figure 4.17 is developed by
using the CSI controllers proposed by Khan et al. (2000), Peng et al., (1989) and
Ponwiangkum et al. (2007). These PLL based controller is mainly formed from
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
74
phase detector (PD), PI controller, voltage controlled oscillator (VCO) and switching
signal generator.
ZERO
CROSSING
DETECTOR
ZERO
CROSSING
DETECTOR
XORLOW
PASS
FILTERx -
+
PI
CONTROLLER
-
+ VOLTAGE
CONTROLLED
OSCILLATOR
COMPARATOR
res-tankV
res-tankI
res-tankI
res-tankV
set
,CSI i
CSI CSI
1Q
2Q
3Q
4Q
1Q
2Q
3Q
4Q
Figure 4.17. Block Diagram of CSI of CSI-IF
In the phase detector part, both current and voltage signals are formed as
square wave with the same zero crossing points as original signals by zero crossing
detectors. Then with using exclusive OR gate (XOR) and low pass filter, the phase
difference between the current and voltage waveforms of parallel resonant circuit
is determined. In order to convert the phase difference to radian the output of low
pass filter is multiplied with π. This phase difference is subtracted from phase
difference set value set to form error signal. In ideal conditions, set is taken 0 but in
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
75
order to provide the load commutation of CSI set must higher from 0. error goes
into the PI controller. The output of PI controller is summing with the initial CSI
angular frequency ,CSI i and CSI inverter operating angular frequency CSI is
calculated. ,CSI i is selected higher than operating values of CSI in order to enforce
the parallel resonant load in capacitive region at start-up CSI-IF. The angular
frequency CSI goes into VCO. VCO is formed from simple integrator and it is used
for generating the phase information CSI related to CSI . CSI is used to generate
switching signals of CSI by the help of the comparator. If CSI is higher than , 1Q
and 2Q are triggered and if CSI is lower than , 3Q and 4Q are triggered.
4.3.3. Simulation Results of CSI-IF
By using the operating frequency range and process conditions of CSI-IF in
steel mill, a simulation scenario is designed operate the furnace from no load to full
load by setting the furnace coil inductance and resistance values. Firstly furnace has
no charge and with starting of simulation furnace is started to charge up to full load
capacity. Then furnace runs for melting the charge completely and heating the charge
up to necessary process temperature. According to this scenario, furnace starts
operating at 150 Hz and operation frequency of furnace reaches up to 250 Hz related
to filling rate of furnace as shown in Figure 4.18.
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
76
50
100
200
250
300
150
f (Hz)
t
Charging and Melting Heating Melted Metal
Figure 4.18. Frequency Trend of Modeled Induction Furnace According To
Operating Scenario
Firstly the controller signals of CSI-IF are presented. In the Figure 4.19 the
trend of phase difference signal is given and in Figure 4.20 the trend of CSI
angular operating frequency CSI is given during the start-up of CSI-IF. It is shown
that in Figure 4.19, the phase difference between parallel resonant tank circuit
current and voltage across the terminals of parallel resonant tank circuit is high at the
beginning. After CSI gets down to the resonance frequency of tank circuit, the phase
difference reaches the set value 15 .
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
77
Figure 4.19. Trend of Phase Difference between Voltage and Current of Resonant
Load
Figure 4.20. Trend of CSI Angular Operating Frequency
The trend of phase difference and the trend of CSI angular operating
frequency CSI values taken during the entire simulation time are presented in Figure
4.21 and Figure 4.22. It is clearly shown that while the operating frequency of
furnace is changing, the CSI controller keeps the phase difference constant. In
other words, the CSI controller keeps the resonant tank circuit in resonant although
the furnace coil inductance and resistance are changing continuously. Moreover CSI
CSI_Controller : Graphs
sec 0.000 0.100 0.200 0.300 0.400 0.500 0.600 0.700 0.800 0.900 1.000 ...
...
...
0.00
0.20
0.40
0.60
0.80
1.00
1.20
1.40
1.60
1.80
Phase
Diffe
rence
(R
adia
n)
PhaseDifference
CSI_Controller : Graphs
sec 0.000 0.100 0.200 0.300 0.400 0.500 0.600 0.700 0.800 0.900 1.000 ...
...
...
0.8k0.9k
1.0k1.1k1.2k1.3k
1.4k1.5k1.6k1.7k
1.8k1.9k2.0k2.1k
2.2k2.3k2.4k
CS
I O
pera
ting F
req (
Radia
n)
PI_ControlSignal
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
78
in the Figure 4.22 shows the same variation with the determined modeling operating
scenario. This shows that the controller of CSI reacts correctly to change of the
furnace coil parameter.
Figure 4.21. Trend of Phase Difference between Voltage and Current of Resonant
Load during Entire Simulation
Figure 4.22. Trend of CSI Angular Operating Frequency during Entire Simulation
In Figure 4.23 the phase of the operating frequency of CSI CSI and in Figure
4.24 gate pulses of SCRs in CSI during the start-up of CSI-IF is shown. It is
CSI_Controller : Graphs
sec 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 ...
...
...
0.00
0.20
0.40
0.60
0.80
1.00
1.20
1.40
1.60
1.80
Phase
Diffe
rence
(R
adia
n)
PhaseDifference
CSI_Controller : Graphs
sec 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 ...
...
...
0.8k0.9k
1.0k1.1k1.2k1.3k
1.4k1.5k1.6k1.7k
1.8k1.9k2.0k2.1k
2.2k2.3k2.4k
CS
I O
pera
ting F
req (
Radia
n)
PI_ControlSignal
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
79
obviously seen that the frequency of CSI signal is higher and the firing pulses of
SCRs are more frequently at the start-up of CSI because of the high value of CSI at
the start-up of CSI-IF.
Figure 4.23. Phase of the Operating Frequency of CSI
Figure 4.24. Thyristor Gate Pulses of CSI
CSI_Controller : Graphs
sec 0.0000 0.0100 0.0200 0.0300 0.0400 0.0500 0.0600 0.0700 0.0800 0.0900 0.1000 ...
...
...
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
5.00
5.50
6.00
6.50
7.00
Ref
Phase
of
CS
I (R
adia
n)
Phase
CSI-IF Controller : Graphs
sec 0.0000 0.0100 0.0200 0.0300 0.0400 0.0500 0.0600 0.0700 0.0800 0.0900 0.1000 ...
...
...
0.0
1.20
Q1-Q
2 G
ate
Puls
es
Q12
0.0
1.20
Q3-Q
4 G
ate
Puls
es
Q34
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
80
The current waveform of parallel resonant tank circuit and the voltage
waveform between the terminals of parallel resonant tank circuit are shown in Figure
4.25. It is seen that while the current res-tankI has square wave shape, the voltage
res-tankV has sinusoidal waveform and alsores-tankI leads res-tankV .with angle .
Figure 4.25. Current and Voltage Waveform between Terminals of Parallel Resonant
Tank Circuit
In Figure 4.26 the current waveform of furnace coil fur-coilI is given. It is seen
that, fur-coilI is higher than the times of res-tankI because of the resonance.
Figure 4.26. Current Waveform of Furnace Coil
CSI-IF : Graphs
sec 3.0000 3.0020 3.0040 3.0060 3.0080 3.0100 3.0120 3.0140 3.0160 3.0180 3.0200 ...
...
...
-6.0
-5.0
-4.0
-3.0
-2.0
-1.0
0.0
1.0
2.0
3.0
4.0
5.0
6.0
Reso
nant
Tank
Circu
it I
&V
(kA
,kV
)
Ires-tank Vres-tank
CSI-IF : Graphs
sec 3.0000 3.0020 3.0040 3.0060 3.0080 3.0100 3.0120 3.0140 3.0160 3.0180 3.0200 ...
...
...
-35.0
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
Furn
ace
Coil
Curr
ent
(kA
)
Ifur-coil
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
81
The trend of firing angle of rectifier during the start-up of CSI-IF is shown
in Figure 4.27. It is seen that at the start-up the firing angle has high delay angle
because CSI cannot reach directly to the resonant frequency of parallel resonant load
at start up. When the parallel resonant load is not operating at the resonant
frequency, it shows low impedance. Because of these, the controller of rectifier
increases the firing angle of SCRs and decreases the DC link voltage DCV in order to
limit the DC link current DCI and prevent the excessive current flow through the CSI
as shown in Figure 4.28 and 4.29.
Figure 4.27. Trend of Firing Angle of 12-Pulse Rectifier
Main : Graphs
sec 0.000 0.100 0.200 0.300 0.400 0.500 0.600 0.700 0.800 0.900 1.000 ...
...
...
0
10
20
30
40
50
60
70
80
90
100
12 P
uls
e R
ec
Firin
g
Ang (
Degre
e)
Alpha
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
82
Figure 4.28. Trend of DC Link Voltage of CSI-IF
Figure 4.29. Trend of DC Link Current of CSI-IF
The trend of DCV and DCI values taken during the entire simulation time are
presented in Figure 4.30 and Figure 4.31.
CSI-IF : Graphs
sec 0.000 0.100 0.200 0.300 0.400 0.500 0.600 0.700 0.800 0.900 1.000 ...
...
...
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
CS
I-IF
DC
Lin
k V
oltage (
kV)
Vdc
CSI-IF : Graphs
sec 0.000 0.100 0.200 0.300 0.400 0.500 0.600 0.700 0.800 0.900 1.000 ...
...
...
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
5.00
CS
I-IF
DC
Lin
k C
urr
ent
(kA
)
Idc
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
83
Figure 4.30. Trend of DC Link Voltage of CSI-IF during Entire Simulation
Figure 4.31. Trend of DC Link Current of CSI-IF during Entire Simulation
In Figure 4.32, the ripple on the DCI is given. It is seen that there is high
ripple content on the DCI which resulted from CSI and causes interharmonic
distortion in the supply current of CSI-IF. The ripple frequency on the DCI is equal to
the two times of the CSI operating frequency.
CSI-IF : Graphs
sec 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 ...
...
...
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
CS
I-IF
DC
Lin
k V
oltage (
kV)
Vdc
CSI-IF : Graphs
sec 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 ...
...
...
-1.00
-0.50
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
5.00
CS
I-IF
DC
Lin
k C
urr
ent
(kA
)
Idc
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
84
Figure 4.32. Ripple on DC Link Current of CSI-IF
The waveforms of current drawn by CSI-IF and busbar voltage of CSI-IF is
given in Figure 4.33 and Figure 4.34. It is obviously seen that current waveform is
highly distorted and voltage form is also distorted because of the voltage drop on the
system impedance.
Figure 4.33. Supply Current Waveform of CSI-IF
CSI-IF : Graphs
sec 3.0000 3.0020 3.0040 3.0060 3.0080 3.0100 3.0120 3.0140 3.0160 3.0180 3.0200 ...
...
...
2.00
2.10
2.20
2.30
2.40
2.50
2.60
2.70
2.80
2.90
3.00
3.10
CS
I-IF
DC
Lin
k C
urr
ent
(kA
)
Idc
CSI-IF : Graphs
sec 3.000 3.010 3.020 3.030 3.040 3.050 3.060 3.070 3.080 3.090 3.100 ...
...
...
-0.40
-0.30
-0.20
-0.10
0.00
0.10
0.20
0.30
0.40
CS
I-IF
Supply
Curr
ents
(kA
)
Ia Ib Ic
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
85
Figure 4.34. Supply Voltage Waveform of CSI-IF
The trend of active and reactive power of CSI-IF is shown in Figure 4.35. The
high reactive power is drawn by CSI-IF at the start-up of CSI-IF because of the high
firing angles of 12-pulse rectifier. However, it is shown that CSI-IF has low and slow
varying reactive power demand.
Figure 4.35. Trend of Active and Reactive Power of CSI-IF
In Figure 4.36, the angular operating frequency CSI at the 1st second of the
simulation is shown. At this time the furnace approximately operates at 175 Hz. In
CSI-IF : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-40
-30
-20
-10
0
10
20
30
40
CS
I-IF
Supply
Voltages
(kV
)
Va Vb Vc
CSI-IF : Graphs
sec 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 ...
...
...
-1.0
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
CS
I-IF
P&
Q (
MW
,MV
Ar)
P_CSI-IF Q_CSI-IF
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
86
Figure 4.37, the most dominant harmonics and interharmonics of CSI-IF calculated
for 175 Hz with Eq. 4.33 is presented and in Figure 4.38(a) and 4.38(b) the harmonic
spectrum of current drawn by CSI-IF is shown. The harmonic spectrum shows the
harmonics with steps of 10 Hz in order to indicate the interharmonics. In Figure
4.38(a) lower order harmonics and interharmonics are presented with larger scale and
in Figure 4.38(b) higher order harmonics and interharmonics are presented with
lower scale. When the Figure 4.37 is compared to harmonic spectrum of furnace
current, it is obviously seen that CSI-IF model produce the all calculated harmonics
and interharmonics.
Average ωo ≈ 1100 rad
fo ≈ 175 Hz
Figure 4.36. Angular Operating Frequency at the 1
st Second of the Simulation
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
87
150
250
350
450
550
650
750
850
950
1050
1150
1250
50
1350
15
0
16
0
17
0
18
0
19
0
20
0
21
0
22
0
23
0
24
0
25
0
f1+2fo
-f1+2fo
f1+4fo
-f1+4fo
13f111f1
25f123f1
13f1-2fo
11f1-2fo
13f1+2fo11f1+2fo
25f1-2fo
23f1-2fo
CSI-IF Operating Frequency
fo
Ge
ne
rati
ng
Ha
rmo
nic
s b
y C
SI-
IF
f i
f1+6fo -f1+6fo
Figure 4.37. Generated Harmonics When CSI-IF Operates at 175 Hz
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
88
Fig
ure
4.3
8. H
arm
onic
Spec
trum
of
CS
I-IF
Curr
ent
when
CS
I-IF
oper
ates
at
175 H
z
(a)
Low
er O
rder
Har
mon
ics
wit
h L
arge
Sca
le
(b)
Hig
her
Ord
er H
arm
onic
s w
ith L
ow
er S
cale
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
89
Another example is given at the 5th
second of the simulation. It is shown in
Figure 4.39, CSI-IF operates at 235 Hz at this time. In Figure 4.40, the calculated
harmonics and interharmonics for 235 Hz is given and in Figure 4.41 the harmonic
spectrum of current of CSI-IF is presented. Again when the figure 4.40 is compared
to harmonic spectrum of furnace current, it is obviously seen that CSI-IF model
produce the all calculated harmonics and interharmonics.
Average ωo ≈ 1490 rad
fo ≈ 235 Hz
Figure 4.39. Angular Operating Frequency at the 5
th Second of the Simulation
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
90
150
250
350
450
550
650
750
850
950
1050
1150
1250
50
1350
15
0
16
0
17
0
18
0
19
0
20
0
21
0
22
0
23
0
24
0
25
0
f1+2fo
-f1+2fo
f1+4fo
-f1+4fo
13f111f1
25f123f1
13f1-2fo
11f1-2fo
13f1+2fo11f1+2fo
25f1-2fo
23f1-2fo
CSI-IF Operating Frequency
fo
Ge
ne
rati
ng
Ha
rmo
nic
s b
y C
SI-
IF
f i
Figure 4.40. Generated Harmonics When CSI-IF Operates at 235 Hz
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
91
Fig
ure
4.4
1. H
arm
onic
Spec
trum
of
CS
I-IF
Curr
ent
when
CS
I-IF
oper
ates
at
235 H
z
(a)
Low
er O
rder
Har
mon
ics
wit
h L
arge
Sca
le
(b)
Hig
her
Ord
er H
arm
onic
s w
ith L
ow
er S
cale
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
92
4.3.4. Comparison of Simulation Results with Real Power Quality
Measurements of Induction Furnace
In this section, harmonics and interharmonics simulation results of CSI-IF
shown in previous section is compared to the real power quality measurements of
CSI-IF in the steel mill. These measurements are taken by IEC 61000-4-30 Class A
compatible measurement device. The harmonics and interharmonic measurements
are recorded with averaging measurements in every 3 seconds.
In Figure 4.42 the harmonic spectrum of CSI-IF during one casting time and
in Figure 4.43 the interharmonic spectrum during one casting time are given. The
interharmonics are calculated with steps of 5 Hz according to IEC 61000-4-7. The nth
interharmonic indicates that the interharmonic frequencies between nth
and (n+1)th
harmonics. In the simulation results, it is presented that the CSI-IF creates
dominantly the harmonics and interharmonics in the range of 1 2 of f and 1 4 of f
in addition to 11th
, 13th
, 23rd
and 25th
harmonics. The CSI-IF in the steel mill
approximately operates between 150 Hz and 250 Hz so 1 2 of f harmonics and
interharmonics are created between 250 Hz and 550 Hz and, 1 4 of f harmonics and
interharmonics are created between 650 Hz and 1050 Hz. The same characteristic of
CSI-IF shown in simulation results is obviously seen in the real harmonic and
interharmonic measurements of CSI-IF in the steel mill shown in both Figure 4.42
and 4.43.
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
93
Figure 4.42. Harmonic Spectrum Obtained by the PQ Measurements in the Steel Mill
Figure 4.43. Interharmonic Spectrum Obtained by the PQ Measurements in the Steel
Mill
4. MODELING AND ANALYSIS OF CSI-IF Adnan TAN
94
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
95
5. MODELING AND ANALYSIS OF PQ COMPENSATION SYSTEMS FOR
CSI-IF
In the previous section the power quality problems of high power melting
CSI-IF is presented in detail. It is presented that CSI-IF produces time varying
harmonic and interharmonic currents in wide frequency spectrum range. Moreover
these distorted currents also causes voltage distortion at the busbar which CSI-IF is
connected. Besides harmonic and interharmonic problems, reactive power demand of
CSI-IF must be compensated. Fortunately the reactive power demand of CSI-IF has
slow varying characteristic and can be easily handled with traditional methods. In
this section passive and active filtering systems are investigated and the most
effective compensation system is determined for the power quality problems of high
power CSI-IF.
5.1. Passive Filters
In order to solve the power quality problems of high power CSI-IF, single
tuned filter, C-type filter and broad-band filter are designed and the performances of
these filters are presented.
5.1.1. Single Tuned Passive Filters
Single tuned passive filters are most commonly applied type shunt passive
filters. As shown in Figure 5.1 single tuned passive filter can be modeled as series
connected inductor, resistor and capacitor. The capacitor and inductor are tuned near
a harmonic frequency in order to bypass that harmonic providing low impedance.
The capacitor of filter also provides reactive power compensation and the capacitor
value is selected according to the reactive power demand of system. The resistor
represents the internal resistance of inductor or an external resistor which can be used
additionally. The resistance value of the filter affects the sharpness and bandwidth of
filter. Because single tuned filters are filtering only harmonics in the tuned
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
96
frequency of filter, one single tuned filter may not be adequate to filter effectively all
the troublesome harmonics (Das, 2004; Nassif et al., 2009).
STFL
,STF YC
STFR
Figure 5.1. Single Tuned Passive Filter
Although single tuned filter acts as a very low impedance at the tuned
frequency, it always creates parallel resonance with system impedance and shows
quite high impedance at a frequency lower than the tuned frequency of filter as
shown in Figure 5.2 (Gonzalez et al., 1987).
Filter +Network
Impedance
Only Network
Impedance
Tuning Frequency
of Filter
Figure 5.2. Impedance Frequency Curve of Single Tuned Filter
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
97
The single tuned passive filter design can be performed by using Eq. 5.1, Eq.
5.2 and Eq. 5.3. In order to design passive filters, firstly the harmonic analysis of
system is performed and harmonics which are exceeding the limits and cause
disturbance in the system is determined. Secondly the reactive power requirement of
system is determined. After harmonic distortion and reactive power requirements of
system are determined, the filter tuning frequencies and reactive power are
determined. The single tuned filters are commonly not tuned exactly to the frequency
it is intended to suppress. The filter capacitors and inductors have tolerances. Besides
these, aging and temperature effects alter the filter inductor and capacitor values
(Das, 2004). These changes in the capacitor and the inductor values of filter can
cause to shift the resonance frequency above the harmonics in the system. This
causes the amplification of harmonics in the power system. Because of these single
tuned filters are tuned slightly below the harmonic frequencies. The reactive power
requirements of system are divided to filters according to amplitudes and frequencies
of harmonics. The lower frequency harmonics are generally higher amplitudes. In
order to filter these harmonics effectively, the filters tuned to lower frequencies
shows lower impedance to these harmonics. It can be achieved by increasing
capacitor value or in other words, the reactive power of filter. The capacitor and
inductor values of single tuned filter are calculated by using Eq. 5.1 and Eq. 5.2
according to tuning frequency and reactive power of filter. The QF of filter
determines the sharpness of filter and resistance value of filter is determined by Eq.
5.3. The quality factors of single tuned filters used in power systems are generally in
the range of 20-100.
,
1
2STF
STF STF Y
fL C
(5.1)
,
2
STF STF Y
LSTF
L C
VQ
X X
(5.2)
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
98
,
STF
STF Y
STF
STF
LC
QFR
(5.3)
If a harmonic compensation system formed from single tuned passive filters
is used for CSI-IF, tuning frequencies of passive filters must be selected correctly.
The modeled CSI-IF has non varying reactive power demand so 2 MVAr reactive
power compensation system is adequate for compensating reactive power demand of
CSI-IF. If a passive filtering system formed from 500 MVAr single tuned filters
which are tuned at 5th
, 7th
, 11th
and 13th
harmonics is designed for compensating the
harmonics and reactive power of CSI-IF, although this compensation system has
good filtering performance in tuning frequencies, this compensation system does not
work well and cause serious resonance problems. As shown in Figure 5.3, the single
tuned filters cause parallel resonance below the tuning frequencies of each branch.
The modeled CSI-IF generates the most dominant time varying harmonics and
interharmonics between 250 Hz and 650 Hz. Because of these this filtering system
cause parallel resonance problem which creates voltage distortion at PCC and causes
excessive harmonic current flow from both single tuned filters and power system.
Therefore such a passive filtering system is not suitable for CSI-IF.
Filters +Network
Impedance
Only Network
Impedance
Figure 5.3. Impedance-Frequency Curve of 5
th, 7
th, 11
th and 13
th Harmonic Single
Tuned Filters
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
99
The solution of avoiding the parallel resonance is to tune the passive filters
below frequencies of harmonics and interharmonics produced by the modeled CSI-
IF. When the simulation results of the modeled CSI-IF in Section 4 is investigated, it
is shown that CSI-IF produces harmonics and interharmonics in very wide spectrum
range. However below the 150 Hz, the magnitudes of harmonics and interharmonics
are inconsiderable, so a single passive filter tuned below the 150 Hz does not cause
resonant problems with power system. Because of these, 2 MVAr single tuned
passive filter tuned at 135 Hz is designed for CSI-IF. The design parameters of single
tuned filter are given in Table 5.1.
Table 5.1. Power Circuit Parameters of Single Tuned Passive Filter Model
Single Tuned Passive Filter
STFQ = 2MVAr , STFf =135 Hz, STFQF =50
STFL 251mH
,STFC 1.845µF
STFR 4.26Ω
The single line diagram of CSI-IF with passive filters and equivalent circuit
diagram for harmonic frequencies is shown in Figure 5.4. In harmonic frequencies
the 50 Hz voltage source acts as short circuited and CSI-IF acts as current source.
sysL
STFR
,STF YC
STFL
CSI-IF
sysL
CSI-IF
,CSI IF harI
Filter SystemZ(a) (b)
STFR
,STF YC
STFL
Figure 5.4. Single Line Diagram and Equivalent Circuit of CSI-IF with Single Tuned
Passive Filter
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
100
The impedance-frequency diagram of 135 Hz single tuned filter with power
system is shown in Figure 5.5. It is shown that the 135 Hz single tuned filter does not
create parallel resonance with system in the dominant harmonic frequencies of CSI-
IF. However, the impedance of this passive filter is slightly below the impedance of
power system in frequencies of dominant harmonics and interharmonics of CSI-IF so
this passive filters has very little filtering effect on harmonics and interharmonics of
CSI-IF and this filtering system is only suitable for reactive power compensation.
Filter +Network
Impedance
Only Network
Impedance
Figure 5.5. Impedance-Frequency Curve of Single Tuned Filter Designed for CSI-IF
This filtering characteristic of 2 MVAr passive filter tuned at 135 Hz is
shown in the PSCAD/EMTDC simulation program. The 2MVAr passive filter is
connected to the input of CSI-IF as shown in Figure 5.6.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
101
sysL
sysL
sysL
,a sourceI
,b sourceI
,c sourceI
aV
bV
cV
3 PHASE
POWER SUPPLY
31.5kV
Ssc = 335MVA
,a CSI IFI
,b CSI IFI
,c CSI IFI
,a STFI
,b STFI
,c STFI
CSI-IF
STFR
,STFC
STFL
STFR
STFL
STFR
STFL
,STFC
,STFC
Figure 5.6. Power Circuit Model of Single Tuned Filter
The waveforms of CSI-IF currents, source currents and single tuned filter
currents are shown in Figure 5.7, Figure 5.8 and Figure 5.9 respectively. It is shown
that there is nearly no change between the waveforms of CSI-IF currents and source
currents. Only the phase of source current is shifted by the effect of reactive power
compensation effect of single tuned filters.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
102
Figure 5.7. CSI-IF Current Waveform in Single Tuned Filter Simulation
Figure 5.8. Source Current Waveform in Single Tuned Filter Simulation
CSI-IF : Graphs
sec 1.000 1.010 1.020 1.030 1.040 1.050 1.060 1.070 1.080 1.090 1.100 ...
...
...
-0.40
-0.30
-0.20
-0.10
0.00
0.10
0.20
0.30
0.40
CS
I-IF
Curr
ents
(kA
)
Ia_CSI-IF Ib_CSI-IF Ic_CSI-IF
Source : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.40
-0.30
-0.20
-0.10
0.00
0.10
0.20
0.30
0.40
Supply
Curr
ent
(kA
)
Ia_source Ib_source Ic_source
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
103
Figure 5.9. Single Tuned Filter Current Waveform in Single Tuned Filter Simulation
The reactive powers drawn from source, CSI-IF and single tuned filters are
shown in Figure 5.10. It is shown that 2MVAr reactive power is supplied by single
tuned filters and reactive power drawn from the source decreases so by the help of
single tuned filters, reactive power compensation requirements of CSI-IF is provided
and reactive power demand of system is kept under the limits.
Figure 5.10. Reactive Powers Drawn From source, Drawn By CSI-IF and Drawn by
Single Tuned Filter in Single Tuned Filter Simulation
STF : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.080
-0.060
-0.040
-0.020
0.000
0.020
0.040
0.060
0.080
ST
F C
urr
ents
(kA
)
Ia_STF Ib_STF Ic_STF
SYS,CSI-IF,STF : Graphs
sec 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 ...
...
...
-3.0
-2.0
-1.0
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
React
ive P
ow
ers
(M
VA
r)
Q_sys Q_CSI-IF Q_STF
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
104
The harmonic spectrums of CSI-IF currents and source currents is given in
Figure 5.11 and Figure 5.12 while CSI-IF is operating at 175 Hz. The harmonic
spectrums in Figure 5.11 and Figure 5.12 show the harmonics with steps of 10 Hz in
order to indicate the interharmonics. In Figure 5.11 lower order harmonics and
interharmonics are presented with larger scale and in Figure 5.12 higher order
harmonics and interharmonics are presented with lower scale. When the harmonic
spectrums of CSI-IF currents and source currents are investigated, it shown that
single tuned filters has very little effect on filtering harmonics and interharmonics.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
105
Fig
ure
5.1
1.
Har
monic
Spec
trum
of
Low
er O
rder
Har
monic
s of
CS
I-IF
Curr
ent
and
Sourc
e C
urr
ent
in S
ingle
Tuned
Fil
ter
Sim
ula
tion
(a)
Har
monic
Spec
trum
of
CS
I-IF
Curr
ent
(b)
Har
monic
Spec
trum
of
Sourc
e C
urr
ent
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
106
Fig
ure
5.1
2.
Har
monic
Spec
trum
of
Hig
her
Ord
er H
arm
onic
s of
CS
I-IF
Curr
ent
and S
ourc
e C
urr
ent
in S
ingle
Tuned
Fil
ter
Sim
ula
tion
(a)
Har
monic
Spec
trum
of
CS
I-IF
Curr
ent
(b)
Har
monic
Spec
trum
of
Sourc
e C
urr
ent
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
107
5.1.2. C - Type Passive Filters
The C-type filters are generally used for attenuation of low order harmonics
and interharmonics created by HVDC transmission systems, EAFs and
cycloconverters (Bodger et al., 1990; Gerçek et al., 2011; Aravena et al., 2009). The
power circuit topology of C-type filter is shown in Figure 5.13. The C-type filters
show impedance and filtering characteristics between the 2nd
and 3rd
order high pass
filters. C-type filter is preferred because of the advantage in low losses in
fundamental frequency of power system. The series ,1CtypeL and
,1CtypeC in parallel with
the CtypeR is tuned to the fundamental frequency of power system.
CtypeR is, therefore,
bypassed by the zero impedance branch formed by the tuned ,1CtypeL and
,1CtypeC at
fundamental frequency. The filter thus behaves as a capacitor at the fundamental
frequency. There is little current flowing through the resistor and the loss is
minimized. As frequency increases, ,1CtypeL becomes resonating with
,1 ,2Ctype CtypeC C ,
what makes the filter behave as a single-tuned filter with a damping resistor. At high
frequencies, ,1CtypeL becomes large, and the current will flow through the resistive
branch, resulting in a performance similar to that of the first-order filter (Nassif et al.,
2009; Xiao et al., 2004).
,1CtypeL
,2CtypeC
CtypeR
,1CtypeC
Figure 5.13. Power Circuit Topology of C-Type Filter
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
108
The values of elements in the C-type filter can be designed by the following
equations. The series ,1CtypeL and
,1CtypeC are tuned to the system fundamental
frequency 1f so that;
1
,1 ,1
1
2 Ctype Ctype
fL C
(5.4)
The damping frequency of filter is commonly selected between the 2nd
and 6th
harmonics and it is determined as;
,1 ,2
,1
,1 ,2
1
.2
Ctype
Ctype Ctype
Ctype
Ctype Ctype
fC C
LC C
(5.5)
By using Eq. 5.4 and Eq. 5.5, the following relation between,1CtypeC and
,2CtypeC is
extracted;
2
,1 ,2
1
1Ctype
Ctype Ctype
fC C
f
(5.6)
The value ,2CtypeC is selected for the desired reactive power rating of the filter and it
must be large enough for the filter to be effective. ,1CtypeC is determined by using Eq.
5.6 and ,1CtypeL is determined by using Eq. 5.4 with the calculated
,1CtypeC value. The
damping resistance CtypeR is obtained by designating the desired quality factor
CtypeQF
for the filter at designed damping frequencyCtypef . For the filter to be effective, the
value CtypeQF should be selected below 5.
CtypeR is calculated as (Bodger et al., 1990);
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
109
,12 Ctype Ctype
Ctype
Ctype
f LR
QF
(5.7)
Using these equations a C-type filter is designed in order to compensate
power quality problems of modeled CSI-IF. The parameters of C-type filter designed
for CSI-IF is given in Table 5.2.
Table 5.2. Power Circuit Parameters of C-Type Filter Model
C-Type Passive Filter
CtypeQ = 2MVAr , Ctypef =100 Hz,
CtypeQF =1
,1CtypeL 526 mH
,1CtypeC 19.24 µF
,2CtypeC 6.415 µF
CtypeR 330 Ω
The single line diagram of C-type filters with CSI-IF and equivalent circuit
diagram for harmonic frequencies is shown in Figure 5.14. In harmonic frequencies
the 50 Hz voltage source acts as short circuited and CSI-IF acts as current source.
sysL
CSI-IF
sysL
CSI-IF
,CSI IF harI
Filter SystemZ
(a) (b)
,1CtypeL
,2CtypeC
CtypeR
,1CtypeC
,1CtypeL
,2CtypeC
CtypeR
,1CtypeC
Figure 5.14. Single Line Diagram and Equivalent Circuit of CSI-IF with C-Type
Filter
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
110
The impedance-frequency diagram of C-type filter with power system is
shown in Figure 5.15. It is shown that the C-type filter does not create any parallel
resonant with system because its quality factor is selected very low in order to
increase the damping effect but, unfortunately the impedance of C-type passive filter
with power system shows the same characteristics with power system impedance
below 900 Hz and above 900 Hz, the impedance of C-type passive filter with power
system gets slightly lower than the system impedance. Due to this impedance-
frequency curve of designed C-type filter, C-type filter has no filtering effect on
dominant harmonics and interharmonics of CSI-IF between 250 Hz and 650 Hz. This
filtering system only performes the reactive power requirements of CSI-IF.
2MVAr C-Type +Network
Impedance
Network Impedance
Figure 5.15. Impedance-Frequency Curve of C-Type Filter Designed for CSI-IF
If the damping of C-type filter is chosen at lower levels by selecting higher
CtypeQF value, the C-type filter designed for the modeled CSI-IF shows high
impedance with system impedance and causes amplification below 900 Hz as shown
in Figure 5.16. In this condition, all dominant harmonics and interharmonics of CSI-
IF is amplified and creates serious voltage distortion in PCC.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
111
As all the damped passive filters, C-type filters need high fundamental MVAr
ratings in order to achieve effective harmonic filtering. In Figure 5.17, the
impedance-frequency curves of C-type filters with power system are shown. In this
figure, C-type filters have different MVAr ratings and their quality factors are equal
to 1. It is clearly shown that the filtering performance is increased with increasing
reactive power rating of filter.
2MVAr C-Type +Network
Impedance
Q.F.=1
2MVAr C-Type +Network
Impedance
Q.F.=3
2MVAr C-Type +Network
Impedance
Q.F.=5
Network Impedance
Figure 5.16. Impedance-Frequency Curve of C-Type Filter with Different Quality
Factor
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
112
2MVAr C-Type +Network
Impedance
Network Impedance
10MVAr C-Type +Network
Impedance
30MVAr C-Type +Network
Impedance
60MVAr C-Type +Network
Impedance
90MVAr C-Type +Network
Impedance
Figure 5.17. Impedance-Frequency Curve of C-Type Filter with Different Reactive
Power Ratings
The filtering characteristic of 2 MVAr C-type filter tuned at 100 Hz is shown
in the PSCAD/EMTDC simulation program. The 2MVAr C type filter is connected
to the input of CSI-IF as shown in Figure 5.18.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
113
sysL
sysL
sysL
,a sourceI
,b sourceI
,c sourceI
aV
bV
cV
3 PHASE
POWER SUPPLY
31.5kV
Ssc = 335MVA
,a CSI IFI
,b CSI IFI
,c CSI IFI
,a C typeI
,b C typeI
,c C typeI
CSI-IF
,1CtypeL
,2CtypeC
CtypeR
,1CtypeC
,1CtypeL
,2CtypeC
CtypeR
,1CtypeC
,1CtypeL
,2CtypeC
CtypeR
,1CtypeC
Figure 5.18. Power Circuit Model of C-Type Filter
The waveforms of CSI-IF currents, source currents and C-type filter currents
are shown in Figure 5.19, Figure 5.20 and Figure 5.21 respectively. It is shown that
there is nearly no change in between the waveforms of CSI-IF currents and source
currents. Only the phase of source current is shifted by the effect of reactive power
compensation effect of C-type filters.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
114
Figure 5.19. CSI-IF Current Waveform in C-Type Filter Simulation
Figure 5.20. Source Current Waveform in C-Type Filter Simulation
When C-type filter current waveforms are investigated in Figure 5.21, the
filter has distorted current waveform. It shows that the C-type filter filters a part of
high frequency harmonics and interharmonics currents because of the lower
impedance of C-type filter than the system impedance above 900 Hz as shown in
impedance-frequency curve of designed filter.
CSI-IF : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.40
-0.30
-0.20
-0.10
0.00
0.10
0.20
0.30
0.40
CS
I-IF
Curr
ents
(kA
)
Ia_CSI-IF Ib_CSI-IF Ic_CSI-IF
Source : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.40
-0.30
-0.20
-0.10
0.00
0.10
0.20
0.30
0.40
Supply
Curr
ent
(kA
)
Ia_source Ib_source Ic_source
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
115
Figure 5.21. C-Type Filter Current Waveform in C-Type Filter Simulation
The reactive powers drawn from source, CSI-IF and C-type filter are shown
in Figure 5.22. It is shown that 2MVAr reactive power is supplied by C-type filters
and reactive power drawn from the source is decreased. By the help of C-type filter,
reactive power compensation requirements of CSI-IF is provided and reactive power
demand of system is kept under the limits.
Figure 5.22.Reactive Powers Drawn From source, Drawn By CSI-IF and Drawn by
C-Type Filter in C-Type Filter Simulation
C-type : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.080
-0.060
-0.040
-0.020
0.000
0.020
0.040
0.060
0.080
ST
F C
urr
ents
(kA
)
Ia_C-type Ib_C-type Ic_C-type
SYS,CSI-IF,C-type : Graphs
sec 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 ...
...
...
-3.0
-2.0
-1.0
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
React
ive P
ow
ers
(M
VA
r)
Q_sys Q_CSI-IF Q_C-type
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
116
The harmonic spectrums of CSI-IF currents and source currents is given in
Figure 5.23 and 5.24 while CSI-IF is operating at 175 Hz. The harmonic spectrums
show the harmonics with steps of 10 Hz in order to indicate the interharmonics. In
Figure 5.23 lower order harmonics and interharmonics are presented with larger
scale and in Figure 5.24 higher order harmonics and interharmonics are presented
with lower scale. When the harmonic spectrums of CSI-IF currents and source
currents are investigated, it is shown that C-type filters has no effect on filtering
harmonics and interharmonics below 900 Hz. C-type filter shows very little filtering
performance to harmonics and interharmonics above 900 Hz.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
117
Fig
ure
5.2
3. H
arm
onic
Spec
trum
of
Low
er O
rder
Har
monic
s of
CS
I-IF
Cu
rren
t an
d S
ourc
e C
urr
ent
in C
-Type
Fil
ter
Sim
ula
tion
(a)
Har
monic
Spec
trum
of
CS
I-IF
Curr
ent
(b)
Har
monic
Spec
trum
of
Sourc
e C
urr
ent
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
118
Fig
ure
5.2
4. H
arm
onic
Spec
trum
of
Hig
her
Ord
er H
arm
onic
s of
CS
I-IF
Cu
rren
t an
d S
ourc
e C
urr
ent
in C
-Type
Fil
ter
Sim
ula
tion
(a)
Har
monic
Spec
trum
of
CS
I-IF
Curr
ent
(b)
Har
monic
Spec
trum
of
Sourc
e C
urr
ent
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
119
5.1.3. Broad - Band Passive Filters
Unlike the shunt and series filters that have a narrow band of harmonic
suppression, broadband filters have a wider range of harmonics suppression property.
Broadband filters employ a combination of the two passive techniques, with a high
series impedance to block the undesired current harmonics (from flowing through the
grid) and a low shunt impedance path to divert their flow through the shunt filter.
They are tuned to a low cut off frequency such that only fundamental component will
pass from the input to the output (Win, 2008). In Figure 5.25, the most known broad-
band filter topologies; LC and LLCL are shown. These types of broad-band filters
are available in market especially for filtering harmonics caused by low voltage
ASDs. However, any high voltage application is not encountered in literature.
,BBF sL
,BBF Y sC
,BBF sR
,i BBFL
,o BBFL
BBFL
BBFC
(a) (b)
Figure 5.25. Broad Band Passive Filter Topologies
(a) LC Type Broad Band Passive Filter
(b) LLCL Type Broad Band Passive Filter
The LC type broadband filter is shown in Figure 5.25(a) and design of this
type filter is proposed by Swamy (1995). This type broad-band filter involves a
simple structure with relatively large components. Also, in particular at no-load the
filter output voltage becomes excessive. In order to prevent high voltage a buck
transformer is used instead of inductor in the filter. Moreover, the power factor is
largely leading at all load conditions to achieve effective harmonic filtering. Thus,
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
120
the filter does not yield overall a satisfactory performance (Swamy, 2005; Zubi et al.,
2010).
In distribution system applications, the effect of broadband filters can be
obtained by installing a capacitor bank on the low-voltage side of a substation
transformer. The size of the capacitor bank would have to be so selected to provide
the desired cutoff frequency when combined with the transformer leakage inductance
and the system impedance. It is then capable of preventing harmonics above the
cutoff frequency from penetrating the high-voltage side of the transformer. Since the
cutoff frequency can be sometimes quite low, the size of the capacitor bank may be
fairly large. This will result in a significant voltage rise. To keep the voltage of
system in rated values, load tap changer of transformer can be used (Dugan et al.,
1996). Again, because of the large capacitor values, over compensation problem
occurs in the system. Other restriction of such a broad-band passive filter occurs in
multi-feeder systems placed at the low voltage side of substation transformer. In
multi-feeder systems, using of large value capacitors under the substation
transformers can cause not estimated resonance problems with the nonlinear loads
connected under distribution transformers which are placed in feeders under the low
voltage side of substation transformer.
In the LLCL type broad-band filters, the tradeoff between the over voltage,
over reactive power compensation and filtering performance can be solved more
easily. As shown in Fig. 5.25(b), the LLCL broad-band filter is created by splitting
the L filter of the simple LC broadband filter into two elements as ,i BBFL and ,BBF sL ,
the filter input-to-output behavior is altered. Further, a 3-5% smoothing reactor
,o BBFL is inserted between the rectifier terminals and the filter output terminals.
Filter capacitors ,BBF Y sC are usually delta connected. ,BBF sR is represents the
internal resistance of inductor or an external damping resistor which can be used
additionally. ,BBF sR changes the damping characteristics of filter (Zubi et al., 2010).
There is limited information about the design and determining optimal
parameters of LLCL type broad-band passive filters in literature. In this thesis work,
by the help of the iteration based design methodology presented by Havva (2005)
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
121
and PSCAD/EMTDC simulation program optimal values of elements in the LLCL
type broad-band filter is determined for solving the power quality problems of
modeled CSI-IF.
The initial values of LLCL filter can be determined by using following
equations. The parallel resonance frequency of filter is determined as;
,
, , ,
1
2p BBF
i BBF BBF s BBF Y s
fL L C
(5.8)
The series resonance frequency of filter is determined as;
,
, ,
1
2s BBF
BBF s BBF Y s
fL C
(5.9)
The value ,BBF Y sC is selected for the desired reactive power rating of the filter. ,i BBFL
and ,BBF sL are determined using Eq. 5.8 and Eq. 5.9 with using calculated ,BBF Y sC
value. The parallel resonance frequency ,p BBFf of filter in Eq. 5.8 is selected near 2
nd
or 3rd
harmonic frequencies and the series resonance frequency,s BBFf of filter in Eq.
5.9 is selected slightly below the most dominant harmonic frequency of nonlinear
load. For CSI-IF the series resonance frequency of filter is selected below the
dominant frequencies of CSI-IF in order to prevent resonances. The damping
resistance ,BBF sR is obtained by designating the desired quality factor BBFQF for the
filter at designed parallel resonance frequency,p BBFf . ,BBF sR is calculated as;
, , ,
,
2 p BBF i BBF BBF s
BBF s
BBF
f L LR
QF
(5.10)
The smoothing reactor ,o BBFL is selected 3-5 % of load impedance value and
calculated as;
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
122
2
,
,
1
3 5 %2
L L rms
o BBF
Load
VL
f S
(5.11)
Using these equations initial values of LLCL type broad band filter is
determined in order to compensate power quality problems of modeled CSI-IF. The
specifications and initial values of LLCL type broad-band filter designed for CSI-IF
is given in Table 5.3.
Table 5.3.Initial Values for Power Circuit Parameters of LLCL Type Broad-Band
Filter Model
LLCL Type Broad-Band Filter
Initial Parameters
BBFQ = 2MVAr , ,p BBFf =150 Hz,
,s BBFf =250 Hz, 1.5BBFQF
,i BBFL 120 mH
,o BBFL 12 mH
,BBF sL 64 mH
,BBF sC 2.05µF
,BBF sR
34 Ω
The power quality design constraints of LLCL type broad-band filter are
input current THD, input power factor and filter output voltage regulation (Havva et
al., 2005). The LLCL type broad-band filter designed for CSI-IF should provide
input current THD below 5%, supply 2MVAr reactive power and keep the filter
output regulation below 5%. With initial values of LLCL filter, these desired
specifications of LLCL type filter for CSI-IF are not maintained. In order to maintain
these specifications the optimum values of filter is determined by the help of
simulation program. The specifications and final values of LLCL type filter designed
for modeled CSI-IF is shown in Table 5.4.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
123
Table 5.4. Final Values for Power Circuit Parameters of LLCL Type Broad-Band
Filter Model
LLCL Type Broad-Band Filter
Final Parameters
,i BBFL 42 mH
,o BBFL 12 mH
,BBF sL 36 mH
,BBF sC 3.7µF
,BBF sR
38 Ω
The single line diagram of LLCL filters with CSI-IF and equivalent circuit
diagram for harmonic frequencies is shown in Figure 5.26. In harmonic frequencies
the 50 Hz voltage source acts as short circuited and CSI-IF acts as current source.
sysL
CSI-IF
CSI-IF
,CSI IF harI
Filter SystemZ(a) (b)
,BBF sL
,BBF Y sC
,BBF sR
,i BBFL
,o BBFL sys
L
,BBF sL
,BBF Y sC
,BBF sR
,i BBFL
,o BBFL
Figure 5.26. Single Line Diagram and Equivalent Circuit of CSI-IF with LLCL Type
Broad Band Filter
(a) Single Line Diagram of CSI-IF with LLCL Type Broad Band Filter
(b) Equivalent Circuit of CSI-IF with LLCL Type Broad Band Filter at
harmonic frequencies
The impedance-frequency diagram of designed LLCL filter with power
system is shown in Figure 5.27. By investigating the impedance-frequency curve of
LLCL type filter, the filtering characteristic of LLCL type filter cannot be
determined because of the series inductors of filters.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
124
Figure 5.27. Impedance-Frequency Curve of LLCL Type Broad-Band Filter
Designed for CSI-IF
In order to show the filtering characteristic of LLCL filter, the AC analysis
technique is applied to the circuit shown in Figure 5.26(b). By applying 1A reference
from current source which represents the CSI-IF to the system in Figure 5.26(b), how
much current flow to system and shunt branch of LLCL filter is determined. As
shown in Figure 5.28, above the 250 Hz, approximately only 40 percentage of
reference current flow to the power system and 60 percentage of current flow to the
shunt branch of LLCL filter.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
125
Reference Current Current Drawn by
Shunt Brach of
BBF FilterCurrent Drawn by
Power System
Figure 5.28. Filtering Characteristic of LLCL Type Broad-Band Filter Designed for
CSI-IF
This effective filtering performance of designed LLCL type broad-band filter
is shown in the PSCAD/EMTDC simulation program. The LLCL type filter is placed
to the input of CSI-IF as shown in Figure 5.29.
sysL
sysL
sysL
,a sourceI
,b sourceI
,c sourceI
3 PHASE
POWER SUPPLY
31.5kV
Ssc = 335MVA
,a CSI IFI
,b CSI IFI
,c CSI IFI
,a BBFI
,b BBFI
,c BBFI
CSI-IF
,BBF sR
,BBF sC
,BBF sL
,BBF sR
,BBF sC
,BBF sL
,BBF sC
,BBF sR
,BBF sL
,o BBFL
,i BBFL
,o BBFL
,i BBFL
,o BBFL
,i BBFL
,a sourceV
,b sourceV
,c sourceV
, a CSI IFV
, b CSI IFV
, c CSI IFV
Figure 5.29. Power Circuit Model of LLCL Type Broad-Band Filter
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
126
The waveforms of CSI-IF currents, source currents and shunt branch of
LLCL filter currents are shown in Figure 5.30, Figure 5.31and Figure 5.32,
respectively. It is shown that LLCL type filter has effective filtering performance.
During the first second of simulation which the current waveforms are taken, THD of
CSI-IF current is 14.35 % and source current THD decreases to 4.85 %. During the
overall simulation time which CSI-IF operates from 150 Hz to 250 Hz, THD of CSI-
IF current is varying from 15.7 % to 7 % and source current THD is varying from 5
% to 2.5 %.
Figure 5.30. CSI-IF Current Waveform in LLCL-Type BBF Filter Simulation
CSI-IF : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.40
-0.30
-0.20
-0.10
0.00
0.10
0.20
0.30
0.40
CS
I-IF
Curr
ents
(kA
)
Ia_CSI-IF Ib_CSI-IF Ic_CSI-IF
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
127
Figure 5.31. Source Current Waveform in LLCL-Type BBF Filter Simulation
Figure 5.32. Current Waveform of Shunt Branch of LLCL Type Filter in LLCL-Type
BBF Filter Simulation
The waveforms of CSI-IF voltage and source voltage are shown in Figure
5.33 and Figure 5.34. respectively. The main drawback of LLCL type filter is shown
in Figure 5.34. Because of the high values of series inductors of LLCL filter, the
current harmonics and interharmonics cause significant voltage drop on the inductors
and create distorted voltage waveforms. During the first second of simulation which
the voltage waveform of CSI-IF is taken, the THD of CSI-IF voltage is 9.1%. During
Source : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.40
-0.30
-0.20
-0.10
0.00
0.10
0.20
0.30
0.40
Supply
Curr
ent
(kA
)
Ia_source Ib_source Ic_source
BBF : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.200
-0.150
-0.100
-0.050
0.000
0.050
0.100
0.150
0.200
BB
F C
urr
ents
(kA
)
Ia_BBF Ib_BBF Ic_BBF
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
128
the overall simulation time which CSI-IF operates from 150 Hz to 250 Hz, THD of
CSI-IF voltage is varying from 6.5 % to 12 %.
Figure 5.33. Source Voltage Waveform in LLCL-Type BBF Filter Simulation
Figure 5.34. CSI-IF Voltage Waveform in LLCL-Type BBF Filter Simulation
The reactive power drawn from source and CSI-IF are shown in Figure 5.35.
It is shown that LLCL type filter provides irregular reactive power compensation. At
the beginning of simulation CSI-IF operates at low power and after 6th
second of the
simulation CSI-IF reaches the maximum power. The reactive power value of the
SYS : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-40
-30
-20
-10
0
10
20
30
40
Supply
Voltages
(kV
)
Va_source Vb_source Vc_source
CSI-IF : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-40
-30
-20
-10
0
10
20
30
40
CS
I-IF
Voltages
(kV
)
Va_CSI-IF Vb_CSI-IF Vc_CSI-IF
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
129
LLCL filter is designed to rated power furnace and when the CSI-IF operates at the
rated power, LLCL filter supplies 2 MVAr reactive power as shown in Figure 5.35.
When the CSI-IF operates at low powers, the current magnitude of CSI-IF decreases
as expected. When the current of CSI-IF decreases, the voltage drop on ,i BBFL
decreases and the voltage at the connection point of shunt branch of filter increased.
Thus, increasing of voltage at the connection point of shunt branch of filter increases
the reactive power supplied by the capacitor so when the CSI-IF operates at lower
powers the reactive power supplied from filter is increased. By the help of designing
the voltage regulation of filter 4.96 %, the reactive power capacity of LLCL filter is
kept so as to avoid over compensation of CSI-IF as shown in Figure 3.35.
Figure 5.35. Reactive Powers Drawn From source and Drawn By CSI-IF in LLCL
Type Filter Simulation
The harmonic spectrums of CSI-IF currents and source currents are given in
Figure 5.36 and Figure 5.37 while CSI-IF is operating at 175 Hz. The harmonic
spectrums in Figure 5.36 and Figure 5.37 show the harmonics with steps of 10 Hz in
order to indicate the interharmonics. In Figure 5.36 lower order harmonics and
interharmonics are presented with larger scale and in Figure 5.37 higher order
harmonics and interharmonics are presented with lower scale. When the harmonic
spectrums of CSI-IF currents and source currents are investigated, it is shown that
SYS,CSI-IF : Graphs
sec 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 ...
...
...
-1.00
-0.50
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
5.00
React
ive P
ow
ers
(M
VA
r)
Q_sys Q_CSI-IF
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
130
LLCL type filter eliminates approximately 60 % of harmonic and interharmonic
currents.
The harmonic spectrum of CSI-IF voltage harmonics is given in Figure 5.38
while CSI-IF is operating at 175 Hz. It is shown that the same harmonics and
interharmonics in the load current occur at the voltage harmonic spectrum.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
131
Fig
ure
5.3
6.
Har
monic
Spec
trum
of
Low
er O
rder
Har
monic
s of
CS
I-IF
Curr
ent
and S
ourc
e C
urr
ent
in L
LC
L T
ype
Bro
ad-B
and
Pas
sive
Fil
ter
(a)
Har
monic
Spec
trum
of
CS
I-IF
Curr
ent
(b)
Har
monic
Spec
trum
of
Sourc
e C
urr
ent
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
132
Fig
ure
5.3
7.
Har
monic
Spec
trum
of
Hig
her
Ord
er H
arm
onic
s of
CS
I-IF
Curr
ent
and S
ourc
e C
urr
ent
in L
LC
L T
ype
Bro
ad-B
and
Pas
sive
Fil
ter
Sim
ula
tion
(a)
Har
monic
Spec
trum
of
CS
I-IF
Curr
ent
(b)
Har
monic
Spec
trum
of
Sourc
e C
urr
ent
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
133
Fig
ure
5.3
8. H
arm
onic
Spec
trum
of
CS
I-IF
Volt
age
LL
CL
Type
Bro
ad-B
and P
assi
ve
Fil
ter
Sim
ula
tion
(a)
Low
er O
rder
Har
mon
ics
wit
h L
arge
Sca
le
(b)
Hig
her
Ord
er H
arm
onic
s w
ith L
ow
er S
cale
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
134
5.2. Hybrid Active Power Filters
In order to form an effective compensation system and decrease loading of
APFs in high power applications, APF and passive filter combinations which are
named as HAPF are commonly used. The most common HAPF types which are
introduced in Section 3.3.2 are shunt APF - shunt passive filter combination, series
APF - shunt passive filter combination and APF series with shunt passive filter
combination which is also named as shunt hybrid active power filter (SHAPF).
The PQ problems of modeled CSI-IF is presented in Section 4 and the
inadequate PQ compensation performances of passive filters are proposed in section
5.1. To solve PQ problems and reactive power compensation of CSI-IF with only
pure active power filters is theoretically possible with increasing the number of APFs
or using multilevel topologies, but in practice because of the cost and design
complexities, such a system formed from pure APFs is not feasible. Because of
these, HAPFs has an important role in high power applications. In this section of
thesis, shunt APF - shunt passive filter type HAPF and SHAPF systems are designed
for power quality and reactive power compensation of the modeled CSI-IF and, their
performances and ratings are investigated.
5.2.1. Shunt Active Power Filter and Parallel Passive Filter Combination
5.2.1.1. Power Circuit Configuration of Proposed HAPF System
The proposed HAPF formed from shunt APF and shunt passive filter for
compensating the power quality problems of modeled CSI-IF is shown in Figure
5.39. The shunt APF is formed from two identical modules which are connected to
31.5 kV busbar via transformer. The proposed APF is divided into two module which
are formed from 2 level bridge VSI based APFs because of the large current ratings
of compensating harmonics and interharmonics of CSI-IF. In Section 4, the dominant
harmonics and interharmonics of CSI-IF are presented. The harmonics and
interharmonics content of CSI-IF are at higher values when the furnace operates at
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
135
lower frequencies. The maximum rms value of the harmonics and interharmonics of
CSI-IF formed at the same time are calculated 35A-rms at 31.5k V level. The shunt
APF must be connected to 31.5kV level via transformer because of the limits of
power semiconductor devices in VSI. In proposed design 31.5/1 kV Y-Y connected
transformer is used to connect APF to the 31.5kV busbar. APF must produce 1100A-
rms at 1kV level in order to compensate the harmonic and interharmonic currents of
CSI-IF. This is possible with very little input reactor value and extremely high DC
link voltage value. DC link voltage value of APF is limited with the ratings of power
semiconductors in the VSI. Instead of 2 level VSI, multilevel inverters can be
preferred but, multilevel inverters have disadvantages in control complexity and high
costs. Because of these reasons, shunt APF is divided into two identical modules.
CSI-IF3 PHASE
POWER SUPPLY
31.5kV
Ssc = 335MVA
3MVA
Y/Y
31.5/1kV
PASSIVE
FILTER
Q=2MVAR
SHUNT APF SYSTEM
SHUNT APF
MODULESHUNT APF
MODULE
Figure 5.39. Proposed HAPF System for CSI-IF
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
136
The power circuit configuration of APF module is formed from interface
inductor, VSI and DC-Link Capacitor as shown in Figure 5.40. The interface
inductors establish a link between VSI and power system. Also the interface
inductors convert the VSI voltage to the current and allow APF to act as a current
source. The value of interface inductor is very crucial in the performance of the
APFs. If a small value of interface inductor is selected, then large switching ripples
are injected into the supply currents, and a large value of interface inductor does not
allow proper tracking of the compensating currents close to the desired values (Singh
et al., 1999). VSI which generates compensating currents with using capacitor
voltage is the main part of APF. Three phase 2 level bridge inverter is the most used
topology in APF applications. DC link voltage must be higher than the peak value of
the utility voltage, otherwise the generated compensation currents cannot be injected
to the power system (Uçak, 2010). DC link capacitors are used as energy storage
elements. APF eliminates harmonics and/or other power quality problems by
supplying energy to DC link capacitors and/or consuming energy from DC link
capacitors. DC link capacitor value of the APF is another important parameter. With
a small value of, large ripples in the steady state and wide fluctuations in the DC link
voltage under transient conditions are observed. A higher value of reduces ripples
and fluctuations in the dc-bus voltage, but increases the cost and size of the system
(Singh et al., 1999).
VSI
INTERFACEINDUCTORS
DC LINK
Figure 5.40. Power Circuit Configuration of APF Modules
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
137
In proposed HAPF system, the reactive power compensation of CSI-IF is
performed by 2 MVAr single tuned passive filters tuned at 135 Hz. The design and
performance of this filter are investigated in Section 5.1.1, it is shown that this 2
MVAr single tuned filter tuned at 135 Hz does not cause any resonance problem and
performs the reactive power requirements of CSI-IF successfully.
5.2.1.2. Control Method of APF Modules in Proposed HAPF System
In the proposed HAPF System, the controllers of each APF modules are
different but the same control method is used at both of the controllers of APF
modules. The block diagram of control method of APF modules is shown in Figure
5.41. It is shown that the control method of APF modules is formed from the
harmonic current extraction, DC link voltage controller and current controller. The
harmonic current extraction method uses the source currents which are the controlled
variables of this control method so the proposed controller method has a feedback
control configuration and APFK is the feedback gain of the controller.
Harmonic
Extraction
DC Link
Controller
Current
Controller
VSI
&
Interface
Reactor
+hI
X
APFK
-
,cap APFV
sourceV
,capref APFI
,ref APFI
+
-
,error APFI
+
-Gate
Signals APFI
sourceI
CSI IFI
sourceI
Figure 5.41. Control Method of Shunt APF Modules in Proposed HAPF System
(1) Harmonic Extraction Method:The block diagram of harmonic current
extraction method used in control method of APF modules is shown in Figure
5.43. In this thesis study, in order to calculate the reference harmonic currents,
an adaptive filtering method named enhanced phase locked loop (EPLL) method
is used. The reason of preferring EPLL is that it has simple structure than most
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
138
preferred time based and frequency based methods and it has fast and accurate
harmonic extraction capability with changing load conditions.
,a sourceI EPLL
,a hI
,b sourceI EPLL
,b hI
,c sourceI EPLL
,c hI
Figure 5.42. Harmonic Extraction Method in Shunt APF Modules
EPLL is proposed by Karimi-Ghartemani and Irvani (2001). The EPLL is
formed from three main parts as conventional phase lock loop (PLL) as shown in
Figure 5.43. These are phase detector (PD), low pass filter (LPF) and voltage
controlled oscillator (VCO). The structure and functions of LPF and VCO in EPLL is
same as LPF and VCO of PLL. The innovation is performed in PD of EPLL. The
new PD adds new features like amplitude estimation, in phase output signal and
more robust and stable loop than conventional PLL. Moreover EPLL has higher
convergence time than conventional PLL. These new features are performed by
changing the structure of PD. The amplitude estimation feature is achieved by adding
a peak detector mechanism into PD. There is used very basic peak detector
mechanism but this structure has many successful effects on the stability, robustness
and convergence time of loop. The speed, accuracy and robustness of EPLL is
proved by Karimi-Ghartemani et al. (2002; 2005).
The EPLL receives the input signal iI and provides an on-line estimate of the
following signals (Karimi-Ghartemani et al., 2004):
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
139
The synchronized fundamental component, ( )fI t
The amplitude, ( )fA t , of ( )fI t .
The phase angle, ( )f t , of ( )fI t .
Time-derivatives of the amplitude, phase and frequency.
The error signal, ( ) ( ) ( )i fe t I t I t , is the total distortion signal of the
input.
x + +
PHASE DETECTOR
PD
LOW-PASS FILTER
LPF
VOLTAGE-CONTROLLED
OSCILLATOR
VCO
+x
-
x
iI
AK
PK
iK
s1
s1
fA
s1
sin
sin
2
fI
o
f
e
Figure 5.43. Structure of EPLL
The gains and time constants of integrals can affect the lock time of loop,
amplitude estimation time and phase accuracy of input signal. Increasing the value of
Ka decreases the estimation time of amplitude and loop lock time but if Ka is
increased so much, it will start to increase the oscillations in the amplitude signal and
disturb the shape of fundamental signal. Decreasing Ka and Kp yields an estimation
of the peak which is insensitive/robust to the undesirable variations and noise in the
input signal (Karimi-Ghartemani et al., 2005).
When the distorted current or voltage signal is applied to EPLL, the
harmonics and interharmonics of distorted signal can be obtained from the ( )e t signal
of EPLL. The performance of EPLL is shown in PSCAD/EMTDC program. The
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
140
current signal of CSI-IF is applied to the EPLL, EPLL extracts the fundamental
components and harmonics and interharmonics of CSI-IF current successfully as
shown in Figure 5.44.
Figure 5.44. Distorted Input signal, Extracted Fundamnetal Signal and Extracted
Harmonics of EPLL
EPLL : Graphs
sec 1.0000 1.0050 1.0100 1.0150 1.0200 1.0250 1.0300 1.0350 1.0400 1.0450 1.0500 ...
...
...
-0.40
-0.30
-0.20
-0.10
0.00
0.10
0.20
0.30
0.40
CS
I-IF
Curr
ent
(kA
)
Ia_CSI-IF
-0.40
-0.30
-0.20
-0.10
0.00
0.10
0.20
0.30
0.40
Fun.C
om
p.o
fCS
I-IF
Cur.
(kA
)
Ia_CSI-IF_fun
-0.100
-0.080
-0.060
-0.040
-0.020
0.000
0.020
0.040
0.060
0.080
0.100
Harm
.ofC
SI-
IFC
ur.
(kA
)
Ia_CSI-IF_har
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
141
(2) DC Link Voltage Controller:The active filter does not require any external dc
power supply, because it can build up and regulate the dc voltage across the
capacitor by itself (Tangtheerajaroonwong et al., 2007). The DC link control of
Shunt APF is achieved by control of active power. In ideal conditions APF does
not consume any active power but due to switching and conduction losses of
switching devices, and resistance of inverter output filter, APF must consume
active power to control the DC link voltage. The block diagram of DC link
controller is shown in Figure 5.45. DC link voltage control is achieved by using
PI controller. In order to keep DC link voltage at a constant level, APF must
draw active power by drawnig current in phase with line voltage. To draw a
current in the same phase with system voltage, phase information of system
voltage must be known. This can be achieved by using EPLL. When the phase
voltage of system is applied to EPLL, EPLL gives the phase information of
system voltage. With using phase of system voltage, DC link control reference
current signal is created by multiplying the PI controller output and sinewave
created by phase information of system voltage as shown in Figure 5.45.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
142
,capset APFV
+
-
PI
CONTROL
,cap APFV
,cappi APFV
,a sourceV EPLL
_ ,a f sourceV
+
-
+
+
sin
sin
sin
X
X
X
_ ,a capref APFI
_ ,b capref APFI
_ ,c capref APFI
2 3
2 3
,cappi APFV
,cappi APFV
,cappi APFV
Figure 5.45. DC Link Voltage Control of Shunt APF Modules
(3) Current Controller:In the current controller of APF modules, PWM switching
method is used as shown in Figure 5.46. The switching pulses are generated by
comparing the difference of reference current and APF current with triangular
wave. PWM switching method obtains a constant switching frequency to the
power electronics devices in VSI. This is important because in high voltage
applications, power electronics devices have limited switching frequency
capabilities because of the turn-on and turn-off times and switching losses.
Because of these, the switching frequency of power electronics devices in APF
modules is selected as 3000 Hz.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
143
+
-Triangular
Wave
_ ,a ref APFI
+
-
,a APFI
+
-Triangular
Wave
_ ,b ref APFI
+
-
,b APFI
+
-Triangular
Wave
_ ,c ref APFI
+
-
,c APFI
G
A
T
E
S
I
G
N
A
L
S
Figure 5.46. Current Control of Shunt APF Modules
5.2.1.3. Simulation Results of Proposed HAPF System
The performance of the proposed HAPF system in compensating the PQ
problems of CSI-IF is investigated in PSCAD/EMTDC simulation program. In this
section the simulation results of system is presented. The proposed HAPF system is
connected to the input of CSI-IF as shown in Figure 5.47. The power circuit
parameters of proposed HAPF used in simulation program are given in Table 5.5.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
144
sysL
sysL
sysL
,a sourceI
,b sourceI
,c sourceI
,a sourceV
,b sourceV
,c sourceV
3 PHASE
POWER SUPPLY
31.5kV
Ssc = 335MVA
,a CSI IFI
,b CSI IFI
,c CSI IFI
,a STFI
,b STFI
,c STFI
CSI-IF
STFR
STFC
STFL
STFR
STFC
STFL
STFC
STFR
STFL
,a APFsI
,b APFsI
,c APFsI
1APFI 2APF
I
, a CSI IFV
, b CSI IFV
, c CSI IFV
, 1cap APFV, 2cap APFV-+ -+
APFL APF
L
,dc APFC
,dc APFC
3MVA
Y/Y
31.5/1kV
Figure 5.47. Power Circuit Model of Proposed HAPF System
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
145
Table 5.5. Power Circuit Parameters of HAPF System
The Proposed HAPF System
Coupling Transformer
3MVA
31.5/1kV Y/Y
Vsc%=%2
Shunt APF Module APFL = 100µH
,dc APFC = 25mF
Single Tuned
Passive Filter
STFQ = 2MVAr
STFf =135 Hz
STFQF =50
STFL =251mH
,STFC =1.845µF
STFR =4.26Ω
The waveforms of CSI-IF currents, current drawn from the connection point
of CSI-IF and single tuned filter, source currents are shown in Figure 5.48, 5.49 and
5.50 respectively. It is shown that proposed HAPF system cannot filter harmonics
and interharmonic currents of CSI-IF completely but it has sufficient filtering
performance on keeping the harmonic currents under the limits. During the first
second of the simulation which the current waveforms are taken, THD of CSI-IF
current is 14.35 % and source current THD decreases to 4.1 %. During the overall
simulation time which CSI-IF operates from 150 Hz to 250 Hz, THD of CSI-IF
current is varying from 15.7 % to 7 % and source current THD is varying from 4.5 %
to 2 %.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
146
Figure 5.48. CSI-IF Current Waveform in Proposed HAPF Simulation
Figure 5.49. CSI-IF and STF Current Waveform in Proposed HAPF Simulation
CSI-IF : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.40
-0.30
-0.20
-0.10
0.00
0.10
0.20
0.30
0.40
CS
I-IF
Curr
ents
(kA
)
Ia_CSI-IF Ib_CSI-IF Ic_CSI-IF
CSI-IF+STF : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.40
-0.30
-0.20
-0.10
0.00
0.10
0.20
0.30
0.40
CS
I-IF
+S
TF
Curr
ents
(kA
)
Ia_CSI-IF+STF Ib_CSI-IF+STF Ic_CSI-IF+STF
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
147
Figure 5.50. Source Current Waveform in Proposed HAPF Simulation
In Figure 5.51 and Figure 5.52, compensating currents of passive filters and
APFs are shown. APFs in proposed HAPF system generates harmonic and
interharmonic currents whereas the passive filter provides 2MVAr reactive power
requirement of CSI-IF in order to compensate the PQ problems of CSI-IF.
Figure 5.51. STF Currents in Proposed HAPF Simulation
SYS : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.40
-0.30
-0.20
-0.10
0.00
0.10
0.20
0.30
0.40
Sourc
e C
urr
ents
(kA
)
Ia_source Ib_source Ic_source
STF : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.080
-0.060
-0.040
-0.020
0.000
0.020
0.040
0.060
0.080
ST
F C
urr
ents
(kA
)
Ia_STF Ib_STF Ic_STF
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
148
Figure 5.52. High Voltage Side APFs Currents in Proposed HAPF Simulation
The harmonic spectrums of CSI-IF currents and source currents are given in
Figure 5.53 and Figure 5.54 while CSI-IF is operating at 175 Hz. The harmonic
spectrums in Figure 5.53 and Figure 5.54 show the harmonics with steps of 10 Hz in
order to indicate the interharmonics. In Figure 5.53 lower order harmonics and
interharmonics are presented with larger scale and in Figure 5.54 higher order
harmonics and interharmonics are presented with lower scale. When the harmonic
spectrums of CSI-IF currents and source currents are investigated, it is shown that
proposed HAPF system eliminates approximately 60 % of harmonic and
interharmonic currents.
APFs : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.060
-0.040
-0.020
0.000
0.020
0.040
0.060
AP
FsC
ur.
A (
kA)
Ia_APFs
-0.060
-0.040
-0.020
0.000
0.020
0.040
0.060
AP
FsC
ur.
B (
kA)
Ib_APFs
-0.060
-0.040
-0.020
0.000
0.020
0.040
0.060
AP
FsC
ur.
C (
kA)
Ic_APFs
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
149
Fig
ure
5.5
3.
Har
monic
S
pec
trum
of
Low
er
Ord
er
Har
monic
s of
CS
I-IF
C
urr
ent
and
Sourc
e C
urr
ent
in
Pro
pose
d
HA
PF
Sim
ula
tion
(a)
Har
monic
Spec
trum
of
CS
I-IF
Curr
ent
(b)
Har
monic
Spec
trum
of
Sourc
e C
urr
ent
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
150
Fig
ure
5.5
4. H
arm
on
ic
Spec
tru
m
of
Hig
her
O
rder
H
arm
on
ics
of
CS
I-IF
C
urr
ent
and
Sourc
e C
urr
ent
in
Pro
pose
d
HA
PF
Sim
ula
tion
(a)
Har
monic
Spec
trum
of
CS
I-IF
Curr
ent
(b)
Har
monic
Spec
trum
of
Sourc
e C
urr
ent
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
151
In Figure 5.55, the voltage waveforms measured from the input of CSI-IF is
given. It is shown that the distortion caused by the low order harmonics and
interharmonics of CSI-IF are not seen at the voltage waveform. However, switching
noise of APFs in the proposed system causes high frequency distortion in the voltage
waveform because of the weak power system.
Figure 5.55. CSI-IF Voltage Waveform in Proposed HAPF Simulation
The reactive powers drawn from source, CSI-IF and single tuned filters of
proposed HAPF are shown in Figure 5.56. It is shown that 2MVAr reactive power is
supplied by single tuned filters of proposed HAPF system and reactive power drawn
from the source is decreased. By the help of the proposed system, reactive power
compensation requirements of CSI-IF is provided and reactive power demand of
system is kept under the limits.
CSI-IF : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-30
-20
-10
0
10
20
30
CS
I-IF
Voltages
(kV
)
Va_CSI-IF Vb_CSI-IF Vc_CSI-IF
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
152
Figure 5.56. Reactive Powers Drawn From source, Drawn By CSI-IF and Drawn By
Single Tuned Filter in HAPF Simulation
In Figure 5.57 and Figure 5.58 the injected currents of each APF modules in
the HAPF system are presented. It is seen that the identical APF modules are
generating the same injected currents in same amplitudes. The peak points of injected
currents of each APF module reach to 800A.
SYS,STF,CSI-IF : Graphs
sec 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 ...
...
...
-3.00 -2.50
-2.00 -1.50 -1.00 -0.50
0.00 0.50 1.00 1.50
2.00 2.50 3.00 3.50
4.00 4.50 5.00
React
ive P
ow
ers
(M
VA
r)
Q_source Q_STF Q_CSI-IF
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
153
Figure 5.57. Injected Current Waveform of APF1 in Proposed HAPF Simulation
APF1 : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.80
-0.40
0.00
0.40
0.80
AP
F1C
urA
(kA
)
Ia_APF1
-0.80
-0.40
0.00
0.40
0.80
AP
F1C
urB
(kA
)
Ib_APF1
-0.80
-0.40
0.00
0.40
0.80
AP
F1C
urC
(kA
)
Ic_APF1
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
154
Figure 5.58. Injected Current Waveform of APF2 in Proposed HAPF Simulation
In Figure 5.59 and Figure 5.60, the DC link voltage trends of each APF
module are presented. It is shown that the DC link voltage controllers of APF
modules operate successfully and keep the DC link voltage at constant 2000V level.
Also the ripples of DC link voltages are in sufficient levels. Besides the switching
ripples in the DC link voltage there is a non-regular ripple is seen on the DC link
voltage. This non-regular ripple is caused by the time varying harmonics and
interharmonics of CSI-IF.
APF2 : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.80
-0.40
0.00
0.40
0.80
AP
F2C
urA
(kA
)
Ia_APF2
-0.80
-0.40
0.00
0.40
0.80
AP
F2C
urB
(kA
)
Ib_APF2
-0.80
-0.40
0.00
0.40
0.80
AP
F2C
urC
(kA
)
Ic_APF2
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
155
Figure 5.59. DC Link Voltage Waveform of APF1 in Proposed HAPF Simulation
Figure 5.60. DC Link Voltage Waveform of APF2 in Proposed HAPF Simulation
The reference currents which are calculated in the controllers and injected
currents of each APF module in HAPF system are shown in Figure 5.61 and Figure
5.62. It is shown that in both of APF modules, the injected currents cannot catch the
reference currents so the reference currents cannot be completely generated by APF
modules of HAPF. At this point, the DC link voltage of APF modules must be
increased in order to generate calculated reference currents completely. However, it
APF1 : Graphs
sec 1.000 1.020 1.040 1.060 1.080 1.100 1.120 1.140 1.160 1.180 1.200 ...
...
...
1.900
1.920
1.940
1.960
1.980
2.000
2.020
2.040
2.060
2.080
2.100
AP
F1 D
C-L
INK
Voltage (
kV)
Vcap_APF1
APF2 : Graphs
sec 1.000 1.020 1.040 1.060 1.080 1.100 1.120 1.140 1.160 1.180 1.200 ...
...
...
1.900
1.920
1.940
1.960
1.980
2.000
2.020
2.040
2.060
2.080
2.100
AP
F2 D
C-L
INK
Voltage (
kV)
Vcap_APF2
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
156
is not feasible to realize such a 3 phase 2 level VSI with DC link voltage over 2000V
in practical applications, because of the limited ratings of power electronics devices.
Figure 5.61. Reference Current and Injected Current Waveforms of APF1 in
Proposed HAPF Simulation
Figure 5.62. Reference Current and Injected Current Waveforms of APF2 in
Proposed HAPF Simulation
According to these simulation results, each VSI power rating in APFs of
HAPF system is calculated as ;
APF1_Control,APF1 : Graphs
sec 1.0000 1.0050 1.0100 1.0150 1.0200 1.0250 1.0300 1.0350 1.0400 ...
...
...
-1.50
-1.00
-0.50
0.00
0.50
1.00
1.50
AP
F1 R
ef&
Inje
cted C
urr
ents
(kA
)
Ia_ref_APF1 Ia_APF1
APF2_Control,APF2 : Graphs
sec 1.0000 1.0050 1.0100 1.0150 1.0200 1.0250 1.0300 1.0350 1.0400 ...
...
...
-1.60
-1.20
-0.80
-0.40
0.00
0.40
0.80
1.20
1.60
AP
F1 R
ef&
Inje
cted C
urr
ents
(kA
)
Ia_ref_APF2 Ia_APF2
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
157
, ,3
2 2
cap APF APF peak
HAPF VSI
V IS (5.12)
From Eq. 5.12, the each converter power rating is find as,
2000 8003 1385
2 2HAPF VSI
V AS kVA (5.13)
And total power ratings of converters of APFs in proposed HAPF is approximately
equal to 2 1385 2770kVA kVA .
5.2.2. Active Power Filter Series with Passive Filter Combination: SHAPF
5.2.2.1. Power Circuit Configuration of Proposed SHAPF System
The proposed SHAPF for PQ problems of CSI-IF is formed from two parallel
connected SHAPF modules which are connected to 31.5kV busbar via 31.5/1 kV Y-
Y connected transformer as shown in Figure 5.62. The proposed SHAPF is divided
into two identical module because the passive filter ratings cause high APF currents
in order to obtain the reactive power requirements of CSI-IF. From the simulation
results of CSI-IF in Section 4, it is determined that 2 MVAr compensation system is
necessary for keeping the reactive power demand of system under the limits. This
causes approximately 1150 A-rms to flow into the APF converter. Also as introduced
in the Section 5.2.1.1, in order to compensate the harmonic and interharmonic
current of CSI-IF additionally 1100 A-rms must be drawn by the SHAPF. In total,
approximately 1600 A-rms must be drawn by SHAPF and also by APF converter. In
SHAPF topology this high value of harmonic and interharmonic currents do not
cause extremely high DC link voltage in converter of SHAPF as in pure shunt APF,
because due to the presence of the LC filter, the fundamental voltage is decoupled
from the power system, thus reducing the voltage rating of the active filter (Inzunza
et al.,2005). If a single branch SHAPF is designed for PQ problems of CSI-IF,
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
158
1600A-rms current must be drawn by SHAPF and APF converter. This problem may
be solved by using high power rating power electronic devices but using of high
power devices in high switching frequencies cause serious switching losses. Because
of these problems, the proposed SHAPF is designed with two SHAPF by placing the
passive filters to the low voltage side of the transformers.
CSI-IF3 PHASE
POWER SUPPLY
31.5kV
Ssc = 335MVA
3MVA
Y/Y
31.5/1kV
SHAPF SYSTEM
SHAPF
MODULE
SHAPF
MODULE
Figure 5.63. Proposed SHAPF System for CSI-IF
The compensation characteristic of SHAPFs is different from pure shunt
APFs. In pure shunt APF, APF acts as current source and filtering the harmonic
currents of nonlinear load by injecting the reverse of the harmonic currents to the
power system. In SHAPF, the passive filter suppresses harmonic currents produced
by the load, whereas the active filter improves the filtering characteristics of the
passive filter by acting as a harmonic isolator between the source and the load (Fujita
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
159
et al., 1991). This compensation characteristic of SHAPF is explained with single
branch SHAPF. The single line equivalent circuits of SHAPF compensation system
is shown in Figure 5.64.
(c)
sysZ
+-
PFZ
sourceI
,load hIPFI
sysZ
+-
PFZ
,source hI
,load hI,PF hI
,SHAPF SHAPF source hV K I
sysZ
PFZ
,source hI
,load hI,PF hI
SHAPFK
(a) (b)
Figure 5.64. Single Line Equivalent Circuit of SHAPF
In Figure 5.64(a), the 50 Hz equivalent circuit of system is represented.
Assuming that the active power filter is an ideal controllable voltage source APFV ,
and that the load is a current source loadI . sV is the source voltage , sysZ is the source
impedance, PFZ is the impedance of single tuned filter, sourceI is the source current
and PFI represents the passive filter current. In Figure 5.64(b) the harmonic
equivalent of circuit in Figure 5.64(a) is given. In harmonic frequencies, sV is equal
to zero, and represented as short circuited. The controllable voltage source APFV
depends on the source harmonic currents as,
,APF SHAPF source hV K I (5.14)
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
160
where SHAPFK is the feedback gain of SHAPF controller. If the circuit in Figure
5.64(b) is analyzed by applying Kirchhoff’s laws with Superposition Theorem, shI is
found as;
,PFh
source h
PFh sysh SHAPF
ZI
Z Z K
(5.15)
Eq. 5.15 shows that APF acts as a resistor in circuit shown in Figure 5.64(c)
to damp parallel resonance between sysZ and PFZ , and increase the filtering
performance of passive filter (Fujita et al., 1991; Srianthumrong et al., 2003). From
the Eq. 5.15, it is shown that theoretically the harmonic content of the source current
goes to zero when SHAPFK approaches to infinity. However due to the stability
problems in the control loop, the gain SHAPFK should be limited to certain values
(Uçak, 2010).
The power circuit configuration of one SHAPF module of proposed system is
formed form single tuned filter, VSI and DC-Link capacitor shown in Figure 5.65.
VSI is the main part of SHAPF and generates voltage reference signal in order to
maintain the harmonic isolation between passive filter and system. Three phase 2
level bridge inverter topology can be easily used through the low DC link voltage of
SHAPF. As in the pure shunt APF, DC link capacitors are used as energy storage
elements. The DC link capacitor value has enough value to keep the DC link voltage
ripple in acceptable limits.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
161
VSI
PASSIVEFILTERS
DC LINK
Figure 5.65. Power Circuit Configuration of SHAPF Modules
In proposed SHAPF system, the design of single tuned filter is realized
according to reactive power demand and the harmonic spectrum of CSI-IF currents.
The power ratings of single tuned filters in each SHAPF module are determined as
1MVAr in order to meet the reactive power demand of CSI-IF. The tuned frequency
of passive filter in SHAPF is generally selected the most dominant harmonic
frequency of load current (Cheng, 1998). The dominant harmonics of CSI-IF are
changed with operating frequency of furnace and they are seen between 250Hz and
650Hz as introduced in Section 4. In order to maintain equal filtering characteristic
between 250 Hz and 650 Hz, tuning frequency of passive filters is selected at 300Hz.
The filter values are determined by using the design equations of single tuned filter
in Section 5.1.1. In the design of single tuned filter of proposed SHAPF, the
transformer leakage reactance must be taken into account when inductor value of
passive filter is calculated. The filtering characteristics of only one module and both
of two modules of proposed SHAPF system at different SHAPFK values are shown in
Figure 5.66 and Figure 5.67 respectively. It is shown that proposed SHAPF system
obtain effective filtering in wide harmonic spectrum range.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
162
KSHAPF=1
KSHAPF=1.5
KSHAPF=2
Figure 5.66. Filtering Characteristics of a Single SHAPF Module with Different
SHAPFK Values
KSHAPF=1
KSHAPF=1.5
KSHAPF=1
Figure 5.67. Filtering Characteristics of Proposed SHAPF System with Different
SHAPFK Values
5.2.2.2. Control Method of SHAPF Modules in Proposed SHAPF System
In the proposed SHAPF system, identical SHAPF modules have separate
controllers but the controllers of each SHAPF module use same control methods. The
general block diagram of control method of SHAPF modules is shown in Figure
5.68. It is shown that the control method of SHAPF modules is formed from the
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
163
harmonic current extraction, DC link voltage controller and voltage controller. The
harmonic current extraction method uses the source currents which are the controlled
variables of this control method so the proposed controller method has a feedback
control configuration and SHAPFK which is introduced in previous section is the
feedback gain of the controller.
Harmonic
Extraction
DC Link
Controller
Voltage
ControllerVSI
+hI
X
SHAPFK
-
,cap SHAPFV
,a SHAPFI
,capref SHAPFV
,ref SHAPFV
+
-Gate
Signals SHAPFI
sourceI
CSI IFI
sourceI
hV
Passive
Filter
+
-SHAPF
V
sourceV
Figure 5.68. Control Method of Shunt APF Modules in Proposed SHAPF System
In the control method of SHAPF modules, EPLL method is used as harmonic
extraction method as used in the controllers of APF modules in HAPF system.
Because the structure and operating principle of EPLL method are presented in
previous section, it is not presented again in this section.
The block diagram of DC link voltage controller of SHAPF modules is shown
in Figure 5.69. It is shown that DC link voltage control is obtained by PI controller.
As the pure shunt APF, SHAPF can build up and regulate the dc capacitor voltage
without any external power supply. The pure shunt APF obtains the DC link voltage
control by generating current in phase with the system voltage. However, SHAPF
controls the DC link voltage by generating voltage in phase with leading current flow
from passive filter. If SHAPF outputs a fundamental voltage that is in phase with the
fundamental leading current of the passive filter, the active power formed by the
leading current and the fundamental voltage is supplied to the dc capacitor (Fujita et
al., 1991). To generate a current in the same phase with fundamental component of
SHAPF current, fundamental component of SHAPF current must be known. In
controller of proposed SHAPF, this can be achieved by using EPLL as shown in
Figure 5.69. When SHAPF current is applied to EPLL, EPLL gives the phase
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
164
information of fundamental component of SHAPF current. Using phase of
fundamental component of SHAPF current, DC link control reference voltage signal
is created by multiplying the PI controller output and sinewave created by phase
information of fundamental component of SHAPF current as shown in Figure 5.69.
,capset SHAPFV
+
-
PI
CONTROL
,cap SHAPFV
,cappi SHAPFV
,a SHAPFI EPLL
_ ,a f SHAPFI
+
-
+
+
sin
sin
sin
X
X
X
_ ,a capref SHAPFV
_ ,b capref SHAPFV
_ ,c capref SHAPFV
2 3
2 3
,cappi SHAPFV
,cappi SHAPFV
,cappi SHAPFV
Figure 5.69. DC Link Voltage Control of SHAPF Modules
The APFs in SHAPF modules acts as voltage source. Therefore, voltage
references are created in the control method of SHAPF and these voltage references
are generated using voltage controller by APF in SHAPF module. The voltage
control of APF is achieved by PWM method as shown in Figure 5.70. The switching
pulses are generated by comparing the generating reference voltage signal with
triangular wave. In the proposed SHAPF the switching frequencies of power
electronic devices is selected 3000 Hz because the switching losses of power
electronic devices extremely increase with switching frequency of power electronic
devices.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
165
+
-Triangular
Wave
_ ,a ref SHAPFV
+
-Triangular
Wave
_ ,b ref SHAPFV
+
-Triangular
Wave
_ ,c ref SHAPFV
G
A
T
E
S
I
G
N
A
L
S
Figure 5.70. Voltage Control of SHAPF Modules
5.2.2.3. Simulation Results of Proposed SHAPF System
The performance of the proposed SHAPF system in compensating the PQ
problems of CSI-IF is investigated in PSCAD/EMTDC simulation program. In this
section the simulation results of system is presented. The proposed SHAPF system is
connected to the input of CSI-IF as shown in Figure 5.71. The power circuit
parameters of proposed SHAPF used in simulation program is given in Table 5.6.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
166
sysL
sysL
sysL
,a sourceI
,b sourceI
,c sourceI
,a sourceV
,b sourceV
,c sourceV
3 PHASE
POWER SUPPLY
31.5kV
Ssc = 335MVA
,a CSI IFI
,b CSI IFI
,c CSI IFI
CSI-IF
SHAPFsI
1SHAPFI
2SHAPFI
, a CSI IFV
, b CSI IFV
, c CSI IFV
, 1cap SHAPFV, 2cap SHAPFV-+ -+
SHAPFL
,dc SHAPFC
,dc SHAPFC
3MVA
Y/Y
31.5/1kV
SHAPFC
SHAPFL
SHAPFC
Figure 5.71. Power Circuit Model of Proposed SHAPF System
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
167
Table 5.6. Power Circuit Parameters of SHAPF System
The Proposed SHAPF System
Coupling Transformer
4MVA
31.5/1kV Y/Y
Vsc% = 3%
SHAPF Module
PFQ = 2MVAr
PFf =300 Hz
PFQF =20
SHAPFL =66µH
SHAPFC =3.1mF
,dc SHAPFC = 90mF
The waveforms of CSI-IF currents, source currents and the proposed SHAPF
currents in 31.5kV level are shown in Figure 5.72, Figure 5.73 and Figure 5.74
respectively. It is shown that proposed SHAPF system compensate the harmonic and
interharmonic currents of CSI-IF effectively and show a better performance than the
proposed HAPF system. During the first second of the simulation which the current
waveforms are taken, THD of CSI-IF current is 14.35% and source current THD
decreases to 2.9%. During the overall simulation time which CSI-IF operates from
150 Hz to 250 Hz, THD of CSI-IF current is varying from 15.7% to 7 % and source
current THD is varying from 3.2 % to 1.8 %. When the proposed SHAPF current
waveform is investigated, it is shown that the proposed SHAPF draws fundamental
leading current with injected harmonic and interharmonic currents.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
168
Figure 5.72. CSI-IF Current Waveform in Proposed SHAPF Simulation
Figure 5.73. Source Current Waveform in Proposed SHAPF Simulation
CSI-IF : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.40
-0.30
-0.20
-0.10
0.00
0.10
0.20
0.30
0.40
CS
I-IF
Curr
ents
(kA
)
Ia_CSI-IF Ib_CSI-IF Ic_CSI-IF
SYS : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.40
-0.30
-0.20
-0.10
0.00
0.10
0.20
0.30
0.40
Sourc
e C
urr
ents
(kA
)
Ia_source Ib_source Ic_source
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
169
Figure 5.74. High Voltage Side APFs Currents in Proposed SHAPF Simulation
The harmonic spectrums of CSI-IF currents and source currents are given in
Figure 5.75 and Figure 5.76 while CSI-IF is operating at 175 Hz. The harmonic
spectrums in Figure 5.75 and Figure 5.76 show the harmonics with steps of 10 Hz in
order to indicate the interharmonics. In Figure 5.75 lower order harmonics and
interharmonics are presented with larger scale and in Figure 5.76 higher order
harmonics and interharmonics are presented with lower scale. In this simulation,
SHAPFK is selected as 1.5 in the control methods of each SHAPF modules. When the
harmonic spectrums of CSI-IF currents and source currents are investigated, it is
shown that proposed SHAPF system shows an approximate filtering characteristic as
in the presented filtering characteristic curve in Section 5.2.2.1. SHAPF cannot show
the same characteristic in the filtering characteristic curve in Section 5.2.2.1 because
this filtering characteristic curve is for SHAPF which has an ideal voltage source
instead of VSI. As shown in the harmonic spectrums, the proposed SHAPF system
eliminates almost all harmonic currents at 300 Hz which is the tuned frequency of
APFs : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-0.080
-0.040
0.000
0.040
0.080
AP
FsC
ur.A
(kA
)
Ia_APFs
-0.080
-0.040
0.000
0.040
0.080
AP
FsC
ur.B
(kA
)
Ib_APFs
-0.080
-0.040
0.000
0.040
0.080
AP
FsC
ur.C
(kA
)
Ic_APFs
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
170
series connected passive filter, 80 % of harmonic currents at 400 Hz, 70% of
harmonic currents at 550 Hz, 60% of harmonic currents at 650 Hz and 750 Hz and
below than 50 % of harmonic current at above 1000 Hz.
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
171
Fig
ure
5.7
5.
Har
monic
S
pec
trum
of
Low
er O
rder
H
arm
onic
s of
CS
I-IF
C
urr
ent
and S
ourc
e C
urr
ent
in P
ropose
d S
HA
PF
Sim
ula
tion
(a)
Har
monic
Spec
trum
of
CS
I-IF
Curr
ent
(b)
Har
monic
Spec
trum
of
Sourc
e C
urr
ent
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
172
Fig
ure
5.7
6.
Har
monic
S
pec
trum
of
Low
er O
rder
H
arm
onic
s of
CS
I-IF
C
urr
ent
and S
ourc
e C
urr
ent
in P
ropose
d S
HA
PF
Sim
ula
tion
(a)
Har
monic
Spec
trum
of
CS
I-IF
Curr
ent
(b)
Har
monic
Spec
trum
of
Sourc
e C
urr
ent
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
173
In Figure 5.77, the voltage waveforms measured from the input of CSI-IF is
given. It is shown that high frequency harmonics are shown in the voltage signal.
This high frequency distortion is the effect of the switching noise of SHAPF in weak
power system. When with compared to HAPF simulation results with SHAPF
results, the switching noise distortion in the SHAPF voltage is lower than HAPF
voltage because the series connected passive filters in SHAPF modules suppress the
switching ripples produced by VSIs.
Figure 5.77. CSI-IF Voltage Waveform in Proposed SHAPF Simulation
The reactive powers drawn from source, CSI-IF, each module of proposed
SHAPF system and complete of the proposed SHAPF system are shown in Figure
5.78. It is shown that 1MVAr reactive power is supplied by series connected single
tuned filters of each module of SHAPF and totally 2 MVAr reactive power is
supplied from complete of proposed SHAPF system. By the help of the proposed
SHAPF system, the reactive power compensation requirement of CSI-IF is provided
and the reactive power demand of CSI-IF can be kept under the limits.
CSI-IF : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
CS
I-IF
Voltages
(kV
)
Va_CSI-IF Vb_CSI-IF Vc_CSI-IF
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
174
Figure 5.78. Reactive Powers Drawn From Source, Drawn By CSI-IF and Drawn By
SHAPF Modules in SHAPF Simulation
In Figure 5.79 and Figure 5.80 the injected currents in 1000V level of each
SHAPF modules in the proposed SHAPF system are presented. It is seen that the
identical SHAPF modules draw the same fundamental leading currents with same
injected harmonic and interharmonic currents. The peak points of injected currents of
each SHAPF modules reach to 1600A.
SYS,CSI-IF,APFs,APF1,APF2 : Graphs
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00 10.00 11.00 12.00 ...
...
...
-3.00 -2.50
-2.00 -1.50 -1.00 -0.50
0.00 0.50 1.00 1.50
2.00 2.50 3.00 3.50
4.00 4.50 5.00
y (M
VA
r)
Q_source Q_CSI-IF Qapfs Qapf1 Qapf2
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
175
Figure 5.79. Injected Current Waveform of SAPF1 in Proposed SHAPF Simulation
Figure 5.80. Injected Current Waveform of SAPF2 in Proposed SHAPF Simulation
APF1 : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-1.60
1.60
AP
F1C
urA
(kA
)Ia_APF1
-1.60
1.60
AP
F1C
urB
(kA
)
Ib_APF1
-1.60
1.60
AP
F2C
urC
(kA
)
Ic_APF1
APF2 : Graphs
sec 1.0000 1.0100 1.0200 1.0300 1.0400 1.0500 1.0600 1.0700 1.0800 1.0900 1.1000 ...
...
...
-1.60
1.60
AP
F2C
urA
(kA
)
Ia_APF2
-1.60
1.60
AP
F2C
urB
(kA
)
Ib_APF2
-1.60
1.60
AP
F2C
urC
(kA
)
Ic_APF2
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
176
In Figure 5.81 and Figure 5.82, the DC link voltage trends of each SHAPF
module are presented. It is shown that the DC link voltage controllers of APF
modules operate successfully and keep the DC link voltage at constant 600V level.
Also the ripples of DC link voltages are in the sufficient levels. Besides the switching
ripples in the DC link voltage there is a non-regular ripple is seen on the DC link
voltage. This non-regular ripple is caused by the time varying harmonics and
interharmonics of CSI-IF.
Figure 5.81. DC Link Voltage Waveform of SHAPF1 in Proposed SHAPF
Simulation
Figure 5.82. DC Link Voltage Waveform of SHAPF2 in Proposed SHAPF
Simulation
APF1 : Graphs
sec 1.000 1.020 1.040 1.060 1.080 1.100 1.120 1.140 1.160 1.180 1.200 ...
...
...
0.5900
0.5920
0.5940
0.5960
0.5980
0.6000
0.6020
0.6040
0.6060
0.6080
0.6100
AP
F1 D
C-L
INK
Voltage (
kA)
Vcap_APF1
APF1 : Graphs
sec 1.000 1.020 1.040 1.060 1.080 1.100 1.120 1.140 1.160 1.180 1.200 ...
...
...
0.5900
0.5920
0.5940
0.5960
0.5980
0.6000
0.6020
0.6040
0.6060
0.6080
0.6100
AP
F1 D
C-L
INK
Voltage (
kA)
Vcap_APF1
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
177
In Figure 5.83 and Figure 5.84, the reference voltages which are calculated in
the controllers and the triangular signals which are generated in the voltage control
blocks are shown for each SHAPF module. It is shown that the generated voltage
reference signals are modulated uniformly and gate signal of VSIs of SHAPF
generated correctly.
Figure 5.83. Reference Voltages and Triangular Wave Waveforms of SHAPF1
Controller in Proposed SHAPF Simulation
Figure 5.84. Reference Voltages and Triangular Wave Waveforms of SHAPF2
Controller in Proposed SHAPF Simulation
APF1_Control : Graphs
sec 1.0000 1.0010 1.0020 1.0030 1.0040 1.0050 1.0060 1.0070 1.0080 1.0090 1.0100 ...
...
...
-0.030
-0.020
-0.010
0.000
0.010
0.020
0.030
AP
F1 R
efV
oltage (
kV)
Va_ref_APF1 PWM_tri_APF1
APF2_Control : Graphs
sec 1.0000 1.0010 1.0020 1.0030 1.0040 1.0050 1.0060 1.0070 1.0080 1.0090 1.0100 ...
...
...
-0.030
-0.020
-0.010
0.000
0.010
0.020
0.030
AP
F1 R
ef&
Inje
cted C
urr
ents
(kV
)
Va_ref_APF2 PWM_tri_APF2
5. MODELING AND ANALYSIS OF PQ COMPENSATION FOR CSI-IF
Adnan TAN
178
According to these simulation results, each VSI power rating in SHAPFs of
proposed SHAPF system is calculated as;
_ _3
2 2
cap SHAPF SHAPF peak
SHAPF VSI
V IS (5.16)
From Eq. 5.16, the each converter power rating is found as,
600 16003 831
2 2SHAPF VSI
V AS kVA (5.17)
And total power rating of converters of APFs in proposed SHAPF is approximately
equal to 2 831 1662kVA kVA .
The power rating of each SHAPF module which contains both the passive
filters and APF is calculated as;
_
,32
peak SHAPF
SHAPF L L rms
IS V (5.18)
From Eq. 5.16, the power rating of each SHAPF module is find as,
16003.1000 . 1960
2SHAPF
AS V kVA (5.19)
And total power rating of converters of SHAPFs in proposed SHAPF system is
approximately equal to 2 1960 3920kVA kVA .
6. CONCLUSIONS Adnan TAN
179
6. CONCLUSIONS
Electric power systems suffer from almost all type power converters because
of the nonlinear load characteristics. The major part of these power converters
produce harmonics related with only the rectifier part of power converter. In most
case, the harmonic distortion of these converters can be reduced under the limits with
using only passive filtering systems. However, such kind of power converters whose
rectifier and inverter sections cannot be satisfactorily isolated as used in CSI-IF
generates harmonics and interharmonics related with operating frequency of inverter.
CSI-IFs are especially preferred in high power applications because of the feature of
CSI and parallel resonant tank circuit of CSI-IF in providing high resonant currents
to the furnace coil with lower converter currents. With increasing power of CSI-IFs,
the effects of CSI-IFs on the power systems are also increased. The reasons of poor
effects of high power CSI-IF on power systems are the high values of harmonic and
interharmonic currents and varying of high value harmonic and interharmonic
currents in wide frequency spectrum related with the wide operating frequency range
of CSI of the furnace power converter.
In this thesis, the time varying harmonics and interharmonics of CSI-IF and
the relation of these varying harmonics and interharmonics with the operating
frequency of CSI of furnace is firstly introduced theoretically. Secondly, these
varying harmonics and interharmonics and relation with the operating frequency of
CSI of furnace are demonstrated in the simulation of CSI-IF model created by using
the furnace parameters of a real CSI-IF. Finally, the simulation results and power
quality measurements of CSI-IF in the steel mill is compared and it is shown that the
simulation results of CSI-IF are corresponding to the power quality measurements of
CSI-IF.
In order to find solutions to these power quality problems of CSI-IF, passive
and active filtering methods are investigated. Firstly, passive filtering methods are
examined by modeling single tuned filters, C-type filters and LLCL type broad band
filters. The use of single tuned filters in PQ compensation of CSI-IF is not possible
because the CSI-IF generates time varying harmonics and interharmonics in very
6. CONCLUSIONS Adnan TAN
180
wide frequency range. If a single tuned filter which is tuned to a frequency in range
of time harmonics and interharmonics of CSI-IF is connected to the input of CSI-IF,
the parallel resonance will occur between filter and power system when CSI-IF
generates harmonics or interharmonics below the tuning frequency of single tuned
filter. Because of these, the only solution to place a single tuned passive filter to the
input of CSI-IF is to tune the filter below the frequencies of generated harmonics and
interharmonics. However, this time single tuned filter has no effect on filtering
harmonics and interharmonics of CSI-IF because single tuned filters attenuate the
harmonics or interharmonics in the tuning frequency. In above frequencies than
tuning frequency, single tuned filter cannot show any filtering effect. Thus single
tuned filters provide solution to the reactive power requirements of CSI-IF.
The C-type filters are thought as being able to provide a solution to the
harmonics and interharmonics of CSI-IF because there are many applications of C-
type filters in interharmonic generating systems such as HVDC transmission
systems, cycloconverters and EAFs. When the C-type filters are investigated, it is
shown that reactive power rating of C-type filter must be large in order to show
lower impedance than power system and damp the harmonics and interharmonics.
When C-type filter is designed according to the reactive power ratings of CSI-IF, it is
observed that the filter has no effect on compensating harmonics and interharmonics
of CSI-IF. Because of the low reactive power rating of CSI-IF, the reactive power
rating of filter cannot be increased in order to maintain reactive power demand
limits.
The LLCL type broad band filters are another attractive passive filter type.
They can show filtering effect in wide frequency range. When this type filter is
designed for the CSI-IF, it is shown that the filter not only shows very effective
filtering performance and decrease the harmonic and interharmonic contents of CSI-
IF currents under the limits but also maintain the reactive power requirements of
CSI-IF. However, this LLCL filter causes high voltage distortion in the output
voltage of filter because of the series reactors of filter. The voltage distortion can be
decreased by decreasing the values of series reactor but this time the harmonic
filtering performance of filter is decreased. While this designed filter keeps the CSI-
6. CONCLUSIONS Adnan TAN
181
IF current harmonic distortion under 5%, it increases the voltage distortion up to
12% level. In this condition, the furnace cannot operate in real operation because
these distorted voltage signals can cause firing problems in rectifier section of
furnace power supply. Moreover, the series reactors with high current ratings are also
a disadvantage of LLCL type broadband filter.
Because of the inadequate performances of passive filtering systems, HAPF
systems are proposed to solve the time varying harmonics and interharmonics
problems and meet the reactive power requirements of CSI-IF. The reason of
preferring HAPF is that it is not feasible to provide solution to both harmonic and
interharmonics problems, and reactive power requirements of CSI-IF with using only
pure APFs because with increasing ratings of power electronics based compensation
systems the cost of system increases incredibly.
In the first proposed HAPF topology, shunt APF and shunt passive filter
combination is used. In this topology, two identical APF modules are used in shunt
APF system because of the high compensating harmonics and interharmonics of CSI-
IF. When the simulation results of the proposed compensation system are
investigated, it is shown that the proposed system performs an adequate performance
on filtering the harmonics and interharmonics of CSI-IF and meets the reactive
power requirements of CSI-IF completely. However, in the control methods of shunt
APF modules in proposed HAPF system, effective current control cannot be
achieved so, the harmonic and interharmonic eliminating performance of APF
modules is decreased. In order to maintain regular current control, the ratings of
shunt APF system must be increased. In proposed system, it can be achieved with
two methods. The first one is the increasing of DC-link voltage of VSI and the
second one is using additional APF modules. Increasing DC-link voltage in APF
modules is not feasible because of the power ratings of power electronics devices.
Because of these, additional APF modules must be used in order to obtain the regular
current control and superior harmonic and interharmonic eliminating performance.
However, this solution increases the cost of proposed HAPF system.
In the second compensation system, SHAPF system is proposed. SHAPF
topology is formed from series connected APF with shunt passive filter. In proposed
6. CONCLUSIONS Adnan TAN
182
SHAPF system, two identical SHAPF modules are used because the passive filter
ratings cause high APF currents in order to obtain the reactive power requirements of
CSI-IF. When the simulation results of the proposed compensation system are
investigated, it is shown that SHAPF provides better harmonic and interharmonic
filtering performance than the shunt APF - shunt passive filter combination and
meets the reactive power requirements of CSI-IF completely.
When the converter ratings of APFs in both proposed HAPF systems are
compared, it is seen that the ratings of converters in SHAPF is significantly lower
than ratings of converters in shunt APF modules because of the low DC link voltage
level. In shunt APF modules the DC link voltage must be higher from the peak value
of supply voltage in order to prevent the reactive power flow to the APF and
injecting the harmonics and interharmonics currents to the power system. However
in SHAPF topology, the DC link voltage only provides the harmonic and
interharmonics currents because the fundamental voltage of system drops to
terminals of series connected passive filters. This feature of SHAPF provides major
advantage in decreasing the ratings of converters.
In this thesis, the performance of passive and active filtering systems is
demonstrated by modeling the systems in the PSCAD/EMDTC. According to the
simulation results, the comparison table of compensation system is presented in
Table 6.1 and the following results are extracted from this study. The single tuned
passive filter and C-type passive filter are certainly not appropriate for the
compensation of the harmonic and interharmonic problems of CSI-IF. The LLCL
type broadband passive filter shows effective harmonic and interharmonic
eliminating performance but the voltage distortion at the output of filter can prevent
the proper operation of CSI-IF so, this filter is also not appropriate for the
compensation of CSI-IF. When the proposed HAPF systems are compared, both of
them presents sufficient performance in both compensating the harmonics and
interharmonics of CSI-IF and meeting the reactive power requirements of CSI-IF.
However, when the converter power ratings of filters are compared the converters in
the proposed SHAPF system has lower power ratings than the converters of shunt
APFs. The power rating of converters is directly proportional to the cost of
6. CONCLUSIONS Adnan TAN
183
converters so the increasing power ratings of converters in APFs increases the costs
of APFs Moreover the increasing power ratings of converters also cause to increase
the losses of the converters. Therefore, the proposed SHAPF system presents more
effective compensation solution for the harmonics and interharmonics problems and
reactive power requirements of CSI-IF.
Table 6.1. Comparison of Investigated Compensation Systems
Single Tuned
Filter C-Type Filter
LLCL Type
Broad Band
Filter
ProposedHAP
F
System
Proposed
SHAPF
System
Load Current
THD% 7-15% 7-15% 7-15% 7-15% 7-15%
Source Current
THD% 7-15% 6.6-14.6% 2.5-5% 2-4.5% 1.8-3.2%
Source Voltage
THD% 2-3.5% 2-3.5% 2%< 2%< 2%<
Output Voltage
of Filter THD% - - 6.5-12% - -
Switching
Frequency - - - 3kHz 3kHz
DC Link Voltage - - - 2000V 600V
RMS Current [email protected] [email protected] [email protected]
APFs=36A
STF=37A
@31.5kV
Max. Peak
Current [email protected] [email protected] [email protected]
APFs=52A
STF=52.5A
@31.5kV
Harmonic
Compensation
Performance
Poor Poor Good Excellent Excellent
Reactive Power
Compensation
Performance
Good Good
Changes
depending on the
loading of CSI-IF
Good Good
Cost Very Low Low Medium High High
Overall
Performance Poor Poor Poor Good Excellent
6. CONCLUSIONS Adnan TAN
184
The following remarks are suggested as future works of this thesis study;
In this thesis the modeling aim of CSI-IF demonstrate the time varying
harmonics and interharmonics of CSI-IF. Because of these, the proposed
controller of CSI-IF and start-up of CSI-IF is not analyzed in detail. The
controller stability and start-up furnace will be investigated as a future work.
The power losses, power ratings and costs of the proposed HAPF and SHAPF
systems will be investigated and compared more detailed as a future work.
185
REFERENCES
AKAGI H., 2005. Active Harmonic Filters. Proceedings of the IEEE, 93(12): 2128 –
2141.
ARAVENA P., VALLEBUONA G., MORAN L., DIXON J. and GODOY O., 2009.
Passive Filters for High Power Cycloconverter Grinding Mill Drives. IEEE
Industry Applications Society Annual Meeting, Page(s):1 – 7.
ARRILLAGA J. and BRADLEY D. A., 1985. Power System Harmonics. John Wiley
& Sons Ltd, Chichester, 335 pages.
ASIMINOAEI L., BLAABJERG F. and HANSEN S., 2007. Detection is Key -
Harmonic Detection Methods for Active Power Filter Applications. IEEE
Industry Applications Magazine, 13(4): 22 – 33.
BAAKE E. Lecture Notes: Technical Basics and Applications of Induction Furnaces.
Leibniz University of Hanover. http://www.uie.org/webfm_send/391 . Last
Access Date: 07/2011.
BENCHAITA L., SAADATE, S. and SALEMNIA, A., 1999. A Comparison of
Voltage Source and Current Source Shunt Active Filter by Simulation and
Experimentation. IEEE Transactions on Power Systems, 14(2):642 - 647.
BHATTACHARYA A., CHAKRABORTY, C. and BHATTACHARYA S., 2009.
Shunt Compensation. IEEE Industrial Electronics Magazine, 3(3): 38 – 49.
BHATTACHARYA S. and MIRZAEE H., 2010. Series Active Filter Control and
Implementation for Utility Interface of Multiple Adjustable Speed Drives
IEEE Industrial Electronics Society 36th Annual Conference, Page(s): 2663 –
2668.
BODGER P.S., IRWIN G.D. and WOODFORD D.A., 1990. Controlling Harmonic
Instability of HVDC Links Connected to Weak AC Systems. IEEE
Transactions on Power Delivery, 5(4): 2039 – 2046.
BONERT R. and LAVERS J.D., 1994. Simple Starting Scheme for A Parallel
Resonance Inverter for Induction Heating. IEEE Transactions on Power
Electronics, 9(3): 281 – 287.
BOSE B.K. 1986. Power Electronics and AC Drives. Prentice Hall, USA, 402 pages.
186
BOYLESTAD R.L., 2007. Introductory Circuit Analysis. Prentice Hall, USA, 1156
pages.
CHANG G.W., RIBEIRO P. F., 1998. Harmonics Theory, 1998 IEEE PES Summer
Meeting, Papers of Tutorial on Harmonics Modeling and Simulation.
CHENG P., BHATTACHARYA S. and DIVAN D.M., 1998. Control of Square-
Wave Inverters in High-Power Hybrid Active Filter Systems. IEEE
Transactions on Industry Applications, 34(3): 458 – 472.
CHUDNOVSKY V., AXELROD B. and SHENKMAN A.L.,1997. An Approximate
Analysis of a Starting Process of a Current Source Parallel Inverter with a
High-Q Induction Heating Load. IEEE Transactions on Power Electronics,
12(2): 294 – 301.
DAS, J.C., 2004. Passive Filters-Potentialities and Limitations. IEEE Transactions on
Industry Applications, 40(1): 232 – 241.
DAVIES E.J., 1990. Conduction and Induction Heating, IEE Power Engineering
Series, Peter Peregrinus Ltd, London, 397 pages.
DAWSON F.P. and JAIN P., 1991. A Comparison of Load Commutated Inverter
Systems For Induction Heating and Melting Applications. IEEE Transactions
on Power Electronics, 6 (3): 430 – 441.
DEDE E.J., JORDAN J., GONZALEZ J.V., LINARES J., ESTEVE V. and MASET
E. 1991. Conception and Design of A Parallel Resonant Converter for
Induction Heating, Applied Power Electronics Conference and Exposition,
Page(s): 38 – 44.
DUGAN R.C., MCGRANAGHAN M.F. and BEATY H. W., 1996. Electrical Power
Systems Quality. McGraw Hill, New York, 265 pages.
DUGAN R.C. and CONRAD L.E., 1999. Impact of Induction Furnace
Interharmonics on Distribution Systems, IEEE Transmission and Distribution
Conference, Page(s): 791 – 796.
EPRI, 1993. Induction Heating Technology.
FUJITA H. and AKAGI H., 1991. A Practical Approach to Harmonic Compensation
in Power Systems-Series Connection of Passive and Active Filters. IEEE
Transactions on Industry Applications, 27(6): 1020 – 1025.
187
GERÇEK C. Ö., ERMIS M., ERTAS A., KOSE K. N. K. and ÜNSAR Ö, 2011.
Design, Implementation, and Operation of a New C-Type 2nd Harmonic
Filter for Electric Arc and Ladle Furnaces. IEEE Transactions on Industry
Applications, 47(4): 1545 – 1557.
GONZALEZ D. A. and MCCALL J. C., 1987. Design of Filters to Reduce Harmonic
Distortion in Industrial Power Systems. IEEE Transactions on Industry
Applications, IA-23(3): 504 – 511.
HABROUK E., DARWISH M and MEHTA M.K., 2000. Active Power Filters: A
Review, IEE Proceedings on Electric Power Applications, 147:403-413.
HALPIN S.M., 2005. Comparison of IEEE and IEC Harmonic Standards. IEEE
Power Engineering Society General Meeting 2005, 3: 2214 – 2216.
HAVA A.M. and ZUBI H., 2005. Improved Broadband Harmonic Filter Design for
Adjustable Speed Drives. International Conference on Power Electronics and
Drives Systems, 1: 298 – 303.
IEC 61000-2-1, 1990. Electromagnetic compatibility (EMC) - Part 2: Environment -
Section 1: Description of the environment - Electromagnetic environment for
low-frequency conducted disturbances and signalling in public power supply
systems.
IEC 61000-2-2, 2002. Electromagnetic compatibility (EMC) - Part 2-2: Environment
- Compatibility levels for low-frequency conducted disturbances and
signalling in public low-voltage power supply systems.
IEC 61000-2-12, 2003. Electromagnetic compatibility (EMC) - Part 2-12:
Environment - Compatibility levels for low-frequency conducted
disturbances and signalling in public medium-voltage power supply systems.
IEC 61000-3-2, 2005. Electromagnetic compatibility (EMC) - Part 3-2: Limits -
Limits for harmonic current emissions (equipment input current ≤ 16 A per
phase).
IEC 61000-3-6, 2008. Electromagnetic compatibility (EMC) - Part 3-6: Limits -
Assessment of emission limits for the connection of distorting installations to
MV, HV and EHV power systems.
188
IEC 61000-3-12, 2004. Electromagnetic compatibility (EMC) - Part 3-12: Limits -
Limits for harmonic currents produced by equipment connected to public
low-voltage systems with input current > 16 A and ≤ 75 A per phase.
IEEE Std.519, 1992. IEEE Recommended Practices and Requirements for Harmonic
Control in Electrical Power Systems.
INDUCTOHEAT INC., Induction Heating Application Note,
http://www.inductoheat.com/literature/misc_products/IHEAT-AppNote
LargeGear-2.pdf, Access Date: 07.2011.
INZUNZA R. and AKAGI H., 2005. A 6.6-kV Transformerless Shunt Hybrid Active
Filter for Installation on a Power Distribution System Power Electronics,
IEEE Transactions on Volume : 20 , Issue:4 On page(s): 893 – 90.
KARIMI-GHARTEMANI M. and IRAVANI M.R., 2001. A New Phase-Locked
Loop (PLL). Proceedings of the 44th IEEE 2001 Midwest Symposium on
System Circuits and Systems, 2001,1: 421 – 424.
KARIMI-GHARTEMANI M. and IRAVANI M.R., 2002. A Nonlinear Adaptive
Filter for Online Signal Analysis in Power Systems Applications. IEEE
Transactions on Power Delivery, 17: 617-622.
KARIMI-GHARTEMANI M., MOKHTARI H., IRAVANI M.R. and SEDIGHY,
M., 2004. A Signal Processing System for Extraction of Harmonics and
Reactive Current of Single-Phase Systems. IEEE Transactions on Power
Delivery, 19(3): 979 – 986.
KARIMI-GHARTEMANI M., IRAVANI M.R. and KATIRAEI F., 2005. Extraction
of Signals for Harmonics, Reactive Current and Network-Unbalance
Compensation. IEE Proceedings Generation, Transmission and Distribution,
152(1): 137 – 143.
KHAN I., TAPSON, J. and DE VRIES I., 2000. Frequency Control of a Current-Fed
Inverter for Induction Heating. Proceedings of the 2000 IEEE International
Symposium on Industrial Electronics, 1: 343 – 346.
LOVELESS D., 1995. An Overview of Solid State Power Supllies for Induction
Heating. Metal Producing & Processing.
189
MCGRANAGHAN M. and BEAULIEU G., 2006. Update on IEC 61000-3-6:
Harmonic Emission Limits for Customers Connected to MV, HV, and EHV.
IEEE PES Transmission and Distribution Conference and Exhibition,
Page(s): 1158 – 1161.
MERTENS A. and SKUDELNY H.C., 1991. Switching Losses in a GTO Inverter for
Induction Heating, IEEE Transactions on Power Electronics, 6(1): 93 – 99.
NASSIF A.B., WILSUN XU and FREITAS W., 2009. An Investigation on The
Selection of Filter Topologies for Passive Filter Applications. IEEE
Transactions on Power Delivery, 24(3): 1710 – 1718.
OTTO-JUNKER GmbH, Medium Frequency Induction Furnaces.
http://www.ottojunker.de, Access Date: 07.2011.
PENG F.Z., AKAGI, H. and NABAE A. 1990. A New Approach to Harmonic
Compensation in Power Systems-A Combined System of Shunt Passive and
Series Active Filters, IEEE Transactions on Industry Applications, 26(6): 983
– 990.
PENG F.Z., AKAGI H., NABAE A. and SUGAWARA S., 1989. High-Frequency
Current-Source Inverters Using SI Thyristors for Induction Heating
Applications. IEEE Transactions on Industry Applications, 25(1):172 – 180.
PENG F.Z., 1998. Application Issues of Active Power Filters, IEEE Industry
Applications Magazine, 4(5): 21 – 30.
PONWIANGKUM N. and KITTIRATSATCHA S., 2007. Switching Frequency
Control Based on Phase-Locked Loop for a Current-fed Parallel Resonant
Inverter. Power Conversion Conference, Pages(s): 157 – 161.
ROUTIMO M., SALO M. and TUUSA H., 2007. Comparison of Voltage-Source and
Current-Source Shunt Active Power Filters. IEEE Transactions on Power
Electronics, 22(2): 636 – 643.
RUDNEV V., LOVELESS D., COOK R. and BLACK M., 1999. Power Quality for
Induction Melting in Metal Production, Electric Power Research Institute,
U.S.A.
RUDNEV V., LOVELESS D., and COOK R., 2003, Handbook of Induction
Heating, Marcel Dekker Inc., New York, Basel, 777 pages.
190
RUDNEV V, 2007. Systematic Analysis of Induction Coil Failures Part 11a:
Frequency selection, Heat Treating Progress, Page(s):19-21.
RUDNEV V, 2008. Successful Induction Heating of RCS Billets, Forge Magazine,
Page(s): 15-18.
RUDNEV V, BROWN D. and DOYON G., 2008. Innovative Induction Heating
Technologies. Proceedings of Material Science & Technology, Conference &
Exhibition.
RUDNEV V, 2009. Single-Coil Dual-Frequency Induction Hardening of Gears. Heat
Treating Progress, Page(s): 9-11.
RUDNEV V., 2011. Intricacies of Computer Simulation of Induction Heating
Processes. Proceedings of the 28th Forging Industry Technical Conference,
Schaumburg.
SINGH B., AL-HADDAD K. and CHANDRA A., 1999. A Review of Active Filters
for Power Quality Improvement, IEEE Transaction on Industrial Electronics,
46: 960-971.
SIEVEKING H.A, 1940, Electrically Manufactured Steels. Journal of the Institution
of Electrical Engineers, 86(521): 401 – 423.
SRIANTHUMRONG S. and AKAGI H., 2003. A Medium-Voltage Transformerless
AC/DC Power Conversion System Consisting of a Diode Rectifier and a
Shunt Hybrid Filter. IEEE Transactions on Industry Applications, 39(3): 874
– 882.
SWAMY M. M., BISEL G. R. and ROSSITER S. L., 1995. Passive Harmonic Filter
System for Variable Frequency Drives, United States Patent, Patent Number:
5,444,609.
SWAMY M. M., 2005. Passive Techniques for Reducing Input Current Harmonics.
http://www.yaskawa.com/site/dmdrive.nsf/link2/AHUG-6J5R4A. Last
Access Date: 07/2011.
TOKUNÇ C.O., 2010. Modeling of a Shunt Active Power Filter With EPLL Based
Control Method for Mitigation of Power Quality Problems Caused by
Induction Furnaces. MSc Thesis, Cukurova University, Institute of Natural
and Applied Sciences.
191
TAYJASANANT T., WANG W., LI C. and XU W., 2005. Interharmonic-Flicker
Curves, IEEE Transactions on Power Delivery, 20(2): 1017 – 1024.
TESTA A., AKRAM M.F., BURCH R., CARPINELLI G., CHANG G., DINAVAHI
V., HATZIADONIU C., GRADY W.M., GUNTHER E., HALPIN M.,
LEHN P., LIU Y., LANGELLA R., LOWENSTEI, M., MEDINA A.,
ORTMEYER T., RANADE S., RIBEIRO P., WATSON N., WIKSTON J.
and XU W., 2007. Interharmonics: Theory and Modeling, IEEE Transactions
on Power Delivery, 22(4): 2335 – 2348.
TREMAYNE J. F, 1983. Impedance and Phase Balancing of Mains – Frequency
Induction Furnaces, IEE Proceedings on Electric Power Applications,
130(3):161 – 170.
UÇAK O., 2010, Design and Implementation of A Voltage Source Converter Based
Hybrid Active Power Filter, MSc Thesis, Middle East Technical University,
The Graduate School Of Natural And Applied Sciences.
WEBER A., CARROLL E. and FRECKE M., 2002. IGCTs for Induction Heating,
International PCIM Conference.
WIN P.P, 2008. Harmonic Mitigation Techniques in Industrial Power System,
GMSARN International Conference on Sustainable Development: Issues and
Prospects for the GMS.
TANGTHEERAJAROONWONG W., HATADA T., WADA K. and AKAGI H.,
2007. Design and Performance of a Transformerless Shunt Hybrid Filter
Integrated Into a Three-Phase Diode Rectifier. IEEE Transactions on Power
Electronics. 22(5): 1882 – 1889.
YACAMINI, R., 1996. Power System Harmonics: Part 4 – Interharmonics, Power
Engineering Journal, 10(4):185 – 193.
XIAO Y., ZHAO J. and MAO S., 2004. Theory for the Design of C-type Filter. 11th
International Conference on Harmonics and Quality of Power, Page(s): 11 –
15.
ZINN S. and SEMIATIN S, 2002, Elements of Induction Heating Design Control
and Applications, ASM International, USA, 323 pages.
192
ZUBI H.M., DUNN R.W., ROBINSON F.V.P. and EL-WERFELLI M.H., 2010.
Passive Filter Design Using Genetic Algorthims for Adjustable Speed Drives.
IEEE Power and Energy Society General Meeting, Page(s): 1 – 7.
193
BIOGRAPHY
Adnan Tan was born in Adana, Turkey in 1985. He received his B.Sc. in
Electrical and Electronics Engineering Department from Çukurova University,
Adana, Turkey. He has been working as Research Assistant in Electrical and
Electronics Engineering Department of Çukurova University since 2008. His
research interests include electrical power quality and utility applications of power
electronics.