Installation Instructions A3000 Trevi Therm built-in thermostatic mixer A3700 Trevi Outline built-in thermostatic mixer E3115 Trevi Traditional built-in thermostatic mixer INSTALLER: After installation please pass this instruction booklet to user TREVI SHOWERS Trevi Outline Trevi Traditional Trevi Therm

Transcript of trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line...

Page 1: trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line strainers/servicing valves (28) which include these flow restrictors. These should be inserted in

Installation InstructionsA3000 Trevi Therm built-in thermostatic mixerA3700 Trevi Outline built-in thermostatic mixerE3115 Trevi Traditional built-in thermostatic mixer

INSTALLER:After installation please pass this instruction booklet to user

TREVI SHOWERS

Trevi Outline

Trevi Traditional Trevi Therm

trevi showers.qxd 07/11/02 10:35 Page 1

Page 2: trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line strainers/servicing valves (28) which include these flow restrictors. These should be inserted in

WATER REGULATIONSHot and cold water supply pressures must bereasonably balanced and from a commonsource - both from storage or both from a supply pipe. (IRN 101). The mixers will functionwithin specification on unequal pressures up toa ratio of 5 : 1, but it is not recommended thatthe cold supply be connected to the rising mainand hot to the tank fed supply as the pressuredifferential is likely to exceed the 5:1 ratio.

The minimum pressure for correct operation is0.1 bar (1m head - see Figure 5). Pressure headis measured as the vertical distance between thebottom of the cold water storage tank whichfeeds the hot water system and the highestpoint on the shower spray plate.

When installing with a shower pump the use ofa secondary tapping from the cylinder is highlyrecommended.

Figure 1 shows the various methods of connectingthe hot water pipe to the cylinder - the mostpreferred on the left and the least preferred onthe right.

The fitting should be so installed as to be readilyaccessible for examination, repair, replacement oroperation. (IRN 111).

The temperature of the hot water must not exceed85ºC but the installer’s attention is drawn to codeof practice BS 6700 which recommends thatstored hot water should normally never exceed65ºC. For correct operation of the valve, a minimum of 52ºC is required.

GENERAL NOTES

Trevi thermostatic shower mixers are designed to be installed on normal UK low pressure storage tank fed systems, unvented high pressure systems, modulating instantaneous water heaters or modulating combination (combi) boilers. They are suitablefor all pumped applications.

Figure 1 Preferred locations of cylinder tapping

1

trevi showers.qxd 07/11/02 10:35 Page 2

Page 3: trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line strainers/servicing valves (28) which include these flow restrictors. These should be inserted in

When installing on a modulating combinationboiler it is sometimes possible for the interac-tion of a thermostatic valve with the combi tocause the boiler to cut out and cut in again withthe result that the water will become alterna-tively cold and hot. To overcome this, flowrestrictors should be fitted upstream of thethermostatic valve.

Trevi supply in-line strainers/servicing valves (28)which include these flow restrictors. Theseshould be inserted in the downstream side ofthe servicing valve as shown on Figure 2. It isessential that they are positioned the right wayround as shown in the sketch. Remove the com-pression nut and olive from the outlet side ofthe Isolating valve and place the restrictor in theoutlet. Push to the bottom of the recess. Fit O-ring in the visible rebate around the edge of therestrictor and push home until it is fully in therebate. Use the tip of a small screwdriver or sim-ilar to achieve this.

CATEGORIES OF RISKThe water regulations published in 1999* take anew approach to backflow in that they look at

different categories of risk. The installer mustassess the risk from the various categories offluid in adjacent appliances before determiningthe level of backflow protection required for aparticular installation. Figures 3 & 4 describe theprotection required in various installations.

CATEGORY 3 RISKWater in a shower tray, basin or bathtub is considered to be a fluid category 3 risk which isa fluid which represents a slight health hazard ifit were to find it’s way back into the supply pipe.For this reason it must not be possible for any flexible shower head to be able to enter any adja-cent washbasin, bath or shower tray unlessappropriate protection is employed. (See Figure 3).

If it is desired to allow the hand spray to be usedinside say a bathtub or a basin it is essential thatdouble check valves be fitted to the inlet onboth hot and cold supplies to the thermostaticvalve. Alternatively single check valves can befitted at the inlets and an additional check valveshould be fitted in the valve outlet.

No check valves need be fitted if the hand sprayis prevented from reaching closer than 25mm ofthe spill over level of any such fixture.

CATEGORY 5 RISKWater in a Sink, WC or Bidet is considered to bea fluid category 5 risk which is a fluid which rep-resents a serious health hazard if it were to findit’s way back into the supply pipe. For this rea-son it must not be possible for any flexibleshower head to be able to enter any adjacentSink, WC or Bidet. If the flexible hose to be fit-ted could reach into any such vessel, therequirements to the system design are so oner-ous it is better not to fit a flexible. Rather, a fixedoverhead showerhead should be considered.(See Figure 4).

Figure 2 in-line filter and service valveshowing restrictor

*A guide to the Water Supply (Water fittings) Regulations 1999 and the Water Byelaws 2000, Scotland is published by WRAS (Water Regulations Advisory Scheme) Fern Close, Pen-y-Fan Industrial Estate, Oakdale, Newport, NP11 3EH.ISBN 0-9539708-0-9.

WATER REGULATIONS 2

trevi showers.qxd 07/11/02 10:35 Page 3

Page 4: trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line strainers/servicing valves (28) which include these flow restrictors. These should be inserted in

It will also be seen that this risk could changeshould the hose be taken out of the restrainingdevice or should a longer replacement hose befitted at a later date. Installers and household-ers are advised to take account of these factors

when fitting replacement hoses.

For pumped applications the pipe supplying thepump must not in addition supply an ascendingspray bidet.

Figure 3 Illustration of backflow risk from fluid Category 3 risk

Figure 4 Illustration of backflow risk from fluid Category 5 risk

WATER REGULATIONS3

trevi showers.qxd 07/11/02 10:35 Page 4

Page 5: trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line strainers/servicing valves (28) which include these flow restrictors. These should be inserted in

GRAVITY/PUMPED SYSTEMS

Figure 5 Recommended system layout for gravity applications

Figure 6 Recommended pumped system layout

GRAVITY & PUMPED SYSTEMS 4

trevi showers.qxd 07/11/02 10:35 Page 5

Page 6: trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line strainers/servicing valves (28) which include these flow restrictors. These should be inserted in

INSTALLATION GUIDEConnections on the built-in mixer body are ¾" BSP (female) and are marked “hot in”, “coldin” and “mixed out” on the body casting. Thereare two mixed outlet ports, one of which must beplugged with the blanking plug supplied. Formaximum flow performance the unplugged out-let should be connected to the wall elbow or thefixed overhead shower using 22mm copper. The¾"/22mm connectors must be jointed to the valvebody using jointing compounds or PTFE tape.Under no circumstances should soldered joints beused near the valve body as this will damage thefitting. It is recommended that isolation valvesbe fitted upstream of the valve body.

TREVI THERM A3000The valve is supplied as per position 1 (Figure 8)with options for installation in positions 2, 3 & 4.Should positions 2, 3 or 4 be required then thetemperature adjustment carrier will need to berepositioned so that the triangular raised mark atthe rear is positioned at the top. The front handlecarrier is rotated if necessary until the triangularindent is again at the top. The handle can then bepushed into position with the override button tothe top.

TREVI OUTLINE THERMOSTAT A3700This valve is supplied as per position 3. Since thewall plate is designed to be mounted vertically,position 4 is the only alternative orientationadvised.

TECHNICAL DIMENSIONS

Figure 7 Trevi thermostatic shower valves - installation dimensions

Figure 8

DIMENSIONS5

trevi showers.qxd 07/11/02 10:35 Page 6

Page 7: trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line strainers/servicing valves (28) which include these flow restrictors. These should be inserted in

TREVI TRADITIONAL BUILT-IN E3115 Trevi Traditional is supplied as per position 3 (Figure 8) and should only be installed in thisorientation. Connections are the same as forTrevi Therm and Trevi Outline.

Build-in guide1. All the fittings covered by this instruction aredesigned to be recessed into the wall. The depthof the recess should be measured from the finished wall surface to the rear of the valvebody. There is an adjustment of 20mm in theinstallation depth. Recess depth is in the range66mm minimum to 86mm maximum. Theseminimum and maximum depths are marked onthe plaster guard (26).

2. Chase out wall for mixer body and pipe work.

3. Remove plaster guard (26).

4. Fit blanking plug to appropriate port of the valve body and connect pipe work. (Do notsolder near the valve body)

5. Replace plaster guard and check that thevalve is horizontal (or vertical if positions 3 or 4have been selected). The two bosses on thefront of the plaster guard allow a spirit level tobe placed on or against it. Check also that thevalve is parallel to the wall surface.

6. Make good the wall by plastering around thevalve up to the plaster guard.

7. Once the plaster has set the wall can be tiledand the plaster guard removed.

8. The temperature control handle can now bepositioned so that the button is to the top (TreviTherm and Trevi Outline Thermostat). If the valveis not being fitted in the position as supplied thenthe temperature adjustment carrier will have tobe repositioned as described on Page 8 underthermostatic cartridge replacement.

9. The pipe work and valve body mustnow be flushed out. Failure to do so willcause the thermostatic cartridge filters tobecome blocked resulting in reduced or erraticperformance. The procedure for this isdescribed on Page 7 under replacement of cartridges.

10. Fit the back cover plate and secure using the fixing screws (3). (These may need to be cutif valve is installed close to the minimum depth).Push front cover plate into position and fit operating handles.Figure 9

INSTALLATION GUIDE 6

trevi showers.qxd 07/11/02 10:35 Page 7

Page 8: trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line strainers/servicing valves (28) which include these flow restrictors. These should be inserted in

1. Remove handles. (see Pages 10/11 for details)

2. Remove the front cover plate (1) by prisingforward using the small slots at the sides ofthe front cover plate.

3. Remove the two cover plate screws and pulloff the back cover plate (2).

4. Remove the volume control handle (6) andcarrier (10) by unscrewing screw (8b) andpulling off.

5. Pull off shroud (9)

6. Remove the two gear box cover fixingscrews and pull off the gear box cover (11).

7. Pull out the drive shaft (15)

8. Loosen the two cartridge cone screws andremove the gear/clutch wheels (16) bypulling forward.

9. Lift off the rear gear box cover (17)

10. Isolate the shower valve from the suppliesand unscrew the two cartridges (18) anticlockwise

11. Fit the flushing adapter (25) in place of thecartridges in turn and flush the pipework.

12. Assemble the valve in reverse order.

13. If fitting replacement cartridges and/orclutches they should be fitted at this stage.

14. Both cartridges must be in the closed position before fitting the gear clutches (16)in position.

CARTRIDGE REPLACEMENTFlushing and replacement of cartridges & gear clutch wheels

Figure 10

VALVE REPLACEMENT7

trevi showers.qxd 07/11/02 10:35 Page 8

Page 9: trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line strainers/servicing valves (28) which include these flow restrictors. These should be inserted in

1. If the volume control handle is in the offposition it should not be necessary to isolatethe valve from the supply for this operation.

2. Remove handles (7). (see pages 10/11 fordetails)

3. Remove the front cover plate (1) by prisingforward using the small slots at the sides ofthe front cover plate.

4. Remove the two cover plate screws (3) andpull off the back cover plate (2).

5. Remove shroud by pulling froward (9)

6. Remove the temperature adjustment carrier(21) by rotating the black locking latch andpulling forward.

7. Remove the rear temperature handle exten-sion (20) by rotating the black locking latchand pulling forward.

8. The thermostatic cartridge (19) can now beremoved by turning anticlockwise.

9. It is usually unnecessary to fit a new thermostatic cartridge. Most problemsoccur because debris from the pipe workhas blocked the cartridge filter screens.

10. The cylindrical filter screens can be removedfor cleaning by removing the o-rings fromthe cartridge and sliding the screens off. Donot attempt to refit the cartridge with thefilter screens missing. Any small particles ofgrit in the water supply will cause the mech-anism to jam. (Place all components whichhave grease on them on a clean piece ofpaper to avoid picking up grit)

11. Grease the cartridge o-rings with siliconegrease when they have been refitted.

12. If a replacement cartridge is being fitted, fitit at this stage.

13. The valve is assembled in reverse order.

THERMOSTATIC CARTRIDGE REPLACEMENT

Figure 11

THERMOSTAT REPLACEMENT 8

trevi showers.qxd 07/11/02 10:35 Page 9

Page 10: trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line strainers/servicing valves (28) which include these flow restrictors. These should be inserted in

The rear temperature handle extension (20) canbe fitted on to the thermostatic cartridge (19) inany position.

The temperature adjustment carrier (21) willneed to be refitted with the triangular raisedmark on the rear of the carrier in the top posi-tion. Providing this assembly has not been sep-arated, (i.e. the red clip removed) the unit willremain calibrated and no adjustments will berequired. Ensure that the front handle carrier isrotated fully anticlockwise before refitting otherwise difficulty will be experienced in fittingthe temperature adjustment carrier to the reartemperature extension. The temperature handleis then refitted with the override button again inthe top position.

CALIBRATIONTrevi thermostats are factory calibrated andrequire no further calibartion during installa-tion. However, if the temperature adjustment

carrier is accidentally disturbed and the calibra-tion altered it is a simple procedure to recali-brate the unit. Before starting this you will needto ensure the hot supply temperature is above52ºC.

1. Remove the temperature control handle.

2. Remove the red U-clip (b) from the temper-ature adjustment carrier. Remove the frontcarrier (e).

3. Ensure the raised triangular mark (a) on therear handle carrier is to the top.

4. Rotate the temperature adjusting spindle(d) until a temperature of 40ºC is measuredat the outlet.

5. Replace the front handle carrier ensuringthe triangular indent (c) is to the top.

6. Refit the red U-clip.

7. Refit the temperature handle.

Figure 12

CALIBRATION9

trevi showers.qxd 07/11/02 10:35 Page 10

Page 11: trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line strainers/servicing valves (28) which include these flow restrictors. These should be inserted in

Trevi Traditional

The volume and temperature control handlesare not pre-fitted but are supplied packedwith the valve.

The Traditional valve should be fitted only inposition 3 as shown as in Figure 8

1. Push the volume control handle insert (10a)into the volume control handle (6a) andpush this assembly on the drive shaft (15).

2 Secure with the screw (8b) and finally pushthe cap (5) into place

For correct operation the temperature handlemust be fitted as follows

1 The temperature adjustment carrier is fittedas below.

2. To fit the temperature handle (7a), push itonto the temperature adjustment carrier(21) with the lever at the 4 o’clock position.The wide key on the inside of the levershould engage with the key way on thetemperature adjustment carrier (21).

3. Secure the lever with the screw (8)

4. When the lever is moved to the 6 o’clockposition the water temperature should beapproximately 35ºC

5. To increase the temperature, move the handle anticlockwise. See Figure 16

Figure 14

Figure 15

Figure 16

HANDLE FIXATION/REMOVAL 10

Figure 13 Fitting Trevi Traditional volume control handle

trevi showers.qxd 07/11/02 10:35 Page 11

Page 12: trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line strainers/servicing valves (28) which include these flow restrictors. These should be inserted in

Trevi Therm and Trevi OutlineTo remove the Outline handles, the cover slip(4d or 5d) should be prised up by inserting asmall screw driver in the recess as shown. Careshould be taken not to scratch the handle whiledoing this and it is advisable to wrap a piece ofmasking tape or similar around the screw driveras shown.

Unscrew screw (8b) and slide the handle off.The handle carrier can then be removed.

To replace the handle slide onto handle carrier(10) ensuring the key inside the handle engageswith the keyway in the carrier (10).

HANDLE FIXATION/REMOVAL11

Figure 17

Temperature over-ride button

The Trevi Therm and the Trevi OutlineThermostat (but not the Trevi Traditional) arefitted with a temperature over-ride button.Normally this is pre-set to limit the temperatureto 40ºC. However, higher temperatures maybe obtained by pressing the button and rotat-ing the temperature handle further.

The Trevi Therm button slides outwards and theTrevi Outline Thermostat button pivots inwardsas shown.

trevi showers.qxd 07/11/02 10:35 Page 12

Page 13: trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line strainers/servicing valves (28) which include these flow restrictors. These should be inserted in

Figure 19

SPARE PARTS 12

trevi showers.qxd 07/11/02 10:35 Page 13

Page 14: trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line strainers/servicing valves (28) which include these flow restrictors. These should be inserted in

Ref. Description

1 Front cover plate

2 Wall plate for Trevi Therm & Traditional

2a Cover plate sealing rings

3 Cover plate fixing screws 50 mm

3a Cover plate fixing screws 60 mm

4d Outline temperature handle cover slip

4e Trevi Therm Temperature handle cap

5 Traditional volume control handle cap

5d Outline volume handle cover slip

5e Trevi Therm volume handle cap

6a Traditional volume handle

6d Outline volume handle

6e Trevi Therm volume handle

7c Traditional temperature handle index

7d Outline temperature handle

7e Trevi Therm Temperature handle

8 Self tapping handle screw

8b Long volume handle screw

9 Standard Shroud

9a Traditional Volume control handle shroud

Ref. Description

10 Volume control handle carrier

10a Traditional volume control handle insert

11 Gear box cover

12 Gear box sealing washer

13 Gear box cover fixing screws

14 Gear/clutch wheels complete

15 Gear/ wheel drive shaft

16 Gear/clutch wheels

17 Gear box back plate

18 1/2” cartridge

19 Thermostatic control cartridge

20 Temperature handle extension

21 Temperature adjustment carrier complete

22 Blanking plug

23 Outline wall plate

24 Traditional temperature handle

25 Flushing adapter outlet

26 Mounting template/plaster guide

27 Mounting template/plaster guide screws

SPARE PARTS13

trevi showers.qxd 07/11/02 10:35 Page 14

Page 15: trevi showers - The Official Ideal Standard and Trevi ... · Trevi supply in-line strainers/servicing valves (28) which include these flow restrictors. These should be inserted in

Trevi Showers pursue a policy of continuingimprovement in design and performance of its products.The right is, therefore, reserved to vary specifications without notice.

Trevi Showers is a division of

American Standard Plumbing (UK) Ltd. T 096 4/02

Trevi Showers.The Bathroom Works,National Avenue,Kingston upon Hull,HU5 4HSEngland.Telephone: 01482 470788Fax: 01482 445886

CUSTOMER CARE HELPLINE

0870 1296082FAX LINE 01482 499611

E965033