Transformer Protection Relaying Scheme
-
Upload
cris-angeles -
Category
Documents
-
view
137 -
download
8
Transcript of Transformer Protection Relaying Scheme
![Page 1: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/1.jpg)
Transformer Protection Relaying Scheme
Prepared by: Angeles, Cris Julius C.2008106430
![Page 2: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/2.jpg)
IntroductionThe two major items of equipment in a power system are the generators and transformers. They have very high chance of fault occurrence and usually takes much time and money to repair the damage.
![Page 3: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/3.jpg)
Faults occurring in TransformersOpen-Circuit faultsEarth faultsPhase-to-Phase faultsInter-Turn faultsOverheating
![Page 4: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/4.jpg)
Factors in choosing Protective Gear for a TransformerType of TransformerSize of the TransformerType of CoolingSystem where usedImportance of service for which it is required
![Page 5: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/5.jpg)
Transformer Relaying Scheme
![Page 6: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/6.jpg)
Buchholz ProtectionAlso known as gas accumulator relay, commonly used on all oil-immersed transformer provided with conservator.
Working Principle:Whenever a fault occur inside the
transformer, the oil of the tank gets overheated and gases are generated. The heat generated by the high local current causes the transformer oil to decompose and produce gas which can be used to detect the winding faults
![Page 7: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/7.jpg)
Buchholz Protection
![Page 8: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/8.jpg)
Core-Balance Leakage ProtectionThis system is used to provide protection against earth faults on high voltage winding. When earth fault occurs, the sum of the three currents is no longer zero and a current is induced in the secondary of the CT causing the trip relay to operate and isolate the transformer from the bus-bars.
![Page 9: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/9.jpg)
![Page 10: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/10.jpg)
Combined Leakage and Overload ProtectionThe core-balance protection cannot provide protection against overload. It is usual practice to provide combined leakage and overload protection for transformer. The earth relay has low current setting and operates under earth faults only. The overload relays have high current setting and are arrange to operate against faults between the phases
![Page 11: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/11.jpg)
In this system, two overload relay and one earth relay are connected. The two overload relays are sufficient to protect against phase to phase faults. The trip contacts of overload relays and earth fault relay are connected in parallel. Therefore the energizing of either one of them, the circuit breaker will tripped.
![Page 12: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/12.jpg)
Description SIEMENS ABB
Multifunction Generator, Motor and
Transformer
SIPROTEC 4 7UM62 REM 543
Two- and three-winding transformers
protection
7SG14 RET650
Voltage regulator for
power transformers with on-load tap-changers
MJ-4A SPAU 341 C
High Impedance Protection
Relay
7VH60 SPAE 011
![Page 13: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/13.jpg)
Sample ComputationA 50MVA, 132/66 kV, / Y three-phase power transformer is protected by percentage differential relays. If the current transformers (CTs) located on delta and wye sides of the power transformer are 300/5 A and 1,200/5 A respectively, determine (a) the output current at full load (b) the relay current at full load (c) the minimum relay current setting to permit 25% overload.
![Page 14: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/14.jpg)
Given:50MVA, 132---66V delta - wyeCT1 = 300---5CT2 = 1200---5
FIND: a) Output current at FLb) Relay current at FLc) Minimum relay current to allow 25% overload
![Page 15: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/15.jpg)
a) Rated current for primary ( - connected side)
= = 218.7 A Ans.
![Page 16: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/16.jpg)
Current in hv side CTs = 218.7 Current in lv side CTs = 437.4 x
b) Relay current at full load = 3.645 = 0.489 A Ans.
![Page 17: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/17.jpg)
c) With 25% overloadLine current in secondaries of CTs
connected on hv side is and line current in secondaries of CTs connected in delta on lv side =
Relay Current = 4.56 – 3.94 = 0.62 ASo relay setting = 62% Ans.
![Page 18: Transformer Protection Relaying Scheme](https://reader036.fdocuments.us/reader036/viewer/2022082416/544e9c11af7959d91e8b4aca/html5/thumbnails/18.jpg)
ConclucionOpen-circuit faults, earth faults, phase-to-
phase faults, inter-turn faults and overheating are the fault that are likely occur in a transformer
Relays control output circuits of a much higher power.
Safety is increasedProtective relays are essential for keeping
faults in the system isolated and keep equipment from being damaged.