8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
1/294
15-13089011No
Arrive Architecture2344 Highway 121 Suite 100Bedford TX 76021
TO:
01/06/2016DATE:
HVACRE:
Clayton Arnal ATTN:
Shop Drawings
Letter
Prints
Change Order
Plans
Samples
Specifications
Other: Submittal
Approval
Your Use
As Requested
Review and Comment
Attached
Sent Via: Newforma
Approved as Submitted
Approved as Noted
Returned After Loan
Resubmit
Submit
Returned
Returned for Corrections
Due Date: 01/20/2016
WE ARE SENDING: SUBMITTED FOR:
SENT VIA:
ACTION TAKEN:
TRANSMITTAL
Courtney Linsacum
Signed:
PROJECT: Mariposa Point of Gilbert
Remarks:
01/06/2016
Date
23 05 00-001
Code
HVAC
Description
Submitted t Architect
Status
CC:
Item
Submittal 23
Package
1
Rev. Copies
3333 E Camelback Road Suite 122Phoenix, AZ 85018
602-840-7700Phone:
Fax:
15-13089PROJECT NO
817-514-0584
817-514-0694
PHONE:
FAX:
Other:
Page
Courtney Linsacum
DATE:__8/21/15____ BY:_Courtney Linsacum_
___X__REVIEWED ____REVIEWED AS NOTED _____REVISE & RESUBMIT
SUMMIT DCK, LLC
(602) 840-7700
08/28/15Dennis Janes
9/9/1509/15/1512/11/15
Dave Geroux
12/16/1501/06/16
Evan Oates
TELIOS COMMENTS:
1. NO TYPE II GREASE DUCT MATERIALS WERE FOUND IN THIS
SUBMITTAL. PROVIDE SUBMITTAL PRIOR TO PROCUREMENT.2. PTAC UNITS SHALL BE PROVIDED WITH HARDWIRE KIT ANDDISCONNECT SWITCH IN LIEU OF CORD AND PLUG AS APPEAR
BE SUBMITTED. COORDINATE FINAL REQUIREMENTS WITHELECTRICAL CONTRACTOR PRIOR TO ROUGH IN.
3. DISCONNECTING MEANS APPEARS TO BE EXCLUDED FROMPACKAGED ROOFTOP UNITS. PROVIDE INTEGRAL DISCONNEC
COORDINATE REQUIREMENT OF DISCONNECTING MEANS WIT
ELECTRICAL CONTRACTOR.4. MECHANICAL CONTRACTOR SHALL COORDINATE ANY
ELECTRICAL CHANGES THAT MAY BE REQUIRED DUE TO ALTERNATE EQUIPMENT CONTAINED IN THIS SUBMITTAL WITH
ELECTRICAL CONTRACTOR PRIOR TO PROCUREMENT OF
MATERIALS.5. REFER TO FOLLOWING PAGES FOR ADDITIONAL COMMENT.
01/24/16
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
2/294
SUBMITTAL DATA
Mariposa Point of Gilbert
DCK Summit
Telios
15-1-1767
23
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
3/294
Mariposa Point of Gilbert
230500 Common Work Results- NA
230513 Common Motor Requirements- NA230529 Hangers and Supports
230553 Identification of HVAC Piping & Equipment
230593 Testing, Adjusting and Balancing
230700 HVAC Insulation
230713 Duct Insulation- Please see section 230700
230719 HVAC Piping Insulation
231123 Facility Natural Gas Piping- NA
232300 Piping
233113 Metal Ducts
233300 Air Duct Accessories
233416 Centrifugal HVAC Fans
233713 Diffusers, Registers, and Grilles
234100 Particulate Air Filtration
236200 Package Compressor and Condenser Units
238113 Package Terminal Air Conditioners
238126 Split System AC- Please see section 236200
238219 Fan Coil Units- Please see section 236200
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
4/294
To Ind
Mariposa Point of Gilbert
230500
Common Work Results- NA
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
5/294
To Ind
Mariposa Point of Gilbert
230513
Common Motor Requirements- NA
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
6/294
To Ind
Mariposa Point of Gilbert
230529
Hangers and Supports
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
7/294
Project: ______________________________________________________________ Approval Stamp:
Architect / Engineer: ___________________________________________________
Date: _________________________ Phone: ________________________________
Contractor: ___________________________________________________________
Address: _____________________________________________________________
____________________________________________________________________
Notes 1: _____________________________________________________________
____________________________________________________________________
Notes 2: _____________________________________________________________
____________________________________________________________________
MATERIAL
Unistrut channels are accurately and carefully cold formed to size
from low-carbon strip steel. All spot-welded combination members,
except P1001T, are welded 3" (76 mm) maximum on center.
STEEL: PLAIN
12 Ga. (2.7 mm), 14 Ga.(1.9 mm) and 16 Ga. (1.5 mm)
ASTM A1011 GR33
STEEL: PRE-GALVANIZED
12 Ga. (2.7 mm), 14 Ga. (1.9 mm) and 16 Ga. (1.5mm)
ASTM A653 GR 33
For other materials, see Special Metals or Fiberglass sections.
FINISHES
All channels are available in:
• Perma Green II (GR)
• Pre-galvanized (PG), conforming to ASTM A653 G90
• Hot-dipped galvanized (HG), conforming to ASTM A123
• Plain (PL)
® 15 ⁄ 8" Channel
41.3
82.61
22
1 5 ⁄ 8"
3 1 ⁄ 4"1
P1001 Wt/100 Ft: 380 Lbs (566 kg/100 mAllowable Moment 14,390 In-Lbs (1,630 N•m
12 Gauge Nominal Thickness .105" (2.7mm
BEAM LOADING – P1001Max Defl. at
Allowable Uniform Uniform Loading at Deflection
Span Uniform Load Load Span/180 Span/240 Span/360
In Lbs In Lbs Lbs Lbs
24 3,130 * 0.03 3,130 * 3,130 * 3,130 *
36 3,130 * 0.07 3,130 * 3,130 * 3,130 *
48 2,400 0.13 2,400 2,400 2,400
60 1,920 0.20 1,920 1,920 1,630
72 1,600 0.28 1,600 1,600 1,130
84 1,370 0.39 1,370 1,240 830
96 1,200 0.50 1,200 950 640
108 1,070 0.64 1,000 750 500
120 960 0.79 810 610 410
144 800 1.13 560 420 280
168 690 1.54 410 310 210
192 600 2.01 320 240 160
216 530 2.55 250 190 130
240 480 3.15 200 150 100
COLUMN LOADING – P1001Maximum
Unbraced Allowable Load Maximum Column Load Applied at C.G.
Height at Slot Face K = 0.65 K = 0.80 K =1.0 K = 1.2
In Lbs Lbs Lbs Lbs Lbs24 6,430 25,060 24,620 23,900 23,050
36 6,230 24,000 23,050 21,570 19,890
48 5,950 22,590 21,030 18,690 16,170
60 5,620 20,890 18,690 15,540 12,400
72 5,240 18,990 16,170 12,400 8,960
84 4,830 16,970 13,640 9,470 6,580
96 4,390 14,900 11,200 7,250 5,040
108 3,930 12,860 8,960 5,730 3,980
120 3,510 10,910 7,250 4,640 **
Channel Finishes:PL, GR, HG, PG;Standard Lengths:10' & 20'
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
8/294PH-1.15
PROJECT INFORMATION APPROVAL STAMP
Project: Approved
Address: Approved as noted
Contractor: Not approved
Engineer: Remarks:
Submittal Date:
Notes 1:
Notes 2:
HANGER RODS
Fig. 146 Continuous Threaded Rod
Size Range: 1⁄4" through 1 1⁄2" Stocked in six, ten, and twelve foot
lengths. Other even foot lengths can be furnished to order.
Material: Carbon steel or Stainless Steel Gr 304
Threads: National Coarse (USS), rod threaded complete length.Finish: Plain or Zinc Plated (Hot-Dip Galvanized optional)
Maximum Temperature: 650° F.
Ordering: Specify rod diameter and length, figure number,
name and finish.
Note: The acceptability of galvanized coatings at temperatures
above 450°F is at the discretion of the end user.
FIG. 146:LOADS (LBS) • WEIGHTS (LBS) • DIMENSIONS (IN)
Rod SizeA
Threadsper Inch
Max Load Weightper Ft.650˚ F
1 ⁄ 4 20 240 0.123 ⁄ 8 16 730 0.301 ⁄ 2 13 1,350 0.535 ⁄ 8 11 2,160 0.843 ⁄ 4 10 3,230 1.207 ⁄ 8 9 4,480 1.70
1 8 5,900 2.30
11 ⁄ 4 7 9,500 3.60
11 ⁄ 2 6 13,800 5.10
Note: Other rod sizes available upon request. Class 2 fit is available upon request.
A
Length
Telios
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
9/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
10/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
11/294PH-11.11
PROJECT INFORMATION APPROVAL STAMP
Project: Approved
Address: Approved as noted
Contractor: Not approved
Engineer: Remarks:
Submittal Date:
Notes 1:
Notes 2:
CLEVIS HANGERS
Fig. 67 Pipe or Conduit Hanger
Size Range: 1⁄2" through 6"
Material: Carbon steel
Finish: Galvanized
Service: Can be suspended by hanger rod or attached to wall. “T” slot in hangerpermits side bolt to be installed after installation and setting of pipe.
Approvals: Complies with Federal Specification A-A-1192A (Type 5),
ANSI/MSS SP-69 and MSS SP-58 (Type 5).
Components: Strap and bolt with nut – assembled.
Ordering: Specify pipe size, figure number and name.
FIG. 67: LOADS (LBS) • WEIGHT (LBS) • DIMENSIONS (IN)
PipeSize
LoadRating
WeightRod Size
AB C D E F G
HWidth
1 ⁄ 2
400
0.21
3 ⁄ 8
25 ⁄ 8
1 ⁄ 4
13 ⁄ 4
7 ⁄ 16
11 ⁄ 2 115 ⁄ 16
1
3 ⁄ 4 0.22 27 ⁄ 8 17 ⁄ 8 111 ⁄ 16 21 ⁄ 8
1 0.25 215 ⁄ 16 115 ⁄ 16 113 ⁄ 16 25 ⁄ 16
11 ⁄ 4 0.27 31 ⁄ 4 2 21 ⁄ 16 25 ⁄ 8
11 ⁄ 2 0.29 39 ⁄ 16 23 ⁄ 16 27 ⁄ 16 27 ⁄ 8
2 0.31 311 ⁄ 16 21 ⁄ 8 29 ⁄ 16 31 ⁄ 16
21 ⁄ 2500
0.71 1 ⁄ 247 ⁄ 16
3 ⁄ 8
27 ⁄ 16
9 ⁄ 16
33 ⁄ 16 35 ⁄ 8
11 / 4
3 0.78 413 ⁄ 16 29 ⁄ 16 31 ⁄ 2 41 ⁄ 16
4550
1.39 5 ⁄ 861 ⁄ 8 33 ⁄ 16 45 ⁄ 8 53 ⁄ 16
5 1.66 63
⁄ 4 31
⁄ 4 51
⁄ 16 53
⁄ 46 600 2.26 3 ⁄ 4 73 ⁄ 4 39 ⁄ 16 513 ⁄ 16 65 ⁄ 8
F
CL
A
G
D
E
C
B
CL
H
Alternate Installation
Bolt/Screw to Vertical Support
Telios
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
12/294
To Ind
Mariposa Point of Gilbert
230553
Identification of HVAC Piping & Equipment
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
13/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
14/294
Use:
Features:
Identification & Safety Experts
20 Thompson Rd. Branford, CT 06405-
Phone: 800-243-
Fax: 800-345-
Email: SetonUSA@seton
Date: / / Job:
Contractor
1763/0409
www.seton.com Phone: 800-243-6624 Fax: 800-345-7819
PRODUCT DATA SHEET
VALVE TAGS
BRASS VALVE TAGS
Material:
Size/Shape:
Ink Fill Color Options:
Maximum Temperature:Top Hole Size:
Letter Height:
Number Height:
STAINLESS STEEL VALVE TAGS
Material:
Size/Shape:
Ink Fill Color Options:
Maximum Temperature:Top Hole Size:
Letter Height:
Number Height:
ALUMINUM VALVE TAGS
Material:
Size/Shape:
Ink Fill Color Options:
Maximum Temperature:Top Hole Size:
Letter Height:
Number Height:
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
15/294
Identification & Safety Experts
20 Thompson Rd. Branford, CT 06405-
Phone: 800-243-
Fax: 800-345-
Email: SetonUSA@seton
Date: / / Job:
Contractor
1763/0409
www.seton.com Phone: 800-243-6624 Fax: 800-345-7819
PRODUCT DATA SHEET
BEADED CHAIN
ALUMINUM BEADED CHAIN
Description: Flexible beaded chain is lightweight and
corrosion resistant
Melting Point: 1250°F
Specifications: 4-1/2" lengths of flexible beaded chain
Ball Diameter: 1/8"
Avg. Tensile Strength: 16 lbs.
STAINLESS STEEL BEADED CHAIN
Description: Grade 304 of stainless steel is great for roughenvironments that need corrosion resistanceand strength.
Melting Point: 2550°F
Specifications: 4-1/2" lengths of flexible beaded chain
Ball Diameter: 1/8"
Avg. Tensile Strength: 45 lbs.
NICKEL BEADED CHAIN
Description: Nickel plate over solid steel material willnot rust or corrode.
Melting Point: 1680°F
Specifications: 4-1/2" lengths of flexible beaded chain
Ball Diameter: 1/8"
Avg. Tensile Strength: 30 lbs.
BRASS BEADED CHAIN
Description: Polished, durable Brass beaded chain willnot rust or corrode.
Melting Point: 1680°F
Specifications: 4-1/2" lengths of flexible beaded chain
Ball Diameter: 1/8"
Avg. Tensile Strength: 30 lbs.
Use: Adjustable open and close links allow for varying the length of
chain for each particular valve.
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
16/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
17/294
To Ind
Mariposa Point of Gilbert
230593
Testing, Adjusting and Balancing
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
18/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
19/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
20/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
21/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
22/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
23/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
24/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
25/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
26/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
27/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
28/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
29/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
30/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
31/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
32/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
33/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
34/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
35/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
36/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
37/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
38/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
39/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
40/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
41/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
42/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
43/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
44/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
45/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
46/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
47/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
48/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
49/294
To Ind
Mariposa Point of Gilbert
230700
HVAC Insulation
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
50/294
Jeff Herron
Vice President Preferred Insulation Contractors, Inc.
Cell (602) 763-1652
P referred
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
51/294
Subm ittal Sheet
TYPE 75
TYPE 100
11/2" (38mm) 11/2" (38mm)
2" (51mm) 2" (51mm)
21/5" (56mm)
2
2
/5" (61mm)
TYPE 15021/2" (64 mm) 11/2" (38mm)
3" (76 mm) 2" (51mm)
31/2" (89 mm)
4" (102 mm)
SO FTR A ll-Service Fiber G lass D uct W rap is now
reform ulated to reduce dust and itch.
Description
SOFTR All-Service F iber Glass D uct W rap is ablanket of glass fiber insulation factory-lam inated toFRK vapor retarder facing. A 2" (50m m ) stapling andtaping flange is provided on one edge. This product isdesigned to m eet existing perform ance standards suchas N FPA 90A and 90B and other m odel building andenergy codes.
Uses
SOFTR A ll-Service Fiber Glass Duct W rap is usedfor external insulation of com m ercial and residentialheating, air conditioning and d ual-tem perature ductsoperating at tem peratures from 40F (4C) to 250F(121C). This insulation, w hen applied inaccordance w ith installation instructions, w illprovide the “installed R-value”as published for theproduct and printed on the facing, assuring specifiedin-place therm al perform ance an d condensationcontrol.
Features/ Benefits
Assured Thermal Performance
W hen installed in accordance w ith instructions sothat com pression is controlled, SO FTR A ll-Service Fiber G lass Duct W rap provides specifiedtherm al perform ance. See R-value table below .O perating costs are controlled due to reduction of
heat loss or gain through duct walls.
All-Service Fiber Glass Duct W rap
Condensation Control
SO FTR All-Service Fiber G lass D uct W rap helps
control m oisture condensation on the ductw ork as well ason the outer vapor retarder jacket. This helps m aintaininsulation efficiency and reduces the likelihood of stained
ceilings due to m oisture dam age.
Enhanced Comfort Control
SO FTR All-Service Fiber G lass D uct W rap helpsheating and cooling system s to deliver conditioned air tooccupied spaces at or near design tem peratures.By conserving heating and cooling energy, H VA C
system s m ay operate under reduced load.
Meets Model Energy and Mechanical Codes
SO FTR All-Service Fiber G lass D uct W rap, w hencorrectly installed, com plies w ith m odel energy codes
and standards including A SH RA E 90.1 and 90.2.A rchitects, contractors, code officials and ow ners areassured of com pliance and “no-problem ”inspection.A pplication of insulation is the responsibility of the
engineer and contractor
Flexible and Easy to Install
SO FTR All-Service Fiber G lass D uct W rap is easily
cut and fit to flat, curved or irregular duct surfaces fora neat, therm ally effective insulation blanket. Becauseit’s easier to install than rigid boards, installation costs
are low ered.
Facings
The facing on O w ens Corning SO FTR A ll-ServiceFiber G lass Duct W rap is a F oil Reinforced K raft(FR K ) low perm eance vapor retarder m eeting therequirem ents of A ST M C 1136, Type II.
Availability and Installed R-ValuesStandard roll w idth: 48" (1.2m )Installed R (RSI) values: W hen installed in accordance w ith recom m ended installation procedures, SO FTRAll-Service Fiber G lass D uct W rap w ill provide installed R (RSI) values as follow s:
Nominal Out-of-Package Installed Installed
Thickness, in. (mm) R (RSI) Value(1) Thickness(2), in. (mm) R (RSI) Value(1)(2)
TYPE 75 – 0.75 pcf (12 kg/ m3)
11/2 (38) 5.1 (0.90) 1 1/8 (29) 4.2 (0.74)2 (51) 6.8 (1.20) 11/2 (38) 5.6 (0.99)21/5 (56) 7.4 (1.30) 1 5/8 (42) 6.0 (1.06)22/5 (61) 8.0 (1.41) 1 13/16 (46) 6.5 (1.14)21/2 (64) 8.3 (1.46) 1 7/8 (48) 6.9 (1.22)3 (76) 10.0 (1.76) 21/4 (57) 8.3 (1.46)
31/2 (89) 11.0 (1.94) 2 5/8 (67) 9.7 (1.71)4 (102) 13.25 (2.33) 3 (76) 11.0 (1.94)
TYPE 100 – 1.00 pcf (16 kg/ m3
)11/2 (38) 5.6 (0.99) 1 1/8 (29) 4.5 (0.79)2 (51) 7.4 (1.30) 11/2 (38) 6.0 (1.06)
TYPE 150 – 1.50 pcf (24 kg/ m3)
11/2 (38) 6.0 (1.06) 1 1/8 (29) 4.8 (0.85)2 (51) 8.0 (1.41) 11/2 (38) 6.4 (1.13)
(1)hr•ft2•F/Btu (m 2•C/W ) at 75F (24C) m ean tem perature. (2)A ssum es 25% com pression of insulation.
Specification Compliance
•A ST M C 1290, Flexible Fibrous G lass Blanket Insulation U sed to E xternally Insulate H VA C D ucts, Type III
•A ST M C 1136, Flexible Low Perm eance Vapor Retarders for Therm al Insulation, Type II (facing only)
•A ST M C 553,* M ineral Fiber Therm al Insulation: Type I –Fiberglas All-Service D uct W rap Type 75; Type II –SO FTR All-Service Fiber Glass D uct W rap Types 100 and 150. (O perating tem peratures to 250F (121C)and therm al values to 150F (66C) m ean.
* Preferred specification is AST M C 1290.
N O TE T O SP E CIFIER S –Fed eral Specification H H -I-558B (Am endm ent 3), Form B (covering the duct w rap), and FederalSpecification H H -B-100B (covering the facing), are obsolete. These are replaced by the above referenced A ST M specifications
Thermal Conductivity
Mean Temperature, F
Apparent thermal conductivity curve determinedin accordance with ASTM Practice C 1045 withdata obtained by ASTM Test Method C 177.Values are nominal, subject to normal testingand manufacturing tolerances.
0.45
0.40
0.35
0.30
0.25
0.20
k, Btu•in/hr•ft2•F
TYPE 75TYPE 100
TYPE 150
25 50 75 100 125 150
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
52/294
OWENS CORNING WORLD HEADQUARTERS
O N E O W E N S C O R N IN G P A R KW A Y
TO LEDO , O H IO , U SA 43659
1-800-G ET-PIN K
w w w .ow enscorning.com
Pub. N o. 59241-A Printed in US A , O ctobe r 2003 Copyright © 200 3 O w ens C orning.
Title Subhead is Futura Bold 9pt/ 12 Leading
SO FTR All Service Fiber Glass D uct W rap
Application Recommendations
Before applying SO FTR A ll-Service Fiber G lassD uct W rap, ducts shall be clean, dry and tightly sealed
at all joints and seam s. SO FTR A ll-Service Fiber
G lass D uct W rap shall be cut to “stretch-out”dim en-
sions and a 2" (50m m ) (approx.) piece of duct w rap
rem oved from the facing at the end of the piece of
duct w rap to form an overlapping staple and tape
flap, as show n below .
Install duct w rap tightly butted w ith facing outside.
O verlap 2" (50m m ) form ed tape flap and facing at
other end of piece of duct wrap. If du cts are
rectangular or squ are, install so insulation is not
excessively com pressed at duct corners. Seam s shall
be stapled 6" (150 m m ) (approx.) on center with
outward clinching staples. A djacent sections of duct
w rap shall be tightly butted w ith the 2" (50m m )
tape flap overlapping.
W here a vapor retarder is required, seal all seam s
and joints w ith pressure-sensitive tape m atching the
facing (either plain foil or FR K backing stock) or
Physical Property Data
Property Test Method Value
O perating tem perature A STM C 411 up to 250F (121C)
Insulation jackettem perature lim it A STM C 1136 up to 150F (66C)
W ater vapor perm eance A STM E 96 0.02 perm s
W ater vapor sorption A STM C 1104
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
53/294
HVAC Insulation
Microlite® EQFormaldehyde-free ™ Fiber Glass Duct Wrap Insulation
Description
Microlite® EQ Formaldehyde-free ™ duct wrap insulation is a brown,
lightweight, highly resilient, blanket-type thermal insulation.
The insulation blanket is manufactured from rotary-process fiberglass bonded with a resin made primarily from rapidly renewable
plant-based materials.
Available Forms
Microlite EQ Formaldehyde-free ™ insulation is available in a variety
of densities, thicknesses and roll lengths. It is supplied with an FSK
(foil-scrim-kraft) vapor barrier facing to meet installed performance
requirements, with a 2" (51 mm) stapling tab.
Uses
Microlite EQ insulation is recommended as thermal insulation for the
exterior of HVAC systems or other spaces or surfaces where temperature
control is required.
Facing Information
FSK Aluminum FoilReinforced with fiber glass scrim laminated to UL-rated kraft.
Permeance: 0.02 perms*
*Per ASTM E96, Procedure A for facing material prior to lamination. After
lamination, permeance values may be higher.
General Properties
Temperature (max.) – ASTM C411 250°F (121°C)
Water vapor sorption – ASTM C1104
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
54/294
717 17th St.
Denver, CO 80202
800-654-3103
www.JM.com
North American Sales Offices,Insulation Systems
Eastern RegionP.O. Box 158
Defiance, OH 43512
(800) 334-2399
Fax: (419) 784-7866
Western Region and CanadaP.O. Box 5108
Denver, CO 80217
(800) 368-4431
Fax: (303) 978-4661
The physical and chemical properties of the Microlite® EQ
Formaldehyde-free ™ fiber glass duct wrap insulation listed hereinrepresent typical, average values obtained in accordance with
accepted test methods and are subject to normal manufacturing
variations. They are supplied as a technical service and are subject
to change without notice. Numerical flame spread and smoke
developed ratings are not intended to reflect hazards presented by
these or any other materials under actual fire conditions. Check with
the Regional Sales Office nearest you to ensure current information.
All Johns Manville products are sold subject to Johns Manville’s
standard Terms and Conditions, including Limited Warranty and
Limitation of Remedy. For a copy of the Johns Manville standard
Terms and Conditions, Limited Warranty and Limitation of Remedy,
and information on other Johns Manville thermal insulation and
systems, call (800) 654-3103.
© 2015 Johns Manville. All Rights Reserved.
Microlite® EQ
Formaldehyde-free ™ Fiber Glass Duct Wrap Insulation
Application Recommendations
The R-value will vary depending upon how much the insulation is
compressed during installation. To obtain the published installed
R-values, the insulation stretch-out should be determined using the
following table:
Duct Wrap Stretch-outs
Installed
Labeled Compressed
Thick. (in) Thickness (in) Round Square Rectangular
1 0.75 P+ 7.0" P+ 6.0" P+ 5.0"
1½ 1.125 P+ 9.5" P+ 8.0" P+ 7.0"
2 1.50 P+ 12.0" P+ 10.0" P+ 8.0"
21 ⁄ 3 1.75 P+ 13.0" P+ 11.0" P+ 8.5"
3 2.25 P+ 17.0" P+ 14.5" P+11.5"
Stretch-outs include 2" (51 mm) for overlap. P = perimeter of duct to be insulated.
Prepare overlap by removing approximately 2" (51 mm) of insulation
from facing.
Stretch-outDimension
2" (51 mm)Overlap
Before applying duct wrap, sheet metal duct shall be clean, dry and
tightly sealed at all joints and seams.
Wrap insulation around duct with facing to the outside so the 2" (51 mm)
flap completely overlaps facing and insulation at the other end of stretch-
out. Insulation shall be snugly butted.
Secure seams with outward clinching staples placed approximately
6" (152 mm) on center. If required, seal seam with pressure-sensitive
tape designed for use with duct insulation. Insulation on the underside of
ducts spanning 24" (610 mm) or greater shall be secured with mechanical
fasteners and speed clips spaced approximately 18" (457 mm) on center.
Fasteners should be cut off flush after the speed clips are installed, and
when required, sealed with the same tape as specified above.
Adjacent sections of duct wrap insulation shall be snugly butted with
the circumferential 2" (51 mm) tape flap overlapping and secured as
recommended for the longitudinal seam. When a vapor seal is required,
two coats of vapor retarder mastic reinforced with one layer of 4"
(102 mm) wide, open-weave glass fabric may be used in lieu of pressure-
sensitive tape.
Guide Specifications
Insulation for Metal Ducts. All ducts shall be insulated on the outsidewith a Formaldehyde-free ™, flexible glass fiber blanket. Microlite EQ
Formaldehyde-free ™ fiber glass duct wrap insulation should have a
minimum installed R-value* of _______, and a Type_____ facing.
Insulation shall be furnished with a factory-applied facing with a
composite UL FHC rating of 25/50.
*The minimum insulation installed R-value should be determined in accordance tothe duct operating and ambient conditions.
Installed R-values
LabeledThickness Installed “R”** Out-of-Package “R”
Type in mm (hr•ft2•°F) /Btu m2•°C/W (hr•ft2•°F)/Btu m2•°C/W
75 1½ 38 4.2 0.74 5.2 0.922 51 5.6 0.99 6.9 1.2221 ⁄ 3 58 6.5 1.15 8.0 1.413 76 8.3 1.46 10.3 1.81
100 1½ 38 4.5 0.79 5.6 0.99
2 51 6.0 1.06 7.4 1.30150 1½ 38 4.7 0.83 6.0 1.06
2 51 6.3 1.11 8.0 1.41
**Installed R-value calculated with a material thickness compressed to a
maximum of 25% following recommended duct wrap stretch-outs.
Thermal Conductivity (ASTM C518)
k* k
Compressed Thickness Labeled Thickness
Type Btu•in/(hr•ft2•°F) W/m•°C Btu•in/(hr•ft2•°F) W/m•°C
75 0.27 0.039 0.29 0.042100 0.25 0.036 0.27 0.039
150 0.24 0.035 0.25 0.036
Conductivity at 75°F (24°C) mean temperature.
*Tested with material thickness compressed 25%.
HVAC-448 5/15 (Replaces 11/14)
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
55/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
56/294
• For cooling, heating or dual
temperature service.
• Friendly Feel® Duct Wrap—
meets the most stringent
IAQ tests—GREENGUARD
Children & SchoolsSM
andCalifornia’s Section 01350
standard.
• Both white and black PSK
facings offer exceptional
durability and performance
for exposed applications.
• KwikStretch Markings allow
for easier, faster measure-
ment of stretch-out lengths.
Facts at a glance
• Black PSK facing is a
desirable solution for
exposed ductwork because
of its appearance and
resiliency.
• Fire-resistant facing
• Conforms to flat or irregular surfaces
• Excellent acoustical properties
• ECOSE Technology is a revolutionary new more sustainable binder based on
rapidly renewable bio-based materials rather than non-renewable petroleum-based
chemicals such as phenol, formaldehyde, acrylics or artificial colors.
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
57/294
Friendly Feel® Duct Wrap with ECOSE ® Technology
Description
Knauf Friendly Feel® Duct Wrap with ECOSE
Technology and KwikStretch® Markings is a thermal
and acoustical insulation blanket made from
highly resilient, inorganic glass fibers bonded by
a thermosetting resin. It is available unfaced, with
a foil-scrim-kraft (FSK) jacket and with a white or
black metalized polypropylene-scrim-kraft (PSK)
jacket. Vapor retarders provide a 2" (51 mm) staple
flange on one edge, and the factory-applied facing
assures uniform quality. KwikStretch Markings on
the staple flange allow for easy and accurate job
site measurements.
ECOSE Technology
ECOSE Technology is a revolutionary new binder
chemistry that makes Knauf Insulation products
even more sustainable than ever. It is based on
rapidly renewable bio-based materials rather
than non-renewable petroleum-based chemicals
traditionally used in fiberglass insulation products.
ECOSE Technology reduces binder embodied
energy and does not contain phenol, formaldehyde,
acrylics or artificial colors.
Application
Knauf Friendly Feel® Duct Wrap is used as external
insulation on commercial or residential heating or
air conditioning ducts. It is suitable for the exterior
of rectangular or round sheet metal ducts and
spaces or surfaces where temperature and conden-
sation must be controlled.
Features and Benefits
• Low “k” factor significantly reduces heat gain or
loss when applied with proper compression.
• Flexible.
• Lightweight.
• KwikStretch Markings on the FSK and PSK
staple flanges.
• Excellent acoustical properties.
• Tough and resilient.
• Energy conservation, which lowers operating costs.
• System efficiency increases; energy usage/costs
decrease.
• Conforms easily to flat or irregular surfaces.
• Rolls allow for faster installation, lower labor costs.
• Easier, faster measurement of stretch-out
lengths.
• Reduces sound transmission through the duct wall.
• Assured condensation control when used with
FSK or PSK facings, proper installation and
sealed joints, seams and penetrations.
• Resists damage in shipment and during and
after installation.
• Certified for indoor air quality as a low emitting
product by The GREENGUARD Environmental
Institute to both the GREENGUARD Certification
ProgramSM and the more stringent GREEN-
GUARD Children and SchoolsSM standard.
Specification Compliance
In U.S.:
• ASTM C 1139 - unfaced; Type I, Type II,
Grade 1 - 0.75 lb/ft3
Grade 2 - 1.0 lb/ft3
Grade 3 - 1.5 lb/ft3
• ASTM C 553; Type I, II, III• ASTM C 1136; Type II
• ASTM C 1290
• GREENGUARD Children & SchoolsSM
Certification
• California Title 24 (installed at 25%
compression)
• HH-I-558C; Form B, Type I, Class 7
• NFPA 90A and 90B
In Canada:
• CAN/ULC S102-M88
• CAN/CGSB-51.5M; Type II (FSK facing)
• CAN/CGSB-51.11-92
Technical Data
Surface Burning Characteristics
• UL/ULC Classified (FSK).
• Unfaced or composite (insulation, facing and
adhesive) does not exceed 25 Flame Spread,
50 Smoke Developed when tested in accor-
dance with ASTM E 84 (PSK only), CAN/ULC
S102-M88, NFPA 255 and UL 723.
Temperature Range (ASTM C 411)
• Faced, can be used on ducts operating up to
250°F (121°C).
• Unfaced, up to 350°F (177°C).
Water Vapor Permeance (ASTM E 96,
Procedure A)
• FSK and white PSK facings have maximum
water vapor permeance of .02 perms.
• Black PSK facing has a maximum water vapor
permeance of .09 perms.
Water Vapor Sorption (ASTM C 1104)
• Less than 5% by weight when tested for
96 hours at 120°F (49°C) and 95% relative
humidity.
Corrosiveness (ASTM C 665)
• Does not accelerate corrosion on steel,
copper or aluminum.Corrosion (ASTM C 1617)
• The corrosion rate in mils/yr will not exceed that
of the 1 ppm chloride solution.
Mold Growth (ASTM C 1338)
• No growth.
Puncture Resistance
(TAPPI Test T803) (Beach Units)
• FSK and PSK: 25
Application & Specification Guidelines
Storage
• Protect stored insulation from water damage,
construction damage and other abuse.
• If stored outside, proper protection from weather
conditions should be provided.
Preparation
• Install Knauf Friendly Feel® Duct Wrap over
clean, dry sheet metal ducts. All sheet metal
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
58/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
59/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
60/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
61/294
To Ind
Mariposa Point of Gilbert
230713
Duct Insulation- Please see section 230700
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
62/294
To Ind
Mariposa Point of Gilbert
230719
HVAC Piping Insulation
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
63/294
Jeff Herron
Vice President Preferred Insulation Contractors, Inc.
Cell (602) 763-1652
P referred
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
64/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
65/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
66/294
To Ind
Mariposa Point of Gilbert
231123
Facility Natural Gas Piping- NA
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
67/294
To Ind
Mariposa Point of Gilbert
232300
Piping
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
68/294
tubeCOPPER TUBE FOR CONSTRUCTION APPLICATIONS
Technical Data: 7-04
Corporate Headquarters
PO Box 66800 • St. Louis, MO 63166-6800
888-237-7611 | 618-337-6000 • f. 618-337-6958
www.cerroflow.com
Copper UNS No. C12200Types K, L, and MASTM B88
Color marking is not applicable to tube furnished in annealed straight
lengths or coils.
Typical uses include:
• Type M - above ground residential and light
commercial uses. (Sizes range from 3/8" - 8"
diameter)
• Type L - residential and commercial uses.
(Sizes range from 1/4" - 8" diameter)
• Type K - underground residential, commercial
and industrial uses. (Sizes range from
1/4" - 8" diameter)• Type DWV - ASTM B306: used for drainage,
waste and vents
Cerro tube is the original copper tube for plumbing, air conditioning and
refrigeration applications in residential, commercial and institutional
installations. We provide a complete range of sizes and types, engineered
to exact specifications to meet the highest standards of performance.
Product
Copper
Water Tube,
Type K
(heavy wall)
Copper
Water Tube,
Type L
(medium wall)
Copper
Water Tube,
Type M
(light wall)
Copper
Drainage
Tube,
Type DWV
Temper
Hard
Soft
Hard
Soft
Hard
Hard
Lengths
10 ft. straight
20 ft. straight
20 ft. straight40 ft. coils
60 ft. coils
100 ft. coils
10 ft. straight
20 ft. straight
20 ft. straight
30 ft. coils
40 ft. coils
60 ft. coils
100 ft. coils
10 ft. straight
20 ft. straight
10 ft. straight
20 ft. straight
Uses
Domestic water
service and
distribution, fire
protection, solar,fuel/fuel oil, HVAC,
snow melting,
compressed air,
natural gas,
liquefied petroleum
(LP) gas, vacuum
Domestic water
service and
distribution, fire
protection, solar,
fuel/fuel oil, HVAC,
snow melting,
compressed air,
natural gas,
liquefied petroleum
(LP) gas, vacuum
General plumbing
and heating purposes;
drainage waste,
vent and other light
pressure uses.
Drainage waste,
vents, soil and other
non-pressure
applications
Specifications
ASTM B88
ASTM B88
ASTM B88
ASTM B306
Code
Green
Blue
Red
Yellow
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
69/294
AHEAD OF THE F LOW®
C o p p e r F i t t i n g
CATALOG C-CF-0508
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
70/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
71/294
A H E A D O F T H E F L O W® www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com6
Revision 5/1/08
703-2Fitting Adapter Ftg x F – Cast APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
1/2 x 1/4 0.11 17 /32
3/4 x 1/2 0.12 19 /16
1 x 3/4 0.38 131 /32
1 x 1/2 0.15 17 /16
2 1/2 1.65 215
/16 3 2.47 31 /4
703-5 Special
Drop Adapter C x F – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
1/2 0.16 3 /4
3/4 0.24 31 /32
703-5BDrop Adapter C x F – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
1/2 0.15 3 /4
ADAPTERS
603Adapter C x F – Wrot APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
1/8 0.03 13 /32
1/8 x 1/4 0.03 1 /2
1/4 0.03 5 /8
1/4 x 3/8 0.05 21 /32
3/8 0.04
11
/16
3/8 x 1/2 0.09 29 /32
3/8 x 1/4 0.03 9 /16
1/2 0.09 27 /32
1/2 x 3/4 0.14 1
1/2 x 3/8 0.04 17 /32
1/2 x 1/4 0.05 1 /2
5/8 x 3/4 0.12 29 /32
5/8 x 1/2 0.11 3 /4
3/4 0.15 29 /32
3/4 x 1 0.21 11 /8
3/4 x 1/2 0.10 5 /8
1 0.24 31 /32
1 x 1 1/4 0.28 17 /32 1 x 3/4 0.19 25 /32
1 x 1/2 0.24 5 /8
1 1/4 0.33 13 /32
1 1/4 x 1 1/2 0.40 11 /4
1 1/4 x 1 0.27 31 /32
1 1/2 0.44 11 /8
1 1/2 x 2 0.50 11 /32
2 0.63 13 /32
2 x 1 1/2 0.74 13 /16
2 1/2 1.13 –
3 1.94 –
703Adapter C x F – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
1/4 x 1/2 0.13 27 /32
1/2 x 1 0.30 1
3/4 x 1 1/4 0.55 11 /8
3/4 x 3/8 0.17 3 /4
1 x 1 1/2 0.6813
/32
1 1/4 x 1 0.27 31 /32
1 1/4 x 3/4 0.29 3 /4
1 1/2 x 2 0.78 11 /32
1 1/2 x 1 0.37 25 /32
1 1/2 x 1 1/4 0.47 11 /4
2 x 1 1/4 0.76 27 /32
2 1/2 1.62 13 /8
3 2.34 11 /2
4 4.05 19 /16
603-2Fitting Adapter Ftg x F – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
1/4 0.03 13 /32
3/8 0.06 13 /16
1/2 0.09 17 /16
1/2 x 3/8 0.05 11 /4
3/4 0.13 111 /16 1 0.27 21 /32
1 1/4 0.31 21 /8
1 1/2 0.43 25 /16
2 0.61 217 /32
Consult price sheet for Made to Order items andfor minimum order quantities.
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
72/294
A H E A D O F T H E F L O W® www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
7
Revision 5/1/08
ADAPTERS continued
604Adapter C x M – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
1/8 x 1/4 0.03 7 /16
1/4 0.03 23 /32
3/8 0.04 15 /32
3/8 x 3/4 0.15 15 /16
3/8 x 1/2 0.09 1 1/2 0.07 5 /8
1/2 x 1 0.25 11 /2
1/2 x 3/4 0.15 13 /16
1/2 x 3/8 0.05 19 /32
1/2 x 1/4 0.07 5 /8
5/8 x 3/4 0.16 11 /8
5/8 x 1/2 0.08 3 /4
3/4 0.14 13 /16
3/4 x 1 0.26 17 /16
3/4 x 1/2 0.10 27 /32
1 0.21 31 /32
1 x 1 1/2 0.54 29 /32
1 x 1 1/4 0.38 11 /2 1 x 3/4 0.18 29 /32
1 x 1/2 0.18 31 /32
1 1/4 0.35 15 /16
1 1/4 x 1 1/2 0.51 119 /32
1 1/4 x 1 0.27 15 /32
1 1/2 0.44 31 /32
1 1/2 x 2 0.81 11 /8
1 1/2 x 1 1/4 0.38 13 /16
1 1/2 x 1 0.37 13 /32
2 0.81 13 /32
2 x 1 1/2 0.64 11 /8
2 1/2 1.48 121 /32
3 1.69 –
Consult price sheet for Made to Order items andfor minimum order quantities.
704Adapter C x M – Cast APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
3/4 x 1 1/2 0.60 117 /32
3/4 x 1 1/4 0.38 17 /32
3/4 x 3/8 0.19 13 /16
1 x 2 1.15 –
1 x 1 1/2 0.6429
/32
1 1/4 x 2 0.88 19 /32
1 1/4 x 3/4 0.30 31 /32
1 1/2 x 2 0.77 11 /8
2 x 2 1/2 1.57 115 /32
2 x 1 1/2 0.71 11 /8
2 x 1 1/4 1.08 –
2 1/2 1.48 121 /32
2 1/2 x 2 1.83 111 /16
3 1.96 11 /2
4 3.66 111 /16
5 8.60 25 /8
6 10.73 2
704-FFlush Adapter C x M – Cast APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
1/2 0.03 9 /16
3/4 0.03 19 /32
704-HHose Adapter C x Hose – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
1/2 0.09 9 /32
NOTE: Fits 1 /2," 5 /8" and 3 /4" Garden Hose.
604-2Fitting Adapter Ftg x M – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
1/8 0.02 11 /8
3/8 0.04 11 /4
1/2 0.09 115 /32
1/2 x 3/4 0.16 113 /16
1/2 x 3/8 0.04 111 /32
3/4 0.17 115 /16
1 0.25 21 /4
704-2
Fitting Adapter Ftg x M – Cast APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
3/4 x 1 0.27 131 /32
3/4 x 1/2 0.12 123 /32
1 x 3/4 0.24 115 /16
1 1/4 0.43 227 /32
1 1/2 0.54 213 /32
2 0.89 23 /4
2 1/2 1.55 33 /8
3 2.21 323 /32
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
73/294
A H E A D O F T H E F L O W® www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com8
Revision 5/1/08
750Bulkhead Fitting C x C – Cast APPROX. DIM. A DIM. B NOM. SIZE NET WT./LBS. INCHES INCHES
1/2 0.48 11 /4 1
3/4 0.77 19 /32 11 /4
1 1.30 11 /2 15 /8
1 1/2 2.87 11 /2 23 /8
2 3.82 21 /32 25 /8
750-3Bulkhead Fitting C x F – Cast APPROX. DIM. A DIM. B NOM. SIZE NET WT./LBS. INCHES INCHES
1/2 0.48 115 /16 1
3/4 0.79 21 /16 11 /4
1 1.43 215 /32 15 /8
750-4Bulkhead Fitting C x M – Cast APPROX. DIM. A DIM. B NOM. SIZE NET WT./LBS. INCHES INCHES
1/2 0.40 131 /32 1
3/4 0.79 25 /32 11 /4
704-2-HHose Adapter Ftg x Hose – Cast APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
3/4 F x 3/4 H 0.16 15 /8
NOTE: Fits 1 /2," 5 /8" and 3 /4" Garden Hose.
619Air Chamber Ftg. – Wrot APPROX. DIM. A DIM. L NOM. SIZE NET WT./LBS. INCHES INCHES
1/2 x 6 0.21 1 6
1/2 x 12 0.41 1 12
1/2 x 14 0.78 11 /8 14
3/4 x 12 0.40 1 12
620-LAir Chamber or Stub-OutFtg – Wrot
As Air Chamber, just solder one joint. When usedas Stub-Out, simply pressure test system then cutoff stub-out (save piece for future use) and installvalve or fixture.
APPROX. DIM. L NOM. SIZE NET WT./LBS. INCHES
1/2 x 6 0.14 6
1/2 x 8 0.19 8
1/2 x 10 0.24 10
1/2 x 12 0.28 12
3/4 x 12 0.46 12
AIR CHAMBERS
BULKHEADFITTINGS
Consult price sheet for Made to Order items andfor minimum order quantities.
618Flush Bushing Ftg x C – Wrot APPROX. DIM. C NOM. SIZE NET WT./LBS. INCHES
1/4 x 1/8 0.01 1 /16
3/8 x 1/4 0.01 1 /16
1/2 x 3/8 0.02 3 /32
1/2 x 1/4 0.04 1 /4
5/8 x 1/2 0.03 1 /16
3/4 x 5/8 0.22 3 /16
3/4 x 1/2 0.08 3 /32
3/4 x 3/8 0.11 7 /16
1 x 3/4 0.12 1 /8
1 x 1/2 0.22 15 /32
1 1/4 x 1 0.17 3 /32
1 1/2 x 1 1/4 0.22 5 /32
2 x 1 1/2 0.66 1 /8
618-3Flush Bushing Ftg x F – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
1/2 x 1/8 0.03 9 /16
1/2 x 1/4 0.03 9 /16
718-3Flush Bushing Ftg x F – Cast APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
3/4 x 3/8 0.06 131 /32
1 x 1/2 0.13 31 /32
1 1/4 x 3/4 0.18 11 /32
1 1/2 x 1 0.25 15 /32
BUSHINGSADAPTERS continued
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
74/294
A H E A D O F T H E F L O W® www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
9
Revision 5/1/08
Consult price sheet for Made to Order items andfor minimum order quantities.
CAPS
617Tube Cap C – Wrot APPROX. DIM. N NOM. SIZE NET WT./LBS. INCHES
1/8 0.01 1 /32
1/4 0.01 3 /32
3/8 0.01 3 /32
1/2 0.02 3 /32
5/8 0.03 1 /8
3/4 0.04 1 /8
1 0.07 5 /32
1 1/4 0.10 3 /32
1 1/2 0.16 1 /8
2 0.27 5 /32
2 1/2 0.50 7 /32
3 0.78 7 /32
4 1.66 1 /4
717Tube Cap C – Cast APPROX. DIM. N NOM. SIZE NET WT./LBS. INCHES
5 5.48 7 /16
6 9.07 17 /32
717-DDrain Cap – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
1/2 0.06 21 /32
COUPLINGS
600Reducing Coupling C x C – Wrot APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
1/8 x 3/16 O.D. 0.01 5 /32
5/16 O.D. x 1/8 0.01 3 /16
1/4 x 5/16 O.D. 0.01 3 /16
1/4 x 1/8 0.01 3 /16
3/8 x 1/4 0.02 3 /16
3/8 x 5/16 O.D. 0.01 1 /4
3/8 x 1/8 0.01 1 /4
1/2 x 3/8 0.03 3 /16
1/2 x 1/4 0.02 1 /4
1/2 x 1/8 0.03 11 /32
5/8 x 1/2 0.05 3 /16
5/8 x 3/8 0.04 11 /32
5/8 x 1/4 0.03 13 /32
3/4 x 5/8 0.07 3 /16
3/4 x 1/2 0.06 9 /32
3/4 x 3/8 0.06 3 /8
3/4 x 1/4 0.05 11 /32
1 x 3/4 0.11 11 /32
1 x 5/8 0.09 3 /8
1 x 1/2 0.10 11 /32
1 x 3/8 0.10 13 /32
1 1/4 x 1 0.16 5 /16
1 1/4 x 3/4 0.18 17 /32
1 1/4 x 5/8 0.18 5 /8
1 1/4 x 1/2 0.14 7 /16
1 1/2 x 1 1/4 0.23 5 /16
1 1/2 x 1 0.22 9 /16
1 1/2 x 3/4 0.20 3 /8
1 1/2 x 1/2 0.19 1 /2
2 x 1 1/2 0.41 9 /16
2 x 1 1/4 0.35 11 /16
2 x 1 0.37 7 /16
2 x 3/4 0.34
17
/32 2 x 1/2 0.35 23 /32
2 1/2 x 2 0.59 9 /16
2 1/2 x 1 1/2 0.65 11 /16
2 1/2 x 1 1/4 0.65 13 /16
2 1/2 x 1 0.73 29 /32
Continues…
APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
3 x 2 1/2 0.98 1 /2
3 x 2 1.06 15 /16
3 x 1 1/2 0.92 11 /32
3 1/2 x 3 1.52 1 /2
4 x 3 1/2 2.12 19 /32
4 x 3 1.92 27 /32
4 x 2 1/2 1.77 1
4 x 2 1.92 11 /4
5 x 4 3.50 331 /32
5 x 3 3.18 115 /32
5 x 2 1/2 3.50 13 /16
5 x 2 3.09 21 /32
6 x 5 5.70 11 /8
6 x 4 5.24 11 /2
6 x 3 5.04 2
6 x 2 1/2 5.13 21 /4
6 x 2 4.89 21 /2
8 x 6 13.06 119 /32
8 x 4 12.22 219 /32
8 x 3 11.79 33 /32
8 x 2 1/2 12.64 33 /8
600-RSCoupling with Rolled Tube StopC x C – Wrot APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
1/8 O.D. 0.01 1 /16
3/16 O.D. 0.01 3 /32
1/8 0.01 1 /16
5/16 O.D. 0.01 3 /32
1/4 0.01 1 /16
3/8 0.01 3 /32
1/2 0.03 3 /32
5/8 0.04 3 /32
3/4 0.06 3 /32
7/8 0.09 3 /32
1 0.11 3 /32
1 1/4 0.16 1 /8
1 1/2 0.23 1 /8
2 0.41 1 /8
2 1/2 0.65 1 /8
3 0.93 1 /8
3 1/2 1.45 5 /32
4 1.93 7 /32
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
75/294
A H E A D O F T H E F L O W® www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com10
Revision 5/1/08
601Coupling without StopC x C – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
1/4 0.01 11 /16
3/8 0.01 27 /32
1/2 0.03 1
5/8 0.04 111
/32 3/4 0.06 119 /32
1 0.11 129 /32
1 1/4 0.16 21 /16
1 1/2 0.23 25 /16
2 0.41 213 /16
2 1/2 0.64 215 /16
3 0.86 35 /16
3 1/2 1.40 313 /16
4 1.84 45 /16
5 3.50 55 /16
6 5.60 63 /16
8 13.68 83 /32
701Reducing Coupling C x C – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
3 x 1 1/4 1.35 23 /32
3 x 1 1.64 27 /32
COUPLINGS continued
Consult price sheet for Made to Order items andfor minimum order quantities.
600-DSCoupling with Dimpled Tube StopC x C – Wrot APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
3/16 O.D. 0.01 3 /32
1/8 0.01 1 /16
5/16 O.D. 0.01 3 /32
1/4 0.011
/16 3/8 0.01 3 /32
1/2 0.03 3 /32
5/8 0.04 3 /32
3/4 0.06 3 /32
7/8 0.09 3 /32
1 0.11 3 /32
1 1/4 0.16 1 /8
1 1/2 0.23 1 /8
2 0.41 1 /8
2 1/2 0.65 1 /8
3 0.93 1 /8
3 1/2 1.45 5 /32
4 1.93 7 /32
5 3.53 7 /32
6 5.63 7 /32
8 14.12 15 /32
701-DDrain Coupling C x C – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
1/2 0.08 1 /4
3/4 0.14 1 /4
1 0.22 1 /4
702Eccentric Coupling C x C – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
3/4 x 1/2 0.10 17 /32
1 x 3/4 0.18 1 /4
1 1/4 x 1 0.25 1 /4
1 1/4 x 3/4 0.24 9 /32
724-5-A
Hy-Set Hanger CouplingC – Cast APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES
1/2 0.05 15 /8 23 /32
3/4 0.09 15 /8 27 /32
1 0.13 15 /8 1
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
76/294
A H E A D O F T H E F L O W® www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
11
Revision 5/1/08
736Cross-Over CouplingC x C – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
1/2 0.27 17 /16
3/4 0.60 129 /32
COUPLINGS continued
735Cross C x C x C x C – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
3/8 0.09 3 /8
1/2 0.15 7 /16
3/4 0.30 9 /16
1 0.54 23 /32
1 1/4 0.78 7 /8
1 1/2 1.05 1
2 2.00 11 /4
2 1/2 2.96 11 /2
CROSSES ELBOWS
60645° Elbow C x C – Wrot APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES
1/8 0.01 1 /4 1 /4
1/4 0.02 9 /32 9 /32
3/8 0.03 3 /16 3 /16
1/2 0.04 9 /32 9 /32
5/8 0.09
15
/32
15
/32
3/4 0.10 11 /32 11 /32
7/8 0.20 11 /16 11 /16
1 0.16 3 /8 3 /8
1 1/4 0.25 17 /32 17 /32
1 1/2 0.35 19 /32 19 /32
2 0.65 25 /32 25 /32
2 1/2 1.07 29 /32 29 /32
3 1.58 11 /8 11 /8
4 3.35 17 /16 17 /16
5 11.05 19 /16 19 /16
6 16.95 2 2
8 23.00 29 /32 29 /32
606-245° Fitting Elbow Ftg x C – Wrot APPROX. DIM. B DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES
1/4 0.029
/16 1
/4 1/2 0.04 3 /4 7 /32
5/8 0.08 11 /8 13 /32
3/4 0.10 11 /16 5 /16
1 0.16 17 /32 15 /32
1 1/4 0.25 119 /32 17 /32
1 1/2 0.35 125 /32 19 /32
2 0.65 23 /16 25 /32
2 1/2 1.07 23 /16 29 /32
3 1.55 219 /32 15 /32
Consult price sheet for Made to Order items andfor minimum order quantities.
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
77/294
A H E A D O F T H E F L O W® www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com12
Revision 5/1/08
ELBOWS continued
Consult price sheet for Made to Order items andfor minimum order quantities.
706-245° Fitting Elbow Ftg x C – Cast APPROX. DIM. B DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES
4 4.31 311 /32 15 /16
60790° Elbow – Close RoughC x C – Wrot APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES
1/8 0.01 13 /32 13 /32
1/4 0.02 9 /32 9 /32
3/8 0.03 1 /2 1 /2
1/2 0.04 3 /8 3 /8
1/2 x 3/8 0.04 9 /16 21 /32
3/4 0.10 17 /32 17 /32
3/4 x 5/8 0.12 29 /32 7 /8
3/4 x 1/2 0.10 17 /32 3 /4
1 0.21 23 /32 23 /32
1 x 3/4 0.16 23 /32 5 /8
1 1/4 0.31 11 /32 11 /32
1 1/4 x 1 0.31 15 /8 115 /32
1 1/2 0.46 17 /32 17 /32
1 1/2 x 1 1/4 0.35 15 /32 13 /32
2 0.84 11 /2 11 /2
2 x 1 1/2 0.58 17 /16 11 /4
2 1/2 1.41 127 /32 127 /32
3 2.07 23 /32 23 /32
3 1/2 2.94 23 /8 23 /8
4 4.23 225 /32 225 /32
5 7.74 27 /8 27 /8
6 10.95 37 /16 37 /16
8 29.50 423 /32 423 /32
70790° Elbow – Close RoughC x C – Cast APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES
1 1/4 x 1 0.42 15 /8 115 /32
1 1/4 x 3/4 0.34 9 /16 13 /16
1 1/4 x 1/2 0.28 15 /32 27 /32
1 1/2 x 1 0.5411
/16 1 1 1/2 x 3/4 0.42 19 /32 31 /32
1 1/2 x 1/2 0.40 5 /8 29 /32
2 x 1 1/4 0.86 7 /8 11 /4
2 x 1 0.78 3 /4 11 /4
2 x 3/4 0.69 5 /8 11 /4
2 1/2 x 2 2.16 13 /16 19 /32
3 x 2 1/2 2.26 111 /16 11 /2
3 x 2 2.68 13 /8 19 /16
4 x 3 5.18 129 /32 215 /32
607-I90° Elbow –Intermediate Radius C x C– Wrot APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES
1/2 0.06 19 /32 19 /32
5/8 0.09 7 /8 7 /8
3/4 0.14 13 /16 3 /16
1 0.24 11 /16 11 /16
607-LT90° Elbow – Long RadiusC x C – Wrot APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES
3/16 O.D. 0.01 13 /32 13 /32
1/8 0.01 13 /32 13 /32
5/16 O.D. 0.02 9 /16 9 /16
1/4 0.0217
/32 17
/32 1/4 x 1/8 0.01 19 /32 1 /2
3/8 0.04 23 /32 23 /32
1/2 0.08 7 /8 7 /8
1/2 x 3/8 0.06 13 /16 13 /16
1/2 x 1/4 0.03 25 /32 21 /32
5/8 0.10 13 /32 13 /32
5/8 x 1/2 0.09 11 /16 11 /16
3/4 0.16 11 /8 11 /8
3/4 x 5/8 0.13 11 /4 13 /32
3/4 x 1/2 0.10 11 /8 11 /16
7/8 0.28 119 /32 119 /32
1 0.28 17 /16 17 /16
1 x 3/4 0.20 11 /4 11 /8
1 x 5/8 0.15 113 /32 13 /32
1 1/4 0.42 17 /8 17 /8
1 1/4 x 1 0.33 125 /32 11 /2
1 1/2 0.66 21 /4 21 /4
2 1.23 215 /16 215 /16
2 1/2 1.96 311 /16 311 /16
3 2.93 41 /32 41 /32
4 5.95 51 /4 51 /4
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
78/294
A H E A D O F T H E F L O W® www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
13
Revision 5/1/08
Consult price sheet for Made to Order items andfor minimum order quantities.
607-290° Fitting Elbow – Close RoughFtg x C – Wrot APPROX. DIM. B DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES
1/4 0.02 3 /4 3 /8
3/8 0.03 15 /16 1 /2
1/2 0.04 31 /32 3 /8
5/8 0.07 17
/32 17
/32 3/4 0.10 111 /32 17 /32
1 0.20 13 /4 27 /32
1 1/4 0.33 21 /8 11 /32
1 1/2 0.46 213 /32 17 /32
2 0.84 227 /32 11 /2
2 1/2 1.39 315 /32 129 /32
3 2.10 313 /16 23 /32
4 4.00 43 /4 225 /32
607-2-I90° Fitting Elbow –Intermediate RadiusFtg x C – Wrot APPROX. DIM. B DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES
1/2 0.06 15 /32 19 /32
5/8 0.09 19
/16 7
/8 3/4 0.14 15 /8 13 /16
1 0.24 21 /32 11 /16
607-2-LT90° Fitting Elbow – Long RadiusFtg x C – Wrot APPROX. DIM. B DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES
1/8 0.01 13 /32 1 /2
1/4 0.02 11 /8 3 /4
3/8 0.05 11 /8 7 /8
1/2 0.08 19
/16 13
/32 1/2 x 3/8 0.06 15 /16 13 /16
1/2 x 1/4 0.03 11 /4 5 /8
5/8 0.10 125 /32 13 /32
3/4 0.16 115 /16 11 /8
1 0.31 21 /2 121 /32
1 1/4 0.43 229 /32 17 /8
1 1/2 0.66 213 /32 21 /4
1 1/2 x 1 1/4 0.50 33 /8 23 /32
2 1.27 411 /32 231 /32
2 1/2 2.16 57 /32 311 /16
3 3.10 53 /4 41 /32
607-2-290° Fitting Elbow – Close RoughFtg x Ftg – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
1/2 0.04 11 /16
3/4 0.12 115 /32
1 0.20 123 /32
1 1/4 0.33 21 /8
1 1/2 0.46 213 /32
2 0.82 227 /32
3 2.12 37 /8
ELBOWS continued
607-2-2-LT90° Fitting Elbow – Long RadiusFtg x Ftg – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
1/4 0.02 27 /32
3/8 0.04 11 /8
1/2 0.08 119 /32
5/8 0.10 111 /16
3/4 0.16 115 /16
1 0.31 21 /2
1 1/4 0.43 229 /32
1 1/2 0.65 37 /16
2 1.25 411 /32
707-2-490° Fitting ElbowFtg x M – Cast APPROX. DIM. B DIM. E NOM. SIZE NET WT./LBS. INCHES INCHES
1/2 0.12 7 /8 25 /32
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
79/294
A H E A D O F T H E F L O W® www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com14
Revision 5/1/08
ELBOWS continued
Consult price sheet for Made to Order items andfor minimum order quantities.
707-390° Elbow C x F – Cast APPROX. DIM. C DIM. E NOM. SIZE NET WT./LBS. INCHES INCHES
1/4 0.06 13 /32 9 /16
3/8 0.09 7 /16 11 /16
3/8 x 1/2 0.13 9 /16 13 /16
1/2 0.12 7 /16 13 /16
1/2 x 3/4 0.18
11
/16
15
/16
1/2 x 3/8 0.09 1 /2 13 /16
1/2 x 1/4 0.10 3 /8 23 /32
3/4 0.18 21 /32 15 /16
3/4 x 1 0.35 13 /16 11 /8
3/4 x 1/2 0.20 9 /16 15 /16
1 0.43 25 /32 11 /4
1 x 3/4 0.35 11 /16 13 /16
1 x 1/2 0.26 9 /16 11 /8
1 1/4 0.67 1 11 /2
1 1/4 x 3/4 0.47 9 /16 111 /16
1 1/2 0.89 11 /8 15 /8
2 1.46 13 /8 115 /16
707-3-590° Drop Elbow C x F – Cast NOM. APPROX. DIM. A DIM. C DIM. E SIZE NET WT./LBS. INCHES INCHES INCHES
3/8 0.12 11 /32 7 /16 11 /16
3/8 x 1/2 0.18 11 /32 9 /16 13 /16
1/2 0.15 13 /32 9 /16 7 /8
1/2 x 3/8 0.17 3 /8 1 /2 13 /16
3/4 0.28 17 /32 21 /32 15 /16
3/4 x 1/2 0.24 17 /32 9 /16 15 /16
1 0.49 5 /8 25 /32 11 /4
707-3-5-A90° Hy-Set Elbow C x F – Cast APPROX. DIM. C DIM. E NOM. SIZE NET WT./LBS. INCHES INCHES
1/2 0.21 9 /16 7 /8
707-3-690° Union Elbow C x F – Cast APPROX. DIM. A DIM. E NOM. SIZE NET WT./LBS. INCHES INCHES
1/2 0.31 11 /8 7 /8
3/4 0.49 17 /16 1
1 0.79 17 /8 11 /4
707-490° Elbow C x M – Cast APPROX. DIM. C DIM. E NOM. SIZE NET WT./LBS. INCHES INCHES
3/8 0.08 5 /16 7 /8 1/2 0.12 7 /16 15 /32
1/2 x 3/4 0.18 9 /16 15 /32
1/2 x 3/8 0.10 5 /16 15 /16
3/4 0.21 9 /16 111 /32
3/4 x 1 0.33 21 /32 113 /32
3/4 x 1/2 0.18 7 /16 17 /32
1 0.43 23 /32 15 /8
1 1/4 0.58 7 /8 111 /16
1 1/2 0.81 1 131 /32
2 1.38 11 /4 29 /32
707-4-690° Union Elbow C x M – Cast APPROX. DIM. A DIM. E NOM. SIZE NET WT./LBS. INCHES INCHES
3/8 0.21 13 /32 13 /16
1/2 0.30 11 /32 11 /2
3/4 0.49 15 /16 113 /16
1 0.72 123 /32 15 /8
1 1/4 1.16 1
3
/4
1
27
/32
707-590° Drop Elbow C x C – Cast APPROX. DIM. A DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES
1/2 0.13 13 /32 7 /16
3/4 0.24 17 /32 9 /16
707-5-A90° Hy-Set Elbow C x C – Cast NOM. APPROX. DIM. A DIM. C DIM. D SIZE NET WT./LBS. INCHES INCHES INCHES
1/2 0.13 31 /32 7 /16 15 /32
3/4 0.21 15 /16 9 /16 9 /16
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
80/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
81/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
82/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
83/294
A H E A D O F T H E F L O W® www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com18
Revision 5/1/08
APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G
1 x 1/2 x 1 0.29 11 /16 1 21 /32
1 x 1/2 x 3/4 0.27 9 /16 13 /16 3 /4
1 x 1/2 x 1/2 0.22 15 /32 25 /32 23 /32
1 1/4 0.43 13 /16 3 /16 13 /16
1 1/4 x 1 1/4 x 2 1.13 130
/32 130
/32 13
/32 1 1/4 x 1 1/4 x 1 1/2 0.60 13 /16 13 /16 29 /32
1 1/4 x 1 1/4 x 1 0.45 25 /32 25 /32 29 /32
1 1/4 x 1 1/4 x 3/4 0.37 21 /32 21 /32 3 /4
1 1/4 x 1 1/4 x 1/2 0.30 1 /2 1 /2 25 /32
1 1/4 x 1 1/4 x 3/8 0.34 23 /32 23 /32 29 /32
1 1/4 x 1 x 1 1/4 0.43 13 /16 11 /32 13 /16
1 1/4 x 1 x 1 0.47 25 /32 7 /8 29 /32
1 1/4 x 1 x 3/4 0.35 21 /32 25 /32 7 /8
1 1/4 x 1 x 1/2 0.30 1 /2 5 /8 29 /32
1 1/4 x 3/4 x 1 1/4 0.42 13 /16 11 /8 13 /16
1 1/4 x 3/4 x 1 0.45 25 /32 11 /32 29 /32
1 1/4 x 3/4 x 3/4 0.37 21 /32 15 /16 7 /8
1 1/4 x 3/4 x 1/2 0.30 1 /2 3 /4 29 /32
1 1/4 x 1/2 x 1 1/4 0.41 13 /16 17 /32 13 /16
1 1/2 0.61 31 /32 31 /32 29 /32
1 1/2 x 1 1/2 x 2 1.11 125 /32 125 /32 13 /32
1 1/2 x 1 1/2 x 1 1/4 0.62 29 /32 29 /32 11 /16
1 1/2 x 1 1/2 x 1 0.55 11 /16 11 /16 7 /8
1 1/2 x 1 1/2 x 3/4 0.45 11 /16 11 /16 11 /32
1 1/2 x 1 1/2 x 1/2 0.40 1 /2 1 /2 11 /32
1 1/2 x 1 1/4 x 1 1/2 0.62 11 /32 13 /16 29 /32
1 1/2 x 1 1/4 x 1 1/4 0.62 31 /32 13 /32 31 /32
1 1/2 x 1 1/4 x 1 0.51 25 /32 1 11 /32
1 1/2 x 1 1/4 x 3/4 0.49 11 /16 13 /16 11 /32
1 1/2 x 1 1/4 x 1/2 0.41 1 /2 25 /32 11 /32
1 1/2 x 1 x 1 1/2 0.59 11 /32 111 /32 29 /32
1 1/2 x 1 x 1 1/4 0.63 29 /32 11 /8 11 /16
1 1/2 x 1 x 1 0.54 25 /32 11 /16 11 /32
1 1/2 x 1 x 3/4 0.44 11 /16 31 /32 15 /16
1 1/2 x 1 x 1/2 0.39 1 /2 25 /32 11 /32
1 1/2 x 3/4 x 1 1/2 0.62 11 /32 17 /16 11 /16
1 1/2 x 3/4 x 1 1/4 0.58 29 /32 111 /32 11 /16
1 1/2 x 3/4 x 1 0.54 25 /32 11 /4 11 /32
1 1/2 x 3/4 x 3/4 0.47 11 /16 13 /32 29 /32
1 1/2 x 3/4 x 1/2 0.39 1 /2 29 /32 31 /32
1 1/2 x 1/2 x 1 1/2 0.62 11 /32 113 /32 31 /32
Continues…
APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G
2 1.30 19 /32 19 /32 11 /32
2 x 2 x 2 1/2 2.34 2 2 121 /32
2 x 2 x 1 1/2 1.17 11 /4 11 /4 123 /32
2 x 2 x 1 1/4 1.12 9 /32 9 /32 17 /8
2 x 2 x 1 0.90 27 /32 27 /32 11 /4
2 x 2 x 3/4 0.88 19 /32 19 /32 11 /4
2 x 2 x 1/2 1.17 1
1
/4
1
1
/4
2
1
/4
2 x 1 1/2 x 2 1.16 19 /32 17 /8 111 /32
2 x 1 1/2 x 1 1/2 1.15 11 /4 13 /4 123 /32
2 x 1 1/2 x 1 1/4 1.15 7 /32 13 /4 111 /32
2 x 1 1/2 x 3/4 0.83 21 /32 15 /16 17 /32
2 x 1 1/2 x 1/2 1.12 11 /4 125 /32 21 /4
2 x 1 1/4 x 2 1.58 19 /32 115 /32 19 /32
2 x 1 1/4 x 1 1/2 1.16 11 /4 131 /32 123 /32
2 x 1 1/4 x 1 1/4 1.19 15 /16 111 /32 111 /32
2 x 1 1/4 x 1 0.90 27 /32 19 /32 111 /32
2 x 1 1/4 x 3/4 0.85 21 /32 1 18 /27
2 x 1 x 2 1.11 11 /8 125 /32 11 /4
2 x 1 x 1 0.89 27 /32 19 /32 111 /32
2 x 3/4 x 2 1.15 19
/32 23
/16 11
/4 2 x 1/2 x 2 1.15 19 /32 23 /8 11 /4
2 1/2 2.40 15 /8 15 /8 15 /8
2 1/2 x 2 1/2 x 2 1.97 15 /16 15 /16 121 /32
2 1/2 x 2 1/2 x 1 1/2 1.53 13 /32 13 /32 121 /32
2 1/2 x 2 1/2 x 1 1/4 1.72 13 /32 13 /32 127 /32
2 1/2 x 2 1/2 x 1 1.34 25 /32 25 /32 111 /16
2 1/2 x 2 1/2 x 3/4 1.34 25 /32 25 /32 113 /16
2 1/2 x 2 1/2 x 1/2 1.34 25 /32 25 /32 21 /8
2 1/2 x 2 x 2 1/2 1.99 121 /32 23 /32 121 /32
2 1/2 x 2 x 2 1.95 111 /32 15 /8 123 /32
2 1/2 x 2 x 1 1/2 1.57 13 /32 213 /32 121 /32
2 1/2 x 2 x 1 1/4 1.57 13 /32 119 /32 127 /32
2 1/2 x 2 x 1 1.40 25 /32 19 /32 13 /4
2 1/2 x 2 x 3/4 1.35 25 /32 19 /32 127 /32
2 1/2 x 1 1/2 x 1 1/2 1.76 13 /32 113 /32 13 /8
2 1/2 x 1 1/4 x 2 1/2 2.40 121 /32 27 /16 121 /32
2 1/2 x 1 x 2 1/2 2.04 121 /32 223 /32 121 /32
2 1/2 x 3/4 x 2 1/2 2.00 121 /32 211 /16 121 /32
Continues…
APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G
3 3.15 17 /8 17 /8 21 /32
3 x 3 x 2 1/2 3.55 129 /32 129 /32 23 /8
3 x 3 x 2 3.19 115 /32 115 /32 131 /32
3 x 3 x 1 1/2 3.08 115 /32 115 /32 29 /32
3 x 3 x 1 1/4 3.10 115 /32 115 /32 27 /16
3 x 3 x 1 2.12 27 /32 27 /32 131 /32
3 x 3 x 3/4 2.39 27 /32 27 /32 23 /16
3 x 3 x 1/2 1.82 27 /32 27 /32 23 /8
3 x 2 1/2 x 3 3.08 17 /8 23 /8 131 /32
3 x 2 1/2 x 2 1/2 3.12 129 /32 211 /32 25 /32
3 x 2 1/2 x 2 2.28 115 /32 127 /32 131 /32
3 x 2 x 3 3.62 129 /32 217 /32 115 /16
3 x 2 x 2 1/2 3.56 129 /32 29 /16 25 /16
3 x 2 x 2 3.22 115 /32 131 /32 131 /32
3 x 1 1/2 x 3 3.13 129 /32 225 /32 23 /32
3 x 1 1/4 x 3 3.63 129 /32 225 /32 115 /16
3 x 1 x 3 3.20 131 /32 219 /32 23 /16
3 x 3/4 x 3 3.55 131 /32 229 /32 23 /16
3 1/2 5.20 217 /32 217 /32 217 /32
4 8.12 213
/32 213
/32 217
/32 4 x 4 x 3 6.70 21 /32 21 /32 221 /32
4 x 4 x 2 1/2 6.65 21 /32 21 /32 35 /32
4 x 4 x 2 5.82 115 /32 115 /32 27 /16
4 x 4 x 1 1/2 3.94 111 /32 111 /32 217 /32
4 x 4 x 1 1/4 4.04 111 /32 111 /32 229 /32
4 x 4 x 1 3.72 1 1 29 /16
4 x 4 x 3/4 3.70 1 1 211 /16
4 x 3 x 4 7.05 225 /32 37 /32 217 /32
4 x 3 x 3 5.03 21 /32 215 /32 215 /32
4 x 3 x 2 1/2 5.04 21 /32 215 /32 229 /32
4 x 3 x 2 5.87 115 /32 131 /32 27 /16
4 x 2 1/2 x 4 7.19 225 /32 315 /32 227 /32
4 x 2 x 4 7.08 225 /32 319 /32 227 /32
Continued on next page.
NOTE: Tee sizes are read Run x Run x Outlet.
611Tee C x C x C – Wrot continued
TEES continued
Consult price sheet for Made to Order items andfor minimum order quantities.
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
84/294
A H E A D O F T H E F L O W® www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
19
Revision 5/1/08
611-HEHeat Exchanger TeeC x C x C – Wrot
Tube slips entirely through fitting on small endof run. Sizes same as listed under 611 where teehas one or more reductions on one end of run.
711Tee C x C x C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G
1 1/4 x 1/2 x 1 0.48 3 /4 3 /4 7 /8
1 1/4 x 1/2 x 1/2 0.50 9 /16 5 /8 1
1 1/2 x 1/2 x 1 1/4 0.70 7 /8 31 /32 1
2 x 2 x 3 3.11 121 /32 121 /32 15 /16
2 x 1 x 1 1/2 1.23 1 11 /4 11 /4
2 x 3/4 x 3/4 0.84 21 /32 7 /8 11 /4
2 1/2 x 2 1/2 x 3 2.98 13 /4 13 /4 117 /32
2 1/2 x 1 1/2 x 2 2.02 11 /4 115 /32 11 /2
2 1/2 x 1 1/2 x 1 1/2 1.76 13 /32 113 /32 13 /8 2 1/2 x 1/2 x 2 1/2 2.46 11 /2 27 /32 11 /2
3 x 3 x 4 6.96 211 /32 211 /32 123 /32
3 x 2 1/2 x 1 1/2 2.53 1 13 /32 13 /4
3 x 2 x 1 1/2 2.62 1 11 /4 13 /4
4 x 4 x 6 16.47 37 /32 37 /32 29 /32
4 x 2 x 2 4.64 11 /4 13 /4 21 /4
711-ASupply and Return TeeC x C x C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C J
1/2 0.17 13 /16 1
TEES continued
Consult price sheet for Made to Order items andfor minimum order quantities.
611Tee C x C x C – Wrot continued APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G
5 8.29 227 /32 227 /32 313 /32
5 x 5 x 4 7.09 27 /32 29 /32 33 /16
5 x 5 x 3 5.91 125 /32 125 /32 33 /16
5 x 5 x 2 1/2 5.90 15 /16 15 /16 33 /16
5 x 5 x 2 5.29 11 /16 11 /16 33 /16
5 x 5 x 1 1/2 4.87 11 /32 11 /32 33 /16
5 x 5 x 1 1/4 4.50 11 /16 11 /16 33 /16
5 x 5 x 1 4.20 9 /16 9 /16 33 /16
5 x 4 x 5 8.53 227 /32 429 /32 313 /32
5 x 4 x 4 8.17 21 /4 417 /32 33 /8
5 x 2 x 5 9.47 23 /4 51 /16 31 /2
6 13.50 39 /32 39 /32 41 /32
6 x 6 x 5 11.67 225 /32 225 /32 41 /32
6 x 6 x 4 10.17 29 /32 29 /32 311 /16
6 x 6 x 3 8.92 125 /32 125 /32 311 /16
6 x 6 x 2 1/2 8.11 117 /32 117 /32 33 /4
6 x 6 x 2 7.78 19 /32 19 /32 311 /16
6 x 6 x 1 1/2 6.86 1 1 311 /16
6 x 6 x 1 1/4 6.66 29 /32 29 /32 311 /16
6 x 6 x 1 7.19 9 /16 9 /16 311 /16
6 x 6 x 3/4 7.18 9 /16 9 /16 49 /16
6 x 6 x 1/2 7.17 9 /16 9 /16 411 /16
6 x 4 x 6 16.60 33 /16 51 /8 41 /8
6 x 4 x 1 1/2 9.62 15 /16 215 /16 33 /4
8 36.81 41 /16 41 /16 51 /32
8 x 8 x 6 27.86 31 /16 31 /16 51 /8
8 x 8 x 5 24.90 225 /32 225 /32 415 /16
8 x 8 x 4 22.26 21 /16 21 /16 43 /4
8 x 8 x 3 20.01 19 /16 19 /16 43 /4
8 x 8 x 2 1/2 19.02 15
/16 15
/16 43
/4 8 x 8 x 2 18.01 11 /16 11 /16 43 /4
NOTE: Tee sizes are read Run x Run x Outlet.
611-2Fitting Tee C x Ftg x C – Wrot APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. B C F
1/2 0.07 11 /32 3 /8 7 /16
3/4 0.15 115 /32 1 /2 17 /32
711-5Drop Tee C x C x C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. A C
1/2 0.16 3 /8 7 /16
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
85/294
A H E A D O F T H E F L O W® www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com20
Revision 5/1/08
712Tee C x C x F – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. E F G
3/8 0.11 11 /16 7 /16 7 /16
1/2 0.14 13 /16 7 /16 7 /16
3/4 0.33 1 21 /32 21 /32
1 0.54 11 /4 7 /8 7 /8
1 1/2 1.08 15 /8 11 /8 11 /8
2 1.74 17 /8 13 /8 13 /8
1/2 x 1/2 x 1/4 0.16 13 /16 1 /2 1 /2
1/2 x 1/2 x 3/8 0.15 13 /16 1 /2 1 /2
1/2 x 1/2 x 3/4 0.23 15 /16 11 /16 11 /16
3/4 x 3/4 x 3/8 0.23 7 /8 1 /2 1 /2
3/4 x 3/4 x 1/2 0.24 57 /64 17 /32 17 /32
1 1/4 x 1 1/4 x 1/2 0.49 11 /4 9 /16 9 /16
1 1/4 x 1 1/4 x 3/4 0.55 15 /16 11 /16 11 /16
1 1/4 x 1 1/4 x 1 0.66 17 /16 7 /8 7 /8
1 x 1 x 1/2 0.34 11 /8 9 /16 9 /16
1 x 1 x 3/4 0.42 13 /16 11 /16 11 /16
1 1/2 x 1 1/2 x 1/2 0.62 13 /8 9 /16 9 /16
1 1/2 x 1 1/2 x 3/4 0.70 17 /16 11 /16 11 /16
1 1/2 x 1 1/2 x 1 0.79 11 /2 13 /16 13 /16
2 x 2 x 1/2 0.97 15 /8 17 /32 17 /32
2 x 2 x 3/4 1.10 111 /16 11 /16 11 /16
2 x 2 x 1 1.23 13 /4 13 /16 13 /16
1/4 0.08 13 /16 9 /32 9 /32
1 1/4 0.76 17 /16 1 1
3/8 x 3/8 x 1/4 0.12 11 /16 7 /16 7 /16
3/4 x 1/2 x 3/4 0.28 1 21 /32 11 /16
3/4 x 3/4 x 1 0.40 11 /8 7 /8 7 /8
712-5Drop Tee C x C x F – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. A C E
1/2 0.25 3 /8 9 /16 7 /8
3/4 0.38 1 /2 21 /32 1
713Tee C x C x M – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. E F
1/2 0.15 13 /32 7 /16
3/4 0.29 19 /32 9 /16
714Tee C x F x C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C E S
1/2 0.18 7 /16 9 /16 7 /8
1/2 x 3/4 x 1/2 0.27 7 /16 9 /16 13 /16 3/4 0.31 9 /16 11 /16 1
3/4 x 1/2 x 3/4 0.26 9 /16 9 /16 15 /16
1 0.52 23 /32 13 /16 11 /4
1 x 3/4 x 1 0.43 23 /32 23 /32 13 /16
1 x 1/2 x 1 0.42 3 /4 3 /4 11 /8
1 1/4 0.70 7 /8 1 113 /32
1 1/4 x 3/4 x 1 1/4 0.62 7 /8 7 /8 17 /32
1 1/4 x 1/2 x 1 1/4 0.56 7 /8 7 /8 13 /16
1 1/2 1.00 1 11 /8 19 /16
1 1/2 x 3/4 x 1 1/2 0.88 1 1 113 /16
2 1.72 11 /4 13 /8 17 /8
2 x 3/4 x 2 1.57 11 /4 11 /4 2
2 x 1/2 x 2 1.58 11 /4 11 /4 2
TEES continued
Consult price sheet for Made to Order items andfor minimum order quantities.
TRAPS
698
Suction Line P-TrapC x C – WrotA major application of this fitting is on thesuction line of a refregeration compressor.The line is looped, by use of the Suction LineP-Trap, to the floor prior to being run verticallyupwards to prevent the drainage of oil back to thecompressor during shut down periods. AdditionalP-Traps are used for each 20' or riser pipe. thisprevents high velocity build-up as the oil or liquidbegins to return to the compressor during thisshut down period.
APPROX. DIMENSIONSNET WT. INCHES
NOM. SIZE LBS. C D J K
1/2 0.36 53 /8 3 3 6
5/8 0.45 53 /8 27 /8 3 6
3/4 0.58 53 /8 23 /4 3
6
1 0.92 51 /4 221 /32 3 6
1 1/4 1.16 53 /8 27 /8 33 /4 61 /8
1 1/2 2.32 75 /8 35 /8 5 9
2 3.93 8 35 /8 6 97 /16
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
86/294
-
8/20/2019 tran ac units2305 00-001 HVAC Submittals_1
87/294
A H E A D O F T H E F L O W® www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
39
Revision 5/1/08
TYPES OF JOINTS
Flared Joint — The principle of the flared joint was first developedfor copper tube plumbing in 1928 by NIBCO. The flared type joint iswholly a mechanical means of joining copper tubes. The tube nut isplaced over the end of the copper tube to be joined; the tube endthen is flared out at an approximate 45 degree angle by a flaring tool.The flared end is then drawn up by the tube nut so the inside surface
is tightly secured against the ball seat of the fitting. This joint canbe readily dismantled at any time and is, in effect, a type of unionconnection. Its use is generally restricted to soft (annealed) coppertubes since hard drawn tubes would be subject to splitting whenflared (if the ends were not previously annealed). The flared endsof NIBCO Flared Fittings are produced to the requirements of ASMEB16.26, “Cast Copper Alloy Fittings for Flared Copper Tube.”
Solder Joint — NIBCO pioneered the development ofthe solder joint and its application to the field of copper tubepiping. Today the solder joint is widely adopted, as evidenced bythe majority of cities and states that have written codes to includecopper tube and solder joints as desirable for general plumbing,water lines, vent, stack, waste and drain lines, as well as other uses
in industry. Testing has shown that often the solder joint has greaterstrength than the tubes being joined, depending upon the solderingalloy selected. While the method of preparing a solder joint is anexacting art to insure a full strength joint, it can be readily masteredby skilled tradesmen. It is for this reason — to insure the public ofthe protection afforded by properly prepared joints — that NIBCOproducts are marketed through the reputable sources of supply to thepiping trades. Important procedures for preparing a solder joint aregraphically illustrated in this catalog on page 48.
Brazed Joint — This type of joint has long been used wherever andwhenever critical situations have been encountered in copper piping.The joint itself is completed much in the same manner as the solderjoint; however, considerably more heat and several refinements of
technique require separate procedures that are described further inthis catalog on pages 49-50.
Threaded Ends — To adapt copper tube to equipment havingNational Standard Pipe Taper (NPT) threads or to add copper tube toexi