TR Series - GE Spark · GE Digital Energy Power Quality Introduction It is a fact that transient...

4
GE Digital Energy Power Quality Introduction It is a fact that transient voltage surges from both external and internal sources directly affect the per- formance and life expectancy of electronic equipment. From electronic lighting ballasts to computer servers, if there is a printed circuit board inside, it is susceptible to transient voltage surge damage. As microprocessors and components that make up this equipment grow smaller and faster with each new generation, their susceptibility to transient voltage surge damage becomes ever greater. The full-featured TR7000 series with its advanced monitoring, disconnect and enclosure options has been designed to handle the highest levels of surge activity found in the most demanding commercial and industrial facilities. These units are ideal for both new and retrot applications where performance cannot be compromised. I Available in ratings from 65kA - 300kA per mode, (130kA - 600kA per phase) the TR7000 series is the perfect surge suppression product for protecting critical sensitive electronic equipment throughout your facility. Recommended installation locations are service entrance and primary and secondary distribution. The TR7000 Series has been third-party tested to ANSI / IEEE C3 (10kA, 8x20μs) service entrance level transient surges including all components. The entire TR7000 line up has been engineered to the highest standards and is designed for rigorous duty and long life as evidenced in our outstanding minimum repetitive surge current capacity test results. Wallmount TR 7000 Series Surge Protective Device (SPD)

Transcript of TR Series - GE Spark · GE Digital Energy Power Quality Introduction It is a fact that transient...

GE Digital EnergyPower Quality

IntroductionIt is a fact that transient voltage surges from bothexternal and internal sources directly affect the per-formance and life expectancy of electronic equipment.From electronic lighting ballasts to computer servers,if there is a printed circuit board inside, it is susceptibleto transient voltage surge damage. As microprocessorsand components that make up this equipment growsmaller and faster with each new generation, theirsusceptibility to transient voltage surge damagebecomes ever greater.

The full-featured TR7000 series with its advancedmonitoring, disconnect and enclosure options has beendesigned to handle the highest levels of surge activityfound in the most demanding commercial and industrialfacilities. These units are ideal for both new and retrofitapplications where performance cannot be compromised.

IAvailable in ratings from 65kA - 300kA per mode, (130kA -600kA per phase) the TR7000 series is the perfect surgesuppression product for protecting critical sensitiveelectronic equipment throughout your facility.

Recommended installation locations are service entranceand primary and secondary distribution. The TR7000Series has been third-party tested to ANSI/IEEE C3 (10kA,8x20μs) service entrance level transient surges includingall components. The entire TR7000 line up has beenengineered to the highest standards and is designedfor rigorous duty and long life as evidenced in our outstanding minimum repetitive surge current capacity test results.

Wallmount

TR7000 Series Surge Protective Device (SPD)

Features and Benefits> The TR7000 provides maximum surge protection with

outstanding clamping characteristics for ultra high,high, medium and low exposure locations with theuse of industrial-grade MOV architecture.

> Third-party tested per IEEE C62.62 and NEMA LS-1for the rated 8x20μs surge current, per mode withfusing included.

> Fast rise-times, high frequency transients andelectrical line noise are reduced with standardEMI / RFI filtering technology.

> Maximum installation flexibility is achieved in theTR7000 through its high surge suppression kA tosmall footprint ratio.

> 10 modes of protection (L-N, L-G, N-G, L-L)

> Green phase status LEDs with Red alarm LED

> NO/NC Form C Dry Contacts for remote monitoring

> Industrial sized MOV technology

> Thermal fuse technology combined with 200kAICsurge rated fuses

> Audible alarm with push-to-test switch, enable/disable function

> Surge counter

> Optional 200kA surge rated disconnect

> NEMA 1, 12, 4 and 4X enclosures available

> Surface and flushmount-style enclosures

> 5 year limited warranty (standard),10 year limited warranty (optional)

DEA-365 • Page 2

Technical Specifications

Nominal Discharge Current (In)

20kA

Short Circuit Current Rating (SCCR)

200kA (60A breaker required)

Operating Frequency

50/60 Hz

Connection

6 to 2/0 AWG Lugs, Parallel Connected

Operating Temperature-40° F to 149° F (-40° C to +65° C)

Operating Humidity

0% to 95% Non-Condensing

Weight

WMN1D 55 lbs. (25 kg)WMN12S, 12F, 4S, 4D 37 lbs. (17 kg)WMN4X 40 lbs. (18 kg)

Standards> UL 1449 3rd Edition, Type 2 > UL 1283, EMI/RFI noise filter > UL 96A, Lightning Protection System > cUL, CSA C22.2> ANSI/IEEE C62.41 - ANSI/IEEE C62.45> IEEE C62.62> NEMA LS-1 - 1992 (R2000)> MIL-STD-220B> ANSI/NFPA 70 (Article 285)

Applications> Service Entrance

> Distribution Equipment

> Branch Panel

> New Construction and Retrofits

> System Expansions

Minimum Repetitive Surge Current Capacity (Per ANSI/IEEE C62.62)

The TR7000 Series is capable of surviving the followingimpulses, at one-minute intervals, without failure andwith less than 10% change in protective characteristics.

> 20,000 Category C3 impulses 20kV/10kA, 8x20μs for 120-300kA rated devices

> 5,000 Category C3 impulses 20kV/10kA, 8x20μs for 65-100kA rated devices

> 5,000 500V/2kA, 10x1000μs long wave impulses for all TR7000 devices

Page 3 • DEA-365

240D 240 Delta 3 Ph, 3 W

240H 120/240 Delta HL 3 Ph, 4 W + G

240Y 240Y/415 3 Ph, 4 W + G

277Y 277Y/480 3 Ph, 4 W + G

347Y 347Y/600 3 Ph, 4 W + G

480D 480 Delta 3 Ph, 3 W

Also available in 600V Delta configurations. For details, please contactGE Power Quality Customer Service at 800 637 1738.

Phase Rating = (L-N + L-G)

* Note: 150V (L-N/G) Phase A & C270V (L-N-G) Phase B

EnclosureDescription Suffix NEMA

Painted Steel 1

12S Painted Steel 12

Painted Steel 12

Mounting

Surface

Surface

Flush

Disconnect

Yes

No

No12F

Fiberglass 4X Surface Yes4D

Painted Steel 4 Surface No4S

Stainless Steel 4X Surface No4X

1D

NominalVoltage

(Volts RMS)

System Voltage

Configuration

MCOV(50/60 Hz)

Max.Continuous Operating

Voltage

120S 120/240 1 Ph, 3 W + G 150V

120Y 120Y/208 3 Ph, 4 W + G 150V

220Y/380 3 Ph, 4 W + G 320V

270V

320V

320V

420V

550V

R 7

220Y

Maximum Surge Current Capacity

Per Mode Per Phase

65kA 130kA

80kA 160kA

100kA 200kA

125kA 250kA

150kA 300kA

065

080

100

125

150

200kA 400kA200

250kA 500kA250

300kA 600kA300

See Note *

WMN1DSuffix

9.28 [235.61]

26.50 [673.10]

12.00 [304.80]

24.00 [609.60]

12.00 [304.80]

12.01 [305.18]

1.25 [31.75]

9.50 [241.30]

0.62 [15.87]

0.62 [15.87]

2X 0.44 [ 11.18] HOLES

2X 0.44 [ 11.18]

0.86 [21.84]

1.22 [30.99]

5.00 [127.00] A

A

A

Dimensions

NOTE:All dimensions are for reference only and are shown in Inches [millimeters]

“A” = Recommended conduit entry areas

Refer to instruction manual for details

Voltage Code 120S / 120Y 240D 240H 220Y / 240Y / 277Y 347Y 480D 600D

Protection Mode L-N L-G N-G L-L L-G L-L L-N HL-N L-G HL-G N-G L-L HL-L L-N L-G N-G L-L L-N L-G N-G L-L L-G L-L L-G L-L

UL 1449, 3rd Edition Voltage Protection Ratings(VPR) (assigned UL rating)

1000 1000 700 1200 1500 1800 1000 1500 1000 1500 700 1200 2500 1500 1500 1000 2000 1800 1500 1500 2500 2000 4000 2000 4000

UL 1449, 2nd Edition Suppression Voltage Ratings(SVR) (assigned UL rating) *

400 400 400 — 800 — 400 700 400 700 400 — — 800 800 800 — 1000 1000 900 — 1500 — 1500 —

* NOTE: SVR Ratings are no longer assigned by UL and are included in the table above for reference purposes only.

WMN1-WMN4 Protection Ratings

Voltage Code 120S / 120Y 240D 240H 220Y / 240Y / 277Y 347Y 480D 600D

Protection Mode L-N L-G N-G L-L L-G L-L L-N HL-N L-G HL-G N-G L-L HL-L L-N L-G N-G L-L L-N L-G N-G L-L L-G L-L L-G L-L

UL 1449, 3rd Edition Voltage Protection Ratings(VPR) (assigned UL rating)

900 800 700 1200 1200 1800 900 1200 800 1200 700 1200 2100 1500 1200 1200 2000 1500 1500 1500 2500 1800 3000 2000 4000

UL 1449, 2nd Edition Suppression Voltage Ratings(SVR) (assigned UL rating) *

400 400 400 — 800 — 400 700 400 700 400 — — 800 800 800 — 1000 1000 900 — 1500 — 1500 —

WMN12F-WMN12S-WMN4S-WMN4X Protection Ratings

DEA-365 (12/09)

GE Digital Energy – Power Quality830 W 40th Street, Chicago, IL 60609 USA800 637 1738 www.gepowerquality.com

Information subject to change without notice. Please verify all details with GE. © 2009 General Electric Company All Rights Reserved

NOTE:All dimensions are for reference only and are shown in Inches [millimeters]

“A” = Recommended conduit entry areas

Refer to instruction manual for details

Dimensions

WMN4DSuffix

2.74[69.57]

0.86[21.77]

0.76 [19.26]

A

A

A

24.00[609.60]

9.91 [251.76] 21.50 [546.10]

20.00 [508.00]

12.65[321.34]

25.50[647.70]

WMN12FSuffix

8.98[228.04]

15.33[389.38]

12.00[304.80]

0.57 [14.50]

0.57 [14.50]1.85 [47.04]

8x 0.28 [ 7.16] HOLES

6.00 [152.40]6.00[152.40]

16.00[406.40]

15.33 [389.38]

11.63 [295.30]

14.19 [360.38]

19.33[490.98]

11.63[295.30]

18.19[461.98]

8.98[228.04]

4.00[101.60]

4.00[101.60]A

A

A3.85

[97.84]

WMN12S,WMN4S,WMN4XSuffix

19.12 [485.61]

9.23 [234.33] 10.40 [264.14]

17.66 [448.53]

9.23 [234.33]

12.00 [304.77]

4x 0.38 [ 9.65] HOLES

16.00 [406.37]

6.00 [152.39]

6.00 [152.39]

4.00 [101.59]A