     eZ-TOMAS Machine Vibration Monitoring

    User’s ManualTotalOnline

    Monitoring and  Analysis

    Software

    © 2001 . . . 2005 by IOtech, Inc 947394  Printed in the United States of America

    Requires one of the followingOperating Systems:

    Windows 2000

    Windows XP

    Windows NT4*

    *Service Pack 5 or greater for NT4

    IOtech, Inc.25971 Cannon Road

    Cleveland, OH 44146-1833Phone: (440) 439-4091

    Fax: (440) 439-4093E-mail (sales): [email protected] (post-sales): [email protected]

    Internet: www.iotech.com

    eZ-TOMAS

    Total Online Monitoringand Analysis Software

    p/n 1086-0923 rev 11.0 

  • 8/17/2019 TOMAS UsersManual

    2/94

    947394

    NOTE: In eZ-TOMAS version 5.2, Spectral Band types are designated as “ A” through “ J”

    instead of “ 1” through “10” (as shown in related screen shots throughout this

    document). Functionality of the band types has not been changed.

  • 8/17/2019 TOMAS UsersManual

    3/94

    Table of Contents

    1 – Introduction

    eZ-TOMAS 937694  i

    What i s eZ-TOMAS …… 1-1Tips for Using eZ-TOMAS …… 1-1Starting eZ-TOMAS …… 1-2Connecting Signals …… 1-2The Order of Operation …… 1-3

     A Look at the Gauge Window& Contro l Pull-down Menu …… 1-4

    2 – Monitoring a Machine

    Creating a Project …… 2-1Configuring the Project …… 2-5Starting an Acquisition …… 2-6Viewing Spect ral Bands …… 2-6Plotting Data …… 2-6Viewing Reports …… 2-9

    3 – File Menu [In Gauge Window]  

    New (Clone) Project …… 3-1Initialize Project …… 3-1Open Project …… 3-2Save As …… 3-2Erase History File …… 3-3Erase Alarm Log …… 3-4Print …… 3-4Exit …… 3-4

    4 – Edit Menu [In Gauge Window] 

    Setup …… 4-1Tachometer Notes …… 4-6Limi ts …… 4-11Digi tal I/O …… 4-17Display Preferences …… 4-19Copy Window …… 4-20Load [or Remove] Graphic Picture …… 4-20Reset Peak Hold Values …… 4-20

    5 – Display Menu . . . Plots

    Introduction …… 5-1Saving and Recalling Plot Setups …… 5-3Changing Display Ranges & Scales …… 5-4 

    “ Real Time” Plot Controls …… 5-5 “ History Data” Plot Controls …… 5-5

    Channels …… 5-7Filtering Data …… 5-8

    6 – Toolbar Buttons

    7 – Plot Examples

    Time …… 7-2

    Spectrum …… 7-3

    Orbit …… 7-4

    Waterfall …… 7-5

    Bode …… 7-6

    Polar …… 7-7

    Strip Chart …… 7-8

    Shaft Centerline …… 7-9

    8 – Display Menu . . . Reports

    Statistical Report …… 8-1 Alarm Log Repor t …… 8-4Snapshot Log ……. 8-5Generate Report using Microsoft Excel 8-6Configuration Setup [.txt File] …… 8-15

    9 – Network Menu [In Gauge Window] 

    vv

    10 – Security Menu [In Gauge Window] 

     Appendix A – Using Function Keys

  • 8/17/2019 TOMAS UsersManual

    4/94

    iv 937694  eZ-TOMAS 

  • 8/17/2019 TOMAS UsersManual

    5/94

    Introduction 1

    What is eZ-TOMAS ? …… 1-1

    Tips for Using eZ-TOMAS …… 1-1

    Starti ng eZ-TOMAS …… 1-2

    Connecting Signals …… 1-2

    The Order of Operation …… 1-3

     A Look at the Guage Window & Control Pull -down Menu…… 1-4

    In regard to data acquisition systems, the following terminology is used throughout this

    manual:

    ZonicBook refers to a ZonicBook/618E.

    Medallion refers to any of the three ZonicBook-Medallion models.

    WaveBook refers to WaveBooks in general, except when a specific model isspecified.

    Reference Note:The information provided in this manual applies to ZonicBook, Medallion, and WaveBooksystems with exceptions as noted. Refer to your system’s specific hardware documentation

    in regard to hardware setup. 

    What is eZ-TOMAS?

    eZ-TOMAS (Total Online Monitoring and Analysis Software) is designed to collect vibration and processdata from rotating machinery. eZ-TOMAS can simultaneously monitor, acquire, store, and display data

    from Medallion, ZonicBook, and WaveBook systems.

    The signals to be acquired are typically associated with a specific machine train. The analog inputs can be

    any combination of Proximity, Velocity, Accelerometer, Tach, or DC proportional voltage signal. Up tothree tachometer signals are supported.

    Tips for Using eZ-TOMAS

    The following suggestions should make your use of eZ-TOMAS more efficient.

    1.  For Medallion only: Make sure your Medallion’s Dip Switches are configured correctly.Typically: Single Ended, AC coupled, and ICP ON.

    2.  For Medallion and WaveBook: Use a standard channel location convention.Typically: A single Tach is used at channel 8.

    3.  For ZonicBook: Tachometers are typically connected to tach-designated input channels.

    eZ-TOMAS 987294  Introduction 1-1

  • 8/17/2019 TOMAS UsersManual

    6/94

     

    Starting eZ-TOMAS

    To run eZ-TOMAS, double-click the eZ-TOMAS icon or use your Windows desktop

    Start button to navigate to the program file.

    The first time you start eZ-TOMAS you will be prompted for your name, yourcompany name, and a password. This password is the software key that will activate

    eZ-TOMAS for every day operations.

     Registration Form 

    If you are loading your software from a CD the password accompanies the CD. If you downloaded your

    software from the website, your password will be e-mailed to you within one business day.

    You will next be prompted to set up your project’s security password. When you click the buttonthe Password Confirm window opens. Retype your security password and click the button.

    After your password is accepted, you are returned to the Main window.

    Connecting Signals

    Medallion Users

    Connect the analog signals to the Medallion’s BNC inputs. Typically, proximity and DC proportional

    signals should be DC coupled; and Accelerometer, Velocity, and Tach signals should be AC coupled.

    Prox: SE(single ended) DC Coupled ICP off

    Accel/Vel: SE AC Coupled ICP on

    Tach: SE AC Coupled ICP off

     Note that these settings are made via Medallion’s DIP switch.

    Reference Note:If necessary, refer to the Medallion user manual (p/n 1086-0901) for information regardingthe following:

    •  Software Installation

    •  System Requirements 

    •  Hardware Setup

    •  Driver Installation 

    WaveBook and ZonicBook Users

    Connect the analog signals to the analog input BNC connectors. WaveBooks, ZonicBooks and the WBK14

    and WBK18 dynamic modules require no physical hardware configuration. All hardware configuration isaccomplished through software.

    Reference Note:Information regarding the following products is provided in documentation as follows:

    WBK14 and WBK18 - WBK Options Manual (p/n 489-0902).

    WaveBook - WaveBook User’s Manual (p/n 489-0901).

    ZonicBook/618E -  ZonicBook/618E User’s Manual (p/n 1106-0901).

    PDF versions of the documents are included on your data acquisition CD. 

    1-2 Introduction 987294  eZ-TOMAS 

  • 8/17/2019 TOMAS UsersManual

    7/94

     

    The Order of Operation

    eZ-TOMAS 987294  Introduction 1-3

  • 8/17/2019 TOMAS UsersManual

    8/94

     

     A Look at the Gauge Window & Control Pull-down Menu

    The Gauge Display Window is used to show real-time values and measurement status. Gauge Display is

    not used for historical data analysis. A Data Display Window, discussed elsewhere, is used to analyze real-time and historical data.

    The Gauge Display Window’s Control pull-down menu repeats the functions of the Gauge window’s lower

     panels. For example, menu selections can be used in place of several Option panel buttons, as well as thetoggle switches and snapshot button. The menu provides a means of displaying high and low peak values,

    gauge values, a machine image, and a list of eZ-TOMAS projects. The menu and its functions are depictedon the Gauge window figure on the following page.

    The main window of the GUI (graphical user interface) includes a set of virtual gauges, which use one of

    10 spectral bands, discussed shortly. There will always be a vertical gauge associated with each input

    channel. When the 1x Amp/Phase selection is made, spectral bands for “1x Amplitude” and “1x Phase” aresimultaneously displayed, with the later being in a circular phase gauge (see second figure).

    In addition to spectral band gauge displays, eZ-TOMAS can interactively display data in a variety of other

    formats, including: Orbit, Polar, Time, Bode, Cascade/Waterfall, Strip Chart, and Shaft Centerline.

    Instrument(Gauge) Panel

     Acquisi tio nPanel

    Limit Check Digital I/O Data Storage Options

    Gauge Window, “Overall” Spectrum Selected

    Vertical Gauge for1x Amp

    Circular Phase

    Gauge

    Vertical GaugeTach Ref (RPM)

    Shown for reference.

    Vertical Gauges (partial) and Circular Phase Gauges

    1-4 Introduction 987294  eZ-TOMAS 

  • 8/17/2019 TOMAS UsersManual

    9/94

    You can “mouse-clicks” on the gauges to:

    Bring up the Limit Configuration Window.

    Bring up the Input Channels Tab (on the Setup Configuration Window). This cannot be done

    from circular phase gauges.

    Drag limit-pointers on vertical gauges to new positions, thus setting new limit values.

    Drag limit-lines on circular phase gauges to new positions, thus setting new values for the phase

    angle limits.

    Although the configuration windows and limits are discussed later, an explanation of how to access them

    from the gauges directly follows.

    eZ-TOMAS 987294  Introduction 1-5

    Vertical Gauges Circular Phase Gauges

    “Right-Click” on an activelimit-pointer to bring up theLimit Configuration Window.

    “Right-Click” elsewhere in avertical gauge to bring up theInput Channels Tab [on the

    Setup ConfigurationWindow].

    “Left-Click and Hold” on alimit-pointer to drag it to anew position, thus setting anew limit value. 

    “Right-Click” within theconfines of a circularphase gauge to bring upthe Limit ConfigurationWindow.

    “Left-Click and Hold” on alimit-line to drag it to anew position, i.e., a newlimit angle.

  • 8/17/2019 TOMAS UsersManual

    10/94

    The data acquired by eZ-TOMAS and the supporting configuration information are stored in user-defined

    files. This allows a single eZ-TOMAS system to be used with several different machines. The acquireddata is stored according to user-defined event changes, e.g., time, overall, and rotating speed.

    Acquisition, instrumentation, and storage configuration parameters are also definable. These parameters

    are stored over time. Configuration changes do not invalidate previously acquired data.

     Functions of the Control Pull-Down Menu

    The straight-forward functions of Control Pull-down menu are depicted in the above figure. The shaded

    numbers in the menu relate to the corresponding non-shaded numbers. The functions, which are self-descriptive by name, are as follows:

    1)  Acquisition – can be use to turn the acquisition on or off, just as can the acquisition toggle switch.

    2)  Limit Check – can be used in the same manner as the Limit Check toggle switch.

    3)  Digital I/O – can be used to turn Digital I/O on or off. Same functionality as the Digital I/Otoggle switch.

    4)  Save Snapshot – A data storage trigger that can be used instead of the “camera” button. Theduration of the data collection is set in the Storage Tab of the Setup Configuration window

    [accessed via the Edit pull-down menu].

    5)  Show Peak Holds – Used to display [or hide] high and low peak markers.

    6)  Show Gauge Values – Used to display [or hide] gauge values.7)  Show Machine Graphic – Used to show or hide a graphic. The image can be positioned

    anywhere on the screen.

    8)  Show TOMAS Projects – Accesses a list of projects and their associated directory locations.

    1-6 Introduction 987294  eZ-TOMAS 

  • 8/17/2019 TOMAS UsersManual

    11/94

     

    The Spectral Bands and Tachs

    Most of the Gauge window is occupied by gauges which display values for spectral bands and tachometers.Selection of the band types and the tachs can be made from the “Gauges” pull-down menu.

    Gauges Pull-down Menu

    To select a spectral band with the mouse, open the Gauge pull-down menu, then place the mouse cursor

    over the selection and click on it. In the preceding figure, Overall has been selected. Note that the Overallvalue is a time domain overall value.

    The Overall, DC Gap Voltage, 1x Amp, and 1x Phase spectral bands cannot be modified. In regard to

     probe values:

    Displacement probe measurements are displayed as peak-to-peak values.

    Velocity probe measurements are displayed as zero-to-peak values.

    Accelerometer probe measurements are displayed as zero-to-rms values

    You can define the parameters of User Defined bands 5 through 10 in the Setup Configuration window.

    To define a parameter:

    1.  Open the Edit pull-down menu.

    2.  Select Setup.

    3.  From the Setup Configuration window select the Spectral Bands tab.

    4.  Set the parameters of the User Defined bands.

    eZ-TOMAS 889895  Introduction 1-7

  • 8/17/2019 TOMAS UsersManual

    12/94

    Gauge Window – The Lower Panels

    Gauge Window, Lower Panels

     Acquis it ion Panel

    The Acquisition Panel contains one toggle switch, which determines the ON/OFF status of data acquisition.Click this toggle switch to turn data acquisition ON (Up/Green), or OFF (Down/Red).

    Limit Check Panel

    The Limit Check panel contains a toggle switch and an alarm log progress bar. The Limit Check toggle

    switch determines the ON/OFF status of the Limit Checking feature. Click this toggle switch to turn limit

    checking ON (Up/Green), or OFF (Down/Red).

    The Alarm Log Progress Bar graphically indicates how full the Alarm File is.

    Double-clicking on the bar, or on its associated text, opens the Alarm Log. The log can also be accessed

    from the Reports pull-down menu. The most recent alarm event will appear below the bar.

    Digital I/O Panel

    The Digital I/O Panel contains an ON/OFF toggle switch and four push buttons. The push button iconsindicate the current status of the digital I/O. Each time you start eZ-TOMAS, the switches will be turned

    off and appear gray. The Digital I/O toggle switch must be turned “ON” to enable digital I/O functionality.

    If the DIO toggle switch is turned on, Digital I/O relay switches will activate [or deactivate] depending on

    the configuration set in the Digital I/O Configuration window (detailed in chapter 4). The window is

    accessible via the Edit pull-menu.

    During an acquisition you can manually activate each of the four switches by clicking on the associated

     button.

     Note that in the following figure, the Digital I/O push buttons are as follows.

    Top two: Digital Input, Digital Output [Normally Closed]

    Bottom two: Digital Output [Normally Opened], Digital Input.

     Digital I/O Panel

    The four Digital I/O button icons agree with the setup in the Digital I/O Configuration window.

    1-8 Introduction 889895 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    13/94

    Data Storage Panel

    The Data Storage Panel is easily recognized by its Snapshot [camera] button and the bar for Current Data

    Record / History File Size.

    The bar graphically indicates how full the FIFO file is. Two numbers, separated by a slash, reside just

     below the progress bar. In the example this is 500 / 500. The first number is the current data record

    number; the second is the number of records that can be stored in the FIFO file, also referred to as the

    History File Size. In this case the data file is full.

    Clicking the (camera) button will save “N” seconds of data to the history file; where “N” is

    defined in the Storage Tab [in the Configuration Panel]. The data storage panel includes the Historical DataFile Date Range.

     Note that you can open the Plot Window from this panel by double-clicking on the capacity bar, the record

    numbers, or the date text.

    FIFO Records Capacity Bar

    Number of Records that can be stored(History File Size)

    Number of Records currently stored

    Snapshot

    Data File’sDate/Time Range

     Data Storage Panel

    Note: The  button initiates multiple continuous snapshots for “N” seconds of time data. The

    time (in seconds) “N” is defined in the Storage Tab of the Setup Configuration Window.

    Options Panel

    Display Peak HoldGauge Pointers

    Show PeakHold Values

    Reset Peak HoldGauge Values

    Display list ofTOMASprojects

    The Options Panel provides a means ofeasily displaying the following:

    •  peak hold gauge pointers

    •  peak values

    •  all real time values(all gauge values)

    • a list of eZ-TOMAS projects andtheir associated directory

    • a graphic to represent the machine

    • a graphic to indicate networktrafficking (see second figure)

    Display AllGauge Values

    Display MachineGraphic Picture 

    eZ-TOMAS 889895  Introduction 1-9

  • 8/17/2019 TOMAS UsersManual

    14/94

    When eZ-TOMAS is being used by multiple computers, a network xfer graphic appears, as indicated in the

    follow figure. Networking is discussed in Chapter 9.

    Options Panel with the Network Xfer Icon

    The Options Panel includes a  button. Clicking the button momentarilyresets the peak values. However, the new peak acquisition values [which exist after the point of reset] will

    immediately apply.

    Clicking the  button brings up a separate window, which allows youto select a jpeg or bitmap image to represent the machine, for example, a picture of an engine or turbine. A

    text field is present, which is convenient for entering a machine identifier, such as a serial number or a

    factory reference label (see figure at right).

    To change the title bar of the machine graphic, pull down the Gauge Window’s” Edit menu, select “Display

    Preferences,” then type the desired entry into the Machine Information panel’s “Name” field.

    In regard to the graphic image, if you right-click in the window, two choices will appear: “Load graphic picture” and “Remove Graphic Picture.” Clicking on the former allow you to browse your PC for the

    appropriate graphic. Note that this can also be accomplished through the Edit pull-down menu.

     Machine Graphic Picture

    1-10 Introduction 889895 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    15/94

    eZ-TOMAS 987294  Monitoring a Machine 2-1

    Monitoring a Machine 2

    Creating a Project …… 2-1Using “Initialize Project”….. 2-2Using “New (Clone) Project”……2-4

    Configuring the Project …… 2-5

    Starting an Acquis ition …… 2-6Viewing Spectral Bands …… 2-6

    Plotting Data …… 2-6Multiple Plots …… 2-6“Real Time” Plot Controls …… 2-7“History Data” Plot Controls …… 2-8

    Viewing Reports …… 2-9

    Creating a Project

    An eZ-TOMAS Project is a collection of data files, typically associated with a monitored machine. The

    data files include configuration and measured data. When eZ-TOMAS runs it attempts to open the last

    eZ-TOMAS Project accessed.If you are monitoring a machine for the first time, you should create a new eZ-TOMAS Project to store the

    machine’s configuration and vibration data. If you have already created an eZ-TOMAS Project for themachine, use the File Open menu to pick up where you left off.

    The vibration data files have a FIFO design. When you turn on the acquisition switch, data will be

    appended to the data files.

  • 8/17/2019 TOMAS UsersManual

    16/94

  • 8/17/2019 TOMAS UsersManual

    17/94

    Fig. 1  Gauge Panel for 24 Input Channels – First Row (Channels 1 through 8) is selected for gauge display

    In Fig. 1 we see that Accel Ch 1 through Accel Ch 8 are being displayed. Channels 5, 6, and 7 would also be displayed, but

    have been removed from the figure for clarity. In addition, the vertical gauges have been greatly compressed.

    Below the gauges we see 3 rows of data cells. The top row provides data for Channels 1 through 8, the second row displaysdata for channels 9 through 16, and the third row displays data for channels 17 through 24. Up to 7 rows (channels 1 through

    56) can be displayed.

    We know that gauges are being displayed for channels 1 through 8. But suppose we wanted to see the gauge for channel 11?

    A single click on the associated cell [in the second row] accomplishes this task. Simply single-click on the third cell in the

    second row to display the gauge for Accel Ch 11. In the following figure we see that channel 11’s gauge replaced thechannel 3’s. This is because each of the 8 columns can display a gauge for only one channel at a time. Thus, column 3 is

    home to channels 3, 11, and 19. The third gauge from the left can only display one of those channels at a time.

    Fig. 2 - Displaying Accel Ch 11 in place of Accel Ch 3Note “A” - Single click on a cell to display the gauge for that cell.

    If we wanted to change our display to show an entire different set of gauges we could single click on individual cells; or we

    could double-click on any cell in a row to display guages for all the channels in that row (see Fig. 3).

    Fig. 3 - Selecting a New Set of Eight Gauges

    Note B - Double-click on any cell in a row to display gauges for all channels in that row.

     Notice the second row of data cells in Fig. 3. Double-clicking on any cell in that row causes all 8 channels in that row tohave a gauge display. The gauge for Accel Ch 1 has been replaced with a guage for Accel Ch 9, the gauge for Accel Ch 2

    has been replaced with a gauge for Accel Ch 10, etc. If we double-clicked on a cell in the third row we would see gauges

    displayed for channels 17 through 24.

    eZ-TOMAS 987294  Monitoring a Machine 2-3

  • 8/17/2019 TOMAS UsersManual

    18/94

     

    Using “ New (Clone) Project”

    Cloning a project keeps all of the values from the original project.

    Each eZ-TOMAS Project contains eZ-TOMAS configuration and data files. You should logically equatean eZ-TOMAS Project with a specific machine. This is accomplished as follows:

    1.  On the File pull-down menu, select New (Clone) Project. This opens the Save As window.

    Save As Window, Being Used to Create a New File

    2.  Select [or create] a Windows folder for the eZ-TOMAS Project.

    3.  Enter the desired filename for this project.

    4.  Click the button to create the new project.

    2-4 Monitoring a Machine 987294  eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    19/94

    Configuring the Project

    A default configuration is automatically loaded when you open an eZ-TOMAS file. However, you may

    want to make some changes to the configuration. To make changes:

    1.  From the eZ-TOMAS Main Window, open the Edit pull-down menu.

    2.  In the Edit menu select Setup. The Setup Configuration window will appear.

    Reference Note:The four tabs of the Setup Configuration window are labeled: Acquisition, Input Channels,

    Spectral Bands, and  Storage. They are discussed briefly in this section and in detail at the beginning of Chapter 4, Edit Menu. 

    3.  Make sure that the Hardware panel reflects the correct device, e.g., ZonicBook/618E.

    Setup Configuration Window, Acquisition Tab

    Clicking the button will undo all the changes you’ve made since you

    opened the Setup Configuration Window.

    4.  Make the desired changes for each of the tabs and then click the button.

    You can start monitoring immediately.

    Acquisition Tab – From the Acquisition tab you can set up parameters that include, but are not limitedto: Block Size, Analysis Frequency, Low Cutoff Frequency, FFT Window, and Number of Averages.

    Input Channels Tab – From the Input Channels Tab you can change channel parameters. Thisincludes, but is not limited to assigning channel types, customizing channel names, setting the instrumentrange per channel, and assigning units.

    Spectral Bands Tab – From the Spectral Bands Tab you can modify “User Defined” bands 5 through10 according to your application. Note that Overall, DC Gap V, 1x Amp, and 1x Phase bands are

     predefined and cannot be modified.

    Storage Tab - From the Storage Tab you can specify how you want trigger data storage. If any oneevent is triggered, data from all channels is stored. Data storage events are triggered when a change occurs

    in the monitored machine’s condition. The basic idea is to activate storage based on Time Change and/or  

    Speed Change and/or  Amplitude Change.

    Refer to chapter 4 for more information regarding the Setup Configuration tabs.

    eZ-TOMAS 987294  Monitoring a Machine 2-5

  • 8/17/2019 TOMAS UsersManual

    20/94

    Starting an Acquisition

    After you configure your eZ-TOMAS Project, click the Toggle Switch to place it in the upright position. This starts the data acquisition. The switch is located in the

    in the lower left corner of the eZ-TOMAS gauge window.

    When acquisition is active, real time overall values are displayed in the instrument gauges.

    The toggle switch is green while data acquisition is active.

    To stop data acquisition, click the switch toggling it down (red).

    Viewing Spectral Bands

    The Main Window’s gauges can be used to display different spectral bands. On the View menu select the band of interest, e.g., Overall, DC Gap V, 1x Amp, 1x Phase, or one of the User Defined bands. Note that

    selecting 1x Amp or 1x Phase results in two gauge types. In both cases vertical gauges will display for

    1x Amplitude and circular phase gauges will display for 1x Phase. This is done automatically since the two

    spectral bands are closely related.

    Spectral Bands

    Plotting Data

    Click on “Display” in the main window’s menu bar, then select “Plots.” The Data Display Window

    will open. Note that you can double-click on a gauge to open the Data Display Window to plot data forthat specific channel.

    Multiple Plots

    1.  On the File pull-down menu of the Plots window, select Open Plot Window.This opens a second display window.

    2.  On the Window pull-down menu of the Plots window, select either Tile Vertically orTile Horizontally.

    All display windows will be shown simultaneously.

    2-6 Monitoring a Machine 987294  eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    21/94

    3.  Select the Channel(s) and Display type for each window.

    Time Display and Spectrum Display Plots Tiled Horizontally

    Each plot is longer in the horizontal direction. 

    A cursor is provided with each display. To move the cursor, place your mouse icon over the cursor and

    drag it to the desired location on the trace or use the East / West Arrows.

    “ Real Time” Plot Controls

    “Real Time” is the default data source. For Real Time displays you can Halt and Resume the display of

    data by using the toggle button (see following figure). As an option to the  button you can use the “P” key on the PC’s keyboard. A table, which identifies all control buttons follows shortly.

    The  button, which looks like a black “X,”allows you to clear the data inthe realtime trend displays. This display option can be used to clear the plot displays prior to starting a

    test.

    Pause/Continue 

    Clear Real TimePlot Buffer  

    SelectsReal TimeMode 

     Real Time Mode is Selected  

    Reference Note:

    Refer to chapter 6 for more detailed information regarding Plots and the associated toolbar buttons and other controls. 

    eZ-TOMAS 987294  Monitoring a Machine 2-7

  • 8/17/2019 TOMAS UsersManual

    22/94

    “History Data” Plot Controls

    When viewing History Data (pre-recorded data files), you can use the set of playback buttons or the slider bar to navigate through the data. A table, which identifies all control buttons, is included in chapter 6.

     Note that the playback buttons and slider remain hidden in the GUI when eZ-TOMAS is in the Real Time

    mode.

    History Data is accumulated according to the parameters setup in the Setup Configuration window’s

    Storage Tab, which is accessed via the Gauge Panel window’s Edit Menu.

    Data Source-History File 

    Play BackButtons

    Slider  

     History Data (Playback) Mode is Selected  

    Use slidersto set thestart andstop timesfor thedesiredplayback.

    Show Alarm Log

    ShowSnapshot Log

    Reference Note:Refer to chapter 6 for more detailed information regarding Plot displays,

    associated toolbar buttons, and other controls. 

    2-8 Monitoring a Machine 987294  eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    23/94

     

    Viewing Reports

    eZ-TOMAS can generate the following types of reports, which are accessible from the Display pull-down

    menu.

     Display Pull-down Menu

    The Statistical Report lists the historical spectral band data. It includes the instrument, the engineering

    units, the minimum value, the mean average value, the maximum value, and the standard deviation bychannel. Statistical reports can be used to automatically generate limit values based on historical data.

    The Alarm Log is a record of the last “N” number of alarm events. The number of alarms was specified in

    the Setup Configuration window under the Storage Tab. The Alarm Log includes the date and time, the

    channel number, reference tachometer, instrument name, spectral band type, alarm type, and value of thealarm signal.

    The Snapshot Log can be accessed from the Reports pull-down menu, or from the History Data Window.

    The Snapshot Log file contains entries which were created whenever the user clicked the  

     button, which is located in the Gauge Window’s Data Storage panel.

    The Generate Report using Microsoft Excel option is available beginning with eZ-TOMAS version5.0.x. The feature allows you to generate a report using Microsoft Excel 2000 (version 9.x) or later.

    An XL Report generation dialog box allows you to format the report and specify its contents.

    Selecting Configuration Setup from the Reports pull-down menu creates a text file that contains

    configuration details of the current project.

    Reference Note:

    Refer to Chapter 6, Display… Reports, for detailed information regarding each report type andfor instructions pertaining to generating limits. 

    eZ-TOMAS 987294  Monitoring a Machine 2-9

  • 8/17/2019 TOMAS UsersManual

    24/94

     

    2-10 Monitoring a Machine 987294  eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    25/94

    File Menu [In Gauge Window]  3

    New (Clone) Project …… 3-1Note: The File Menu discussed in this chapter is located

    in the Gauge Window’s menu bar. It is not to be

    confused with the Plot Window’s File Menu.

    Initialize Project ….. 3-1

    Open Project …… 3-2

    Save As …… 3-2

    Erase History Data …… 3-3Erase Alarm Log …… 3-4

    Print …… 3-4

    Exit …… 3-4

    New (Clone) Project – Creates a Copy of a Project and its Data 

    Cloning a project keeps all of the values from the original project.

    The New (Clone) Project option opens the Save As window. The first step in

    creating a new project is to select or create a Folder where the new project’s files

    should be saved. Enter a filename for the project, then click the button.

     Note that the “Save As” window that is accessed via the New (Clone) Project

    selection is not the same Window that results from clicking the “Save As” optionin the Gauge Window’s File pull-down menu. The later is for saving one of

    three backup formats. These are: Entire Project, Partial Project, and Gauge Data

    (ASCII). After selecting one of the three formats and clicking the button,the Save As window will appear.

    Using the Save As Window to

     Create a New Project

    Initialize Project – Creates a New Project and Sets the Number of Available Channel Inputs 

    When a project is initialized you are essentially starting with a “clean slate.” No data is carried over as when a

    project is cloned.

    To inform eZ-TOMAS as to what type of hardware will be used, select “Initialize Project” from the Gauge Window’s

    File pull-down menu. The resulting window allows you to select a Hardware Device and the applicable number of inputchannels. Chapter 2 includes an example.

     Initialize Project

    eZ-TOMAS 958794  File Menu 3-1

  • 8/17/2019 TOMAS UsersManual

    26/94

     

    Open Project

    The Open Project option provides a means of locating and opening an existing eZ-TOMAS project.

    Note:  When eZ-TOMAS is started, it opens the last active project.

    Save As

    The Save As option allows you to backup history files in a binary file format, or export files in an ASCII

    file format. This command opens the Backup/Save eZ-TOMAS Project window. The options in thiswindow change as you make selections. You can backup and export full or partial files.

    Note:  The disk space required to backup the selected records is displayed on the left panel.

    Entire Project

    The Entire Project option is only available when data acquisition is turned off. Entire Project performs a

    file copy operation to the specified Windows Directory. This backup method is the fastest. 

    Save As… Entire Project

    Partial Project

    The Partial Project option can be used when data acquisition is

    active. This option copies data and the configuration setup to the

    designated folder for the date and time range specified in the panel onthe right.

    To make a partial backup:

    1.  Use the sliders in the Partial Project Backup panel (see figure atright) to select the start and stop times of the range that you want

    included in the backup.

    2.  Click the button. TheSave As

     window will open.3.  Select the folder where the file is to be saved.

    4.  Enter a filename.

    5.  Click the button.

    Save As… Partial Project

    3-2 File Menu 958794 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    27/94

     

    Backup Format – Guage Data (ASCII)

    This option creates an exportable ASCII file for the gauge data.

    Save As… Gauge Data (ASCII)

    Backup Format – Time History Data (BUNV)

    This option creates an exportable Binary Universal (UFF-58B) format (BUNV) file for the

    Time History data.

    Save As… Time History Data (BUNV)

    eZ-TOMAS 958794  File Menu 3-3

  • 8/17/2019 TOMAS UsersManual

    28/94

     

    Erase History Data

     Erase History Warning

    Use the Erase History Data option with caution. This menu item will erase History Data

    for the project. All data for the active project will be permanently removed. It is not

    recoverable.

    The configuration information will not be erased.

    Erase Alarm Log

     Erase Alarm Log

    Use the Erase Alarm Log option with caution. This menu item will erase the Alarm Log

    file for the project. It is not recoverable.

    Print

    “Print” brings up the Print Window for printing the current screen.

    Exit

    Closes the eZ-TOMAS application.

    3-4 File Menu 958794 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    29/94

    Edit Menu [In Gauge Window]  4

    Setup…… 4-1 Acquisition Tab…… 4-1Input Channels Tab …… 4-3Spectral Bands Tab …… 4-9

    Default Tach …… 4-5Spectral Bands …… 4-5

    Tachometer Notes ….. 4-7Synopsis of Tach Modes …… 4-8Storage Tab …… 4-10

    Limi ts …… 4-12

    Digi tal I/O…… 4-18

    Display Preferences …… 4-20

    Copy Window …… 4-22

    Load [or Remove] Graphic Picture … 4-22

    Reset Peak Hold Values …… 4-22

    Note: The Edit Menu discussed in this chapter is located in the Gauge Window’s menu bar.

    It is not to be confused with the Plot Window’s Edit Menu.

    Setup…… 

    The Setup Configuration Window has individual panels for configuring the acquisition device. Click the

    appropriate tab at the top of the window to configure the data acquisition system. Make the necessary

    changes in each panel. Click the button to save all your changes and close the window.

    Clicking the button will undo all the changes you’ve made since you

    opened the Setup Configuration Window.

     Acquis it ion Tab

     Acquisition Tab

    The Acquisition tab is used to configure how the data will be acquired and processed. A breakdown of

    the panel tabs follows.

    eZ-TOMAS 947394  Edit Menu 4-1

  • 8/17/2019 TOMAS UsersManual

    30/94

     

    You must turn acquisition off and then on again for Acquisition Configuration changes

    to take effect. 

    Panels of the Acquisition Tab

    Hardware 

    The Hardware Panel has a pull-down list from which the applicable

    data acquisition device must be selected; i.e., WaveBook, ZonicBook,or Medallion.

    dB Reference 

    This panel is used to set the 0 dB reference point in Engineering Units(EU). The EU value for 0 dB reference is used with microphone inputchannel types. The default setting is 20 micro-Pascals (0.000020 pa).

     Acquisition  

     Analysis Frequency (Hz) The maximum frequency of interest. Thesampling rate will be 2.56 times the analysis frequency. Verify the

    maximum frequency response of your probes. For a Tach signal,your Analysis Frequency should be a higher multiple of the maximumrotating speed. Typically, this multiple is at least 10 times the rotatingfrequency.

    Spectral Lines The number of lines per spectrum and the number ofdata samples used in the FFT (Fast Fourier Transform) process. Themore spectral lines, the greater the data resolution. As the number ofspectral lines increases, so does the time that it takes to collect thedata and the amount of disk space. 

    Overlap Data Acquisition For slow speed data acquisitionapplications, you have the option to select overlap data processing tospeed up real time data displays. This option is enabled when the

     Acquisition Time is greater than 2 seconds. 

    If you select Overlap Data Acquisition, eZ-Tomas will automaticallydetermine the overlap percentage needed to achieve a 1 to 2 seconddisplay update rate. For example, if your analysis frequency is500 Hz and you have 3200 spectral lines, the acquisition time is 6.4seconds. With Overlap Data Acquisition, the overlap percentage willbe 75% and the update rate will be 1.6 seconds. (6.4 sec / 4). Thedivisor is a power of 2. 

    Number of Averages  The number of data blocks averaged before ablock of data is accepted and displayed. Typically, the value is “1”indicating no averaging. 

    FFT Window  Fast Fourier Transform. FFT is an efficient techniquefor calculating the frequency of components in a time-domainwaveform based on digitized voltage measurements. The result is adisplay of amplitude versus frequency and phase versus frequency.The FFT Window is a weighting window, typically either Hanning orFlat Top. Hanning provides better frequency resolution. Flat Topprovides better amplitude resolution. 

    4-2 Edit Menu 947394 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    31/94

    Note: Filter Panels apply to ZonicBook/618E and WBK18 channels. Filter Panel functionality does not applyto WaveBook direct channels or to Medallion channels.

    High Pass Coupling Filter (Hz)

    High Pass Filter (AC Coupling): When AC Coupling is selected inthe Input Channels tab, the associated input signals will pass througha 0.1 Hz or a 1 Hz High Pass Filter, depending on which radio buttonis selected. 

    High Pass Display Filter (Hz)

     Allows you to eliminate the lower frequencies from the full frequencyrange for “no,” “single,” and “double” integrations by entering thedesired cutoff value in Hz. All data points that exist below thespecified value are set to zero. 

    Integration Units

     Accelerometer and Velocity signals can be integrated. Select the

    desired integration value (g’s/ips/mils, g’s/ips/in, or g’s/mmps/mm).Points to note:

    (1) If the signal is acceleration, then(a) single integration results in velocity, and(b) double integration results in displacement .

    (2) If the signal is velocity, then single integration results indisplacement .

    (3) The type of integration (none, single, or double) is selected in theInput Channels tab.

    Terms and factors related to the Acquisition Panel

    Nyquist Factor   In eZ-TOMAS waveform frequency is multiplied by a nyquist factor of 2.56. Thisensures that a sampled analog signal is accurately reconstructed. The 2.56 nyquistfactor is the most efficient in FFT Analysis.

    Sampling Rate  A rate that is 2.56 times the Analysis Frequency. If the Analysis Frequency was1000 Hz and if the Spectral Lines was 800 lines; then the Sampling Rate would be2560 samples per second. This rate would apply to each channel. Derived from:

     Analysis Frequency x 2.56 = 1000 x 2.56 = 2560.

    SpectralResolution

     A value related to Analysis Frequency and Spectral Lines. Where SpectralResolution equals the Analysis Frequency divided by 2.56. If the Analysis Frequencywas 1000 Hz and if the Spectral Lines was 800 lines; then the Spectral Resolutionwould be 1.25 Hz per spectral line.

    Derived from: Analysis Frequency divided by Spectral Lines = 1000 Hz / 800 = 1.25 Hz

    eZ-TOMAS 947394  Edit Menu 4-3

  • 8/17/2019 TOMAS UsersManual

    32/94

    Input Channels Tab

    This tab is used to configure each channel for your project. The available setup options in this window aredependent on the instrument type selected.

     Input Channels Tab, Showing the Leftmost Column

    To configure a channel: 

    1.  Select the channel to be configured.2.  Set the instrument type.3.  Set the value for each attribute of the channel.

    Repeat this process for each channel.

    The parameters of one channel can be copied to another channel by usingoptions on the Edit menu.

    Medallion Users Only: Configure the Dip Switches for each probe, according to probe

    type. For details refer to the Medallion user’s manual (p/n 1086-0901).

    Input Channels Tab Column Functions

    No.  is the channel number. Selecting the channel number highlights all attributes for thatchannel.

    Type  is the type of instrument attached to the channel. Options are:

    o  Accelerometer

    o  Velocityo  Displacemento  Statico  Tach

    o  Microphone

    o  Pressureo  Generalo  Unused (select “Unused” for channels that

    have no instrument attached.)

    Name  is a Label you will use to identify the channel.

    Gauge Min,

    Gauge Max 

    represent the instrument range minimum and maximum gauge values.

    Units is the Engineering Units you want to use. Options depend on the instrument type. 

    4-4 Edit Menu 947394 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    33/94

    eZ-TOMAS 947394  Edit Menu 4-5

    Accelerometer and Velocity signals can be integrated. This column is used to select thetype of integration (none, single, or double). Points to note:

    (1) If the signal is acceleration, then

    (a) single integration results in velocity, and(b) double integration results in displacement.

    (2) If the signal is velocity, then single integration results in displacement.

    Integration 

    (3) The integration value (g’s/ips/mils, g’s/ips/in, or g’s/mmps/mm) is selected in the

    Acquisition Tab.

    mV / EU  is the instrument sensitivity. (Typical displacement probes: 200 milli-Volts per mil.Typical accelerometer probes: 100 milliVolts per G. For Tach probes

    enter 1000.) For static channels, this property represents the slope variable (m) of the

    linear equation y = mx + b.

    Offset Sets the offset factor that is to be applied to the Engineering Units.

    FSV  FSV (Full Scale Voltage) is the maximum input voltage for the instrument. If you areunsure of the instrument’s maximum voltage value, select a high voltage value.

    ICP A constant 4mA bias current is available for ICP transducers that are used as signal input

    for ZonicBook/618E’s analog channels (CH1 through CH8) and for compatible expansionmodules that accept ICP transducers, for example, the WBK18. The bias current is

    sourced through the center conductor of the input channel BNC connector and returns tothe acquisition device [e.g., ZonicBook/618E or the WBK18] via the BNC’s outer

    conductor.

    The current source features an operating compliance of 24V and is protected in regard to

     both short-circuit and overvoltage. Operating compliance refers to the highest voltagethat can be applied without change of the current source value. In the absence of a

    transducer, the current source will output an open circuit voltage of 30V. For applications

    that do not require bias, the current source can be disconnected from the input by un-checking ICP in the Input Channels tab on a per-channel basis.

    When the ICP cell is checked for a channel, the current source is enabled, the input

    voltage is continuously monitored with level detection circuitry. Recognition of a voltage

    greater than 25V (transducer open) or less than 1V (transducer short) triggers a transducer

    fault condition for the affected channel. This error is communicated to the user via a front panel LED and is also available through a software status request at the end of an

    acquisition. When recognized, an error is latched until the commencement of a new

    acquisition. Consequently, even intermittent faults are detected and communicated.Detection of a fault does not, however, alter the acquisition process or its data.

    When the ICP function is not available to a channel a dash appears in the ICP column for

    the associated channel.

    Coupling AC or DC coupling can be set on an individual channel basis from the Input Channels tab

    Coupling is available for analog channels (CH1 through CH8) and for compatible

    expansion channels [e.g., from a WBK18]. AC Coupling can be set to a high pass filtervalue of 0.1 Hz or 1 Hz. The value is selected in the Edit Menu’s Acquisition Tab.

     Note that when DC Coupling is selected the high pass filter is bypassed.

    When the Coupling function is not available to a channel, or not used by a channel, a dashappears in that channel’s Coupling column.

    Angle Loc  is the physical angular location of a probe. Zero degrees is defined to be the top dead

    center. The angle value is measured in the counterclockwise (CCW) direction as viewedfrom the driver end. Orbit and Polar displays utilize Instrument Angle for data correction

    1xA Ref  and1xP Ref  

    1x Amplitude Reference and 1x Phase Reference are the slow roll values used for Runout

    Compensation on Bode or Polar displays.

    Gap Volt  is the DC voltage value when the shaft is at rest. This value is used for Shaft Center Line

    displays. 

  • 8/17/2019 TOMAS UsersManual

    34/94

    XY Pair  associates 2 probes on a bearing. Typically, probe pairs are located 90 degrees apart.Orbit displays require a Channel Pair.

    Brg Clear  Bearing Clearance is measured in the instrument’s engineering units. You can

    optionally overlay the bearing clearance circle onto an orbit display or shaft centerline.

    Brg Start Bearing Start is the location of the shaft relative to the bearing when the machine is at

    mechanical rest. Three possible locations are taken into consideration: Bottom, Center,and Top. For horizontal shafts, a bearing start of bottom is typical, due to gravity;

    However, in some situations mechanical linkage can result in a bearing start with the shaft

    at the top. For shafts that are oriented vertically, a bearing start of center is likely.

    DefaultTach

    The "Default Tach" column allows you to define the Tach Preference for each channel.Thus, on Gauge Display and Plot Display eZ-TOMAS can show 1x values relative to the

     preferred tach. When two or more tachs are defined eZ-TOMAS computes spectral data

    relative to each. For example, with two tachs: If Tach 1 measures 3000 rpm and Tach 2measures 4500 rpm eZ-TOMAS computes 1xA values for each. With the RPMs given,

    the resulting 1x Frequency values are 50 Hz for Tach 1 and 75 Hz for Tach2.

    Clicking the Default Tach column brings up a pull-down list which indicates the

    tachometer channels available for use as reference [for the currently displayed data].

    Tach Section of the Input Channels Tab

    Rotation  is the shaft’s rotation direction, either clockwise or counter-clockwise. The direction

    indicated is as viewed from the driver end of the machine train.

    Trig/Rev is the number of pulses per 360 degree revolution. (Default: 1) 

    Trig Dir is the “negative’ [down arrow] or “positive” [up arrow] direction of the moving shaft. 

    Trig Volt  defines the Tach pulse for tach signals. A keyway will generate a Negative Tach pulse.

    Typical Tach signals will generate at least a 1 V pulse. You can check the voltage value

    using a Time display.

    Mode Used to select one of three available modes: Voltage, Counter, or Period.Edge Detect Edge Detect  – Edge Detect is short for “Tach Pulse Edge Detection.” The term

     pertains to detecting the rising or falling edge of a tachometer pulse using either an

    “Immediate” or “Delayed” mode.

    Immediate Edge Detection (“Before Stable”) – “Immediate” is one of two EdgeDetect modes. The term is synonymous with “Before Stable.” If “Immediate” edge

    detection is selected a tach pulse will be recognized on any instantaneous measurement

    that meets the trigger level criteria. In this setup the “Delay Value” is the amount of time

     before the next tach pulse can be recognized. If a keyway is being used as a tach trigger

    you must calculate the minimum pulse width, based on the maximum RPM rate

    expected.Delayed Edge Detection (“After Stable”) – “Delayed” is one of two Edge Detect

    modes. The term is synonymous with “After Stable.” If “Delayed” edge detection isselected a tach pulse will be recognized when the measurement meets the trigger criteria

    for the specified duration. In this setup the “Delay Value” defines the length of time that

    the trigger criteria must be stable before the tach pulse will be recognized.

    Delay Time: One of several time settings between 500 ns and 25.5 ms. The delay time is used inconjunction with edge detect and is used to optimize noise reduction.

    4-6 Edit Menu 947394 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    35/94

    eZ-TOMAS 947394  Edit Menu 4-7

    Tachometer Notes 

    To Assign a

    Tachometer to a

    Channel

    1.   Navigate in eZ-TOMAS as follows: Edit [pull-down men] \ SetupConfiguration \ Input Channels Tab \ Default Tach column.

    2.  Click in the Default Tach column and select the desired tachometer from the pull-down list.

    To Assign

    Tachometers to

    the GaugeWindow View

    1.  Select “View” from the gage window’s tool bar.

    2.  From the resulting list, select the desired Tach, or select Default Tach. Notethat a Tach selection option will only be available if there are two or moretachometers to choose from.

    If you select a Tach, for example, Tach 1 – that Tachometer will apply to all

    applicable gauges, regardless of what tachometer is assigned to the channelin Setup Configuration.

    If you select “Default Tach,” Tachometers will apply to the gauges inaccordance with the Setup Configuration assignments, as described in row 1

    of this table, which describes how to assign a tachometer to a channel.

    To Edit a

    Tachometer

    Channel’s

    Parameters

    1.   Navigate in eZ-TOMAS as follows: Edit [pull-down menu] \ SetupConfiguration \ Input Channels tab.

    2.  Edit the parameters on a column by column basis, as desired. Note that thereare two places from which you can edit tachometer parameters:

    (a) The main area of the Input Channels tab. This is where you can edit the

    tachometer channel’s name, minimum and maximum gauge values, units,etc.

    (b) The lower panel of the Input Channels tab. From here you can configure

    the tachometer channel’s rotation (CW or CCW), trigger/revolution, triggerdirection (POS or NEG), and trigger voltage.

    For applicable illustrations of the channel configuration areas, refer to the

     preceding two figures.

    To obtain optimalnoise rejection 1.  Setup the input for Voltage Mode.2.  Take a measurement.

    3.  View the Tach Signal on a TimeWaveform plot.

    4.  Set the Trigger Slope [Trig Slope] to Positive (POS) or Negative (NEG).

    5.  Set Edge Detect to “Immediate” or “Delayed.” You may need to experimenwith Edge Detect settings to determine whether “Immediate” or “Delayed”

    works best for your application. Optimum settings will vary from machine

    to machine.

    6.  Set the Delay Time to a pre-set value between 500 ns and 25.5 ms. To haveno delay time select “none.”

  • 8/17/2019 TOMAS UsersManual

    36/94

    Synopsis o f Tach Modes

    When you connect a tach sensor to a tachometer designated connector, such as the ZonicBook/618E’s

    TACH BNCs (TACH1, TACH2, TACH3, or TACH4) you can select one of the following three modes:

    Counter, Period, or Voltage. If you connect a tachometer sensor to a direct Analog Signal Input channel

    (CH1 through CH8) then the tachometer signal will only be accepted in the Voltage Mode.

    If tachometer triggers will occur at a rate greater than or equal to the “scan rate

    divided by 10” then the Period Mode must be used.

    Counter Mode

    Use Counter Mode when Pulses perRevolution are needed.

    Counter Mode can be used for phaseshift observance.

    Counter Mode generates a Pulse of Amplitude “+1” for each tachtrigger. The counter mode can be used when the number of

     pulses is less than the scan rate divided by ten (< scan rate / 10).

    Once you have established the phase relationship of a machine

    running near optimum, the observance of phase shifts can be

    used to signal the development of a mechanical problem.

    Period Mode

    Use Period Mode when multiplepulses are involved, such as fromgear teeth.

    Period Mode cannot be used forphase shift observance. 

    The period is the time from the rising edge of one pulse to the

    rising edge of the next pulse, or the time from the falling edge of

    one pulse to the falling edge of the next pulse.

    The Period Mode is used for Tachometer inputs which exhibitmultiple pulses per revolution. The mode provides accurate

    overall RPM without sacrificing scan rate. Phase measurements

    are not possible when using period mode.

    Note: 60 seconds divided by the period [in seconds] equals RPM.

    Voltage Mode

    Use Voltage Mode when you need todetermine a trigger voltage. 

    Voltage Mode is used for Tachometer inputs to view actual input

    voltages from the Tach Sensor. Voltage mode is useful forlocating an ideal Tach Trigger Voltage setting. An ideal trigger

    voltage is one that is in a clean region of a leading edge. Note

    that Voltage Mode cannot be used for Phase measurements between Analog Inputs and Tachometer Inputs.

    If you connect a tachometer sensor to one of the 8 Analog Signal

    Input channels (CH1 through CH8) instead of a TACH channel,

    then the tachometer signal will only be accepted in the Voltage

    Mode.

    4-8 Edit Menu 947394 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    37/94

    Spectral Bands Tab

    Up to 10 Spectral Bands can be selected for each dynamic channel. The bands named Overall, DC Gap V,1x Amplitude and 1x Phase are pre-defined and cannot be modified. However, you can modify “User

    Defined” bands 5 through 10, customizing them for your specific application.

    Spectral Band values are displayed on the dynamic instrument gauges on the eZ-TOMAS main window.

    All gauges are vertical, with exception of circular phase gauges. When “1x Amplitude or 1x Phase is

    selected both a vertical gauge [for 1x Amplitude] and circular phase gauge [for 1x Phase] are displayed.

    Spectral Bands Tab

    Default Tach  Refers to the tach channels being used in the project. You must select the tach of

    interest.

    Channel Name  is the name you assigned to the input channel in the Channels Panel.

    Band is the Spectral Band Number of interest. Only the “User Defined” bands

    [5 through 10] can be modified.

    Spectral Band  is the name you assign to a spectral band. It is displayed on the dynamic instrument

    gauge in the main window.

    Freq Units  can be either Frequency or Orders. If you do not have a tach defined, the Orders

    option will not be available.

    Freq LO Freq HI

    Used to set the range of the frequency or order. It is a good practice to set the range2 to 4 spectral lines wider than the frequency of interest. This is due to the FFT

    window. For example, if your frequency of interest is the 3rd  order. You shouldspecify a range of 2.9 to 3.1 orders

    CALC  Specifies to calculate Peak, Overall, or Phase.

    Peak is the highest spectral amplitude within the specified range.Overall is the sum of vibrations of each spectral amplitude within the specified range.

    Phase is the time relationship between the vibration probe and tach signal.

    Amp LO

    Amp HI

    Used to set the low and high amplitudes. These high and low values define the gauge

    range.

    eZ-TOMAS 947394  Edit Menu 4-9

  • 8/17/2019 TOMAS UsersManual

    38/94

      Storage Tab

    Storage Tab

    Basic Description

    Data storage is activated by trigger events. If any one event is triggered, data from all channels is stored.

    Data storage events are triggered when a change occurs within the range of your defined parameters. An

    example follows the parameter definitions.

    Panel Description

    History FIFO Displays the number of storage records in the History FIFO (First-In-First-Out) file.Based on the configuration, values for both the required and the available disk space

    are shown. The panel includes a checkbox to enable backing up the project.

    RPM Range The range in which a specified RPM change and/or time change must occur to trigger

    data storage.RPM Change  An RPM-based trigger for the storage of data. Data will be stored when the machine

    speed changes by the specified RPM value. To enable the delta RPM storage trigger

    check the “Enabled” checkbox and enter an RPM value.

    Time Change  A time-based trigger for the storage of data. Enter the number of seconds, minutes,

    hours, or days between desired storage events. To enable the time-based triggercheck the “Enabled” checkbox.

    Overall Change  An amplitude-based trigger that can be defined for each channel. Data is stored whenthe overall amplitude changes by the specified value. The user must check the

    “Enabled” box for each channel that is to be used as an overall change trigger.

    User Snapshot Used to specify the duration of continuous data gathering (in seconds) for a datasnapshot. When the snapshot button is clicked [the button with the camera image],

    data will be collected for the specified duration.

    The history file is a FIFO file. You can define the depth of the history file; however, the amount of time

    needed to fill the file depends on the trigger event values. The smaller the trigger values, the faster thehistory file fills. The current data storage status is shown in the Main Window.

    4-10 Edit Menu 947394 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    39/94

    Example

    Assume that a motor typically runs at 3600 RPM and we would like to store data when the motor is running

    above 200 RPM and below 5000 RPM.

    1.  Open the Edit menu.

    2.  Select “Setup.” The Setup Configuration window will open.

    3.  Select “Storage Tab.”

    4.  For RPM Range enter a value of 5000 for the maximum and 200 for the minimum.

    5.  Set one or more of the following to trigger data storage:a) Time Change

     b) RPM Change

    c) Overall Change (the overall change in engineering units)

    For this example assume that Time Change and RPM Change were both set to “None” and the

    Overall Change trigger for a channel was set to set to 0.25 mils.

    6.  Click .

    With this configuration, data will be stored if . . . the motor’s speed is greater than 200 RPM and less

    than 5000 RPM and the overall value changes by 0.25 mils [since the last trigger event]. In this case

    eZ-TOMAS will store time waveform and spectral gauge (band) data for all channels. All event triggers

    are reset whenever any event trigger occurs.

    In other words:

    IF minRPM < Motor Speed < maxRPM

    AND IF {delta Time, OR delta Speed, OR delta EU = specified setting}THEN data is stored.

    eZ-TOMAS 947394  Edit Menu 4-11

  • 8/17/2019 TOMAS UsersManual

    40/94

    Limits

    The Limits Configuration window is accessed from the Edit pull-downmenu. The window provides the user with a means of setting limits and

    ranges via three main scenarios. These involve setting:

    Default Spectral Limits [without RPM ranges]

    (used for Acquisitions, or in Post Acquisition for reports) • 

    • 

    • 

    RPM Alarm Ranges and RPM Alarm Limits

    (used for Acquisitions, or in Post Acquisition for reports)  Selecting Limits from the Edit Pull-down MenuExcel Report Ranges and Delayed Limits

    ( Only used in Post Acquisition for reports) 

    The type of configuration is determined by radio button selection, as can be seen in the following pages.

    Up to two High (HI and HI-HI) and two Low (LO and LO-LO) limits can be defined for each channel’s

    operating condition. The graph colors are defined in the Display Preferences window. If the channel

    value is lower than the LO-LO limit, the bar graph will change to the color indicated in the LO-LO columnheader (see following figure). A value between LO-LO and LO limits will cause the bar graph color to

    change to the specified LO limit color. HI and HI-HI limits have the same effect, relative to channel value.

    A bar will be green for normal channel values (those between the LO and Hi limits.

     Partial Spectral Limits Panel Showing

    User-set Color Indications for LO-LO, LO, HI, and HI-HI

     Example of Limits Effects on the Gage Panel’s Color Bars

    4-12 Edit Menu 947394 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    41/94

     

    Gauges and Mouse-Clicks

    eZ-TOMAS 947394  Edit Menu 4-13

    Vertical Gauges Circular Phase Gauges

    “Right-Click” on an activelimit-pointer to bring up the

    Limit Configuration Window.

    “Right-Click” elsewhere in avertical gauge to bring up theInput Channels Tab [on theSetup ConfigurationWindow].

    “Left-Click and Hold” on alimit-pointer to drag it to anew position, thus setting anew limit value. 

    “Right-Click” within theconfines of a circularphase gauge to bring upthe Limit ConfigurationWindow.

    “Left-Click and Hold” on alimit-line to drag it to anew position, i.e., a newlimit angle.

     Addi tional Limit Configurat ion Aspects

    When a limit value is set to zero, the limit setting is turned off.

    In the Limits dialog you can choose to ignore the RPM limits feature by clicking the Use Defaults Spectral

     Limits option (see upper screen shot on next page), or you can click the Use Spectral Limits with RPM Ranges option and define an additional set of limits for each desired RPM range.

    Settings pertaining to the “Set Excel Report Ranges and Delayed Limits” have no effect on an acquisition.These settings only apply to Excel reports. Chapter 6 provides details.

    The following pages pertain to the following three bulleted scenarios:

    Default Spectral Limits [without RPM ranges](used for Acquisitions, or in Post Acquisition for reports) •

     

    • 

    • 

    RPM Alarm Ranges and RPM Alarm Limits

    (used for Acquisitions, or in Post Acquisition for reports) 

    Excel Report Ranges and Delayed Limits

    ( Only used in Post Acquisition for reports) 

    Each section shows the Limit Configurations window with the appropriate radio button selection. In eachcase a flow diagram is provided to allow the user to visualize the key configuration elements. Comparing

    the three methods to each other will improve your understanding of the Limit Configuration windows

    functionality.In each of the following cases, a spreadsheet representation of Spectral Band limits is visible for only 1

    input channel at a time. Note that a given channel can have several different sets of spectral limits and

    delays. For example, a different set for each tachometer; and when ranges are used, a different set of limitscan for each of 5 possible ranges and for each of up to 3 tachometers.

    Although Excel Report Ranges and Delays are set in the Limit Configurations window, it is from the XL

    Report window (discussed in chapter 6) that the setting options are selected for the report. Please refer tothat chapter for details.

  • 8/17/2019 TOMAS UsersManual

    42/94

     

    Using Default Spectral Limits [RPM Ranges not used]

    Note: In the above figure “Tach Channel(s) Tach Ref” is the same as “Default Tach.”

    4-14 Edit Menu 947394 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    43/94

    If the RPM Range option is selected [following figure] you can define up to 5 non-overlapping RPM

    ranges. There can be gaps in the user defined RPM ranges; however, the ranges may not overlap. For

    example: Range 1 can be assigned to cover 400 to 800 RPM, and Range 2 can be set to cover 900 to 1000RPM - ignoring speeds between 800 to 900 RPM. But you can't set Range 2 to cover 700 to 1000 RPM,

    as that overlaps the coverage in Range 1.

    When RPM ranges are used, there is a unique set of limit set-points for each combination of: Tach

    Channel, Input Channel, Range, and Spectral Band. For convenience, you may copy and paste limit

    settings between Channels.

    Limit values are not used if:(a) the ‘HiHi limit value’ minus the ‘LoLo limit value’ is less than 5% of the

    instrument scale, or

    (b) the limit value is outside of the instrument range.

    (c) the limit value is set to Zero.

    Limits from one channel can be copied to another from the Limit Configuration

    Window’s Edit pull-down menu, using the “Copy Channel” option, or by selecting

    multiple channels.

    Tach You may have up to three tachs per project.

    Select the Default Tach for the limits.

    Channel   Number of interest. Select the channel(s) of interest.

    Spectral Band  To which the limits should be applied. ( i.e. Overall, DC Gap, 1x Amp,

    1x Phase)

    HIHI, HI, LO, LOLO  Are Limits. Up to two High and two Low limits can be defined for each

    channel’s operating condition. Limit values are typed (entered) into theapplicable rows and columns. See previous figure.

    You can modify limits on the graphical bar graph display in the main window by

    dragging the limit arrows and then opening this window to save your changes. You may

    also right-click on a limit arrow to open the Limit's configuration dialog box. Note that

    right-clicking elsewhere on the bar will bring up the Setup Configuration Window.

    FIFO Records Is the number of Alarm events logged. When an alarm occurs, eZ-TOMASautomatically saves the data to the History FIFO file.

    RPM Range The RPM range as defined by the minimum and maximum RPM values of thelimit check. This RPM Range is the limit check range.

    An Example of Using Limit Ranges

    With exception of speed change transients, an experimental induction fan was designed to run at one of three normal

    operating speeds: 2,500 RPM at low speed; 7,500 RPM at medium speed, and 12,500 RPM at high speed. Anengineer wants to run limit checks for the medium and high speeds. More specifically, he wants to check Channel 2

    for a range of 5,001 to 10,000 RPM; and Channel 3 for a range of 10,001 to 15,000 RPM. Thus, he performs the

    following steps:

    1. Opens the Edit menu.

    2. Selects “Limits.” The Limit Configuration window opens.

    3. In the Limit Configuration window he:o  Selects the Use Spectral Limits with RPM Ranges option.

    o  Checks Channel 2 and Channel 3 to “ON.” (See following figure, upper screen image).

    o  Sets the limit check range for Channel 2 as follows: Min. RPM to 5,001; Max RPM to 10,000.

    o  Sets the limit check range for Channel 3 as follows: Min RPM to 10,001; Max RPM to 15,000.

    o  Un-checks all remaining channels to turn them “Off.”

    o  Clicks .

     Note that the following figure reflects these settings.

    eZ-TOMAS 947394  Edit Menu 4-15

  • 8/17/2019 TOMAS UsersManual

    44/94

     

    Setting RPM Alarm Ranges and Limits

    Note: In the above figure “Tach Channel(s) Tach Ref” is the same as “Default Tach.”

    4-16 Edit Menu 947394 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    45/94

     

    Setting Excel Report Ranges and Limits

    Note: In the above figure “Tach Channel(s) Tach Ref” is the same as “Default Tach.”

    eZ-TOMAS 947394  Edit Menu 4-17

  • 8/17/2019 TOMAS UsersManual

    46/94

    Digital I/O Conf iguration

    Hardware Panel

    The top panel of the Digital I/O Configuration Window is the Hardware panel (see following figure).

    To ensure proper output:

    (1) An NDTRelay must be connected as indicated in separate NDTRelay documentation.

    (2) The relay’s model number must be indicated in eZ-TOMAS’s Digital I/O

    Configuration window.

    (3) The applicable COM Port must be identified.

    Model Number: Select the applicable output relay module: NDTRelay1 or NDTRelay2.

    RS 232 COM Port: Select the COM (serial) Port to which the output Relay module is connected.

    Time (seconds)

    that the DigitalOutput is to be

     Act ive 

     Act ion Selec ted(from pull-downlist) for DigitalInput

    Sets the DigitalOutput’s NormalState to “ Opened”or “ Closed”

    Digital Inputis Selected

    Digital Outputis Selected

    Enable/DisableDigital I/O

     Alarm Event fo rDigital Output

     Digital I/O Configuration, Accessible from the Edit Pull-Down Menu (2 views)

    The panel below the Digital I/O Panel will be an Alarm Event panel for Digital Output channels, as indicated in theleft-hand image; and will be an Action Performed panel for Digital Input channels, as indicated in the right-handimage.

    Digital I/O Channels Panel

    The second panel of the Digital I/O Configuration window is the Digital I/O Channels panel. There are

    four Digital I/O channels, each of which can be configured for digital input or digital output. As seen in the

    above figure [which shows a Digital Output example on the left and a Digital Input example on the right].

    Each of the 4 channels has a Checkbox that is used to enable or disable the digital I/O function of the

    channel. A checkmark in the box indicates that the channel is active.

    • 

    • 

    • 

    The “DI / DO” column is used to select Digital Input or Digital Output. Clicking on the small

    schematic icon (in the column) toggles between the two options, i.e., Input and Output and displays an

    associated image. The arrow going into a connector represents Digital Input, the arrow leaving the

    connector represents Digital Output.

    The “NO / NC” column refers to the normal state of the Digital Output. The normal state can be set to

     be Normally Opened or Normally Closed on limit/alarm status. You can use up to four relays. A blue

    line, showing an open between two points is used for Normally Open. A red line, connecting two

     points, is used for Normally Closed.

    4-18 Edit Menu 947394 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    47/94

    eZ-TOMAS 947394  Edit Menu 4-19

    •  The DO Timer column refers to the time [in seconds] that the Digital Output is to be active. The DOTimer box will display “n/a” when Digital I/O is selected.

     Alarm Events Panel (Digital Output Only)

    The color of the response channel in the “Alarm Events” panel indicates the limit/alarm status that willcause the switch to change status, i.e., from Opened to Closed, or visa versa. Click on a channel number

    until the desired limit color is displayed. If the relay is normally Opened when monitored data causes the

    specified limit/alarm, the relay will change to Closed for the duration specified by the timer; then it willreturn to the normally Opened status.

     Note that you can have the system count the number of consecutive alarms and change the relay statuswhen that number of alarms is reached.

     Action Performed Panel (Digi tal Input Only)

    This panel consists of a pull-down list that allows you to select one of several “actions” for Digital Input

    applications.

    Possible actions are:

    •  Store Snapshot

    •  Change Acquisition State•  Change Limit Check State

    •  Increment Serial Number

    •  Increment Serial Number and Reset Peak Hold

    When you click the Save button, any of the unchecked check boxes for relay channels

    will close and stay closed until the condition is met for that relay channel. If you have

    something that will actuate when the channel closes, it will do so as soon as you click the

    Save button. 

  • 8/17/2019 TOMAS UsersManual

    48/94

    Display Preferences Window [in Edit Menu] 

     Display Preferences Window

    The Display Preferences Window provides a means of changing various display colors and other

     parameters, including, but not limited to, Waterfall latitude and longitude angles, and units for thefrequency axis. If a machine name is entered (upper-right text field), it will appear on the eZ-TOMAS

    main window, in the Machine Description region.

    Although most display preference functionality is self-explanatory, the following information may be

    useful to some.

    The Gauge Window Colors panel allows you to define the colors seen on themain EZ-TOMAS window. Gauge refers to the background color of the

    Analog Input Channel gauges. Tach is specific to the Tach Input Channelson the ZonicBook/618E.

    The Machine Information panel consists of a textbox for displaying the

    machine name, serial number, of some other identifying information.

    The Plot Window Colors panel allows you to define the Plot Display's

     border, background, and grid colors.

    The Display Buffer panel consists of a single numeric field for indicatingthe Realtime Trend. This value defines the amount time [in minutes] that

    data will be displayed before scrolling will begin. For example, if theRealtime Trend was set for 2 minutes the trend display would show the data

     being collected for two minutes, and then start scrolling after 2 minutes. In

    this example the screen will always display the most recent 2 minutes of

    data.

    4-20 Edit Menu 947394 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    49/94

     

     Display Preferences (continued)

    The Plot Trace Colors panel allows you to define colors for use

    in the plot displays. If you select "By Trace" the sequentialorder of the Trace Number will define the plot color. If you

    select "By Channel" colors will be assigned to specific

    channels according to the numbered color squares (see figureat left).

    The Alarms panel defines alarm colors for the Gauge and Plot displays. The

     panel includes two numeric fields. The upper field indicates the number of

    records to be displayed. The lower field, for Pre/Post Alarm Event, definesthe amount of data that will be displayed when using the Alarm Log report.

    The Waterfall Display panel is limited to a fixed number of spectrum traces,

    up to 100 traces. The Longitude Angle defines the vertical tilt of the display.

    The Latitude Angle defines the horizontal tilt.

    The Frequency Axis panel is used to set the frequency axis to Hz or CPM.

    Select Hz-Orders for cycles per second ; or select CPM-Orders for cycles

     per minute.

    The Bode Display panel allows for selecting “Unwrap Phase” by means of acheckbox. When the box is unchecked the phase plot will be "Wrapped."

    Wrapped means the Y-axis scale is 0 to 360 degrees. Data that straddles the

    0 / 360 boundary will show a vertical line.

    Unwrapped allows the Y-axis scale to span multiple 360 degrees. When

    “Unwrap Phase” is selected data will smoothly transition across the 0 / 360 boundary.

    The Main Cursor and Harmonic Cursors can be shown with or without a

    vertical line. Click on the first button [in the associated cursor panel, left

    figure] to toggle to the desired choice (line or no line). The second button in

    each panel allows you to choose a color for the associated cursor.

    The Orbit Display - Bearing Circle panel allows the user to select “ProbeLocation” or “X / Y Axis.” The selection defines the Bearing Circle on the

    Orbit display. If the bearing clearance is elliptical, select the locations that

    will be used to measure the clearance.

    eZ-TOMAS 947394  Edit Menu 4-21

  • 8/17/2019 TOMAS UsersManual

    50/94

     

    Copy Window

    “Copy Window” is not a window, but a command to copy the currently selected window to the clipboard.

    After using this command you can paste the copied window into another application, such as Microsoft

    Word or Excel. The feature is useful for creating reports, or sending screen images to others via e-mail.

    Load [or Remove] Graphic Picture

    The Load command places a selected graphic ( .bmp or .jpg format) into the Machine Description Window.

    The Remove command removes it.

    An alternative to using the command is to right-click  in the graphic region. You can then load the desired

    graphic file.  Right-clicking in this region also provides you with the option of removing an existing

    graphic.

    The title bar text is entered in the Display Preferences Window (accessed via the Edit pull-down menu.

    The lower text field information is entered directly into the field.

    Reset Peak Hold Values

    Momentarily resets the peak values. However, the new peak acquisition values [which exist from the point

    of reset] will immediately apply.

    4-22 Edit Menu 947394 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    51/94

    Display Menu . . . Plots 5

    Introduction …… 5-1

    Saving and Recalling Plot Setups …… 5-3

    Changing Display Ranges and Scales …… 5-4 

    “ Real Time” Plot Controls …… 5-5“ History Data” Plot Controls …… 5-5

    Channels …… 5-7

    Filtering Data …… 5-8

    Introduction

    The Display pull-down menu [following figure] provides a means of displaying plots and several types of

    logs, or reports. This chapter covers the Plots aspect. Chapter 6 pertains to the various logs (reports) that

    can be generated from the menu.

    Select Plots from the Display Pull-down Menu

    Selecting Plots from the Display pull-down menu opens a Data Display window. Note that you candouble-click on a gauge to open a Data Display window for plotting that gauge’s data.

    For real-time displays, you can halt and resume the display of data by using the Pause/Continue toggle button, or use the “P” key on the keyboard. When viewing historical data, you can use the five playback

     buttons and the slider to navigate through the data (see the following figure).

    You can view either real-time data or historical data. In the examples that follow we are view historicaldata, thus the History button has been clicked, and appears “active” [green] on our screen.

    Prior to viewing a plot you need to:

    select the channels to be displayed• 

    • 

    • • 

    select the desired data display format, e.g., Time Display, Spectrum, or Waterfall

    select the data source, i.e., a “Real Time” source, or a history data file.

    change the scale, if desired

     Reference Notes:

    For toolbar button functions refer to chapter 6.For examples of various plot display types refer to chapter 7.

    eZ-TOMAS 947294  Display Menu … Plots 5-1

  • 8/17/2019 TOMAS UsersManual

    52/94

    In the Window below the following is true:

    o  four Time Waveform plots are present

    o  the plot at the lower right has “focus,” thus the toolbars currently apply to that plot

    o  channels 1 and 2 have been selected for display in each of the plots

    o  from the first (top) toolbar button we can see that historical data is being used (the  button is active)

    o  from the second toolbar we can see that the Time Waveform display format is selected

    o  from the third toolbar we know that:- Auto Scale (magnifying glass) has been selected , instead of Instrument Scale or User Scale)

    - Cursor Display (9th button) is selected. This shows a plot cursor with annotation.

    - Cursor Update for Peak Search (11th button) is active

    - Overlay Bearing Clearance Circle (16th button) is active

     History Data – Time Waveforms

    Plot controls can be data that is in “Real Time” or pre-recorded, i.e., “History Data.” A different set of

    control buttons will be present depending on which mode you are using. In addition, Time Display andSpectrum Display formats differ in regard to certain control options.

     Reference Notes:

    For toolbar button functions refer to chapter 6.

    For examples of various plot display types refer to chapter 7.

    5-2 Display Menu … Plots 947294 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    53/94

     

    Saving and Recalling Plot Setups  

    You can save and recall plot setups. If you typically need to display data in a fixed format, this option can

    simplify the display setup process. After you can setup your plot displays, select the “Save Plot Setup” file

    menu option and save the setup. The next time you need to display data in that format, you can use the

    ”Recall Plot Setup” file menu option to quickly display data in that format.

     File Pull-down Menu with

    “Save Plot Setup” and “Recall Plot Setup” Options

     Preparing to Save a Plot Setup

     Preparing to Recall [Open] a Plot Setup 

    eZ-TOMAS 947294  Display Menu … Plots 5-3

  • 8/17/2019 TOMAS UsersManual

    54/94

    Changing Display Ranges and ScalesTo change the maximum or minimum range value (following figure): Left-click on

    upper or lower scale value that is to be changed, then enter the new value. An example follows. This technique works for

     both X and Y axis.

    In this example, the cursor and PC

    keyboard were used to change the

    maximum scale value from 3.000 volts

    to 3.800 volts.

    To change the X-Axis (following figures): Hold down the  key, at the same time, left-click and drag the mousecursor horizontally on the plot. Two vertical cursor lines will define the new x-axis end points.

    To change the Y-Axis (following figures):  Hold down the  key, at the same time, left-click and drag the mouse

    cursor vertically on the plot. Two horizontal cursor lines will define the new Y-axis end-points.

    To simultaneously change the X & Y Axes (following figures):  Hold down the  and keys, at the same time,left-click and drag the mouse cursor diagonally on the plot. A rectangle will define the new area of the plot.

    5-4 Display Menu … Plots 947294 eZ-TOMAS

  • 8/17/2019 TOMAS UsersManual

    55/94

    “ Real Time” Plot Controls

    “Real Time” is the default data source. For Real Time displays you can Halt and Resume the display of

    data by using the toggle button (see following figure). As an option to the  button you can use the “P” key on the PC’s keyboard. A table, which identifies all control buttons follows shortly.

    The  button, which looks like a black “X,”allows you to clear the data in

    the realtime trend displays. This display option can be used to clear the plot displays prior to starting atest.

    Pause/Continue 

    Clear Real TimePlot Buffer  

    SelectsRealTimeMode 

     Real Time Mode is Selected

    eZ-TOMAS 947294  Display Menu … Plots 5-5

    “ History Data” Plot Controls

    When viewing History Data (pre-recorded data files), you can use the set of playback buttons or the slider bar to navigate through the data. A table, which identifies all control buttons, is presented in chapter 6.

     Note that the playback buttons and slider remain hidden in the GUI when eZ-TOMAS is in the Real Time

    mode.

    History Data is accumulated according to the parameters setup in the Setup Configuration window’s

    Storage Tab, which is accessed via the Gauge Panel window’s Edit Menu.

    Data Source-History File 

    Play BackButtons

    History Data Playback UpdateSlider [Delay] Slider  

     History Data (Playback) Mode is Selected

    The playback buttons from left to right are: Rewind, Step backward one record, Play Backward, Stop, Play,and Step forward one record

     Note that you can drag the History Data Slider (at the right of the play buttons) to a specific area of the file

     before you start playing back the data.

    The Playback Update [Delay] Slider allows you to slow down (delay) the playback update. The delay value

    can be set to anywhere from 0 to 1000 milliseconds, in 200 millisecond increments.

  • 8/17/2019 TOMAS UsersManual

    56/94

    Alternate clicking on the button will toggle the History Data dialogue box on