AIR IONIZATION FOR ODOR CONTROL OPERATING INSTALLATIONS
Dennis Tulenko, REMRegistered Environmental Manager
National Registry of Environmental Professionals
Presented at the 2003 Joint Annual RMWEA/RMAWWA Conference
Casper, Wyoming
Trans-Tech Energy and Environmental, Inc.
9212 Highland Road
Pittsburgh, PA 15237
Phone: 412-366-9177
www.trans-tech.org
Albuquerque Convention Center
Albuquerque, New Mexico
April 29, 2002
50F5 Modular Ionizers
• Ionizer modules can be rack or flange mounted to fresh air inlet duct or recirculation plenum or duct
• Power consumption only 50 watts per module
• Oxygen present in air flow over tubes becomes bipolar - ionized and reactive
• Ionized air flows via HVAC air distribution ducts to building or enclosure
• No ozone produced.
And Ionization of VOCs Shown to be Effective
• Ammonia
• Acetic Acid
• Acetone
• Butyl Alcohol
• Carbon Monoxide
• Chloro Benzene
• Chloroform
• Dimethyl Disulfide
• Diethylamine
• Ethyl Cyanide
• Formaldehyde
• Hydrogen Sulfide
• Methane
• Methyl Mercaptans
• and many more ....
Heritage Lift Station San Jacinto River Authority The Woodlands, Texas 77380
• A very smelly lift station is positioned within a few feet of the property line of a $1M home
• End of pipe systems including chemical drum scrubbers and chemical spray systems did not solve the problem
• Trans-Tech custom designed and installed an air ionizer system with positive pressure air feed on April 2, 2001
• Within minutes the wet well exhaust was clean and odor free. Trans-Tech Energy and Environmental,
Inc.9212 Highland Road, Pittsburgh, PA 15237Phone: 412-366-9177 www.trans-tech.org PATENT PENDING
Waste Processing Room ApplicationsWaste Processing Room Applications
Inlet Air
Ionizers
Exhaust
Three Rivers, MI, Preliminary Treatment Building Air Ionization Retrofit Reznor air handling unitinlet hood to accept modular air ionizer units
Four 50F5 modules arerack mounted.
Ionized air flowenters room through air inlet ducts
FS200 ion levelcontroller controlsion level in room.Bipolar oxygen ionization eliminatesodor and reduces corrosion.
Denver MWRD Sludge Processing Building Basement Pre-design Demonstration Scale Pilot
46 PPM H2S
Aisles prior to ionization 5 PPM H2S Aisles after ionization 0 PPM H2S
Five (5) model 50F5 ionizer
modules installed in duct
Ionized air
Denver MWRD Sludge Processing Building Basement Pre-design Pilot
Pilot Ionization Plenum
Dump Zone 46 PPM H2S prior to Ionization Dump Zone 0-2 PPM H2S after ionization
Ionized air flow
MWRD Denver from Pilot to System Design and Installation
• 50F5 modular ionizers will be flange mounted to plenums
• Shown during construction is one (1) of two (2) twenty-four (24) module MWRD plenums
• Total treated volume includes the SPB Basement at 26,800 CFM (45,543 M3/Hr.) and Cake Storage Building at 16,700 CFM (28,373 M3/Hr.)
• MWRD ionization system coming on line September 2003.
Cost Comparisons Dewatering Buildings
Cost ($/CFM)
@12 AC/Hr.
10 PPM H2S
Trans-Tech Air Ionization
Biofilter Wet Chemical
Scrubber
Capital
($/CFM) 7 - 10 15 - 30 12 - 15
O&M
($/CFM)0.5 - 1.0 1.0 – 2.0 5.0 – 10.0
CONCLUSIONS
• Bipolar air ionization provides a simple and cost effective odor control solution
• Added value includes corrosion control, health and safety advantages
• Recommendation: Do not allow simplicity of concept to be misinterpreted as lack of need for thoughtful system design and engineering.
• Total costs - capital plus O&M are less than “end of pipe” odor control system alternatives.