UDC 697.9
SFB (57.9) X
Features- Certified to Current test standards BS EN 1366-2
- Fully tested and CE marked and compliant
- Galvanised or stainless interlocking double skin blades
- Stainless steel frame side seals
- 4 modes of operation
- Connections to suit most proprietary ductwork
- Extensive range of supporting controls
DUCTGARDDuct Mounting Smoke and Fire Control Dampers
Dampers 1 JAN 2015
Gilberts Ductgard presents an
‘engineered’ range of combined
smoke and fire dampers
suitable for use in all types of
HVAC ductwork. Benefitting
from over 50 years of
engineering
experience in the industry
considerable ingenuity has
been applied in the design and
construction of this product to
produce a damper of high
efficiency, reliability, durability
and ease of use.
Ductgard has been tested to
the latest BS-EN1366-2 fire
test standard and includes
mandatory CE marking.
I N T R O D U C T I O N
The Gilbert’s 2014 Ductgard
presents a re-engineered range of
combined fire and smoke dampers
suitable for use in HVAC ductwork
systems.
Developed from a well proven
heritage of tried and tested damper
designs, considerable ingenuity and
manufacturing expertise has been
applied to produce a robust,
effective, competitive unit that is
easy to install and maintain.
The unit is designed to fit within all
types of ductwork at its junction with
a fire barrier wall, where it can be
fixed directly in or immediately
adjacent to the building structure in
both the horizontal and vertical
positions.
With a choice of 4 different modes
of operation all units are fully
automatic and motorised.
All units comprise of an air-tight
galvanised casing (DW144 Class
C Specification) with stainless steel
interlocking blades and frame side
seals, which provides a four-hour
fire rated assembly. Sizes range
from 200 x 200 upto a maximum of
1000 x 1000 in one unit.
Dampers over this size are supplied
in multiple units.
Mode Description Page
9A Fully automatic opening operating on 24v with failsafe spring 4
return closure via 72˚c electro thermal link release
9B Fully automatic opening operating on 230v with failsafe spring 4
return closure via 72˚c electro thermal link release
10A Fully automatic closure operating on 24v with failsafe spring 4
return opening via 72˚c electro thermal link release
10B Fully automatic closure operating on 230v with failsafe spring 4
return opening via 72˚c electro thermal link release
Control Mode Options
DescriptionMode 9 provides a fully automatic type of smoke and fire
damper that operates on the basis of fail safe closure with
automatic reset. It has been designed to close in smoke and
fire conditions upon a failure of the supply voltage to the
motor or in the event of an electro thermal fusible link
separating at a pre-determined temperature (72°C standard).
Volt free microswitches are included as standard.
OperationMode 9 is fitted with a spring return square drive motor which
will hold the damper open for as long, as the supply voltage
is available. Interruption of this supply will cause controlled
damper closure by way of the motors spring return operation.
In addition however, the damper is fitted with an electro
thermal fusible link which will fail at a pre-determined
temperature (72°C standard) and close the damper
irrespective of the status of the motor.
An integral test pushbutton on the electro thermal fuse
housing allows for the local testing of the damper operation.
Motor Voltage Control OptionsMode A: 24V AC or DC supply.
Mode B: 230V AC supply.
Note: All options include position microswitches as standard.
Re-set ProcedureProvided the fusible link is intact the damper will
automatically reset after an interruption of the supply voltage
to the motor. The motor will take
approximately 80 seconds to open the damper.
The spring return motor and terminal box (if fitted) are
mounted on the ductwork connection sleeve. Fully
assembled prior to despatch they
require only the external electrical connections to be made.
4
DUCTGARDDuct Mounting Smoke and Fire Control Dampers
Mode 9
DescriptionMode 10 performs in exactly the same manner as the Mode
9 except that the operation is reversed and the units are fail
safe open. The motor sets the unit in the full closed position
and the unit will only open in the event of an interruption of
the supply voltage to the motor or separation of the thermal
fusible link.
Mode 10
Duct Height/Dia. 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
Dimension ‘A’ 84 109 84 159 184 159 184 259 284 259 284 359 384 359 384 459 484 459 484
Dimensional Data
Square/Rectangular
Spigot Connection
* Allow extra 50mm
for cables
Dimension ‘A’
E
90 40DUCT WIDTH - 4mm
(100 to 1000) 40
40
DU
CT
HE
IGH
T -
4m
m(1
00
to
10
00
)4
0
AL
LO
W F
OR
AC
TU
AT
OR
RE
MO
VA
L
50
25
39 120 39
VARYING LENGTHS OF OPTIONAL STUB DUCT AVAILABLE210MM TO 450MM. PLEASE REFER TO SALES OFFICE
194
19
8*
19
8*
336*
Dim
en
sio
n ‘
A’
Se
e T
ab
le
39
DUCT DIAMETER - 3mm(100 to 1000)
39
DU
CT
DIA
ME
TE
R -
3m
m(1
00
to
10
00
)3
9
16
90 39A
LL
OW
FO
R A
CT
UA
TO
R R
EM
OV
AL
50
16 16
16
B 41 120
194
41 B
336*
19
8*
19
8*
Dim
en
sio
n ‘
A’
Se
e T
ab
le
16
38
Circular Spigot
Connection
* Allow extra 50mm
for cables
B Dimension:
Up to 350mm dia = 41mm
Over 350mm dia = 55mm
Damper Handing
Right hand motor positioning
(as shown) as standard
5
6
DUCTGARDDuct Mounting Smoke and Fire Control Dampers
InstallationFrame(HEVAC)Ref. IF
DUCT WIDTH OR DIA. + 136mm
DU
CT
HE
IGH
T O
R D
IA.
+ 1
36
mm
285*
CONNECTING DUCTWORK BY OTHERS
Sleeve with AngleRef. SF
40 40 40O 12mm HOLE FOR DROP RO
Drop RodCleatsRef. DF
35
120
Angle FrameRef. AF
3413134
50 50
50
50
1818
DUCT WIDTH or DIA. + 225
DU
CT
HE
IGH
T O
R D
IA.
+ 1
98
mm
60
60
DIMENSION = X + 25mm DIMENSION = X
CENTRE LINE OF DUCT
6085
DU
CT
HE
IGH
T O
R D
IA.
+ 8
1m
m
DU
CT
HE
IGH
T O
R D
IA.
+1
61
mm
DUCT WIDTH OR DIA. + 189
DUCT WIDTH OR DIA. + 109
DIMENSION = X + 25mm DIMENSION = X
CENTRE LINE OF DUCT
* Suitable for walls
up to 200mm.
Above this thickness
refer to our technical
sales office.
Installation Dimensional Data
SLEEVE
ANGLES
7
Concrete/masonry floor with HEVAC frame (Ref...IF)Single section sizes (mm):100 x 100 to 1000 x 1000
Tested to BS EN 1366-2 for 4 hoursEquivalent to BS EN 13501-3 classification: ES240 (E240s)BS EN 1366-2 test/assessment references: 216413/cc 254958/cc 261450Meets the requirements of BS 476-20/22 - refer BS 476-10.6.6.3
FRAME POSITIONED CENTRALLYOR THE CENTRE TO BE AT LEAST50MM AWAY FROM NEARESTWALL FACE
MORTAR OR CONCRETE BACK FILL
BUILDING TIES
SOLID FLOOR
Block/masonry wallwith HEVAC frame (Ref...IF)Single section sizes (mm):100 x 100 to 1000 x 1000
Tested to BS EN 1366-2 for 4 hoursEquivalent to BS EN 13501-3 classification: ES240 (E240S)BS EN 1366-2 test/assessment references: 256538/CC 261450Meets the requirements of BS 476-20/22 - refer BS 476-10.6.6.3
BLOCK WALL
FRAME POSITIONED CENTRALLY ORTHE CENTRE TO BE AT LEAST 50MMAWAY FROM NEAREST WALL FACE
MIN. 150MM
BUILDING TIES
MORTAR OR CONCRETE BACK FILL
M1
M2
M3
MIN
. 150M
M
Installation Methods
Tested to BS EN 1366-2 for 4 hoursEquivalent to BS EN 13501-3 classification: ES240 (E240S)BS EN 1366-2 test/assessment references: 256538/CC 261450Meets the requirements of BS 476-20/22 - refer BS 476-10.6.6.3
Ductgard can be installed in a wide variety of approved ways using thedifferent installation options detailed on page 6. Please remember that onlythe installation methods detailed are tested and approved to EN1366-2.If your installation varies from these options you will need to confirm
approval with Building Control. Manufacturers are not able to approvealternative installation methods.
Block/masonry wall with sleeve & angles (Ref...SF)Single section sizes (mm):100 x 100 to 1000 x 1000
ALL R
OU
ND
GA
P 5
MM
8
DUCTGARDDuct Mounting Smoke and Fire Control Dampers
Dry wall with sleeve & angles (Ref...SF)Single section sizes (mm):100 x 100 to 1000 x 1000
Tested to BS EN 1366-2 for 4 hoursEquivalent to BS EN 13501-3 classification: ES240 (E240S)BS EN 1366-2 test/assessment references: 256538/CC 261450Meets the requirements of BS 476-20/22 - refer BS 476-10.6.6.3
Dry wall with drop rod cleats (Ref...DF)Single section sizes (mm):100 x 100 to 1000 x 1000
Tested to BS EN 1366-2 for 4 hoursEquivalent to BS EN 13501-3 classification: ES240 (E240S)BS EN 1366-2 test/assessment references: 256538/CC 261450Meets the requirements of BS 476-20/22 - refer BS 476-10.6.6.3
M10 DROP RODS
OPENING LINED WITH TRACKAND BOARD
STONE WOOL
TYPE 5 PLASTERBOARD
OPENING LINED WITH TRACKAND BOARD
M5
M6
M9
ALL R
OU
ND
GA
P 5
MM TYPE 5 PLASTERBOARD
SLEEVE
ANGLES
MIN. 100MMMAX. 200MM
STONE WOOL
OPENING LINED WITH TRACKAND BOARD
STONE WOOL
MIN. 100MMMAX. 200MM
FLANGE SCREWED TO TRACK
TYPE 5 PLASTERBOARD
Dry wall - with angleframe (Ref...AF)Single section sizes (mm):-100 x 100 to 1200 x 1200
Tested to BS EN 1366-2 for 4 hoursEquivalent to BS EN 13501-3 classification: ES240 (E240s)BS EN 1366-2 test/assessment references: 216413/cc 254958/cc 261450Meets the requirements of BS 476-20/22 - refer BS 476-10.6.6.3
9
CLAMPBRACKET
REVERSE MOUNTEDTRANSFER DRIVE
M6 BOLTS & WASHERS (X4)
ACTUATOR WITH FIXINGBRACKET SUB ASSEMBLY
Reverse Mounted
Actuator Clamping
Kit
439.5
195.5 145
50MM FORCABLE
268
40 DUCT WIDTH - 4MM 40
40
40
DU
CT
HE
IGH
T -
4M
M
25.5
105
565
195.5 270.5
Standard Position
Alternative
Position 1
Alternative
Position 2
145
198
50MM FORCABLE
268
439.5
195.5 145
19
8
50MM FORCABLE
268
19
8
* If your proposed installation method has minor variations to that shown, please confirm acceptance with the local BuildingControl Authority (BCA) before proceeding. Manufacturers are not able to "approve" specific installation methods.
Actuator - Inboard Mounting OptionThe actuator is normally fitted to the outside face of the motor mountingbracket. Where limited clearence or other factors dictate it is posible to
move the motor to an inboard position. The motor can also be rotated intothree alternative positions either on site or in the factory.
WiringDiagrams
All ModesAddressable
Mode 9 and 10 Ductgards are normally controlled, by a remote switch on the Motor Supply.
Note: To interface with Gilberts remote indicators it is easier to switch the negative rather than the positive.
Mode 9 and 10 Ductgards in this option are interfaced with our Gardex Controller as described on Page 11. Motorised
dampers are fitted with the Belimo BLF-T range as standard. Other actuators are available upon request.
1 2
- +
M
Control Option A
1 2
- +
M
Control Option B
S1 S2 S3 S4 S5 S6
5° 80°
S1 S2 S3 S4 S5 S6
5° 80°
L N E
M
N L 1 2 3 4 5 6 + + - - S S
1 2 3 4 5 6
2 Core ScreenedCommunication Cable
Belimo Damper Motor
DCM Damper Control Module
240V 50HZFused Spur(option 24V DC)
24 V WIRING DIAGRAM
Power Supply 24V AC +-20%
50/60 Hz
24V DC +-20%
Current Rating 380mA AC max
POWER CONSUMPTION
Opening 5 watts
Holding 2.5 watts
S1 - S2 made when damper
closes
S4 - S6 made when damper
open
240V WIRING DIAGRAM
Power Supply 240V AC +15% -10%
50/60 Hz
240V AC +10% 50Hz
Current Rating 200mA AC max
POWER CONSUMPTION
Opening approx 6 watts
Holding approx 3 watts
10
DUCTGARDDuct Mounting Smoke and Fire Control Dampers
11
ControlSystems
Gilberts offer a wide choice of hard wired and multiplex controlled systems to meet the challenge of effective fire and
smoke control monitoring.
Available as stand alone, or suitable for interfacing or incorporating with building management or fire/smoke control
systems designs, the range includes four simple off the shelf packages through to bespoke designs to satisfy the most
demanding criteria.
Gardex (Modes 9/10 Options Only) Multiplex SystemThe Gardex system has been designed to reduce the cost of electrical wiring installations and satisfy the most complex of
control changes. Up to 126 dampers can share the same 2 wire communication line to transmit information to and from the
central controller.
Features
Housing - Metal wall mounted enclosure complete with a clear hinged lockable front cover and lower cabling
chamber. Protection rating IP55
Keyboard and Display - Directory command programming via arrow keys and 2 line x 40 character LCD display are
provided as an operator interface.
Fault reporting - Faults are identified on the LCD display and the controller can be interrogated to determine the
nature of the fault and its location.
TYPICAL OPTIONAL FEATURES
- MIMIC AND DAMPER STATUS INDICATOR LIGHTS
- INTEGRAL FIREMANS INTERFACE SWITCH
- MECHANICAL FAN CONTROL
- LINE ISOLATION
- REMOTE ALARM INTERFACE
Field Stations (DCM)Available as an integral part of the damper, or as a
separate enclosure, the addressable module has been
designed to provide independent operation of individual
or groups of dampers in accordance with a pre-
programmed logic sequence of events.
Individual dampers are controlled and have there status
constantly monitored by the module in response to
signals from the pre-programmed controller. Maximum
length of communications 2km. In the event of
communications failure dampers assume failsafe
position.
These are available in a number of configurations and are
designed and manufactured to suit individual specific
requirements. The electro-mechanical control/monitoring
panels are based on IP55 wall mounting enclosures, which
can be provided to include such features as:
- FIREMANS/BMS INTERFACE
- MULTI ZONE CONTROL & DAMPER STATUS
INDICATIONS
- UPS
- VOLT FREE CONTROLS FOR REMOTE
INDICATION OR ALARM
GardexController
DamperIndicator
DamperIndicatorExpander
400mm
500m
m
Bottom Entry GlandPlate 300x90mm (approx)
CENTRAL CONTROLLER
PROGRAMRESET
ACKNOWLEDGE
POWER ON
SYSTEM FAULT
LAMP TEST
FIRE COMMAND
FAULTACKNOWLEDGED
SMOKE DAMPER STATUS INDICATION
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
SMOKE DAMPER STATUS INDICATION
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
SMOKE DAMPER STATUS INDICATION
41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60
SMOKE DAMPER STATUS INDICATION
61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80
Please contact Head Office to discuss specific requirements.
BespokeControlPanels
AncillaryItems
Gilberts range of ancillary Items have been designed for use in conjunction with both the Ductgard and Smokegard models.
Purpose built for straightforward connection and compatibility they offer a number of useful services.
Remote Indicators/Master MonitorsGilberts remote indicator panels can be linked to
damper Modes 5 and 6 and will provide remote
indication of the status of one or more dampers.
Ref:- RT1 (1 damper)
MM1-12 (upto 12 dampers)
Larger Panels available upon request
Standard Power SupplyStandard power supplies are available in two
sizes to suit up to 6 or up to 12 dampers. They
provide conversion from 240v AC input to a
smooth and stabilised 24v DC output.
Ref:- G6 = 6 UNIT OUTPUT
G12 = 12 UNIT OUTPUT
G6R = 6 UNIT OUTPUT + RELAY
G12R = 12 UNIT OUTPUT + RELAY
Uninterruptible Power SupplyUninterruptible power supplies operating on a
240v AC input provide a smooth 24v DC output to
power up to 12 dampers. Unlike standard power
supplies however, in the event of a power failure,
there will be an automatic changeover to in-built
batteries without tripping the dampers providing
continued power for a period of up to 1 hour.
Ref:- UPS6 = 6 UNIT OUTPUT
UPS12 = 12 UNIT OUTPUT
UPS6R = 6 UNIT OUTPUT + RELAY
UPS12R = 12 UNIT OUTPUT + RELAY
Smoke DetectorsSmoke Detectors are available for in duct or ceiling mounting and can link directly into Modes
5 & 6 or the output relay of the Power Supply units. Detectors are 24v DC Ionisation type
Ref: In-duct 4 wire - SD3
4 wire - SD2
RED LIGHT
SYSTEM TRIPPED
GREEN LIGHT
SYSTEM SET
UNIT No.
AIIFA No.
OUTLINE OF PCB
NOTE: When damper is open yellow is +VE
When damper is closed blue is +VE
O
R
G
YE
LLO
W
BL
UE -V
E D
C
FROM
DUCTGARD
100m
m
76mm 35mm
240mm
240mm
87mm
POWER SUPPLY
UNITTYPE G12
MAINS INPUT 240 V.A.C.l
OUTPUT TO DAMPER 24 V.A.C.l
WARNING - ISOLATE
MAINS SUPPLY BEFORE
ENTERING
E
N
L
MAIN POWER SUPPLY
240v AC
24v DC POWER OUT
240mm
350mm
87mm
UNINTERUPTABLE
POWER SUPPLY
CELLS:- 27.6v DC MAX: TEST YEARLY
MAINS INPUT: 240v AC
OUTPUT TO DAMPERS 24v DC
ON
ON
THIS UNIT IS DESIGNED TO SUPPLY UP
TO 12 DAMPERS FOR UP TO 1 HOURTHE INTERNAL DRY-FIT CELLS DO NOT REQUIRE SERVICE OR
ELECTROLYTE LEVEL TOPPING-UP. WARNING: TAKE CARE WHEN
INSIDE THIS UNIT CELLS GIVE 100+ AMPS IF SHORTED OUT
E
N
L
MAIN POWER SUPPLY
240v AC
24v DC POWER OUT
Master MonitorA more advanced form of remote indication is
available with a master monitor. This unit
provides remote indication for the status of up to
12 individual dampers.
Ref:- MM1-12*
* dependant on number of dampers on the
system
Master Monitor
UP TO 12 PCBs IN 1
MASTER MONITOR
NOTE: When damper is open yellow is +VE
When damper is closed blue is +VE
FROM
DUCTGARD
YE
LLO
W
BLU
E -VE
DC
O
R
G
O
R
G
240mm
240m
m
87mm
12
DUCTGARDDuct Mounting Smoke and Fire Control Dampers
13
Test Data
Velocity (m/s)
Pressure Drop BSRIA Report 15633/1
Calculated performance at various damper settings
Size tested: 500mm x 600mm
25%
OP
EN
50%
OP
EN
75%
OP
EN
100%
OP
EN
1000
100
10
1
Pre
ssure
Dro
p (
Pa)
0.01 0.1 1 10
100
Weight Chart (kg approx.)
Square/Rectangular Spigot
Height
(mm)
Width (mm)
100 200 300 400 500 600 700 800 900 1000
7.8 9.0 9.8 10.8 11.9 13.2 14.3 15.4 16.5 17.7
9.0 10.5 11.3 12.4 13.6 15.4 16.7 18.1 19.4 20.7
10.3 11.9 12.8 14.1 15.4 17.7 19.3 20.8 22.4 23.9
11.6 13.4 14.4 15.8 17.3 20.0 21.8 23.6 25.4 27.2
12.9 14.9 16.0 17.6 19.1 22.3 24.3 26.4 28.4 30.4
14.2 16.3 17.6 19.3 21.0 24.6 26.9 29.1 31.4 33.6
15.5 17.8 19.1 21.0 22.8 26.9 29.4 31.9 34.3 36.8
16.8 19.3 20.7 22.7 24.6 29.3 31.9 34.6 37.3 40.0
18.1 20.8 22.3 24.4 26.5 31.6 34.5 37.4 40.3 43.2
19.4 22.3 23.9 26.1 28.3 33.9 37.0 40.2 43.3 46.4
To include a HEVAC/ HVCA Installation Frame, apply the following multiplier: 1.4
100
200
300
400
500
600
700
800
900
1000
Weight Chart (kg approx.)
Circular Spigot
Weight (kg)
30.0
33.2
36.0
39.5
42.5
46.3
49.6
53.6
57.1
Dia. (mm
600
650
700
750
800
850
900
950
1000
Weight (kg)
8.4
9.8
11.8
13.4
15.1
17.2
19.1
21.3
23.4
25.8
Dia. (mm
100
150
200
250
300
350
400
450
500
550
Casing Leakage
Ductgard was tested and found to meet Class ‘C’ Classification BS
EN 1751:1999. Leakage recorded at less than 0.1l/s/m² at 2000 Pa
Class C
(BS EN
1751)
Leakage (m3/hr/m2)
Blade Leakage
100mm x 100mm (smallest) unit as tested to BS EN 1366-2
1000mm x 1000mm (largest) unit as tested to BS EN 1366-2
10 50 100 200 1000
500
300
100
Pre
ssure
Dro
p (
Pa)
Leakage (l/s/m2)
Blade Leakage
for a 500mm square Damper
500mm x 500mm unit as tested to BS EN 1366-2
5 50
1000
100
10
0
Duct
Pre
ssure
(P
a)
EN1751 Class 3
EN1751 Class 2
EN1751 Class 1
Tested Result
Operation &MaintenanceInstructions
Operating and Maintenance
InstructionsAll Ductgard units are tested before
leaving the factory but should be test
operated prior to commissioning to
ensure correct operation. Quick and
easy testing and reset procedures for
each operational mode are detailed on
their respective data pages in this
brochure. In addition to their initial test
however, being a fire safety product, it
is also recommended that the units are
test operated regularly thereafter . Test
frequency will depend upon the damper
environment but, in the absence of any
other information, a maximum interval
of 6 months is recommended. In
addition an annual visual inspection is
also advisable to permit cleaning and
removal of any airborne contaminants
which may affect the dampers
operation.
Note
For safety the damper blades should be
closed on modes 9 and open on modes
10, before personally approaching them
for inspection/cleaning.
Since the drive, linkage, motors and
electronic components on the ductgard
units are ‘sealed for life’ there should
be no requirement for periodic
maintenance and spares are not
normally required. Items such as reset
levers and test keys however can be
misplaced over time. In this event
replacements are readily available
from Head Office.
Trouble-Shooting
GilbertsDamper,Smoke andFireControlRange
All Ductgard units are both inspected and tested before leaving our premises. Manufactured using maintenance free ‘sealed
for life’ components there is no reason why they should not reach site in full working order and continue to function when
installed providing that our fitting and wiring instructions have been adhered to. In the event of operational difficulties please
contact our Head Office for on-line guidance and advice.
Telephone: (01253) 766911
Ductgard units carry a full 1 year warranty from the date of delivery for all parts and labour.
Smokegard
Door, Wall and Partition
Mounted Smoke and Fire
Dampers
Series 54
Smoke Evacuation Damper
Firegard
Curtain Fire Dampers
Airgard
Volume Control
Dampers
Series RD
Iris Duct Damper
14
DUCTGARDDuct Mounting Smoke and Fire Control Dampers
15
Declaration of Performance: Ductgard Range
1. Unique identification code of the product-type:
DUCTGARD fire damper (see table below for specific damper installation type) To be used in
conjunction with walls/partitions/floors to maintain fire compartments in heating, ventilating and
air conditioning Installations
2. Name, registered trade name or registered trade mark and contact address of the manufacturer as required under
Article 11(5):
Gilberts (Blackpool) Ltd, Clifton Road, Blackpool, FY4 4QT
3. System or systems of assessment and verification of constancy of performance of the construction product as set
out in CPR, Annex V:
System 1
4. In case of the declaration of performance concerning a construction product covered by a harmonized standard:
BRE Global Ltd (notified body 0832) performed the determination of the product type on the
basis of type testing (including sampling), type calculation, tabulated values or descriptive
documentation of the product, the initial inspection of the manufacturing plant and of factory
production control and continuous surveillance, assessment and evaluation of factory
production control under system 1 and issued the certificate of constancy of performance of the
factory production control ( certificate number-CPR-P0010).
5. Declared performance according to:
EN 15650 (Ventilation for Buildings — Fire Dampers)
Fire resistance according to EN 1366-2 and Classification according to EN 13501.3 and Harmonised Technical
specification to EN 15650:2010:
Range Type Supporting Construction Document Ref Classification
100x100mm - 1000x1000mm DUC/IF Blockwork Wall 287719F E240 (ve i -> o) S
100x100mm - 1000x1000mm DUC/SF Dry Wall 287719A E120 (ve i -> o) S
100x100mm - 1000x1000mm DUC/DF Dry Wall 287719B E120 (ve i -> o) S
100x100mm - 1200x1200mm DUC/AF Dry Wall 287719C E120 (ve i -<> o) S
100x100mm - 1000x1000mm DUC (No Frame) Dry Wall 287719E E120 (ve i -> o) S
Nominal activation conditions/sensitivity according to ISO 10294-4:
- sensing element load bearing capacity Pass
- sensing element response tine Pass
Response delay (response time) according to EN 1366-2:
- closure time 50 Cycles Pass
Operational reliability according to EN 1366-2:
- cycling Pass
Durability of response delay according to EN 1366-2:
- sensing element response temperature and load bearing capacity Pass
Durability of operational reliability according to EN 15650:
- open and closing cycle 10.000 cycles Pass
OrderingSpecification
SERIES:
SIZE (mm width x Height or Dia)
FIXING OPTION
Installation Frame (HEVAC)....IF
Sleeve and Angle...SF
Drop Rod...DF
Angle Frame...AF
STANDARD POWER SUPPLIES:
6 Way.....................................................................G6
6 Way c/w output relay...........................................G6R
12 Way...................................................................G12
12 Way c/w/ output relay........................................G12R
REMOTE INDICATORS:
Single unit.........................................................SR1
SMOKE DETECTORS:
24V DC wire ionisation......................................SD2
MASTER MONITOR:
1 - 12 unit..........................................................SMM1 -12
plus per damper
UNINTERRUPTIBLEPOWER SUPPLIES:
6 Way.....................................................................UPS6
6 Way c/w output relay...........................................UPS6R
12 Way...................................................................UPS12
12 Way c/w/ output relay........................................UPS12R
TYPE:
Square/Rectangular:..............S
Circular...................................C
CONTROL OPTION
A or B
MODE
9 or 10
NUMBER REQUIRED
DUC 450 x 200 A 159 FC/NCS
SpecificationFire and smoke dampers shall be
LPCB certificated and pass the test
requirements stated in EN 1366-2 with
an ES classification to EN 13501-3.
Dampers to be fitted with an actuator
that can respond to a smoke alarm
signal to ensure closure at the first sign
of smoke.
Motors Dampers to be motor operated with a
failsafe thermal fuse set to operate at
72°C. The damper will close (or open)
in less than 30 seconds.
Damper Blades & LinkageDampers to have opposed blade
operation with interlocking double
skinned blades on robust 19mm
spindles for both resistance to fire and
daily airflow exposure. The drive
linkage shall be fully enclosed and set
outside of the air stream for protection
against damage and air contamination.
CasingStainless steel gaskets shall be
provided at the top, bottom and sides to
reduce casing leakage to below the
levels stated in EN 1366-2. Damper
casings shall be fully welded to meet
the air tightness test requirements of
HVCA specification DW144 to classes
A, B and C at up to 1500Pa.
ApprovalsThe fire and smoke damper shall
have a tested or assessed installation
method that matches the requirement
of the supporting construction into
which it is built.
DUCTGARDDuct Mounting Smoke and Fire Control Dampers
Gilberts (Blackpool) Ltd reserve the right to alter the specification without notice. The information contained in this leaflet is correct at time of going to press © 2015.For our latest product data please visit www.gilbertsblackpool.com.