Table of Contents · Switch Symbols Switch symbols are also used to indicate an open or closed path...
Transcript of Table of Contents · Switch Symbols Switch symbols are also used to indicate an open or closed path...
1
Table of Contents
Introduction ............................................................................. 2
Control Circuits........................................................................ 4
Electrical Symbols ................................................................... 6
Line Diagrams ....................................................................... 16
Overload Protection ............................................................... 22
Overload Relays .................................................................... 26
Manual Control ...................................................................... 34
Magnetic Contactors and Starters ......................................... 41
Starter Ratings ....................................................................... 46
Furnas INNOVA PLUS Starters .............................................. 49
ESP100 Starters .................................................................... 50
Sirius Type 3R Starters ........................................................... 51
World Series Type 3TF Starters .............................................. 53
Multi-Speed and Reversing Starters ...................................... 55
Reduced-Voltage Starting ...................................................... 59
Pilot Devices ......................................................................... 64
Control Transformers .............................................................. 75
Control Relays ....................................................................... 76
Timing Relays ........................................................................ 83
Limit Switches ...................................................................... 88
Pressure Switches ................................................................ 92
Photoelectric Control ............................................................. 95
Inductive Proximity Switches .............................................. 101
Capacitive Proximity Switches ............................................ 106
Ultrasonic Sensors .............................................................. 109
LOGO! Logic Module ........................................................... 111
Review Answers .................................................................. 114
Final Exam ............................................................................ 115
2
Introduction
Welcome to another course in the STEP 2000 series, SiemensTechnical Education Program, designed to prepare ourdistributors to sell Siemens Energy & Automation productsmore effectively. This course covers Basics of ControlComponents and related products.
Upon completion of Basics of Control Components you willbe able to:
� State the purpose and general principles of controlcomponents and circuits
� State the difference between manual and automaticcontrol operation
� Identify various symbols which represent controlcomponents
� Read a basic line diagram
� Describe the construction and operating principles ofmanual starters
� Describe the construction and operating principles ofmagnetic contactors and magnetic motor starters
� Identify various Siemens and Furnas manual starters andmagnetic motor starters, and describe their operation in acontrol circuit
� Explain the need for motor overload protection
� State the need for reduced-voltage motor starting
� Describe typical motor starting methods
3
� Describe the difference between normally open andnormally pilot devices
� Describe the operating principles of control relays
� Describe how limit switches, photoelectric sensors, andproximity switches are used in control circuits
This knowledge will help you better understand customerapplications. In addition, you will be better able to describeproducts to customers and determine important differencesbetween products. You should complete Basics of Electricitybefore attempting Basics of Control Components. Anunderstanding of many of the concepts covered in Basics ofElectricity is required for Basics of Control Components.
If you are an employee of a Siemens Energy & Automationauthorized distributor, fill out the final exam tear-out card andmail in the card. We will mail you a certificate of completion ifyou score a passing grade. Good luck with your efforts.
Siemens & Furnas Controls is a business unit of SiemensEnergy & Automation, Inc.
BERO and SIMICONT are registered trademarks of SiemensEnergy & Automation, Inc.
INNOVA PLUS and ESP100 are trademarks of Siemens Energy& Automation, Inc.
National Electrical Code® and NEC® are registered trademarksof the National Fire Protection Association, Quincy, MA 02269.Portions of the National Electrical Code are reprinted withpermission from NFPA 70-1996, National Electrical CodeCopyright, 1995, National Fire Protection Association, Quincy,MA 02269. This reprinted material is not the complete andofficial position of the National Fire Protection Association onthe referenced subject which is represented by the standard inits entirety.
Underwriters Laboratories Inc. is a registered trademark ofUnderwriters Laboratories Inc., Northbrook, IL 60062. Theabbreviation �UL� shall be understood to mean UnderwritersLaboratories Inc.
CAGE CLAMP is a trademark of WAGO Corporation, BrownDeer, WI 53223
4
Control Circuits
The National Electrical Code® (NEC®) defines a controller as adevice or group of devices that serves to govern, in somepredetermined manner, the electrical power delivered to theapparatus to which it is connected (Article 100-definitions).
Control Control, as applied to control circuits, is a broad term thatmeans anything from a simple toggle switch to a complexsystem of components which may include relays, contactors,timers, switches, and indicating lights. Every electrical circuit forlight or power has control elements. One example of a simplecontrol circuit is a light switch used to turn lights on and off.
Of course there are many other devices and equipmentsystems in industrial applications. Motor control, for example,can be used to start and stop a motor and protect the motor,associated machinery, and personnel. In addition, motorcontrollers might also be used for reversing, changing speed,jogging, sequencing, and pilot-light indication. Control circuitscan be complex: accomplishing high degrees of automatic andprecise machine operation.
NEC® and National Electrical Code® are registered trademarks of the National Fire ProtectionAssociation. Reprinted with permission from NFPA 70-1996, the NationalElectrical Code®, Copyright©
1995, National Fire Protection Association, Quincy, MA02269.
5
Manual Control Control is considered to be manually operated when someonemust initiate an action for the circuit to operate. For example,someone might have to flip the switch of a manual starter tostart and stop a motor.
Automatic Operation While manual operation of machines is still common practice,many machines are started and stopped automatically.Frequently there is a combination of manual and automaticcontrol. A process may have to be started manually, but may bestopped automatically.
Control Elements The elements of a control circuit include all of the equipmentand devices concerned with the circuit function. This includesenclosures, conductors, relays, contactors, pilot devices, andovercurrent-protection devices. The selection of controlequipment for a specific application requires a thoroughunderstanding of controller operating characteristics and wiringlayout. The proper control devices must be selected andintegrated into the overall plan.
Note: Article 725, 240-5, and 430-71 to 430-74 in the NationalElectrical Code® covers the application of control circuits. Youare encouraged to become familiar with this material.
6
Electrical Symbols
Language has been developed in order to transfer ideas andinformation. In order to understand the ideas and informationbeing communicated, an understanding of the language isnecessary. The language of controls consists of a commonlyused set of symbols which represents control components.
Contact Symbols Contact symbols are used to indicate an open or closed path ofcurrent flow. Contacts are shown as normally open (NO) ornormally closed (NC). Contacts shown by this symbol requireanother device to actuate them.
The standard method of showing a contact is by indicating thecircuit condition it produces when the actuating device is in thedeenergized or nonoperated state. For example, in the followingillustration a relay is used as the actuating device. The contactsare shown as normally open, meaning the contacts are openwhen the relay is deenergized. A complete path of current doesnot exist and the light is off.
7
Normally Open Contact In a control diagram or schematic, symbols are usually notExample shown in the energized or operated state. For the purposes of
explanation in this text, a contact or device shown in a stateopposite of its normal state will be highlighted. For example, inthe following illustration the circuit is first shown in thedeenergized state. The contacts are shown in their normallyopen (NO) state. When the relay is energized, the contactsclose completing the path of current and illuminating the light.The contacts have been highlighted to indicate they are nowclosed. This is not a legitimate symbol. It is used here forillustrative purposes only.
Battery Battery
RelayEnergized
RelayDeenergized
Contacts are shown oppositeof their normal state (NO).
Normally Closed Contact In the following illustration the contacts are shown as normallyExample closed (NC), meaning the contacts are closed when the relay is
deenergized. A complete path of current exists and the light ison. When the relay is energized, the contacts open turning thelight off.
Battery Battery
RelayEnergized
RelayDeenergized
Contacts are shown oppositeof their normal state (NC).
8
Switch Symbols Switch symbols are also used to indicate an open or closed pathof current flow. Variations of this symbol are used to representlimit switches, foot switches, pressure switches, level switches,temperature-actuated switches, flow switches, and selectorswitches. Switches, like contacts, require another device oraction to change their state. In the case of a manual switchsomeone must manually change the position of the switch.
Normally Open Switch In the following illustration a battery is connected to one side ofExample a normally open switch and a light to the other. Current is
prevented from flowing to the light when the switch is open.When someone closes the switch, the path of current flow iscompleted and the light illuminates.
Normally Closed Switch In the following illustration a battery is connected to one sideExample of a normally closed switch and a light to the other. Current is
flowing to the light when the switch is closed. When someoneopens the switch, the path of current flow is interrupted and thelight turns off.
9
Pushbutton Symbols There are two basic types of pushbuttons: momentary andmaintained. A normally open momentary pushbutton closes aslong as the button is held down. A normally closed momentarypushbutton opens as long as the button is held down. Amaintained pushbutton latches in place when the button ispressed.
NO NC
Normally Open In the following illustration a battery is connected to one sidePushbutton Example of a normally open pushbutton and a light is connected to the
other side. When the pushbutton is depressed, a complete pathof current flow exists through the pushbutton and the light isilluminated.
Normally Closed In the following example current will flow to the light as longPushbutton Example as the pushbutton is not depressed. When the pushbutton is
depressed, current flow is interrupted and the light turns off.
10
Coil Symbols Coils are used in electromagnetic starters, contactors, andrelays. The purpose of contactors and relays is to open andclose associated contacts. A letter is used to designate the coil;for example, �M� frequently indicates a motor starter and �CR�indicates a control relay. The associated contacts have the sameidentifying letter. Contactors and relays use an electromagneticaction which will be described later to open and close thesecontacts. The associated contacts can be either normally openor normally closed.
M CR
M CR
AssociatedContacts
AssociatedContacts
Coil Coil
Coil Example Using In the following example, the �M� contacts in series with theNormally Open Contacts motor are controlled by the �M� contactor coil. When someone
closes the switch, a complete path of current flow existsthrough the switch and �M� contactor coil. The �M� contactorcoil actuates the �M� contacts which provide power to themotor.
M M
L1 L1
L2 L2
L3 L3
Motor Motor
M M
M M
M M
11
Overload Relay Symbols Overload relays are used to protect motors from overheatingdue to an overload on the driven machinery, low-line voltage,or an open phase in a three-phase system. When excessivecurrent is drawn for a predetermined amount of time, the relayopens and the motor is disconnected from its source of power.
ThermalOverload
Pilot Light Symbols A pilot light is a small electric light used to indicate a specificcondition of a circuit. For example, a red light might be used toindicate a motor is running. The letter in the center of the pilotlight symbol indicates the color of the light.
Other Symbols In addition to the symbols discussed here, there are many othersymbols used in control circuits. The following chart showsmany of the commonly used symbols.
12
13
14
Abbreviations Abbreviations are frequently used in control circuits. Thefollowing list identifies a few commonly used abbreviations.
15
Review 11. A control is ____________ operated when someone
must initiate an action for the circuit to operate.
2. Which of the following symbols represents a normallyopen contact?
a. b. c.
3. Which of the following symbols represents a normallyclosed contact?
a. b. c.
4. Which of the following symbols indicates a normallyopen pushbutton?
a. b. c.
5. Which of the following symbols indicates a mushroomhead pushbutton?
a. b. c.
16
Line Diagrams
The method of expressing the language of control symbols isa line diagram, also referred to as a ladder diagram. Linediagrams are made up of two circuits, the control circuit andthe power circuit. Electrical wires in a line diagram arerepresented by lines. Control-circuit wiring is represented by alighter-weight line and power-circuit wiring is represented by aheavier-weight line. A small dot or node at the intersection oftwo or more wires indicates an electrical connection.
ControlWiring
PowerWiring
NotConnected
Connected
Line diagrams show the functional relationship of componentsand devices in an electrical circuit, not the physicalrelationship. For example, the following illustration shows thephysical relationship of a pilot light and a pushbutton.
17
The functional relationship can be shown pictorially with thefollowing illustration.
L1 L2
Pushbutton PilotLight
Reading a Line Diagram This functional relationship is shown symbolically with a linediagram. Line diagrams are read from left to right. Depressingthe pushbutton would allow current to flow from L1 through thepushbutton, illuminating the pilot light, to L2. Releasing thepushbutton stops current flow turning the pilot light off.
L1 L2
Pushbutton PilotLight
Power Circuit and The power circuit, indicated by the heavier-weight line, is whatControl Circuit actually distributes power from the source to the connected load
(motor). The control circuit, indicated by the lighter-weight line, isused to �control� the distribution of power.
L1T1
T2
T3
L2
L3
OL
OL
OL
OL
M
M
M
Ma
MMotor
StartStop
Power Circuit
Control Circuit
18
Connecting Loads and Control circuits are made up of control loads and controlControl Devices devices. The control load is an electrical device that uses
electrical power. Pilot lights, relays, and contactors are examplesof control loads. Control devices are used to activate the controlload. Pushbuttons and switches are examples of controldevices. The following illustration shows the proper connectionof a pilot light (load) with a pushbutton (control device). Thepower lines are drawn vertically and marked L1 and L2. In thisexample the voltage potential between L1 and L2 is 120 VAC.The pilot light selected must be rated for 120 VAC. When thepushbutton is depressed, the full 120 volt potential is applied tothe pilot light.
L1 L2
Pushbutton 120 VACPilot Light
120 VAC
Connecting the Load to L2 Only one control load should be placed in any one circuit linebetween L1 and L2. One side of the control load is connected toL2 either directly or, in some instances, through overload relaycontacts. In the following example a pilot light is directlyconnected to L2 on one circuit line. A contactor coil is indirectlyconnected through a set of overload contacts (OL) to L2 on asecond circuit line. This is a parallel connection. Depressing thepushbutton would apply 120 VAC to the pilot light and the �M�contactor.
L1 L2
Pushbutton 120 VACPilot Light
120 VACContactor
120 VAC
M
OL
Pilot LightConnected
Directly To L2
ContactorConnected
Indirectly To L2
19
Control loads are generally not connected in series. Thefollowing illustration shows two ways to connect a control load.In one instance the control loads are improperly connected inseries. When the pushbutton is depressed, the voltage acrossL1 and L2 is divided across both loads, the result being thatneither load will receive the full 120 volts necessary for properoperation. If one load fails in this configuration, the entire circuitis rendered useless.
In the other instance the loads are properly connected inparallel. In this circuit there is only one load for each linebetween L1 and L2. The full 120 volts will appear across eachload when the pushbutton is depressed. If one load fails in thisconfiguration, the other load will continue to operate normally.
L1 L1L2 L2
120 VACPilot Light
120 VACPilot Light
120 VACPilot Light
120 VACPilot Light
120 VAC 120 VAC
Improper Series Connection Proper Parallel Connection
Connecting Control Control devices are connected between L1 and the load. TheDevices control device can be connected in series or parallel,
depending on the desired results. In the following illustration,the pushbuttons are connected in parallel. Depressing eitherpushbutton will allow current to flow from L1, through thedepressed pushbutton, through the pilot light, to L2.
Pushbutton 1
Pushbutton 2
L1 L2
PilotLight
20
In the following illustration, two pushbuttons are connected inseries. Both pushbuttons must be depressed in order to allowcurrent to flow from L1 through the load to L2.
Pushbutton 1 Pushbutton 2
L1 L2
PilotLight
Line Numbering Numbering each line makes it easier to understand morecomplex line diagrams. In the following illustration, line 1connects pushbutton 1 to pilot light 1. Line 2 connectspushbutton 2 to pilot light 1. Line 3 connects switch 1 to pilotlight 2 and the �M� contactor on line 4.
Switch 1 Pilot Light 2
Contactor
M
OL
Pushbutton 1
Pushbutton 2
L1 L2
Pilot Light 1
1
2
3
4
21
Review 21. Line diagrams are read from ____________ to
____________ , or L1 to L2.
2. Match the items on the line diagram with the associ-ated list.
A B
C
D
EF
Control WiringControl DeviceNodePower WiringPower LoadControl Load
A ____________
B ____________
C ____________
D ____________
E ____________
F ____________
22
Overload Protection
Before discussing specific control components, it is necessaryto review what an overload is and what steps can be taken tolimit the damage an overload can cause.
Current and Temperature Current flow in a conductor always generates heat due toresistance. The greater the current flow, the hotter theconductor. Excess heat is damaging to electrical components.For that reason, conductors have a rated continuous currentcarrying capacity or ampacity. Overcurrent protection devicesare used to protect conductors from excessive current flow.Thermal overload relays are designed to protect the conductors(windings) in a motor. These protective devices are designed tokeep the flow of current in a circuit at a safe level to prevent thecircuit conductors from overheating.
Normal Current Flow
Excessive Current Flow
23
Reprinted with permission from NFPA 70-1996, the National Electrical Code®, Copyright©
1995, National Fire Protection Association, Quincy, MA 02269.
Excessive current is referred to as overcurrent. The NationalElectrical Code® defines overcurrent as any current in excessof the rated current of equipment or the ampacity of aconductor. It may result from overload, short circuit, or groundfault (Article 100-definitions).
Short Circuits When two bare conductors touch, a short circuit occurs. When ashort circuit occurs, resistance drops to almost zero. Short-circuit current can be thousands of times higher than normaloperating current.
Conductor
Insulator
Ohm�s Law demonstrates the relationship of current, voltage,and resistance. For example, a 240 volt motor with 24 W ofresistance would normally draw 10 amps of current.
IE
R
I
I amps
=
=
=
240
24
10
When a short circuit develops, resistance drops. If resistancedrops to 24 milliohms, current will be 10,000 amps.
I
I amps
=
=
240
024
10 000
.
,
The heat generated by this current will cause extensive damageto connected equipment and conductors. This dangerouscurrent must be interrupted immediately when a short circuitoccurs.
24
25
Overload Protection Fuses and circuit breakers are protective devices used toprotect circuits against short circuits, ground faults, andoverloads. In the event of a short circuit, a properly sized fuse orcircuit breaker will immediately open the circuit.
There is, however, a dilemma that occurs when applying fusesand circuit breakers in motor control circuits. The protectivedevice must be capable of allowing the motor to exceed its full-load rating for a short time. Otherwise, the motor will trip eachtime it is started. In this situation it is possible for a motor toencounter an overload condition which does not draw enoughcurrent to open the fuse or trip the circuit breaker. This overloadcondition could easily cause enough heat to damage the motor.In the next section we will see how overload relays are used tosolve this problem.
26
Overload Relays
Overload relays are designed to meet the special protectiveneeds of motor control circuits. Overload relays:
� allow harmless temporary overloads, such as motorstarting, without disrupting the circuit
� will trip and open a circuit if current is high enough tocause motor damage over a period of time
� can be reset once the overload is removed
Trip Class Overload relays are rated by a trip class, which defines thelength of time it will take for the relay to trip in an overloadcondition. The most common trip classes are Class 10, Class 20and Class 30. Class 10, for example, has to trip the motor offline in 10 seconds or less at 600% of the full load amps. This isusually sufficient time for the motor to reach full speed. Manyindustrial loads, particularly high inertia loads, use Class 30.Siemens standard overload relays are Class 10 or Class 20 withClass 30 available with some starters.
27
Overload Relay in a The following schematics show a motor circuit with a manualMotor Circuit starter and overloads. Current flows through the overloads
while the motor is running. Excess current will cause theoverload to trip at a predetermined level, opening the circuitbetween the power source and the motor. After apredetermined amount of time the starter can be reset. Whenthe cause of the overload has been identified and corrected themotor can be restarted.
Melting Alloy One method of providing overload protection is with a meltingalloy overload relay. The alloy is a solder which melts at a veryprecise temperature. When it reaches this specific temperatureit will change from its solid state to a liquid state. Thistemperature never changes, ensuring the accuracy of theoverload during the life of the relay.
The overload relay is connected in series between the line andthe motor. Current flows from L1 through a normally closed (NC)contact and a heater element to the motor. During normaloperation the melting alloy is solid and holds the ratchet wheelfirmly in place. The contacts are held closed by a pawl that isconnected to the ratchet wheel.
LineL1
MotorT1
Reset Button
Spring
Normally Closed Contact
Heater ElementRatchet Wheel
Pawl
Tube
MeltingAlloy
28
If an overload occurs, the current flow through the heaterelement is sufficient to cause the melting alloy to melt. Theratchet wheel is free to turn. Spring tension pushes the resetbutton up, opening the normally closed contacts and stoppingthe motor. Current no longer flows through the heater elementallowing the melting alloy to solidify. Once the melting alloy hasbecome solid, the contacts can be closed by manuallydepressing the reset button, forcing the pawl across the ratchetwheel until the contacts are closed and the spring and ratchetwheel are returned to the original condition. The start button canthen be pressed to restart the motor.
LineL1
MotorT1
Reset Button
Spring
Normally Closed Contact
Heater ElementRatchet Wheel
Pawl
Tube
MeltingAlloy
Class 48 Melting Alloy The Furnas Class 48 melting alloy overload relay is available inOverload Relay single-pole or three-pole configurations. This type of relay
requires heater elements and comes with a Class 20 trip rating.The melting alloy overload relay must be manually reset. As anoption, for the three-pole configuration, an isolated normallyopen or a normally closed auxiliary contact is available.
29
Bimetal Overloads Another type of overload relay is the bimetal overload relay.Overload protection is accomplished with the use of a bimetalstrip. This component consists of a small heater element wiredin series with the motor and a bimetal strip that can be used asa trip lever. A bimetal strip is made of two dissimilar metalsbonded together. The two metals have different thermalexpansion characteristics, so the bimetal bends at a given ratewhen heated.
Under normal operating conditions the heat generated by theheater element will be insufficient to cause the bimetal strip tobend enough to trip the overload relay. As current rises, heatalso rises. The hotter the bimetal becomes, the more it bends. Inan overload condition the heat generated from the heater willcause the bimetal strip to bend until the mechanism is tripped,stopping the motor.
Some overload relays that are equipped with a bimetal strip aredesigned to automatically reset the circuit when the bimetalstrip has cooled and reshaped itself, restarting the motor. If thecause of the overload still exists, the motor will trip again andreset at given intervals. Care must be exercised in the selectionof this type of overload as repeated cycling will eventuallydamage the motor.
30
Ambient Compensated In certain applications, such as a submersible pump, the motorOverload Relay may be installed in a location having a constant ambient
temperature. The motor control, along with the overload relay,may be installed in a location with a varying ambienttemperature. The trip point of the overload relay will vary withthe temperature of the surrounding air as well as currentflowing through the motor. This can lead to premature andnuisance tripping.
Ambient compensated overload relays are designed toovercome this problem. A compensated bimetal strip is usedalong with a primary bimetal strip. As the ambient temperaturechanges, both bimetal strips will bend equally and the overloadrelay will not trip the motor. However, current flow through themotor and the heater element will affect the primary bimetalstrip. In the event of an overload condition the primary bimetalstrip will engage the trip unit.
I
31
Class 48 Bimetal The Class 48 bimetal overload relay is available in single-pole or Overload Relay three-pole designs. Like the melting alloy overload relay, this
overload relay requires separate heaters. Unlike the meltingalloy overload relay, the bimetal overload relay can be set formanual or self-resetting operation. An adjustment dial locatedon the unit allows the ampere trip setting to be adjustedby ±15%. The bimetal overload relay heater elements areavailable in Class 20 or Class 10 ratings. Ambient compensatedoverload relays are also available. A normally open or normallyclosed auxiliary contact is available as an option.
Sirius 3RU11 The Siemens Sirius 3RU11 is a bimetal type of overload relayOverload Relay with the heater elements as an integral part of the design. The
unit comes with a Class 10 trip as standard. The Sirius 3RU11features manual or automatic reset, adjustable current settings,and ambient compensation. A switch-position indicator alsoincorporates a test function which is used to simulate a trippedoverload relay. A normally open and a normally closed auxiliarycontact are included.
32
Electronic Overload Relays Electronic overload relays are another option for motorprotection. The features and benefits of electronic overloadrelays vary but there are a few common traits. One advantageoffered by electronic overload relays is a heaterless design. Thisreduces installation cost and the need to stock a variety ofheaters to match motor ratings. Electronic relays offer phaseloss protection. If a power phase is lost, motor windings canburn out very quickly. Electronic overload relays can detect aphase loss and disconnect the motor from the power source.This feature is not available on mechanical types of overloadrelays.
Furnas ESP 100 A single ESP100 overload relay replaces at least six size rangesElectronic Overload Relay of heaters. Instead of installing heaters the full-load amperes
(FLA) of the motor is set with a dial. The ESP100 overloadrelay illustrated below, for example, is adjustable from 9 to18 amperes. NEMA Class 10, 20, and 30 trip curves areavailable for a variety of applications. The relay comes in eithera manual or self-resetting version. Auxiliary contacts areavailable as an option.
33
Siemens 3RB12 In addition to heaterless construction and phase loss protection,Electronic Overload Relay the 3RB12 offers ground fault protection, phase unbalance,
LED displays (ready, ground fault, and overload), automaticreset with remote capability, and selectable trip classes (5, 10,15, 20, 25, or 30). The 3RB12 is self-monitoring and is providedwith 2 normally open and 2 normally closed isolated auxiliarycontacts.
Review 31. With an increase in current, heat will ____________ .
a. increaseb. decreasec. remain the same
2. The National Electrical Code® defines overcurrent asany current in ____________ of the rated current ofequipment or the ampacity of a conductor.
3. An ____________ occurs when electrical equipment isrequired to work harder than it is rated.
4. A Class __________ overload relay will trip an over-loaded motor offline within 10 seconds at six times full-load amps.
a. 10b. 20c. 30
5. A ____________ strip uses two dissimilar metalsbonded together.
34
Manual Control
Manual control, as the name implies, are devices operated byhand. A simple knife switch, like the one shown in thefollowing illustration, was the first manual-control device usedto start and stop motors. The knife switch was eventuallyreplaced with improved control designs, such as manual andmagnetic starters.
Basic Operation The National Electrical Code® requires that a motor controldevice must also protect the motor from destroying itself underoverload conditions. Manual starters, therefore, consist of amanual contactor, such as a simple switch mechanism, and adevice for overload protection. The following diagram illustratesa single-pole manual motor starter. Each set of contacts is calleda pole. A starter with two sets of contacts would be called atwo-pole starter.
35
Two-Pole Manual Starter Starters are connected between the power source and theload. For example, a Two-pole or single-phase motor starter isconnected to a motor. When the switch is in the �OFF�position, the contacts are open preventing current flow to themotor from the power source. When the switch is in the �ON�position, the contacts are closed and current flows from thepower source (L1), through the motor, returning to the powersource (L2).
This is represented with a line drawing and symbols asillustrated in the following drawing.
Low Voltage Protection Some manual motor starters offer low-voltage protection (LVP)as an option. LVP will automatically remove power from themotor when incoming power drops or is interrupted. The startermust be manually reset when power is restored. This protectspersonnel from potential injury caused by machinery that mayotherwise automatically restart when power is restored.
36
SMF Fractional- Siemens SMF fractional-horsepower starters provide overloadHorsepower Manual protection and manual �ON/OFF� control for small motors.Starters SMF starters are available in one- or two-pole versions suitable
for AC motors up to 1 HP and 277 VAC. The two-pole version issuitable for DC motors up to 3/4 HP and 230 VDC. SMF manualstarters are available in a variety of enclosures. A two-speedversion is available.
MMS and MRS Siemens MMS and MRS manual switches are similar to SMFManual Switches starters but do not provide overload protection. MMS and
MRS switches only provide manual �ON/OFF� control ofsingle- or three-phase AC motors where overload protection isprovided separately. These devices are suitable for use withthree-phase AC motors up to 10 HP and 600 VAC and up to1-1/2 HP and 230 VDC. The MMS and MRS manual switchesare available in various enclosures. Two-speed and reversingversions are available.
37
Furnas Class 11 Furnas Class 11 manual starters use a melting-alloy overloadManual Starter relay with interchangeable heater elements and a manual reset.and Manual Contactor It has a maximum rating of 10 HP at 460 VAC (3Ø) and 5 HP at
230 VAC (1Ø). Class 11 manual starters are available in acomplete line of general-purpose and industrial-dutyenclosures. Class 11 manual starters may also be furnishedwith a low-voltage protection circuit. Class 11 manualcontactors provide no overload protection.
3RV10 Motor Starter 3RV10 motor starter protectors (MSPs) are part of the SiemensProtectors Sirius 3R motor control product line. A thermal overload with a
bimetal strip is used to provide overload protection with the3RV10 motor starter protector. 3RV10 MSPs come in four framesizes: 3RV101, 3RV102, 3RV103, and 3RV104.
38
The 3RV101 is available in both screw-terminal and CAGECLAMP� versions. The 3RV102, 3RV103, and 3RV104 areavailable with screw terminals.
CAGE CLAMP� The CAGE CLAMP� is available on many Siemens Sirius 3Rproducts including the MSPs. To connect a wire, simply push anelectrician blade screwdriver into the appropriate portal, insertthe stripped end of the wire into the portal directly above,remove the screwdriver, and the wire is securely connected.CAGE CLAMP� devices are especially beneficial ininstallations that are subject to vibration.
Enclosures and Options Siemens 3RV10 MSPs are available in a variety of enclosures.Several options, such as indicator lights, are also available.
39
Reversing Drum Controller Manually operated drum controllers, like the Furnas Class 58reversing drum controller, stop and change direction ofreversible AC motors. Overload protection is not provided bythe reversing drum controller and must be supplied by anexternal means. The Furnas Class 58 reversing drum controlleris rated for 10 HP at 460 VAC. Another style of drum switch isused to change speed of multi-speed motors.
Foot Switch The Furnas Class 56 foot switch is another type of manualcontrol. Typical applications include the control of drill presses,conveyors, tapping machines, etc. Foot switches, rated foracross-the-line operations, operate motors up to 7.5 HP at 460VAC. They come in either momentary or maintained operationsas well as reversing.
40
Master Switch The Furnas Class 53 master switches provide single-handlecontrol of hoists, cranes, oven pushers, and other equipmentrequiring speed steps of wound rotor or direct-current motors.Master switches are available with momentary or maintainedcontacts and up to five speed settings.
41
Magnetic Contactors and Starters
Most motor applications require the use of remote controldevices to start and stop the motor. Magnetic contactors, similarto the ones shown below, are commonly used to provide thisfunction. Contactors are also used to control distribution ofpower in lighting and heating circuits.
Basic Contactor Operation Magnetic contactors operate utilizing electromagneticprinciples. A simple electromagnet can be fashioned bywinding a wire around a soft iron core. When a DC voltage isapplied to the wire, the iron becomes magnetic. When the DCvoltage is removed from the wire, the iron returns to itsnonmagnetic state. This principle is used to operate magneticcontactors.
42
The following illustration shows the interior of a basic contactor.There are two circuits involved in the operation of a contactor:the control circuit and the power circuit. The control circuit isconnected to the coil of an electromagnet, and the power circuitis connected to the stationary contacts.
The operation of this electromagnet is similar to the operationof the electromagnet we made by wrapping wire around a softiron core. When power is supplied to the coil from the controlcircuit, a magnetic field is produced magnetizing theelectromagnet. The magnetic field attracts the armature to themagnet, which in turn closes the contacts. With the contactsclosed, current flows through the power circuit from the line tothe load. When the electromagnet�s coil is deenergized, themagnetic field collapses and the movable contacts open underspring pressure. Current no longer flows through the powercircuit.
43
The following schematic shows the electromagnetic coil of acontactor connected to the control circuit through a switch(SW1). The contacts of the contactor are connected in the powercircuit to the AC line and a three-phase motor. When SW1 isclosed, the electromagnetic coil is energized, closing the �M�contacts and applying power to the motor. Opening SW1deenergizes the coil and the �M� contacts open, removingpower from the motor.
Overload Relay Contactors are used to control power in a variety of applications.When applied in motor-control applications, contactors can onlystart and stop motors. Contactors cannot sense when themotor is being loaded beyond its rated conditions. They provideno overload protection. Most motor applications requireoverload protection. However, some smaller-rated motorshave overload protection built into the motor (such as ahousehold garbage disposal). Overload relays, similar to the oneshown below, provide this protection. The operating principle,using heaters and bimetal strips, is similar to the overloadsdiscussed previously.
44
Motor Starter Contactors and overload relays are separate control devices.When a contactor is combined with an overload relay, it is calleda motor starter.
45
Motor Starter in a The following diagram shows the electrical relationship of theControl Circuit contactor and overload relay. The contactor, highlighted with the
darker grey, includes the electromagnetic coil, the main motorcontacts, and the auxiliary contacts. The overload relay,highlighted by the lighter grey, includes the �OL� heaters andoverload contacts. The contactor and the overload relay haveadditional contacts, referred to as auxiliary contacts, for use inthe control circuit. In this circuit a normally closed �OL� contacthas been placed in series with the �M� contactor coil and L2. Anormally open �M� auxiliary contact (�Ma�) has been placed inparallel with the �Start� pushbutton.
L1
L2
L3
OL
OL
OL
OL
M
M
M
Ma
MMotor
StartStop
Contactor Overload Relay
Heater Element
Electromagnetic Coil
Overload ContactAuxiliaryContactor Contact(Holding Circuit)
Review 41. A starter with two sets of contacts would be called a
____________ -pole starter.
2. ____________ will automatically disconnect power fromthe motor when incoming power drops or is interrupted.
3. The Furnas Class 11 motor starter protects motors up to____________ HP at 460 VAC and ____________ HP at230 VAC.
4. The 3RV102 motor starter protector protects motors upto ____________ HP at 460 VAC.
5. When a contactor is combined with an overload relay, itis called a ____________ ____________ .
46
Starter Ratings
Starter contactors are rated according to size and type ofload they handle. The National Electrical ManufacturersAssociation (NEMA) and the International ElectrotechnicalCommission (IEC) are two organizations that rate contactorsand motor starters. NEMA is primarily associated withequipment used in North America. IEC, on the other hand, isassociated with equipment sold in many countries including theUnited States. International trade agreements, marketglobalization, and domestic and foreign competition have madeit important for controls manufacturers to be increasingly awareof international standards.
NEMA NEMA ratings are maximum horsepower ratings, according tothe National Electrical Manufacturers Association ICS2standards. NEMA starters and contactors are selectedaccording to their NEMA size. These sizes range from size 00to size 9.
47
NEMA motor-control devices have generally become known fortheir very rugged, heavy-duty construction. Because of theirrugged design NEMA devices are physically larger than IECdevices. NEMA motor starters and contactors can be used invirtually any application at their stated rating, from simple �ON�and �OFF� applications to more-demanding applications thatinclude plugging and jogging. To select a NEMA motor starterfor a particular motor one need only know the horsepower andvoltage of the motor. If there is considerable plugging andjogging duty involved, however, even a NEMA-rated device willrequire some derating.
Motor Matched Sizes Siemens also has what are called Motor Matched sizesavailable on some Siemens motor starters. The ratings for thesedevices fall in between the ratings of normal NEMA sizes. Thisallows the user to more closely match the motor control to theactual application. The following table shows Motor Matchedsizes available.
IEC Not all applications require a heavy-duty industrial starter. Inapplications where space is more limited and the duty cycle isnot severe, IEC devices represent a cost-effective solution. IECdevices are rated for maximum operational current as specifiedby the International Electrotechnical Commission in publicationIEC 158-1. IEC does not specify sizes. Utilization categories areused with IEC devices to define the typical duty cycle of an IECdevice. AC-3 and AC-4 are the categories of most interest forgeneral motor-starting applications.
48
Definite Purpose Definite Purpose (DP) contactors have certain characteristicswhich must be taken into consideration. DP contactors weredesigned for specific applications where the operatingconditions are clearly defined. These operating conditionsinclude full load amps, locked rotor amps, noninductive amps(resisitive load), number of power poles, duty cycle, and thetotal number of expected operations.
DP contactors are sized by the motor full-load amps (FLA) andlocked rotor amps (LRA). FLA is the amount of current themotor draws at full speed, under full mechanical load, at ratedvoltage. LRA is the maximum current the motor will draw at theinstant full-line voltage is applied to the motor. DP contactorsare well suited for loads found in the following areas:
• Heating, Ventilating, and Air Conditioning (HVAC)• Farm Equipment and Irrigation• Environmental Control Systems• Office Equipment• Pool and Spa Controls• Welding Equipment• Medical Equipment• Food-Service Equipment
Other Organizations There are several other organizations that have developedstandards and tests for electrical equipment. UnderwritersLaboratory (UL), for example, specifies a maximum horsepowerrating for which a contactor can be used. The contactor is testedby Underwriters Laboratory using test procedure U.L. 508. AllSiemens contactors are rated in accordance with at least one ofthe previous organizations� test procedures. Some carry multipleratings. For example, Furnas INNOVA starters meet or exceedNEMA and UL standards. Siemens Sirius starters meet orexceed NEMA, IEC, and UL standards.
49
Furnas INNOVA PLUS Starters
Furnas INNOVA PLUS� starters are available in NEMA sizes 0through 4. They are available up to 100 HP.
Ambient-Compensated Furnas INNOVA PLUS starters are available with two types ofBimetal Overload Relay overload relays. A Class 20 melting alloy overload (shown in the
above illustration) is standard. INNOVA PLUS is also availablewith Class 10 or 20 ambient-compensated bimetal overloadrelay (shown below).
50
ESP100 Starters
The Furnas ESP100� starters use the same contactor as theINNOVA PLUS� starters. The ESP100 starters are supplied witha Class 10, 20, or 30 ESP100 solid-state overload relay. TheESP100 overload relay protects 3Ø motors with FLA of ¼ampere through 135 amperes. From ¼ ampere to 10 amperesthe overload has a 4:1 FLA range, i.e.; 2½ - 10 amperes. Above10 amperes the range is 2:1. The ESP100 overload relayillustrated below, for example, is adjustable from 9 to 18amperes.The ESP100 also protects the motor against phaseloss. The ESP100 trips within three seconds of loss of one ofthe power-supply phases.
51
Sirius Type 3R Starters
Sirius 3R is a complete modular, building-block system. Thesystem includes a structured range of contactors and overloadrelays covering loads up to 95 amps in four frame sizes. Thesefour frame sizes are referred to as S00 (12A), S0 (25A), S2(50A), and S3 (95A). A feature of the Sirius product line is anarrow mounting width. An S3 contactor rated at 75 HP, forexample, is only 70mm (2.75�). Sirius 3R contactors andoverload relays can operate in ambient temperatures up to140°F (60°C). This, along with the smaller size, allows moreunits to be packed into a panel without overheating thecomponents.
52
CAGE CLAMP� Size S00 contactors and overload relays are available with CAGECLAMP� connections on power and control-circuit terminals.Size S0, S2, and S3 contactors and overload relays have CAGECLAMP� connections on the control-circuit terminals only.
Overload Relays Sirius 3R overload relays provide Class 10 overcurrent protectionfor both AC and DC motors. Ambient-compensated bimetalstrips prevent the overload relay from nuisance tripping whenthe panel temperature is higher than the ambient temperatureof the motor. The design of the overload relay also includes adifferential trip bar that causes the unit to trip faster in the eventof a phase-loss condition. An optional remote-reset module (notshown) is available.
53
World Series Type 3TF Starters
The World Series starters are supplied with a type 3TFcontactor and overload relay. World Series starters are availablein horsepower ratings from 100 to 500 HP at 460 VAC. Auxiliarycontacts are provided for use in the control circuit. World Seriestype 3TF contactors are available with various enclosures.Additional auxiliary contacts can be added. Coil voltages for theelectromagnetic coil range from 24 to 600 VAC.
The overload relay is a Class 10 relay that uses a bimetal stripunit and heater element to detect overloads. Each phasemonitors current. The unit has a full-load amps adjustment, testbutton, and reset button. The full-load amps adjustmentcorresponds to the range of the motor full-load ampere rating.The test button is to ensure the overload relay is functioningproperly. The reset button is used to reset a trip. It can be eitherautomatic or manual reset. There is also a trip indicator.
54
Overload Relay Selection The following chart is useful in selecting the correct contactorand overload-relay combination. The chart reflects themaximum horsepower rating using Underwriters Laboratorytest procedure U.L. 508 and the appropriate overload relay.
Review 51. ____________ is an organization primarily associated
with rating equipment used in North America and____________ is associated with rating equipment usedin many countries including the U.S.
2. A NEMA Size ____________ starter is rated for 200 HPat 460 volts .
3. IEC utilization category ____________ applications aredescribed as the starting of squirrel-cage motors andswitching off only after a motor is up to speed.
4. Furnas INNOVA PLUS� starters are available in NEMAsizes 0 through ____________ .
5. The ESP100 trips within ____________ seconds of lossof one of the power-supply phases.
6. The maximum load current of a size S2 Sirius 3Rstarter is ____________ amps.
7. The correct overload relay for a 3TF54 contactor is____________ .
55
Multi-Speed and Reversing Starters
Full-voltage AC magnetic multi-speed controllers are designedto control squirrel-cage induction motors for operation at two,three, or four different constant speeds, depending on motorconstruction. The speed of a constant-speed motor is a functionof the supply frequency and the number of poles and is given inthe following formula:
Synchronous Speed in RPM =120 x Frequency
Number of Poles
The speed in RPM is the synchronous speed or the speed ofthe rotating magnetic field in the motor stator. Actual rotorspeed is always less due to slip. The design of the motor andthe amount of load applied determine the percentage of slip.This value is not the same for all motors. A motor with fourpoles on a 60 hertz AC line has a synchronous speed of 1800RPM. This means that, after allowing for slip, the motor is likelyto run at 1650 to 1750 RPM when loaded.
1800 =120 x 60
4
An induction motor with two poles on a 60 hertz AC line,however, would run at twice that speed.
When motors are required to run at different speeds, themotor�s torque or horsepower characteristics will change with achange in speed. The proper motor must be selected andcorrectly connected for the application. In these applications,there are three categories.
Constant Torque (CT)Variable Torque (VT)Constant Horsepower (CHP)
56
Separate-Winding There are two basic methods of providing multi-speed controlusing magnetic starters: separate-winding motors andconsequent-pole motors. Separate-winding motors have aseparate winding for each speed. The speed of each windingdepends on the number of poles. The low-speed winding iswound for more poles than the high-speed winding.The motorcost is higher than consequent pole, but the control is simpler.There are many ways multi-speed motors can be connecteddepending on speed, torque, and horsepower requirements. Thefollowing schematic shows one possible connection of a two-speed, two-winding, wye-connected motor.
T1
T3T2
L1
L2
L3
T11
T12T13
1
2
3
4
5
6
Low Speed: Close 1, 2, 3Open 4, 5, 6
High Speed: Close 4, 5, 6Open 1, 2, 3
Speed =120 x Frequency
Number of Poles- Slip
Consequent-Pole Consequent-pole motors have a single winding for two speeds.Motors Taps can be brought from the winding for reconnection for
a different number of poles. Two-speed, consequent-polemotors have one reconnectable winding. Low speed of a two-speed, consequent-pole motor is one half the speed of highspeed. Three-speed motors have one reconnectable windingand one fixed winding. Four-speed motors have tworeconnectable windings.
One North PoleOne
NorthPole
OneSouthPole
Speed Selection There are three control schemes of speed selection for multi-speed motors: selective control, compelling control, andprogressive control. Selective control permits motor starting atany speed and to move to a higher speed the operatordepresses the desired speed pushbutton. Compelling controlrequires the motor to be started at the lowest speed, then theoperator must manually increment through each speed step tothe desired speed. With progressive control the motor is startedat the lowest speed and automatically increments to theselected speed.
57
Reversing Many applications require a motor to run in both directions. Inorder to change the direction of motor rotation, the direction ofcurrent flow through the windings must be changed. This isdone on a three-phase motor by reversing any two of the threemotor leads. Traditionally T1 and T3 are reversed. The followingillustration shows a three-phase reversing motor circuit. It hasone set of forward (F) contacts controlled by the �F� contactor,and one set of reverse (R) contacts controlled by the �R�contactor.
L1T1
T2
T3
L2
L3
F
F
F
R
R
R
Forward:
Reverse:
L1 - T1L2 - T2L3 - T3
L1 - T3L2 - T2L3 - T1
MechanicalInterlocks
When the �F� contacts are closed, current flows through themotor causing it to turn in a clockwise direction.
L1T1
T2
T3
L2
L3
F
F
F
R
R
R
Forward:
Reverse:
L1 - T1L2 - T2L3 - T3
L1 - T3L2 - T2L3 - T1
MechanicalInterlocks
58
When the �R� contacts are closed, current flows through themotor in the opposite direction causing it to rotate in acounterclockwise direction. Mechanical interlocks prevent bothforward and reverse circuits from being energized at the sametime.
L1T1
T2
T3
L2
L3
F
F
F
R
R
R
Forward:
Reverse:
L1 - T1L2 - T2L3 - T3
L1 - T3L2 - T2L3 - T1
MechanicalInterlocks
59
Reduced-Voltage Starting
Full-Voltage Starting The most common type of motor starting is full-voltage starting.The motor is placed directly across the line with this method.
With this type of starter the motor receives the full-line voltage.When a motor is started with full voltage, starting current canbe as high as 600% of full-load current on standard squirrelcage motors. It can be even higher on high efficiency motors.There are situations where this method of starting is notacceptable. On large motors the high starting current isreflected back into the power lines of the electric utility, causinglights to flicker and in more serious situations can causecomputers to malfunction. Many power companies in the U.S.require reduced-voltage starting on large-horsepower motors.
60
Another potential problem with applying full-voltage starts is thehigh torque developed when power is first applied to the motor.This can be as high as 175% to 200% of full-load torque on astandard NEMA B type motor. Many applications require thestarting torque to be applied gradually. A conveyor belt, forexample, requires the starting torque to be applied gradually toprevent belt slipping or bunching.
Reduced-Voltage Starting In general, starting methods which deviate from full-voltagestarting by providing a lower starting voltage are referred to asreduced-voltage starting. Reduced-voltage starting should beused when it is necessary to limit the initial inrush of current orit is desired to reduce the starting torque of a motor.
Reduced-voltage starting reduces the starting voltage of aninduction motor with the purpose of confining the rate ofchange of the starting current to predetermined limits. It isimportant to remember that when the voltage is reduced tostart a motor, current is also reduced, which also reduces theamount of starting torque a motor can deliver. Several methodsare available for reduced-voltage starting. The application or thetype of motor generally dictates the method to use. A few ofthe methods offered by Siemens are described in the followingparagraphs.
61
Autotransformer Reduced- Autotransformer reduced-voltage starters provide the highestVoltage Starters starting torque per ampere of line current and is one of the
most effective means of starting a motor for an application inwhich starting current must be reduced with a minimumsacrifice of starting torque. Autotransformers have adjustabletaps to reduce starting voltage to 50%, 65%, or 80% of full-linevoltage.
Applications: Blowers, Pumps, Compressors
Part-Winding Starters Part-winding, reduced-voltage starters are used on motors withtwo separate parallel windings on the stator. The windings usedduring start draw about 65 - 80% of rated locked rotor current.During run each winding carries approximately 50% of the loadcurrent. Part-winding, reduced-voltage starters are the least-expensive type of reduced-voltage starters and use a verysimplified control circuit. However, they require special motordesign and are not suitable for high inertia loads. There is noadjustment of current or torque.
Applications: Pumps, Fans, Refrigeration, Compressors
62
Wye-Delta Starters Wye-delta, reduced-voltage starters are applicable only withmotors having stator windings not connected internally and allsix motor leads available. Connected in a wye configuration, themotor starts with reduced starting line current. The motor isreconfigured to a delta connection for run. This type of starter isa good method for applications requiring frequent starts. Thestarting torque is lower compared to other methods of reducedvoltage starters.
Applications: Central Air Conditioning Equipment, Compressors
Primary Resistance Starter This is a simple and effective starting method. The motor isinitially energized through a resistor in each of the threeincoming lines. Part of the voltage is dropped through theresistors. The motor receives 70% to 80% of the full-linevoltage. As the motor picks up speed, the motor sees more ofthe line voltage. At a preset time a time-delay relay closes aseparate set of contacts, shorting out the resistors and applyingfull voltage to the motor. This type of reduced voltage starting islimited by the amount of heat the resistors can dissipate.
Applications: Conveyors, Belt-Driven and Gear Drive Equipment
63
Furnas Nordic Solid-State, The Furnas Nordic solid-state, reduced-voltage starter line has aReduced-Voltage Starters wide variety of products for different applications. Specific
controllers are available for 10 - 700 HP and voltages of 110/230VAC and 200 - 575 VAC. Nordic provides smooth, soft starts andstops. Contact your Siemens representative for additionalinformation on reduced voltage starters including Nordicproducts.
Review 61. ____________ - ____________ ____________ is a method
of providing multi-speed control that utilize taps broughtout from a reconnectable winding.
2. With ____________ ____________ the motor is startedat the lowest speed and automatically increments tothe selected speed.
3. In general, starting methods which deviate from full-voltage starting by providing a lower starting voltage arereferred to as ___________ ___________ ___________ .
4. ____________ reduced-voltage starters have adjustabletaps to reduce starting voltage to 50%, 65%, or 80% offull line voltage.
5. The Furnas ____________ is a solid-state, reduced-voltage starter.
64
Pilot Devices
A pilot device directs the operation of another device(pushbuttons and selector switches) or indicates the status ofthe operating system (pilot lights). This section discussesSiemens 3SB and Furnas Class 51/52 pushbuttons, selectorswitches, and pilot lights. 3SB0 devices are available in 22 mmand 30 mm diameters. Class 51/52 pilot devices are available in30 mm diameter only. The diameter refers to the size of theknockout hole required to mount the devices. Class 51 devicesare rated for hazardous locations environments such as Class I,Groups C and D and Class II, Groups E, F, and G. Class 52devices are heavy duty for harsh, industrial environments.
Bifurcated Contacts Whether one chooses the 3SB or the Class 51/52 pilot devices,the fine silver contacts have a 10 A/600 V continuous-currentrating and can be used on solid state equipment. The 3SB andthe Class 51/52 devices use bifurcated movable contacts. Thedesign of the bifurcated contacts provides four differentpathways for current to flow, thus improving contact reliability.
65
Pushbuttons A pushbutton is a control device used to manually open andclose a set of contacts. Pushbuttons are available in a flushmount, extended mount, with a mushroom head, illuminated ornonilluminated. Pushbuttons come with either normally open,normally closed, or combination contact blocks. The Siemens 22mm and 30 mm pushbuttons can handle up to a maximum of10 circuits. The Furnas 30 mm pushbutton can handle up to amaximum fo 16 circuits.
Normally Open Pushbuttons are used in control circuits to perform variousPushbuttons functions. For example, pushbuttons can be used when starting
and stopping a motor. A typical pushbutton uses an operatingplunger, a return spring, and one set of contacts. The followingdrawing illustrates a normally open (NO) pushbutton. Normallythe contacts are open and no current flows through them.Depressing the button causes the contacts to close. When thebutton is released, the spring returns the plunger to the openposition.
66
Normally Closed Normally closed (NC) pushbuttons, such as the one shownPushbuttons below, are also used to open and close a circuit. In the
pushbutton�s normal position the contacts are closed to allowcurrent flow through the control circuit. Depressing the buttonopens the contacts preventing current flow through the circuit.These types of pushbuttons are momentary contactpushbuttons because the contacts remain in their activatedposition only as long as the plunger is held depressed.
Pushbuttons are available with variations of the contactconfiguration. For example, a pushbutton may have one set ofnormally open and one set of normally closed contacts so thatwhen the button is depressed, one set of contacts is open andthe other set is closed. By connecting to the proper set ofcontacts, either a normally open or normally closed situationexists.
Using Pushbuttons in a The following line diagram shows an example of how aControl Circuit normally open and a normally closed pushbutton might be used
in a control circuit.
L1T1
T2
T3
L2
L3
OL
OL
OL
OL
M
M
M
Ma
MMotor
StartStop
67
Momentarily depressing the �Start� pushbutton completes thepath of current flow and energizes the �M� contactor�selectromagnetic coil.
L1T1
T2
T3
L2
L3
OL
OL
OL
OL
M
M
M
Ma
MMotor
StartStop
Holding Circuit This closes the associated normally open �M� and �Ma�Three-Wire Control contacts. When the �Start� pushbutton is released a holding
circuit exists to the �M� electromagnetic coil through theauxiliary contacts �Ma�. The motor will run until the normallyclosed �Stop� pushbutton is depressed, breaking the path ofcurrent flow to the �M� electromagnetic coil and opening theassociated �M� and �Ma� contacts. This is referred to as three-wire control because there are three wires or three connectionpoints required to connect the �Start� and �Stop� pushbuttonsand the holding circuit (�Ma�). An advantage to three-wirecontrol is low-voltage protection. If an overload causes the �OL�contacts in the control circuit to open, the �M� coil isdeenergized and the motor shut down. When the overload iscleared, the motor will not suddenly restart on its own. Anoperator must depress the �Start� button to restart the motor.
L1T1
T2
T3
L2
L3
OL
OL
OL
OL
M
M
M
Ma
MMotor
StartStop
68
Two-Wire Control In comparison, a two-wire control has only two connectionpoints for the �Start/Stop� circuit. When the contacts of thecontrol device close, they complete the coil circuit of thecontactor, causing it to be energized and connect the load to theline through the power contacts. When the contacts of thecontrol device open, the power is removed from the motor andit stops.
A two-wire control circuit provides low-voltage release but notlow-voltage protection. This means that in the event of a powerloss the contactor will deenergize, stopping the motor. This islow-voltage release. However, when power is restored, themotor will restart without warning if the control device is stillclosed. This type of control scheme is used for remote orinaccessible installations such as water-treatment plants orpumping stations. In these applications it is desireable to havean immediate return to service when power is restored.
L1T1
T2
T3
L2
L3
OL
OL
OL
OL
M
M
M
MMotor
Start/Stop
69
Selector Switches Selector switches are also used to manually open and closecontacts. Selector switches can be maintained, spring return orkey operated. Selector switches are available in two-, three-, andfour-position types. The basic difference between a push buttonand a selector switch is the operator mechanism. With aselector switch the operator is rotated to open and closecontacts. Contact blocks used on pushbuttons areinterchangeable with those on used on selector switches.Selector switches are used to select one of several circuitpossibilities such as manual or automatic operation, low or highspeed, up or down, right or left, and stop or run. The Siemens 22mm and 30 mm selector switches can handle up to a maximumof 10 circuits. The Furnas selector switch can handle up to amaximum of 16 circuits.
Two Position In the following example PL1 is connected to the power sourceSelector Switch when the switch is in position 1. PL2 is connected to the power
source when the switch is in position 2. In this circuit either PL1or PL2 would be on at all times. If there were only one load,then the selector switch could be used as an On/Off switch.
70
Contact Truth Tables There are two accepted methods of indicating contact positionof a selector switch in a circuit. The first method uses solid anddashed lines to denote contact position as shown in theprevious example. In the second method truth tables, alsoknown as target tables, are used. Each contact is marked with aletter. An �X� in the truth table indicates which contacts areclosed for a given switch position. In this example contact A isclosed, connecting PL1 to the power source, when the switch isin position 1. Contact B is closed, connecting PL2 to the powersource, when the switch is in position 2.
Three-Position A three-position selector switch can be used to select either oftwo sets of contacts or to disconnect both sets of contacts.Hand/Off/Auto is a typical application for a three-positionselector switch used for controlling a pump. In the Hand(manual) position the pump will start when the Start pushbuttonis pressed. The pump can be stopped by switching the switchto the Off position.The liquid level switch has no effect in eitherthe Hand or Off position. When the selector switch is set toAuto, the pump will be controlled by the liquid-level switch. At apredetermined level the liquid level switch closes, starting thepump. At a predetermined level the liquid level switch opens,stopping the pump.
71
Pilot Lights Pilot lights provide visual information at a glance of the circuit�soperating condition. Pilot lights are normally used for �ON/OFF�indication, caution, changing conditions, and alarm signaling.
Pilot lights come with a color lens, such as red, green, amber,blue, white, or clear. A red pilot light normally indicates that asystem is running. A green pilot light normally indicates that thesystem is off or deenergized. For example, a red pilot lightlocated on a control panel would give visual indication that amotor was running. A green pilot light would give visualindication that a motor was stopped.
RedPilot Light
GreenPilot Light
MotorRunning
MotorStopped
72
Using a Pilot Light in a In the following line diagram, a red pilot light is connected inControl Circuit parallel with the �M� electromagnetic coil.
L1 L2
OL
M
Ma
StartStop
R
When the coil is energized, the light will illuminate to indicatethe motor is running. In the event the pilot light burns out themotor will continue to run.
L1 L2
OL
M
Ma
StartStop
R
In the following line diagram a green pilot light is connectedthrough a normally closed �M� auxiliary contact (Mb). When thecoil is deenergized, the pilot light is on to indicate the motor isnot running.
L1 L2
OL
M
Ma
Mb
StartStop
G
73
Depressing the �Start� pushbutton and energizing the �M�contactor opens the normally closed �Mb� contacts, turning thelight off.
L1 L2
OL
M
Ma
Mb
StartStop
G
8WD43 Signalling Columns Signalling columns can be mounted locally on individualmachines, making it possible for the operating personnel tomonitor production stations from a distance. Individual modules,or elements, are connected together. Various visual elementsare available, including strobe lights, steady or flashing lights,and incandescent or LED lights. Lenses for the light elementsare available in red, yellow, green, blue, and clear. Audibleelements include a siren and a buzzer. In addition, acommunication element is available allowing the signallingcolumn to communicate with PLCs or computers through theActuator Sensor Interface (ASI) network. Up to 10 elements canbe used on a signalling column.
74
Review 71. A ____________ ____________ directs the operation of
another device.
2. Which of the following circuits represents a two-wirecontrol and which represents a three-wire control?
Start/Stop
StartStop
____ - Wire Control
____ - Wire Control
3. Pilot lights provide ____________ information of thecircuit�s operating condition.
4. A ____________ pilot light normally indicates a motor isrunning and a ____________ pilot light normally indicatesa motor is stopped.
75
Control Transformers
It is often desirable to operate the control circuit at a lowervoltage than the power circuit. Control transformers are used tostep a voltage down to a lower level. Siemens controltransformers are available in various primary and secondaryvoltages from 50 to 5000 VA.
Fuse Holder
In the following example, the power circuit is 460 VAC. A controltransformer is used to step the voltage down to 24 VAC for usein the control circuit. The electromagnetic coil voltage must berated for 24 VAC. Fuses on the primary and secondary windingsof the transformer provide overcurrent protection.
L1T1
T2
T3
L2
L3
OL
OL
OL
OL
M
M
M
Ma
MMotor
StartStop
460 VAC
24 VAC
24 VAC
Fuse
76
Control Relays
Relays are widely used in control circuits. They are used forswitching multiple control circuits and for controlling light loadssuch as starting coils, pilot lights, and audible alarms.
Relay Operation The operation of a control relay is similar to a contactor. In thefollowing example a relay with a set of normally open (NO)contacts is used. When power is applied from the controlcircuit, an electromagnetic coil is energized. The resultantelectromagnetic field pulls the armature and movable contactstoward the electromagnet closing the contacts. When power isremoved, spring tension pushes the armature and movablecontacts away from the electromagnet opening the contacts.
Stationary Contacts
Movable Contacts
Spring
Armature
Electromagnet
Control Signal
77
Contact Arrangement A relay can contain normally open, normally closed, or bothtypes of contacts. The main difference between a control relayand a contactor is the size and number of contacts. The contactsin a control relay are relatively small because they need tohandle only the small currents used in control circuits. There areno power contacts. Also, unlike a contactor, each contact in acontrol relay controls a different circuit. In a contactor, they allcontrol the starting and stopping of the motor. Some relayshave a greater number of contacts than are found in the typicalcontactor. The use of contacts in relays can be complex. Thereare three words which must be understood when dealing withrelays.
Pole Pole describes the number of isolated circuits that can passthrough the relay at one time. A single-pole circuit can carrycurrent through one circuit. A double-pole circuit can carrycurrent through two circuits simultaneously. The two circuits aremechanically connected so that they open or close at the sametime.
Throw Throw is the number of different closed-contact positions perpole. This is the total number of different circuits each polecontrols.
Single-Throw Double-Throw
Circuit 1
Circuit 1
Circuit 2
The following abbreviations are frequently used to indicatecontact configurations:
SPST Single-Pole, Single-ThrowSPDT Single-Pole, Double-ThrowDPST Double-Pole, Single-ThrowDPDT Double-Pole, Double-Throw
78
Break Break is the number of separate contacts the switch contactsuse to open or close individual circuits. If the switch breaks thecircuit in one place, it is a single-break. If the relay breaks thecircuit in two places, it is a double-break.
Single-Break Double-Break
The following illustrates various contact arrangements.
Single-PoleSingle-ThrowSingle-Break
Single-PoleDouble-ThrowSingle-Break
Double-PoleDouble-ThrowSingle-Break
Single-PoleSingle-ThrowDouble-Break
Single-PoleDouble-ThrowDouble-Break
Double-PoleSingle-ThrowDouble-Break
Double-PoleDouble-ThrowDouble-Break
Double-PoleSingle-ThrowSingle-Break
79
Interposing a Relay The following line diagram illustrates one way a control relaymight be used in a circuit. A 24 VAC coil may not be strongenough to operate a large starter. In this example theelectromagnetic coil of the �M� contactor selected is rated for460 VAC. The electromagnetic coil of the control relay (CR)selected is 24 VAC. This is known as interposing a relay.
OL
M
CR
CR
L1T1
T2
T3
L2
L3
OL
OL
OL
M
M
CR
MMotor
StartStop
460 VAC
24 VAC
1
2
When the �Start� pushbutton in line 2 is momentarilydepressed, power is supplied to the control relay (CR).
OL
M
CR
CR
L1T1
T2
T3
L2
L3
OL
OL
OL
M
M
CR
MMotor
StartStop
460 VAC
24 VAC
1
2
80
The �CR� contacts in lines 1and 2 close. The �CR� contacts inline 2 maintain the start circuit. The �CR� contacts in line 1complete the path of current to the �M� motor starter. The �M�motor starter energizes and closes the �M� contacts in thepower circuit, starting the motor. Depressing the �Stop�pushbutton deenergizes the �CR� relay and �M� motor starter.
OL
M
CR
CR
L1T1
T2
T3
L2
L3
OL
OL
OL
M
M
CR
MMotor
StartStop
460 VAC
24 VAC
1
2
Sirius 3RH11 Control Relays Siemens has a complete line of industrial-control relays. Sirius3RH11 relays are available with screw terminal or Cage Clamp.The screw terminal version is shown in the following illustration.Four contacts are available in the basic device. Four additionalcontacts in the form of a snap-on device can be added to thefront of the relay. Some Sirius 3RH11 relays are specificallydesigned to interface directly with PLCs and other solid-statecontrol devices. Sirius 3RH11 relays are rated for switching bothAC and DC circuits. Coil voltages range from 12 VDC to 230VDC and 24 VAC to 600 VAC.
81
Class 46 Machine- Furnas Class 46 machine-tool relays are available with coilTool Relay voltages from 12 VDC to 250 VDC, and 24 VAC to 600 VAC.
Relays with two, three, or four poles may be expanded up toeight poles with an adder deck. Standard, gold flashed, andoverlapping contacts are rated at 10 amperes. Master contactsare rated at 20 amperes.
Class 46 machine-tool relay contacts can be field changedbetween normally open (NO) and normally closed (NC).
82
Class 46 Industrial- Class 46 industrial-control relays are used in a wide variety ofControl Relays applications including assembly, packaging, and material
handling systems. The basic unit consists of four poles, butadditional top-mounted adder decks and snap on side mountsallow for a maximum of 12 poles per relay. Class 46 relays areavailable with coil voltages up to 600 VAC.
General-Purpose Relays Siemens also manufactures a variety of general-purpose relays(Plug-In Relays) for socket and flange mounting. Coil voltages are available in 24
VAC, 120 VAC or 24 VDC. The biggest benefit of this type ofrelay is all the wiring stays in place with the socket if the relayneeds to replaced with a new one.
83
Timing Relays
Timing relays, such as the Sirius 3RP timing relays, are used incontrol switching operations involving time delay. Sirius 3RP1timing relays have timing ranges available from .05 seconds to10 hours. Sirius 3RP15 have timing ranges from .05 seconds to100 hours.
Time Delay A timing relay has two major functions: On-delay and Off-delaytiming. An arrow is used to denote the function of the timer. Anarrow pointing up indicates an On-delay timing action. An arrowpointing down indicates an Off-delay timing action.
84
On-delay and Off-delay timers can turn their connected loads onor off, depending on how the timer�s output is wired into thecircuit. On-delay indicates that once a timer has received asignal to turn on, a predetermined time (set by the timer) mustpass before the timer�s contacts change state. Off-delayindicates that once a timer has received a signal to turn off, apredetermined time (set by the timer) must pass before thetimer�s contacts change state.
On-Delay, Time Closed The following is an example of On-delay, timed closed. For thisexample a set of normally open (NO) contacts is used. This isalso referred to as normally open timed closed (NOTC). Thetiming relay (TR1) has been set for an On-delay of 5 seconds.
L1 L2
PL1
TR1S1
TR1
When S1 is closed, TR1 begins timing. When 5 seconds haselapsed, TR1 will close its associated normally open (NO) TR1contacts, illuminating pilot light PL1. When S1 is open,deenergizing TR1, the TR1 contacts open immediately,extinguishing PL1.
L1 L2
PL1
TR1S1
TR1Closes 5 SecondsAfter S1 Is Closed
85
On-Delay, Timed Open The following is an example of On-delay, timed open. For thisexample a set of normally closed (NC) contacts is used. This isalso referred to as normally closed, timed open (NCTO). PL1 isilluminated as long as S1 remains open. The timing relay (TR1)has been set for an ON delay of 5 seconds.
L1 L2
PL1
TR1S1
TR1
When S1 is closed, timing relay TR1 is energized. After a timeddelay of 5 seconds, the associated normally closed TR1contacts open, extinguishing PL1. When S1 is open,deenergizing TR1, the TR1 contacts close immediately,illuminating PL1.
L1 L2
PL1
TR1S1
TR1Opens 5 SecondsAfter S1 Is Closed
Off-Delay, Timed Open The following is an example of Off-delay, timed open. For thisexample a set of normally open contacts (NO) is used. This isalso referred to as normally open, timed open (NOTO). Thetiming relay (TR1) has been set for an off delay of 5 seconds.Closing S1 energizes TR1 causing its associated normally openTR1 contacts to close immediately, illuminating PL1.
L1 L2
PL1
TR1S1
TR1
L1 L2
PL1
TR1S1
TR1
86
When S1 is opened, TR1 begins timing. When 5 seconds haselapsed, TR1 will open its associated normally open contacts,extinguishing pilot light PL1.
L1 L2
PL1
TR1S1
TR1Opens 5 SecondsAfter S1 Is Opened
Off-Delay, Timed Closed The following is an example of Off-delay, timed closed. For thisexample a set of normally closed (NC) contacts is used. This isalso referred to as normally closed, timed closed (NCTC). Thetiming relay (TR1) has been set for 5 seconds. PL1 is on.Closing S1 energizes TR1 causing its associated contacts toopen immediately, extinguishing PL1.
L1 L2
PL1
TR1S1
TR1
L1 L2
PL1
TR1S1
TR1
When S1 is opened, timing relay TR1 is deenergized. After 5seconds, the associated normally closed contacts close,illuminating PL1.
L1 L2
PL1
TR1S1
TR1Closes 5 SecondsAfter S1 Is Opened
87
Instantaneous Contacts Timing relays can also have normally open or normally closedinstantaneous contacts. In the following example, when switchS1 is closed, the TR1 instantaneous contacts will closeimmediately, illuminating PL1. After a preset time delay the TR1timing contacts will close, illuminating PL2.
L1 L2
PL1
PL2
TR1S1
TR1
TR1(INST)
Review 81. ___________ is the total number of different circuits
each pole controls.
2. ___________ describes the number of isolated circuitsthat can pass through a relay at one time.
3. An SPDT relay has ___________ pole(s) and____________ closed contact position(s).
4. A timing relay that has received a signal to turn on, andthen delays a predetermined amount of time before anaction takes place is referred to as ____________ delay.
88
Limit Switches
Position-Sensing Devices One type of feedback that is frequently needed by industrial-control systems is the position of one or more components ofthe operation being controlled. Position-sensing devicesprovide information on the presence or absence of an object byopening or closing an electrical circuit. This information is usedto determine when to start, stop, reverse, slow down or speedup a process. Siemens position-sensing devices include limitswitches, photoelectric control, inductive and capacitiveproximity switches, and ultrasonic sensors. TAG (TechnicalApplication Guides) sheets for sensing devices are availablefrom your Siemens sales representative.
Limit Switches One type of position-sensing device is a limit switch. Thestandard limit switch is mechanical and uses physical contact todetect the presence of an object. When the object to bedetected comes in contact with the actuator (lever), it movesthe actuator to a point where the mechanical contacts changestate. Through this action an electrical circuit is energized or de-energized. When the object no longer makes contact with theactuator, the mechanical contacts return to their original state,either opened or closed. This is a momentary operation.
89
Limit Switch Used in a In the following diagram, a limit switch (LS1) has been placed inControl Circuit series with the �M� contactor. The motor has been started and
is running.
L1
L2
L3
OL
OL
OL
OL
M
M
M
Ma
MMotor
StartStop
LS1
When the object to be detected comes in contact with theactuator, the limit switch will open. The �M� contactor is de-energized and the motor stops. The motor can be manuallyrestarted when the object is no longer in contact with theactuator and the limit switch is closed.
L1
L2
L3
OL
OL
OL
OL
M
M
M
Ma
MMotor
StartStop
LS1
90
Principle of Operation The limit switch design in the following illustration uses anactuator to move a set of movable contacts to a set of stationarycontacts. A number of positions must be considered when anobject comes in contact with the actuator arm.
The free position is the position of the actuator when noexternal force is applied.
Pretravel is the distance or angle traveled in moving the actuatorfrom the free position to the operating position.
The operating position is where contacts in the limit switchchange from their normal state (NO or NC) to their operatedstate.
Overtravel is the distance the actuator can travel safely beyondthe operating point.
Differential travel is the distance traveled between the pretraveland the release position.
The release position is where the contacts change from theiroperated state to their normal state.
Release travel is the distance traveled from the release positionto the free position.
Overtravel
PretravelFree Position
Differential Travel
Release Travel
Operating Position
Release Position
91
Types of Actuators Several styles of limit switches and actuators are available,some of which are shown below. The contacts of a momentaryswitch return from their operated state to their normal statewhen the operating force is removed. There is also amaintained switch. The actuator is typically a �fork� design. Theactuator and mechanical contacts remain in the operated stateafter the operating force is removed. The actuator andmechanical contacts return to their original state when anoperating force is applied in the opposite direction. Limitswitches are also available with slow-action contacts or snap-action contacts. The speed of the slow-action contact make/break action is dependent on the speed of the actuator. Thespeed of the snap-action contact make/break action isindependent of the operating speed.
Plunger FlexibleLoop
SpringRod
AdjustableRod
AdjustableRollerCrank
Fork
For more information on mechanical limit switches refer to TAGCP1403.
92
Pressure Switches
Pressure switches are control devices that respond to changesin pressure of liquid or air. The liquid or air is referred to as fluidpressure. They open or close electrical contacts in response topressure changes by either turning on or off a motor, opening orclosing louvers, or signaling a warning light or horn. For loads upto 5 HP the pressure switches may handle the current directly.For larger loads the pressure switch is used to energize relays,contactors, or motor starters, which then energize the load.
Pressure Switch The basic components of a pressure switch are illustratedComponents below. Electrical contacts are operated by the movement of a
diaphragm against the force of a spring. The contacts maybe normally open (NO) or normally closed (NC). The springsetting determines how much fluid pressure is required tooperate the contacts.
93
Application Pressure switches are frequently used to maintain a specifiedpressure range in a storage tank. Storage tanks can be used tohold a liquid, such as water, or a gas, such as air.
Operation In this example a normally closed pressure switch is used. Thepump starts as soon as power is applied to the circuit. When thepressure in the storage tank has reached a predetermined level,the contacts in the pressure switch open, removing power fromthe pump motor. As the contents of the storage tank are used,the pressure in the tank decreases. At a predetermined levelthe pressure switch will close its contacts, applying power tothe pump motor.
94
Pressure Range Pressure switches are designed to operate within a specifiedpressure range, usually given in pounds per square inch (PSI). Inthe following example, a Furnas Class 69ES water pressureswitch operates within a range of 10 to 80 PSI. The minimumclose, or cut-in pressure, is 10 PSI. This is the point at whichfluid pressure on the diaphragm causes the contacts to close.The maximum open, or cut-out pressure, is 80 PSI. This is thepoint at which fluid pressure on the diaphragm causes thecontacts to open. Pressure differential is the difference betweenthese two settings. The Furnas Class 69ES pressure switch canhave a differential range of 15-25 PSI. In this example the cut-inpressure has been set to 30 PSI. The cut-out pressure has beenset to 50 PSI. The pressure differential is 20 PSI. The pressureswitch will regulate the pressure between 30 and 50 PSI.
Reverse Action Reverse action pressure switches cut-in on a rising pressure.They are designed to ground the ignition on gas engine drivenpumps and compressors when the maximum pressure hasbeen reached. In the following example a Furnas Class 69WR5reverse action pressure switch has been selected. The 69WR5has a minimum open (cut-out) of 10 PSI and a maximum close(cut-in) of 80 PSI. The differential is set so that the switch opensat 30 PSI and closes at 50 PSI.
95
Photoelectric Control
A photoelectric sensor is another type of position sensingdevice. Photoelectric sensors, similar to the one shown below,use a modulated infrared light beam that is either broken orreflected by the object to be detected. The control consists ofan emitter (light source), a receiver to detect the emitted light,and associated electronics that evaluate and amplify thedetected signal causing the photoelectric�s output switch tochange state. Unlike limit switches, photoelectric sensorsoperate without physical contact (no touch control).
Limit SwitchStyle Housing
Thru Scan A scan technique is a method used by photoelectric devices fordetecting objects. There are two basic scan techniques, thruscan and reflective scan. Thru scan is also referred to as beambreak, thru beam, transmitted beam, and opposed. Light from anemitter is transmitted in a straight line to a separate receiver.The receiver converts the light into electrical energy. An objectplaced in the path of the light beam blocks the light from theemitter causing the receiver�s output to change state. When theobject no longer blocks the light path, the receiver�s outputreturns to its normal state. The maximum sensing range is300 feet.
96
A photoelectric sensing device, for example, might bepositioned over a roll of paper. When the roll on the winderreaches a predetermined diameter, it will interrupt the lightbeam and automatically stop the motor.
Reflective Scan Reflective scan is also referred to as retroreflective. Thephotoelectric sensor contains both the emitter and the receiver.Light from the emitter is transmitted in a straight line to aretroreflective target and returns to the receiver along the sameoptical axis. When an object blocks the path of light, the outputchanges state. When the object no longer blocks the light path,the output returns to its normal state. The maximum sensingrange is 35 feet.
Sensor SensorRetroreflector
Light PathLight
Blocked
Object
Receiver
Emitter
97
Polarized Reflective Scan A variation of reflective scan is polarized reflective scan.Polarizing filters are placed in front of both the emitter andreceiver lens. The filters are oriented such that the planes oforientation are at 90 degrees to one another. The emitted light ispolarized horizontally. Reflected light from a corner cuberetroreflector is depolarized sufficiently to allow reflected lightto pass through the polarizing filter into the receiver. Lightreflected from a shiny surface is not depolarized and thereflected light is blocked from entering the receiver by thepolarizing filter. The maximum sensing range is 15 feet.
Diffuse Reflective Scan Another reflective technique is diffuse reflective. Light from theemitter strikes the object to be detected and the light is diffusedfrom the surface of the object at all angles. If the receiverreceives enough reflected light, the load will energize. When nolight is reflected back to the receiver, the load returns to itsoriginal state. The maximum sensing range is 40 inches.
98
Operating Modes There are two basic operating modes, dark operate (DO) andlight operate (LO). Dark operate is an operating mode in whichthe load is energized when light from the emitter is absent fromthe receiver.
Light operate is an operating mode in which the load isenergized when light from the emitter reaches the receiver.
The following chart shows the relationship between theoperating mode and load status:
OperatingMode
Light Path
Load Status
Thru Scan andRetroreflective
DiffuseReflective
Not Blocked
Blocked
Not Blocked
Blocked
Energized
Deenergized
Deenergized
Energized
Deenergized
Energized
Energized
Deenergized
Light Operate(LO)
Dark Operate(DO)
99
Fiber Optics Fiber optics is not a scan technique, but another method fortransmitting light. The maximum sensing distance is 25.5inches. Fiber optics can be used with thru scan, reflective scan,or diffuse reflective scan depending on the fiber optic cableselected.
100
Review 91. The part of the limit switch the object to be detected
comes in contact with is known as the ____________ .
2. ____________ is the distance the actuator travels fromthe free position to the operating position.
3. The liquid or air pressure that operates against thediaphragm of a pressure switch is referred to as____________ pressure.
4. ____________ ____________ is a scan technique usinga separate emitter and receiver in which, when anobject blocks a light beam, the sensor�s output changesstate.
5. When light from the emitter is absent from the receiverand the receiver�s output changes state, the switch isoperating in the ____________ ____________.
6. ____________ ____________ is an operating mode inwhich the load is energized when light from the emitteris incident on the receiver.
101
Inductive Proximity Switches
Another type of position sensing device is the inductiveproximity switch. The Siemens line of proximity switches carriesthe trademark BERO® which stands for Bounce-free Eddycurrent Radio frequency Oscillator. Unlike limit switches,inductive proximity switches require no physical contact withthe object to be detected.
Inductive Proximity Inductive proximity switches only detect conductive metalSwitches objects. An electromagnetic field emanates from the sensing
face to detect the presence or absence of a metal object. Whena metal object enters the field, the object is detected and theoutput switch changes state. When the object leaves theelectromagnetic field, the output switch returns to its originalstate. Depending on the device, inductive proximity switcheshave a maximum sensing range of 2.5 inches.
ElectromagneticField
ElectricalCoil
Object To Be Detected
102
Mounting Depending on the specific device, there are two waysinductive proximity switches are mounted. Some devices areshielded and may be embedded in metal flush with theirsensing face without adversely affecting their sensingcharacteristics. Other devices are unshielded and require a freezone around their sensing face.
Free Zone
Flush Mounting(Shielded)
Non-Flush Mounting(Unshielded)
Response Characteristic Proximity switches respond to an object only when it is in adefined area in front of the switch�s sensing face. The shape ofthis response area is called the response characteristic of theswitch.
ObjectResponse
Characteristic
SensingFace
ReferenceAxis
103
The point at which the proximity switch recognizes an incomingobject is the operating point. The point at which an outgoingobject causes the device to switch back to its normal state iscalled the release point. The area between these two points iscalled the hysteresis zone.
Object Object
OperatingPoint
ReleasePoint
Hysteresis
Response Curve The size and shape of the response characteristic varies withthe size and shape of the switch. The following graph shows theresponse characteristic of one type of proximity switch.
1
0.8
0.6
0.4
0.2
012mm mm
-x 1 2+x
ymm
Reference Axis
Locus OfOperating Points
Categories Inductive proximity switches are available in eight categoriesfrom standard duty to submersible. They are also available invarious sizes and styles. Refer to Siemens Pricing and SelectionGuide, PC8000, for the description and application of each type.
104
Output Siemens inductive proximity switch product lines include AC,DC and AC/DC (universal voltage) models. Direct currentmodels are typically three-wire devices requiring a separatepower supply.
Some DC models and universal-voltage models are two-wiredevices which can be used with DC or AC circuits. A separatepower supply is also required. These models can be connectedto such control devices as contactors because of their ability toproduce output currents up to 500 milliamps, and they can alsobe used with programmable controllers.
105
Applications Inductive proximity switches have a number of uses. In thisexample, an inductive proximity switch is used for counting orsorting bottles by detecting the metal bottle cap.
Sensing Device
Short switching times allow it to perform high-speed countingfor speed monitoring.
Sensing Device
106
Capacitive Proximity Switches
Capacitive proximity switches are similar to inductive proximityswitches. The main difference between the two types is that acapacitive proximity switch produces an electrostatic fieldinstead of an electromagnetic field. Capacitive proximityswitches will sense metal and also nonmetallic materials suchas paper, glass, liquids, and cloth.
Best Suited For There are two types of capacitive sensors: best suited forNonconductive Material nonconductive materials and best suited for conductive
materials. Capacitive proximity switches best suited fornonconductive materials can be used with materials suchas glass, plastic, cloth, wood, and paper. This type of sensor willalso detect conductive material. Care must be taken to ensurethat this type of sensor is used in a dry environment. Liquid onthe sensing surface could cause the sensor to operate. Thesedevices may be flush mounted without adversely affecting theirsensing characteristics.
107
Best Suited For Capacitive proximity switches best suited for conductiveConductive Material material can be used with materials such as copper, aluminum,
brass, steel, and conductive fluids. Formation of liquid on thesensing surface is generally not a problem. These devicesrequire a free zone around the sensing face.
Detection Through One application for capacitive proximity switches is liquid levela Barrier or solid level detection. For example, a proximity switch could
be used to detect the liquid or solid level of material inside abarrier or container.
Sensing Device
Barrier
Material To Be Detected
108
The following chart illustrates the proper capacitive proximityswitch when detecting material through a barrier.
Correction Factors Sensing distance varies with different types of material to bedetected. The rated operating distance for a specific sensor isgiven in the PC8000 catalog. To determine the actual sensingdistance, multiply the rated operating distance times thecorrection factor for the material selected. The following chartgives typical correction factors.
For example, if the rated operating distance for a best suited fornonconductive sensor is 15 mm, and the material to bedetected is glass, the sensing distance is 10.5 mm (15 x 0.7).
109
Ultrasonic Sensors
Ultrasonic sensors use a transducer to send and receive highfrequency sound signals. When an object to be detected entersthe beam, the sound is reflected back to the switch, causing it toenergize or deenergize the output circuit.
Principle of Operation The SONAR-BERO® uses a piezoelectric ceramic disk whichcan transmit and receive high-frequency pulses. A high-frequency voltage is applied to the disk, causing it to vibrate atthe same frequency. The vibrating disk produces high-frequencysound waves. When transmitted pulses strike a sound-reflectingobject, echoes are produced. These echoes are received by thetransducer and transformed into electrical signals. When theobject to be detected enters the preset operating range, theoutput of the switch changes state. When the object leaves thepreset operating range, the output returns to its original state.
Transmitted Sound Waves Echo Sound Waves
Object To Be Detected
110
Applications Typical applications for the SONAR-BERO include level sensing,spacing and height differentiations, object sensing, andcounting. In the following example a sensing device detects theheight and spacing of packages on a conveyor.
Sensing Device
111
LOGO! Logic Module
LOGO! is a logic module used to perform control tasks. Themodule is compact and user friendly, providing a cost-effectivesolution for the end user.
Hard-Wired Control In the past, many of these control tasks were solved withcontactor or relay controls. This is often referred to as hard-wiredcontrol. Circuit diagrams had to be designed and electricalcomponents specified and installed. A change in controlfunction or system expansion could require extensivecomponent changes and rewiring.
112
Many of the same tasks can be performed with LOGO!. Initialhard-wiring, though still required, is greatly simplified.Modifying the application is as easy as changing the programvia the keypad located on the front of the LOGO!. Likewise,control programs can be created and tested beforeimplementation via a PC software program. Once the program isperforming per specification, the transfer to LOGO! is as simpleas plugging in a cable.
Basic LOGO! Operation LOGO! accepts a variety of digital inputs, such as pushbuttons,switches, and contacts. LOGO! makes decisions and executescontrol instructions based on the user-defined program. Theinstructions control various outputs. The outputs can beconnected to virtually any type of load such as relays,contactors, lights, and small motors.
Design Features LOGO! is available in many different versions for different supplyvoltages (12 VDC, 24 VDC, or 115/230 VAC).
All models have:
� Relay outputs with maximum 8 amp or 10 amp outputcurrent (not LOGO! 24/24L models)
� Integrated display� Integrated keypad� Integrated basic and special functions� Integrated EEPROM for storing programs and setpoints� Optional program module� Basic AND, OR, NOT, NAND, NOR, and XOR functions� Special ON delay, latching ON delay, OFF delay, pulse
relay, latching relay, clock pulse generator, and counter (up/down) functions
The basic versions feature:
� Six digital inputs, four digital outputs� Integral clock (LOGO! 230RC, 24RC)
113
The L models feature:
� Twelve digital inputs, eight digital outputs� Four additional inputs and outputs on the AS-interface
modules� Impulse relay� Elapsed time meter� Six-digit counter (instead of four-digit counter)� Retentivity for counters, operating-hours counter, impulse
relay, and latching in conjunction with the optional programmodule with retentivity
� �Know-how� protection with the optional program modulefor copy protection and retentivity
Review 101. Inductive proximity switches can only detect
____________ objects.
2. The point at which the proximity switch recognizes anincoming object is the ____________ point.
3. ____________ proximity switches can be used to detectmetal objects and nonconductive objects.
a. Inductive b. Capacitive
4. A type of proximity switch which uses a transducer tosend and receive high-frequency sound signals is the____________ proximity switch.
114
Review Answers
Review 1 1) manually; 2) a; 3) b; 4) b; 5) c.
Review 2 1) left to right; 2) A - Node, B - Power Wiring, C - Power Load,D- Control Wiring; E - Control Device; F - Control Load.
Review 3 1) a; 2) excess; 3) overload; 4) a; 5) bimetal.
Review 4 1) 2; 2) LVP; 3) 10, 5; 4) 20; 5) motor starter.
Review 5 1) NEMA, IEC; 2) 5; 3) AC3; 4) 4; 5) 3; 6) 50; 7) 3UA66.
Review 6 1) Consequent-pole motor; 2) progressive control; 3) reduced-voltage starting; 4) Autotransformer; 5) Nordic.
Review 7 1) pilot device; 2) Three-Wire Control, Two-Wire Control; 3)visual; 4) red, green.
Review 8 1) Throw; 2) Pole; 3) one, two; 4) ON.
Review 9 1) actuator; 2) Pretravel; 3); fluid; 4) Thru Scan; 5) Dark Operate;6) Light Operate.
Review 10 1) metal; 2) operate; 3) Capacitive; 4) ultrasonic
115
Final Exam
The final exam is intended to be a learning tool. The book maybe used during the exam. A tear-out answer sheet is provided.After completing the test, mail in the answer sheet for grading. Agrade of 70% or better is passing. Upon successful completionof the test a certificate will be issued.
Questions 1. Contacts are shown on a line diagram in their____________ state.
a. normally closed b. normally openc. energized d. deenergized
2. A motor that is running would usually be indicated by a____________ pilot light.
a. green b. redc. amber d. white
3. Which of the following symbols represents a normallyclosed, timed open (NCTO) contact?
a. b.
c. d.
4. With an increase of current, temperature will____________ .
a. decrease b. increasec. remain the same d. increase and decrease
5. The two circuits involved in the operation of a contactor are the ____________ circuits.
a. power and controlb. power and armaturec. control and electromagneticd. control and starter
116
6. A motor starter is a combination of a/an ____________ .
a. electromagnet and armatureb. contactor and electromagnetc. contactor and overload relayd. overload relay and instantaneous contacts
7. Which of the following is not part of a contactor?
a. armatureb. electromagnetic coilc. overcurrent sensing deviced. stationary contacts
8. One reason reduced-voltage starting may be used tostart a motor is to ____________ .
a. apply torque graduallyb. increase starting torquec. get motor to full speed fasterd. run the motor at a lower speed
9. A type of speed selection control that requires theoperator to manually increment through each speedstep to get to the desired speed is ____________control.
a. selective b. compellingc. progressive d. consequent pole
10. The organization primarily concerned with the rating ofcontactors and starters used in many countries,including the U.S. is ____________ .
a. NEMA b. ULc. ICS d. IEC
11. The proper overload relay for a World Series3TF50 contactor is ____________ .
a. 3UA50 b. 3UA54c. 3UA58 d. 3UA60
12. A device used to provide visual information of thecircuit�s operating condition is a ____________ .
a. pushbutton b. selector switchc. proximity switch d. pilot light
117
13. A relay that has two isolated circuits and one closedcontact position per pole is a ____________ .
a. DPST b. DPDTc. SPST d. SPDT
14. The type of position sensing switch that requiresphysical contact to detect the presence of an object isa/an ____________ .
a. limit switch b. photoelectric sensorc. proximity switch d. ultrasonic sensor
15. The distance the actuator arm can travel safely beyondthe operating point is referred to as ____________ .
a. pretravel b. overtravelc. forced travel d. normal travel
16. The maximum sensing distance of a photoelectricsensor using the thru scan technique is ____________ .
a. 100 feet b. 200 feetc. 300 feet d. 500 feet
17. Furnas INNOVA PLUS� starters are available up to____________ HP.
a. 25 b. 50c. 100 d. 250
18. Sirius Type 3R motor starters are available for loads up to___________ amps.
a. 95 b. 135c. 200 d. 270
118
19. In the following diagram, the motor will stop when____________ .
a. the �Stop� button is depressedb. limit switch �LS1� opensc. the motor overload contact opensd. all of the above
L1
L2
L3
OL
OL
OL
OL
M
M
M
Ma
MMotor
StartStop
LS1
20. If the rated operating distance for a best suited fornonconductive sensor is 15 mm and the material tobe detected is wood, the sensing distance is____________ mm.
a. 15 b. 10.5c. 7.5 d. 6
119
Notes
120
Notes