Symmetrical Fault Calculations Symmetrical Fault Calculations

Transcript of Symmetrical Fault Calculations -...

Page 1: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Symmetrical Fault CalculationsSymmetrical Fault Calculations

Page 2: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 1Example 1

34.5kV

SCC = 1200 MVA

10/12.5 MVA6%

13.8 kV

F

Calculate the fault current at F

Page 3: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 1Example 1

10/12.5 MVA6%

F

13.8 kV

Calculate the fault current at F

A55.2898kV5.34

MVA100kV

MVAI

ohms9.11100

5.34

MVAkV

Z

5.34kV100MVA

base

basebase

2base

2base

base

base

base

=

==

==

=

==

Step 1: Calculate Base Values34.5kV

SCC = 1200 MVA

Page 4: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 1Example 1

10/12.5 MVA6%

F

13.8 kV

Calculate the fault current at F

48.05.12

100x06.0

MVAMVA

xZZoldbase

basetTpu

==

=

Step 2: Calculate p.u impedances34.5kV

SCC = 1200 MVA

Page 5: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 1Example 1

10/12.5 MVA6%

F

13.8 kV

Calculate the fault current at F

48.05.12

100x06.0

MVAMVA

xZZoldbase

basetTpu

==

=

Step 2: Calculate p.u impedances

0833.05.345.34

x1200100

kVkV

xMVAMVA

Zbase

oldbase

oldbase

baseutility

=

=

=

34.5kV

SCC = 1200 MVA

Page 6: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 1Example 1

10/12.5 MVA6%

F

13.8 kV

Calculate the fault current at F

pu775.10833.048.0

0.1Z

VI

total

puFpu

=+

=

=

Step 3: Calculate fault current34.5kV

SCC = 1200 MVA

Page 7: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 1Example 1

10/12.5 MVA6%

F

13.8 kV

Calculate the fault current at F

pu775.10833.048.0

0.1Z

VI

total

puFpu

=+

=

=

Step 3: Calculate fault current

A7426

5.34x8.13

II

A29703

55.2898x775.1

3

IxII

FHVFLV

baseFpuFHV

=

=

==

=

34.5kV

SCC = 1200 MVA

Page 8: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 2 Example 2 –– Addition of a GeneratorAddition of a Generator

34.5kV

SCC = 1200 MVA

10/12.5 MVA6% 5MVA

Xd”=0.12

13.8 kV

F

Calculate the fault current at F

Page 9: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 2 Example 2 –– Addition of a GeneratorAddition of a Generator

0833.05.345.34

x1200100

kVkV

xMVAMVA

Zbase

oldbase

oldbase

baseutility

=

=

=Step 1: Calculate impedances

34.5kV

SCC = 1200 MVA

10/12.5 MVA6% 5MVA

Xd”=0.12

13.8 kV

F

Calculate the fault current at F

Page 10: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 2 Example 2 –– Addition of a GeneratorAddition of a Generator

48.05.12

100x06.0

MVAMVA

xZZoldbase

basetTpu

==

=

0833.05.345.34

x1200100

kVkV

xMVAMVA

Zbase

oldbase

oldbase

baseutility

=

=

=Step 1: Calculate impedances

34.5kV

SCC = 1200 MVA

10/12.5 MVA6% 5MVA

Xd”=0.12

13.8 kV

F

Calculate the fault current at F

Page 11: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 2 Example 2 –– Addition of a GeneratorAddition of a Generator

48.05.12

100x06.0

MVAMVA

xZZoldbase

basetTpu

==

=

0833.05.345.34

x1200100

kVkV

xMVAMVA

Zbase

oldbase

oldbase

baseutility

=

=

=Step 1: Calculate impedances

34.5kV

SCC = 1200 MVA

10/12.5 MVA6% 5MVA

Xd”=0.12

13.8 kV

4.25

100x12.0

MVAMVA

xZZoldbase

baseGGpu

==

=F

Calculate the fault current at F

Page 12: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 2 Example 2 –– Addition of a GeneratorAddition of a Generator

Step 2: Calculate equivalent impedances34.5kV

SCC = 1200 MVA1.0V

10/12.5 MVA6%

F

13.8 kV

Calculate the fault current at F

5MVAXd

”=0.12

0.0833Zutility ZGpu2.4

ZTpu 0.48

Page 13: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 2 Example 2 –– Addition of a GeneratorAddition of a Generator

Step 2: Calculate equivalent impedances

456.04.25633.04.2*5633.0

ZEq =+

=1.0V

0.456

0.0833

Zutility

2.4

ZTpu 0.48

ZGpu

Page 14: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 2 Example 2 –– Addition of a GeneratorAddition of a Generator

Step 3: Calculate fault current

456.04.25633.04.2*5633.0

ZEq =+

=1.0V

0.456

pu192.2456.00.1

Z

VI

Eq

puFpu ===

0.0833

Zutility

2.4

ZTpu 0.48

ZGpu

Page 15: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 2 Example 2 –– Addition of a GeneratorAddition of a Generator

Step 3: Calculate fault current

456.04.25633.04.2*5633.0

ZEq =+

=1.0V

0.456

pu192.2456.00.1

Z

VI

Eq

puFpu ===

0.0833

Zutility

2.4

ZTpu 0.48

ZGpu

A9170

5.34x8.13

II

A36683

55.2898x192.2

3

IxII

FHVFLV

baseFpuFHV

=

=

==

=

Page 16: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 1 & 2 ComparisonExample 1 & 2 Comparison

34.5kV

SCC = 1200 MVA

34.5kV

10/12.5 MVA6%

F

13.8 kV

5MVAXd

”=0.12

IF =9170 Amps

SCC = 1200 MVA

10/12.5 MVA6%

13.8 kV

F

IF =7426 Amps

Page 17: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 3 Example 3 ––Presence of transformer & motorPresence of transformer & motor

34.5kV

SCC = 1200 MVA

10/12.5 MVA6%

5MVAXd

”=0.12

13.8 kV

F 3 MVA5%

2.4 kV

M 2500 HPXd

”=0.17

Calculate the fault current at F

Page 18: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 3 Example 3 ––Presence of transformer & motorPresence of transformer & motor

0833.05.345.34

x1200100

kVkV

xMVAMVA

Zbase

oldbase

oldbase

baseutility

=

=

=Step 1: Calculate impedances

34.5kV

SCC = 1200 MVA

10/12.5 MVA6%

5MVAXd

”=0.12

13.8 kV

F 3 MVA5%

2.4 kV

M 2500 HPXd

”=0.17

Calculate the fault current at F

Page 19: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 3 Example 3 ––Presence of transformer & motorPresence of transformer & motor

0833.05.345.34

x1200100

kVkV

xMVAMVA

Zbase

oldbase

oldbase

baseutility

=

=

=

48.05.12

100x06.0

MVAMVA

xZZoldbase

baset1Tpu

==

=

Step 1: Calculate impedances34.5kV

SCC = 1200 MVA

10/12.5 MVA6%

5MVAXd

”=0.12

13.8 kV

F 3 MVA5%

2.4 kV

M 2500 HPXd

”=0.17

Calculate the fault current at F

Page 20: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 3 Example 3 ––Presence of transformer & motorPresence of transformer & motor

0833.05.345.34

x1200100

kVkV

xMVAMVA

Zbase

oldbase

oldbase

baseutility

=

=

=

48.05.12

100x06.0

MVAMVA

xZZoldbase

baset1Tpu

==

=

Step 1: Calculate impedances34.5kV

SCC = 1200 MVA

10/12.5 MVA6%

5MVAXd

”=0.12

13.8 kV

F 3 MVA5%

2.4 kV

4.25

100x12.0

MVAMVA

xZZoldbase

baseGGpu

==

=M 2500 HP

Xd”=0.17

Calculate the fault current at F

Page 21: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 3 Example 3 ––Presence of transformer & motorPresence of transformer & motor

pu4.2Z

pu48.0Z

pu0833.0Z

Gpu

1Tpu

utility

=

=

=Step 1: Calculate impedances34.5kV

SCC = 1200 MVA

10/12.5 MVA6%

5MVAXd

”=0.12

F

13.8 kV

Calculate the fault current at F

667.13

100x05.0

MVAMVA

xZZoldbase

baset2Tpu

==

=

3 MVA5%

2.4 kV

M 2500 HPXd

”=0.17

Page 22: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 3 Example 3 ––Presence of transformer & motorPresence of transformer & motor

pu667.1Z

pu4.2Z

pu48.0Z

pu0833.0Z

2Tpu

Gpu

1Tpu

utility

=

=

=

=Step 1: Calculate impedances34.5kV

SCC = 1200 MVA

10/12.5 MVA6%

5MVAXd

”=0.12

89.7154.2

100x17.0

MVAMVA

xZZ

2154866.0

1865pf

746.0*2500ratingMotor

oldbase

basemMpu

==

=

==

=13.8 kV

F 3 MVA5%

2.4 kV

M 2500 HPXd

”=0.17

Calculate the fault current at F

Page 23: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 3 Example 3 ––Presence of transformer & motorPresence of transformer & motor

Step 1: Calculate impedances34.5kV

SCC = 1200 MVA

pu89.7Z

pu667.1Z

pu4.2Z

pu48.0Z

pu0833.0Z

Mpu

2Tpu

Gpu

1Tpu

utility

=

=

=

=

=10/12.5 MVA6%

5MVAXd

”=0.12

13.8 kV

F 3 MVA5%

2.4 kV

M 2500 HPXd

”=0.17

Calculate the fault current at F

Page 24: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 3 Example 3 ––Presence of transformer & motorPresence of transformer & motor

Step 2: Calculate Equivalent impedances34.5kV

SCC = 1200 MVA1.0V

10/12.5 MVA6%

5MVAXd

”=0.12

F

13.8 kV

Calculate the fault current at F

3 MVA5%

2.4 kV

M 2500 HPXd

”=0.17

ZTpu1

0.0833

Zutility

0.48

ZGpu

2.4

7.89

1.667

ZMpu

ZTpu2

Page 25: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 3 Example 3 ––Presence of transformer & motorPresence of transformer & motor

Step 2: Calculate Equivalent impedances

1.0V 1.0V

ZTpu1

0.0833

Zutility

0.48

ZGpu

2.4

7.89

1.667

ZMpu 0.4354

ZTpu2

Page 26: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Example 3 Example 3 ––Presence of transformer & motorPresence of transformer & motor

Step 3: Calculate fault current

pu297.24354.0

0.1Z

VI

Eq

puFpu ===

1.0V

A9609

5.34x8.13

II

A38443

55.2898x297.2

3

IxII

FHVFLV

baseFpuFHV

=

=

==

=

0.4354

Page 27: Symmetrical Fault Calculations - NTUAecourses.dbnet.ntua.gr/fsr/14819/SymmetricalFaultCalculations.pdf · Symmetrical Fault Calculations Author: jtaylor Created Date: 1/19/2006 4:44:34

Symmetrical FaultSymmetrical Fault

34.5kV34.5kV34.5kV SCC = 1200 MVA

SCC = 1200 MVASCC = 1200 MVA

10/12.5 MVA6%

10/12.5 MVA6%

10/12.5 MVA6%

5MVAXd

”=0.12

13.8 kV5MVAXd

”=0.12

F

IF =7426 Amps

F

13.8 kV

F

13.8 kV

3 MVA5%

2.4 kV

M 2500 HPXd

”=0.17

IF =9170 Amps IF =9609 Amps