Hands-On Relay School
Jon F. DaumeBonneville Power Administration
March 14-15, 2011
Theory TrackTransmission Protection Theory
Symmetrical Components & Fault Calculations
![Page 2: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/2.jpg)
2
Class Outline
Power system troublesSymmetrical componentsPer unit system Electrical equipment impedancesSequence networksFault calculations
![Page 3: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/3.jpg)
3
Power System ProblemsFaultsEquipment troubleSystem disturbances
![Page 4: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/4.jpg)
4
Fault CausesLightningWind and iceVandalismContaminationExternal forces
Cars, tractors, balloons, airplanes, trees, critters, flying saucers, etc.
Equipment failuresSystem disturbances
Overloads, system swings
![Page 5: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/5.jpg)
5
![Page 6: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/6.jpg)
6
Fault TypesOne line to ground (most common)Three phase (rare but most severe)Phase to phasePhase to phase to ground
![Page 7: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/7.jpg)
7
Symmetrical Components
![Page 8: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/8.jpg)
8
Balanced & Unbalanced Systems
Balanced System:3 Phase load3 Phase fault
Unbalanced System:Phase to phase faultOne line to ground
faultPhase to phase to
ground faultOpen pole or
conductorUnbalanced load
![Page 9: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/9.jpg)
9
Balanced & Unbalanced Systems
A
C
BBalancedSystem
A
C
BUnbalanced System
![Page 10: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/10.jpg)
10
Sequence Currents for Unbalanced Network
Ia2
Ic2Ib2
Negative Sequence
Ic0Ib0
Ia0
Zero Sequence
Ia1
Ic1
Ib1
Positive Sequence
![Page 11: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/11.jpg)
11
Sequence Quantities
Condition + - 03 Phase load - -3 Phase fault - -Phase to phase fault -One line to ground faultTwo phase to ground faultOpen pole or conductorUnbalanced load
![Page 12: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/12.jpg)
12
Phase Values From Sequence Values
Currents:IA = Ia0 + Ia1 + Ia2
IB = Ib0 + Ib1 + Ib2
IC = Ic0 + Ic1 + Ic2
Voltages:VA = Va0 + Va1 + Va2
VB = Vb0 + Vb1 + Vb2
VC = Vc0 + Vc1 + Vc2
![Page 13: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/13.jpg)
13
a Operatora = -0.5 + j √3= 1 ∠ 120°
2a2 = -0.5 – j √3= 1 ∠ 240°
2
1 + a + a2 = 0
1
a
a 2
![Page 14: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/14.jpg)
14
Phase Values From Sequence Values
Currents:IA = Ia0 + Ia1 + Ia2
IB = Ia0 + a2Ia1 + aIa2
IC = Ia0 + aIa1 + a2Ia2
Voltages:VA = Va0 + Va1 + Va2
VB = Va0 + a2Va1 + aVa2
VC = Va0 + aVa1 + a2Va2
![Page 15: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/15.jpg)
15
Sequence Values From Phase Values
Currents:Ia0 = (IA + IB + IC)/3Ia1 = (IA + aIB + a2IC)/3Ia2 = (IA + a2IB + aIC)/3
Voltages:Va0 = (VA + VB + VC)/3Va1 = (VA + aVB + a2VC)/3Va2 = (VA + a2VB + aVC)/3
![Page 16: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/16.jpg)
16
Zero Sequence Filter3Ia0 = Ig = Ir = IA + IB + ICand: 1 + a + a2 = 0
IA = Ia0 + Ia1 + Ia2
+IB = Ia0 + a2Ia1 + aIa2
+IC = Ia0 + aIa1 + a2Ia2
= Ig = 3Iao + 0 + 0
![Page 17: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/17.jpg)
17
Ia
Ic
Ib
3I0 = Ia + Ib + Ic
Zero Sequence Current Filter
![Page 18: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/18.jpg)
18
Zero Sequence Voltage Filter
3V0
3 VO Polarizing Potential
Ea Eb Ec
![Page 19: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/19.jpg)
19
Negative Sequence FilterSome protective relays are designed to
sense negative sequence currents and/or voltages
Much more complicated than detecting zero sequence values
Most modern numerical relays have negative sequence elements for fault detection and/or directional control
![Page 20: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/20.jpg)
20
ExampleIA = 3 + j4IB = -7 - j2IC = -2 + j7
+j
-j
IA = 3+j4
IB = -7-j2
IC = -2+j7
![Page 21: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/21.jpg)
21
Zero SequenceIa0 = (IA + IB + IC)/3= [(3+j4)+(-7-j2)+(-2+j7)]/3= -2 + j3 = 3.61 ∠ 124°
Ia0 = Ib0 = Ic0
Ic0Ib0
Ia0
Zero Sequence
![Page 22: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/22.jpg)
22
Positive SequenceIa1 = (IA + aIB + a2IC)/3
= [(3+j4)+(-0.5+j√3/2)(-7-j2)+(-0.5-j√3/2)(-2+j7)]/3
= [(3+j4)+(5.23-j5.06)+(7.06-j1.77)]/3= 5.10 - j 0.94 = 5.19 ∠ -10.5°
Ib1 is rotated -120º Ic1 is rotated +120º
![Page 23: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/23.jpg)
23
Positive Sequence
Ia1
Ic1
Ib1
![Page 24: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/24.jpg)
24
Negative SequenceIa2 = (IA + a2IB + aIC)/3
= [(3+j4)+(-0.5-j√3/2)(-7-j2)+(-0.5+j√3/2)(-2+j7)]/3
= [(3+j4)+(1.77+j7.06)+(-5.06-j5.23)]/3= -0.1 + j 1.94 = 1.95 ∠ 92.9°
Ib2 is rotated +120º Ic2 is rotated -120º
![Page 25: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/25.jpg)
25
Negative Sequence
Ia2
Ic2Ib2
![Page 26: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/26.jpg)
26
Reconstruct Phase Currents
Ia
Ic
Ib
Ic1
Ib1
Ia1
Ib0
Ia0
Ic0
Ia2
Ib2
Ic2
![Page 27: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/27.jpg)
27
Positive, Negative, and Zero Sequence Impedance
Network Calculations for a Fault Study
![Page 28: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/28.jpg)
28
+, -, 0 Sequence Networks
Simple 2 Source Power System Example
Fault
1PU
Z1
I1
Z2
I2
Z0
I0
V0
-
+
V2
-
+
V1
-
+
![Page 29: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/29.jpg)
29
Impedance Networks & Fault TypeFault Type + - 03 Phase fault - -Phase to phase fault -One line to ground faultTwo phase to ground fault
![Page 30: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/30.jpg)
30
Per Unit
![Page 31: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/31.jpg)
31
Per UnitPer unit values are commonly used for fault
calculations and fault study programsPer unit values convert real quantities to
values based upon number 1Per unit values include voltages, currents and
impedances Calculations are easier
Ignore voltage changes due to transformers Ohms law still works
![Page 32: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/32.jpg)
32
Per UnitConvert equipment impedances into per unit
valuesTransformer and generator impedances are
given in per cent (%)Line impedances are calculated in ohmsThese impedances are converted to per unit
ohms impedance
![Page 33: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/33.jpg)
33
Base kVA or MVAArbitrarily selectedAll values converted to common KVA or MVA
Base100 MVA base is most often usedGenerator or transformer MVA rating may be
used for the base
![Page 34: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/34.jpg)
34
Base kVUse nominal equipment or line voltages
765 kV 525 kV345 kV 230 kV169 kV 138 kV115 kV 69 kV34.5 kV 13.8 kV12.5 kV etc.
![Page 35: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/35.jpg)
35
Base Ohms, AmpsBase ohms:kV2 1000 = kV2 base kVA base MVA
Base amps:base kVA = 1000 base MVA
√3 kV √3 kV
![Page 36: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/36.jpg)
36
Base Ohms, Amps (100 MVA Base)kV Base Ohms Base Amps525 2756.3 110.0345 1190.3 167.3230 529.0 251.0115 132.3 502.069 47.6 836.7
34.5 11.9 1673.513.8 1.9 4183.712.5 1.6 4618.8
![Page 37: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/37.jpg)
37
ConversionsPercent to Per Unit:base MVA x % Z of equipment
3φ MVA rating 100= Z pu Ω @ base MVA
If 100 MVA base is used:% Z of equipment = Z pu Ω3φ MVA rating
![Page 38: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/38.jpg)
38
Ohms to Per Unitpu Ohms = ohms / base ohmsbase MVA x ohms = pu Ω @ base MVA
kV2LL
![Page 39: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/39.jpg)
39
Per Unit to Real StuffAmps = pu amps x base amps
kV = pu kV x base kVOhms = pu ohms x base ohms
![Page 40: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/40.jpg)
40
Converting Between Bases
Znew = Zold x base MVAnew x kV2old
base MVAold kV2new
![Page 41: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/41.jpg)
41
Evaluation of System Components
Determine positive, negative, and zero sequence impedances of various devices (Z1, Z2, Z0)
Only machines will act as a voltage source in the positive sequence network
Connect the various impedances into networks according to topography of the system
Connect impedance networks for various fault types or other system conditions
![Page 42: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/42.jpg)
42
Synchronous Machines
~
Machine values:
Machine reactances given in % of the machine KVA or MVA rating
Ground impedances given in ohms
![Page 43: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/43.jpg)
43
Synchronous MachinesMachine values:
Subtransient reactance (X"d) Transient reactance (X'd) Synchronous reactance (Xd) Negative sequence reactance (X2)Zero sequence reactance (X0)
![Page 44: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/44.jpg)
44
Synchronous MachinesMachine neutral ground impedance: Usually
expressed in ohmsUse 3R or 3X for fault calculations
Calculations generally ignores resistance values for generators
Calculations generally uses X”d for all impedance values
![Page 45: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/45.jpg)
45
Generator ExampleMachine nameplate values:
250 MVA, 13.8 kVX"d = 25% @ 250 MVAX'd = 30% @ 250 MVAXd = 185% @ 250 MVAX2 = 25% @ 250 MVAX0 = 10% @ 250 MVA
![Page 46: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/46.jpg)
46
Generator ExampleConvert machine reactances to per unit @
common MVA base, (100):X"d = 25% / 250 = 0.1 puX'd = 30% / 250 = 0.12 puXd = 185% / 250 = 0.74 puX2 = 25% / 250 = 0.1 puX0 = 10% / 250 = 0.04 pu
base MVA x % Z of equipment = Z pu Ω @ base MVA3φ MVA rating 100
![Page 47: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/47.jpg)
47
Generator Example
~R1 jX1” = 0.1
R0 jX0 = 0.04
R2 jX2 = 0.1
![Page 48: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/48.jpg)
48
TransformersZx X
Ze
ZhH 1:N
Vh
Ih
ZhxH X
Equivalent Transformer - Impedance in %
Zhx Ω = Vh /Ih = Zh + Zx /N2
Zhx % = Vh /Ih x MVA/kV2 x 100
![Page 49: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/49.jpg)
49
TransformersImpedances in % of the transformer MVA
ratingConvert from circuit voltage to tap voltage:
%Xtap = %Xcircuit kV2circuit
kV2tap
![Page 50: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/50.jpg)
50
TransformersConvert to common base MVA:%X @ base MVA =base MVA x %X of Transformer
MVA of Measurement
%X of Transformer = pu X @ 100 MVAMVA of MeasurementX1 = X2 = X0 unless a special value is given for
X0
![Page 51: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/51.jpg)
51
Transformer Example250 MVA Transformer13.8 kV Δ- 230 kV Yg10% Impedance @ 250 MVAX = 10% = 0.04 pu @ 100 MVA
250X1 = X2 = X0 = XAssume R1, R2, R0 = 0
![Page 52: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/52.jpg)
52
Transformer ExampleR1 jX1 = 0.04
R0 jX0 = 0.04
R2 jX2 = 0.04
Zero sequence connection depends upon winding configuration.
![Page 53: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/53.jpg)
53
Transformer Connections
Winding Connection Sequence NetworkConnections
Z1, Z2 Z0
Z1, Z2 Z0
![Page 54: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/54.jpg)
54
Transformer ConnectionsWinding Connection Sequence Network Connections
Z1, Z2 Z0
Z1, Z2 Z0
Z1, Z2 Z0
Z1, Z2 Z0
![Page 55: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/55.jpg)
55
Delta Wye Transformer
A
B
C
b
a
Ia
Ic
Ib
IA
IB
IC
nIA
nIC
3I0 = IA+IB+IC
nIB
![Page 56: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/56.jpg)
56
Delta Wye TransformerIa = nIA - nIC = n(Ia0+Ia1+Ia2- Ia0-aIa1-a2Ia2 )
= n(Ia1 - aIa1 + Ia2 - a2Ia2 )Ib = nIB - nIA
= n(Ia0+a2Ia1+aIa2 -Ia0-Ia1-Ia2 )= n(a2Ia1 - Ia1 + aIa2 - Ia2 )
Ic = nIC - nIB = n(Ia0+aIa1+a2Ia2 -Ia0-a2Ia1-aIa2 )= n(aIa1 - a2Ia1 + a2Ia2 - aIa2 )
No zero sequence current outside delta
![Page 57: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/57.jpg)
57
Transformer ConnectionsA YG / YG connection provides a series
connection for zero sequence currentA Δ / YG connection provides a zero sequence
(I0) current source for the YG windingAuto transformer provides same connection as
YG / YG connectionUse 3R or 3X if a Y is connected to ground
with a resistor or reactor
![Page 58: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/58.jpg)
58
Three Winding TransformerImpedances ZHL, ZHM, & ZML given in % at
corresponding winding ratingConvert impedances to common base MVACalculate corresponding “T” network
impedances:ZH = (ZHL+ ZHM - ZML)/2
ZM = (- ZHL+ ZHM + ZML)/2 ZL = (ZHL- ZHM + ZML)/2
![Page 59: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/59.jpg)
59
“T” NetworkCalculate corresponding “T” network
impedances:ZH = (ZHL+ ZHM - ZML)/2 ZM = (- ZHL+ ZHM + ZML)/2 ZL = (ZHL- ZHM + ZML)/2 ZHL= ZH + ZL
ZHM = ZH + ZM
ZML= ZM+ ZL
ZH ZM
ZL
![Page 60: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/60.jpg)
60
Transformer Example230 kV YG/115 kV YG/13.2 kV ΔNameplate Impedances ZHL= 5.0% @ 50 MVAZHM = 5.75% @ 250 MVAZML = 3.15% @ 50 MVA
![Page 61: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/61.jpg)
61
Transformer ExampleConvert impedances to per unit @ common
MVA Base (100)ZHL= 5.0% @ 50 MVA = 5.0 / 50
= 0.10 puZHM = 5.75% @ 250 MVA = 5.75 / 250
= 0.023 puZML = 3.15% @ 50 MVA = 3.15 / 50
= 0.063 pu
![Page 62: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/62.jpg)
62
Transformer ExampleConvert impedances to “T” network equivalentZH = (ZHL+ ZHM - ZML)/2
= (0.1 + 0.023 - 0.063)/2 = 0.03 puZM = (- ZHL+ ZHM + ZML)/2
= (-0.1 + 0.023 + 0.063)/2 = - 0.007 puZL = (ZHL- ZHM + ZML)/2
= (0.1 - 0.023 + 0.063)/2 = 0.07 pu
![Page 63: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/63.jpg)
63
Transformer Example
0.03 -0.007
0.07
H M 0.03 -0.007
0.07
H M
LL
H, 230 kV L, 13.8 kV M, 115 kV
+, - Sequence 0 Sequence
![Page 64: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/64.jpg)
Problem
Calculate pu impedances for generators and transformers
Use 100 MVA base Ignore all resistances
![Page 65: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/65.jpg)
65
Problem
Fault
13.8 kV 13.8 kV230 kV230 kV
115 kV
![Page 66: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/66.jpg)
66
Problem - Generator DataMachine nameplate values:
300 MVA Nameplate rating X"d = 25% @ 300 MVAX'd = 30% @ 300 MVAXd = 200% @ 300 MVAX2 = 25% @ 300 MVAX0 = 10% @ 300 MVALeft generator: 13.8 kVRight generator: 115 kV
![Page 67: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/67.jpg)
67
Problem - Transformer DataTwo winding transformer nameplate values
300 MVA Transformer13.8 kV Δ- 230 kV Yg10% Impedance @ 300 MVA
Three winding transformer nameplate values230 kV Yg/115 kV Yg/13.8 kV ΔZHL= 5.0% @ 50 MVA (230 kV – 13.8 kV)ZHM = 6.0% @ 300 MVA (230 kV –115 kV)ZML = 3.2% @ 50 MVA (115 kV – 13.8 kV)
![Page 68: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/68.jpg)
68
Transmission Lines
R jX
![Page 69: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/69.jpg)
69
Positive & Negative Sequence Line Impedance
Z1 = Z2 = Ra + j 0.2794 f log GMDsep
60 GMRcond
or
Z1 = Ra + j (Xa + Xd) Ω/mileRa and Xa from conductor tables
Xd = 0.2794 f log GMD60
![Page 70: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/70.jpg)
70
Positive & Negative Sequence Line Impedance
f = system frequencyGMDsep = Geometric mean distance
between conductors = 3√(dabdbcdac) where dab, dac, dbc = spacing between conductors in feet
GMRcond = Geometric mean radius of conductor in feet
Ra = conductor resistance, Ω/mile
![Page 71: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/71.jpg)
71
Zero Sequence Line ImpedanceZ0 = Ra + Re +j 0.01397 f log De _______
3√(GMRcond GMDsep2)
or
Z0 = Ra + Re + j (Xa + Xe - 2Xd) Ω/mile
![Page 72: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/72.jpg)
72
Zero Sequence Line ImpedanceRe = 0.2862 for a 60 Hz. system. Re does
not vary with ρ.De = 2160 √(ρ /f) = 2788 @ 60 Hz.ρ = Ground resistivity, generally assumed to
be 100 meter ohms.Xe = 2.89 for 100 meter ohms average
ground resistivity.
![Page 73: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/73.jpg)
73
Transmission LinesRa j(Xa+Xd)
Ra+Re j(Xa+Xe-2Xd)
Ra j(Xa+Xd)
Z1
Z2
Z0
![Page 74: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/74.jpg)
74
Transmission Line Example230 kV Line50 Miles long1272 kcmil ACSR Pheasant Conductor
Ra = 0.0903 Ω /mile @ 80° CXa = 0.37201 Ω /mileGMR = 0.0466 feet
Structure: horizontal “H” frame
![Page 75: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/75.jpg)
75
Transmission Line ExampleStructure “H” frame:
GMD = 3√(dabdbcdac) = 3√(23x23x46) = 28.978 feet
Xd = 0.2794 f log GMD60
= 0.2794 log 28.978 = 0.4085 Ω /mile
A CB
23 Feet 23 FeetJ6 Configuration
![Page 76: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/76.jpg)
76
Transmission Line ExampleZ1 = Z2 = Ra + j (Xa + Xd)
= 0.0903 + j (0.372 + 0.4085) = 0.0903 + j 0.781 Ω /mile
Z1 Line = 50(0.0903 + j 0.781) = 4.52 + j 39.03 Ω = 39.29 Ω ∠ 83.4 °
Per unit @ 230 kV, 100 MVA Basebase MVA x ohms = pu Ω @ base MVA
kV2LL
Z1 Line = (4.52 + j 39.03)100/2302
= 0.0085 + j 0.0743 pu
![Page 77: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/77.jpg)
77
Transmission Line ExampleZ0 = Ra + Re + j (Xa + Xe – 2Xd) = 0.0903
+ 0.286+ j (0.372 + 2.89 - 2 x0.4085) = 0.377 + j 2.445 Ω /mile
Z0 Line = 50(0.377 + j 2.445) = 18.83 + j 122.25 Ω = 123.69 Ω ∠ 81.2 °
Per unit @ 230 kV, 100 MVA BaseZ0 Line = (18.83 + j 122.25)100/2302
= 0.0356 + j 0.2311 pu
![Page 78: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/78.jpg)
78
Transmission Line Example
Z1
Z2
Z0
0.0085 j0.0743
0.0356 j0.2311
0.0085 j0.0743
![Page 79: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/79.jpg)
79
Long Parallel LinesMutual impedance between lines
![Page 80: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/80.jpg)
80
Mutual ImpedanceResult of coupling between parallel linesOnly affects Zero sequence networkWill affect ground fault magnitudesWill affect ground current flow in lines
Line #1
Line #2
3I0, Line #1
3I0, Line #2
![Page 81: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/81.jpg)
81
Mutual ImpedanceZM = Re + j 0.838 log De Ω/mile
GMDcircuits
or ZM = Re + j (Xe − 3Xd circuits) Ω/mile
Re = 0.2862 @ 60 HzDe = 2160 √(ρ /f) = 2788 @ 60 HzXe = 2.89 for 100 meter ohms average
ground resistivity
![Page 82: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/82.jpg)
82
Mutual ImpedanceGMDcircuits is the ninth root of all possible
distances between the six conductors, approximately equal to center to center spacing
GMDcircuits = 9√(da1a2da1b2da1c2db1a2db1b2db1c2dc1a1dc1b2dc1c2)
Xd circuits = 0.2794 log GMDcircuits
![Page 83: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/83.jpg)
83
Mutual Impedance Example
A CB
23 Feet 23 Feet
A CB
23 Feet 23 Feet
Circuit #1 Circuit #2
46 Feet
46 Feet
92 Feet69 Feet
69 Feet
92 Feet115 Feet
138 Feet115 Feet
92 Feet
![Page 84: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/84.jpg)
84
Mutual Impedance ExampleGMDcircuits = 9√(da1a2da1b2da1c2db1a2db1b2db1c2dc1a1dc1b2dc1c2) =
9√(92x115x138x69x92x115x46x69x92)= 87.84 feet
Xd circuits = 0.2794 log GMDcircuits = 0.2794 log 87.84 = 0.5431 Ω/mile
ZM = Re + j (Xe − 3Xd circuits) = 0.2862 + j (2.89 - 3x0.5431) = 0.2862 + j 1.261 Ω/mile
(Z0 = 0.377 + j 2.445 Ω /mile)
![Page 85: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/85.jpg)
85
Mutual Impedance Model
Bus 1 Bus 2
Z0 Line 1
Z0 Line 2
ZM
Bus 1 Bus 2Z02 - ZM
Z01- ZM
ZM
![Page 86: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/86.jpg)
86
Mutual Impedance ModelModel works with at least 1 common busZM Affects zero sequence network only
ZM For different line voltages:pu Ohms = ohms x base MVA
kV1 x kV2
Mutual impedance calculations and modeling become much more complicated with larger systems
![Page 87: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/87.jpg)
87
Mutual Impedance Fault ExampleTaft
Taft
645 Amps
1315 Amps645 Amps
1980 Amps
920 Amps
260 Amps920 Amps
1370 Amps
1LG Faults With Mutual Impedances
1LG Faults Without Mutual Impedances
Garrison
Garrison
Taft Garrison
Taft Garrison
![Page 88: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/88.jpg)
88
ProblemCalculate Z1 and Z0 pu impedances for a
transmission lineCalculate R1, Z1, R0 and Z0
Calculate Z1 and Z0 and the angles for Z1and Z0
Calculate Z0 mutual impedance between transmission lines
Use 100 MVA base and 230 kV base
![Page 89: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/89.jpg)
89
Problem
Fault
13.8 kV 13.8 kV230 kV230 kV
115 kV
![Page 90: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/90.jpg)
90
Transmission Line Data2 Parallel 230 kV Lines
60 Miles long1272 kcmil ACSR Pheasant conductorRa = 0.0903 Ω /mile @ 80° CXa = 0.37201 Ω /mileGMR = 0.0466 feetH frame structure - flat, 23 feet between
conductorsSpacing between circuits = 92 feet centerline to
centerline
![Page 91: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/91.jpg)
91
Fault Calculations and Impedance Network
Connections
![Page 92: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/92.jpg)
92
Why We Need Fault StudiesRelay coordination and settingsDetermine equipment ratingsDetermine effective grounding of systemSubstation ground mat designSubstation telephone protection
requirementsLocating faults
![Page 93: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/93.jpg)
93
Fault StudiesFault Types:
3 PhaseOne line to groundPhase to phasePhase to phase to ground
Fault Locations:Bus faultLine end Line out fault (bus fault with line open)Intermediate faults on transmission line
![Page 94: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/94.jpg)
94
Fault Study AssumptionsIgnore loadsUse generator X”d
Generator X2 equal X”d
Ignore generator resistanceIgnore transformer resistance0 Ω Fault resistance assumedNegative sequence impedance = positive
sequence impedance
![Page 95: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/95.jpg)
95
Positive Sequence Network
Z1sl Z1tl Z1Ll Z1Lr Z1sr
Z1h Z1m
Z1lV1=1-I1Z1
+
Vl = 1 Vr = 1
I1
Fault
![Page 96: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/96.jpg)
96
Negative Sequence Network
Z2sl Z2tl Z2Ll Z2Lr Z2sr
Z2h Z2m
Z2lV2= -I2Z2
+
I2
Fault
![Page 97: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/97.jpg)
97
Zero Sequence Network
Z0sl Z0tl Z0Ll Z0Lr Z0sr
Z0h Z0m
Z0lV0= -I0Z0
+
I0
Fault
![Page 98: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/98.jpg)
98
Network Reduction
Simple 2 Source Power System Example
Fault
1PU
Z1
I1
Z2
I2
Z0
I0
V0
-
+
V2
-
+
V1
-
+
![Page 99: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/99.jpg)
99
Three Phase Fault
Only positive sequence impedance network used
No negative or zero sequence currents or voltages
Simple 2 Source Power System Example
Fault
![Page 100: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/100.jpg)
100
Three Phase Fault
1PU
Z10.084
I1=11.9 I2=0 I0=0
V0
-
+
V2
-
+
V1
-
+
Z00.081
Z20.084
![Page 101: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/101.jpg)
101
Three Phase Fault
Simple 2 Source Power System Example
Fault
Z1sl Z1tl Z1Ll Z1Lr Z1sr
Z1h Z1m
Z1lV1=1-I1Z1
+
Vl = 1 Vr = 1
Sequence Network Connection for 3 Phase Fault
I10.1 0.0370.04 0.037 0.1
0.03
0.07
-0.007
![Page 102: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/102.jpg)
102
Three Phase Fault
Positive Sequence Network Reduced
Simple 2 Source Power System Example
Fault
V1=1-I1Z1+
Vl = 1 Vr = 1
I1
0.177 0.160
![Page 103: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/103.jpg)
103
Three Phase Fault Vectors
Va
Vc
Vb
Ia
Ic
Ib
![Page 104: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/104.jpg)
104
Three Phase FaultMVAFault = MVABase
ZFault puorI pu Fault current = 1 pu ESource
ZFault pu
![Page 105: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/105.jpg)
105
Three Phase FaultI1 = E / Z1 = 1 / Z1
I2 = I0 = 0IA = I1 + I2 + I0 = I1IB = a2I1IC = aI1V1 = 1 – I1Z1 = 0V2 = 0, V0 = 0VA = VB = VC = 0
![Page 106: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/106.jpg)
106
Phase to Phase Fault
Positive and negative sequence impedance networks connected in parallel
No zero sequence currents or voltages
Simple 2 Source Power System Example
Fault
![Page 107: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/107.jpg)
107
Phase to Phase Fault
1PU
Z1
I1
Z2
I2
Z0
I0
V0
-
+
V2
-
+
V1
-
+
![Page 108: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/108.jpg)
108
Phase to Phase Fault
Z2sl Z2tl Z2Ll Z2Lr Z2sr
Z2h Z2m
Z2lV2= -I2Z2
+
I2 = -I1
Z1sl Z1tl Z1Ll Z1Lr Z1sr
Z1h Z1m
Z1lV1=1-I1Z1
I1
+
Vl = 1 Vr = 1
Sequence Network Connection for Phase to Phase Fault
Fault
![Page 109: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/109.jpg)
109
Phase to Phase Fault Vectors
Va
Vc
Vb
Ic
Ib
![Page 110: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/110.jpg)
110
Phase to Phase FaultI1 = - I2 = E = ___1___ I0 = 0
(Z1 + Z2) (Z1 + Z2)IA = I0 + I1 + I2 = 0IB = I0 + a2I1 + aI2 = a2I1 - aI1IB = (a2 - a) E = _-j √3 E_ = -j 0.866 E
(Z1 + Z2) (Z1 + Z2) Z1
IC = - IB(assume Z1 = Z2)
![Page 111: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/111.jpg)
111
Phase to Phase FaultV1 = E - I1Z1 = 1 - I1Z1
V2 = - I2Z2 = V1
V0 = 0VA = V1 + V2 + V0 = 2 V1
VB = V0 + a2V1 + aV2 = a2V1 + aV1 = -V1
VC = -V1
Phase to phase fault = 86.6% 3 phase fault
![Page 112: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/112.jpg)
112
Single Line to Ground Fault
Positive, negative and zero sequence impedance networks connected in series
Simple 2 Source Power System Example
Fault
![Page 113: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/113.jpg)
113
Single Line to Ground Fault
1PU
Z1.084
I0=4.02
V0
-
+
V2
-
+
V1
-
+
Z2.084
Z0.081
I2=4.02I1=4.02
![Page 114: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/114.jpg)
114
Single Line to Ground Fault
Z2sl Z2tl Z2Ll Z2Lr Z2sr
Z2h Z2m
Z2l
V2= -I2Z2+
Z0sl Z0tl Z0Ll Z0Lr Z0sr
Z0h Z0m
Z0lV0= -I0Z0
+
Z1sl Z1tl Z1Ll Z1Lr Z1sr
Z1h Z1m
Z1lV1=1-I1Z1
+
Vl = 1 Vr = 1
I1
I2
I0
Sequence Network Connection for One Line to Ground Fault
I1 = I2 = I0
0.1 0.0370.04 0.037 0.10.03
0.07
-0.007
0.04 0.1160.04 0.116 0.040.03
0.07
-0.007
0.1 0.0370.04 0.037 0.10.03
0.07
-0.007
![Page 115: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/115.jpg)
115
Single Line to Ground Fault Vectors
Va
Vc
Vb Ia
![Page 116: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/116.jpg)
116
Single Line to Ground FaultI1 = I2 = I0 = ____E_____ = ____1_____
(Z1 + Z2 + Z0) (Z1 + Z2 + Z0)IA = I1 + I2 + I0 = 3 I0IB = I0 + a2I1 + aI2 = I0 + a2I0 + aI0 = 0IC = 0
I Ground = I Residual = 3I0
![Page 117: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/117.jpg)
117
Single Line to Ground FaultV1 = E - I1Z1 = 1 - I1Z1
V2 = - I2Z2
V0 = - I0Z0
VA = V1 + V2 + V0 = 0VB = V0 + a2V1 + aV2 = (Z1 - Z0 ) + a2
(Z0+Z1+Z1)VC = V0 + aV1 + a2V2 = (Z1 - Z0 ) + a(assumes Z1 = Z2) (Z0+Z1+Z1)
![Page 118: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/118.jpg)
118
Two Phase to Ground Fault
Positive, negative and zero sequence impedance networks connected in parallel
Simple 2 Source Power System Example
Fault
![Page 119: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/119.jpg)
119
Two Phase to Ground Fault
1PU
Z1
I1
Z2
I2
Z0
I0
V0
-
+
V2
-
+
V1
-
+
![Page 120: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/120.jpg)
120
Two Phase to Ground Fault
Z2sl Z2tl Z2Ll Z2Lr Z2sr
Z2h Z2m
Z2lV2= -I2Z2
+
Z0sl Z0tl Z0Ll Z0Lr Z0sr
Z0h Z0m
Z0lV0= -I0Z0
+
Z1sl Z1tl Z1Ll Z1Lr Z1sr
Z1h Z1m
Z1lV1=1-I1Z1
+
Vl = 1 Vr = 1
I1
I2
I0
Sequence Network Connection for Phase to Phase to Ground Fault
![Page 121: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/121.jpg)
121
Two Phase to Ground Fault Vectors
Va
Vc
Vb
Ic
Ib
![Page 122: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/122.jpg)
122
Other ConditionsFault calculations and symmetrical
components can also be used to evaluate:Open pole or broken conductorUnbalanced loadsLoad included in fault analysisTransmission line fault location
For these other network conditions, refer to references.
![Page 123: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/123.jpg)
123
ReferencesCircuit Analysis of AC Power Systems, Vol. 1 &
2, Edith ClarkeElectrical Transmission and Distribution
Reference Book, Westinghouse Electric Co., East Pittsburgh, Pa.
Symmetrical Components, Wagner and Evans, McGraw-Hill Publishing Co.
Symmetrical Components for Power Systems Engineering, J. Lewis Blackburn, Marcel Dekker, Inc.
![Page 124: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/124.jpg)
124
The end
Jon F. DaumeBonneville Power Administration
Retired!
![Page 125: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/125.jpg)
1
Hands-On Relay School
Jon F. DaumeBonneville Power Administration
March 14-15, 2011
Theory TrackTransmission Protection Theory
Transmission System Protection
![Page 126: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/126.jpg)
2
Discussion Topics• Protection overview• Transmission line protection
– Phase and ground fault protection– Line differentials– Pilot schemes– Relay communications– Automatic reclosing
• Breaker failure relays• Special protection or remedial action schemes
![Page 127: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/127.jpg)
3
Power TransferVs VrX
Power Transfer
0
0.5
1
0 30 60 90 120 150 180
Angle Delta
Tran
smitt
ed P
ower
P = Vs Vr sin δ / X
![Page 128: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/128.jpg)
4
Increase Power Transfer• Increase transmission system operating
voltage• Increase angle δ• Decrease X
– Add additional transmission lines– Add series capacitors to existing lines
![Page 129: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/129.jpg)
5
![Page 130: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/130.jpg)
6
Power Transfer During FaultsPower Transfer
0
0.2
0.4
0.6
0.8
1
1.2
0 30 60 90 120 150 180
Angle Delta
Tran
smitt
ed P
ower
Normal
1LG
LL
LLG
3 Phase
![Page 131: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/131.jpg)
7
Vs Vr
Power Transfer
0
0.2
0.4
0.6
0.8
1
1.2
0 30 60 90 120 150 180
Angle Delta
Pow
er BP1
3
21
P2
6
4
5
A
![Page 132: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/132.jpg)
8
System Stability• Relay operating speed • Circuit breaker opening speed• Pilot tripping• High speed, automatic reclosing• Single pole switching• Special protection or remedial action
schemes
![Page 133: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/133.jpg)
9
IEEE Device NumbersNumbers 1 - 97 used21 Distance relay25 Synchronizing or synchronism check
device27 Undervoltage relay32 Directional power relay43 Manual transfer or selector device46 Reverse or phase balance current relay50 Instantaneous overcurrent or rate of rise
relay (fixed time overcurrent)(IEEE C37.2)
![Page 134: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/134.jpg)
10
51 AC time overcurrent relay52 AC circuit breaker59 Overvoltage relay62 Time delay stopping or opening relay63 Pressure switch67 AC directional overcurrent relay 79 AC reclosing relay81 Frequency relay86 Lock out relay87 Differential relay
(IEEE C37.2)
IEEE Device Numbers
![Page 135: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/135.jpg)
11
Relay Reliability• Overlapping protection
– Relay systems are designed with a high level of dependability
– This includes redundant relays– Overlapping protection zones
• We will trip no line before its time– Relay system security is also very important– Every effort is made to avoid false trips
![Page 136: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/136.jpg)
12
Relay Reliability• Relay dependability (trip when required)
– Redundant relays– Remote backup– Dual trip coils in circuit breaker– Dual batteries– Digital relay self testing– Thorough installation testing– Routine testing and maintenance– Review of relay operations
![Page 137: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/137.jpg)
13
Relay Reliability• Relay security (no false trip)
– Careful evaluation before purchase– Right relay for right application– Voting
• 2 of 3 relays must agree before a trip– Thorough installation testing – Routine testing and maintenance– Review of relay operations
![Page 138: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/138.jpg)
14
Transmission Line Protection
![Page 139: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/139.jpg)
15
Western Transmission System
Northwest includes Oregon, Washington, Idaho, Montana, northern Nevada, Utah, British Columbia and Alberta.WECC is Western Electricity Coordinating Council
which includes states and provinces west of Rocky Mountains.
Voltage, kV Northwest WECC115 - 161 27400 miles 48030 miles
230 20850 miles 41950 miles
287 - 345 4360 miles 9800 miles
500 9750 miles 16290 miles
260 - 500 DC 300 miles 1370 miles
![Page 140: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/140.jpg)
16
Transmission Line Impedance• Z ohms/mile = Ra + j (Xa + Xd)• Ra, Xa function of conductor type, length• Xd function of conductor spacing, length
Ra j(Xa+Xd)
![Page 141: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/141.jpg)
17
Line Angles vs. VoltageZ = √[Ra
2 + j(Xa+Xd)2]∠θ ° = tan-1 (X/R)
Voltage Level Line Angle (∠θ °)7.2 - 23 kV 20 - 45 deg.23 - 69 kV 45 - 75 deg.69 - 230 kV 60 - 80 deg.230 - 765 kV 75 - 89 deg.
![Page 142: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/142.jpg)
18
Typical Line Protection
![Page 143: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/143.jpg)
19
Distance Relays(21, 21G)
![Page 144: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/144.jpg)
20
Distance Relays• Common protective relay for non radial
transmission lines• Fast and consistent trip times
– Instantaneous trip for faults within zone 1– Operating speed little affected by changes
in source impedance• Detect multiphase faults• Ground distance relays detect ground
faults• Directional capability
![Page 145: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/145.jpg)
21
CT & PT Connections
21
67N
I Phase
3I0 = Ia + Ib + Ic 3V0
V Phase
I Polarizing
![Page 146: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/146.jpg)
22
Instrument Transformers• Zsecondary = Zprimary x CTR / VTR• The PT location determines the point from
which impedance is measured• The CT location determines the fault
direction– Very important consideration for
• Transformer terminated lines• Series capacitors
• Use highest CT ratio that will work to minimize CT saturation problems
![Page 147: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/147.jpg)
23
Saturated CT Current
-100
-50
0
50
100
150
-0.017 0.000 0.017 0.033 0.050 0.06
![Page 148: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/148.jpg)
24
Original Distance Relay• True impedance characteristic
– Circular characteristic concentric to RX axis• Required separate directional element• Balance beam construction
– Similar to teeter totter– Voltage coil offered restraint– Current coil offered operation
• Westinghouse HZ– Later variation allowed for an offset circle
![Page 149: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/149.jpg)
25
Impedance Characteristic
R
X
Directional
![Page 150: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/150.jpg)
26
mho Characteristic• Most common distance element in use• Circular characteristic
– Passes through RX origin– No extra directional element required
• Maximum torque angle, MTA, usually set at line angle, ∠θ °– MTA is diameter of circle
• Different techniques used to provide full fault detection depending on relay type– Relay may also provide some or full
protection for ground faults
![Page 151: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/151.jpg)
27
3 Zone mho CharacteristicX
R
Zone 1
Zone 2
Zone 3
3 Zone Distance Elements Mho Characteristic
![Page 152: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/152.jpg)
28
Typical Reaches
21 Zone 1 85-90%
21 Zone 2 125-180%, Time Delay Trip
21 Zone 3 150-200%, Time Delay Trip
Typical Relay Protection Zones
67 Ground Instantaneous Overcurrent
67 Ground Time Overcurrent
67 Ground Time Permissive Transfer Trip Overcurrent
![Page 153: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/153.jpg)
29
Coordination Considerations, Zone 1
• Zone 1– 80 to 90% of Line impedance– Account for possible errors
• Line impedance calculations• CT and PT Errors• Relay inaccuracy
– Instantaneous trip
![Page 154: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/154.jpg)
30
Coordination Considerations• Zone 2
– 125% or more of line impedance• Consider strong line out of service• Consider lengths of lines at next substation
– Time Delay Trip• > 0.25 seconds (15 cycles)• Greater than BFR clearing time at remote bus• Must be slower if relay overreaches remote zone
2’s.– Also consider load encroachment– Zone 2 may be used with permissive
overreach transfer trip w/o time delay
![Page 155: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/155.jpg)
31
Coordination Considerations• Zone 3
– Greater than zone 2• Consider strong line out of service• Consider lengths of lines at next substation
– Time Delay Trip• > 1 second• Greater than BFR clearing time at remote bus• Must be longer if relay overreaches remote zone
3’s.– Must consider load encroachment
![Page 156: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/156.jpg)
32
Coordination Considerations• Zone 3 Special Applications
– Starter element for zones 1 and 2– Provides current reversal logic for permissive
transfer trip (reversed)– May be reversed to provide breaker failure
protection– Characteristic may include origin for current
only tripping– May not be used
![Page 157: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/157.jpg)
33
Problems for Distance Relays• Fault in front of relay• Apparent Impedance• Load encroachment• Fault resistance• Series compensated lines• Power swings
![Page 158: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/158.jpg)
34
3 Phase Fault in Front of Relay• No voltage to make impedance
measurement-use a potential memory circuit in distance relay
• Use a non-directional, instantaneous overcurrent relay (50-Dead line fault relay)
• Utilize switch into fault logic– Allow zone 2 instantaneous trip
![Page 159: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/159.jpg)
35
Apparent Impedance• 3 Terminal lines with apparent
impedance• Fault resistance also looks like an
apparent impedance • Most critical with very short or
unbalanced legs• Results in
– Short zone 1 reaches– Long zone 2 reaches and time delays
• Pilot protection may be required
![Page 160: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/160.jpg)
36
Apparent ImpedanceBus A Bus BZa = 1 ohm
Ia = 1
Zb = 1
Ib = 1
Z apparent @Bus A = Za +
ZcIc/Ia= 3 Ohms
Apparent Impedance
Ic = Ia + Ib = 2 Zc = 1
Bus C
![Page 161: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/161.jpg)
37
Coordination Considerations• Zone 1
– Set to 85 % of actual impedance to nearest terminal
• Zone 2– Set to 125 + % of apparent impedance to
most distant terminal– Zone 2 time delay must coordinate with all
downstream relays• Zone 3
– Back up for zone 2
![Page 162: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/162.jpg)
38
Load Encroachment• Z Load = kV2 / MVA
– Long lines present biggest challenge– Heavy load may enter relay characteristic
• Serious problem in August, 2003 East Coast Disturbance
• NERC Loading Criteria– 150 % of emergency line load rating – Use reduced voltage (85 %)– 30° Line Angle
• Z @ 30° = Z @ MTA cos (∠MTA° -∠30° ) for mho characteristic
![Page 163: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/163.jpg)
39
Load Encroachment• NERC Loading Criteria
– Applies to zone 2 and zone 3 phase distance• Other overreaching phase distance elements
– All transmission lines > 200 kV– Many transmission lines > 100 kV
• Solutions– Don’t use conventional zone 3 element– Use lens characteristic– Use blinders or quadrilateral characteristic– Tilt mho characteristic toward X axis– Utilize special relay load encroachment
characteristic
![Page 164: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/164.jpg)
40
Load EncroachmentX
R
Zone 1
Zone 2
Zone 3
Load Consideration with Distance Relays
LoadArea
![Page 165: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/165.jpg)
41
Lens Characteristic• Ideal for longer transmission lines• More immunity to load encroachment• Less fault resistance coverage• Generated by merging the common area
between two mho elements
![Page 166: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/166.jpg)
42
Lens Characteristic
![Page 167: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/167.jpg)
43
Tomato Characteristic• May be used as an external out of step
blocking characteristic• Reaches set greater than the tripping
elements• Generated by combining the total area of
two mho elements
![Page 168: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/168.jpg)
44
Quadrilateral Characteristic• High level of freedom in settings• Blinders on left and right can be moved in
or out– More immunity to load encroachment (in)– More fault resistance coverage (out)
• Generated by the common area between– Left and right blinders– Below reactance element– Above directional element
![Page 169: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/169.jpg)
45
Quadrilateral Characteristic
R
X
Quadrilateral Characteristic
![Page 170: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/170.jpg)
46
Special Load Encroachment
X
R
Zone 1
Zone 2
Zone 4
![Page 171: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/171.jpg)
47
Fault Resistance• Most severe on short lines• Difficult for ground distance elements to
detect• Solutions:
– Tilt characteristic toward R axis– Use wide quadrilateral characteristic– Use overcurrent relays for ground faults
![Page 172: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/172.jpg)
48
Fault ResistanceX
R
Zone 1
Zone 2
Zone 3
Fault Resistance Effect on a Mho Characteristic
Rf
![Page 173: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/173.jpg)
49
Series Compensated Lines• Series caps added to increase load
transfers– Electrically shorten line
• Negative inductance• Difficult problem for distance relays• Application depends upon location of
capacitors
![Page 174: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/174.jpg)
50
Series Caps
21
21
Zl Zc
Zl > Zc
![Page 175: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/175.jpg)
51
Series CapsBypass MOD
Bypass Breaker
Discharge Reactor
Damping Circuit
Metal-Oxide Varistor (MOV)
Capacitor (Fuseless)
Triggered Gap
Isolating MOD Isolating MOD
Platform
Main Power Components for EWRP Series Capacitors
![Page 176: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/176.jpg)
52
Coordination Considerations • Zone 1
– 80 to 90% of compensated line impedance– Must not overreach remote bus with caps in
service• Zone 2
– 125% + of uncompensated apparent line impedance
– Must provide direct tripping for any line fault with caps bypassed
– May require longer time delays
![Page 177: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/177.jpg)
53
Power Swing• Power swings can cause false trip of 3
phase distance elements• Option to
– Block on swing (Out of step block)– Trip on swing (Out of step trip)
• Out of step tripping may require special breaker• Allows for controlled separation
• Some WECC criteria to follow if OOSB implemented
![Page 178: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/178.jpg)
54
Out Of Step BlockingX
R
Zone 1
Zone 2
Typical Out Of Step Block Characteristic
OOSB Outer Zone
OOSB Inner Zone
t = 30 ms?
![Page 179: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/179.jpg)
55
Ground Distance Protection
and Kn(21G)
![Page 180: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/180.jpg)
56
Fault Types• 3 Phase fault
– Positive sequence impedance network only• Phase to phase fault
– Positive and negative sequence impedance networks in parallel
• One line to ground fault– Positive, negative, and zero sequence
impedance networks in series• Phase to phase to ground fault
– Positive, negative, and zero sequence impedance networks in parallel
![Page 181: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/181.jpg)
57
Sequence Networks
![Page 182: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/182.jpg)
58
What Does A Distance Relay Measure?
• Phase current and phase to ground voltageZrelay = VLG/IL (Ok for 3 phase faults only)
• Phase to phase current and phase to phase voltageZrelay = VLL/ILL (Ok for 3 phase, PP, PPG
faults)• Phase current + compensated ground
current and phase to ground voltageZrelay = VLG/(IL + 3KnI0) (Ok for 3 phase, 1LG,
PPG faults)
![Page 183: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/183.jpg)
59
Kn - Why?• Using phase/phase or phase/ground
quantities does not give proper reach measurement for 1LG fault
• Using zero sequence quantities gives the zero sequence source impedance, not the line impedance
• Current compensation (Kn) does work for ground faults
• Voltage compensation could also be used but is less common
![Page 184: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/184.jpg)
60
Current Compensation, KnKn = (Z0L - Z1L)/3Z1L
Z0L = Zero sequence transmission line impedanceZ1L = Positive sequence transmission line
impedanceIRelay = IA + 3I0(Z0L- Z1L)/3Z1L = IA + 3KnI0
ZRelay = VA Relay/IRelay = VA/(IA + 3KnI0) = Z1L
Reach of ground distance relay with current compensation is based on positive sequence line impedance, Z1L
![Page 185: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/185.jpg)
61
Current Compensation, Kn• Current compensation (Kn) does work for
ground faults.• Kn = (Z0L – Z1L)/3Z1
– Kn may be a scalar quantity or a vector quantity with both magnitude and angle
• Mutual impedance coupling from parallel lines can cause a ground distance relay to overreach or underreach, depending upon ground fault location
• Mutual impedance coupling can provide incorrect fault location values for ground faults
![Page 186: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/186.jpg)
62
Ground Fault Protection
(67N)
![Page 187: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/187.jpg)
63
Ground Faults• Directional ground overcurrent relays
(67N)• Ground overcurrent relays
– Time overcurrent ground (51)– Instantaneous overcurrent (50)
• Measure zero sequence currents• Use zero sequence or negative sequence
for directionality
![Page 188: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/188.jpg)
64
Typical Ground Overcurrent Settings
• 51 Time overcurrentSelect TOC curve, usually very inversePickup, usually minimumTime delay >0.25 sec. for remote bus fault
• 50 Instantaneous overcurrent>125% Remote bus fault
• Must consider affects of mutual coupling from parallel transmission lines.
![Page 189: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/189.jpg)
65
Polarizing for Directional Ground Overcurrent Relays
• I Residual and I polarizing– I Polarizing: An autotransformer neutral CT
may not provide reliable current polarizing• I Residual and V polarizing
– I Residual 3I0 = Ia + Ib + Ic– V Polarizing 3V0 = Va + Vb + Vc
• Negative sequence – Requires 3 phase voltages and currents– More immune to mutual coupling problems
![Page 190: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/190.jpg)
66
Current Polarizing
I Polarizing
Auto Transformer Polarizing Current Source
CT
H1
X1
H3
X3
H2
X2
Y1
Y2
Y3
H0X0
![Page 191: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/191.jpg)
67
Voltage Polarizing
3 VO Polarizing Potential
Ea Eb Ec
![Page 192: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/192.jpg)
68
Mutual Coupling• Transformer affect between parallel lines
– Inversely proportional to distance between lines
• Only affects zero sequence current• Will affect magnitude of ground currents• Will affect reach of ground distance relays
![Page 193: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/193.jpg)
69
Mutual Coupling
Line #1
Line #2
3I0, Line #1
3I0, Line #2
![Page 194: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/194.jpg)
70
Mutual Coupling vs. Ground Relays
Taft
Taft
645 Amps
1315 Amps645 Amps
1980 Amps
920 Amps
260 Amps920 Amps
1370 Amps
1LG Faults With Mutual Impedances
1LG Faults Without Mutual Impedances
Garrison
Garrison
Taft Garrison
Taft Garrison
![Page 195: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/195.jpg)
71
Other Line Protection Relays
![Page 196: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/196.jpg)
72
Line Differential
87 87
![Page 197: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/197.jpg)
73
Line Differential Relays• Compare current magnitudes, phase, etc.
at each line terminal• Communicate information between relays• Internal/external fault? Trip/no trip?• Communications dependant!• Changes in communications paths or
channel delays can cause potential problems
![Page 198: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/198.jpg)
74
Phase Comparison• Compares phase relationship at terminals• 100% Channel dependant
– Looped channels can cause false trips• Nondirectional overcurrent on channel
failure• Immune to swings, load, series caps• Single pole capability
![Page 199: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/199.jpg)
75
Pilot Wire• Common on power house lines• Uses metallic twisted pair
– Problems if commercial line used– Requires isolation transformers and protection
on pilot wire• Nondirectional overcurrent on pilot failure• Newer versions use fiber or radio• Generally limited to short lines if metallic
twisted pair is used
![Page 200: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/200.jpg)
76
Pilot Wire
![Page 201: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/201.jpg)
77
Current Differential• Similar to phase comparison• Channel failure?
– Distance relay backup or– Non directional overcurrent backup or– No backup – must add separate back up
relay• Many channel options
– Changes in channel delays may cause problems
– Care required in setting up digital channels
![Page 202: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/202.jpg)
78
Current Differential• Single pole capability• 3 Terminal line capability• May include an external, direct transfer trip
feature • Immune to swings, load, series caps
![Page 203: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/203.jpg)
79
Transfer Trip
![Page 204: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/204.jpg)
80
Direct Transfer Trip• Line protection• Equipment protection
– Transformer terminated lines– Line reactors– Breaker failure
• 2 or more signals available– Analog or digital tone equipment
![Page 205: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/205.jpg)
81
Tone 1 Xmit
Tone 2 Xmit
PCB Trip Coil PCB Trip Coil
Tone 1 Rcvd
Tone 2 Rcvd
Direct Transfer Trip
Protective RelayProtective Relay
Direct Transfer Trip
![Page 206: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/206.jpg)
82
Direct Transfer Trip Initiation• Zone 1 distance• Zone 2 distance time delay trip• Zone 3 distance time delay trip• Instantaneous ground trip• Time overcurrent ground trip• BFR-Ring bus, breaker & half scheme• Transformer relays on transformer
terminated lines• Line reactor relays
![Page 207: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/207.jpg)
83
Tone 2 Xmit
Tone 2 Rcvd
Permissive Relay
PCB Trip Coil PCB Trip Coil
Tone 2 Xmit
Tone 2 Rcvd
Permissive Transfer Trip
Permissive Relay
Permissive Transfer Trip
![Page 208: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/208.jpg)
84
Permissive Keying• Zone 2 instantaneous• Permissive overcurrent ground (very
sensitive setting)• PCB 52/b switch• Current reversal can cause problems
![Page 209: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/209.jpg)
85
PRT Current Reversal
A
C D
B
Ib
Id
Ia
Ic
Fault near breaker B. Relays at B pick upRelays at B key permissive signal to A, trip breaker B instantaneously
Relays at A pick up and key permissive signal to B.Relays at C pick up and key permissive signal to C.
Relays at D block
I Fault, Line AB
I Fault, Line CD
![Page 210: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/210.jpg)
86
PRT Current Reversal
A
C D
B
Id
Ia
Ic
Breaker B opens instantaneously. Relays at B drop out.Fault current on line CD changes direction.
Relays at A remain picked up and trip by permissive signal from B.Relays at C drop out and stop keying permissive signal to C.
Relays at D pick up and key permissive signal to D.
I Fault, Line AB
I Fault, Line CD
![Page 211: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/211.jpg)
87
Directional Comparison Blocking
• Overreaching relays• Delay for channel time• Channel failure can allow overtrip• Often used with “On/Off” carrier
![Page 212: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/212.jpg)
88
Block Xmit
Block Rcvd
PCB Trip Coil PCB Trip Coil
Block Xmit
Block Rcvd
Directional Comparison Blocking Scheme
Time DelayTime Delay
ForwardRelay
ReverseRelay
ReverseRelay
ForwardRelay
TDTD
Directional Comparison
![Page 213: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/213.jpg)
89
Directional Comparison Relays• Forward relays must overreach remote
bus• Forward relays must not overreach remote
reverse relays• Time delay (TD) set for channel delay• Scheme will trip for fault if channel lost
– Scheme may overtrip for external fault on channel loss
![Page 214: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/214.jpg)
90
Tone Equipment
• Interface between relays and communications channel
• Analog tone equipment• Digital tone equipment• Security features
– Guard before trip– Alternate shifting of tones– Parity checks on digital
![Page 215: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/215.jpg)
91
Tone Equipment
• Newer equipment has 4 or more channels– 2 for direct transfer trip– 1 for permissive transfer trip– 1 for drive to lock out (block reclose)
![Page 216: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/216.jpg)
92
Relay to Relay Communications• Available on many new digital relays• Eliminates need for separate tone gear• 8 or more unique bits of data sent from
one relay to other• Programmable functions
– Each transmitted bit programmed for specific relay function
– Each received bit programmed for specific purpose
![Page 217: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/217.jpg)
93
Telecommunications Channels
• Microwave radio– Analog (no longer available)– Digital
• Other radio systems• Dedicated fiber between relays
– Short runs• Multiplexed fiber
– Long runs• SONET Rings
![Page 218: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/218.jpg)
94
Telecommunications Channels
• Power line carrier current– On/Off Carrier often used with directional
comparison• Hard wire
– Concern with ground mat interconnections– Limited to short runs
• Leased line– Rent from phone company– Considered less reliable
![Page 219: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/219.jpg)
95
Automatic Reclosing (79)• First reclose ~ 80% success rate• Second reclose ~ 5% success rate• Must delay long enough for arc to
deionizet = 10.5 + kV/34.5 cycles
14 cycles for 115 kV; 25 cycles for 500 kV• Must delay long enough for remote
terminal to clear• 1LG Faults have a higher success rate
than 3 phase faults
![Page 220: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/220.jpg)
96
Automatic Reclosing (79)• Most often single shot• Delay of 30 to 60 cycles following line trip
is common• Checking:
– Hot bus & dead line– Hot line & dead bus– Sync check
• Utilities have many different criteria for transmission line reclosing
![Page 221: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/221.jpg)
97
More on Reclosing• Only reclose for one line to ground faults • Block reclose for time delay trip (pilot
schemes)• Never reclose on power house lines• Block reclosing for transformer fault on
transformer terminated lines• Block reclosing for bus faults• Block reclosing for BFR• Do not use them
![Page 222: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/222.jpg)
98
Breaker Failure Relay(50BF)
![Page 223: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/223.jpg)
99
Breaker Failure• Stuck breaker is a severe impact to
system stability on transmission systems• Breaker failure relays are recommended
by NERC for transmission systems operated above 100 kV
• BFRs are not required to be redundant by NERC
![Page 224: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/224.jpg)
100
Breaker Failure Relays1. Fault on line2. Normal protective relays detect fault and
send trip to breaker.3. Breaker does not trip.4. BFR Fault detectors picked up.5. BFR Time delay times out (8 cycles)6. Clear house (open everything to isolate
failed breaker)
![Page 225: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/225.jpg)
101
Breaker Failure Relay
Typical Breaker Failure Scheme with Retrip
BFR FaultDetectorPCB Trip
Coil #1TD
Protective Relay
86
Trip
Block Close
TD
PCB TripCoil #2
BFR Retrip
BFR TimeDelay, 8~
![Page 226: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/226.jpg)
102
Typical BFR Clearing TimesProper Clearing:0 Fault occurs
+1~ Relays PU, Key TT+2~ PCB trips+1~ Remote terminal clears
3-4 Cycles local clearing time
4-5 Cycles remote clearing time
Failed Breaker:0 Fault occurs
+1~ BFR FD PU+8~ BFR Time Delay+1~ BFR Trips 86 LOR+2~ BU PCBs trip+1~ Remote terminal clears
12-13 Cycles local back up clearing time
13-14 Cycles remote backup clearing
![Page 227: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/227.jpg)
103
Remedial Action Schemes (RAS)
aka: Special Protection Schemes
![Page 228: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/228.jpg)
104
Remedial Action Schemes• Balance generation and loads• Maintain system stability• Prevent major problems (blackouts)• Prevent equipment damage• Allow system to be operated at higher
levels• Provide controlled islanding• Protect equipment and lines from thermal
overloads• Many WECC & NERC Requirements
![Page 229: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/229.jpg)
105
Remedial Action Schemes• WECC Compliant RAS
– Fully redundant– Annual functional test– Changes, modifications and additions must be
approved by WECC• Non WECC RAS
– Does not need full redundancy– Local impacts only– Primarily to solve thermal overload problems
![Page 230: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/230.jpg)
106
Underfrequency Load Shedding• Reduce load to match available generation• Undervoltage (27) supervised (V > 0.8 pu)• 14 Cycle total clearing time required• Must conform to WECC guidelines• 4 Steps starting at 59.4 Hz.• Restoration must be controlled• Must coordinate with generator 81 relays• Responsibility of control areas
![Page 231: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/231.jpg)
107
Undervoltage Load Shedding• Detect 3 Phase undervoltage• Prevent voltage collapse• Sufficient time delay before tripping to ride
through minor disturbances• Must Conform to WECC Guidelines• Primarily installed West of Cascades
![Page 232: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/232.jpg)
108
Generator Dropping• Trip generators for loss of load• Trip generators for loss of transmission
lines or paths– Prevent overloading
![Page 233: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/233.jpg)
109
Reactive Switching• On loss of transmission lines
– Trip shunt reactors to increase voltage– Close shunt capacitors to compensate for loss
of reactive supplied by transmission lines– Close series capacitors to increase load
transfers– Utilize generator var output if possible– Static Var Compensators (SVC) provide high
speed adjustments
![Page 234: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/234.jpg)
110
Direct Load Tripping• Provide high speed trip to shed load
– May use transfer trip – May use sensitive, fast underfrequency (81)
relay• Trip large industrial loads
![Page 235: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/235.jpg)
111
Other RAS Schemes• Controlled islanding
– Force separation at know locations• Load brake resistor insertion
– Provide a resistive load to slow down acceleration of generators
• Out of step tripping– Force separation on swing
• Phase shifting transformers– Control load flows
![Page 236: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/236.jpg)
112
Typical RAS Controller
![Page 237: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/237.jpg)
113
Typical RAS Controller Outputs• Generator tripping• Load tripping • Controlled islanding and separation (Four
Corners)• Insert series caps on AC Intertie• Shunt capacitor insertion• Shunt reactor tripping• Chief Jo Load Brake Resister insertion• Interutility signaling• AGC Off
![Page 238: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/238.jpg)
114
Chief Jo Brake
1400 Megawatts @ 230 kV
![Page 239: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/239.jpg)
115
RAS Enabling Criteria• Power transfer levels• Direction of power flow• System configuration• Some utilities are considering automatic
enabling/disabling based on SCADA data• Phasor measurement capability in relays
can be used to enable RAS actions
![Page 240: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/240.jpg)
116
RAS Design Criteria• Generally fully redundant • Generally use alternate route on
telecommunications• Extensive use of transfer trip for signaling
between substations, power plants, control centers, and RAS controllers
![Page 241: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/241.jpg)
117
UFOs vs. Power Outages
![Page 242: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/242.jpg)
118
the end
Jon F. DaumeBonneville Power Administration
retired
March 15, 2011
![Page 243: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/243.jpg)
![Page 244: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/244.jpg)
![Page 245: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/245.jpg)
![Page 246: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/246.jpg)
![Page 247: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/247.jpg)
![Page 248: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/248.jpg)
![Page 249: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/249.jpg)
![Page 250: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/250.jpg)
![Page 251: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/251.jpg)
![Page 252: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/252.jpg)
![Page 253: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/253.jpg)
![Page 254: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/254.jpg)
![Page 255: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/255.jpg)
![Page 256: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/256.jpg)
![Page 257: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/257.jpg)
![Page 258: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/258.jpg)
![Page 259: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/259.jpg)
![Page 260: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/260.jpg)
![Page 261: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/261.jpg)
![Page 262: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/262.jpg)
![Page 263: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/263.jpg)
![Page 264: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/264.jpg)
![Page 265: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/265.jpg)
![Page 266: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/266.jpg)
![Page 267: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/267.jpg)
![Page 268: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/268.jpg)
![Page 269: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/269.jpg)
![Page 270: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/270.jpg)
![Page 271: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/271.jpg)
![Page 272: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/272.jpg)
![Page 273: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/273.jpg)
![Page 274: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/274.jpg)
![Page 275: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/275.jpg)
![Page 276: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/276.jpg)
![Page 277: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/277.jpg)
![Page 278: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/278.jpg)
![Page 279: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/279.jpg)
![Page 280: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/280.jpg)
![Page 281: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/281.jpg)
![Page 282: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/282.jpg)
![Page 283: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/283.jpg)
![Page 284: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/284.jpg)
![Page 285: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/285.jpg)
![Page 286: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/286.jpg)
![Page 287: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/287.jpg)
![Page 288: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/288.jpg)
![Page 289: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/289.jpg)
![Page 290: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/290.jpg)
![Page 291: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/291.jpg)
![Page 292: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/292.jpg)
![Page 293: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/293.jpg)
![Page 294: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/294.jpg)
![Page 295: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/295.jpg)
![Page 296: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/296.jpg)
![Page 297: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/297.jpg)
![Page 298: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/298.jpg)
![Page 299: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/299.jpg)
![Page 300: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/300.jpg)
![Page 301: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/301.jpg)
![Page 302: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/302.jpg)
![Page 303: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/303.jpg)
![Page 304: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/304.jpg)
![Page 305: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/305.jpg)
![Page 306: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/306.jpg)
![Page 307: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/307.jpg)
![Page 308: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/308.jpg)
![Page 309: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/309.jpg)
![Page 310: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/310.jpg)
![Page 311: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/311.jpg)
![Page 312: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/312.jpg)
![Page 313: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/313.jpg)
![Page 314: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/314.jpg)
![Page 315: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/315.jpg)
![Page 316: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/316.jpg)
![Page 317: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/317.jpg)
![Page 318: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/318.jpg)
![Page 319: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/319.jpg)
![Page 320: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/320.jpg)
![Page 321: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/321.jpg)
![Page 322: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/322.jpg)
![Page 323: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/323.jpg)
![Page 324: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/324.jpg)
![Page 325: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/325.jpg)
![Page 326: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/326.jpg)
![Page 327: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/327.jpg)
![Page 328: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/328.jpg)
![Page 329: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/329.jpg)
![Page 330: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/330.jpg)
![Page 331: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/331.jpg)
![Page 332: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/332.jpg)
![Page 333: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/333.jpg)
![Page 334: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/334.jpg)
![Page 335: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/335.jpg)
![Page 336: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/336.jpg)
![Page 337: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/337.jpg)
![Page 338: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/338.jpg)
![Page 339: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/339.jpg)
![Page 340: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/340.jpg)
![Page 341: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/341.jpg)
![Page 342: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/342.jpg)
![Page 343: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/343.jpg)
![Page 344: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/344.jpg)
![Page 345: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/345.jpg)
![Page 346: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/346.jpg)
![Page 347: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/347.jpg)
![Page 348: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/348.jpg)
![Page 349: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/349.jpg)
![Page 350: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/350.jpg)
![Page 351: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/351.jpg)
![Page 352: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/352.jpg)
![Page 353: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/353.jpg)
![Page 354: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/354.jpg)
![Page 355: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/355.jpg)
![Page 356: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/356.jpg)
![Page 357: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/357.jpg)
![Page 358: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/358.jpg)
![Page 359: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/359.jpg)
![Page 360: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/360.jpg)
![Page 361: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/361.jpg)
![Page 362: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/362.jpg)
![Page 363: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/363.jpg)
![Page 364: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/364.jpg)
![Page 365: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/365.jpg)
![Page 366: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/366.jpg)
![Page 367: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/367.jpg)
![Page 368: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/368.jpg)
![Page 369: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/369.jpg)
![Page 370: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/370.jpg)
![Page 371: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/371.jpg)
![Page 372: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/372.jpg)
Transmission System Faults and Event AnalysisFault Analysis Theory
andModern Fault Analysis Methods
Presented by:Matthew Rhodes
Electrical Engineer, SRP1
![Page 373: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/373.jpg)
Transmission System Fault Theory
• Symmetrical Fault Analysis• Symmetrical Components• Unsymmetrical Fault Analysis using
sequence networks
• Lecture material originally developed by Dr. Richard Farmer, ASU Research Professor
2
![Page 374: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/374.jpg)
3
Symmetrical Faults
![Page 375: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/375.jpg)
4
FaultsShunt faults:Three phase a
bc
Line to line
Line to ground
2 Line to ground
ba
c
abc
abc
![Page 376: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/376.jpg)
5
Faults
Series faultsOne open phase:
abc
2 open phasesabc
Increased phase impedance
Z abc
![Page 377: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/377.jpg)
6
Why Study Faults?• Determine currents and voltages in the
system under fault conditions• Use information to set protective devices• Determine withstand capability that
system equipment must have:– Insulating level– Fault current capability of circuit breakers:
• Maximum momentary current• Interrupting current
![Page 378: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/378.jpg)
7
Symmetrical Faults
α
t=0
2 V
i(t)
Fault at t = 0AC
R L
)sin(2)( αω += tVte
![Page 379: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/379.jpg)
8
Symmetrical Faults
For a short circuit at generator terminals at t=0and generator initially open circuited:
dtdiLRite +=)(
dtdiLRitVSin +=+ )(2 αω
by using Laplace transforms i(t) can be found
(L is considered constant)
![Page 380: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/380.jpg)
9
Symmetrical Faults]/)()([2)( TteSintSin
ZVti −−−−+= θαθαω
2222 )( XRLRZ +=+= ω
RXTan
RLTan 11 −− ==
ωθ
Where:
RX
RLT
ω== Time Constant
]/)()([2)( TteSintSinacIti −−−−+= θαθαω
Where: Iac = ac RMS fault current at t=0 (Examples)
Note that for a 3-phase system α will be different for each phase. Therefore, DC offset will be different for each phase
![Page 381: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/381.jpg)
10
t = 0
acI2 iac
Idc = 0
]/)()([2)( TteSintSinacIti −−−−+= θαθαω
o90== θαV2 e(t)
o90=α
![Page 382: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/382.jpg)
11
]/)()([2)( TteSintSinacIti −−−−+= θαθαω
0=αo90=θ
V2 e(t)
t = 0
iac02 acI
02 acI idc
![Page 383: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/383.jpg)
12
iac02 acI
02 acI idc
022 acI
t
0=αo90=θ
]/)()([2)( TteSintSinacIti −−−−+= θαθαω
)(ti
![Page 384: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/384.jpg)
13
Symmetrical FaultsIac and Idc are independent after t = 0
22
dcIacIRMSI +=
TteacoIdcI −= 2
Substituting:
Tteac
ITt
eac
Iac
IRMS
I 221)222((max) −+=−
+=
]/)2/([2)( TtetSinZVti −+−+= πω
![Page 385: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/385.jpg)
14
Asymmetry FactorIRMS(max) = K(τ) Iac
Asymmetry Factor = K(τ)
rxeK
τπτ
421)(−
+=
Where:
τ = number of cycles
(Example 7.1)
fRXT π2/=
![Page 386: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/386.jpg)
15
Example 7.1
•Fault at a time to produce maximum DC offset
•Circuit Breaker opens 3 cycles after fault inception
IFault at t = 0AC
R = 0.8 Ώ XL = 8 Ώ
V = 20 kVLN-
+
CB
Find:
1. Iac at t = 0
2. IRMS Momentary at = 0.5 cycles
3. IRMS Interrupting Current
τ
![Page 387: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/387.jpg)
16
Example 7.1a. RMSAC kAI 488.2
88.020)0(
22=
+=
b.438.121)5.0( )10
5.(4=+=
Π−eKKAImomentary 577.3)488.2)(438.1( ==
c.
023.121)3( )103(4
=+=Π−eK
KAI ngInterrupti 545.2)488.2)(023.1( ==
![Page 388: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/388.jpg)
17
AC DecrementIn the previous analysis we treated the
generator as a constant voltage behind a constant impedance for each phase. The constant inductance is valid for steady state conditions but for transient conditions, the generator inductance is not constant.
The equivalent machine reactance is made up of 2 parts:
a) Armature leakage reactance b) Armature reaction
(See Phasor Diagram)
![Page 389: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/389.jpg)
18
AC Decrement
Steady state model of generatorXL is leakage reactance
XAR is a fictitious reactance and XAR>> XL
XAR is due to flux linkages of armature current with the field circuit. Flux linkages can not change instantaneously. Therefore, if the generator is initially unloaded when a fault occurs the effective reactance is XL which is referred to as Subtransient Reactance, x”.
EI
R XL XAR
Load
![Page 390: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/390.jpg)
19IL
jILXL
jILXAR(t)
EIField Flux
Armature Reaction
Resultant Field
ET
XL XAR
-
+EI
I=IL
Load
Loaded Generator
![Page 391: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/391.jpg)
20
E”Field Flux
Armature Reaction = 0
Resultant Field ET0
t = 0 -
XL XAR=0ET0
-
+E” = E’ = E = ET0
I=0
Unloaded Generator
![Page 392: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/392.jpg)
21
XL XAR
-
+E” = E’ = E = ET0
I=0
t=0
E”Field Flux
Armature Reaction = 0
Resultant Field
ET0 = 0
Faulted Generator
![Page 393: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/393.jpg)
22
XL XAR=0
-
+E” = E’ = E = ET0
I = I”
E” = jI”XL
t=0+
Field Flux
Resultant Field
ET = 0
I”
Armature Reaction = 0
![Page 394: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/394.jpg)
23
XL XAR’
-
+E” = E’ = E = ET0
I = I’
E’ = jI’(XL + XAR’)
t ≈ 3Cyc.
Field Flux
Resultant Field
ET = 0
I’
Armature Reaction = 0
![Page 395: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/395.jpg)
24
XL XAR
-
+E” = E’ = E = ET0
I = I
E’ = jI(XL + XAR)
t =∞
Field Flux
Resultant Field
ET = 0
I’
Armature Reaction = 0
![Page 396: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/396.jpg)
25
AC DecrementAs fault current begins to flow, armature reaction will
increase with time thereby increasing the apparent reactance. Therefore, the ac component of the fault current will decrease with time to a steady state condition as shown in the figure below.
"2I '2I I2"2I
![Page 397: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/397.jpg)
26
AC DecrementFor a round rotor machine we only need to
consider the direct axis reactance.
dXEI
""2"2 = Subtransient
dXEI
''2'2 =
dXEI 22 =
Transient
Synchronous(steadystate)
![Page 398: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/398.jpg)
27
AC Decrement
Can write the ac decrement equation[ ] ([ )])'()'"(2)( '" θαω −++−+−=
−− tSinIeIIeIItaci dTtdTt
For an unloaded generator (special case):TEEEE === '"
T”d: Subtransient time constant (function of amortisseur winding X/R)
T’d: Transient time constant (function of field winding X/R)
Look at equation for t=0 and t=infinity
![Page 399: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/399.jpg)
28
AC Decrement
For t = 0
[ ] ([ )])'()'"(2)( '" θαω −++−+−=−− tSinIeIIeIItaci dT
tdTt
For t = ∞
IIiac 2]00[2(max) =++=
"2])'()'"[(2(max) IIIIIIiac =+−+−=
![Page 400: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/400.jpg)
29
ac and dc DecrementTransform ac decrement equation to phasor form
] θα −+−
−+−
−=⎢⎢⎣
⎡/')'(")'"(
_IdT
teIIdT
teIIacI
dc decrement equation:
AT
t
eSinIdcI−
−= )("2 θα
Where TA = Armature circuit time constant
(Example 7.2)
![Page 401: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/401.jpg)
30
Example 7.2
IFault at t = 0AC
R = 0
V = 1.05 pu-
+
CB
x”d =.15pu T”d = .035 Sec.x’d = .24pu T’d = 2.0 Sec.xd = 1.1pu TA = 0.2 Sec.
No load when 3-phase fault occurs Breaker clears fault in 3 cycles.Find: a) I”, b) IDC(t)
c) IRMS at interruption d) Imomentry (max)
S
500 MVA, 20kV, 60 Hz Synchronous Generator
![Page 402: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/402.jpg)
31
Example 7.2⎥⎦⎤
⎢⎣⎡ +⎟
⎠⎞
⎜⎝⎛ −+⎟
⎠⎞
⎜⎝⎛ −= −−
1.11
1.11
24.1
24.1
15.105.1)( 2035. tt
AC eetI
2.max "2)(
t
DC eItI −= KAIBase 434.14
320500
==
kApudx
EI 1010.715.05.1
""" ==== a
DCI
2.2.max 9.9)7(2)(
tt
DC eetI −−== b
![Page 403: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/403.jpg)
32
Example 7.2Part c: Find IRMS at interruption (3 cycles)
.sec05.0603==t
⎥⎦⎤
⎢⎣⎡ +⎟
⎠⎞
⎜⎝⎛ −+⎟
⎠⎞
⎜⎝⎛ −= −−
1.11
1.11
24.1
24.1
15.105.1)( 205.035.
05.eetI AC
( )[ ] puI AC 92.4909.)975)(.258.3()24(.5.205.1)05(. =++=
pueI DC 71.79.9)05(. 2.05.
==−
kApuI RMS 132146.971.792.4)05(. 22 ==+= c
![Page 404: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/404.jpg)
33
Example 7.2Part d: Find IMomentary(max) at t = ½ cycle
sec0083.605.==t
( )[ ] puI AC 43.6909.)996)(.258.3()79(.5.205.1)0083(. =++=
⎥⎦⎤
⎢⎣⎡ +⎟
⎠⎞
⎜⎝⎛ −+⎟
⎠⎞
⎜⎝⎛ −= −−
1.11
1.11
24.1
24.1
15.105.1)( 20083.035.
0083.eetI AC
pueI DC 5.99.9 2.0083.
==−
kApuI RMS 2159.145.943.6 22 ==+= d
![Page 405: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/405.jpg)
34
TurbineGen.
Energy
![Page 406: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/406.jpg)
35
Superposition for Fault Analysis
![Page 407: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/407.jpg)
36
Superposition for Fault AnalysisNew representation:
IF1
IF2=0
Bus 1
Bus 1 Bus 2
IG = IG! + IG2 = IG1+ IL IM = IM1 – IL IF = IG1 + IM1Example 7.3
IG1IG2
ILIM1
IGIF IM
![Page 408: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/408.jpg)
37
Example 7.3For the system of Slide 35 and 36 the generator is operating at 100 MVA, .95 PF Lagging 5% over rated voltage
Part a: Find Subtransient fault current magnitude.From Slide 36
pujjjZ
VITH
FF 08.9
116.05.1
655.)505)(.15(.
05.1"1 −====
Part b: Neglecting load current, find Generator and motor fault current.
pujjIG 7655.505.08.9"1 −=−=
pujjjI M 08.2)7(08.9"1 −=−−−=
![Page 409: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/409.jpg)
38
Example 7.3Part c: Including load current, find Generator and motor current during the fault period.
22*
*
18/952.05.118/1
0/05.195.cos/1
MGo
o
oLoad IIVSI −==−=
−=
−==
pujI ooG 83/35.718/953.7" −=−+−=
pujI ooM 243/00.218/952.08.2" =−−−=
c
c
![Page 410: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/410.jpg)
39
Z Bus Method
For Z bus method of fault studies the following approximations are made:
• Neglect load current• Model series impedance only• Model generators and synchronous
motors by voltage behind a reactance for the positive sequence system
![Page 411: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/411.jpg)
40
AC
AC
AC
+
Eg”
-
+
E m
-
J 0 . 2
J 0 . 305J 0 . 15
1 2
-VFIF
![Page 412: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/412.jpg)
41
Z Bus MethodFor the circuit of Figure 7.4d (Slide 36 & 40)
⎥⎦
⎤⎢⎣
⎡⎥⎦
⎤⎢⎣
⎡=⎥
⎦
⎤⎢⎣
⎡
2
1
22
12
21
11
2
1
EE
YY
YY
II
Injected node currents
[matrix
Y-bus] nodal admittance
Node voltages
Premultiplying both sides by the inverse of [Y-bus
Pre-fault node Voltage
[Z-Bus] =[Y-Bus]-1
Injected node Current
-IF1
0For a fault at Bus 1
)( 1111 FIZE −=
⎟⎟⎠
⎞⎜⎜⎝
⎛ −−=
−=
1111
11 Z
VZEI F
F
⎥⎦
⎤⎢⎣
⎡⎥⎦
⎤⎢⎣
⎡=⎥
⎦
⎤⎢⎣
⎡
2
1
2221
1211
2
1
II
ZZZZ
EE
![Page 413: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/413.jpg)
42
Z-Bus Method
⎟⎟⎠
⎞⎜⎜⎝
⎛ −−=
−=
1111
11 Z
VZEI F
F
)( 1111 FIZE −=
111 Z
VI FF =
where:
For a fault at Bus 1
IF1 = Fault current at bus 1 VF = Prefault voltage of the faulted bus (Bus 1)
![Page 414: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/414.jpg)
43
Z-Bus MethodFor N bus system, fault on Bus n
⎥⎥⎥⎥⎥⎥⎥⎥
⎦
⎤
⎢⎢⎢⎢⎢⎢⎢⎢
⎣
⎡
−
⎥⎥⎥⎥⎥⎥⎥⎥
⎦
⎤
⎢⎢⎢⎢⎢⎢⎢⎢
⎣
⎡
=
⎥⎥⎥⎥⎥⎥⎥⎥
⎦
⎤
⎢⎢⎢⎢⎢⎢⎢⎢
⎣
⎡
0.
000
...,...
.
.
.
.
.
321
321
33333231
22232221
11131211
3
2
1
Fn
NNNnNNN
nNnnnnn
Nn
Nn
Nn
N
N I
ZZZZZ
ZZZZZZZZZZZZZZZZZZZZ
E
EEEE
-VF
nn
FFn Z
VI = Where: VF = Pre-fault voltage at faulted bus Znn = Thevinen impedance
![Page 415: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/415.jpg)
44
Z-Bus MethodAfter IFn is found the voltage at any bus can be
found from:E1 = Z1n (-Ifn) E2 = Z2n(-Ifn) Etc.
If voltage at each bus is found, current through any branch can be found:I12 = (E1 - E2) / Ž12 Etc/Note: Ž12 is series impedance between Bus1
and Bus 2, not from Z-Bus.(Example 7.4)
![Page 416: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/416.jpg)
45
Example 7.4For the system of Figure 7.3 (Slide 40) using the Z-bus method find:a) Z busb) IF and I contribution from Line for Bus 1
faultc) IF and I contribution from Line for Bus 2
fault
Y20 = -j5Y10 = -j6.67
Y12 = -j3.28
1 2
IF
![Page 417: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/417.jpg)
46
Example 7.4[ ] ⎥
⎦
⎤⎢⎣
⎡−
−=
95.928.328.395.9
jjjj
YBus
[ ] [ ] ⎥⎦
⎤⎢⎣
⎡== −
139.046.046.1156.1
jjjj
YZ busBus
⎥⎦
⎤⎢⎣
⎡⎥⎦
⎤⎢⎣
⎡=⎥
⎦
⎤⎢⎣
⎡
2
1
2
1
139.046.046.1156.
II
jjjj
EE
0
-IF
11 )1156.( IjE =
-VF -IF
08.91156.
" jjVI F
F −==
a
b
![Page 418: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/418.jpg)
47
Example 7.4
⎥⎦
⎤⎢⎣
⎡⎥⎦
⎤⎢⎣
⎡=⎥
⎦
⎤⎢⎣
⎡
2
1
2
1
139.046.046.1156.
II
jjjj
EE
For fault at Bus 1: E1 = E11+ E1
2 = 0
E2 = E21 + E2
2 = VF + (j.046)I1E2 = 1.05 + (j.046)(j9.08) = .632 /0o
07.2305.
0632.21
1221 j
jZEEI −=
−=
−=
Find: Line current
b
![Page 419: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/419.jpg)
48
Example 7.4
Y20 = -j5Y10 = -j6.67
Y12 = -j3.281 2
IFFind IF and I contribution from Line for Bus 2 fault
⎥⎦
⎤⎢⎣
⎡⎥⎦
⎤⎢⎣
⎡=⎥
⎦
⎤⎢⎣
⎡
2
1
2
1
139.046.046.1156.
II
jjjj
EE
-VF
pujj
IF 55.7139.05.1
2 −==
- I F2
oFF jjIjVE 0/703.)55.7)(046.(05.1))(046.(1 =+=−+=
pujjZ
EEI 3.2305.
0703.12
2112 −=
−=
−= c
![Page 420: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/420.jpg)
49
Z-Bus Method
[Z-Bus] = [Y-Bus]-1
Will not cover formation of [Z-Bus] or [Y-Bus]
[Z-Bus] can be considered a fictitious circuit which has the appearance of a rake. See Figure 7.6 on Page 371.
![Page 421: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/421.jpg)
50
nn
FnF Z
VII ==Example: Fault at Bus n
))(( 11 nnF IZVE −=
Etc.
Z-Bus Rake equivalent
![Page 422: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/422.jpg)
51
Class Problem 1
pujZbus⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
08.06.04.06.12.08.04.08.12.
For the given Bus Impedance matrix(where subtransient reactances were used) and a pre-fault voltage of 1 p.u.:
a. Draw the rake equivalent circuit
b. A three-phase short circuit occurs at bus 2. Determine the subtransient fault current and the voltages at buses 1, 2, and 3 during the fault.
![Page 423: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/423.jpg)
52
Symmetrical Components
![Page 424: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/424.jpg)
53
Symmetrical Components
Symmetrical Components is often referred to as the language of the Relay Engineer but it is important for all engineers that are involved in power.
The terminology is used extensively in the power engineering field and it is important to understand the basic concepts and terminology.
![Page 425: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/425.jpg)
54
Symmetrical Components• Used to be more important as a calculating
technique before the advanced computer age. • Is still useful and important to make sanity
checks and back-of-an-envelope calculation.• We will be studying 3-phase systems in
general. Previously you have only considered balanced voltage sources, balanced impedance and balanced currents.
![Page 426: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/426.jpg)
55
Symmetrical Components
naa
b b
c
Va Vb
Vc
Va
Vb
Vc
Balanced load supplied by balanced voltages results in balanced currents
This is a positive sequence system,
In Symmetrical Components we will be studying unbalanced systems with one or more dissymmetry.
ZY
ZYZY
Ib
Ia
Ic
![Page 427: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/427.jpg)
56
Symmetrical ComponentsFor the General Case of 3 unbalanced voltages
VA
VB
VC6 degrees of freedom
Can define 3 sets of voltages designated as positive sequence, negative sequence and zero sequence
![Page 428: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/428.jpg)
57
Symmetrical ComponentsCommon a operator identities
a =1/120o
a2 = 1/240o
a3 = 1/0o
a4 = 1/120o
1+a+a2 = 0
(a)(a2) = 1
![Page 429: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/429.jpg)
58
Symmetrical ComponentsPositive Sequence
120o
120o120o
VA1
VB1
VC1
2 degrees of freedom
VA1 = VA1
VB1 = a2 VA1
VC1 = a VA1
a is operator 1/120o
![Page 430: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/430.jpg)
59
Symmetrical ComponentsNegative Sequence
120o
120o120o
VA2
VC2
VB2
2 degrees of freedom
a is operator 1/120o
VA2 = VA2 VB2 = aVA2 VC2 = a2 VA2
![Page 431: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/431.jpg)
60
Symmetrical ComponentsZero Sequence
2 degrees of freedom
VA0VB0VC0
VA0 = VB0 = VC0
![Page 432: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/432.jpg)
61
Symmetrical ComponentsReforming the phase voltages in terms of the symmetrical component voltages:
VA = VA0 + VA1 + VA2
VB = VB0 + VB1 + VB2
VC = VC0 + VC1 + VC2
What have we gained? We started with 3 phase voltages and now have 9 sequence voltages. The answer is that the 9 sequence voltages are not independent and can be defined in terms of other voltages.
![Page 433: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/433.jpg)
62
Symmetrical ComponentsRewriting the sequence voltages in term of the Phase A sequence voltages:
VA = VA0 + VA1 +VA2VB = VA0 + a2 VA1 + aVA2VC = VA0 + aVA1 +a2 VA2
VA = V0 + V1 +V2VB = V0 + a2 V1 + aV2VC = V0 + aV1 +a2 V2
Drop A
Suggests matrix notation:
VA 1 1 1 V0
VB 1 a2 a V1
VC 1 a a2 V2
=
[VP] = [A] [VS]
![Page 434: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/434.jpg)
63
Symmetrical ComponentsWe shall consistently apply:[VP] = Phase Voltages[VS] = Sequence Voltages
1 1 1[A] = 1 a2 a
1 a a2
[VP] = [A][VS]
Pre-multiplying by [A]-1
[A]-1[VP] = [A]-1[A][VS]= [I][VS]
[VS] = [A]-1 [VP]
![Page 435: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/435.jpg)
64
Operator aa = 1 /120o = - .5 + j .866
a2 = 1 / 240o = - .5 - j.866
a3 = 1 / 360o = 1
a4 = 1 / 480o = 1 / 120o = a
a5 = a2 etc.
1 + a + a2 = 0
a - a2 = j 3
1 - a2 = /30o
1/a = a2
3
Relationships of a can greatly expedite calculations
( Find [A]-1)
![Page 436: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/436.jpg)
65
Inverse of A
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
2
2
11
111
aaaaA
Step 1: Transpose
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
2
2
11
111
aaaaA T
Step 2: Replace each element by its minor
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−−−−−−−−−
1111
22
22
222
aaaaaaaa
aaaaaa1
1
2
3
2 3
![Page 437: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/437.jpg)
66
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−−−−−−−−−
1111
22
22
222
aaaaaaaa
aaaaaa1
1
2
3
2 3
Inverse of A
Step 3: Replace each element by its cofactor
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−−−−−−−−−
1111
22
22
222
aaaaaaaaaaaaaa1
1
2
3
2 3
![Page 438: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/438.jpg)
67
Inverse of A
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−−−−−−−−−
1111
22
22
222
aaaaaaaaaaaaaa1
1
2
3
2 3
Step 4: Divide by Determinant
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
2
2
11
111
aaaaA
)(3)(1)(1)(1 2222 aaaaaaaaD −=−+−+−=
aaaa
aaa
aa
aaa
=−−
=−−
⎟⎠⎞
⎜⎝⎛=
−−
1111
2
2
2
2
2
2
22
11111 a
aaa
aaaa
==−−
⎟⎠⎞
⎜⎝⎛=
−−
![Page 439: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/439.jpg)
68
Inverse of A
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=−
aaaaA
2
21
11
111
31
![Page 440: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/440.jpg)
69
Symmetrical ComponentsPrevious relationships were developed for voltages. Same could be developed for currents such that:
IAIBIC
[IP] =I0I1I2
[IS] =
[IP] = [A] [IS] [IS] = [A]-1 [IP]
1 1 1[A] = 1 a2 a
1 a a2
1 1 1[A]-1 = 1/3 1 a a2
1 a2 a
![Page 441: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/441.jpg)
70
Significance of I0
IAIBIC
I0I1I2
1 1 1= 1/3 1 a a2
1 a2 a
I0 = 1/3 ( IA + IB + IC)
n
IA
IB
IC
In
In = IA + IB + IC = 3 I0
For a balanced system I0 = 0
For a delta system I0 = 0
(Examples 8.1, 8.2 and 8.3)
![Page 442: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/442.jpg)
71
Example 8.1
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−=aaV
o
o
o
P
277277
277
120/277120/2770/277
2
[ ] [ ] [ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡==
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡= −
00/277
01
11
111
3277 2
2
21
2
1
0o
PS
aa
aaaaVA
VVV
V0
12
Find [VS] (Sequence voltages)
a
bc
![Page 443: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/443.jpg)
72
Example 8.2Y connected load with reverse sequence
[ ] ( )⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−=
2
110
120/10120/10
0/10
aaI
o
o
o
P
a
bc
Find IS (Sequence Currents)
[ ] [ ] [ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡== −
oPS
aa
aaaaIAI
0/10001
11
111
310
22
210
1
2
![Page 444: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/444.jpg)
73
Example 8.3Ia = 10 / 0o
Ic = 10 /120o
Ib = o
In
[ ] [ ] [ ]PS IAIII
I 1
2
1
0−=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
aaaaaI S 0
1
11
111
310
2
2
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−
−=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
+
+=
o
o
o
S
a
a
a
aI
60/33.30/67.6
60/33.32
310
12
1
310
2
2
0
1
2
on II 60/103 0 ==
a
bc
![Page 445: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/445.jpg)
74
Sequence Impedance for Shunt Elements
Sequence Networks of balanced Y elements( Loads, Reactors,capacitor banks, etc.)
VA = IAZy + (IA + IB +IC) Zn = (ZY + Zn)IA + ZnIB + ZnIC
VB = ZnIA + (ZY + Zn)IB + ZnIC
VC = ZnIA + ZnIB +(ZY + Zn)IC
n
IB
IC
.
IA
VB
VA VC
ZYZY
ZYZn
![Page 446: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/446.jpg)
75
Sequence Impedance for Shunt Elements
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
++
+=⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
C
B
A
nYnn
nnYn
nnnY
C
B
A
III
ZZZZZZZZZZZZ
VVV
[VP] = [ZP] [IP] (1)Transform to sequence reference frame. We know: [VP] = [A] [VS] and [IP] = [A] [IS], Substitute in(1)
[A][VS] = [ZP][A][IS] premultiply both sides by [A]-1
[VS] = [A]-1[ZP][A][IS] = [ZS][IS]
where: [ZS] = [A]-1[ZP][A]
![Page 447: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/447.jpg)
76
Sequence Impedance forShunt Elements
[ZS] =⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
++
+
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
2
2
2
2
222120
121110
020100
11
111
11
111
31
aaaa
ZZZZZZZZZZZZ
aaaa
ZZZZZZZZZ
nYnn
nnYn
nnnY
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡ +=
Y
Y
nY
S
ZZ
ZZZ
000003 0
1
2
0 1 2
![Page 448: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/448.jpg)
77
Sequence Impedance for Shunt Elements
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡ +=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
2
1
0
2
1
0
0000003
III
ZZ
ZZ
VVV
Y
Y
nY
V0 = Z00 I0 where: Z00 = ZY +3 Zn
V1 = Z11 I1
V2 = Z22 I2 where Z11 = Z22 = ZY
Systems are uncoupled: Zero sequence currents only produce zero sequence voltages. Positive sequence currents only produce positive sequence voltages, etc.
![Page 449: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/449.jpg)
78
Sequence Impedance forShunt Elements
We can form sequence circuits which represent the equations:
ZY
3 Zn
ZY
ZY
V0
V1
V2
I0
I1
I2
Zero sequence circuit Znonly in zero Sequence No neutral: Zn = infinity Solid ground: Zn = 0
Positive sequence circuit
Negative sequence circuit
![Page 450: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/450.jpg)
79
Sequence Impedance forShunt Elements
Delta connected shunt element
ZYV0
V1
V2
I0
I1
I2
open
ZΔ/3
ZΔ/3
Sequence circuits.A
B
C
IA
IB
IC
ZΔ
ZΔ ZΔ
![Page 451: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/451.jpg)
80
Sequence Impedance forShunt Elements
For the general case: [ZS] = [A]-1[ZP][A]
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
2
2
2
2
222120
121110
020100
11
111
11
111
31
aaaa
ZZZZZZZZZ
aaaa
ZZZZZZZZZ
CCCBCA
BCBBBA
ACABAA
If there is symmetry: ZAA = ZBB = ZCC and ZAB = ZBC = ZCA we could perform multiplication and get:
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−−
+=
ABAA
ABAA
ABAA
S
ZZZZ
ZZZ
0000002
We see that: Z11 = Z22 and Z00 > Z11
![Page 452: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/452.jpg)
81
ZAB
ZBC
ZAA
ZCC
VAA’
ZBB
VAA’
VBB’
IA
IB
IC
VA
VB
VC
ZCA
VA’VB’
VC ’
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−−−
C
B
A
CCCBCA
BCBBBA
ACABAA
CC
BB
AA
III
ZZZZZZZZZ
VVVVVV
'
'
'
n n
Series Element Sequence Impedance
![Page 453: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/453.jpg)
82
Series Element Sequence ImpedanceMatrices in compact form
[VP]-[VP’] = [ZP] [IP]
We can transform to the symmetrical component reference frame:
[VS] - [VS’] = [ZS] [IS] where: [ZS] = [A]-1[ZP][A]
If ZAA = ZBB = ZCC and ZAB = ZBC = ZCA , [ZS] will be the diagonal matrix:
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
2
1
0
ZZ
ZZS
![Page 454: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/454.jpg)
83
Series Element Sequence Impedance
The sequence circuits for series elements are:
Z0V0 V0’I0
o n0
Z1V1 V1’I1
o n1
Z2V2 V2’I2
o n2
![Page 455: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/455.jpg)
84
Series Element Sequence Impedance
We have quickly covered the calculation of Positive and Negative sequence parameters for 3-phase lines. To determine the zero sequence impedance we need to take the effect of the earth into account. This is done by using Carson’s Method which treats the earth as an equivalent conductor.
![Page 456: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/456.jpg)
85
Rotating Machine Sequence Networks
A
B
C
ZK
ZK
ZK
-
- -
+
+ +
EB
EAEC
ICIA
IB
Zn
ZAB
ZBC
ZCA
ZCB
ZBA
ZAC
eA = Em Cos ωt eB = Em Cos(ωt – 120o)eC = Em Cos(ωt + 120o)
In phasor form:EA= ERMS / 0 = E EB = ERMS /-120o = a2 E EC = ERMS /120o = a E
![Page 457: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/457.jpg)
86
Rotating Machine Sequence Networks
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
aEEa
EEPg
2EA= ERMS / 0 = E EB = ERMS /-120o = a2 E EC = ERMS /120o = a E
or
[ ] [ ] [ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡== −
0
0
11
111
31 2
2
21 EaE
EaE
aaaaEAE PgSg
Therefore, only the positive sequence system has a generator voltage source.
0
12
abc
![Page 458: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/458.jpg)
87
Rotating Machine Sequence Networks
A
B
C
ZK
ZK
ZK
-
- -
+
+ +
EB
EAEC
ICIA
IB
Zn
ZAB
ZBC
ZCA
ZCB
ZBA
ZAC
Machine is not passive: Mutual Reactances: ZAB ≠ ZBA , etc.
ZAB = ZBC = ZCA = ZR
ZBA = ZCB = ZAC = ZQ
![Page 459: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/459.jpg)
88
Rotating Machine Sequence Networks
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
+++++++++
=⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
C
B
A
NKNQNR
NRNKNQ
NQNRNK
C
B
A
III
ZZZZZZZZZZZZZZZZZZ
EEE
[ ] [ ][ ]PPGPG IZE =
[ ] [ ] [ ][ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡== −
2
1
01
000000
G
G
G
PGSG
ZZ
ZAZAZ
From the machine diagram we can write:
Where: ZG0 = ZK + ZR + ZQ
ZG1 = ZK + a2 ZR + a ZQ
ZG2 = ZK + a ZR + a2 ZQ
uncoupled0
12
0 1 2
![Page 460: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/460.jpg)
89
Rotating Machine Sequence NetworksGenerator sequence circuits are uncoupled
3Zn
ZG0
I0
V0
EG1-
+ ZG1 I1V1
ZG2 I2V2
Generator Terminal Voltages
![Page 461: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/461.jpg)
90
Rotating Machine Sequence Networks
Sequence impedances are unequal
ZG1 varies depending on the application
a) Steady state, power flow studies: ZG1 = ZS(synchronous) b) Stability studies ZG1 = Z’ (transient) c) Short circuit and transient studies: ZG1 = Z” (subtransient)
Motor circuits are similar but there is no voltage source for an induction motor.
(Example 8.6)
![Page 462: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/462.jpg)
91
Example 8.6- [ EP ] +
[ IP ] Z L = 1.0 / 85o Ώ
LoadZ∆ = 30 / 40o Ώ
Unbalanced Source
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−=o
o
o
PE115/295120/2600/277 a
bc
Find phase Currents [ IP ]
Ω+=Ω== Δ 43.666.740/103 jZZ oY
Ω+=Ω= 996.087.85/1 jZ oL
Ω=+=+=== oLY jZZZZZ 7.43/72.10426.7747.7210
![Page 463: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/463.jpg)
92
Example 8.6- [ EP ] +
[ IP ] Z L = 1.0 / 85o Ώ
LoadZ∆ = 30 / 40o Ώ[ ]
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−=o
o
o
PE115/295120/2600/277
[ ] [ ] [ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−=⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡== −
o
o
o
o
o
o
PS
aaaaEAE
6.216/22.977.1/1.2771.62/91.15
115/295120/2600/277
11
111
31
2
21012
![Page 464: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/464.jpg)
93
Example 8.6
10.72 /43.7o Ώ
-
+15.91 /62.1o
I 0
10.72 /43.7o Ώ
-
+277.1 /-1.77o
I1
10.72 /43.7o Ώ
-
+9.22 /216.6o
I2
00 =I
o
o
I7.43/72.10
77.1/2771
−=
AI o5.45/84.251 −=
o
o
I7.43/72.106.216/22.9
2 =
AI o9.172/86.02 =
![Page 465: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/465.jpg)
94
Example 8.6
[ ] [ ][ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡ −==
o
o
o
SP IAI8.73/64.264.196/72.257.46/17.25
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡−=
o
oSI
9.172/86.05.45/84.25
0 0
1
2
a
b
c
Amps
Amps
How would you do problem without Symmetrical Components?
![Page 466: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/466.jpg)
95
Transformer Connections for Zero Sequence
P Q
Ic IaIb
IC
IAIB
P Q
Ia + Ib + Ic is not necessarily 0 if we only look at P circuit but Ia = nIA Ib = nIB and Ic = nIC Therefore since IA + IB + IC = 0 , Ia + Ib + Ic = 0 and I0 = 0
P0Q0Z0
n0
No zero sequence current flow through transformer
![Page 467: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/467.jpg)
96
Transformer Connections for Zero Sequence
P Q
Ic IaIb
IC IAIB
P Q
Ia + Ib + Ic is not necessarily 0 and IA + IB + IC is not necessarily.
P0 Q0Z0
n0
I0 can flow through the transformer.Therefore I0 is not necessarily 0,
I0
![Page 468: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/468.jpg)
97
Transformer Connections for Zero Sequence
P Q
Ic IaIb IC
IA
IB
P Q
Ia + Ib + Ic is not necessarily 0 and Ia/n + Ib/n + Ic/n is not necessarily 0
P0 Q0Z0
n0
Provides a zero sequence current source
Ib/nIc/n
Ic/n
I0but IA + IB + IC = 0
![Page 469: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/469.jpg)
98
Transformer Connections for Zero Sequence
P Q
Ic IaIb I
C
IA
IB
P Q
Ia + Ib + Ic = 0 Ia/n + Ib/n + Ic/n is not necessarily 0, but IA + IB + IC = 0
P0 Q0Z0
n0
No zero sequence current flow
Ib/nIc/n
Ic/n
![Page 470: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/470.jpg)
99
Transformer Connections for Zero Sequence
P Q
IC
IA
IB
P Q
Ia + Ib + Ic = 0 IA + IB + IC = 0
P0 Q0Z0
n0
No zero sequence current flow
∆ ∆Ia
IbIc
![Page 471: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/471.jpg)
100
Power In Sequence NetworksFor a single phase circuit we know that:
S = EI* = P + jQ
In a 3-phase system we can add the power in each phase such that:
SP = EAIA* + EBIB* + ECIC*
Written in matrix form
[ ] [ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
***
C
B
A
CBAP
III
EEES
![Page 472: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/472.jpg)
101
Power in Sequence Networks
If we want the apparent power in the symmetrical component reference frame, we can substitute the following:
[EP] = [A][ES] [IP] = [A][IS]
[EP]T =[ES]T [A]T [IP]* = [A]*[IS]*
Into (1) resulting in [SP] = [ES]T [A]T[A]*[IS]*
which results in: [SP] = 3[ES]T [IS]* = 3[SS]
Where: [SS] = E0I0* + E1I1* + E2I2*
From our previous definitions: [SP] = [EP]T [IP]* (1)
![Page 473: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/473.jpg)
102
Class Problem 2One line of a three-phase generator is open circuited, while the other two are short-circuited to ground. The line currents are:
Ia=0, Ib= 1500/90 and Ic=1500/-30
a. Find the symmetrical components of these currents
b. Find the ground current
![Page 474: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/474.jpg)
103
Class Problem 3The currents in a delta load are:
Iab=10/0, Ibc= 20/-90 and Ica=15/90
Calculate:
a. The sequence components of the delta load currents
b. The line currents Ia, Ib and Ic which feed the delta load
c. The sequence components of the line currents
![Page 475: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/475.jpg)
104
Class Problem 4The source voltages given below are applied to the balanced-Y connected load of 6+j8 ohms per phase:
Vag=280/0, Vbg= 290/-130 and Vcg=260/110
The load neutral is solidly grounded.
a. Draw the sequence networks
b. Calculate I0, I1 and I2, the sequence components of the line currents.
c. Calculate the line currents Ia, Ib and Ic
![Page 476: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/476.jpg)
105
Unsymmetrical Faults
![Page 477: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/477.jpg)
106
Phase and Symmetrical Component Relationship
Phase Reference FrameIAIBIC
nVC
VBVA
Symmetrical Components Reference Frame
I0I1
I2
V0
V1
V2
n0
n1
n2
![Page 478: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/478.jpg)
107
Unsymmetrical Fault Analysis
For the study of unsymmetrical faults some, or all, of the following assumptions are made:
• Power system balanced prior to fault• Load current neglected• Transformers represented by leakage
reactance• Transmission lines represented by series
reactance
![Page 479: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/479.jpg)
108
Assumptions Continued• Synchronous machines represented by constant
voltage behind reactance(x0, x1. x2)• Non-rotating loads neglected• Small machines neglected• Effect of Δ – Y transformers may be included
![Page 480: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/480.jpg)
109
Faulted 3-Phase Systems
Sequence networks are uncoupled for normal system conditions and for the total system we can represent 3 uncoupled systems: positive, negative and zero.
When a dissymmetry is applied to the system in the form of a fault, we can connect the sequence networks together to yield the correct sequence currents and voltages in each sequence network.
From the sequence currents and voltages we can find the corresponding phase currents and voltages by transformation with the [A] matrix
![Page 481: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/481.jpg)
110
Faulted 3-Phase SystemsTo represent the dissymmetry we only need to
identify 2 points in the system: fault point and neutral point:
Zero System
Positive System
Negative System
f0 f1 f2
n0 n1n2
IF0IF1 IF2
EF0 EF1 EF2
The sequence networks are connected together from knowledge of the type of fault and fault impedanceExample 9.1
![Page 482: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/482.jpg)
111
.
AC
Bus 1
AC
Bus 2X1=X2 =20Ώ
. .
∆ ∆
100MVA 13.8kV
X”=0.15puX2 = 0.17puX0 =0.05pu
100MVA 13.8:138kV X = 0.1pu
100MVA 138:13.8kV X = 0.1pu
100MVA 13.8kV
X”=0.20puX2 = 0.21puX0 =0.05puXn = 0.05pu
Example 9.1
G M
Prefault Voltage = 1.05 pu
Draw the positive, negative and zero sequence diagrams for the system on 100MVA, 13.8 kV base in the zone of the generator
Line Model:
X0 = 60Ώ
( )Ω= 4.190
100138 2
BZ pujjZZ 105.04.190
2021 === pujjZ 315.0
4.19060
0 ==
![Page 483: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/483.jpg)
112
AC AC
.
AC AC
j.15
-
+
J0.1 J0.105 J0.1
J0.2.
-
+
1 2
1.05 / 0o 1.05 / 0o
n1
AC AC
j.17
J0.1 J0.105 J0.1
J0.21.
1 2
n2
AC AC
.
AC AC
.AC
j.05J0.1
J0.315
J0.1J0.1.
1 2
j.15
n0
Example 9.1
![Page 484: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/484.jpg)
113
Example 9.1Reduce the sequence networks to their
thevenin equivalents as viewed from Bus 2
AC AC
.AC
j.05J0.1
J0.315
J0.1J0.1.
1 2
j.15
n0Zero Sequence Thevenin Equivalent
from Bus 2
f0
n0
J0.25
![Page 485: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/485.jpg)
114
Example 9.1
AC AC
.
AC AC
j.15
-
+
J0.1 J0.105 J0.1
J0.2.
-
+
1 2
1.05 / 0o 1.05 / 0o
n1Positive Sequence Thevenin Equivalent
from Bus 2
139.655.
)2)(.455(. jjZthev ==
f1
n1
J0.139+
-1.05 / 0 o
![Page 486: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/486.jpg)
115
Example 9.1
Negative Sequence Thevenin Equivalent from Bus 2
146.685.
)21)(.475(. jjZthev ==
f2
n2
J0.146
AC AC
j.17
J0.1 J0.105 J0.1
J0.21.
1 2
n2
AC AC
.
![Page 487: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/487.jpg)
116
Single Line-to-Ground Fault
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
00FA
FP
II
[ ] [ ] [ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡== −
FA
FA
FAFA
FPFS
IIII
aaaaIAI
31
00
11
111
31
2
21
IF0 = IF1 = IF2EFA = IFA ZF
EF0 + EF1 + EF2 = (IF0 + IF1 + IF2) ZF EF0 + EF1 + EF2 = 3IF0 ZF
ABCIFA
EF
A
IFB
IFC
nZF
![Page 488: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/488.jpg)
117
Single Line to Ground Fault
Zero System
Positive System
Negative System
f0 f1 f2
n0n1 n2
IF0 IF1 IF2
EF
0
EF1 EF2
3ZF
![Page 489: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/489.jpg)
118
Single Line to Ground Fault
Zero System
Positive System
Negative System
f0
f1
f2
n0
n1
n2
IF0
IF1
IF2
EF0
EF1
EF2
3 ZF
![Page 490: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/490.jpg)
119
Example 9.3For the system of Example 9.1 there is a bolted Single-Line-to-Ground fault at Bus 2.
Find the fault currents in each phase and the phase voltages at the fault point.
f0
n0
J0.25
f1
n1
J0.139+
-1.05 / 0 o
f2
n2
J0.146IF0IF2
IF1
96.1146.139.25.
0/05.1210 j
jjjIII
o
FFF −=++
===
![Page 491: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/491.jpg)
120
Example 9.3
f0
n0
J0.25
f1
n1
J0.139+
-1.05 / 0 o
f2
n2
J0.146
IF0 = IF1 = IF2 = -j1.96
EF0 EF2
EF1
pujjVF 491.)25.)(96.1(0 −=−−=
pujVF 777.)139.)(96.1(05.11 =−−=
pujjVF 286.)146.)(96.1(2 −=−−=
![Page 492: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/492.jpg)
121
Example 9.3[ ] [ ][ ]FSFP IAI =
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡−=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−−−
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
0088.5
96.196.196.1
11
111
2
2
puj
jjj
aaaa
III
FC
FB
FA
[ ] [ ][ ]FSFP EAE =
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−
−
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
pupu
aaaa
EEE
o
o
FC
FB
FA
7.128/179.1231/179.10
286.777.491.
11
111
2
2
Note: Unfaulted phase voltages are higher than the source voltage.
abc
abc
![Page 493: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/493.jpg)
122
.
Example 9.3a
Find fault current in the transmission line, I L
1) Find ILS
2) Find ILP
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡−=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
0088.5 puj
III
FC
FB
FA
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−−−
=⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
96.196.196.1
2
1
0
jjj
III
F
F
F. .
AC
Bus 1
AC
Bus 2∆ ∆G M
SLG Fault
IF
I L
![Page 494: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/494.jpg)
123
Zero Sequence
AC AC
.AC
j.05J0.1
J0.315
J0.1J0.1.
1 2(f0)
j.15
n0
-j1.96
I L0 = 0
I L0 =0
![Page 495: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/495.jpg)
124
Positive Sequence
AC AC
.
AC AC
j.15
-
+
J0.1 J0.105 J0.1
J0.2.
-
+
1 2
1.05 / 0o 1.05 / 0o
n1
e j30 : 1 SLG
e j30 : 1
n1
-j1.96
I T1I L1
6.655.2.)96.1(1 jjIT −=−= o
LI 60/6.01 −=
n1
j.455 j .22
I T1 -j1.96f1 f1
![Page 496: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/496.jpg)
125
Negative Sequence
e -j30 : 1
n2
-j1.96
I T2I L2
n2
j.475 j .22
I T2-j1.96
6.685.21.)96.1(2 jjIT −=−= o
LI 120/6.02 −=
AC AC
.
AC
j.17
J0.1 J0.105 J0.1
J0.21.
1 2
n2
e -j30 : 1 SLG
f2 f2
![Page 497: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/497.jpg)
126
Example 9.3a
[ ] [ ][ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡−=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−−
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡==
puj
puj
aaaaIAI
o
oPSPL
039.10039.1
120/6.60/6.
0
11
111
2
2
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−−=
o
oLSI
120/6.60/6.
0 012
abc
. .
AC
Bus 1
AC
Bus 2∆ ∆G M
SLG Fault
IF
I L
![Page 498: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/498.jpg)
127
Line to Line Fault
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−=
FB
FBFP
III0
[ ] [ ] [ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡== −
FB
FB
FB
FBFPFS
IjIj
II
aaaaIAI
330
31
0
11
111
31
2
21
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−=
FFBFB
FB
FA
FP
ZIEEE
E
n
ABC
IFA
EF
A
IFB IFC
EF
B
EF
CZF
IF0 = 0 IF1 = IF2
( ) FFFFBFFBFFBFF ZIZIjZIjZIaaEE 1
2
21 333
==−−=−
−=−
FBF IjI 31 = so 31
jII F
FB =
EF1 = EF2 + IF1ZF
012
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−−−−−+
=⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
FFBFBFA
FFBFBFA
FFBFBFA
FFBFB
FB
FA
FS
ZaIEEZIaEEZIEE
ZIEEE
aaaaE 2
2
2
2
31
11
111
31
![Page 499: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/499.jpg)
128
Line to Line Fault
Zero System
Positive System
Negative System
f0 f1 f2
n0 n1 n2
IF0IF1 IF2
EF0 EF1 EF
2
ZF
![Page 500: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/500.jpg)
129
Example 9.4For the system of Example 9.1 there is a bolted Line-to-Line fault at Bus 2.
Find the fault currents in each phase and the phase voltages at the fault point.
f0
n0
J0.25
f1
n1
J0.139+
-1.05 / 0 o
f2
n2
J0.146
IF1IF1
IF0
pujjj
IIo
FF 69.3146.139.
0/05.121 −=
+=−=00 =FI
( ) ( )( ) pujjjIEE FFF 537.0146.69.3146.221 =−=−==
EF1=EF2EF0
00 =FE
![Page 501: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/501.jpg)
130
Example 9.4
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡−=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡−
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
pupu
jjjj
jj
aaaa
III
FC
FB
FA
39.639.60
)69.3(3)69.3(3
0
69.369.3
0
11
111
2
2abc
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−−=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
pupu
pu
aaaa
EEE
FC
FB
FA
537.537.07.1
537.537.0
11
111
2
2abc
![Page 502: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/502.jpg)
131
2 Line to Ground Fault
[ ] ( )( ) ⎥
⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
++=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
FFCFB
FFCFB
FA
FC
FB
FA
FP
ZIIZII
E
EEE
E
ABC
IFA
EF
A
IFB IFC
nEF
B
EF
CZF
IFA = 0 = IF0 + IF1 + IF2
Since IFA = 0, IFB + IFC = 3IF0
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
−−+
=⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
FFFA
FFFA
FFFA
FF
FF
FA
FS
ZIEZIEZIE
ZIZI
E
aaaaE
0
0
0
0
02
2
3/3/
23/
33
11
111
31
EF0 – EF1 = 3 IF0 ZF so EF0 = EF1 + 3IF0 ZF and EF1 = EF2
012
![Page 503: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/503.jpg)
132
2 Line to Ground Fault
Zero System
Positive System
Negative System
f0 f1 f2
n0 n1 n2
IF0IF1 IF2
EF0 EF1 EF2
3ZF
![Page 504: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/504.jpg)
133
For the system of Example 9.1 there is a 2-line-to-ground bolted fault at Bus 2. a) Find the fault currents in each phase b) Find the neutral current c) Fault current contribution from motor and generator
Neglect delta-wye transformers
Example 9.5
. .
AC
Bus 1
AC
Bus 2∆ ∆G M
2LG Fault
IF
I L
![Page 505: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/505.jpg)
134
Example 9.5
f0
n0
J0.25
f1
n1
J0.139+
-1.05 / 0 o
f2
n2
J0.146IF0IF2
IF1
pujjj
IF 547.4
25.146.)25)(.146(.139.
05.11 −=
++
=
pujII FF 674.125.146.
146.)( 10 =+
−=
pujjjIII FFF 873.2)547.4(674.1102 =−−−=−−=
![Page 506: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/506.jpg)
135
Example 9.5
This image cannot currently be displayed.[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡−
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
pupu
jj
j
aaaaI
o
oFP
3.21/9.67.158/9.6
0
873.2547.4
674.1
11
111
2
2abc
pujjII FFn 02.5)674.1)(3(3 0 ===
![Page 507: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/507.jpg)
136
Example 9.5
n1
j.455 j .22I T1 -j4.547
n2
j.475 j .22I T2 J2.87
3
00 =GFI pujjIII GFFMFO 674.10674.100 =−=−=
39.1655.2.)547.4(! jjIGF −=−=
pujjjIII GFFMF 16.3)39.1(547.4111 −=−−−=−=
88.685.21.)8773.2(2 jjIGF ==
pujjjIII GFFMF 993.188.873.2222 =−=−=
f1
f2
![Page 508: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/508.jpg)
137
Example 9.5
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡ −=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡−
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
pupu
puj
jj
aaaaI
o
oGFP
4.7/98.16.172/98.1
51.
88.39.1
0
11
111
2
2
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡ −=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡−
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
pupu
puj
jj
j
aaaaI
o
oMFP
9.26/0.51.153/0.5
504.
99.116.3
674.1
11
111
2
2
![Page 509: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/509.jpg)
138
Example 9.5 results
AC AC
.AC
j.05J0.1
J0.315
J0.1J0.1.
1 2
j.15n
0
I L0 = 0
2LGJ1.674
X
AC AC
.
AC AC
j.15
-
+
J0.1J0.105 J0.1
J0.2.
-
+
1 2
1.05 / 0o 1.05 / 0o
n1
e -j30 : 1 2LGe j30 : 1-j3.16X
-j1.39
Find the fault current contribution from the generator considering the delta-wye transformer phase shift.
Example 9.6
1.39/ -60o-j1.39
![Page 510: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/510.jpg)
139
Example 9.6Example 9.5 results
J1.99
AC AC
.
AC
j.17
J0.1J0.105 J0.1
J0.21.
1 2
n2
e -j30 : 1 2LGe j30 : 1 X
j.88.88/ 60oj.88
. .
AC
Bus 1
AC
Bus 2∆ ∆G M
2LG Fault
I L
X
[ ]⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡ −=
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡−
⎥⎥⎥
⎦
⎤
⎢⎢⎢
⎣
⎡=
pupu
puj
jj
aaaaI
o
oGP
7/98.1173/98.151.
88.39.1
0
11
111
2
2abc
IGP
![Page 511: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/511.jpg)
140
Class Problem 5
The system data in p.u. based on SB = 100MVA, VB = 765kV for the lines are:
G1: X1=X2=.18, X0=.07 T1: X=.1 LINE 1-3: X1=X2=.4 X0=.17
G2: X1=X2=.2, X0=.10 T2: X=.1 LINE 1-2: X1=X2=.085 X0=.256
G3: X1=X2=.25, X0=.085 T3: X=.24 LINE 2-3: X1=X2=.4 X0=.17
G4: X1=.34, X2=.45, X0=.085 T4: X=.15
a) From the perspective of Bus 1, draw the zero, positive and negative sequence networks.
b) Determine the fault current for a 1 L-G bolted fault on Bus 1.
AC
Bus 1
AC
Bus 3
∆
G1 G3
G4
G2
Bus 2
LINE 1-3
LINE 1-2 LINE 2-3∆
T1
T2
T3
T4
![Page 512: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/512.jpg)
141
Modern Fault Analysis Methods
![Page 513: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/513.jpg)
142
Modern Fault Analysis Tools• Power Quality Meters (Power Quality Alerts)• Operations Event Recorder (ELV, Electronic
Log Viewer)• Schweitzer Relay Event Capture• Schweitzer Relay SER (Sequential Events
Record)
![Page 514: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/514.jpg)
143
Modern Fault Analysis Example:Line current diff with step distance
• First indication of an event - Power Quality alert email notifying On-Call Engineer that there was a voltage sag in the area. This event was a crane contacting a 69kv line. Time of event identified.
![Page 515: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/515.jpg)
144
Modern Fault Analysis Example• Event Log Viewer stores breaker operation
events. Search done in ELV using time from PQ Alert and breakers identified where trip occurred. Ferris and Miller breakers
operated.
![Page 516: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/516.jpg)
145
Modern Fault Analysis Example• Next the line relays (SEL-311L) at the two
substations are interrogated for a possible event at this time.
• Use command EVE C 1 to capture the event you desire. The C gives you the digital elements as well as the analog quantities.
Ferris and Miller triggered an event record at this time (HIS command used in SEL relay)
Reclosing enabled at Miller, additional record is the uncleared fault after reclosing.
![Page 517: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/517.jpg)
146
Modern Fault Analysis Example• If the fault distance is not reasonable from the
relays, i.e. the fault distances from each end is longer then the line length, the fault magnitude can be modeled in Aspen to determine fault distance by running interim faults. This discrepancy in distance can result from tapped load or large infeed sources.
![Page 518: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/518.jpg)
147
Modern Fault Analysis Example• Event capture file is opened in SEL-5601 to
view waveforms and digital elements of event. Miller initial fault:
![Page 519: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/519.jpg)
148
Modern Fault Analysis Example• Event capture file is opened in SEL-5601 to
view waveforms and digital elements of event. Ferris initial fault: Unknown
source voltage
![Page 520: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/520.jpg)
149
Modern Fault Analysis Example• Event capture file is opened in SEL-5601 to
view waveforms and digital elements of event. Miller reclose operation:
![Page 521: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/521.jpg)
150
Modern Fault Analysis Example• This SEL-311L setup is a current differential
with step distance protection.• Analysis from line relay SER to ensure proper
relaying operation:
• Question, why didn’t Z1G pickup?
![Page 522: Symmetrical Components Fault Calculations](https://reader034.fdocuments.us/reader034/viewer/2022050708/58788bd41a28ab375f8b4da9/html5/thumbnails/522.jpg)
151
Questions