Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
Property of Sto Corp.All Rights Reserved.
StoTherm® ciSystem Components
Detail No.: 52s.00Date: November 2015
Notes:
1. StoTherm ci System Components: - StoGuard Air and Moisture Barrier - Sto Adhesive - Sto EPS or Sto GPS Insulation Board - Sto Mesh - Sto Primer (optional) - Sto Base Coat - Sto Finish
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
StoGuard® Air and Moisture Barrier Sheathing Joint Treatment
Sheathing
Sto EPS Insulation Board
Sto MeshSto Base Coat (with Sto Mesh Embedded)
Sto Primer (Optional)
Sto Finish
Sto Adhesive
StoTherm® ciSystem Components: Ultra-High Impact Resistance
Detail No.: 52s.01Date: November 2015
Property of Sto Corp. All Rights Reserved.
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1.StoTherm ci System Components: - StoGuard air and Moisture Barrier - Sto Adhesive - Sto EPS or Sto GPS Insulation Board - Sto Armor Mat XX - Sto Mesh - Sto Primer (optional) - Sto Base Coat - Sto Finish
2. Ultra-high impact resistance recommended at all ground floors to a minimum height of 6'-0" (1.8 m) above finished grade and other areas accessible to pedestrian traffic, abnormal stress or impact.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Sto Materials:
1.Sample Text
1.Sample Notes
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
StoGuard® Air and Moisture Barrier Sheathing Joint Treatment
(with Sto Mesh Embedded)
Sto Primer (Optional)
Sto Finish
Sto Adhesive
Sheathing
Sto EPS Insulation Board
Sto MeshSto Base Coat
Sto Base Coat (with Sto Armor Mat Embedded)
StoTherm® ciTermination at Grade - Sheathing Flush with Foundation or Slab Edge
Detail No.: 52s.03ADate: November 2015
Property of Sto Corp. All Rights Reserved.
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Terminate system minimum 6" (15.2 cm) above finished grade, higher for areas with heavy snow accumulations, or where required by code.
2. Ultra-high impact resistance recommended at all ground floors to a minimum height of 6'-0" (1.8 m) above finished grade and other areas accessible to pedestrian traffic, abnormal stress or impact.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sto Primer (Optional)
Sto Finish
Sto AdhesiveSheathing
Sto EPSInsulation Board, Pre- Wrapped
Sto Mesh
(with Sto Mesh Embedded) Sto Base Coat
StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (Protect with StoCoat Acryl Plus or Flashing)
StoGuard® Air and Moisture Barrier Detail ComponentFlashing, Sloped
Backer Rod & Sealant w/ Weep Holes
Terminate Assembly 6" (152 mm) Above Grade, min.
StoTherm® ciTermination at Grade - Sheathing Overlapping Slab or Foundation
Detail No.: 52s.03BDate: November 2015
Property of Sto Corp. All Rights Reserved.
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Terminate system minimum 6" (15.2 cm) above finished grade, higher for areas with heavy snow accumulations, or where required by code.
2. Ultra-high impact resistance recommended at all ground floors to a minimum height of 6'-0" (1.8 m) above finished grade and other areas accessible to pedestrian traffic, abnormal stress or impact.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sto Primer (Optional)
Sto Finish
Sto AdhesiveSheathing
Sto EPSInsulation Board, Pre-Wrapped
Terminate Assembly 6" (152 mm) Above Grade, min.
Sto Mesh
(with Sto Mesh Embedded) Sto Base Coat
StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (Protect with StoCoat Acryl Plus or Flashing)
StoGuard® Air and Moisture Barrier Detail Component
Flashing, Sloped
Backer Rod & Sealant w/ Weep Holes
StoTherm® ciAesthetic Feature Band
Detail No.: 52s.04Date: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Feature band attached with Sto TurboStick Adhesive, also used as filler and rasped smooth at any gaps between feature band and base layer of insulation board.
2. Slope top surface of feature band minimum 27 degrees. Increase slope for northern climates to prevent snow and ice accuulations.
3. Limit thickness of build-out to reduce maintenance associated with projecting architectural features.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
StoGuard® Air and Moisture Barrier
Sto Primer (Optional)
Sheathing
Sto EPSInsulation Board
Sto Base Coat (with Sto Mesh Embedded)
StoGuard® Air and Moisture Barrier
Sheathing
Sto EPSInsulation Board
(with Sto Mesh Embedded) Sto Base Coat
Sto Flexyl (with Sto Mesh or Sto Detail Mesh Embedded); Return Vertically 4" (102 mm) min. Above and Below Feature Band
Sto Mesh
Sto Mesh
Sto Finish
Sto Finish
Sto Primer (Required over Sto Flexyl and Sto Base Coat Above and Below)
Sto Adhesive
Sto Adhesive
Thin Build-Out
Thick Build-Out
Thick Build-Out, 2-4 in. (51-102 mm)
Thin Build-Out, ≤ 2 in. (51 mm)
StoTherm® ciAesthetic Reveal
Detail No.: 52s.05Date: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Slope bottom surface of reveal minimum 27 degrees. Increase slope for northern climates to prevent snow and ice accumulations.
2. Maintain minimum 3/4 inch (19 mm) thickness of insulation board at base of reveal.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Sto Primer (Optional)
Sto Finish
Sto Adhesive
Sto EPSInsulation Board
Sto Base Coat (with Sto Detail Mesh Embedded)
3/4" (19 mm) min.
2 1/2" (64 mm) min. Ovelap of Sto Detail Mesh w/ Sto Mesh @ Top and Bottom of Reveal
StoGuard® Air and Moisture Barrier
Sto Base Coat (with Sto Mesh Embedded) Sto Mesh
Sto Detail Mesh
Sto Primer (Optional)
Sto Finish
Sto Adhesive
Sto EPSInsulation Board
3/4" (19 mm) min.
StoGuard® Air and Moisture Barrier
Sto Base Coat (with Sto Mesh Embedded) Sto Mesh
Sheathing
Sheathing
Option 1 with Sto Detail Mesh
Option 2 with Continuous Sto Mesh
StoTherm® ciReceptor-Type Window Sill
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.
2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Detail No.: 52s.23A-1Date: November 2015
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sheathing
StoGuard® Air and Moisture Barrier Rough Opening Protection Over Blocking
Blocking
StoGuard® Air and Moisture Barrier Rough Opening Protection
Step 1 - Rough Opening Protection
StoTherm® ciReceptor-Type Window Sill
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.
2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Detail No.: 52s.23A-2Date: November 2015
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sheathing
End Dam Set in Sealant
StoGuard® Air and Moisture Barrier Rough Opening Protection
Sto EPS Insulation Board, Pre-Wrapped
Sto TurboStick Adhesive (Fill Gap Between EPS Boards at Corner with this Adhesive, Cut Flush with Surface and Rasp Smooth)
Sto EPS Insulation Board, Pre-Wrapped around Rough Opening
Sill Receptor w/ Weep Holes (Sill Flashing Extender Not Shown for Clarity)
Sto Adhesive
Weep Holes
Angle (As Needed for Attachment of Sill Receptor and Support)
StoGuard® Air and Moisture Barrier Rough Opening Protection
Blocking
Step 2 - Receptor with End Dam
StoTherm® ciReceptor-Type Window Sill
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.
2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Detail No.: 52s.23A-3Date: November 2015
Sto Primer (Optional)
Sto Finish
Sto Mesh
(with Sto Mesh Embedded)
Sto Base Coat
Backer Rod & Sealant (Entire Perimeter)
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sheathing
StoGuard® Air and Moisture Barrier Rough Opening Protection
Sto EPS Insulation Board, Pre-Wrapped at Jamb
Sto EPS Insulation Board, Pre-Wrapped around Rough Opening
Sill Receptor w/ Weep Holes
Sto Adhesive
Spray Polyurethane Foam Insulation
Jamb Receptor
Sill Extender w/ Continuous Bead of Sealant @ Bottom
Window Assembly
Air Seal, Backer Rod & Sealant (Air Seal Entire Perimeter)
Angle (As Needed for Attachment of Sill Receptor and Support)
StoGuard® Air and Moisture Barrier Rough Opening Protection
Blocking
Step 3 - Window and Sill Flashing, Cladding, and Perimeter Weather and Air Seals
StoTherm® ciReceptor-Type Window Head
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.
2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Detail No.: 52s.23B-1Date: November 2015
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sheathing
StoGuard® Air and Moisture Barrier Rough Opening Protection
Cement Board Filler or Other TrimFlashing
StoGuard® Air and Moisture Barrier Rough Opening Protection
StoGuard® Air and Moisture Barrier
StoGuard® Air and Moisture Barrier Detail Component
Step 1 - Rough Opening Protection, Head Flashing
StoTherm® ciReceptor-Type Window Head
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.
2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Detail No.: 52s.23B-2Date: November 2015
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sheathing
StoGuard® Air and Moisture Barrier Rough Opening Protection
Sto EPS Insulation Board, Pre-Wrapped
Sto TurboStick Adhesive (Fill Gap Between EPS Boards at Corner with this Adhesive, Cut Flush with Surface and Rasp Smooth, Reinforce Top Corner with Sto Mesh or Sto Detail Mesh Embedded in Base Coat)
Sto EPS Corner Board, Pre-Wrapped around Rough Opening
Window Assembly
Spray Polyurethane Foam Insulation
Head Receptor
Jamb Receptor
Cement Board Filler or Other TrimFlashing
StoGuard® Air and Moisture Barrier Rough Opening Protection
StoGuard® Air and Moisture Barrier
Sto Adhesive
Step 2 - Receptor and Window
StoTherm® ciReceptor-Type Window Head
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.
2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Detail No.: 52s.23B-3Date: November 2015
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sheathing
StoGuard® Air and Moisture Barrier Rough Opening Protection
Sto EPS Insulation Board, Pre-WrappedSto TurboStick Adhesive (Fill Gap Between EPS Boards at Corner with this Adhesive, Cut Flush with Surface and Rasp Smooth)
Sto EPS Corner Board, Pre-Wrapped around Rough Opening
Window Assembly
Sto Adhesive
Sto Primer (Optional)
Sto Finish
Sto Mesh
(with Sto Mesh Embedded)
Sto Base Coat
Air Seal, Backer Rod and Sealant (Air Seal Entire Perimeter)
Head Receptor
Jamb Receptor Backer Rod & Sealant (Entire Perimeter, with Weeps at Head)
Cement Board Filler or Other Trim (Finish Cement Bd. w/ StoCoat Acryl Plus)
Flashing
StoGuard® Air and Moisture Barrier Rough Opening Protection
StoGuard® Air and Moisture Barrier
Spray Polyurethane Foam Insulation
Step 3 - Cladding and Perimeter Weather and Air Seals
StoTherm® ciFlanged Window-Sill
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.
2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Detail No.: 52s.24A-1Date: November 2015
Property of Sto Corp. All Rights Reserved.
Step 1 - Rough Opening Protection, Sill Flashing
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sheathing
StoGuard® Air and Moisture Barrier Rough Opening Protection
1/8" (3 mm) Thick Washers Behind Mounting Flange
StoGuard® Air and Moisture Barrier Rough Opening Protection
StoGuard® Detail Component
Flashing
Slope
StoTherm® ciFlanged Window-Sill
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.
2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Detail No.: 52s.24A-2Date: November 2015
Property of Sto Corp. All Rights Reserved.
Step 2 - Window and Trim
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sheathing
StoGuard® Air and Moisture Barrier Rough Opening Protection
Sto EPS Insulation Board, Pre-Wrapped Around Opening (Cut Kerf in Back of Insulation and Slide over End Dam. Position insulation over Flashing with 1/4" [6 mm] Gap for Drainage)
Spray Polyurethane Foam Insulation
StoGuard® Air and Moisture Barrier Rough Opening Protection
Sealant Behind Mounting Flange (Jambs and Head Only)
Sto Adhesive
StoGuard® Detail Component
Flashing
Slope
Window Assembly
1/8" (3 mm) Thick Washers Behind Mounting Flange
Spray Polyurethane Foam Insulation
StoTherm® ciFlanged Window-Sill
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.
2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Detail No.: 52s.24A-3Date: November 2015
Property of Sto Corp. All Rights Reserved.
Step 3 - Cladding and Perimeter Weather and Air Seals
Sto Primer (Optional)
Sto Finish
Sto Mesh
(with Sto Mesh Embedded)
Sto Base Coat
Backer Rod & Sealant (Entire Perimeter)
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sheathing
StoGuard® Air and Moisture Barrier Rough Opening Protection
Sto EPS Insulation Board, Pre-Wrapped Around Opening
Sto EPS Insulation Board
Spray Polyurethane Foam Insulation
Window Assembly
StoGuard® Air and Moisture Barrier Rough Opening Protection
Sto Adhesive
StoGuard® Detail ComponentFillet Bead of Sealant (not
shown) Between Underside of Flashing and Base Coat
1/8" (3 mm) Thick Washers Behind Mounting Flange
Sealant Behind Mounting Flange (Jambs and Head Only)
Air Seal, Backer Rod & Sealant (Air Seal Entire Perimeter)
Spray Polyurethane Foam Insulation
Backer Rod & Sealant with Weeps Between Trim and Flashing Leg
Flashing
Air Seal, Backer Rod & Sealant (Air Seal Entire Perimeter)
StoTherm® ciFlanged Window-Head
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.
2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Detail No.: 52s.24B-1Date: November 2015
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sheathing
StoGuard® Air and Moisture Barrier Rough Opening Protection
Window Assembly
StoGuard® Air and Moisture Barrier Rough Opening Protection
StoGuard® Detail Component
Sealant Behind Mounting Flange (Jambs and Head Only)
Flashing
Sealant Behind Mounting Flange (Jambs and Head Only)
Sealant
Property of Sto Corp. All Rights Reserved.
Step 1 - Rough Opening Protection, Head Flashing
StoTherm® ciFlanged Window-Head
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.
2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Detail No.: 52s.24B-2Date: November 2015
Property of Sto Corp. All Rights Reserved.
Step 2 - Window and Trim
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sheathing
StoGuard® Air and Moisture Barrier Rough Opening Protection
Sto EPS Insulation Board, Pre-Wrapped Around Opening
Sto EPS Insulation Board
Window Assembly
StoGuard® Air and Moisture Barrier Rough Opening Protection
Sto Adhesive
StoGuard® Detail Component
Sealant Behind Mounting Flange (Jambs and Head Only)
Sealant
Spray Polyurethane Foam Insulation
Flashing
Backer Rod & Sealant Weather and Air Seals (Entire Perimeter with Weeps Between Underside of Trim & Flashing Leg)
Spray Polyurethane Foam Insulation
StoTherm® ciFlanged Window-Head
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.
2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Detail No.: 52s.24B-3Date: November 2015
Property of Sto Corp. All Rights Reserved.
Step 3 - Cladding and Perimeter Weather and Air Seals
Sto Primer (Optional)
Sto Finish
Sto Mesh
(with Sto Mesh Embedded)
Sto Base Coat
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sheathing
StoGuard® Air and Moisture Barrier Rough Opening Protection
Sto EPS Insulation Board, Pre-Wrapped Around Opening
Sto EPS Insulation Board
StoGuard® Air and Moisture Barrier Rough Opening Protection
Sto Adhesive
StoGuard® Detail Component
Sealant Behind Mounting Flange (Jambs and Head Only)
Sealant
Spray Polyurethane Foam Insulation
Flashing
Spray Polyurethane Foam Insulation
Window Assembly
Backer Rod & Sealant Weather and Air Seals (Entire Perimeter with Weeps Between Underside of Trim & Flashing Leg)
StoTherm® ciSoffit: Insulated and Unvented
Detail No.: 52s.30Date: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Continue StoGuard air and moisture barrier onto dissimilar material or construction where required after verifying substrate material compatibility. Refer to Sto Detail 52s.53 for typical detailing of inside corner if substrate material or construction is dissimilar. Refer to Sto Detail 52s.54A if substrate material is similar at inside corner.
2. 4" (10 cm) thick insulation board typically required for proper lap of accessory with mesh "tail." For thinner sections of insulation board pre-wrap insulation board with Sto base coat and mesh.
3. Multi-story buildings where construction is required to be Noncombustible may require special examination of soffit conditions with foam plastic insulation. Verify with professional fire protection engineer and building code official.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Nominal 1/4 inch (6 mm) Gap for Drainage
Sheathing
Sto EPS Insulation Board, Pre-Wrapped
Sto Base Coat (with Sto Mesh Embedded) Sto Mesh
Sto Adhesive
StoGuard® Joint Treatment
Backer Rod and Sealant
Structure
Sto Drip Edge Profile
Sto Drip Edge Profile (See Drawing Below) Dissimilar Material or
Wall Construction
Light Gauge Steel Stud Framing
StoGuard® Air and Moisture Barrier
Sto Primer (Optional)
Sto Finish
StoTherm® ciSoffit: Uninsulated and Vented
Detail No.: 52s.31Date: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Prevent "communication" of vented air space with conditioned interior air to reduce the likelihood of condensation on materials in the vented space.
3. Typical soffit board is gypsum sheathing in compliance with ASTM C 1177. Refer to Sto Specification No. F601S and Sto Detail Series 14.xx.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Nominal 1/4 inch (6 mm) Gap for Drainage
Sheathing
Sto EPS Insulation Board, Pre-Wrapped
Sto Base Coat (with Sto Mesh Embedded) Sto Mesh
Sto Adhesive
Backer Rod and Sealant
Structure
Sto Drip Edge Profile
Sto Drip Edge Profile (See Drawing Below) Dissimilar Material or
Wall Construction
Light Gauge Steel Stud FramingStoGuard® Air and Moisture Barrier
Sto Primer (Optional)
Sto Finish
StoGuard® Joint Treatment
Soffit Vent
Casing Bead
StoTherm® ciFloor Line Without Deflection
Detail No.: 52s.40Date: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. This detail is typically limited to low-rise construction where no floor line deflection is anticipated. Refer to Sto Detail 52s.41A, B, or C for a floor line condition with deflection.
2. Sheathing attachment is typically at 8" (20.3 cm) on center or less vertically. Add C-channels or other attachment means along slab edge if necessary to conform with required fastener spacing.
3. Provide fire stopping at floor line as needed.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
StoGuard® Air and Moisture Barrier
Sto Primer (Optional)
Sto Finish
Sheathing
Sto EPS Insulation Board
Sto Base Coat (with Sto Mesh Embedded)
Sto Adhesive
Sto Mesh
StoGuard® Air and Moisture Barrier Sheathing Joint Treatment
Structure
StoTherm® ciFloor Line With Deflection -Concealed Flashing and Drainage at Floor Line
Detail No.: 52s.41ADate: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Sheathing attachment is typically at 8" (20.3 cm) on center or less vertically. Add C-channels or other attachment means along slab edge if necessary to conform with required fastener spacing.
2. Provide fire stopping at floor line as needed.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
StoGuard® Air and Moisture Barrier
Sto Primer (Optional)
Sto Finish
Sheathing
Sto EPS Insulation Board, Pre-Wrapped @ Top and Bottom to Allow for Drainage
Sto Base Coat (with Sto Mesh Embedded)
Sto Mesh
Sto Adhesive StoGuard® Air and Moisture Barrier Sheathing Joint Treatment
StoGuard® Transition Membrane
Horizontal Deflection Joint: Backer Rod & Sealant w/ Drainage Openings. Sealant Applied to Base Coat as per Sealant Manuf'r Instructions
Slotted Deflection Track
Backer Rod
Structure
StoGuard® Transition Membrane Applied from Face of StoGuard® Air & Moisture Barrier and Lapped onto Top of EPS Insulation Board with Slight Slope for Drainage @ Bottom of Joint
StoTherm® ciFloor Line With Deflection - No Drainage at Floor Line
Detail No.: 52s.41BDate: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Sheathing attachment is typically at 8" (20.3 cm) on center or less vertically. Add C-channels or other attachment means along slab edge if necessary to conform with required fastener spacing.
2. Provide fire stopping at floor line as needed.
3. Provide drainage at floor lines as deemed by Design Professional, typically no more than every third floor line. Refer to Sto Detail 52s.41A.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
StoGuard® Air and Moisture Barrier
Sto Primer (Optional)
Sto Finish
Sheathing
Sto EPS Insulation Board, Pre-Wrapped @ Top and Bottom to Allow for Drainage
Sto Base Coat (with Sto Mesh Embedded)
Sto Mesh
Sto Adhesive StoGuard® Air and Moisture Barrier Sheathing Joint Treatment
StoGuard® Transition Membrane
Horizontal Deflection Joint: Backer Rod & Sealant. Sealant Applied to Base Coat as per Sealant Manuf'r Instructions
Slotted Deflection Track
Backer Rod
Structure
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Detail apples to Balcony Protected Overhead by Balcony Ceiling Above.
2. Slope balcony to direct water away from wall.
3. Consider the use of high or ultra-high reinforcing meshes on balcony walls to supplement standard reinforcing mesh for added abuse and impact resistance.
4. Verify compatibility of StoGuard Air and Moisture Barrier with balcony waterproof membrane material where they interface or lap one another.
5. Counter flash balcony membrane on wall if not fluid applied.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Detail No.: 52s.42ADate: November 2015
StoTherm® ciBalcony Floor/Wall
Sto Primer (Optional)
Sto Finish
Sto Mesh
(with Sto Mesh Embedded) Sto Base Coat
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sheathing
Sto EPS Insulation Board, Pre-Wrapped
Sto Adhesive
Balcony Slab Recess
Backer Rod & Sealant w/ Weeps
Balcony Waterproof Membrane and Finished Flooring
Balcony
Cant and Air Seal Transition Material
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Detail applies to Balcony Protected by Balcony Ceiling Above.
2. Underside of balcony may also be finished with Sto Finish or other Sto smooth or textured coatings.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Detail No.: 52s.42BDate: November 2015
StoTherm® ciBalcony Ceiling/Wall
StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier
Sto Primer (Optional)
Sto Finish
Sto Adhesive
(with Sto Mesh Embedded) Sto Base Coat
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Sheathing
Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination
Sto Mesh
Backer Rod
Backer Rod and Sealant
Balcony
Slotted Deflection Track
Skim Coat of Sto Base Coat
Sto Primer Smooth
StoCoat Acryl Plus
StoTherm® ciHorizontal Termination at Dissimilar Cladding
Detail No.: 52s.50Date: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Sto EPS Insulation Board, Back-Wrapped
Sto Base Coat (with Sto Mesh Embedded)
Sto Mesh
Sto Adhesive
Light Gauge Steel Stud Framing
Sto Primer (Optional)
Sto Finish
Backer Rod and Sealant with Weep Holes
Sheathing
StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier
Sealant
StoGuard® Air and Moisture Barrier Detail Component
Wood Blocking
Brick Cavity Wall
Masonry Sill
Flashing
StoGuard® Air and Moisture Barrier
StoGuard® Air and Moisture Barrier
StoTherm® ciVertical Termination at Dissimilar Cladding
Detail No.: 52s.51ADate: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Sheathing
Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination
Sto Base Coat (with Sto Mesh Embedded)
Sto Mesh
Sto AdhesiveLight Gauge Steel Stud Framing
StoGuard® Air and Moisture Barrier
Sto Primer (Optional)
Sto Finish
Masonry Veneer or Other Dissimilar Material
Sealant and Backer Rod
StoTherm® ciVertical Termination at Dissimilar Backup Wall Construction
Detail No.: 52s.51BDate: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier Sheathing
Light Gauge Steel Stud Framing
StoGuard® Air and Moisture Barrier (Minimum Two Coats on CMU Wall Surface)
CMU Backup
Masonry Veneer or Other Dissimilar Material
Sto Finish
Sealant and Backer Rod
Sto Base Coat (with Sto Mesh Embedded)
Sto Mesh
Sto Primer (Optional)
Sto Adhesive
Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination
StoTherm® ciVertical Expansion Joint in Back-Up Wall
Detail No.: 52s.52ADate: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Sheathing
Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination
Sto Base Coat (with Sto Mesh Embedded)
Sto Mesh
Sto AdhesiveLight Gauge Steel Stud Framing
StoGuard® Air and Moisture Barrier
Sto Primer (Optional)
Sealant and Backer Rod
Sto Finish
StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier
StoTherm® ciVertical Expansion Joint in Back-Up Wall,StoTherm ci and Dissimilar Cladding
Detail No.: 52s.52BDate: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination
Masonry Veneer or Other Dissimilar Material
StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier
StoGuard® Air and Moisture Barrier
SheathingSto Primer (Optional)
Sto Base Coat (with Sto Mesh Embedded)
Sto Mesh
Sto Finish
Sealant and Backer Rod
Light Gauge Steel Stud Framing
StoTherm® ciInside Corner with Dissimilar Backup Wall
Detail No.: 52s.53Date: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Sto EPS Insulation Board, Back-Wrapped
Sto Base Coat (with Sto Mesh Embedded)
Sto Mesh
Sto Adhesive
StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture BarrierLight Gauge Steel Stud Framing
Sto Primer (Optional)
Sto Finish
Sealant and Backer Rod
StoGuard® Air and Moisture Barrier (Minimum Two Coats on CMU Wall Surface)
CMU Backup
Sheathing
StoTherm® ciInside and Outside Corner with Common Substrateand StoMesh Corner Bead Reinforcement
Detail No.: 52s.54ADate: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Provide joint at interior corner if movement is anticipated. Refer to Sto Detail 52s.53.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Sto EPS Insulation Board
Sto Base Coat (with Sto Mesh Embedded)
Sto Adhesive StoGuard® Joint Treatment
Light Gauge Steel Stud Framing
Sto Primer (Optional)
Sto Finish
StoGuard® Air and Moisture Barrier
Sheathing
Sto-Mesh Corner Bead Standard (Embedded in Sto Base Coat)
Sto Mesh, (Overlap StoMesh Corner Bead 4 in. ea. Side, min.)
Return Sto Mesh 6 in. min. @ Inside Corner
StoTherm® ciInside and Outside Corner with Common Substrateand Sto Mesh Reinforcement
Detail No.: 52s.54BDate: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Provide joint at interior corner if movement is anticipated. Refer to Sto Detail 52s.53.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Sto EPS Insulation Board
Sto Base Coat (with Sto Mesh Embedded)
Sto Adhesive StoGuard® Joint Treatment
Light Gauge Steel Stud Framing
Sto Primer (Optional)
Sto Finish
StoGuard® Air and Moisture Barrier
Sheathing
Return Sto Mesh 6 in. min. Around Corner
Return Sto Mesh 6 in. min. @ Inside Corner
Sto Mesh
StoTherm® ciTermination at Parapet - Front
Detail No.: 52s.60ADate: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Sto EPS Insulation Board, Back-Wrapped
Sto Base Coat (with Sto Mesh Embedded)
Sto Adhesive
Metal Coping
Light Gauge Steel Stud Framing
Sto Primer (Optional)
Sto Finish
StoGuard® Air and Moisture Barrier
Sheathing
Roof Structure
StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (or Compatible Roofing Membrane)
Wood Blocking
StoGuard® Detail Component
Sto Mesh
Backer Rod & Sealant
StoTherm® ciTermination at Parapet - Back
Detail No.: 52s.60BDate: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Sto EPS Insulation Board, Pre-Wrapped
Sto Base Coat (with Sto Mesh Embedded)
Sto Adhesive
Metal Coping
Roof Membrane
Sto Primer (Optional)
Sto Finish
StoGuard® Air and Moisture Barrier Detail Component
Sheathing
Roof Structure
StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (or Compatible Roofing Membrane)
Wood Blocking
Backer Rod and Sealant
Sto Mesh
StoGuard® Detail Component
Termination Bar for Roof Membrane
Light Ga. Steel Stud Framing
Cover BoardRoof Insulation
StoGuard® Air and Moisture Barrier
Termination Bar for Roof Membrane
Sto EPS Insulation Board, Pre-Wrapped
Wood Blocking
StoGuard® Detail Component
Insulation
Z-Flashing
Roof Membrane
StoGuard® Air and Moisture Barrier
Sheathing
Backer Rod and Sealant with Weep Holes
StoTherm® ciParapet with Cornice Feature
Detail No.: 52s.61Date: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Cornice feature limited to 12" (30.5 cm) maximum thickness for noncombustible type construction. Special analysis with regard to fire propagation may enable thicker sections. Thicker sections permitted within practical limits for combustible construction.
2. Cornice feature attached with Sto TurboStick Adhesive; also used as filler and rasped smooth at any gaps between feature band and base layer of insulation board.
3. Cornice feature may also be attached directly to StoGuard where applicable.
4. Supplemental mechanical attachment of feature band maybe necessary in some cases. Verify installation method for adequate attachment before commencing work.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
View of Pre-Wrapped CorniceView of Mesh Overlap
Sto Mesh Embedded in Base Coat Laps Sto Mesh on Cornice 2 1/2 in. (64 mm) min.
Sto EPS Insulation Cornice Feature
Cornice Feature Pre-Wrapped with Sto Base Coat (with Sto Mesh Embedded)
StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (or Compatible Roofing Membrane)
Wood Construction as Required StoGuard® Air and Moisture Barrier Sheathing Joint Treatment Extends 2 in. (51 mm) min. at Vertical and Horizontal Surfaces
Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination
Sto Base Coat (with Sto Mesh Embedded)
Metal Coping
Sto Primer (Optional)
Sto Finish
Sheathing
Backer Rod and Sealant
Sto Mesh
Light Gauge Steel Stud Framing
StoGuard® Air and Moisture Barrier
1/2 in. (13 mm) min. Gap Between Top Surface of Cornice Feature and Underside of Wood ConstructionPre-Wrapped
Cornice
StoTherm® ciDiverter Flashing at Roof/Wall Abutment
Detail No.: 52s.62Date: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Maintain minimum 2" (51 mm) gap between roof shingles and StoTherm ci termination. Increase gap for low slope roofs to prevent snow and ice accumulations.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Backer Rod and Sealant Around Vertical Leg of Diverter Flashing
Diverter Flashing
StoGuard® Air and Moisture Barrier
StoGuard® Air and Moisture Barrier Detail Component
Sto EPS Insulation Board, Pre-Wrapped
Sto Base Coat (with Sto Mesh Embedded) Sto Primer (Optional)
Sto Finish
Sheathing
Sto Mesh
Light Gauge Steel Stud Framing
Drip Edge Flashing
Gutter
StoGuard® Air and Moisture Barrier Sheathing Joint Treatment
Sto AdhesiveDiverter Flashing
Terminate StoTherm ci 2 in. (51 mm) Above Finished Roof
Fascia
Drip Edge Flashing
Roof Structure
Step Flashing
Step Flashing
Sto Finish
Roof ShinglesRoof Underlayment
StoTherm® ciGravel Stop
Detail No.: 52s.63Date: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
StoGuard® Air and Moisture Barrier
Sto EPS Insulation Board, Back-Wrapped
Sto Base Coat (with Sto Mesh Embedded)
Sto Primer (Optional)
Sto Finish
Roof Air Barrier
Sto Mesh
Light Gauge Steel Stud Framing
Sto Adhesive
Gravel Roof Ballast
Continuous Cleat
Gravel Stop
Sheathing
1/4" (6 mm) Min. Gap Between Top of EPS Insulation Board and Wood Blocking
Wood Blocking
Roof Membrane
Roof Insulation
Roof Sheathing
Roof Structure
StoGuard® Air and Moisture Barrier Sheathing Joint Treatment
Backer Rod & Sealant
StoTherm® ciSaddle Flashing at Lower/Higher Wall Abutment
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Provide minimum 2" (51 mm) gap between parapet cap flashing and StoTherm ci termination.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Sheathing
Detail No.: 52s.64-1Date: November 2015
StoGuard® Detail Component
StoGuard® Air and Moisture Barrier
Light Gauge Steel Stud Framing
Step 1 - Air and Moisture Barrier
StoTherm® ciSaddle Flashing at Lower/Higher Wall Abutment
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Provide minimum 2" (51 mm) gap between parapet cap flashing and StoTherm ci termination.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Detail No.: 52s.64-2Date: November 2015
A
BC
StoGuard® Air and Moisture Barrier
StoGuard® Air and Moisture Barrier
Assembled Saddle Flashing
Saddle Flashing Components
Step 2 - Saddle Flashing
StoTherm® ciSaddle Flashing at Lower/Higher Wall Abutment
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Provide minimum 2" (51 mm) gap between parapet cap flashing and StoTherm ci termination.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Detail No.: 52s.64-3Date: November 2015
Parapet Cap Flashing Assembly Extends to Perpendicular Wall
Light Gauge Steel Stud Framing
StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (or Compatible Roofing Membrane)
StoGuard® Detail Component
Wood Blocking
Saddle Flashing Assembly
Backer Rod & Sealant Between StoTherm ci and Saddle Flashing Assembly
StoGuard® Air and Moisture Barrier
Sto EPS Insulation Board, Pre-Wrapped at Termination
StoTherm ci Assembly
Step 3 - Cladding, Coping, and Sealant
StoTherm® ciScupper Penetration
Detail No.: 52s.65Date: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
StoGuard® Air and Moisture Barrier
Sto EPS Insulation Board, Back-Wrapped Around Scupper Penetration
Sto Base Coat (with Sto Mesh Embedded) Sto Primer (Optional)
Sto Finish
Sto Mesh
Light Gauge Steel Stud Framing
Sto Adhesive
Sheathing
Wood Blocking
Roof Membrane
Roof Insulation
Roof Structure
Backer Rod & Sealant
StoGuard® Air and Moisture Barrier Detail Component
Scupper Assembly
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Refer to Sto Detail 52s.70B where sheathing is "rough cut" around pipe or where gap around pipe exceeds allowable gap dimension for StoGuard Air and Moisture Barrier Detail Component.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
StoGuard® Air and Moisture Barrier
Sto EPS Insulation Board, Back-Wrapped Around Pipe Penetration
Sto Base Coat (with Sto Mesh Embedded)
Sto Primer (Optional)
Sto Finish
Sto Mesh
Light Gauge Steel Stud Framing
Sto Adhesive
Sheathing
Backer Rod & Sealant
StoGuard® Air and Moisture Barrier Detail Component
Pipe
Detail No.: 52s.70ADate: November 2015
StoTherm® ciPipe Penetration - Precision Cut Sheathing
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Appropriate spray foam is used to fill gaps in sheathing. Where sheathing fits snug around pipe refer to Sto Detail 52s.70A.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
Retrofit or Oversized Pipe Penetration Opening
Detail No.: 52s.70BDate: November 2015
StoTherm® ciPipe Penetration - Rough Cut Sheathing
StoGuard® Air and Moisture Barrier
Sto EPS Insulation Board, Back-Wrapped Around Pipe Penetration Sto Base Coat (with
Sto Mesh Embedded)
Sto Primer (Optional)
Sto Finish
Sto Mesh
Light Gauge Steel Stud Framing
Sto Adhesive
Sheathing
Backer Rod & Sealant
StoGuard® Air and Moisture Barrier Detail Component
Pipe
Spray Foam (to Fill Gaps, Shaved or Rasped Flush with Sheathing Surface)
StoTherm® ciSign Attachment
Detail No.: 52s.71Date: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Blocking not required where solid substrate or wood-based sheathing is capable of supporting the sign (or other attached object). Use appropriate fasteners for attachment.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
StoGuard® Air and Moisture Barrier
Sto Base Coat (with Sto Mesh Embedded)
Sto Primer (Optional)
Sto Finish
Sto Mesh
Light Gauge Steel Stud Framing
Sheathing
Wood Blocking
Hole Drilled in EIFS and Lined with Sealant
PVC or Stainless Steel Sleeve (Sleeve Extends From Finish Through Blocking, Shown Partial Length for Clarity)
Neutral Cure Sealant
Sign
Washer Behind Sign Set in Sealant
Sto EPS Insulation Board
Sto Adhesive
Bolt w/ Washers at Each End
StoTherm® ciFixture Attachment
Detail No.: 52s.73Date: November 2015
IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.
ATTENTION
Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.
STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.
www.stocorp.com
®
Notes:
1. Attach fixture to blocking or solid substrate. Where attached to blocking seal the blocking with Sto Detail Component.
- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.
- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.
Property of Sto Corp. All Rights Reserved.
StoGuard® Air and Moisture Barrier
Sto Base Coat (with Sto Mesh Embedded)
Sto Primer (Optional)
Sto Finish
Sto Mesh
Light Gauge Steel Stud Framing
Sto AdhesiveSheathing
Backer Rod & Sealant
StoGuard® Air and Moisture Barrier Detail Component on Blocking; Extend onto Sheathing 2" min.
Electric Box for Fixture AttachmentBlocking
Sto EPS Insulation Board, Back-Wrapped Around Electric Box Penetration