StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com. www.stocorp.com Property of Sto Corp. All Rights Reserved.

Transcript of StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ®...

Page 1: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciFrame ConstructionSeries 52s.xxNovember 2015

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp.All Rights Reserved.

Page 2: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciSystem Components

Detail No.: 52s.00Date: November 2015

Notes:

1. StoTherm ci System Components: - StoGuard Air and Moisture Barrier - Sto Adhesive - Sto EPS or Sto GPS Insulation Board - Sto Mesh - Sto Primer (optional) - Sto Base Coat - Sto Finish

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

Sheathing

Sto EPS Insulation Board

Sto MeshSto Base Coat (with Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Sto Adhesive

Page 3: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciSystem Components: Ultra-High Impact Resistance

Detail No.: 52s.01Date: November 2015

Property of Sto Corp. All Rights Reserved.

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1.StoTherm ci System Components: - StoGuard air and Moisture Barrier - Sto Adhesive - Sto EPS or Sto GPS Insulation Board - Sto Armor Mat XX - Sto Mesh - Sto Primer (optional) - Sto Base Coat - Sto Finish

2. Ultra-high impact resistance recommended at all ground floors to a minimum height of 6'-0" (1.8 m) above finished grade and other areas accessible to pedestrian traffic, abnormal stress or impact.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Sto Materials:

1.Sample Text

1.Sample Notes

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

(with Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Sto Adhesive

Sheathing

Sto EPS Insulation Board

Sto MeshSto Base Coat

Sto Base Coat (with Sto Armor Mat Embedded)

Page 4: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciTermination at Grade - Sheathing Flush with Foundation or Slab Edge

Detail No.: 52s.03ADate: November 2015

Property of Sto Corp. All Rights Reserved.

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Terminate system minimum 6" (15.2 cm) above finished grade, higher for areas with heavy snow accumulations, or where required by code.

2. Ultra-high impact resistance recommended at all ground floors to a minimum height of 6'-0" (1.8 m) above finished grade and other areas accessible to pedestrian traffic, abnormal stress or impact.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sto Primer (Optional)

Sto Finish

Sto AdhesiveSheathing

Sto EPSInsulation Board, Pre- Wrapped

Sto Mesh

(with Sto Mesh Embedded) Sto Base Coat

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (Protect with StoCoat Acryl Plus or Flashing)

StoGuard® Air and Moisture Barrier Detail ComponentFlashing, Sloped

Backer Rod & Sealant w/ Weep Holes

Terminate Assembly 6" (152 mm) Above Grade, min.

Page 5: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciTermination at Grade - Sheathing Overlapping Slab or Foundation

Detail No.: 52s.03BDate: November 2015

Property of Sto Corp. All Rights Reserved.

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Terminate system minimum 6" (15.2 cm) above finished grade, higher for areas with heavy snow accumulations, or where required by code.

2. Ultra-high impact resistance recommended at all ground floors to a minimum height of 6'-0" (1.8 m) above finished grade and other areas accessible to pedestrian traffic, abnormal stress or impact.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sto Primer (Optional)

Sto Finish

Sto AdhesiveSheathing

Sto EPSInsulation Board, Pre-Wrapped

Terminate Assembly 6" (152 mm) Above Grade, min.

Sto Mesh

(with Sto Mesh Embedded) Sto Base Coat

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (Protect with StoCoat Acryl Plus or Flashing)

StoGuard® Air and Moisture Barrier Detail Component

Flashing, Sloped

Backer Rod & Sealant w/ Weep Holes

Page 6: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciAesthetic Feature Band

Detail No.: 52s.04Date: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Feature band attached with Sto TurboStick Adhesive, also used as filler and rasped smooth at any gaps between feature band and base layer of insulation board.

2. Slope top surface of feature band minimum 27 degrees. Increase slope for northern climates to prevent snow and ice accuulations.

3. Limit thickness of build-out to reduce maintenance associated with projecting architectural features.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sheathing

Sto EPSInsulation Board

Sto Base Coat (with Sto Mesh Embedded)

StoGuard® Air and Moisture Barrier

Sheathing

Sto EPSInsulation Board

(with Sto Mesh Embedded) Sto Base Coat

Sto Flexyl (with Sto Mesh or Sto Detail Mesh Embedded); Return Vertically 4" (102 mm) min. Above and Below Feature Band

Sto Mesh

Sto Mesh

Sto Finish

Sto Finish

Sto Primer (Required over Sto Flexyl and Sto Base Coat Above and Below)

Sto Adhesive

Sto Adhesive

Thin Build-Out

Thick Build-Out

Thick Build-Out, 2-4 in. (51-102 mm)

Thin Build-Out, ≤ 2 in. (51 mm)

Page 7: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciAesthetic Reveal

Detail No.: 52s.05Date: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Slope bottom surface of reveal minimum 27 degrees. Increase slope for northern climates to prevent snow and ice accumulations.

2. Maintain minimum 3/4 inch (19 mm) thickness of insulation board at base of reveal.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Sto Primer (Optional)

Sto Finish

Sto Adhesive

Sto EPSInsulation Board

Sto Base Coat (with Sto Detail Mesh Embedded)

3/4" (19 mm) min.

2 1/2" (64 mm) min. Ovelap of Sto Detail Mesh w/ Sto Mesh @ Top and Bottom of Reveal

StoGuard® Air and Moisture Barrier

Sto Base Coat (with Sto Mesh Embedded) Sto Mesh

Sto Detail Mesh

Sto Primer (Optional)

Sto Finish

Sto Adhesive

Sto EPSInsulation Board

3/4" (19 mm) min.

StoGuard® Air and Moisture Barrier

Sto Base Coat (with Sto Mesh Embedded) Sto Mesh

Sheathing

Sheathing

Option 1 with Sto Detail Mesh

Option 2 with Continuous Sto Mesh

Page 8: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciReceptor-Type Window Sill

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.23A-1Date: November 2015

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection Over Blocking

Blocking

StoGuard® Air and Moisture Barrier Rough Opening Protection

Step 1 - Rough Opening Protection

Page 9: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciReceptor-Type Window Sill

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.23A-2Date: November 2015

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

End Dam Set in Sealant

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-Wrapped

Sto TurboStick Adhesive (Fill Gap Between EPS Boards at Corner with this Adhesive, Cut Flush with Surface and Rasp Smooth)

Sto EPS Insulation Board, Pre-Wrapped around Rough Opening

Sill Receptor w/ Weep Holes (Sill Flashing Extender Not Shown for Clarity)

Sto Adhesive

Weep Holes

Angle (As Needed for Attachment of Sill Receptor and Support)

StoGuard® Air and Moisture Barrier Rough Opening Protection

Blocking

Step 2 - Receptor with End Dam

Page 10: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciReceptor-Type Window Sill

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.23A-3Date: November 2015

Sto Primer (Optional)

Sto Finish

Sto Mesh

(with Sto Mesh Embedded)

Sto Base Coat

Backer Rod & Sealant (Entire Perimeter)

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-Wrapped at Jamb

Sto EPS Insulation Board, Pre-Wrapped around Rough Opening

Sill Receptor w/ Weep Holes

Sto Adhesive

Spray Polyurethane Foam Insulation

Jamb Receptor

Sill Extender w/ Continuous Bead of Sealant @ Bottom

Window Assembly

Air Seal, Backer Rod & Sealant (Air Seal Entire Perimeter)

Angle (As Needed for Attachment of Sill Receptor and Support)

StoGuard® Air and Moisture Barrier Rough Opening Protection

Blocking

Step 3 - Window and Sill Flashing, Cladding, and Perimeter Weather and Air Seals

Page 11: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciReceptor-Type Window Head

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.23B-1Date: November 2015

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Cement Board Filler or Other TrimFlashing

StoGuard® Air and Moisture Barrier Rough Opening Protection

StoGuard® Air and Moisture Barrier

StoGuard® Air and Moisture Barrier Detail Component

Step 1 - Rough Opening Protection, Head Flashing

Page 12: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciReceptor-Type Window Head

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.23B-2Date: November 2015

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-Wrapped

Sto TurboStick Adhesive (Fill Gap Between EPS Boards at Corner with this Adhesive, Cut Flush with Surface and Rasp Smooth, Reinforce Top Corner with Sto Mesh or Sto Detail Mesh Embedded in Base Coat)

Sto EPS Corner Board, Pre-Wrapped around Rough Opening

Window Assembly

Spray Polyurethane Foam Insulation

Head Receptor

Jamb Receptor

Cement Board Filler or Other TrimFlashing

StoGuard® Air and Moisture Barrier Rough Opening Protection

StoGuard® Air and Moisture Barrier

Sto Adhesive

Step 2 - Receptor and Window

Page 13: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciReceptor-Type Window Head

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.23B-3Date: November 2015

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-WrappedSto TurboStick Adhesive (Fill Gap Between EPS Boards at Corner with this Adhesive, Cut Flush with Surface and Rasp Smooth)

Sto EPS Corner Board, Pre-Wrapped around Rough Opening

Window Assembly

Sto Adhesive

Sto Primer (Optional)

Sto Finish

Sto Mesh

(with Sto Mesh Embedded)

Sto Base Coat

Air Seal, Backer Rod and Sealant (Air Seal Entire Perimeter)

Head Receptor

Jamb Receptor Backer Rod & Sealant (Entire Perimeter, with Weeps at Head)

Cement Board Filler or Other Trim (Finish Cement Bd. w/ StoCoat Acryl Plus)

Flashing

StoGuard® Air and Moisture Barrier Rough Opening Protection

StoGuard® Air and Moisture Barrier

Spray Polyurethane Foam Insulation

Step 3 - Cladding and Perimeter Weather and Air Seals

Page 14: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciFlanged Window-Sill

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Detail No.: 52s.24A-1Date: November 2015

Property of Sto Corp. All Rights Reserved.

Step 1 - Rough Opening Protection, Sill Flashing

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

1/8" (3 mm) Thick Washers Behind Mounting Flange

StoGuard® Air and Moisture Barrier Rough Opening Protection

StoGuard® Detail Component

Flashing

Slope

Page 15: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciFlanged Window-Sill

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Detail No.: 52s.24A-2Date: November 2015

Property of Sto Corp. All Rights Reserved.

Step 2 - Window and Trim

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-Wrapped Around Opening (Cut Kerf in Back of Insulation and Slide over End Dam. Position insulation over Flashing with 1/4" [6 mm] Gap for Drainage)

Spray Polyurethane Foam Insulation

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sealant Behind Mounting Flange (Jambs and Head Only)

Sto Adhesive

StoGuard® Detail Component

Flashing

Slope

Window Assembly

1/8" (3 mm) Thick Washers Behind Mounting Flange

Spray Polyurethane Foam Insulation

Page 16: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciFlanged Window-Sill

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Detail No.: 52s.24A-3Date: November 2015

Property of Sto Corp. All Rights Reserved.

Step 3 - Cladding and Perimeter Weather and Air Seals

Sto Primer (Optional)

Sto Finish

Sto Mesh

(with Sto Mesh Embedded)

Sto Base Coat

Backer Rod & Sealant (Entire Perimeter)

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-Wrapped Around Opening

Sto EPS Insulation Board

Spray Polyurethane Foam Insulation

Window Assembly

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto Adhesive

StoGuard® Detail ComponentFillet Bead of Sealant (not

shown) Between Underside of Flashing and Base Coat

1/8" (3 mm) Thick Washers Behind Mounting Flange

Sealant Behind Mounting Flange (Jambs and Head Only)

Air Seal, Backer Rod & Sealant (Air Seal Entire Perimeter)

Spray Polyurethane Foam Insulation

Backer Rod & Sealant with Weeps Between Trim and Flashing Leg

Flashing

Air Seal, Backer Rod & Sealant (Air Seal Entire Perimeter)

Page 17: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciFlanged Window-Head

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Detail No.: 52s.24B-1Date: November 2015

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Window Assembly

StoGuard® Air and Moisture Barrier Rough Opening Protection

StoGuard® Detail Component

Sealant Behind Mounting Flange (Jambs and Head Only)

Flashing

Sealant Behind Mounting Flange (Jambs and Head Only)

Sealant

Property of Sto Corp. All Rights Reserved.

Step 1 - Rough Opening Protection, Head Flashing

Page 18: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciFlanged Window-Head

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Detail No.: 52s.24B-2Date: November 2015

Property of Sto Corp. All Rights Reserved.

Step 2 - Window and Trim

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-Wrapped Around Opening

Sto EPS Insulation Board

Window Assembly

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto Adhesive

StoGuard® Detail Component

Sealant Behind Mounting Flange (Jambs and Head Only)

Sealant

Spray Polyurethane Foam Insulation

Flashing

Backer Rod & Sealant Weather and Air Seals (Entire Perimeter with Weeps Between Underside of Trim & Flashing Leg)

Spray Polyurethane Foam Insulation

Page 19: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciFlanged Window-Head

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Consult with window and sealant manufacturers to verify window installation and detailing and to assure no water leakage into the wall assembly. Consult with window manufacturer regarding window and/or flashing assembly thermal breaks to avoid condensation. Test the final assembly using materials and trades associated with the project to verify performance. Correct any deficiencies associated with excess air leakage, water infiltration into the wall assembly, or structural inadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with the project to verify installation sequencing, detailing, and aesthetics.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Detail No.: 52s.24B-3Date: November 2015

Property of Sto Corp. All Rights Reserved.

Step 3 - Cladding and Perimeter Weather and Air Seals

Sto Primer (Optional)

Sto Finish

Sto Mesh

(with Sto Mesh Embedded)

Sto Base Coat

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-Wrapped Around Opening

Sto EPS Insulation Board

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto Adhesive

StoGuard® Detail Component

Sealant Behind Mounting Flange (Jambs and Head Only)

Sealant

Spray Polyurethane Foam Insulation

Flashing

Spray Polyurethane Foam Insulation

Window Assembly

Backer Rod & Sealant Weather and Air Seals (Entire Perimeter with Weeps Between Underside of Trim & Flashing Leg)

Page 20: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciSoffit: Insulated and Unvented

Detail No.: 52s.30Date: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Continue StoGuard air and moisture barrier onto dissimilar material or construction where required after verifying substrate material compatibility. Refer to Sto Detail 52s.53 for typical detailing of inside corner if substrate material or construction is dissimilar. Refer to Sto Detail 52s.54A if substrate material is similar at inside corner.

2. 4" (10 cm) thick insulation board typically required for proper lap of accessory with mesh "tail." For thinner sections of insulation board pre-wrap insulation board with Sto base coat and mesh.

3. Multi-story buildings where construction is required to be Noncombustible may require special examination of soffit conditions with foam plastic insulation. Verify with professional fire protection engineer and building code official.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Nominal 1/4 inch (6 mm) Gap for Drainage

Sheathing

Sto EPS Insulation Board, Pre-Wrapped

Sto Base Coat (with Sto Mesh Embedded) Sto Mesh

Sto Adhesive

StoGuard® Joint Treatment

Backer Rod and Sealant

Structure

Sto Drip Edge Profile

Sto Drip Edge Profile (See Drawing Below) Dissimilar Material or

Wall Construction

Light Gauge Steel Stud Framing

StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sto Finish

Page 21: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciSoffit: Uninsulated and Vented

Detail No.: 52s.31Date: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Prevent "communication" of vented air space with conditioned interior air to reduce the likelihood of condensation on materials in the vented space.

3. Typical soffit board is gypsum sheathing in compliance with ASTM C 1177. Refer to Sto Specification No. F601S and Sto Detail Series 14.xx.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Nominal 1/4 inch (6 mm) Gap for Drainage

Sheathing

Sto EPS Insulation Board, Pre-Wrapped

Sto Base Coat (with Sto Mesh Embedded) Sto Mesh

Sto Adhesive

Backer Rod and Sealant

Structure

Sto Drip Edge Profile

Sto Drip Edge Profile (See Drawing Below) Dissimilar Material or

Wall Construction

Light Gauge Steel Stud FramingStoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sto Finish

StoGuard® Joint Treatment

Soffit Vent

Casing Bead

Page 22: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciFloor Line Without Deflection

Detail No.: 52s.40Date: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. This detail is typically limited to low-rise construction where no floor line deflection is anticipated. Refer to Sto Detail 52s.41A, B, or C for a floor line condition with deflection.

2. Sheathing attachment is typically at 8" (20.3 cm) on center or less vertically. Add C-channels or other attachment means along slab edge if necessary to conform with required fastener spacing.

3. Provide fire stopping at floor line as needed.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sto Finish

Sheathing

Sto EPS Insulation Board

Sto Base Coat (with Sto Mesh Embedded)

Sto Adhesive

Sto Mesh

StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

Structure

Page 23: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciFloor Line With Deflection -Concealed Flashing and Drainage at Floor Line

Detail No.: 52s.41ADate: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Sheathing attachment is typically at 8" (20.3 cm) on center or less vertically. Add C-channels or other attachment means along slab edge if necessary to conform with required fastener spacing.

2. Provide fire stopping at floor line as needed.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sto Finish

Sheathing

Sto EPS Insulation Board, Pre-Wrapped @ Top and Bottom to Allow for Drainage

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Adhesive StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

StoGuard® Transition Membrane

Horizontal Deflection Joint: Backer Rod & Sealant w/ Drainage Openings. Sealant Applied to Base Coat as per Sealant Manuf'r Instructions

Slotted Deflection Track

Backer Rod

Structure

StoGuard® Transition Membrane Applied from Face of StoGuard® Air & Moisture Barrier and Lapped onto Top of EPS Insulation Board with Slight Slope for Drainage @ Bottom of Joint

Page 24: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciFloor Line With Deflection - No Drainage at Floor Line

Detail No.: 52s.41BDate: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Sheathing attachment is typically at 8" (20.3 cm) on center or less vertically. Add C-channels or other attachment means along slab edge if necessary to conform with required fastener spacing.

2. Provide fire stopping at floor line as needed.

3. Provide drainage at floor lines as deemed by Design Professional, typically no more than every third floor line. Refer to Sto Detail 52s.41A.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sto Finish

Sheathing

Sto EPS Insulation Board, Pre-Wrapped @ Top and Bottom to Allow for Drainage

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Adhesive StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

StoGuard® Transition Membrane

Horizontal Deflection Joint: Backer Rod & Sealant. Sealant Applied to Base Coat as per Sealant Manuf'r Instructions

Slotted Deflection Track

Backer Rod

Structure

Page 25: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Detail apples to Balcony Protected Overhead by Balcony Ceiling Above.

2. Slope balcony to direct water away from wall.

3. Consider the use of high or ultra-high reinforcing meshes on balcony walls to supplement standard reinforcing mesh for added abuse and impact resistance.

4. Verify compatibility of StoGuard Air and Moisture Barrier with balcony waterproof membrane material where they interface or lap one another.

5. Counter flash balcony membrane on wall if not fluid applied.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Detail No.: 52s.42ADate: November 2015

StoTherm® ciBalcony Floor/Wall

Sto Primer (Optional)

Sto Finish

Sto Mesh

(with Sto Mesh Embedded) Sto Base Coat

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

Sto EPS Insulation Board, Pre-Wrapped

Sto Adhesive

Balcony Slab Recess

Backer Rod & Sealant w/ Weeps

Balcony Waterproof Membrane and Finished Flooring

Balcony

Cant and Air Seal Transition Material

Page 26: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Detail applies to Balcony Protected by Balcony Ceiling Above.

2. Underside of balcony may also be finished with Sto Finish or other Sto smooth or textured coatings.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Detail No.: 52s.42BDate: November 2015

StoTherm® ciBalcony Ceiling/Wall

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sto Finish

Sto Adhesive

(with Sto Mesh Embedded) Sto Base Coat

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination

Sto Mesh

Backer Rod

Backer Rod and Sealant

Balcony

Slotted Deflection Track

Skim Coat of Sto Base Coat

Sto Primer Smooth

StoCoat Acryl Plus

Page 27: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciHorizontal Termination at Dissimilar Cladding

Detail No.: 52s.50Date: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Sto EPS Insulation Board, Back-Wrapped

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Adhesive

Light Gauge Steel Stud Framing

Sto Primer (Optional)

Sto Finish

Backer Rod and Sealant with Weep Holes

Sheathing

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier

Sealant

StoGuard® Air and Moisture Barrier Detail Component

Wood Blocking

Brick Cavity Wall

Masonry Sill

Flashing

StoGuard® Air and Moisture Barrier

StoGuard® Air and Moisture Barrier

Page 28: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciVertical Termination at Dissimilar Cladding

Detail No.: 52s.51ADate: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Sheathing

Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto AdhesiveLight Gauge Steel Stud Framing

StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sto Finish

Masonry Veneer or Other Dissimilar Material

Sealant and Backer Rod

Page 29: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciVertical Termination at Dissimilar Backup Wall Construction

Detail No.: 52s.51BDate: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier Sheathing

Light Gauge Steel Stud Framing

StoGuard® Air and Moisture Barrier (Minimum Two Coats on CMU Wall Surface)

CMU Backup

Masonry Veneer or Other Dissimilar Material

Sto Finish

Sealant and Backer Rod

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Primer (Optional)

Sto Adhesive

Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination

Page 30: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciVertical Expansion Joint in Back-Up Wall

Detail No.: 52s.52ADate: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Sheathing

Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto AdhesiveLight Gauge Steel Stud Framing

StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sealant and Backer Rod

Sto Finish

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier

Page 31: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciVertical Expansion Joint in Back-Up Wall,StoTherm ci and Dissimilar Cladding

Detail No.: 52s.52BDate: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination

Masonry Veneer or Other Dissimilar Material

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier

StoGuard® Air and Moisture Barrier

SheathingSto Primer (Optional)

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Finish

Sealant and Backer Rod

Light Gauge Steel Stud Framing

Page 32: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciInside Corner with Dissimilar Backup Wall

Detail No.: 52s.53Date: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Sto EPS Insulation Board, Back-Wrapped

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Adhesive

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture BarrierLight Gauge Steel Stud Framing

Sto Primer (Optional)

Sto Finish

Sealant and Backer Rod

StoGuard® Air and Moisture Barrier (Minimum Two Coats on CMU Wall Surface)

CMU Backup

Sheathing

Page 33: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciInside and Outside Corner with Common Substrateand StoMesh Corner Bead Reinforcement

Detail No.: 52s.54ADate: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Provide joint at interior corner if movement is anticipated. Refer to Sto Detail 52s.53.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Sto EPS Insulation Board

Sto Base Coat (with Sto Mesh Embedded)

Sto Adhesive StoGuard® Joint Treatment

Light Gauge Steel Stud Framing

Sto Primer (Optional)

Sto Finish

StoGuard® Air and Moisture Barrier

Sheathing

Sto-Mesh Corner Bead Standard (Embedded in Sto Base Coat)

Sto Mesh, (Overlap StoMesh Corner Bead 4 in. ea. Side, min.)

Return Sto Mesh 6 in. min. @ Inside Corner

Page 34: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciInside and Outside Corner with Common Substrateand Sto Mesh Reinforcement

Detail No.: 52s.54BDate: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Provide joint at interior corner if movement is anticipated. Refer to Sto Detail 52s.53.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Sto EPS Insulation Board

Sto Base Coat (with Sto Mesh Embedded)

Sto Adhesive StoGuard® Joint Treatment

Light Gauge Steel Stud Framing

Sto Primer (Optional)

Sto Finish

StoGuard® Air and Moisture Barrier

Sheathing

Return Sto Mesh 6 in. min. Around Corner

Return Sto Mesh 6 in. min. @ Inside Corner

Sto Mesh

Page 35: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciTermination at Parapet - Front

Detail No.: 52s.60ADate: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Sto EPS Insulation Board, Back-Wrapped

Sto Base Coat (with Sto Mesh Embedded)

Sto Adhesive

Metal Coping

Light Gauge Steel Stud Framing

Sto Primer (Optional)

Sto Finish

StoGuard® Air and Moisture Barrier

Sheathing

Roof Structure

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (or Compatible Roofing Membrane)

Wood Blocking

StoGuard® Detail Component

Sto Mesh

Backer Rod & Sealant

Page 36: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciTermination at Parapet - Back

Detail No.: 52s.60BDate: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Sto EPS Insulation Board, Pre-Wrapped

Sto Base Coat (with Sto Mesh Embedded)

Sto Adhesive

Metal Coping

Roof Membrane

Sto Primer (Optional)

Sto Finish

StoGuard® Air and Moisture Barrier Detail Component

Sheathing

Roof Structure

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (or Compatible Roofing Membrane)

Wood Blocking

Backer Rod and Sealant

Sto Mesh

StoGuard® Detail Component

Termination Bar for Roof Membrane

Light Ga. Steel Stud Framing

Cover BoardRoof Insulation

StoGuard® Air and Moisture Barrier

Termination Bar for Roof Membrane

Sto EPS Insulation Board, Pre-Wrapped

Wood Blocking

StoGuard® Detail Component

Insulation

Z-Flashing

Roof Membrane

StoGuard® Air and Moisture Barrier

Sheathing

Backer Rod and Sealant with Weep Holes

Page 37: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciParapet with Cornice Feature

Detail No.: 52s.61Date: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Cornice feature limited to 12" (30.5 cm) maximum thickness for noncombustible type construction. Special analysis with regard to fire propagation may enable thicker sections. Thicker sections permitted within practical limits for combustible construction.

2. Cornice feature attached with Sto TurboStick Adhesive; also used as filler and rasped smooth at any gaps between feature band and base layer of insulation board.

3. Cornice feature may also be attached directly to StoGuard where applicable.

4. Supplemental mechanical attachment of feature band maybe necessary in some cases. Verify installation method for adequate attachment before commencing work.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

View of Pre-Wrapped CorniceView of Mesh Overlap

Sto Mesh Embedded in Base Coat Laps Sto Mesh on Cornice 2 1/2 in. (64 mm) min.

Sto EPS Insulation Cornice Feature

Cornice Feature Pre-Wrapped with Sto Base Coat (with Sto Mesh Embedded)

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (or Compatible Roofing Membrane)

Wood Construction as Required StoGuard® Air and Moisture Barrier Sheathing Joint Treatment Extends 2 in. (51 mm) min. at Vertical and Horizontal Surfaces

Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination

Sto Base Coat (with Sto Mesh Embedded)

Metal Coping

Sto Primer (Optional)

Sto Finish

Sheathing

Backer Rod and Sealant

Sto Mesh

Light Gauge Steel Stud Framing

StoGuard® Air and Moisture Barrier

1/2 in. (13 mm) min. Gap Between Top Surface of Cornice Feature and Underside of Wood ConstructionPre-Wrapped

Cornice

Page 38: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciDiverter Flashing at Roof/Wall Abutment

Detail No.: 52s.62Date: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Maintain minimum 2" (51 mm) gap between roof shingles and StoTherm ci termination. Increase gap for low slope roofs to prevent snow and ice accumulations.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Backer Rod and Sealant Around Vertical Leg of Diverter Flashing

Diverter Flashing

StoGuard® Air and Moisture Barrier

StoGuard® Air and Moisture Barrier Detail Component

Sto EPS Insulation Board, Pre-Wrapped

Sto Base Coat (with Sto Mesh Embedded) Sto Primer (Optional)

Sto Finish

Sheathing

Sto Mesh

Light Gauge Steel Stud Framing

Drip Edge Flashing

Gutter

StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

Sto AdhesiveDiverter Flashing

Terminate StoTherm ci 2 in. (51 mm) Above Finished Roof

Fascia

Drip Edge Flashing

Roof Structure

Step Flashing

Step Flashing

Sto Finish

Roof ShinglesRoof Underlayment

Page 39: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciGravel Stop

Detail No.: 52s.63Date: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto EPS Insulation Board, Back-Wrapped

Sto Base Coat (with Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Roof Air Barrier

Sto Mesh

Light Gauge Steel Stud Framing

Sto Adhesive

Gravel Roof Ballast

Continuous Cleat

Gravel Stop

Sheathing

1/4" (6 mm) Min. Gap Between Top of EPS Insulation Board and Wood Blocking

Wood Blocking

Roof Membrane

Roof Insulation

Roof Sheathing

Roof Structure

StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

Backer Rod & Sealant

Page 40: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciSaddle Flashing at Lower/Higher Wall Abutment

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Provide minimum 2" (51 mm) gap between parapet cap flashing and StoTherm ci termination.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Sheathing

Detail No.: 52s.64-1Date: November 2015

StoGuard® Detail Component

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Step 1 - Air and Moisture Barrier

Page 41: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciSaddle Flashing at Lower/Higher Wall Abutment

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Provide minimum 2" (51 mm) gap between parapet cap flashing and StoTherm ci termination.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.64-2Date: November 2015

A

BC

StoGuard® Air and Moisture Barrier

StoGuard® Air and Moisture Barrier

Assembled Saddle Flashing

Saddle Flashing Components

Step 2 - Saddle Flashing

Page 42: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciSaddle Flashing at Lower/Higher Wall Abutment

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Provide minimum 2" (51 mm) gap between parapet cap flashing and StoTherm ci termination.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.64-3Date: November 2015

Parapet Cap Flashing Assembly Extends to Perpendicular Wall

Light Gauge Steel Stud Framing

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (or Compatible Roofing Membrane)

StoGuard® Detail Component

Wood Blocking

Saddle Flashing Assembly

Backer Rod & Sealant Between StoTherm ci and Saddle Flashing Assembly

StoGuard® Air and Moisture Barrier

Sto EPS Insulation Board, Pre-Wrapped at Termination

StoTherm ci Assembly

Step 3 - Cladding, Coping, and Sealant

Page 43: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciScupper Penetration

Detail No.: 52s.65Date: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto EPS Insulation Board, Back-Wrapped Around Scupper Penetration

Sto Base Coat (with Sto Mesh Embedded) Sto Primer (Optional)

Sto Finish

Sto Mesh

Light Gauge Steel Stud Framing

Sto Adhesive

Sheathing

Wood Blocking

Roof Membrane

Roof Insulation

Roof Structure

Backer Rod & Sealant

StoGuard® Air and Moisture Barrier Detail Component

Scupper Assembly

Page 44: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Refer to Sto Detail 52s.70B where sheathing is "rough cut" around pipe or where gap around pipe exceeds allowable gap dimension for StoGuard Air and Moisture Barrier Detail Component.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto EPS Insulation Board, Back-Wrapped Around Pipe Penetration

Sto Base Coat (with Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Sto Mesh

Light Gauge Steel Stud Framing

Sto Adhesive

Sheathing

Backer Rod & Sealant

StoGuard® Air and Moisture Barrier Detail Component

Pipe

Detail No.: 52s.70ADate: November 2015

StoTherm® ciPipe Penetration - Precision Cut Sheathing

Page 45: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Appropriate spray foam is used to fill gaps in sheathing. Where sheathing fits snug around pipe refer to Sto Detail 52s.70A.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

Retrofit or Oversized Pipe Penetration Opening

Detail No.: 52s.70BDate: November 2015

StoTherm® ciPipe Penetration - Rough Cut Sheathing

StoGuard® Air and Moisture Barrier

Sto EPS Insulation Board, Back-Wrapped Around Pipe Penetration Sto Base Coat (with

Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Sto Mesh

Light Gauge Steel Stud Framing

Sto Adhesive

Sheathing

Backer Rod & Sealant

StoGuard® Air and Moisture Barrier Detail Component

Pipe

Spray Foam (to Fill Gaps, Shaved or Rasped Flush with Sheathing Surface)

Page 46: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciSign Attachment

Detail No.: 52s.71Date: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Blocking not required where solid substrate or wood-based sheathing is capable of supporting the sign (or other attached object). Use appropriate fasteners for attachment.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto Base Coat (with Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Sto Mesh

Light Gauge Steel Stud Framing

Sheathing

Wood Blocking

Hole Drilled in EIFS and Lined with Sealant

PVC or Stainless Steel Sleeve (Sleeve Extends From Finish Through Blocking, Shown Partial Length for Clarity)

Neutral Cure Sealant

Sign

Washer Behind Sign Set in Sealant

Sto EPS Insulation Board

Sto Adhesive

Bolt w/ Washers at Each End

Page 47: StoTherm ci · 2018-07-05 · StoTherm ® ci Frame Construction Series 52s.xx November 2015 ® ATTENTION Sto products are intended for use by qualified professional contractors, not

StoTherm® ciFixture Attachment

Detail No.: 52s.73Date: November 2015

IMPORTANT: Components not identified as Sto are furnished by other manufacturers and are not necessarily installed by trades who install Sto products. Refer to project specific contract documents.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Notes:

1. Attach fixture to blocking or solid substrate. Where attached to blocking seal the blocking with Sto Detail Component.

- Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maintenance Guides for complete information.

- Refer to applicable ICC or CCMC Evaluation Reports for building code compliance information.

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto Base Coat (with Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Sto Mesh

Light Gauge Steel Stud Framing

Sto AdhesiveSheathing

Backer Rod & Sealant

StoGuard® Air and Moisture Barrier Detail Component on Blocking; Extend onto Sheathing 2" min.

Electric Box for Fixture AttachmentBlocking

Sto EPS Insulation Board, Back-Wrapped Around Electric Box Penetration