ASHRAE/USGBC/IES Standard 189.1
Lynn G. Bellenger, PE, FASHRAE ASHRAE HBDP, LEED®APPathfinder Engineers and Architects LLP
Standard for the Design ofHigh-Performance Green Buildings
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS2
What is Standard 189.1?
ANSI standard being developed in model code language
Provides minimum requirements for high-performance, green buildings
Applies to all buildings except low-rise residential buildings (same as ASHRAE/IESNA Std 90.1)
Not a design guide, not a rating system
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS3
Standard Project Committee 189.1
Sponsor and co-sponsors ASHRAE USGBC IES
Project committee 37 total members Diverse backgrounds
Consensus process
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS4
Scope of Standard 189.1
Applies to … new buildings and their systems new portions of buildings and their systems new systems and equipment in existing buildings
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS5
Goals for Standard 189.1
Establish mandatory criteria in all topic areas One “challenge” is existing green building rating systems contain
few mandatory provisions
Provide simple compliance options Complement green building rating programs Standard is not intended to compete with green building rating
programs
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS6
What Happens When Green Becomes Code?
Do Buildings Get Better?
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS7
Development of Standard 189.12006Preliminary meeting (Jun)
20071st public review (May-Jul)
20082nd public review (Feb)Committee reconstituted (Nov)
20093rd public review (May-Jun)4th public review of ISCs (Sep-Oct)Publication approval (Dec)
2010Publication (Jan)Transition to SSPC (June)
2007 2008 2009 2010 2011
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS8
Standard 189.1 Building Blocks
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS9
Standard 189.1 Chapter Structure
x.1: Scope x.2: Compliance x.3: Mandatory
(required for all projects) x.4: Prescriptive Option
(simple option, very few calculations) x.5: Performance Option
(more options, but more effort)
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS10
Compliance Paths
Mandatory + Prescriptive Path
Performance PathMandatory +
(Simple option, very few calculations)
(More options, but more effort)
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS11
Standard 189.1 Topic Areas
SS
WE
EE
IEQ
MR
CO
Sustainable Sites
Water Use Efficiency
Energy Efficiency
Indoor Environmental Quality
Building’s Impact on the Atmosphere, Materials & Resources
Construction and Operations Plans
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS12
Climate Zones
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS13
Sustainable SitesMandatory Provisions
Site selection Reduce heat island effect Reduce light pollution
SS WE EE IEQ MR CO
solar reflectance index (SRI): a measure of a constructed surface’s ability to reflect solar heat, as shown by a small temperature rise. A standard black surface (reflectance 0.05, emittance 0.90) is 0 and a standard white surface (reflectance 0.80, emittance0.90) is 100.
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS14
Sustainable SitesMandatory Provisions
Site Selection Allowable sites
• Existing building envelope• Brownfields, greyfields• Greenfield sites where 1/2 mile to:
- transit or 10 basic services, or residential area with density > 10 units/acre
Prohibited development activity• Flood plains • 100 ft of wetlands • 150 ft of fish and wildlife habitat
conservation areaSS WE EE IEQ MR CO
brownfield site: a site documented as contaminated by means of an ASTM E1903 Phase II Environmental Site Assessment or a site classified as a brownfield by a local, State, or Federal government agency.
fish and wildlife habitat conservation area: areas with which state or federally designated endangered, threatened, or sensitive species have a primary association.
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS15
Sustainable SitesMandatory Provisions
Reduce Heat Island Effect Site hardscape
• 50% to be shaded (within 5 years of planting), or be SRI 29, and/or shaded by structures
Walls• to be shaded on at least 30% of
east and west walls up to 20 feet above grade within 5 years
Roofs• (climate zones 1-3): 75% to be SRI
78 (low-slope), 29 (steep-slope) or cool roof
solar reflectance index (SRI): a measure of a constructed surface’s ability to reflect solar heat, as shown by a small temperature rise. A standard black surface (reflectance 0.05, emittance 0.90) is 0 and a standard white surface (reflectance 0.80, emittance 0.90) is 100.
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS16
Sustainable SitesMandatory Provisions
Reduction of Light Pollution Outdoor lighting lumen limits per
parking space, per ft2 of hardscape or per ft2 complete site (Standard 90.1 Addendum i)
Maximum allowable Backlight, Uplight and Glare (BUG) ratings for luminaires by lighting zone type
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS17
Sustainable SitesPrescriptive Options
Site Development All sites:
• Minimum 40% of site area to be effective pervious surface (vegetation, green roof, porous pavers) – exceptions for areas with <10 inches annual average rainfall
Greenfield sites:• Minimum 20% of area to be
native or adapted plants
greenfield site: a site of which 20% or less has been previously developed with impervious surfaces.
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS18
Sustainable SitesPerformance Option
Site Development Existing Building: minimum 20% Greyfield Sites: minimum 40% Brownfield Sites: minimum 40% All Other Sites: minimum 50%
greyfield site: a site of which more than 20% is already developed with impervious surfaces.
SS WE EE IEQ MR CO
of the average annual rainfall on the development footprint shall be managed through infiltration, reuse, or evapotranspiration
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS19
Water Use EfficiencyMandatory Provisions
Site Water Use Bio-diverse plantings, hydrozoning, &
smart irrigation controllers
Building Water Use Plumbing fixtures & fittings,
appliances, HVAC systems & equipment, generally 40% lower than U.S. EPAct 1992
Disallow once through cooling with potable water
Recover condensate from steam systems & A/C units > 65,000 BTU/h capacity SS WE EE IEQ MR CO
hydrozoning: to divide the landscape irrigation system into sections in order to regulate each zone’s water needs based on plant materials, soil and other factors.
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS20
Water Use EfficiencyMandatory Provisions
Water Metering Measurement devices with remote communication
capability shall be provided to collect water consumption data
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS21
Water Use EfficiencyMandatory Provisions
Water Metering
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS22
Water Use EfficiencyPrescriptive Option
Site Water Use Max 1/3 of improved landscape can be irrigated with
potable water
SS WE EE IEQ MR CO
Building Water Use Cooling towers
• <200 ppm hardness to have minimum 5 cycles of concentration• >200 ppm hardness to have minimum 3.5 cycles of
concentration Efficient commercial food service and laboratories
Special Water Features Fountain water must be from alternate source or reclaimed (no potable
water)
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS23
Water Use EfficiencyPerformance Option
Site Water Use proposed potable water for
irrigation < 35% of baseline evapotranspiration
Building Water Use proposed water use < mandatory
plus prescriptive
SS WE EE IEQ MR CO
evapotranspiration (ET): the sum of evaporation and plant transpiration. Evaporation accounts for the movement of water to the air from sources such as the soil, canopy interception, and water bodies. Transpiration accounts for the movement of water within a plant and the subsequent loss of water as vapor through stomata in its leaves.
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS24
Building Energy Codes
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS25
Energy Efficiency Highlights
More stringent than Standard 90.1-2007 Includes plug/process loads Electric peak load reduction Renewable energy provisions Energy measurement for verification
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS26
Energy EfficiencyMandatory Provisions
Meet 90.1 Mandatory Requirements Sections 5.4, 6.4, 7.4, 8.4, 9.4 and 10.4
SS WE EE IEQ MR CO
on-site renewable energy system: photovoltaic, solar thermal, geothermal energy, and wind systems used to generate energy and located on the building project.
Provide for future on-site renewable energy systems Building projects design shall show
allocated space and pathways for installation of on-site renewable energy systems
Minimum rating of 3.7 W/ft2 or 13 Btu/h/ft2multiplied by the total roof area
Exception for locations with poor incident solar radiation
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS27
Energy EfficiencyMandatory Provisions
Energy Consumption Measurement Measurement devices with remote
communication capability shall be provided to collect energy consumption data
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS28
Energy EfficiencyMandatory Provisions
Energy Consumption Measurement
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS29
Energy EfficiencyPrescriptive Option
On-site renewable energy systems Annual energy production equivalent
of 4 KBtu/ft2 of conditioned space Exception for areas with incident solar
radiation less than 1.36 kBtu/ft2-day and purchase of green power of at least 7 kWh/ft2 until cumulative purchase of 70 kWh/ft2
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS30
Energy EfficiencyPrescriptive Option
CZ-3 Building Envelope (IP) Roof Insulation
• 90.1 R- 20 c.i., R- 38 attic• 189.1 R- 25 c.i., R- 49 attic
Walls – Steel Framed• 90.1 R-13 cavity + R-3.8 c.i. • 189.1 R-13 cavity + R-5.0 c.i.
Walls – Mass• 90.1 R-7.6 c.i. • 189.1 R-9.5 c.i.
Continuous air barrier requirement
Little Rock, AR Non-Residential Example SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS31
Energy EfficiencyPrescriptive Option
CZ-3 Building Envelope (IP) Fenestration Assemblies
SS WE EE IEQ MR CO
90.1 189.1nonmetal frame U-0.65 U-0.45curtainwall U-0.60 U-0.50other metal U-0.65 U-0.55SHGC 0.25 0.25
Little Rock, AR Non-Residential Example
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS32
Energy EfficiencyPrescriptive Option
Building Envelope Vertical fenestration area < 40% of the gross wall area W, S & E permanent projections for vertical fenestration (climate zones 1-5)
Fenestration orientation (climate zones 1,2,3&4): (AN*SHGCN + AS*SHGCS) ≥ 1.1*(AE*SHGCE + AW*SHGCW)
SS WE EE IEQ MR CO
Projection Factor PF ≥ 0.5
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS33
Energy EfficiencyPrescriptive Option
Building Envelope Continuous air barrier requirement
• Using individual materials that have an air permeability ≤ 0.004 cfm/ft2
under a pressure differential of 0.3 in. W.C.
• Using assemblies of materials and components that have an average air leakage ≤ 0.04 cfm/ft2 under a pressure differential of 0.3 in. W.C.
• Testing the completed building and demonstrating that the air leakage rate of the building envelope ≤ 0.4 cfm/ft2 under a pressure differential of 0.3 in. W.C.
SS WE EE IEQ MR CO
continuous air barrier: the combination of interconnected materials, assemblies and flexible sealed joints and components of the building envelope that provide air-tightness to a specified permeability.
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS34
Energy EfficiencyPrescriptive Option
Mechanical Minimum equipment efficiencies –
either• Baseline is EPAct efficiencies
(Std 90.1) plus- 6 KBtu/ft2 renewable energy- 10% electrical peak load
reduction• Greater of Energy Star / Appendix
C equipment efficiencies- 4 KBtu/ft2 renewable energy- 5% electrical peak load
reduction
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS35
Energy EfficiencyPrescriptive Option
Mechanical Demand control ventilation for
densely occupied spaces Std 90.1 Seal Level A duct sealing Economizer cycle for units ≥ 33,000
Btu/h Fan power to be 10% less than
Std 90.1 Exhaust air energy recovery
SS WE EE IEQ MR CO
densely occupied space: those spaces with a design occupant density greater than or equal to 25 people per 1000 ft2
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS36
Energy EfficiencyPrescriptive Option
Lighting Interior lighting power to be 10% less
the 90.1-2007 lighting power density Occupancy sensor controls Occupancy sensor controls with multi-
level switching or dimming Lighting for building security or
emergency egress ≤ 0.1 W/ft2
Automatic controls for lighting in daylight zones
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS37
Energy EfficiencyPrescriptive Option
Other Equipment Motor efficiencies higher than Standard
90.1-2007 Supermarket waste heat recovery system
on permanently installed refrigeration equipment in supermarkets 25,000 ft2 or greater
Energy Star equipment and appliances if installed prior to issuance of certificate of occupancy
Commercial refrigerators, freezers and clothes washers to comply with Appendix C
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS38
Energy EfficiencyPerformance Option
Annual Energy Cost Proposed ≤ mandatory plus prescriptive Normative Appendix D – Performance option for energy efficiency
Annual Carbon Dioxide Equivalent (CO2e) Proposed ≤ mandatory plus prescriptive
Peak Electric Demand Proposed ≤ mandatory plus prescriptive Minimum annual load factor of 0.25
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS39
Indoor Environmental Quality (IEQ)
Indoor air quality Environmental tobacco smoke control Outdoor air delivery monitoring Thermal comfort Building entrances Acoustic control Daylighting Low emitting materials
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS40
Indoor Environmental QualityMandatory Provisions
Indoor Air Quality Ventilation rates per ASHRAE
Standard 62.1 Outdoor air flow rate monitoring of
minimum outside air MERV 8 filter (MERV 13 in PM2.5
non-attainment areas) Eliminate air bypass around filters No smoking inside building Building entrance entry mat system
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS41
Indoor Environmental QualityMandatory Provisions
Thermal Environmental Conditions Comply with ASHRAE Standard 55 Section 6.1 Design and 6.2
Documentation
Acoustical Control Defined STC values for exterior and interior assemblies
Daylighting by Toplighting (Skylights) Targeted for large enclosed spaces in buildings ≤ three stories
Soil Gas Retarder System Brownfields or radon
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS42
Indoor Environmental QualityPrescriptive Option
Daylighting by Sidelighting Office spaces and classrooms Minimum effective apertures Minimum interior surface visible light
reflectances Minimum shading projection factors
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS43
Indoor Environmental QualityPrescriptive Option
Materials Emissions and VOC requirements
• Adhesives and sealants• Paints and coatings• Floor covering materials• Composite wood and agrifiber
products• Office furniture systems and
seating• Ceiling and wall systems
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS44
Indoor Environmental QualityPerformance Option
Daylighting Physical or computer model, minimum
illuminance target: 30 fc (300 lux) on work surfaces, noon equinox
It shall be demonstrated that direct sun does not strike anywhere on a worksurface in any daylitspace for more than 20% of the occupied hours during an equinox day in regularly occupied office spaces
Materials VOC emissions model for building materials per
CA/DHS/EHLB/R-174 Section 4.3
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS45
The Building’s Impact on the AtmosphereMandatory Provisions
Construction waste management A minimum of 50% of non-hazardous construction and demolition
waste material shall be diverted Total waste on new building projects shall not exceed 42 cubic
yards or 12,000 lbs per 10,000 ft2 of new building area
Wood products Refrigerants Storage and collection of recyclables and
discarded goods
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS46
The Building’s Impact on the AtmospherePrescriptive Option
Reduced Impact Materials Post-consumer recycled content + one-half of the pre-consumer
recycled content ≥ 10% of the total materials in the building project, based on cost
≥ 5% of building materials used shall be bio-based products, based on cost
≥ 15% of building materials or products used shall be regionally extracted/harvested/recovered or manufactured within a radius of 500 miles of the project site, based on cost
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS47
The Building’s Impact on the AtmospherePerformance Option
Life Cycle Assessment ISO Standard 14044 – Environmental management -- Life cycle
assessment -- Requirements and guidelines Minimum of two building alternatives The building alternative chosen for the project shall have a 5%
improvement over the other building alternative in a minimum of two of the impact categories
Impact categories - land use (or habitat alteration), resource use, climate change, ozone layer depletion, human health effects, ecotoxicity, smog, acidification, and eutrophication
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS48
Construction and OperationMandatory Provisions
Plans for Construction Building Acceptance Testing
• Verify installation and start-up• Verify systems manual
Building Commissioning Erosion and Sediment Control IAQ Construction Management Moisture Control Construction Activity Pollution Prevention
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS49
Construction and OperationMandatory Provisions
Commissioning (> 5,000 ft2) Activities prior to building permit
• Designate commissioning authority• Owner Project Requirements• Basis of Design• Commissioning Plan
Activities prior to occupancy• Verify performance• Verify training• Commissioning report
Post-occupancy activities
SS WE EE IEQ MR CO
commissioning authority (CxA): An entity identified by the owner who leads, plans, schedules, and coordinates the commissioning team to implement the building commissioning process.
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS50
Construction and OperationMandatory Provisions
IAQ Construction Management Plan Air conveyance materials shall remain clean Post-construction, pre-occupancy flush-out
• Option A - 24-hr flush-out & baseline IAQ testing prior to occupancy
• Option B - Continuous flush-out
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS51
Construction and OperationMandatory Provisions
Plans for Operation High-Performance Building Operation
Plan• Site sustainability• Track and assess energy and water
use• Measurement & verification• Indoor air quality• Green cleaning
Maintenance plans
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS52
Construction and OperationMandatory Provisions
Energy Efficiency Plan for Operation Initial measurement & verification
• After acceptance testing is complete Track and assess energy consumption
• After 12 months but no later than 18 months after certificate of occupancy
• Energy usage reports (both consumption and demand)
• Energy Star Portfolio Manager to track performance
• Assess energy performance
verification: The process by which specific documents, components, equipment, assemblies, systems, and interfaces among systems are confirmed to comply with the criteria described in the owner’s project requirements.
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS53
Normative Appendices
Appendix A – Prescriptive Building Envelope Tables Appendix B – Prescriptive Continuous Air Barrier Appendix C – Prescriptive Equipment Efficiency Tables Appendix D – Performance Option for Energy Efficiency Appendix E – IAQ Limit Requirements for Office Furniture
Systems and Seating Appendix F – Building Concentrations
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS55
Integrative Project Team
SS WE EE IEQ MR CO
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS56
What is Your Best Path Forward?
Begin to understand the impact of these new requirements on your business and technical expertise
Identify what requisite skills and knowledge you will need once this standard and green codes are implemented
STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN BUILDINGS57
Further Information
Information on Standard 189.1: www.ashrae.org/greenstandard
ASHRAE Training on Standard 189.1 User Manual will be developed to assist in the
understanding in how to apply the standard