Stacking HUB 10.3 Quick Start Guide HUB 10 · identified by MATE3 on power-up: 3-Phase/Split...
Transcript of Stacking HUB 10.3 Quick Start Guide HUB 10 · identified by MATE3 on power-up: 3-Phase/Split...
#10 x ½” Screws x 2
Quick Start Guide
900-0154-01-00 Rev A.vsd\2013-03-13©2013 OutBack Power Technologies. All Rights Reserved.
HUB 10.3
HUB10.3 HUB Wiring CoverCable, CAT5e, 3' (1 m) x 2Cable, CAT5e, 6' (2 m) x 3
Parts List
Cable, CAT5e, 10' (3 m) x 4
Contact Technical Support:Telephone: +1.360.618.4363Email: [email protected]: www.outbackpower.com
IMPORTANT: Not intended for use with life support equipment.
OutBack Power, the OutBack Power Logo, and FLEXgrid are trademarks owned and used by OutBack Power Technologies, Inc. The ALPHA logo and the phrase “member of the Alpha Group” are trademarks owned and used by Alpha Technologies. These trademarks may be registered in the United States and other countries.
Stacking HUB 10.3
900-0154-01-00 Rev A.vsd\2013-03-13©2013 OutBack Power Technologies. All Rights Reserved.
Jumper position identified by MATE3 on power-up:
3-Phase/Split Single-Phase
3.
Changing Jumpers1. 2.
Used for classic series, OutBack series, and parallel stacking. This is the factory-installed initial position.
Used for Subphase Master stacking (both three-phase and series configurations).
4a.Single-phase(all jumpers)
4b.3-Phase/Split(all jumpers)
3.
2.
1.
1" recommended
Mounting
NOTE: This option requires MATE3 firmware revision 002.013.000 or higher.
Master A
Master C SlaveSlave
Slave Slave
or
X1st MATE
12
3
45
6
78
9
10
Three-Phase Stack (Subphase Master)Up to 9 inverters (ports 1 to 9); 1 other device (port 10); MATE3 onlyPorts 1, 4, and 7 are required regardless of the number of slaves; also, the number of slaves should be even
Jumpers must be in “3-Phase/Split” position
Rev 002.013.000 or higher
Port 1Stack Mode Master
Port 2Stack Mode Slave
orOB Slave L1
Port 4
Stack Mode B Phase Master or3p Classic B
Port 7
Stack Mode C Phase Masteror3p Classic C
Also ports 3, 5, 6, 8, and 9
1st
MATE
Xor
Port 1Stack Mode Master
Port 2Stack Mode 3phase OB Slave A
3phase OB Slave B3phase OB Slave C
Three-Phase StackUp to 9 inverters; 1 other device (MATE or MATE3)
10 9 8 7 6 5 4 3 2 1
Models
Ports 2 to 10 can be assigned any 3phase OB Slave stack mode;
no more than 3 inverters per mode Jumpers must be in “Single-phase” position
GTFX (E Series)
GVFX (E Series)
A
CBMaster B SlaveSlave
Back of HUB 10.3
10.63" (27 cm)
6.18" (15.7 cm)
1.27" (3.2 cm)
4.23" (10.7 cm)
9.24" (23.5 cm)
Dimensions
GS7048E
GFX
GFX (E Series)
Models
A
CB
Single-phase inverters:Three-phase output
PHASE A
PHASE B
PHASE C
Shutter Bushing x 2Snap Bushing x 2
or
Single-phase inverters:Three-phase output
Stacking HUB 10.3Stacking
10 9 8 7 6 5 4 3 2 1X
1st
MATE
FX / VFX (includes J, M, N Series)
ModelsPort 1
Stack Mode Master or 1-2phase Master
Port 2Stack Mode OB Slave L1
orOB Slave L2
Series Stack (OutBack)Up to 10 inverters or other devices (MATE or MATE3)Requires balancing transformer
HUB 10.3
Jumpers must be in “Single-phase” position
900-0154-01-00 Rev A.vsd\2013-03-13©2013 OutBack Power Technologies. All Rights Reserved.
900-0154-01-00 Rev A.vsd\2013-03-13©2013 OutBack Power Technologies. All Rights Reserved.
10 9 8 7 6 5 4 3 2 1X
1st
MATE
FX / VFX (includes J, M, N Series)
GTFX
GVFX
GTFX (LA Series)
GVFX (LA Series)
ModelsPort 1
Stack Mode Master or 1-2phase Master
Port 2
Stack Mode Classic Slave
Series Stack (Classic)2 inverters; up to 8 other devices (MATE or MATE3)
GFX
Jumpers must be in “Single-phase” position
10 9 8 7 6 5 4 3 2 1X
1st
MATE
GFXModels
Series Stack (Subphase Master) Up to 8 inverters (ports 1 to 4, 7 to 10); 2 other devices (ports 5, 6); MATE or MATE3No balancing transformer requiredImproves control of individual phase voltages and outputsPorts 2 to 4 are L1 slaves; ports 8 to 10 are L2 slaves despite the screen selection (OB Slave L1); equal inverters should be on L1 and L2Port 7 is the L2 subphase master despite the screen selection (Classic Slave); this port is required regardless of number of slaves
Jumpers must be in “3-Phase/Split” position
Port 1Stack Mode Master
Port 2Stack Mode OB Slave L1
Also ports 3, 4, 8, 9, and 10
Port 7Stack Mode Classic Slave
1st
MATE
Xor
Port 1
Stack Mode Master or 1-2phase Master
Port 2
Stack Mode Slave or OB Slave L1
Parallel StackUp to 10 inverters or other devices (MATE or MATE3 where appropriate)
10 9 8 7 6 5 4 3 2 1GS8048
ModelsFX / VFX (all series, including E, J, M, N, and W)
Also port 3, etc.Jumpers must be in
“Single-phase” position
GS7048E
GFX
GFX (E Series)
(with FX-class inverter)
or
or
Single-phase inverters:Single-phase output
Split-phase inverters:Split-phase output
GTFX (E Series)
GVFX (E Series)
Single-phase inverters:Split-phase output
Single-phase inverters:Split-phase output
Ports 2 to 10 can be assigned to either OB Slave L1 or OB Slave L2;
equal numbers of inverters should be assigned to each side
or
Single-phase inverters:Split-phase output