SPEL Products data manual - WhatDoTheyKnow
Transcript of SPEL Products data manual - WhatDoTheyKnow
SPEL Products data manual
Section 9SPEL Separator commissioning,operation and maintenance
SPEL Storrnceptor" class 1 and 2by-pass separators.
SPEL full retention class 2 separators.
SPEL Puraceptor" class 1 fullretention separators (single and twochamber models).
RESTRICTED
--------_ .._._-,
RESTRICTED
SPELStorrnceptor" by-pass separators
Maintenance
The SPEL Stormccptor" by-pass separator IS a well proven high quality factory made unit, designed and tested in accordance with the EuropeanStandard BS EN 858-1 and meets the requirements of the Environment Agency's Pollution Prevention Guidelines PPG3 and the ConstructionProducts Regulations.
SPEL Stormceptors are designed for long term peliormance and with SPEL high volume coalescer units, low maintenance.
SPEL Stormceptor by-pass separators are manufactured in class 1 and class 2 models and with or without silt capacity in accordance withBS EN 858-1. The range of models is listed in section 6 or on the SPEL Stormceptor selection chart - available on request.
Chamber 1 Junction chamber 2 Chamber 3
Flow according to nominal size (NSB)
The polluted surface water first enters the primarychamber where silt settles out and is retained. The fuel,oil and other pollutants lighter than water, rise to thesurface and are efficiently skimmed off and transferredto the separation chamber.
All flows within the nominal size pass through theseparation chamber, where the quiescent conditionsallow the pollutants to separate out efficiently. Waterfrom the cleanest zone in the separation chamberflows through a coalescer unit, to remove smallerglobules of oil, up to the junction chamber and thenceto the outlet.
Chamber 1 Junction chamber 2 Chamber 3
Storm flows above NSB
During a storm the level in the primary chamber risesand the storm water passes over the weir into thejunction chamber and to the outlet.
The design keeps the turbulence within the separationchamber to a minimum which avoids disturbing thecontaminants retained.
Maintenance requirements
The SPEL automatic alarm/monitoringsystem will automatically warn you when theSPEL Stormceptor requires emptying of lightliquids, however, silt will accumulate andrequire removing at intervals depending onthe site conditions.
We recommend the SPEL Stormceptor ischecked at 3,6 or 12 monthly intervalsto determine the depth of silt in theprimary chamber.
Where a SPEL automatic alarm/monitoringsystem is not fitted, the SPEL Stormceptorshould be checked at 3,6, 12 monthlyintervals, depending upon site conditions, todetermine the depth of retained pollutants.When the depth of light liquids retained hasreached the predetermined design level inaccordance with the European StandardBS EN 858-1, or if excessive silt hasaccumulated, it should be emptied.
Chamber 1
The inlet connects directly into chamber 1- the primary chamber where silt etc. isdeposited and light liquids are skimmedoff to be transferred to the main separationchamber, chamber 3.
Maintenance requires the removal ofaccumulated silt etc., checking the skim pipeis not blocked and removing floating debris.
Chamber 2
This is the junction chamber where the cleanwater passing out of the main separationchamber and the storm flow over the weirfrom the primary chamber meet and passto the outlet. This chamber is an approvedsampling point if samples are required foranalysis. As it is mainly clean water passingthrough the chamber, maintenance isconfined to checking the weir plate is freeof debris.
Chamber 3
The main separation chamber is where thelight liquids are retained and in the case ofclass 1 Stormceptors, where the coalescerunits are incorporated.
If coalescer units are incorporated, theseshould be removed and cleaned in accordancewith the requirements set out in Data SheetRef. 9.4 steps 1 to 5.
Retained light liquids should be removedfrom the top and any sediment from thebottom. Small Stormceptor by-pass separatorsgenerally need to be completely emptied.
SPEL automatic alarm/monitoring system
If a SPEL automatic alarm/monitoring systemis fitted this will automatically signal whenthe Stormceplor requires light liquids to beremoved. If this system is fitted see ref. 10.1and 10.2.
When emptying take care not to damage orshift the probe protection tube situated in theaccess shaft of chamber 3.
© SPELProducts, Lancaster Road, Shrewsbury, Shropshire, SY13NQ, England. T. +44 (0)1743 445200 E +44 (0)1743 465441 E. [email protected]
RESTRICTED
SPEL Stormceptcr" by-pass separators
Maintenance
SPEL Stormceptor class 1 by-passseparators 400, 500 & 600 series
A wide range of SPEL Stormceptor class 1by-pass separators is available incorporatingcoalescer unit/s for the larger catchment areas.
Manhole access 1
This is the access to the primary chamber forremoval of silt, the inspection of the skim pipeand clearing of any floating debris.
Manhole access 2
These provide access to the junction chamberwhich is suitable as a sampling point for thefinal discharge.
Manhole access 3 & 4 (larger models)
These provide access for the inspection,removal and reinsertion of the coalescer units.
Manhole access 5
Where manhole access is required formaintenance personnel to enter the separator,a minimum 750mm dia. manhole accessshaft is provided and where required, a GRPladder and stainless steel fittings.
The SPEL automatic alarm/monitoringsystem probe is generally situated at the baseof this access shaft. If system fitted see ref.10.1 and 10.2.
SPEL Econoskim light liquid skimming!separate containment system
For optimum performance and efficientlow cost maintenance for the larger SPELSeparators serving large and/or heavilypolluted catchment areas. If a SPELEconoskim system is fitted refer to the SPELData Manual, section 11.
Manhole 1
Manhole 2Junction chamberand sampling point
Manholes 3 and 4Access tocoalescer units Manhole 5
Skim pipe: check fordebris - keep dear
Handle withlocating/lockingbracket to guiderail system
SPEL automaticalarm/monitoring system
Coalescer unit
© SPEL Products, Lancaster Road, Shrewsbury, Shropshire, SYI 3NQ, England, T. + 44 (O)! 743445100 E +44 (O)! 743465441 E. [email protected]
RESTRICTED
SPEL full retention class 2 separators
These are generally single chamber units with a single, or in the caseof large separators two access shafts, to enable periodic removal ofpollutants and silt. An automatic closure device (ACD) is fitted andshould be checked that it is operating correctly. See ACD ref 9.5.
SPEL Puraceptor class 1 separators
The SPEL Puraceptor class 1 separator is available in single chamberor two chamber models.
Single chamber models (Figure 1)These incorporate a coalescer unit and an automatic closure devicetype 'R'. For maintenance see ref. 9.5.
Two chamber models (Figure 2)The maintenance procedure for the SPEL Puraceptor class 1 twochamber models is detailed on sheet ref. 9.4.
Maintenance requirements
The SPEL automatic alarm/monitoring system will automatically warnyou when the SPEL Separator requires emptying of light liquids.See ref. 10.1 and 10.2. However, silt will accumulate and requireremoving at intervals depending on the site conditions.
We recommend the SPEL Separator is checked at 3,6 or 12 monthlyintervals to determine the depth of silt in the primary chamber.
SPEL automatic
FUEUOIL
o 0 0 0 a0.. Q:: 0" •• Q 0.
0" 0 : ~ :·0 o •• 00 ••
• '00 0 (I .. (I.. 00 0'''''·0
WATER
Figure 2 Maximum light liquid depthwhen automatic valve is closed
Silt baffleplate
SPELfull retention class 2 and Puraceptor" class 1 separators
Maintenance
SPEL automaticalarm/monitoringsystem (supplied
when required)
Sampling pointwith screw cap
Delivery tube Coalescer unitfor automatic
closure device
Automaticclosure device
Where a SPEL automatic alarm/monitoring system is not fitted, theSPEL Separator should be checked at 3,6, 12 monthly intervals,depending upon site conditions, to determine the depth of retainedpollutants. When the depth of light liquids retained has reached thepredetermined design level in accordance with the European StandardBS EN 858-1, or if excessive silt has accumulated, it should be emptiedin accordance with the following procedures.
Light liquid/waterCoalescerretaining/liftinghandle
Automaticclosure device
Stainless steelcoalescer unit
© SPEL Products, Lancaster Road, Shrewsbury, Shropshire, SYJ 3NQ,England. I + 44 (0)1743 445200 f + 44 (0)1743465442 E. [email protected]
Figure 1
RESTRICTED
Maintenance
SPEL Puraceptor" class 1 separators FP2C and all two chamber models
Maintenance procedure
The SPEL automatic alarm/monitoringsystem will automatically warn you whenthe Puraceptor requires emptying. See ref.10.1 and 10.2. Where a SPEL automaticalarm/monitoring system is not fitted, SPELPuraceptors should be checked at three-,six- or twelve-monthly intervals dependingon site conditions, to determine the depth ofretained pollutants and silt in both chambersand the correct operating of the ACO(automatic closure device). When the depthof the oil/fuel retained has reached the pre-determined design level, in accordance withBS EN 858-1, it should be emptied.
Important Note.
When emptying, ensureboth chambers areemptied equally startingwith the oil retentionchamber and then thecoalescer chamber andback again until empty.
STEP 3STEP 6
Washing outfoam insert
Step 1: Sucking out oil/fuel and silt Step 5: Re-insert coalescer unit and ACO
Suck off the retained oil from both chambers ofthe Puraceptor and then the silt deposited onthe bottom, leaving sufficient water to ensurethe ACO remains floating.
Re-insert the foam insert into the stainlesssteel coalescer unit and re-insert the coalescerunit into the Puraceptor. Re-clip the wire ropeor location pin as provided with the SPELlifting/locating/locking system (see ref: 9.7).
Step 2: Coa lescer unitPartially fill the Puraceptor with clean waterto ensure the ACO when re-inserted remainsfloating. Check the ACO is not damaged andthe closure plate is clean. Re-insert the ACO.
Use the lifting handle or unclip the retaining clipfor the wire rope and lift the coalescer unit outof the tank and place ahead of the Puraceptor.
Step 3: Cleaning foam insertFinally check the ACO is floating and theretaining cap has been replaced to safeguardagainst its removal by unauthorised persons,unless depth of tank precludes doing so fromground level.
Remove foam insert and wash with normalwater pressure ensuring the dirty water runsinto the Puraceptor.
Step 4: Sucking out complete contents(if necessary)
If the quantity of pollutants exceedsrecommended levels, the complete contents
Step 6: SPEL automatic alarm/mon ito ring system
The SPEL automatic alarm/monitoring systemprobe should be lifted out of the probe
of the Puraceptor may need to be removed. protection tube, wiped clean and re-inserted.After sucking out completely, remove the ACO The system should now be reset accordingin the ACO retaining tube by first removing the to instructions. See ref. 10.1 and 10.2.retaining cap (this is to safeguard against theremoval of the float by unauthorised persons).Then, by means of a pole with a hook, liftout the ACO using the lifting eye on the float.Check the seating at the base of the retainingtube is free of debris/silt that could prevent theACO closing off in an emergency.
STEP 4(if necessary)
STEP 2 STEP 5STEP 1
Tanker desludging
WATER
Sampling pointo 0 0 0,,:O;;~:':'~~Mff:T!0fuV~j!.-;::
Oil retention chamber Coalescer unit Coalescer chamberBaffle
© SPELProducts, Lancaster Road, Shrewsbury, Shropshire, SY! 3NQ.England. T. +44 (0)1743445200 E +44 (0)1743465442 E. [email protected]
RESTRICTED
The purpose of the automatic closuredevice (ACD) is to close the separator offautomatically when the maximum storagecapacity of light liquid is attained.
The ACD is to ensure that in the event of amajor spillage, pollutants do not pass intothe drainage system; it should not be regardedas a substitute for an automatic alarm/monitoring system.
Prior to installation
Prior to installation the ACD retaining tubeshould be covered with polythene to preventingress of concrete etc., which would fall ontothe ACD and upset its calibration.
Operation and maintenance
If the tank should fill with light liquid the ACD,which is calibrated for a specific gravity of0.85, will automatically fall and close off theSPEL Puraceptor.
Normally routine maintenance would includeremoving light liquid intercepted withinthe Puraceptor. If a SPEL automatic alarm/monitoring system is incorporated, it willautomatically indicate when the Puraceptorshould be emptied. Only in an emergency willthe Puraceptor fill to its maximum and operatethe ACD.
In such an event the Puraceptor should becompletely sucked out and the ACD lifted out(see Maintenance Procedure - Ref: 9.4).
SPEL Puraceptor class 1 separatorstwo chamber models and full retentionclass 2 separators
Commissioning
After the tank has been installed, leave thewater in.
1. Remove the ACD from the packing box,taking care not to cause damage.
2. Remove the retaining cap from the top ofthe retaining tube in the separator.
3. Insert the ACD into the retaining tube usingthe lifting eye provided, ensuring it floatscorrectly with the float just visible abovethe water level.
4. Replace the retaining cap. This is tosafeguard against the removal of the floatby unauthorised persons or rising above thetube under abnormal conditions.
Note: If the tank's invert depth exceeds 1m it isadvisable to remove the retaining cap prior toinstallation and only replace after inserting theACD, if it is possible to do so from ground level.
SPEL Puraceptor class 1 separators singlechamber models
Models P004/l C to P050/l CSC.
Commissioning
After the tank has been installed, leave thewater in.
1. Remove the ACD from the packing box,taking care not to cause damage.
2. Remove the retaining cap from the top ofthe retaining tube in the separator.
3. Insert the ACD into the retaining tube usingthe lifting eye provided. Allow it to sink tothe bottom. The stainless steel retainingplate should seat on the base flange andthe ACD attain its operating position asshown in the open position.
4. Replace the retaining cap This is tosafeguard against the removal of the floatby unauthorised persons or rising above thetube under abnormal conditions.
Note: If the tank's invert depth exceeds 1m itis advisable to remove the retaining cap priorto installation and only replace after insertingthe ACD, if it is possible to do so fromground level.
Larger Models
Where the ACD is al ready positioned in theunit, proceed as follows:
1. Before putting any water in the tank,lift rope attached to ACD up to the nextknot and hang it from the rope hook. Thisis now in the 'operating position'.
2. As soon as the water level in the tank isabove the ACD, the rope must beremoved altogether and the rope hookmust be unbolted. Do not leave the ropehook attached to the shaft. Ensure theACD automatically remains in the'operating position'
3. Tape up or fill the hole(s) in the shaftwhere the rope hook was attached toprevent any backfill seeping into the shaft.
Maintenance
Dependent upon site conditions it is advisableto remove the ACD periodically taking carenot to raise it too quickly and damage theplastic/copper float. Clean from debris/silt toprevent premature closing. Check the seatingin the base unit is free of debris/silt that couldprevent proper closing in an emergency.
SPEL automatic closure device (ACO)
Automatic closure device Type F (Floating)SPEL Puraceptor class 1 separators (two chamber)& full retention class 2 separators.
Lockable retaining cap SIS lifting eye
l:i ,_.P'5""+~:=:!.9_11-------'
Initial operatingposition ofautomatic closuredevice(no oil present)
Water levelSIS lifting hook .,_ :.~<;:
"""ff'"
oo
.S: ...
Automatic closuredevice retaining tube
Automatic closure device(closed position)
Automatic closure device Type R (Retained)SPEL Puraceptor class 1 separator (single chamber),
+--I~·· ..·············..·..~ ACD closed position
c"/I ...- ........ _ Retaining stainlessr"""=!!j="",r---- steel plate
c·........·......---- ACD closed position~l__,''''% ....'" ....;,..!..''---_,__ ... Flow
© SPELProducts, Lancaster Road, Shrewsbury, Shropshire, SYI 3NQ,England. T. +44 (0)1743 445200 E +44 (0)1743 465442 E. [email protected]
RESTRICTED
! SPEL coalescer units - with handles
The SPEL Puraceptor class 1 separator and SPEL Stormceptor class 1 by-pass separatorsincorporate coalescer units. The coalescer units provide a coalescence process for the separationof smaller globules of light liquid pollutants before final discharge to the surface water drain.
Prior to Installation
1. Remove any strapping/ropes which havebeen used to hold the coalescer units fromshifting in transit.
2. The access shaft(s) above the coalescerunits should be covered with polythene toprevent ingress of concrete, dust, debrisetc. which could clog the foam inserts.
3. On completion of the installation, checkthat the coalescer unit is inserted securelyinto the base socket.
Stainless steel;::==~==t~~··-~~-~,,-~retaining clip
Extensionshaft
Lifting handle
Static waterlevel
Where wire ropes are fitted in place of thelifting, locating and locking system
Fig 1. The stainless steel wire rope lifting deviceswill be situated on top of the coalescer unitsand will have to be taken up out of the accessshaft(s) above. A small slit in the polythenewill allow you to pass the handles out.
Installation
During installation, it is important that thefoam inserts are not clogged with dust, debrisor drops of wet concrete. To safeguard againstthis, we recommend covering the access shaftwith a sheet of polythene, if not already covered.
Commissioning
On completion of installation, check thefoam insert is fitted inside the stainless steelcoalescer unit (Fig 2) and the coalescer unit isinserted securely into the base socket.
Maintenance
1. Lift handle and coalescer unit out of thetank and place ahead of the Puraceptor.
2. Remove foam insert and wash with normalwater pressure ensuring the dirty waterruns into the Puraceptor.
3. Re-insert the foam insert into the stainlesssteel coalescer unit (Fig 2) and re-insert thecoalescer unit into the Puraceptor.
1····--· __· Coalescerunit Lifting chains
Figure 1
Stainless steel wire rope lifting device to facilitate liftingcoalescer unit for maintenance. For 200/300 seriesseparators with deep inverts.
On heavily polluted sites silt and contaminantsmay build up in the coalescer unit foaminserts and add significantly to it's weight. It isrecommended that in this situation the largercoalescer units, NS40 and NS60, are fittedwith SPEL lifting chain sets (Fig 3) to suit thetank invert depth at ground level for safe liftingwith the SPEL tripod and hoist (see 9.8)
Two types ofcoalescer baskets,Left the NSB/15and right theNS30/40/60
Retaining bar
«Figure 2
Ensure the foam insert isfitted inside the stainlesssteel coalescer unitand secured under theretaining bar.
Retaining clip .. "B :=JExtension ~~~"_---,,
shaft
Static waterlevel
Coalescer unit ~~~--~--
© SPELProducts,LancasterRoad,Shrewsbury,Shropshire,SY13NQ,England.T. +44 (0)1743445200F. +44 (0)[email protected]
Figure 3
Coalescer unit withlifting chains.
RESTRICTED
locating/lockingbracket to guiderail system
Handle extension(optional extra withextension shafts)
Coalescer guiderail system
SPEL coalescer unit guide rail system/lifting,locating and locking system.
SPELcoalescer unit guide rail system/lifting, locating and locking system
SPEL coalescer unit guide rail system
This facilitates easy insertion and removal of coalescer units. The system is robust,manufactured throughout in stainless steel and the action positive, leaving no doubt thecoalescer unit is located properly.
Brackets fixed to the top and bottom of the coalescer unit simply engage the stainless steel guiderail fixed to the top of the stub access shaft. The coalescer is then lowered in the normal way,being guided at the correct angle into the conical base unit which finally locates the coalescerunit into its final position.
Extension guide rails can be incorporated into SPEL extension shafts to suit (preferably whenordered with the separator).
SPEL coalescer unit lifting/locating/locking system for positive location andsecurity locking
SPEL coalescer units lowered into theseparator with the SPEL guide rail systemare easily guided into the base unit's conicalmoulding to automatically seat correctly.
However, when the separator is full of water,debris or sludge accumulated over a periodcould prevent the coalescer unit fromre-seating correctly after servicing.
The coalescer unit lifting/locating/lockingsystem ensures the coalescer unit is seatedcorrectly and can be locked into position toprevent tampering.
The system is particularly suitable in SPELSeparator + Econoskim systems where thetotal contents of the separator are not emptiedon servicing.
The system comprises a robust stainless steellifting and lowering handle that locates on theguide rail system. When the coalescer unitis correctly located in the conical seating inthe separator the handle will align with guiderail top bracket ie. the handles slotted holeswith the top bracket clip locking groove, seediagram. When aligned the stainless steel clipcan be located through the slots and lock intoposition on the top bracket.
The stainless steel lifting handle can be extendedto suit deep tank inverts and provide easyaccess for lifting manually or with the SPELtripod and hoist utilising the lifting hook.
Guide rail Stainless steel clip Handle
© SPEL Products, lancaster Road, Shrewsbury, Shropshire, SYI 3NQ,England. T. + 44 (0)1743 445200 F. + 44 (0)1743 41>5442 E. [email protected]
RESTRICTED
i SPEL tripod and hoist
For maintenance of coalescer units and pumps
SPEL tripod and hoist Health & safety
Where surface water run-off has a high siltcontent the coalescer units can become filled,making them heavy to lift out. In order tofacilitate easy withdrawal of coalescer unitsthe SPEL tripod & hoist is recommended.
The HSE state that all equipment used forthe health and safety of people at work shouldbe periodically examined and tested in linewith the manufacturer's recommendations.Safe working load is 200kg.
A stainless steel lifting hook is included forautomatically engaging the coalescer unit,even under water. This enables coalescerunits to be lifted out safely from ground level.
Note: The SPEL tripod and hoist can be usedfor servicing pumps incorporated in SPELpackage pumping stations.
Service & maintenance
For service and maintenance contact SPELon +44 (0)1743 445200.
SPEL tripodand hoist
Sampling point extended byremoving blanking cap,
fitting double socket andextension pipe (!10mm dial.
Refitting blanking cap Extension shaftaccess
Guide rail system (extended)
© SPELProducts, Lancaster Road,Shrewsbury,Shropshire, SYI 3NQ, England. T. + 44 (0)1743 445200 E +44 (0)1743 465442 [email protected]
RESTRICTED
For maintenance of coalescer units
SPEL tripod and hoist
SPEL tripod and hoist used in conjunction withthe SPEL coalescer unit lifting/locating/locking system
Step 1&2 - Snap the 'lifting hook' onto the SPEL lifting! Step 3 - Lower the 'liftinglocating/locking system handle shaft. hook' down the shaft to
the bottom bracket.
Step 4 - Swivel the hoistchain until the 'liftinghook' is at 90° to thebottom bracket, allowingit to pass the lifting hookswelded each side of thebottom bracket.
Step 7 - Raise thecoalescer unit.
Step 5 - Once passedthe lifting hooks, swivelthe 'lifting hook' through90' to allow it to saddlethe bottom bracket andposition itself under thelifting hooks.
Step 8 - As the coalescerunit rises, steer the liftinghandle past the tripodhead and hoist to allowcontinued lifting of thecoalescer unit.
Step 6 - Raise thelifting chain to engagethe 'lifting hook' withthe lifting hooks on thebottom bracket.
Step 9 - Once thecoalescer unit is aboveground level, swing it toone side of the manholefor maintenance.
© SPEL Products, Lancaster Road, Shrewsbury, Shropshire, SY13NQ, England. T. + 44 (0)1 743 44!i100 F. + 44 (0)1743 465442 E. [email protected]
RESTRICTED