SPECIALISING IN THE SUPERVISION AND ... - Eden Transformer Oil · On-site purification avoids costs...

4
TRANSFORMER OIL PURIFICATION 1 Regent Business Centre, Revenge Road, Chatham, Kent, ME5 8UD Local Rate Tel. 0844 335 0877 | www.edenoil.co.uk | [email protected] SPECIALISING IN THE SUPERVISION AND MAINTENANCE OF ELECTRICAL OILS SINCE 1985 To ensure a site is in compliance with the Electricity at Work Regulations 1989 (EAWR) and its insurance obligations transformers should be inspected and sampled according to BS EN 60475:2011 and the liquids analysed against their specific British Standard. When an insulating liquid fails to meet the defined specifications engineers are left with just two options; change the insulating liquid or, if the liquid has not turned acidic, apply on-site purification. On-site purification has a number of advantages over an oil change:- Higher specification oil Reduced costs Reduced downtime – if any Elimination of virgin products Elimination of waste products WHY USE PURIFICATION

Transcript of SPECIALISING IN THE SUPERVISION AND ... - Eden Transformer Oil · On-site purification avoids costs...

Page 1: SPECIALISING IN THE SUPERVISION AND ... - Eden Transformer Oil · On-site purification avoids costs of new oil and waste disposal. The oil change of a typical 2MVA mineral oil site

TRANSFORMEROIL PURIFICATION

1 Regent Business Centre, Revenge Road, Chatham, Kent, ME5 8UD

Local Rate Tel. 0844 335 0877 | www.edenoil.co.uk | [email protected]

SPECIALISING IN THE SUPERVISION AND MAINTENANCE OF ELECTRICAL OILS SINCE 1985

To ensure a site is in compliance with the Electricity at Work Regulations 1989 (EAWR) and its insurance obligations transformers should be inspected and sampled according to BS EN 60475:2011 and the liquids analysed against their specific British Standard.

When an insulating liquid fails to meet the defined specifications engineers are left with just two options; change the insulating liquid or, if the liquid has not turned acidic, apply on-site purification.

On-site purification has a number of advantages over an oil change:-

Higher specification oil

Reduced costs

Reduced downtime – if any

Elimination of virgin products

Elimination of waste products

WHY USE PURIFICATION

Page 2: SPECIALISING IN THE SUPERVISION AND ... - Eden Transformer Oil · On-site purification avoids costs of new oil and waste disposal. The oil change of a typical 2MVA mineral oil site

SPECIALISING IN THE SUPERVISION AND MAINTENANCE OF ELECTRICAL OILS SINCE 1985

Using mineral oil as a working example, oil in service is permitted to contain up to 30 mg/Kg moisture in order to meet the requirements of ‘Good Condition’ by BS EN 60422:2013.

On-site purification avoids costs of new oil and waste disposal.

The oil change of a typical 2MVA mineral oil site transformer by a maintenance company will be in excess of £3,570.00+VAT, whereas Eden’s on-site purification results in a higher specification oil at just 52%. MIDEL 7131 changes for a 2MVA transformer will typically cost in excess of £10,500+VAT.

A MIDEL 7131 filled transformer will increase the oil change cost by £6,665.00+VAT.

SPECIFICATION OF INSULATING LIQUID

Typically on-site purification will achieve moisture levels below 10 mg/ Kg and dielectric strength in excess of 75kV.

It should also be noted that the specification for new oil in a drum (BS EN 60296:2012) need only be a low as 40mg/Kg and some suppliers will achieve only that and the oil needs pre-processing.

COMPARATIVE SPECIFICATION

COMPARATIVE COSTS

Many transformers can be purified whilst live and underload, live working actually aids the purification process.

Simple OilReplacement

On-site Treatment

100%

52%

0

20

40

60

80

100

Comparative Costs

40

30

20

10

0New Oil in drums

BS EN 60296:2012Oil in Equipment

BS EN 60422:2013Eden On-site

treatment

Permitted Moisture Content (mg/Kg)

40mg/Kg <30mg/Kg

<10mg/Kg

Eden On-sitetreatment

Permitted Moisture Content (mg/Kg)

Comparative Costs

Page 3: SPECIALISING IN THE SUPERVISION AND ... - Eden Transformer Oil · On-site purification avoids costs of new oil and waste disposal. The oil change of a typical 2MVA mineral oil site

SUPPORTING TRANSFORMER REPAIRSEden are regularly called upon to work alongside high voltage engineers in the repair of transformers such as tap-changer replacements, failed drain valves and general leaks.

In these works Eden can provide work shelter and lifting equipment and. If required we can, subcontract engineers to prove a turnkey solution.

1 Regent Business Centre, Revenge Road, Chatham, Kent, ME5 8UD

Local Rate Tel. 0844 335 0877 | www.edenoil.co.uk | [email protected]

ON-SITE PURIFICATION IN HARD TO REACH PLACESUnfortunately not all electrical planners factor in the supervision and maintenance of transformers, or compromises must be made when fitting out older properties.

To meet these challenges Eden has invested in a range of purification plants to access the most inaccessible place from basements, to roof tops via fire escapes or cranes to offshore platforms.

Page 4: SPECIALISING IN THE SUPERVISION AND ... - Eden Transformer Oil · On-site purification avoids costs of new oil and waste disposal. The oil change of a typical 2MVA mineral oil site

Eden was formed by Alan Denbow and Eddie Gregory in August 1985.

Former employees of Burmah Castrol, they realised that the vast majority of electrical engineers were simply replacing expensive transformer oil without fully appreciating the additional technical benefits of purification to the electrical equipment, and that Eden could achieve a more convenient solution at a significantly lower cost.

In more recent years the treatment of transformer oil is the first choice for a cost effective and efficient maintenance program: the increasing cost of new oil, the importance of productivity and equipment downtime, coupled with the environmental benefits of avoiding the transportation of hazardous waste and use of virgin products, are all part of the equation.

As well as providing on-site transformer oil treatment, if needed, Eden can supply and install new or reconditioned insulating liquid and provide all of the on and off site sampling and analysis to ensure transformers are supervised and maintained according to British Standards (BS EN 60422:2013) and insurance underwriters requirements.

SPECIALISING IN THE SUPERVISION AND MAINTENANCE OF ELECTRICAL OILS SINCE 1985

1 Regent Business Centre, Revenge Road, Chatham, Kent, ME5 8UD

Local Rate Tel. 0844 335 0877 | www.edenoil.co.uk | [email protected]

Company Registration Number: 05094065

VAT Number: 426 7570 36

Waste Carrier License: CBDU1214230

Waste Storage Permit : EPR/BB3506LF

ABOUT US

Our online store is ideal for customers requiring smaller quantities of insulating liquids, desiccant breathers, spill kits and other regularly used consumables. All of our products are sourced in the UK and used on site every day by Eden staff, so they are tried and tested in the field.