Special Requirements of IEEE C37.013 for Generator Circuit ... · PDF fileGenerator Circuit...
-
Upload
nguyenmien -
Category
Documents
-
view
265 -
download
7
Transcript of Special Requirements of IEEE C37.013 for Generator Circuit ... · PDF fileGenerator Circuit...
Schutzvermerk / Copyright-Vermerk
November 20, 2009
Sector Energy, Business Unit Medium Voltage© Siemens AG 2009
Special Requirements of IEEE C37.013 for Generator Circuit BreakerApplications
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 2
Generator Circuit Breaker Applications
What is different about generator circuit breakers?
Applicable standards Special considerations Vacuum versus SF6 technology Questions.
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 3
Generator and Distribution Circuit Breakers
Generator circuit breaker Distribution circuit breaker
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 4
Circuit Breakers for DistributionRequirements
Standards:IEEE C37.04 Rating structure for HV circuit breakersIEEE C37.09 Tests for HV circuit breakersIEEE C37.10 Application guide for HV circuit breakers.
X/R ratio: 17 (60 Hz).
Time constant of dc decay: 45 ms.
TRV typical values (15 kV, class S1 cable):Peak voltage (uc) = 25.7 kVTime-to-peak (t3) = 66 µsRRRV 0.39 kV/µs.
Duty cycle: O – t’ – CO – t – CO t’ = 0.3 s for reclosing / 15 s for non-reclosing
t = 3 minutes.
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 5
Circuit Breakers for GenerationRequirements
Standards:IEEE C37.013 Generator circuit breaker.
X/R ratio: 50 (60 Hz).
Time constant of dc decay: 133 ms.
TRV typical values (15 kV, 100 MVA machine):Peak voltage (E2) = 1.84 V = 1.84 x 15.0 = 27.6 kVTime-to-peak (T2) = 0.62 V = 0.62 x 15.0 = 9.3 µsRRRV 3.5 kV/µs.
Duty cycle: CO – 30 min – CO.
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 6
IEEEC37.04 for distribution circuit breakers expresses TRV in terms harmonized with IEC with peak voltage uc, and time-to-peak t3.
IEEE C37.013 still uses old TRV expressions with peak voltage E2 and time-to-peak T2. Peak voltage is not changed, but t3 is approximately 0.88 x T2.
The physics are not changed, just the representation.
Notes on TRV Representation
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 7
IEEE C37.04-1999 Scope
IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers
1. Scope
This standard establishes a symmetrical current rating structure and construction requirements for all indoor and outdoor types of ac high-voltage circuit breakers rated above 1000 V. It is only applicable to three-pole circuit breakers used in three-phase systems and single-pole circuit breakers used in single-phase systems.
This standard does not cover circuit breakers used at frequencies other than 50 Hz or 60 Hz, or generator circuit breakers that are covered in IEEE Standard C37.013-1997.
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 8
IEEE C37.013-1997 Scope
IEEE Standard for AC High-Voltage Generator Circuit Breakers Rated on a Symmetrical Current Basis
1. Scope
This standard applies to all ac high-voltage generator circuit breakers rated on a symmetrical current basis that are installed between the generator and the transformer terminals...
Note: Since no other national or international standard on generator circuit breakers exists, this standard is used worldwide.
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 9
IEEE C37.013 – the International Standard for Generator Circuit Breakers
IEEE C37.013 Revision PAR (Project) PAR approved by IEEE-SA
Standards Board, March, 2009 Joint development with IEC SC 17A
(HV Switchgear and Controlgear) IEEE WG chair is convenor (WG chair) of
IEC working group.
IEC has no standard for a generator circuit breaker. The IEEE and IEC intent has been that IEEE C37.013 would be the global standard.
IEC SC 17A WG 52 WG scope: Joint IEC/IEEE revision of
IEEE C37.013: IEEE Standard for AC High- Voltage Generator Circuit Breakers Rated on a Symmetrical Current Basis
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 10
X/R = 17, τ = 45 ms X/R = 50, τ = 133 ms
X/R Ratio Determines %dc Component
%dc vs Contact Part for X/R = 17 and X/R = 50
0.0
20.0
40.0
60.0
80.0
100.0
120.0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
Contact Part time (ms)
%dc
Com
pone
nt
X/R = 17X/R = 50
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 11
X/R Ratio Effect on Asymmetrical InterruptingX/R Ratio Effect on Asymmetrical Interrupting
-2.00
-1.50
-1.00
-0.50
0.00
0.50
1.00
1.50
2.00
2.50
3.000
180
360
540
720
900
1080
1260
1440
1620
1800
1980
2160
2340
2520
2700
2880
3060
3240
3420
3600
Time (in degrees)
Cur
rent
(Isc
= 1
.00)
Instantaneous (total) current
dc component
S-factor (C37.04-1979)
dc component (in decimal form) (multiply by 100 for %dc component) (C37.04-1999)
Symmetrical current (ac component)
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 12
X/R Ratio Effect on Asymmetrical Interrupting
S factor (from IEEE C37.04-1979)Ratio of rms asymmetrical current to rms symmetrical current
Assume contact part time of 55 ms, and 50 kA symmetrical current
X/R = 17 %dc = 29.5 S = 1.084 I = 54.2 kA
X/R = 50 %dc = 66.1 S = 1.369 I = 68.5 kAover 26% higher
)100/(%21 dcI
IS
lsymmetrica
total +==
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 13
Short-Circuit Currents
Consider system shown:
Transformer1,000 A full load (self-cooled)impedance = 10%
Generator1,000 A full loadXd’’ (subtransient reactance) = 20%
For fault at F2, circuit breaker sees transformer fault current, roughly 1,000 A / 0.10 = 10 kA
For fault at F1, circuit breaker sees generator fault current, roughly 1,000 A / 0.20 = 5 kA
Note: Fault current for generator source fault is only about 50% of fault current for system (transformer) source fault
F1
F2
G
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 14
Generator Circuit Breaker Ratings
32.24.5 / 4.5 / 4.51.4 / 1.8 / 1.8
27.63.5 / 4.51.6 / 1.8
kVkV/µskV/µs
TRV parameters Peak voltage (1.84 V) RRRV transformer source RRRV generator source
30 / 30 / 3040 / 30msDelayed current zero*
75 / 65 / 6573 / 61%%dc component
50 / 63 / 7225 / 31.5 / 36
40 / 6320 / 31.5
kAkA
Short-circuit current Transformer source Generator source
50 / 11038 / 95kV/kVDielectric 60 Hz / BIL
17.515.0kVMaximum voltage
Fixed-Mounted
Drawout (Metal-Clad)
UnitCharacteristic
* Higher values may be available
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 15
Generator Circuit Breakers
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 16
Generator Circuit Breakers
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 17
Out-of-Phase Switching
Circuit Breakers for Standard Applications:
IEEE C37.04 (clause 5.12):
Out-of-phase switching is optional, not required for general purpose circuit breakersIf a rating is assigned, the preferred rating is 25% of the rated symmetrical interrupting rating, with recovery voltage of (250% rated voltage / 1.732).Therefore, out-of-phase ratings are not typically assigned to general purpose circuit breakers rated per IEEE C37.04 and tested to IEEE C37.09.
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 18
Out-of-Phase Switching
Circuit Breakers for Generator Switching Applications:
IEEE C37.013 (clause 6.2.9):
Out-of-phase switching is optional, not required for generator circuit breakersIf a rating is assigned, the assigned rating is shall be 50% of the rated symmetrical interrupting rating (transformer or system source).Out-of-phase switching recovery voltage values are based on a maximum out-of-phase condition of 90 degrees between generator and system. This is reasonable as more extreme angles would result in damage to the machine.The likelihood of out-of-phase switching is influenced by generator inertia, i.e., low-inertia machines are more likely to be subject to out-of-phase switching conditions. Generator circuit breakers should have an assigned out-of-phase switching rating.
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 19
Other Differences
Reclosing:Reclosing duty not required for generator circuit breakers.
Short-time current duration:Normal circuit breakers
3 seconds (metal-clad switchgear = 2 seconds)Generator circuit breakers
1.0 second (typically test to 3 seconds).
Closing & latching rating:Normal circuit breakers
Peak current 260% of symmetrical short-circuit (60 Hz)With X/R = 17, “real” peak is 259.3%
Generator circuit breakersPeak current 274% of symmetrical short-circuit (60 Hz)With X/R = 50, “real” peak is 274.2%.
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 20
Delayed Current Zero Example – C37.013
-4.000
-3.500
-3.000
-2.500
-2.000
-1.500
-1.000
-0.500
0.000
0.5000 10 20 30 40 50 60 70 80 90 10
0
110
120
130
140
150
160
Time (ms)
Curr
ent (
uniti
zed)
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 21
Delayed Zero Test Example
20.6 ms 30.0 ms
40.1 ms 57.7 ms
Sector Energy, Business Unit Medium Voltage
© Siemens AG 2009November 09Folie 22
Generator Circuit Breaker Technologies
VacuumWell-suited to smaller units (up to 6,000 A or so)
Most economic for small units
Derived from proven distribution unit operators and interrupters
High experience-base
Very low arc voltage (20 - 50 V)Little affect on X/R ratioLower arc voltage = less arc energy = lower contact erosion
Extremely rapid recovery of dielectric strength between contacts after interruption – good for extreme TRV levels
SF6Only option for very large units
VERY expensive
Unlike distribution products
Lower experience-base
SF6 low arc voltage (several 100 V)Somewhat higher impact on X/R ratioHigher arc voltage = higher arc energy = greater contact erosion
Less able to cope with high TRV levels