MEDIUM VOLTAGE CE-B METAL CLAD
SWITCHBOARDS
CE - B - C - en - REV.00 2015.6 32
MEDIUM VOLTAGE CE-B METAL CLADSWITCHBOARDS
AP
PLI
CA
TIO
NS
TAN
DA
RD
CE-B Metal Clad switchboards
family are designed for use in public
and industrial distribution system
up to 40,5kV for the operation and
protection of lines, generators,
transformers, motors, capacitor
banks. The switchboards are
composed combining the various
typical standard cubicles.
IEC 62271-200 International standard
IEC 60-298 (replaced by IEC 62271-200)
DPR 547 Italian accident prevention Standard
IEC 60129 Earthing switches
IEC 60694 High voltage switchgear
IEC 62271-1
IEC 62271 - 100 Circuit breakers
IEEE C37.013 Generator breakers
IEEE C37.04 - C37.06 - C37.09 Circuit breakers
UL / CSA field evaluation on request.
These switchboards have performed all relevant
type tests carried out by qualified laboratories.
Utilities and Power Plants• Power Stations
• Generator switchgear
• Transformer stations
• Main and auxiliary switchboards
Industry• Metallurgy
• Pulp and Paper
• Cement
• Chemical
• Rolling mills
• Automotive
• Petrochemical
• Oil and gas
Marine applications• Drilling platforms
• Off-shore oil rigs
• Ferries and ships
Services• Hospitals
• Infrastructures
• Data center
Transports• Airports
• Ports
• Railways
TY
PIC
AL
US
ES
The company is qualified to supply standard ENEL type units.
MEDIUM VOLTAGE CE-B METAL CLADSWITCHBOARDS
CE - B - C - en - REV.00 2015.6
General CharacteristicsAccording to the international standard IEC 62271-200
the CE-B switchboards are classified for “loss of service
continuity category” as LSC2B.
The optional version CE-BA is foreseen fully withstanding to
internal arc fault:
• Internal arc classification (IAC)
• Accessibility type:
A (restricted to authorized personnel only)
F (Front)
L (Lateral)
R ( Rear)
Mechanical characteristicsEnclosure: Under normal operation the degree of protection
is of IP 31 for metal enclosure and IP2X in the LV instrument
compartment.
The individual structures are made of die-bended galvanized
sheet steel elements of no less than 2 mm thickness.
The external coloured panels are realized with carbon steel
painted with electrostatic epoxy powder, the standard
colour is light grey RAL 7035 smooth (all RAL scale colours
or specific colours can be realized on request). Standard
painting minimum thickness of 60 +/- 10 microns is
guaranteed.
Structure: all structural parts are solidly fastened together by
special screws ensuring a good electrical contact between
the connected parts.
Nuts and bolts used to assemble structure and enclosure
are galvanized and passivated with minimum thickness of
12 microns.
Earthing Circuit-breaker: earthing of circuit-breaker is ensured on
the whole isolating stroke by means of a sliding jaw type
contact on the copper conductor which is directly connected
with the earthing bus-bar.
Components: all main components such as CTs, VTs, etc.,
are positively earthed.
Doors: are connected to the frame by a 25 mmq. cross
section flexible braids.
Earthing bus-bar: the earthing bus-bar in copper with a
normal 350 mmq. cross section runs along the length of the
switchboard, thus ensuring maximum safety for personnel
and equipment.
Access and limited overall dimensions: the overall dimensions are particularly restricted if compared
with the high performances achieved for the insulation level,
rated busbars current and short-circuit current.
Optionally only front access could be required for installation
and maintenance.
Versatility and flexibility: any single line
diagram can be realized to meet the most various technical
requirements. Special and customized adaptation units
allow easy extension of existing switchboards even supplied
by other manifacturers or not yet in production.
Maximum service reliability: reinforced
insulation of all live parts minimizes the occurrence of faults
between phases or to earth. The various compartments of
each cubicle are fully segregated and can, besides, be simply
and rapidly inspected. As a matter of fact, equipment such as
circuit-breakers, instrument transformers and terminals are
readily accessible for inspection and maintenance purposes.
Easy inspection and maintenance: through easy access to the equipment in the various
compartments by hinged doors or removable bolted panels
and through the isolation and withdrawal on truck of circuit-
breakers, VT, fuses.
Easy installation and connection: the
cubicles are factory assembled and tested before being
shipped to site, therefore they only need to be secured to the
floor, coupled together and connected to the external circuits.
Personnel safety ensured by:
• positive earthing on the entire switchboard structure
• earthing of circuit-breaker frame throughout racking-in or
withdrawing operations;
• metal shutters automatically operated during circuit
breaker truck movement;
• metal shutters automatically operated during VTs truck movement
if foreseen Optional ;
• insulating protections and coatings are available for live
parts;
• easy access to low voltage apparatus and control wirings
without any risk of accidental contact with medium voltage
parts;
• set of mechanical and electromechanical interlocks;
• various signalling and control devices.
No fire risk: metal partitions of compartments and use
of self-estinguishing insulating material prevent fires from spreading.
Normal Service Conditions:• Maximum ambient temperature C° +40
• Minimum ambient temperature C° -5
• Height m a.s.l. ≤ 1000
• Maximum relative humidity % 95
Standard routine factory tests:• Visual inspection and check.
• Mechanical sequence operations.
• Wiring check.
• Electrical sequence operations.
• Insulation and Dielectric Tests.
FEATURES
54
MEDIUM VOLTAGE CE-B METAL CLADSWITCHBOARDS
CE - B - C - en - REV.00 2015.6
A Instrument compartmentAll the low voltage equipment can be housed in the instrument
compartment, which is usually placed above the circuit-
breaker compartment
B Circuit-breaker compartmentThis compartment is designed to accommodate the circuit-
breaker, contactor or link complete of its withdrawable truck
and all mechanical parts required for the extraction.
The device is provided with auxiliary switches for signalling
the “connected position” and “disconnected/test position”.
C Feeder compartmentThe feeder compartment, accessible from the rear of the
cubicle by removing the panel or by opening the eventual door.
D Busbar compartmentThis compartment contains the main bus-bars which are
directly supported by the lower fixed isolating contacts of the
circuit-breakers and isolator supports fixed on the structure.
E Wiring duct for interconnectionsOn the cubicle roof front side, a wiring duct is provided to hold the
auxiliary connections between the various cubicles and towards
the external installation.
F Voltage transformer compartment (VT compartment)This compartment can contain the VTs and related fuses, it
can be provided in fixed or drawout version.
The drawout compartment version, allows an easy
replacement , with the switchboard out of service.
The optional version of drawout compartment, is equipped
with insulated bushing and shutter from feeder compartment
and this, it allows the replacement of VTs and fuses in safety
condition even with the switchboard in service.
This compartment can be provided on all unit configuration
CONSTRUCTION SAFETY INTERLOCKS
(incoming, outgoing and bus tie).
The drawer could be provided with auxiliary end switches for
signalling the position of drawer, extracted / inserted
G Earthing switchThe unit can be equipped with Casagrande Elettrocostruzioni
“CE-SEZ” earthing switch. The switch is activated with an high
speed rotating snap, sized to conduct the rated short circuit
making current when close to under load. The speed of the
snap action closing operation is independent of controls.
A manual switch operating lever is provided on the front of the switchbord.
The device is provided with auxiliary switches for signalling the
open and closed positions.
H Gas exhaust duct (Optional)The gas exhaust duct, positioned on the top of the cubicles,
collects and ejects outside the safety area the gas resulting by
the eventual internal arc fault.
Earthing switch• Mechanical key lock to prevent the earthing switch closing
if the circuit-breaker is in connected position
On the circuit-breaker• Mechanical lock to prevent the connection or disconnection
of the circuit breaker when closed
• Mechanical key lock to prevent the circuit breaker
connection when the earthing switch is in closed position.
• Mechanical lock to prevent the disconnection of auxiliary
connector with circuit breaker in connected position if the
door lock option is not present.
• Mechanical lock to prevent the manual opening of the
shutters when the circuit breaker is removed from the
compartment. The shutters can only be operated by the
circuit breaker truck.
• Mechanical protection (IP20) form live parts even with door
open is always maintained with circuit breaker in connected
and disconnected position.
76
MEDIUM VOLTAGE CE-B METAL CLADSWITCHBOARDS
CE - B - C - en - REV.00 2015.6
Rated voltage kV 12 17,5 24
Rated power frequency withstand voltage (1min) kV 28 38 50
Rated lightning impulse withstand voltage kV 75 95 125
Rated frequency Hz 50/60 50/60 50/60
Rated short-time withstand current (3 sec) kA 50 50 40
Peak current kA 125 125 100
Internal arc withstand current IAC-AFLR (1sec)* kA 50 50 40
Rated current max. A 3150 3150 2500
Rated current with forced ventilation ** max. A 4000 4000 4000
Rated current with two breakers in parallel ** max. A 5000 5000 4000
Rated voltage 12KV 17,5KV 24KV
Depth (mm) 1625 1860 2000
Height (mm) 2325 2325 2325
Height (mm) - IAC 2780 2780 2780
Width (mm) 600 ÷ 1000 700 ÷ 1000 700 ÷ 1000
Rated current up to (A) 630 ÷ 4000 1600 4000 1600 2500
Note * Internal arc withstanding in option ** Type tested
CE-B VERSION UP TO 24 kV
Electrical Data
Dimensions could be affected by specific equipment and configuration.
D
H H HE E E
D D D
A A A
B B
F F
F
FC C
G G G
98
MEDIUM VOLTAGE CE-B METAL CLADSWITCHBOARDS
CE - B - C - en - REV.00 2015.6
CE-BP VERSION UP TO 24 kV
Rated voltage 12 kV 17,5 kV 24 kV
Depth (mm) 1450 1450 1450
Depth (mm) IAC 1600 1600 1600
Height (mm) IAC > to 25 kA 2628 2628 2628
Height (mm) IAC up to 25 kA 2329 2329 2329
Width (mm) 600 ÷ 1000 800 1000 800 1000
Rated current up to (A) 630 ÷ 2500 1600 2500 1600 2500*
Note * With main Bus Bar 1600A
Dimensions could be affected by specific equipment and configuration.
Electrical Data
D
E
A
B
F
G
C
H
EXAMPLE OF CONFIGURATION
CE- PMETAL ENCLOSED SWITCHBOARD
CE- BMETAL CLAD SWITCHBOARD
TYPICAL SECTIONS TYPICAL SECTIONS
P
1110
MEDIUM VOLTAGE CE-B METAL CLADSWITCHBOARDS
CE - B - C - en - REV.00 2015.6
CE-B36 VERSION UP TO 36 kV / 40,5 kV
Rated voltage kV 36 40,5
Rated power frequency withstand voltage (1min) kV 70 85
Rated lightning impulse withstand voltage kV 170 185
Rated frequency Hz 50/60 50/60
Rated short-time withstand current (3 sec) kA 31,5 31,5
Peak current kA 80 80
Internal arc withstand current IAC-AFLR (1sec)* kA 31,5 31,5
Rated current max. A 2500 2500
Rated current with forced ventilation ** max. A 3150 3150
Rated current with two breakers in parallel ** max. A 4000 4000
Dimensions
Note * Internal arc withstanding in option ** Type tested
Electrical Data
W
H
Width (mm) 1000 - 1200
Height 2475 - 2550
Height (mm) - IAC 2925
Depth (mm) 2550 - 3000
Dimensions could be affected by specific equipment and configuration.
D
H H HE E E
D D DA A A
F
F
B B
C C C
G G G
1312
MEDIUM VOLTAGE CE-B METAL CLADSWITCHBOARDS
CE - B - C - en - REV.00 2015.6
VERSIONS AND CONFIGURATIONS TYPICAL UNITS
Special VersionsEnvironment
• For special environments and temperature
• For indoor use with protection degree up to IP54
• Type CE-BO for outdoor use in metal box up to protection degree IP66
or NEMA 4
Connection
• Incoming/outgoing by cables form the TOP
• Incoming/outgoing by bus duct form the TOP
Options and accessoriesAvailable Locks
• Key locks permitting the key to be released with Circuit
Breaker locked in open positions
• Key locks permitting the key to be released with Circuit
Breaker locked in disconnected position
• Key locks permitting the key to be released with circuit
breaker door closed
• Key lock permitting the key to be released with earthing
switch closed and locked in closed position
• Key lock permitting the key to be released with earthing
switch open and locked in open position
• Electromechanical lock to prevent closing of earthing switch
• Mechanical lock to allow door opening only if circuit breaker
is in disconnected position and the shutters closed
• Padlock facility on circuit breaker shutters in closed position
• Padlock facility to prevent circuit breaker connecting or
disconnecting movement
• Padlock facility to prevent opening or closing of earthing switch
• Padlock facility on circuit breaker door
• Mechanical lock to allow rear connection door opening only with
earthing switch in close position
Command
• Motorized command for draw-out / draw-in circuit breaker
trolley for SWG up to 24 kV
• Motorized command for earthing switch for SWG up to 24 kV
Accessories
• Light or pressure device to limit internal arc fault duration
• Circuit breaker trolley for handling when removed from the compartment
• Contactor trolley for handling when removed from the compartment
• Handle for circuit breaker / contactor connecting or
disconnecting movement
• Handle for earthng switch command
Eart
hing
Eart
hing
Eart
hing
Optional
Type CE-BO for outdoor installation, with metal enclosure and protection degree up to IP66 / NEMA 4
1514
MEDIUM VOLTAGE CE-B METAL CLADSWITCHBOARDS
Headquarters and Factory:
via G. Rossini, 24
37060 Castel d’Azzano
(Verona) Italy
Tel. +39 045 8546511
Fax +39 045 8520214
E-mail: [email protected]
Production Branch:
Contrada Piana Z.I.
86019 Vinchiaturo
(Campobasso) Italy
Tel. +39 0874 340225
Fax +39 0874 340227
www.casagrande.vr.it