Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

download Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

of 22

Transcript of Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    1/22

    Schutzvermerk / Copyright-Vermerk

    November 20, 2009

    Sector Energy, Business Unit Medium Voltage Siemens AG 2009

    Special Requirements

    of IEEE C37.013 forGenerator Circuit Breaker Applications

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    2/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 2

    Generator Circuit Breaker Applications

    What is different about generatorcircuit breakers?

    Applicable standards Special considerations Vacuum versus SF6 technology

    Questions.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    3/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 3

    Generator and Distribution Circuit Breakers

    Generator circuit breaker Distribution circuit breaker

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    4/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 4

    Circuit Breakers for Distribution

    Requirements

    Standards:IEEE C37.04 Rating structure for HV circuit breakersIEEE C37.09 Tests for HV circuit breakersIEEE C37.10 Application guide for HV circuit breakers.

    X/R ratio: 17 (60 Hz).

    Time constant of dc decay: 45 ms.

    TRV typical values (15 kV, class S1 cable):Peak voltage (uc) = 25.7 kVTime-to-peak (t3) = 66 sRRRV 0.39 kV/ s.

    Duty cycle: O t CO t CO

    t = 0.3 s for reclosing / 15 s for non-reclosingt = 3 minutes.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    5/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 5

    Circuit Breakers for Generation

    Requirements

    Standards:IEEE C37.013 Generator circuit breaker.

    X/R ratio: 50 (60 Hz).

    Time constant of dc decay: 133 ms.

    TRV typical values (15 kV, 100 MVA machine):Peak voltage (E2) = 1.84 V = 1.84 x 15.0 = 27.6 kVTime-to-peak (T2) = 0.62 V = 0.62 x 15.0 = 9.3 sRRRV 3.5 kV/ s.

    Duty cycle: CO 30 min CO.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    6/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 6

    IEEEC37.04 for distribution circuitbreakers expresses TRV in termsharmonized with IEC with peak voltageuc, andtime-to-peak t3.

    IEEE C37.013 still uses old TRVexpressions with peak voltage E2 andtime-to-peak T2. Peak voltage is notchanged, but t3 is approximately 0.88 xT2.

    The physics are not changed, just therepresentation.

    Notes on TRV Representation

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    7/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 7

    IEEE C37.04-1999 Scope

    IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers

    1. Scope

    This standard establishes a symmetrical current rating structure and construction

    requirements for all indoor and outdoor types of ac high-voltage circuit breakersrated above 1000 V. It is only applicable to three-pole circuit breakers used inthree-phase systems and single-pole circuit breakers used in single-phasesystems.

    This standard does not cover circuit breakers used at frequencies other than50 Hz or 60 Hz, or generator circuit breakers that are covered in IEEEStandard C37.013-1997.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    8/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 8

    IEEE C37.013-1997 Scope

    IEEE Standard for AC High-Voltage Generator Circuit Breakers Rated on aSymmetrical Current Basis

    1. Scope

    This standard applies to all ac high-voltage generator circuit breakers rated on a

    symmetrical current basis that are installed between the generator and thetransformer terminals...

    Note: Since no other national or international standard on generator circuitbreakers exists, this standard is used worldwide.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    9/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 9

    IEEE C37.013 t h e International Standard

    for Generator Circuit Breakers

    IEEE C37.013 Revision PAR (Project) PAR approved by IEEE-SA

    Standards Board, March, 2009 Joint development with IEC SC 17A(HV Switchgear and Controlgear)

    IEEE WG chair is convenor (WG chair) ofIEC working group.

    IEC has no standard for a generator circuit breaker.The IEEE and IEC intent has been that IEEEC37.013 would be the global standard.

    IEC SC 17A WG 52 WG scope: Joint IEC/IEEE revision ofIEEE C37.013: IEEE Standard for AC High-

    Voltage Generator Circuit Breakers Rated on a Symmetrical Current Basis

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    10/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 10

    X/R = 17, = 45 ms X/R = 50, = 133 ms

    X/R Ratio Determines %dc Component

    %dc vs Contact Part for X/R = 17 and X/R = 50

    0.0

    20.0

    40.0

    60.0

    80.0

    100.0

    120.0

    0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100

    Contact Part time (ms )

    % d c

    C o m p o n e n

    t

    X/R = 17X/R = 50

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    11/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 11

    X/R Ratio Effect on Asymmetrical InterruptingX/R Ratio Effect on Asymmetrical Interrupting

    -2.00

    -1.50

    -1.00

    -0.50

    0.00

    0.50

    1.00

    1.50

    2.002.50

    3.00

    0

    1 8 0

    3 6 0

    5 4 0

    7 2 0

    9 0 0

    1 0 8 0

    1 2 6 0

    1 4 4 0

    1 6 2 0

    1 8 0 0

    1 9 8 0

    2 1 6 0

    2 3 4 0

    2 5 2 0

    2 7 0 0

    2 8 8 0

    3 0 6 0

    3 2 4 0

    3 4 2 0

    3 6 0 0

    Time (in degrees)

    C u r r e n

    t ( I s c =

    1 . 0

    0 )

    Instantaneous (total) current

    dc component

    S-factor (C37.04-1979)

    dc component (in decimal form) (multiply by 100 for %dc component) (C37.04-1999)

    Symmetrical current (ac component)

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    12/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 12

    X/R Ratio Effect on Asymmetrical Interrupting

    S factor (from IEEE C37.04-1979)

    Ratio of rms asymmetrical current to rms symmetrical current

    Assume contact part time of 55 ms, and 50 kA symmetrical current

    X/R = 17 %dc = 29.5 S = 1.084 I = 54.2 kA

    X/R = 50 %dc = 66.1 S = 1.369 I = 68.5 kAover 26% higher

    )100/(%21 dc I

    I S

    l symmetrica

    total +==

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    13/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 13

    Short-Circuit Currents

    Consider system shown:

    Transformer 1,000 A full load (self-cooled)impedance = 10%

    Generator 1,000 A full load Xd (subtransient reactance) = 20%

    For fault at F2, circuit breaker sees transformerfault current, roughly 1,000 A / 0.10 = 10 kA

    For fault at F1, circuit breaker sees generatorfault current, roughly 1,000 A / 0.20 = 5 kA

    Note:

    Fault current for generatorsource fault is only about50% of fault current forsystem (transformer)source fault

    F1

    F2

    G

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    14/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 14

    Generator Circuit Breaker Ratings

    32.24.5 / 4.5 / 4.51.4 / 1.8 / 1.8

    27.63.5 / 4.51.6 / 1.8

    kVkV/ skV/ s

    TRV parameters Peak voltage (1.84 V) RRRV transformer source RRRV generator source

    30 / 30 / 3040 / 30msDelayed current zero*

    75 / 65 / 6573 / 61%%dc component

    50 / 63 / 7225 / 31.5 / 3640 / 6320 / 31.5kAkA

    Short-circuit current

    Transformer source Generator source

    50 / 11038 / 95kV/kVDielectric 60 Hz / BIL

    17.515.0kVMaximum voltage

    Fixed-Mounted

    Drawout(Metal-Clad)

    UnitCharacteristic

    * Higher values may be available

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    15/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 15

    Generator Circuit Breakers

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    16/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 16

    Generator Circuit Breakers

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    17/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 17

    Out-of-Phase Switching

    Circuit Breakers for Standard Applications:

    IEEE C37.04 (clause 5.12):

    Out-of-phase switching is optional, not required for general purpose circuitbreakers

    If a rating is assigned, the preferred rating is 25% of the rated symmetricalinterrupting rating, with recovery voltage of (250% rated voltage / 1.732).Therefore, out-of-phase ratings are not typically assigned to general purposecircuit breakers rated per IEEE C37.04 and tested to IEEE C37.09.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    18/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 18

    Out-of-Phase Switching

    Circuit Breakers for Generator Switching Applications:

    IEEE C37.013 (clause 6.2.9):

    Out-of-phase switching is optional, not required for generator circuit breakersIf a rating is assigned, the assigned rating is shall be 50% of the rated

    symmetrical interrupting rating (transformer or system source).Out-of-phase switching recovery voltage values are based on a maximumout-of-phase condition of 90 degrees between generator and system. This isreasonable as more extreme angles would result in damage to the machine.The likelihood of out-of-phase switching is influenced by generator inertia, i.e.,low-inertia machines are more likely to be subject to out-of-phase switchingconditions.Generator circuit breakers should have an assigned out-of-phase switchingrating.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    19/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 19

    Other Differences

    Reclosing:Reclosing duty not required for generator circuit breakers.

    Short-time current duration:Normal circuit breakers

    3 seconds (metal-clad switchgear = 2 seconds)

    Generator circuit breakers1.0 second (typically test to 3 seconds).

    Closing & latching rating:Normal circuit breakers

    Peak current 260% of symmetrical short-circuit (60 Hz)With X/R = 17, real peak is 259.3%

    Generator circuit breakersPeak current 274% of symmetrical short-circuit (60 Hz)

    With X/R = 50, real peak is 274.2%.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    20/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 20

    Delayed Current Zero Example C37.013

    -4.000

    -3.500

    -3.000

    -2.500

    -2.000

    -1.500

    -1.000

    -0.500

    0.000

    0.500 0 1

    0 2 0

    3 0

    4 0

    5 0

    6 0

    7 0

    8 0

    9 0

    1 0 0

    1 1 0

    1 2 0

    1 3 0

    1 4 0

    1 5 0

    1 6 0

    Time (ms)

    C u r r e n

    t ( u n

    i t i z e

    d )

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    21/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 21

    Delayed Zero Test Example

    20.6 ms 30.0 ms

    40.1 ms 57.7 ms

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    22/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 22

    Generator Circuit Breaker Technologies

    VacuumWell-suited to smaller units(up to 6,000 A or so)

    Most economic for small units

    Derived from proven distribution unitoperators and interrupters

    High experience-base

    Very low arc voltage (20 - 50 V)Little affect on X/R ratioLower arc voltage = less arc energy =

    lower contact erosion

    Extremely rapid recovery of dielectricstrength between contacts afterinterruption good for extreme TRV levels

    SF 6Only option for very large units

    VERY expensive

    Unlike distribution products

    Lower experience-base

    SF 6 low arc voltage (several 100 V)Somewhat higher impact on X/R ratioHigher arc voltage = higher arc energy =

    greater contact erosion

    Less able to cope with high TRV levels