NETWORK MONITORING!
Impressive integration features and eight communication paths
• Create,configureandmanageuptoeightcommunicationpathsbetweenthepanelandCentralStation
• On-boardEthernetconnection• FlashUpdateable:Nomorefirmwarechipstoreplace• Providesupto500DMP1100XWirelessdevices• AdaptiveTechnology™instantlytransfersstandardlinesupervisionfromprimarytobackuppaths
• ULListedforBurglary,Fire,AccessControl
DMPXR500SeriesCommandProcessor™Panelsmeetallyourburglary,fireandaccesscontrolintegrationneeds.
XR500 SERIES ACCESS/BURGLARY/FIRE 574-ZONE COMMAND PROCESSOR™ PANEL
SYSTEM FEATURES• SelectArea,All/Perimeter,orHome/Sleep/Awayoperation• 32individualreportingareas,withcommonareas• Upto16superviseddooraccess-pointsand/orkeypads• OutputGroups:Maximumfunctionality—Minimumprogramming• Upto502fully-programmableFormCrelays• Upto562two-wiresmokedetectororfire-initiatingzones• 10,000usercodeswith99profiles• 12,000eventbuffer• UptofourindependentshiftschedulesperareaORuseoneshiftscheduletocontrolallareas
• Upto100outputschedulestocontrolrelaysandpaneloutputs• Upto20holidaydatesforshiftandoutputschedules• Serial3digitaldialerorCIDreportingtomultiplereceivers• Built-inphonelinemonitor• Built-inDB-9RS-232orLX-Bus(Selectable)• Multi-lingualmenusavailable
• 1.5Amps12VDCsmokeandauxiliaryoutputwithOVCprotection
• 16.5VAC50VAplug-intransformerincluded• 1.5Amps12VDCsupervisedbelloutput
XR500N/XR500E SYSTEM FEATURES• On-boardEthernet• Bank,SafeandVaultOperation• TwoManRule,PanicButtonTestandEarlyMorningAmbush
XR500E SYSTEM FEATURES• Built-inAES(AdvancedEncryptionStandard)Encryption• NISTCertifiedandULListedEncryption• Uniqueuser-programmablepassphraseforgreatersecurity
NYCMEA
XR500 SERIES
FLEXIBLE COMMUNICATIONThe XR500N has transitioned from dialer-focusedcommunicationstoatruenetworkand cellular communications approach byproviding stronger, multi-layered panelcommunications that ensure a constantlink between the panel and CentralStation. Installers have the ability tocreate, configureandmanageup toeightcommunicationpaths.
The unique DMP Serial 3 format supports16-characteruser,zoneandareanamestodecreasethecentralstationresponsetimeandlimitdependenceonautomationliteraltablesformessageconversion.
ENCRYPTIONThe XR500E provides encrypted datatransmission and is ideal for secureenvironments where encrypted data isrequired.UsingAES (Advanced EncryptionStandard) Encryption ensures secure datatransmissionbyusingauniquealphanumericpassphrase. UL Listed and NIST CertifiedEncryption.
NETwORk OR CELLULAR COMMUNICATIONBuilt-inEthernetCommunicationsenhancenetworkoptionsandprovidesStandardandEncryptedLineSecurity.BothUDPandTCParesupported.Thenetworkoptioncanbeusedastheprimarypathorasabackuppathtothedigitaldialerorcellularoption.
The 463G p lug- in D ig i ta l Cel lu larCommunicatorcanbeusedastheprimarypath, providing installation flexibilitywhere no land lines are available. Usedas the backup path, the 463G providesthe securityofa communication link thatcontinuestofunction,evenwhenlandlinesare cut or compromised. This interfaceworks on digital Cellular GSM/GPRS datanetworks over a variety of carriers in theUSAandCanada.
EIGHT COMMUNICATION PATHSCreate,configureandmanageuptoeightcommunicationpathsbetweenthepanelandCentralStation.Eachpathhasitsownpanelcommunication programming parameters,andcanbeidentifiedaseitherprimaryorbackup.Thisenablesinstallerstoconfigurea reliable communication link, offeringgreaterconfidencethatthepanelwillalwaysbeconnectedtotheCentralStation
ADAPTIvE TECHNOLOGYIf a current primary communication pathbecomesunavailable,AdaptiveTechnologydirects the panel to make a seamlesstransitionfromonecommunicationpathtoanotherwithinmilliseconds,ensuringthatnocheck-inorsupervisionmessagesaremissed.Thisallowsasystemtobefullysupervisedwhen the primary communication path isunavailable,whileminimizingexpensivecelltrafficwhenallpathsaregood.Thepanelisconstantlycheckingthefailedpathtoenablethepaneltorevertbacktotheprimarypathwhencommunicationisrestored.
BUILT-IN PROGRAMMER AND DIAGNOSTICSEnablesinstallersandservicetechnicianstofullyprogramthesystemandrundiagnosticsfromanyDMPLCDkeypad.
CANCEL/vERIFYIn a Home/Sleep/Away orAll/Perimetersystem,CANCELaburglaryalarmorVERIFYthat a valid burglar alarm has occurred.SelectingVERIFYmanuallyverifiesthealarmandanalarmverificationmessageissenttotheCentralStation.
FLASH UPDATEABLEThe XR500 Series panel accepts softwareupdates from a remote location usingRemote Link™ software.As new XR500featureupdatesrelease,performtheflashupdateremotely.
AREASProgram up to 32 areaswith a variety ofoptions,includingindependentarming.Eachareahasauniquenameandmayhave itsownaccountnumber.Common areas automatically arm whenthe last independent area is armed anddisarmwhenthefirst independentarea isdisarmed.Thisisidealforlobbiesorareaswhereusersneedcommonaccesstospecificareasonly.
AREA DISPLAY
Toprovidemoresystemflexibility,anycombinationofareasmaybeassignedtoaparticularkeypad.Inthismanner,a32-areasystemcouldfunctionas16mini-systems,eachhavingtwoareasofprotectionthatarecontrolledfromasinglekeypad.
ALL/PERIMETER OR HOME/SLEEP/AwAY OPTIONSThe XR500 Series panels support All/PerimeterorHome/Sleep/Awayoperation.WhenAll/Perimeteroperation is selected,Area1isthePerimeterandcanbeseparatelyarmed allowingArea 2, the Interior, toremainunarmedwhileyouareinside.When Home/Sleep/Away operation isselected,Areas 1 and 2 operate as in anAll/Perimetersystem.Area3istheBedroomareaandallowsuserstoarmtheperimeterand interior at night while leaving thebedroomareadisarmed.
DMP wIRELESSTheeasilyprogrammable900MHzfrequency-hopping spread-spectrum DMP1100XSerieswirelesssystemfeaturesTwo-waycommunicationforsuperioroperation,supervision and battery life. Two-waycommunication minimizes repetitivesignaling and helps to quickly identifymissingtransmitters.Simplekeypadaccesscanbeusedtoverifythatwirelessdevicezonesareinworkingorder.
ZONE EXPANSIONThe XR500 provides up to 574 zones,programmableforburglary,fireandaccessapplications. The system contains eightburglary zones and two Class B 12VDCpoweredzones.Upto64zonesareavailableon16keypadaddressesandupto100zonesareavailableonthebuilt-inLX-Bus.Addupto500zonesusingExpansionModules.
CROSS-ZONINGThis powerful feature allows zones to beprogrammed to report alarms onlywhenone ormore zones trip twicewithin 4 to250programmableseconds.Ifonlyonezonetripswithinthespecifiedtime,afaultreportissenttothecentralstation.
10,000 USER CODESEach user can be assigned to one of 99different profiles that provide access toanycombinationofareas.
12,000 EvENT MEMORYThe Display Events feature allows usersto view up to 2,000 stored openings andclosings, zone events, user code andschedule changes and supervisory events.Sorteventsbyaparticularuser,dooranddate range.The remaining 10,000 eventsdetaildooraccessgrantedeventsseparatelyforeasy review.EventsmaybeviewedatanysystemkeypadoruploadedtoRemoteLink™software.
SPEC SHEET
EvENTS MANAGERSavedial-upmonitoringcostsbyusingtheEvents Manager option to buffer specificnon-alarmreports.AutomaticallydownloadthemtothereceiverwhenmemoryisfullorkeeptheminmemoryuntildownloadedwithDMPRemoteLink™Software.
FIRE DRILL AND ONE-MAN wALk TESTUsers can test fire notification bells usingthe Fire Drill feature.A special code isalso available for installers to test thesystem. The one-man walk test featureallows a single technician to check thepanelresponsetoburglary,fire,panicandsupervisoryzones.
OUTPUTSTheXR500allowstheuseoftwoSPDTrelayoutputs and four open-collector outputs,whichmaybeactivatedbyzoneorsystemevents,byschedule,throughtheUserMenuorwhenacardispresented.OutputGroupsallowmultiple outputs to activatewith asingle event and/or can be assigned to aparticularuserprofile.Upto500outputsareavailableontheXR500LX-Buswhenoptionaloutputexpandersareused.
OUTPUT SCHEDULESAchievemaximum system flexibilitywith100programmableschedulesthatsimplifyplanning and operations. Control anycontact-activated device with schedulesthat automatically regulate relays andswitched-groundoutputs.
DOOR STRIkE SCHEDULES wITH OvERRIDESpecificdoorsmayuseoutputschedulestounlock during certain times of the day ornight,orthecardreadercanbecompletelydisabled when desired. The scheduleoverridefeaturekeepsdoorslockedshouldthebusinessopenlaterorcloseearlierthanscheduled.
MULTI-LINGUAL DISPLAY OPTIONXR500SeriessystemsmaybeprogrammedtodisplaytheUserMenuandStatusDisplaytextinmultiplelanguages.WhentheCommandkey is pressed, the option to choose alanguage displays. Select the languageto use.The language chosen continues todisplayatthekeypaduntilanotherlanguageischosen.
SHIFT SCHEDULES wITH HOLIDAYSUp to four independent Shift schedulesare available for each of the 32 areas.Shift schedules are usedwhen areas areprogrammed to automatically arm ordisarmandtotransmitareaLate-to-Closereports. Shift schedules are assigned touser authorities, called Profiles, to definescheduled permissions for system users.Override normal day-to-day schedules upto a year in advancewith up to 20 user-selectable Holiday Dates. Independentholiday schedules are available for eachshift,outputanddoor-strikeschedule.
kEYPAD SHORTCUT kEYS Keypad shortcut keys are provided tosimplify operation and allow the user toarm,monitororresetthesystem.
AUTOMATIC BURGLARY SYSTEM DISARMING
TheXR500isanintegratedburglary,fireandaccesscontrolsystemthatcanbeconfiguredforuserstogainaccessanddisarmtheareausingasinglecardread!
ACCESS CONTROLThe XR500 system can restrict access byschedule, arming level or other criteria.The specific reason for access denial canbe displayed on the keypad, stored inevents,loggedonalocalprinter(DMP462Prequired),senttothecentralstationandtoDMPAdvancedReportingsoftware.
THINLINE™ AND AqUALITE™ kEYPADSThe stylish and sleek 7000 Series keypadsprovide three 2-button Panic keys, ACpower and Armed LEDs, 32-characterdisplay,backlit logoandkeyboardplusaninternal speaker.Aqualite Series keypadsoffer a brilliantAqua colored LCD displayandbacklighting.
Aqualite/Thinline Keypad
vALUABLE vISUAL ALARM INDICATOR In a normal state, both the keypad andlogo backlighting remain Blue onAqualitekeypads or Green on Thinline keypads.However,duringanalarmstate,thekeypadandlogoturnRed.Thechangeincolorallowspersons on-site to instantly recognize analarmcondition.
Red Backlighting for Alarm Conditions
7760 CLEAR TOUCH™Anattractivenewuserinterfacefeaturingaglasstouchscreeninsteadoftraditionalkeys.TheBluetouchscreendisplayturnsRedforalarmconditions.AvailableinWhite,Blackor Platinum, the 7760 adds elegance andstyletoanyinstallation.
7760 Clear Touch™ Keypad
16 INDEPENDENT ACCESS CONTROL DOORS Anyaccesscontrolreaderwitha26-40bitWiegand output can be connected to theXR500 Series panel.Attach card readerinputstoupto16differentlocations.
ANTI-PASSBACkSpecificdoorsandreaderscanbedesignatedforaccessto,oregressfrom,specificareasinthesystem.Thisoperationrequiresuserstocardinandcardoutofaspecificarea.Users failing to egress the area are notallowed access into the area again untilauthorizedbythesystemadministrator.
LT-0684©2008DigitalMon
itoringProd
ucts,Inc.
I N T R U S I O N • F I R E • A C C E S S • N E T W O R K S
2500 No r t h Pa r t ne r s h i p Bou l e va rd
800 - 641 - 4282
www.dmp . com
Made i n t he USA Sp r i n gfie l d , M i s s ou r i 6 5803 - 8877
XR500 SERIES
8302
kEYPADS7000 SeriesThinlineKeypads7000A SeriesAqualiteKeypads7760 ClearTouchKeypad630F LCDRemoteFireCommand690/790 SeriesLCDSecurityCommandePAD™ VirtualKeypad
EXPANSION MODULES708 BusExtender710/710FBusSplitter/Repeater711 SingleZoneExpansion712-8 8-zoneExpansion714 4-zoneClassBExpansion714-8 8-zoneClassBExpansion714-16 16-zoneClassBExpansion715 4-zone2-wiresmokeExpansion715-8 8-zone2-wiresmokeExpansion715-16 16-zone2-wiresmokeExpansion716 OutputExpansion,
4FormCrelays, 4opencollectoroutputs
717 GraphicAnnunciator:20open collectoroutputs
725 4-zoneExpansion,24VDC736P RadionicsInterface739 X-10Interface
INTERFACE CARDS461 InterfaceAdaptorCard462N NetworkInterfaceCard462P PrinterInterfaceCard481 ExpansionInterfaceCard
AUXILIARY MODULES860 RelayOutputModule865 StyleY/ZNotificationCircuitModule866 StyleWNotificationCircuitModule867 LX-BusNotificationCircuitModule869 StyleDInitiatingCircuitModule893ADualPhoneLineModule
PULL STATIONS850 SeriesPullStations
SMOkE/HEAT DETECTORS521B/BXT AddressableSmoke,CleanMeNS6-100W DetectorBase521LX/LXTAddressableSmoke/Heat
CleanMeSLR-835B ConventionalSmokeSLR-835BHConventionalSmoke/Heat
TRANSFORMERS322 Wire-in56VA327 Plug-in50VA(Included)323 Wire-in56VA(350or350A
enclosurerequired)
POwER SUPPLIES502-12 2Amps@12VDC505-12/LX 5Amps@12VDC505-12L 5Amps@12VDC505-12A 5Amps@12VDC
INTRUSION DETECTORSSentrol®ContactsandSensorsOptexPIRsPotterContactsandSensorsTaneContactsandWaterSensorsVirtuallyanyotherIntrusionDetectors
ACCESS CONTROL 733or734 WiegandInterfaceModuleOP-08CB REXMotionDetectorPB-2 Request-to-ExitButtonProximityReadersandCredentialsDMPProxPatch
CENTRAL STATION RECEIvERSSCS-1R SecurityControlReceiverSCS-105 Single-LineDMPSerial3ReceiverCompatiblewithCentralStation
ReceiversthatacceptStandardCID,DD,orDMPSerial3messaging
wIRELESS738A Ademco32-pointExpansion
Module738I ITI96-pointExpansionModule
DMP wIRELESS1100X WirelessReceiver1100XIWirelessIn-lineReceiver1100XHWirelessHighPowerReceiver1101 UniversalTransmitter,
InternalandExternalContacts1102 UniversalTransmitter,
ExternalContact1114 WirelessFour-ZoneExpander1116 WirelessRelayOutput1117 WirelessLEDAnnunciator1118 WirelessRemoteIndicatorLight1121 PetImmunePIRMotionDetector1125 PIRMotionDetector1129 GlassbreakDetector1139 BillTrap1142 Two-ButtonHold-upTransmitter1142BCTwo-ButtonBeltClipHold-up
Transmitter1145 Four-ButtonKeyFob1146 Two-ButtonKeyFob1147 One-ButtonKeyFob1161 ResidentialSmokeDetector1162 ResidentialSmoke/HeatDetector
ACCESSORIES300 Four-wireHarness303 Silence/ResetPush-Button305 Plug-inOutputRelay306 TamperHarness307-S Screw-OnTamperSwitch3012 Clip-OnTamperSwitch335 IntrusionSiren370 LightningSuppressor374 SurgeVoltageSuppressor382-6 AnyNET-DMPCable(6')382-50AnyNET-DMPCable(50')399 ProgrammingHarness431 OutputHarness861 PowerDistributionModule
COMPUTER SOFTwARE RemoteLinkProgrammingSoftwareSystemLinkEnd-UserManagementSoftware
LinkServerApplication
SYSTEM SPECIFICATIONSPrimaryPower(included)16.5VAC50VAtransformerSecondaryPower 12VDCBatteryModels 365,366,367,368or369
OutputRatingBell 1.5Ampsat12VDCSmokeandAuxiliary 1.5Ampsat12VDC
CurrentDraw 180mAEnclosures:Material Cold-rolledsteelModel350 17.5”Wx13.5”Hx3.5”D (GrayorRed)Model350A(Gray) 17.5”Wx13.5”Hx3.75”DModel352X(Gray) 14.5”Wx32”Hx4.0”DModel341(Gray) 12.75”Wx6.55”Hx2.9”D
LISTINGS AND APPROvALSRefertotheXR500SeriesInstallationGuide(LT-0681),XR500SeriesProgrammingGuide (LT-0679)andspecificcompliance listings forinstallation and programming requirements necessary tomeet aparticularapproval.ANSI/SIACP-01-2000FalseAlarmReductionCaliforniaStateFireMarshal(CSFM)FCCPart15FCCPart68NewYorkCity(MEA)NISTValidatedXR500EEncryptedCommandProcessorCertificate#130UnderwritersLaboratories(UL)ListedULBank,SafeandVaultULStandardLineSecurityULEncryptedLineSecurity
UnderwritersLaboratoriesCanada(ULC)ListedForadditionalinformation,visitwww.dmp.comandselectCompliance.