Solar Photovoltaics: Principles, Application and case study
Transcript of Solar Photovoltaics: Principles, Application and case study
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
1/57
SOLAR PHOTOVOLTAICS
PRINCIPLES AND CASE STUDY
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
2/57
ABSTRACT
We all are aware of the exhausting energy sources and its time that we
think about alternative solutions for our day to day
requirements since we cannotcurb down our needs and ourdependency on the energy sources. It is peak time that
we need
to start reaching out for the alternative ways before we completely
run out of
the resources. Some of the renewable energy alternatives are wind
energy, solar energy,
tidal energy, thermal energy, geo-thermal energy. But most of these cannot be
harnessed at all locations. Hence, the best alternatives we can think of is the solar
energy which is never exhausting and also pollution free. Solar energy can be
harnessed at any location without any hindrance. One can install
them for the street
lights, on the rooftops, fields, etc. So why not we
go eco-friendly and harness the solar
energy which has less maintenance and presents easy installation on roof-tops or
ground.
There are many players in India manufacturing and providing a wide
range of solar energy products and solutions. The following report gives technical
details of a solar cell, module manufacturing procedure and also detailed description
of 1MW and 10MW solar power plants. Report concludes with a live Case Study on
off-grid solar power plant design.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
3/57
CONTENTS
1. INTRODUCTION
2.
SOLAR CELL AND ELECTRICAL PARAMETERS
3. MANUFACTURING OF SOLAR CELLS
4. MANUFACTURING OF SOLAR MODULES
5. INVERTERS
5.1 STRING INVERTER
5.1 CENTRAL INVERTER
6.
TRACKERS
6.1 SINGLE AXIS TRACKERS
6.2 DUAL AXIS TRACKERS
7. MAXIMUM POWER POINT TRACKING
8. GRID SYNCHRONIZATION
9. MOMINPET POWER PLANT VISIT
10.MIDJIL POWER PLANT VISIT
11.
ANALYSIS OF SOLAR POWER PLANT
11.1 SOLAR PLANT PERFORMANCE INDEX
11.2 POTENTIAL INDUCED DEGRADATION
11.3 FILL FACTOR IMPACT
12.CASE STUDY
13.CONCLUSION
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
4/57
-1 -
1.INTRODUCTION
The shortage of power, rapid consumption of non-renewable energy, ever-
increasing demand for power supply, daily warnings about our environment are enough
signs to tell us that it is time we need to do something. So, what can we do? How aboutharnessing solar energy?? Some of the advantages of plugging into sun are:
Reduces dependence on exhausting resources.
Solar energy is renewable.
Making way for a healthier environment.
Solar panels help protect the atmosphere by generating electricity without the
greenhouse gases that traditional power plants produce. 1 kWh produced from coal
emits 0.33 kg of CO2. 1 kWhproduced by the combination of all sources of renewableenergyemits0.04 kg of CO2.
If we build a solar power plant that produces 40,500 kWh peryear, we would save
7.3 tons of CO2 at no longer producethose watts in a carbon plant. So for every 1MWh
per year, we wouldsave 0.18 tons of CO2.
Under JNNSM (Jawaharlal Nehru National Solar Mission),Government of India
has taken steps to develop and deploy solar energy for supplementing the energy
requirements of the country. JNNSM was launched on 11th
January, 2010 by the PrimeMinister and has set the ambitious target of deploying 20,000 MW of grid connected
solar power by 2022 is aimed at reducing the cost of solar power generation in the
country through (i) long term policy; (ii) large scale deployment goals; (iii) aggressive
R&D; and (iv) domestic productionof critical raw materials, components and products,
as a result toachieve grid tariff parity by 2022. Solar mission will create an enablingpolicy
framework to achieve this objective and make India a globalleader in solar energy.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
5/57
-2 -
Another such program is Clean Development Mechanism (CDM) which allows a
country with anemission-reduction or emission-limitation commitment to implement
an emission-reduction project in developing countries. Such projectscan earn saleable
certified emission reduction (CER) credits, eachequivalent to one tonne of CO2. The
mechanism is seen by many as a trailblazer. It is the first global, environmental
investment and credit scheme of its kind, providing a standardized emissions offset
instrument, CERs. A CDM project activity might involve, for example, a rural
electrification project using solar panels or the installation of more energy-efficient
boilers. The mechanism stimulates sustainable development and emission reductions,
while giving industrialized countries some flexibility in how they meet their emission
reductionorlimitation targets.
The solar cell is the basic building block of solar photovoltaics. The cell canbe considered as a two terminal device which conductslike a diode in the dark and
generates a photovoltage when chargedby the sun. These solar cells are then made into
solar photovoltaic (SPV) modules by sequence of processes. The prepared solar
modulesare then arranged into series connection to form a completePV array. These
arrays are then fixed in ground or roof-top. The supply from PV arrays is DC in nature,
but most of the electrical appliancesneed AC supply. Hence, inverters are used for the
conversion fromDC to AC. Inverters can be either central or string in naturedepending
on our need. The power so obtained is later sent to the substation following the
synchronization of the power with thegrid.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
6/57
-3 -
2. SOLAR CELL AND ELECTRICALPARAMETERS
The sunrays falling on earth have two componentslight and heat. The heat
component has the solar Joules energy and the light component has the solar photon
energy.
Photons in, electrons out: The Photovoltaic effect
Solar photovoltaic energy conversion is a one-step conversion process which
generates electrical energy from light energy. The explanation relies on ideas from
quantum theory. Light is made up of packets of energy, called photons, whose energy
depends only upon the frequency, or colour, of the light. The energy of visible photons
is sufficient to excite electrons, to higher energy levels where they are free to move.
An extreme example of this is the photoelectric effect, which was explained by
Einstein in 1905, where blue or ultraviolet light provides enough energy for electrons
to escape completely from the surface of a metal. Normally, when light is absorbed by
matter, photons are given up to excite electrons to higher energy states within the
material, but the excited electrons quickly relax back to their ground state. In a
photovoltaic device, however, there is some built-in asymmetry which pulls the excited
electrons away before they can relax, and feeds them to an external circuit. The extra
energy of the excited electrons generates a potential difference, or electro-motive force(emf). This force drives the electrons through a load in the external circuit to do
electrical work.
The photovoltaic effect was first reported by Edmund Becquerel in 1839 when he
observed that the action of light on a silver coated platinum electrode immersed in
electrolyte produced an electric current.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
7/57
-4 -
The solar cell is the basic building block of solar photovoltaics. The cell can be
considered as a two terminal device which conducts like a diode in the dark andgenerates a photovoltage when charged by the sun.
In reality cells dissipate power through the resistance of the contacts and through
leakage currents around the sides of the device. These effects are equivalent electrically
to two parasitic resistances in series (Rs) and in parallel (Rsh) with the cell.
Fig: Equivalent circuit of solar cell including series and shunt resistances.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
8/57
-5 -
I-V characteristics of a solar cell is shown in the figure below
Effect of resistances on I-V characteristics of a solar cell
Effect of (a) increasing series and (b) reducing parallel resistances.
Like all other semiconductor devices, solar cells are sensitive totemperature. In a
solar cell, the parameter most affected by an increase in temperature is the open-circuit
voltage (Voc). The impact of increasingtemperature is shown in the figure below.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
9/57
-6 -
Open-circuit voltage decreases with increase in temperaturewhereas short-circuit
current increases slightly. In a solar cell the rate of change of open-circuit voltage and
short-circuit current with respect to temperature is given by
Solar cells convert the photon light around the pn-junction directly into electricity
without any moving or mechanicalparts. PV cells produce energy from sunlight,
not from heat. In fact,they are most efficient when they are cold.
When exposed to sunlight (or other intense light source), thevoltage produced
by a single solar cell is about 0.58V DC, with thecurrent flow being proportional to thelight energy (photons).In most solar cells, the voltage is nearly constant, and the
current is proportional to the size of the cell and the intensity of the light.
Some of the key concepts regarding the solar cells are the StandardTest Conditions
(STC) which are as follows:
1.
AM (Air Mass Index) =1.5
2.
Temp= 25oC
3.
Irradiance= 100mW/cm2
Key performance characteristics:
1.
Jsc = q bs(E)QE(E)dE
Jsc = Short-circuit current density q= is the electron charge
bs= Incident spectral photon flux density QE (E) = Quantum efficiency
2.
Voc= (kT/q) ln(Jsc/Joc +1)
Jo c= Open circuit current density k=Boltzmann constant
T= temperature
3. FF (fill factor) = (Jm Vm)/ (Jsc Voc)
Voc= Open circuit Voltage Jm = Maximum current density
Vm = Maximum voltage
4.
(efficiency) = (Jm Vm)/Ps Ps= input solar power
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
10/57
-
7 -
3. MANUFACTURING OF SOLAR CELLS
Silicon is the eighth most common element in the universe bymass, but very rarely
occurs as the pure free element in nature. It is most widely distributed in dusts, sands,
planetoids, and planets asvarious forms of silicon dioxide (silica) or silicates. Over 90% oftheEarth's crust is composed of silicate minerals, making silicon the second most abundant
element in the Earth's crust (about 28% by mass) after oxygen. More modern silicon
compounds such as silicon carbide form abrasives and high-strength ceramics. Siliconis the
basis of the widely used synthetic polymers called silicones.
The process of solar cells manufacturing, first starts with the mining of quartz from
the earth and then conversion of that quartz into Mg-Si by carbothermic reaction. Mg-Si
is processed into poly-silicon by Siemens process. The poly-silicon is then made into ingot
with the help of a seed of the silicon. The circular ingot obtained is then cut into particular
shape at the edges. This structure is then cut into very thin slices to give wafers which are
processed to give solar cells. The upper surface of the module is n-type and the bottom
part needs to be made into p-type by diffusing POCl3at 800C. The edges are then made
proper by the process of plasma edging and it removes the excess of the p-type material.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
11/57
-
8 -
Extraction of metallurgical grade Silicon:
Metallurgical grade Silicon is commercially prepared by the reaction ofhigh-purity silica
with wood, charcoal, and coal in an electric arc furnace using Carbon electrodes. At
temperatures above 1900 C (3450 F), Carbon in the above mentioned materials and the
Silicon undergo the chemical reaction SiO2 + 2C Si + 2CO.Liquid Silicon collects in the
bottom of the furnace, which is thendrained and cooled. The silicon produced in this manner
is called metallurgical grade silicon and is at least 98% pure. Using thismethod, Silicon Carbide
(SiC) may also form from an excess of Carbonin one or both of the following ways:
SiO2 + C SiO + CO
SiO + 2C SiC + CO.
However, provided the concentration of SiO2 is kept high,the Silicon Carbide can be
eliminated by the chemical reaction as:-
2SiC +SiO2 3Si + 2 CO
Mono-crystalline silicon ingot grown by the Czochralski processPolycrystalline silicon rod made by the Siemens process
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
12/57
-
9 -
Methods of manufacturing ingot:
a)
Czochralski method: Used to create a monocrystalline cell. A single monocrystalline
silicon seed crystal is slowly pulled from the high-heat molten Silicon. As it is drawn
upwards, the Silicon cools and solidifies as a single ingot. This cylindrical ingot is then
sliced into thin pieces that are then cut into the cell shapes as visible on a monocrystalline
solar panel.
b)
Siemens Process: This technique grows high-purity Silicon crystallites directly on the
surface of (pre-existing) pure Silicon seed rods by a chemical decomposition that takes
placewhen the gaseous Trichlorosilane (HSiCl3) is blown over the rod'ssurface at 1150C.
This technique is called Chemical Vapour Deposition (CVD) and produces high-purity
Polycrystalline Silicon, also known as polysilicon. Whilethe conventional Siemens process
produces electronic grade polysilicon at typically 9N11N purities, that is, it containsimpurity levels of less than one part per billion , themodified Siemens process is a dedicated
process-route for the production of solar grade silicon (SoG-Si) with purities of 6N
(99.9999%) and less energy demand.
c)
FBR Method: A more recent alternative for the production ofpolysilicon is the fluidized
bed reactor (FBR) manufacturing technology. Compared to the traditional Siemens
process, FBRfeatures a number of advantages that lead to cheaper polysilicon demanded
by the fast-growing photovoltaic industry.Contrary to Siemens batch process, FBR runscontinuously,wasting fewer resources and requires less setup and downtime.It uses about
10% of the electricity consumed by aconventional rod reactor in Siemens process, asitdoes
not waste energy by placing heated gas and silicon incontact with cold surfaces. In the FBR,
silane (SiH4) is injected into the reactor from below and forms a fluidized bed together
with the silicon seed particles that are fed from above. Thegaseous silane then decomposes
and deposits silicon on theseedparticles. When the particles have grown to larger granules,
they eventually sink to the bottom of the reactor where they arecontinuously withdrawn.
The FBR technology produces polysilicon at 6N to 9N, apurity still higher than the 5N
to 6N of upgraded metallurgical silicon (UMG-Si), a third technology used by the
photovoltaic industry, that dispenses altogether with chemical purification, using
metallurgical techniques instead. Solar grade purity is 99.999% (5N) and electronic grade
purity is99.9999999(9N)
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
13/57
-
10 -
The two types of PV crystalline cells mono and multi are compared in the table below.Monocrystalline
(Single crystalline)Multi-crystalline
(Polycrystalline)
1.
Composed of single crystal of silicon
2.
Czochralski method is employed.
Cylindrical shaped ingot is obtained
with the help of a seed crystal.
3.
Can function in low light conditions
also.
4.
More expensive
5.
More efficient in real life conditions.
1.
Composed of many crystals of silicon
2.
Siemens method or Fluidized Bed
reduction method is employed. Cube
shaped ingot is obtained
3.
Function better under high heat
conditions
4.
Less expensive
5.
More efficient in lab conditions.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
14/57
-
11 -
4. MANUFACTURING OF SOLAR MODULES
Before getting into manufacturing process of solar modules let ushave a look at some of
the IEC standards.
IEC TC 82 Working Groups
WG1: Glossary
Task: To prepare a glossary of terms relevant to PV.
WG2: Modules, non-concentrating
Task: To develop international standards for non-concentrating,terrestrial
photovoltaic modules -crystalline & thin-film.
WG3: Systems
Task: To give general instructions for photovoltaic system designand
maintenance.
WG6: Balance-of-system (BOS) components
Task: To develop international standards for BOS components forPV systems.
WG 7: Concentrator modules
Task: To develop international standards for photovoltaicconcentrators and
receivers.
WG 8: Solar cells and wafers (new group to be formed in 2013)
Task: To develop international standards for photovoltaic cells andwafers.
JWG 21/TC 82 Batteries
Task: To draw up standard requirements for battery storagesystems intended for use
in photovoltaic systems.
JWG 1-TC 82/TC 88/TC21/SC21A
Task: To prepare guidelines for Decentralized Rural Electrification(DRE) projectswhich are now being implemented.
Here are some of the IEC TC 82 standards
IEC 60891:2009 Edition 2.0 (2009-12-14)
Photovoltaic devices - Procedures for temperature and irradiance corrections to measured
I-V characteristics
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
15/57
-
12 -
IEC 60904-1:2006
Edition 2.0 (2006-09-13)
Photovoltaic devices - Part 1: Measurement of photovoltaic current-voltage characteristics
IEC 60904-2:2007
Edition 2.0 (2007-03-20)
Photovoltaic devices - Part 2: Requirements for reference solar devices
IEC 60904-3:2008
Edition 2.0 (2008-04-09)
Photovoltaic devices - Part 3: Measurement principles for terrestrial photovoltaic (PV)
solardevices with reference spectral irradiance data
IEC 60904-4:2009
Edition 1.0 (2009-06-09)
Photovoltaic devices - Part 4: Reference solar devices - Procedures for establishing
calibration traceability
IEC 60904-5:2011
Edition 2.0 (2011-02-17)
Photovoltaic devices - Part 5: Determination of the equivalent cell temperature (ECT) of
photovoltaic (PV) devices by the open-circuit voltage method
IEC 60904-7:2008
Edition 3.0 (2008-11-26)
Photovoltaic devices - Part 7: Computation of the spectral mismatch correction for
measurements of photovoltaic devices
IEC 60904-8:2014
Edition 3.0 (2014-05-08)
Photovoltaic devices - Part 8: Measurement of spectral responsivity of a PV device
Complete standards published by TC 82 can be found on at this link:
http://www.iec.ch/dyn/www/f?p=103:23:0::::FSP_ORG_ID,FSP_LANG_ID:1276,25
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
16/57
-
13 -
The process of manufacturing solar modules involves the followingsteps:
1.
Segregation and Cell testing
2.
Tabbing
3.
Stringing
4.
Lamination
5.
Testing with sun simulator and tagging with RFID reader
6.
Silicone taping and Framing
7.
Bypass diode connections
1.
Segregation and Cell Testing
The incoming solar cells are already processed with anti-reflective coating, screen
printing and BSF (Back Surface Field=250m) coating. The incoming cells with silver
lining are first tested. The silver lining on the cells has very less thickness sincemore open
area is needed to capture the sunlight. The front part of the cell is made n-type by using
phosphorous metal on silicon and therear surface is made p-type diffusing boron.
2.
Tabbing:
Tabbing wire is used to connect the solar cells in series to get the desired voltage. The
tabbingwire should be 18-20 mm thick to get better current. A good tab wireis made out of
copper coated with solder for easy flow.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
17/57
-
14 -
Bus Wire (Connecting wire): Similar to tab wire but it is muchwider and used to carry
the current across the cell and can rangefrom 2.5mm to 5mm depending on the power and
size of the cell. It ismade out of copper coated with solder. At the end of the tabbingprocess,
2 pairs of positive and negative terminals are left out forfurther connection into the bypass
diodes which are fixed at the endof the whole process.
3.
Stringing:Process where the solar cells are connected inseries. Standard module sizes are 6 x 3,
6 x 6, 6 x10 and 6 x12. At the end of the process weget a cell module. After this process the
module is sent for lamination.
4.
Lamination:
The cell module so obtained is covered with Ethylene Vinyl Acetate (EVA) sheetsat
the top and bottom which reduces the loss of electrical conductivity and also reducing the
CTM (cell to module) loss. High transmission glass (having low iron content) is fixed onthe top EVA and the bottom EVA is covered with a back cover which is made up of PVF
(Poly Vinyl Fluoride) made of TPT (Tedlar Polyester Tedlar). The TPT is made up of
multi-laminated sheets andpossesses highdurability, impermeability, insolubility, erosion
durability, mechanical stability, hydrophobic property.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
18/57
-
15 -
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
19/57
-16 -
In the laminator, renise sheets are used to avoid sticking of the EVA sheets. The
elasticity of EVA and toughness of TPT gives the solar cell better astigmatic property and
comprehensive protections. The laminator is a double vacuum chamber with temperature
around 100C which melts EVA in about 8-10 mins. Once the lamination is completed, the
structure so obtained is sent to the curing oven where the cross-linking of the EVA sheettakes place. After curing, the edges of module are sharpened and sent for testing.
5.Testing with Sun Simulator and RFID reader
The module is placed on a sun simulator. A beam is made incident on the module
which has a spectrum similar to the sun spectrum. This simulates the IV characteristics
(upside down characteristics of a forward biased diode) and provides the specifications
about the modules.
Radio Frequency Identification (RFID)
RFID is a method for Automatic Identification and Data Capture (AIDC). It is
wireless use of electromagnetic fields to transfer data for automatically identifying and
tracking purpose. The tags contain electronically stored data. The RFID reader and writer
feeds the data related to the module to RFID tag placed on the solar module. Unlike a
barcode, the tag does not necessarily need to be within line of sight of the reader, and may
be embedded in the tracked object.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
20/57
-
17 -
Data sheet of an SPV module of 60 cells
6.
Silicone Taping and Framing
Once the modules are cleared from testing, they are sent for silicone taping and framing.
Silicone taping is done to protect the modules fromwater.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
21/57
-
18 -
Silicones:
Alternating silicon-oxygen chains with hydrogen attached to the remaining silicon
bonds form the ubiquitous silicon-based polymeric materials known as silicones. These
compounds containing silicon-oxygen and occasionally silicon-carbon bonds have thecapability to act as bonding intermediates between glass and organic compounds, and to
form polymers with useful properties such as impermeability to water, flexibility and
resistance to chemical attack. Silicones are often used in waterproofing treatments,
moulding compounds, mould-release agents, mechanical seals, high temperature greases
andwaxes, and caulking compounds.
Once the silicone taping is done, the modules are framed withaluminium metal and
the name plate with the specifications is alsoplaced.
7.
Bypass diodeconnections
While selecting bypass diodes or blocking diodes, Imaxis taken into consideration. Bypass
diodes are used in parallel with either a single or a number of photovoltaic solar cells to
prevent the current(s) flowing from unshaded solar cells overheating and burning out
weaker or partially shaded solar cells. Bypass diode hence provides current path around the
weaker cell. Bypass diodes in solar panels are connected in parallel with a photovoltaic cell
or panel to shunt the current around it, whereas blocking diodes are connected in series
with the PV panels to prevent current flowing back into them.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
22/57-
19 -
Two types of diodes are available as bypass diodes in solar panels and arrays: the pn-
junction Silicon diode and the Schottky diode. Both are available with a wide range of
current ratings. The Schottky barrier diode has a much lower forward voltage drop of
about 0.4V as opposed to the PN diodes 0.7Vdrop for a Silicon device.
This lower voltage drop allows a savings of one full PV cell in eachseries branch of
the solar array therefore; the array is more efficient since less power is dissipated in the
blocking diode. Mostmanufacturers include both blocking diodes and bypass diodes in
their solar panels simplifying the design.
SPV Modules:
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
23/57
-
20 -
Special Features:
High energy conversion efficiency because of high fill factor.
Cells sorted by power and current to minimize field mismatch losses.
Electroluminescence test carried out for micro-cracks.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
24/57
-
21 -
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
25/57
-
22 -
5. INVERTERS
Inverter converts DC output of PV panels into a clean AC current for AC appliances
or fed back into grid line. Inverter is a critical component used in any PV system where
alternative current (AC) power output is needed.Basically there are two types of inverters, they are:
String inverter
Central inverter
5.1
STRING INVERTER:
A string inverter is commonly used in home and commercial solar power systems and
is often situated some distance away from the solar array. Depending on the size of the
installation, there may be more than one string inverters for a solar power plant.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
26/57
-
23 -
5.1 CENTRAL INVERTER:
Central inverters are designed for applications such as large arrays installed on buildings,
industrial facilities as well as field installations - they are basically just a very large string
inverter.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
27/57
-
24 -
6. TRACKERS
A solar tracker is a device that orients a payload toward the sun. Payloads can be
photovoltaic panels, reflectors, lenses or otheroptical devices.
In concentrated photovoltaic (CPV) and concentrated solar thermal (CSP)
applications, trackers are used to enable the optical components in the CPV and CSP
systems. The optics in concentrated solar applications accepts the direct component of
sunlight light and therefore must be oriented appropriately to collect energy. Tracking
systems are found in all concentrator applications because such systems do not produce
energy unless pointed at the sun.
The sun travels through 360 East to West per day, but from the perspective of any
fixed location the visible portion is 180 during an average 1/2 day period (more in spring
and summer; less, in fall and winter). Local horizon effects reduce this somewhat, making
the effective motion about 150. A solar panel in a fixed orientation between the dawn and
sunset extremes will see a motion of 75 to either side, and thus, according to the table
above, will lose 75% of the energy in the morning and evening. Rotating the panels to the
east and west can help recapture those losses. A tracker rotating in the East-West direction
is known as a single-axis tracker.
The sun also moves through 46 North and South during a year. The same set of
panels set at the midpoint between the two local extremes will thus see the sun move 23on either side, causing losses of 8.3%. A tracker that accounts for both the daily and seasonal
motions is known as a dual-axis tracker. Generally speaking, the losses due to seasonal angle
changes are complicated by changes in the length of the day, increasing collection in the summer
in northern or southern latitudes. This biases collection toward the summer, so if the panels are
tilted closer to the average summer angles, the total yearly losses are reduced compared to a system
tilted at the spring/fall solstice angle (which is the same as the site's latitude).
The primary benefit of a tracking system is to collect solar energy for the longest period ofthe day, and with the most accurate alignment as the Sun's position shifts with the seasons.
In addition, the greater the level of concentration employed, the more important accurate
tracking becomes, because the proportion of energy derived from direct radiation is higher, and
the region wherethat concentrated energy is focused becomes smaller.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
28/57
-25 -
There are mainly two types of trackers:
1. Single-Axis tracker: Single axis trackers have one degree of freedomthat acts as an axis
of rotation. The axis of rotation of single axistrackers is typically aligned along a true North
meridian.
2. Dual-Axis tracker: Dual axis trackers have two degrees of freedom that act as axes of
rotation which are normal to oneanother. The axis that is fixed with respect to the ground
can be considered a primary axis. The axis that is referenced to the primary axis can be
considered a secondary axis.
6.1 SINGLE AXIS TRACKERS:
1.
HSAT: Horizontal Single Axis TrackerThe axis of rotation for horizontal single axis tracker is horizontal with respect to the
ground. The posts at either end of the axis of rotationof a horizontal single axis tracker can
be shared between trackers tolower the installation cost.
Field layouts with horizontal single axis trackers are very flexible. Thesimple geometry
means that keeping all of the axes of rotationparallel to one another is all that is required for
appropriatelypositioning the trackers with respect to one another.
Appropriate spacing can maximize the ratio of energy production to cost, this beingdependent upon local terrain and shading conditions and the time-of-day value of the
energy produced. Backtracking is onemeans of computing the disposition of panels.
Horizontal trackers typically have the face of the module orientedparallel to the axis of
rotation. As a module tracks, it sweeps acylinder that is rotationally symmetric around the
axis of rotation.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
29/57
-
26 -
2.
HTSAT: Horizontal Tilt Single Axis Tracker
In HSAT, the modules are mounted flat at 0, while in HTSAT;the modules are installed at
a certain tilt. It works on same principleasHSAT, keeping the axis of tube horizontal in N-S
line and rotating the solar modules E-W throughout the day. These trackers are usually
suitable in high latitude locations but do not take as much land space as consumed by
Vertical single axis tracker (VSAT).
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
30/57
-
27 -
3.VSAT: Vertical Single Axis Tracker
The axis of rotation for vertical single axis trackers is vertical withrespect to the
ground. These trackers rotate from East to West overthe course of the day. Such trackers
are more effective at highlatitudes than are horizontal axis trackers.Field layouts must consider shading to avoid unnecessary energy losses and to
optimize land utilization. Also optimization for dense packing is limited due to the
nature of the shading over the course ofa year.
Vertical single axis trackers typically have the face of the module oriented at an
angle with respect to the axis of rotation. As a module tracks, it sweeps a cone that is
rotationally symmetric around the axisof rotation.
4.
TSAT: Tilted Single Axis Tracker
All trackers with axes of rotation between horizontal and vertical areconsidered
tilted single axis trackers. Tracker tilt angles are often limited to reduce the wind profile
and decrease the elevated endheight.
Field layouts must consider shading to avoid unnecessary losses andto optimize
land utilization. With backtracking, they can be packed without shading perpendicular
to their axis of rotation at any density. However, the packing parallel to their axes of
rotation is limited by the tilt angle and the latitude.
Tilted single axis trackers typically have the face of the moduleoriented parallel to
the axis of rotation. As a module tracks, it sweepsa cylinder that is rotationally symmetric
around the axis of rotation.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
31/57
-
28 -
5.
PASAT: Polar Aligned Single Axis Tracker
This method is scientifically well known as the standard method of mounting a
telescope support structure. The tilted single axis is aligned to the polar star. It is
therefore called a polar aligned single axis tracker (PASAT). In this particularimplementation of a tiltedsingle axis tracker, the tilt angle is equal to the site latitude.
Thisaligns the tracker axis of rotation with the earths axis of rotation.
6.2
DUAL AXIS TRACKERS:
1.
TTDAT: Tip Tilt Dual Axis Tracker
A tip-tilt dual axis tracker is so-named because the panel array ismounted on the
top of a pole. Normally the E-W movement isdriven by rotating the array around the top
of the pole. On top of therotating bearing is a T- or H-shaped mechanism that provides
verticalrotation of the panels and provides the main mounting points for thearray. The
posts at either end of the primary axis of rotation of a tip-tilt dual axis tracker can be
shared between trackers to lowerinstallation costs.
Other such TTDAT trackers have a horizontal primary axis and a dependent
orthogonal axis. The vertical azimuthal axis is fixed. Thisallows for great flexibility of the
payload connection to the groundmounted equipment because there is no twisting of
the cablingaround the pole.
Field layouts with tiptilt dual axis trackers are very flexible.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
32/57
-
29 -
2.
AADAT: Azimuth Altitude Dual Axis Tracker
An azimuthaltitude dual axis tracker has its primary axis (the azimuthaxis) vertical
to the ground. The secondary axis (often called elevationaxis) is normal to the primary
axis. They are similar totip-tilt systems in operation, but they differ in the way the arrayis rotated for daily tracking. Instead of rotating the array around the top of the pole,
AADAT systems can use a large ring mounted on theground with the array mounted on
a series of rollers. The mainadvantage of this arrangement is the weight of the array is
distributedover a portion of the ring, as opposed to the single loading point of the pole
in the TTDAT. This allows AADAT to support much largerarrays.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
33/57
-
30 -
7. MAXIMUM POWER POINT TRACKING
Maximum Power Point Tracking (MPPT) is a technique used to get the maximum
power from one or more power plants. It is the purpose of the MPPT system to sample
the output of the cells and apply the proper resistance (load) to obtain maximum powerfor any given environmental conditions. MPPT devices are typically integrated into an
electric power converter system that provides voltage or current conversion, filtering, and
regulation for driving various loads, including power grids, batteries, or motors.
Solar inverters convert the DC power to AC power and may incorporate MPPT: such
inverters sample the output power (I-V curve) from the solar cell and apply the proper
resistance (load) so as to obtain maximum power.
Maximum power point is the product of the maximum voltage (Vmpp) and maximumcurrent (Impp). Some solar panels have a higher maximum power than others.
In the above graph, the line which intersects the IV-curve givesthe maximum power
transfer point.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
34/57
-
31 -
8. GRID SYNCHRONIZATION
Inverters are used in grid synchronization with the solar power plant. Special protective
devices are used to prevent the risk of danger in the event of mains interference. The more
the PV plants feed into the grid, greater are the demands placed on the grid services.If the feed-in power of the PV plants is greater than the capacity of the local grids, then
adjustable local grid transformers are used to regulate the voltage and prevent the upper
limit from being exceeded. This task can be performed by power storage systems.
When a large amount of power is being consumed, then the line voltage in these weak
grid lines decreases, thus the act of feeding in solar power counteracts this voltage drop and
in turn, supports the grid. Measures need to be taken to avoid excessive increasing in
voltage during the period when the feed-in is high and the consumption is low. Also, in thissituation the currents may also flow in reverse direction. Disconnection devices are used in
between the PV generating plant and the grid, which can disconnect the plant from the grid
in cases of repair, failure, etc. In smaller plants, ADD or manual disconnection is done.
ADD (Automatic Disconnecting Device):
ADD device monitors the energy feedback into the 230/400 V grid. If mains power is
switched off by the electricity supply company, or by a protective device, it is vital for small-
scale power plants to be disconnected within a few milliseconds. Monitoring the voltageand frequency and recognizing isolated (off-grid) operation are essential requirements for
any ADD.
MSD (Mains Switching Devices): Similar to the ADD; itmeasures the grid
impedance and is able to recognize power failure and cut-offs on the basis of
impedance jumps.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
35/57
-
32 -
9. MOMINPET POWER PLANT - 1 MW
Location: Mominpet, Sangareddy, Telangana.Production - 1 MW
Types of tracker system-Single axis, Single axis horizontal tiltand Dual axis
In single axis tracking system 19 modules are connected inseries to form one string.
Inverters used here are string inverters of capacity 17kW, for every 4 strings (76 modules)
one inverter is used.
Readings of an inverter at the time of visit:
Day: 16th
Dec 2014Time: 2:16 PM
Power 9771 W
Day 41.72 kWh
Total 76350 kWh
DC input current 13.6 A
DC input voltage 511 V
AC output current 12.6 AAC output voltage 236 V
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
36/57
-
33 -
AC supply from inverters is stepped up to 11kV using transformer and finally
connected to the grid.
Transformer Specifications:
Rated kVA 1250Rated voltage HV 11000 V
LV 400 V
Rated current HV 65.6 A
LV 1804.2 A
Phases 3
Frequency 50 Hz
Switchyard which gives extra protection to the system contains components like
auxiliary relay, vacuum switch gear,over current and earth fault relay, trip circuit supervisionrelay, under voltage relay and master trip relay.
Vacuum switchgear:
Remote Terminal Units (RTU) are installed in all inverters and any fault at inverter level can
be identified by theoperator sitting in the control room with the help of SCADA system.
Number of lightning arrestors used - 1
PV arrays are earthed using GI Flat material.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
37/57
-
34 -
10.MIDJIL POWER PLANT - 10 MW
Each block with 12 rows has a motor for single axis tracking. Each row contains two
strings and each string contains 24modules in series. For every 8 strings i.e. 4 rows there
is one AJB (Array Junction Box). Number of inputs for AJB is 8 (+)inputs and 8 (-) inputsfrom total 8 strings
Fig: Internal circuit diagram of AJB
Fig: Internal circuit of AJB
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
38/57
-
35 -
Fig: Single axis tracking setup
DC supply from AJBs is given to inverter. In this plant centralized inverters are
used. Inputs from 16 AJBs are connected to one AJB. Inverter consists of three parts.
(i) DC section
(ii)
IGBT section(iii)AC section
In total there are 9 inverters. Capacity of each inverter is630kW.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
39/57
-36 -
DC to AC conversion happens in IGBT section. AC output from inverter is given to
380V/33kV transformer. Output from transformer is given to Ring Main Unit (RMU). Each
RMU has 1input and 2 outputs. Input terminal is connected to output of a transformer and one
of the output terminals of RMU isconnected to HT panel and the other is connected to RMU
of other transformer. The purpose of RMU is to form a ring busproviding an alternate path to
supply from transformer in case of any faulty condition that effects the connection between
transformer output and grid.
Fig: Ring Main Unit
HT panel is connected to switch yard which is installed withswitching devices and CTs
and PTs to measure energy being supplied to the grid.
Fig: Switchyard
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
40/57
-37 -
Protecting devices:
Lightning arrestors are installed for protection from lightning. In total there are 7
lightning arrestors.
Earthing is done to every AJB with GI Flat material andconnected to earth pit. Theseearth pits are internally connected to form a loop.
Fencing is done for protection from intruders.
SCADA system is also installed for identification of faults.
As of now generation of the plant is 6.5MW and construction for generation of
remaining 3.5 MW is under progression. PR of the plant is 82.07% and PLF is 24.56%- 30%.
The total area of plant is 68 acres.
Fig: Transformer
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
41/57
-38 -
Specifications:
kVA 2400
HV -33kV
Voltage at no-load LV1-380V
LV2-380V LV3-380 VRated current HV- 41.98ALV1- 1215.47ALV2- 1215.47ALV3-
1215.47A
Remote Terminal Units (RTU) are installed in all inverters and any fault at
inverter level can be identified by theoperator sitting in the control room with the help of
SCADA system.
Readings on SCADA monitor at the time of visit:
Day: 22 Dec 2014Time: 12:40 PM
Fig: Plant generation on the time of visit
Fig: Readings of one of the inverters
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
42/57
-
39 -
11. ANALYSIS OF SOLAR POWER PLANT
11.1 SOLAR PLANT PERFORMANCE INDEX
Evaluating technical performance of a solar power plant is veryimportant for the
growth of solar PV industry. There are two solarplant performance indices. They are:
1.
Plant Load Factor
2.
Performance Ratio
1.
PLANT LOAD FACTOR:
The ratio of the total number of kWh supplied by a generator orgenerating station to the
total number of kWh which would havebeen supplied if the generator or generating station
had been operated continuously at its maximum continuous rating is called Plant Load
Factor. This is also known as Capacity Utilization Factor (CUF). PLF of a plant will
generally be around 22%.
2.
PERFORMANCE RATIO:
The performance ratio is a measure of the quality of a PV plant that is independent of
location and it therefore often described as a qualityfactor. The performance ratio (PR) is
stated as percentage and describes the relationship between the actual and theoretical
energy outputs ofthe PV plant. It thus shows the proportion of the energy that is actuallyavailable for export to the grid after deduction of energy loss (e.g. due to thermal losses and
conduction losses) and of energy consumption for operation.
The closer the PR value determined for a PV plant approaches 100%,the more efficiently
the respective PV plant is operating. In real life, a value of 100% cannot be achieved, as
unavoidable losses always arisewith the operation of the PV plant (e.g. thermal loss due to
heating of the PV modules). High-performance PV plants can however reach a
performance ratio of up to 80%.
Performance Ratio (PR) of a plant for a period of time = Energy
measured (kWh)/
(Irradiance (kWh/m2) on the panel x Active area of
PV module (m2) x PV module
efficiency)
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
43/57
-
40 -
In the Indian solar context, CUF is perhaps the most overused word when it comes to
measuring a solar power plant performance. The interesting thing is, not many people
outside India understand the CUF because most of them use a much better metric
Performance Ratio (PR).
How CUF is calculated and how different it is from the globally accepted standard
of Performance Ratio (PR).
CHROSIS, a Germany based consulting firm, has published this excellent whitepaper on
the subject that gives some good insights on the subject.
Some of the highlights of the whitepaper are as follows:-
Capacity Utilisation Factor (CUF) =Energy measured (kWh) / (365*24*installed
capacity of the plant).So on one side, PR is a measure for the performance of a PV system taking into
account environmental factors (temperature, irradiation, etc.) and on the other side is
CUF that completely ignores all these factors and also the de-rating or degradation of the
panels.
Some more factors that can also be important when comparing PR vs. CUF:
PR will take into account the availability of the grid, CUF will not.
PR will take into account the minimum level of irradiation needed to generateelectrical energy, CUF will not.
PR will take into account irradiation levels at a given period of time, CUF will not
PR can be used as a tool to compare different solar PV systems with each other even
if they are located at different locations since all environmental factors will be taken into
account. Therefore only the design and the ability of the system to convert solar energy
into electrical energy will be compared with each other.
Therefore it is not convincing that the CUF is a good tool to provide insights into asolar PV system.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
44/57
-
41 -
An example of calculating PR:
To calculate the Performance Ratio (PR) of the installed 127 kWp SPVplant for January
Analysis period: Jan-2012
Measured total solar irradiation intensity in Jan-2012: 171 kWh/m2(Calculation below)
Generator area of the PV plant: 889 m2
Efficiency factor of the PV modules: 14.4%
Electrical energy actually exported by plant to grid: 16,833 kWh
PR= Actual reading of plant output in kWh p.m. / Calculated nominalplant output in
kWh p.m.
Calculated nominal plant output= Annual incident solar irradiation atthe generator surface
of the PV plant x relative efficiency of the PVplant modules=171 x 889 x 14.4%
=21,890 kWh
=> PR=16,833/21,890
=76.8%
Solar radiation data:
Jan-2012 Daily average solar intensity in W/m2
Day Average solar intensity in W/m2
1 251
2 258
3 257
4 242
5 171
6 221
7 242
8 184
9 251
10 225
11 105
12 241
13 244
14 243
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
45/57
-
42 -
15 209
16 220
17 229
18 247
19 239
20 229
21 233
22 238
23 256
24 255
25 252
26 250
27 241
28 245
29 194
30 227
31 230
Daily Average 230 W/m2
Jan Total- 230 x 24 hrs x 31 days=171 kWh/m2
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
46/57
-
43 -
11.2 POTENTIAL INDUCED DEGRADATION
Potential Induced Degradation is a very recent phenomenonthat has taken the solar
industry by surprise.
Introduction:Potential Induced Degradation (PID) is an undesirable property of some solar
modules. The factors that enable PID (voltage, heat andhumidity) exist on all photovoltaic
(PV) systems, but the effect doesnot occur on all or even most PV systems. According to
Dr. Peter Hacke of the National Renewable Energy Laboratory (NREL), All c-Si
[crystalline silicon] modules have elements of reversible and non- reversible [PID]
mechanisms. The key is to understand the extent towhich modules experience these
mechanisms.
PID was first recognized in the 1970s, and has been studiedsince. The rapid growth
in PV plant deployments, combined withdramatic reduction in module prices (and in some
cases, modulequality), has brought renewed interest in the phenomenon. Andbecause the
issue is highly technical, requiring at least someunderstanding of chemistry and physics, the
renewed interest hasbeen accompanied by substantial fear, uncertainty and doubt in the
market today.
The Causes of PID:
Potential Induced Degradation, as the designation implies, occurswhen the modules
voltage potential and leakage current drive ion mobility within the module between the
semiconductor material andother elements of the module (e.g. glass, mount and frame), as
shown in Figure 1, thus causing the modules power output capacity todegrade. The ion
mobility accelerates with humidity, temperature andvoltage potential. Tests have revealed
the relationship of mobility to temperature and humidity: Planar contact with the panel
surfacealso causes a capacitive coupling to the cells, resulting in a capacitiveleakage current
of varying strength. The PV system and environment interact to cause PID. Theconditions necessary for the occurrence ofPID involve:-
(i)
Environmental factors
(ii) System
(iii)Module
(iv) Cells.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
47/57
-
44 -
While the environment is set for each individual installation, it ispossible to prevent PID
by properly controlling only one of the factors
JOINT PRESS RELEASE FOR EU PVSEC 2011
Initial test conditions for potential induced degradation (PID) of solar modules developed
German testing institutes and solar companies present first step toward specific,
relevant PID test conditions
Test conditions make it possible to clearly, easily and quickly distinguish between
crystalline silicon modules that are stabilised against PID and those prone to PID
PVSEC Hamburg, 5 September 2011 Potential induced degradation (PID) has recently
been identified as a key factor impacting the energyyield of solar modules. Output of a solar
module can be reduced if themodule is exposed to high negative voltage between solar cells
and the ground during operation, especially in major plants. Basically, this effect is
reversible. It can also be avoided by implementing additionalsystem design measures. The
more economical option, however, isusing a technology that provides for modules or cells
that areresistantagainst PID.
A broadly accepted or even standardized test for PID resistance, which would
facilitate quick and easy assessment, is not available at present, though couple of solar
companies have obtainedPID test reports.Four independent institutes the Fraunhofer Institute for Solar Energy Systems
(ISE), Photovoltaic Institute Berlin (PI-Berlin), TV Rheinland and VDE Testing and
Certification Institute and theGerman Solar companies Q-Cells, Schott Solar and Solon
have defined conditions to test crystalline PV modules for their PID sensitivity. These
conditions were comprehensively checked for applicability andaccuracy in separating PID-
free products from items that are prone toPID.
The inspection was carried out at room temperature (25 Celsius) to provide a
simple test that would not require expensive special equipment. According to the
established parameters, negativevoltage of 1,000 volts is to be applied to the cells of a
module forseven days (168 hours) through the junction box.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
48/57
-
45 -
The front panels of all modules are covered with aluminiumfoil or a continuous
film of water and grounded, ensuring fullcomparability. A module will be deemed resistant
against PID ifpower output decreases by less than 5% during the test. Solon hadproduced
special modules that were prone to PID to confirm the test conditions relevance.
Significant losses in output were observedwhen testing these modules.When they were inspected at the institutes laboratories, PID-protected glass-
foil standard modules from series production atQ-Cells, Solon and Schott achieved output
reductions of less than 5%,proving that they are resistant against PID. A cross check with
an unrepresentative sample of modules from other brand manufacturers procured in the
market revealed a loss of output of significantly more than 50% for some modules. This
means a preliminary test design has been developed, which assesses crystalline solar
modules sensitivityto PID in a simple, specific and relevant manner and separatesmodules
that are prone to PID from their PID-resistant counterparts.
However, it is not yet possible to draw conclusions on the long-term
performance of installed modules on the basis of these test conditions, as it will largely
depend on module wiring and climaticfactors. The involved institutes and companies are
committed tofurther developing PID tests into a general standard.
Conclusion:
Potential Induced Degradation can have profound adverse impact on the financingand operating of PV plants. While the entirePV system interacts to cause PID, the failure
mode occurs in themodules. Fortunately PID does not occur in all modules, and tests are
available to determine whether modules are susceptible or resistant to the effect. Many
module manufacturers have taken steps toproduce PID resistant modules. And for existing
c-Si modules that do experience PID, the effect is usually reversible with cost-effective
mitigation measures.
Because mitigating PID in the PV plant can increase initial system costs, a judiciouschoice of resistant modules and otherpreventative efforts, within the constraints of each
individual system, may be warranted. But it is also possible, of course, to intentionally
design a new PV plant with modules susceptible to PID if the savings from using such
modules is greater than the mitigation measures required. Refer to the Mitigating Panel
Polarization application notefor options using Advanced Energy inverters.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
49/57
-
46 -
The best solution for the industry long-term is to minimize or eliminate PID by
making design changes at the system, module and/or cell levels. Until then, it will remain
important for operators to overcome any fear, uncertainty, and doubt by becoming more
knowledgeable about PID, and hopefully the information and references provided here
help achieve that objective.
11.3 Fill Factor Impact
The short-circuit current and the open-circuit voltage are themaximum current and
voltage respectively from a solar cell. However,at both of these operating points, the power
from the solar cell iszero. The "fill factor", more commonly known by its abbreviationFF",
is a parameter which, in conjunction with Voc and Isc, determinesthe maximum power from
a solar cell. The FF is defined as the ratio ofthe maximum power from the solar cell to the
product of Voc and Isc.Graphically, the FF is a measure of the "squareness" of the solar celland is also the area of the largest rectangle which will fit in the IVcurve. The FF is illustrated
below.
Graph of cell output current (red line) and power (blue line) asfunction of voltage.
Also shown are the cell short-circuit current (Isc)and open-circuit voltage (Voc) points, as
well as the maximum power point (Vmp
, Imp
). Click on the graph to see how the curve
changes for acell with low FF.
As FF is a measure of the "squareness" of the IV curve, a solar cellwith a higher voltage
has a larger possible FF since the "rounded" portion of the IV curve takes up less area. The
maximum theoreticalFF from a solar cell can be determined by differentiating the power
from a solar cell with respect to voltage and finding where this isequal to zero.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
50/57
-47 -
Hence:
However, the above technique does not yield a simple or closed formequation. Theequation above only relates Voc to Vmp, and extra equations are needed to find Imp andFF. A
more commonly usedexpression for the FF can be determined empirically as:
where Voc is defined as a "normalized Voc":
where n isIdeality factor
The above equations show that a higher voltage will have a higher possible FF.However, large variations in open-circuit voltage within a given material system are
relatively uncommon. For example, at onesun, the difference between the maximum open-
circuit voltagemeasured for a silicon laboratory device and a typical commercialsolar cell
is about 120 mV, giving maximum FF's respectively of 0.85 and 0.83. However, the
variation in maximum FF can be significant for solar cells made from different materials.
For example, a GaAs solarcell may have a FF approaching 0.89.
The above equation also demonstrates the importance of the ideality factor, alsoknown as the "n-factor" of a solar cell. The ideality factoris a measure of the junction quality
and the type of recombination in a solar cell. For the simple recombination mechanisms,
the n-factorhas a value of 1. However, some recombination mechanisms,particularly if they
are large, may introduce recombinationmechanisms of 2. A high n-value not only degrades
the FF, but since itwill also usually signal high recombination, it gives low open-circuit
voltages.
A key limitation in the equations described above is that theyrepresent a maximum
possible FF, although in practice the FF will be lower due to the presence of parasitic
resistive losses. Therefore, theFF is most commonly determined from measurement of the
IV curveand is defined as the maximum power divided by the product ofIsc*Voc, i.e.:
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
51/57
-
48 -
Influence of FF:
The picture below illustrates the I-V curves of both a high fill factorsolar panel and a
low fill factor panel.
As can be seen, both curves (solar panels) hold the same open circuitvoltage and
short circuit current, however, the lower fill factor panelactually produces less power at its
maximum power point comparedto the higher fill factor panel.
During the manufacture of commercial grade solar panels, each andevery single solar
cell is tested for its fill factor. If its fill factor is low(below 0.7), the cells are sold off as Grade-
B cells, then sliced, andused for hobbyist use.
To make things clearer, look at the picture below.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
52/57
-
49 -
We can see that the dummy power (or the theoretical power) is thearea in red, and
the actual power is the area in the blue. The fill factoris the ratio of the blue area to the red
area. The higher the fill factorofa solar panel, the closer the blue curve is to the red curve.
One can say that a higher FF solar panel has less parasitic losses, i.e.,losses due to theseries and parallel resistances within the cell itself.
When commercial solar panels are labelled, they take the FF intoaccount, and only
measure the real power. When hobby cells arelabelled, you will see that most of the time
they will just states theshort circuit current and open circuit voltage.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
53/57
-
50 -
12. CASE STUDY
OFF GRID SOLAR POWER PLANT DESIGN:
Location: Narketpally, Nalgonda Dist., Telangana.
Latitude and Longitude: 17.2 and 79.2 respectively.Area of the site: 8 acres.
Fig: Site layout
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
54/57
-
51 -
Solar PV system includes different components dependedon your system type, site
location and applications. The major components for solar PV system are solar charge
controller, inverter, battery bank, auxiliary energy sources and loads (appliances).
Total watt hours per day required on an average by allappliances in the nearby industry to
which power is to be supplied is 572500
The lowest month solar has a daily average of 4.1 kWh/ m2
/day and is observed in the
month of august.
This is equivalent to 4.1 hours of 1000 W/m2sunlight every day. Each Wp of the panel
would therefore deliver 4.1Wh/day.
Corrections that have to be considered include:
15% for temperature above 25 C 5% for losses due to sunlight not striking the panelstraight on (caused by glass
having increasing reflectance at lower angles of incidence)
10% for losses due to not receiving energy at the maximum power point (not
present if there is a MPPT controller)
5% allowance for dirt
10% allowance for the panel being below specification and for ageing
Total power = 0.85 x .95 x .90 x .95x .90 = 0.62 of the originalWp rating.
Accounting for losses, Panel Generation Factor (PGF) can be calculated as
4.1*0.62=2.54 Wh/Wp/day
Losses that have to be addressed by panel are
Wiring and connection losses about 10%
Losses in the battery about 20%
Total losses around 30%, so the panel will need to produce enough Wh/day for theload plus enough to cover the losses. So it will have to produce about 130% of the energy
required by the load
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
55/57
-
52 -
To calculate the Wh/day needed from the panel, multiply the load Wh/day times 1.3
Minimum Wp (peak wattage) of the plant needed to meet loadrequirement is
= 572500*1.3/PGF
= 572500*1.3/2.54
=293012
So capacity of solar plant can install is approximately293kW.
PV Module Specification:
Pmax (Wp) = 255.55
Vmax =31.42
Imax = 8.13A
Voc= 37.59 VIsc= 8.7116 A
FF= 78.04%
Efficiency= 15.7%
Total number of PV modules required = 293012/255.55
= 1146.82
= 1147 (approx.)
Two blocks can be designed each of 12 rows. Each row can be made of two strings
with each string comprising of 24 modules in series. This setup needs in total of 1152
modulesand it is always a better choice to use a bit more number of modules than required.
One motor can be used for each block for the purpose of single axis tracking. If we
consider 4 rows as a group, there are 6 groups in total and each group can be arranged with
oneAJB. So there are 6 AJBs in total. 8 strings connected to oneAJB are arranged in parallel
configuration.
ELECTRICAL CALCULATION
Output voltage of each string = 24*31.42 =754.08 V Output current of each string = 8.13 A
Output voltage of each group = 754.08 V Output current of each group = 8.13*8=65.04 A
Dc Output Calculation:
Output power of each string = 754.08*8.13=6130.67 W
Output power of each group = 754.08*65.04=49045.36 W Output power of 6 groups =
294.3 kW
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
56/57
-
53 -
Battery Size:
If battery of 48V is used
Battery Size (Ah) = (572500*1.3*1)/ (0.85*0.6*48) = 30402.4
Since formula for battery size is:
'0.85' accounts for battery losses 0.6 accounts for depth of discharge
Solar Charge Controller Sizing:
Its function is to regulate the voltage and currentfrom the solar arrays to the battery
in order to preventovercharging and also over discharging. According to standard practice,
the sizing of solar charge controller is to take the short circuit current (Isc) of the PV array,
and multiply it by 1.3
Solar charge controller sizing = Short circuit current of PV Array*1.3Isc of a module or
string = 8.7116 A
Number of strings = 48
Solar charge controller rating = 48*8.7116*1.3 =543.6 A
Inverter sizing:
An inverter is used in the system where AC power output is needed. Inverter cantolerate input up to 120% of itscapacity so a central inverter of size 280kW is suitable for
thispurpose.
-
7/24/2019 Solar Photovoltaics: Principles, Application and case study
57/57
13. CONCLUSION
Solar radiation data is available from several sources including satellite simulations.
The data collection and simulation is a complex procedure and can have inaccuracies
varying from 3-20%. The most reliable data isground measured with accurate instruments.Capacity utilization factor (CUF) depends on several factors including the solar
radiation,temperature, air velocity apart from the module type andquality, angle of tilt (or
tracking), design parameters to avoid cable losses and efficiencies of inverters and
transformers. There are some inherent losses which can be reduced through proper
designing but not completely avoided. It would be desirable to monitor the solar plant
installations and build updatabase for future work.
How to reasonably utilize green energy and keepsustainable development is themost important challenge. Solar Photovoltaic power plants will play an important role inthe
overall energy supply. The grid parity is likely to be achieved around 2017-2020. We should
grasp the opportunity to build the most suitable environmental friendly solar PV power
plants, and welcome a better tomorrow.