SMARTONLINE ® 3-PHASE UPS SYSTEMS • 380Y/220V, 400Y/230V or 415Y/240V The Most Reliable and Cost-Effective Power Solutions for Your Data Center SMARTONLINE KX2 SERIES (80-120 KVA) IDEAL OUTPUT POWER PROTECTS CRITICAL SYSTEMS MODULAR ARCHITECTURE ELIMINATES DOWNTIME SCALABLE DESIGN GROWS WITH YOUR DATA CENTER 1-TO-1 GENERATOR SIZING LOWERS INSTALLATION COSTS EXTREME EFFICIENCY LOWERS OPERATING COSTS SUPPORT UP TO 480 KVA IN PARALLEL

Transcript of SmartOnline 3-Phase KX2 230V Series UPS System · PDF fileredundant control circuits eliminate...

Page 1: SmartOnline 3-Phase KX2 230V Series UPS System · PDF fileredundant control circuits eliminate a single point ... 3525 3162 8700 7803 5288 4743 11599 14499 ... Advanced high-utilization

SMARTONLINE® 3-PHASE UPS SYSTEMS •380Y/220V,400Y/230Vor415Y/240V

The Most Reliable and Cost-Effective Power Solutions for Your Data Center

SMARTONLINE KX2 SERIES (80-120KVA)

IDEAL OUTPUT POWER PROTECTS CRITICAL SYSTEMS

MODULAR ARCHITECTURE ELIMINATES DOWNTIME

SCALABLE DESIGN GROWS WITH YOUR DATA CENTER

1-TO-1 GENERATOR SIZING LOWERS INSTALLATION COSTS

EXTREME EFFICIENCY LOWERS OPERATING COSTS

SUPPORT UP TO 480 KVA IN PARALLEL

Page 2: SmartOnline 3-Phase KX2 230V Series UPS System · PDF fileredundant control circuits eliminate a single point ... 3525 3162 8700 7803 5288 4743 11599 14499 ... Advanced high-utilization

SMARTONLINE KX2 SERIES UPS SYSTEMSExtremely efficient protection for your most important equipment

IDEAL OUTPUT POWER PROTECTS CRITICAL SYSTEMSOn-line, double conversion operation continuously

delivers precision-regulated, pure sine wave output,

isolating your critical systems from damaging and

disruptive power problems.

MODULAR ARCHITECTURE ELIMINATES DOWNTIMEInternal N+1 power module redundancy, parallel

capability (up to four units) and fault-tolerant bypass

features keep your critical systems highly available

and productive around the clock.

1-TO-1 GENERATOR SIZING LOWERS INSTALLATION COSTSAn advanced IGBT rectifier produces <4% THDi

(input Total Harmonic Distortion), eliminating costly

over-sizing requirements for generators, breakers

and cables.

SCALABLE DESIGN GROWS WITH YOUR DATA CENTER Models with less than 120 kVA capacity can be

expanded up to 120 kVA as infrastructure grows and

more equipment is added.

EXTREME EFFICIENCY LOWERS OPERATING COSTSEfficiency up to 97% significantly lowers power and

cooling costs compared to multiple smaller units or

legacy high-capacity units.

2

C O N T E N T S

SMARTONLINE KX2 SERIES UPS SYSTEMS

SU80KX2 80kVA/64kW

SU100KX2 100kVA/80kW

SU120KX2 120kVA/96kW

IDEAL OUTPUT POWER 3

MODULAR ARCHITECTURE 3

SCALABLE DESIGN 3

PARALLEL FEATURES 3

1-TO-1 GENERATOR SIZING 4

EXTREME EFFICIENCY 4

GREEN POWER 4

MONITORING AND CONTROL 5

BATTERY CABINETS 5

COMPACT FOOTPRINT 6

ORDERING INFORMATION 6

TECHNICAL SPECIFICATIONS 7

Page 3: SmartOnline 3-Phase KX2 230V Series UPS System · PDF fileredundant control circuits eliminate a single point ... 3525 3162 8700 7803 5288 4743 11599 14499 ... Advanced high-utilization

IDEAL OUTPUT POWERSmartOnline KX2 Series UPS Systems isolate your critical

equipment from power problems, including surges, line noise,

harmonic distortion, electrical impulses, frequency variations,

brownouts, overvoltages and blackouts. True on-line operation

continually transforms AC input power into filtered DC power,

then resynthesizes it into precision-regulated AC output with a

pure sine wave. Strong overload capacity supports up to 150%

output for up to 60 seconds. Reliable backup power with zero

transfer time to battery keeps equipment operating safely

through shorter power failures and allows time to shut down

or switch to generator power during longer outages. Rapid

recharging restores battery charge levels in as little as two

hours.

MODULAR ARCHITECTUREIntelligent, independent 20 kVA power modules provide internal

redundancy. When the UPS is configured for N+1 redundancy,

convenient hot-swap power modules can be replaced without

powering down the connected load. In the event of a power

module fault, the load is automatically distributed among

the remaining modules. Because load redistribution happens

without interrupting critical systems, mean time to recovery

is zero—far superior to legacy UPS systems. In addition,

redundant control circuits eliminate a single point of failure

commonly found in less-reliable UPS designs. Power module

installation is simple—each module is completely self-contained

and can be installed or removed in minutes using nothing

but a screwdriver.

If service or repair requires UPS shutdown, all models include

a manual bypass breaker and automatic bypass function that

maintain system availability by passing through AC power

until the UPS system returns to service.

SCALABLE DESIGNUPS systems in the KX2 Series with less than 120 kVA capacity

include empty slots to accommodate more 20 kVA power

modules. All systems can be upgraded to 120 kVA load

capacity, or six 20 kVA power modules. This scalable design

allows for capacity to be added slowly as the needs of your

data center grow, allowing more flexibility when selecting

a UPS, saving on up-front costs and facilitating

infrastructure planning.

PARALLEL FEATURESIncrease fault tolerance or quadruple output capacity by

connecting up to four SmartOnline KX2 Series UPS Systems

in parallel. If one UPS system is taken offline for maintenance,

the other UPS systems automatically compensate to

support the equipment load—without requiring

additional programming.

SmartOnline KX2 Series UPS Systems ship ready for parallel

operation. Patented dual-DSP technology provides optimal

synchronization of power sources.

External Battery Cabinet 120 kVA UPS System

100 kVALoad

20 kVARedundancy

20 kVAPower Module

20 kVAPower Module

20 kVAPower Module

20 kVAPower Module

20 kVAPower Module

20 kVAPower Module

MODULAR ARCHITECTUREINTERNAL N+1 REDUNDANCY

SCALABLE DESIGN GROWS WITH YOUR DATA CENTER

80 kVA UPS System

20 kVAPower Module

20 kVAPower Module

20 kVAPower Module

20 kVAPower Module

120 kVA UPS System

20 kVAPower Module

20 kVAPower Module

20 kVAPower Module

20 kVAPower Module

20 kVAPower Module

20 kVAPower Module

20 kVAPower Module

20 kVAPower Module

+ =

120 kVAUPS System

120 kVAUPS System

120 kVAUPS System

120 kVAUPS System

ExternalBattery Cabinet

80 kVAUPS System

ExternalBattery Cabinet

80 kVAUPS System

360 kVALoad

100% Support 100% Support

160 kVALoad

PARALLEL FOR N+1 REDUNDANCY

1+1 PARALLEL CAPACITY DOUBLING

ExternalBattery Cabinet

80 kVAUPS System

ExternalBattery Cabinet

80 kVAUPS System

100% Support 100% Support

160 kVALoad

PARALLEL TO MAXIMIZE CAPACITY

1+1 PARALLEL CAPACITY DOUBLING

120 kVAUPS System

120 kVAUPS System

120 kVAUPS System

120 kVAUPS System

480 kVALoad

Four 120 kVA SmartOnline KX2 Series UPS Systems can provide backup power for a 480 kVA load.

Four 120 kVA SmartOnline KX2 Series UPS Systems can provide redundant backup power for a 360 kVA load.

In an N+1 configuration, the supported load is at least 20 kVA less than the maximum output capacity of the UPS system. For example, a 120 kVA UPS is configured for N+1 redundancy when the connected load is 100 kVA or less.

SMARTONLINE KX2 SERIES UPS SYSTEMS

3

KX2 models with less than 120 kVA capacity can be expanded up to 120 kVA as infrastructure grows and more equipment is added.

Page 4: SmartOnline 3-Phase KX2 230V Series UPS System · PDF fileredundant control circuits eliminate a single point ... 3525 3162 8700 7803 5288 4743 11599 14499 ... Advanced high-utilization

1-TO-1 GENERATOR SIZINGSmartOnline KX2 Series UPS Systems

have a generator-friendly design that

decreases installation costs. A high input

power factor and IGBT rectifier with DSP

control create less than 4% input Total

Current Harmonic Distortion (THDi).

Low Current THDi enables cost-

saving 1-to-1 sizing of UPS systems to

generators, allows generators to run

cooler and extends the operational

lifespan of all input components.

Low Current THDi also reduces sizing

requirements for cables and breakers

and improves reliability by eliminating

nuisance breaker tripping and

overheated transformers.

2900

2601

17631

2

3

4

5

1581

5800

5202

3525

3162

8700

7803

5288

4743

11599

14499

13005

8813

7904

10404

7050

6323

CUMULATIVE ENVIRONMENTAL IMPACT OVER FIVE YEARS

Legacy UPS Energy Usage (MWh)

SmartOnline UPS Energy Usage (MWh)

Legacy UPS Carbon Emissions (Metric Tons)

SmartOnline UPS Carbon Emissions (Metric Tons)

GREEN POWEREfficient SmartOnline

KX2 Series UPS Systems

save energy and reduce

your carbon footprint.

Replacing 240 kVA of

legacy UPS capacity

can reduce CO2 emissions by 182 metric

tons and save 300 megawatt-hours* of

electricity per year—enough to power

24 single-family homes.

An extremely wide voltage correction

range reduces battery wear up to 40%,

so batteries last longer. Batteries are also

recyclable and contain a high percentage

of recycled materials, creating an efficient

manufacturing loop that conserves

resources and reduces landfill waste.

Tripp Lite also restricts

hazardous substances during

manufacture, maintaining

industry leadership in RoHS

compliance.

* 1 megawatt-hour = 3,6 gigajoules.

EXTREME EFFICIENCYAdvanced high-utilization IGBT inverter technology and high-speed DSP control

provide superior operating efficiency at all load levels—up to 97% in economy mode.

Increasing efficiency lowers UPS system operating costs by reducing electricity

consumption, heat emissions and cooling costs. Replacing up to 480 kVA of legacy

UPS capacity with SmartOnline KX2 UPS Systems can save more than US $60 000

per year.

In addition, SmartOnline KX2 Series UPS Systems automatically correct the widest

range of incoming voltages in their class. The wide voltage acceptance window and

temperature-compensated charging combine to decrease battery wear significantly,

extending service life and reducing replacement costs.

SmartOnline KX2 Series UPS Systems reduce installation

costs up to 30% versus legacy UPS systems.

INSTALLATION COST COMPARISON

Generators

Cabling

Breakers

Related Costs

Cost

Smar

tOnl

ine

KX

2Le

gac

y U

PS

Replacing 240 kVA of legacy UPS capacity with SmartOnline KX2 Series UPS Systems

can save 300 megawatt-hours* and reduce CO2 emissions by 182 metric tons

(enough to offset 3 000+ flights from London to Paris) per year.

4

Page 5: SmartOnline 3-Phase KX2 230V Series UPS System · PDF fileredundant control circuits eliminate a single point ... 3525 3162 8700 7803 5288 4743 11599 14499 ... Advanced high-utilization

Convenient communication and

management features allow you

to monitor power conditions,

receive automatic alerts and

control SmartOnline KX2 Series

UPS Systems with drift-proof digital

precision from any distance.

• CONTACTCLOSUREINTERFACE

Connects to an Emergency Power

Off (EPO) circuit for emergency

UPS system shutdown. Also allows

the UPS system to monitor

external battery cabinets and

communicate operational

messages.

• RS-232SERIALPORT

Connects to a server for shutdown

commands and reporting through

PowerAlert software (included).

• ACCESSORYCARDSLOT

Optional network card

(SNMPWEBCARD) provides

remote monitoring and control.

Optional environmental sensor

(ENVIROSENSE) monitors

temperature, humidity

and more.

• NETWORKPOWER

MANAGEMENT

You can manage UPS systems with

PowerAlert Network Management

System (included) or a third-party

network management system.

• LED/LCDCONTROLPANEL

Offers convenient push button

control and communicates

operational modes,

conditions and warnings.

BATTERY CABINETSAll SmartOnline KX2

Series UPS Systems

require an external

battery cabinet.

Additional battery

cabinets can be

connected to expand

runtime.

Real-Time Power Status Consoles

PowerAlert allows you to manage hundreds of UPS systems from a single workstation.

MONITORING AND CONTROL

BP480V55

The LED/LCD control panel provides detailed UPS status information.

5

POWERALERTNETWORKMANAGEMENTSYSTEM

LED/LCDCONTROLPANEL

The rear panel includes several communication interfaces.

NETWORKCONTROLINTERFACESNMPWEBCARD Slot

Input Dry Contact Interface

Parallel Configuration

Port

Parallel Configuration

Port

DIP Switches

RS-232 Serial Port

Output Dry Contact Interface

Page 6: SmartOnline 3-Phase KX2 230V Series UPS System · PDF fileredundant control circuits eliminate a single point ... 3525 3162 8700 7803 5288 4743 11599 14499 ... Advanced high-utilization

COMPACT FOOTPRINTEach SmartOnline KX2 Series UPS System provides more than

sufficient power for multiple racks of equipment while maintaining

a compact footprint, saving valuable data center floor space for

critical systems and cooling. Wall-mounted distribution and

bypass panels do not require additional floor space.

ORDERING INFORMATION

MODEL OUTPUT CAPACITY NOMINAL INPUT/OUTPUT VOLTAGE BATTERY CONFIGURATION

SU80KX2 80kVA/64kW 380Y/220V,400Y/230Vor415Y/240V(3ø,4-wire+ground)

No internal batteries; external battery cabinet required.

SU100KX2 100kVA/80kW 380Y/220V,400Y/230Vor415Y/240V(3ø,4-wire+ground)

No internal batteries; external battery cabinet required.

SU120KX2 120kVA/96kW 380Y/220V,400Y/230Vor415Y/240V(3ø,4-wire+ground)

No internal batteries; external battery cabinet required.

SU20KSPM 20kVA/16kW 380Y/220V,400Y/230Vor415Y/240V(3ø,4-wire+ground)

Independent power module; chassis and external battery cabinet required.

SU120KXNP ChassisforindividualSU20KSPMpowermodules.Holdsupto6for120kVAcapacity.

EXTERNAL BATTERY CABINETS (Hardwire connection. Multiple cabinets can be parallel connected for extended runtime.)

BP480V55+/-240VDCexternalbatterycabinet.Heavy-gaugesteelcabinetwith10-yeardesignlifebatteries. (Seewww.tripplite.comforruntimeandloadsupportdata.)

BP480V78+/-240VDCexternalbatterycabinet.Heavy-gaugesteelcabinetwith10-yeardesignlifebatteries. (Seewww.tripplite.comforruntimeandloadsupportdata.)

BP480V103+/-240VDCexternalbatterycabinet.Heavy-gaugesteelcabinetwith10-yeardesignlifebatteries. (Seewww.tripplite.comforruntimeandloadsupportdata.)

BP480V140+/-240VDCexternalbatterycabinet.Heavy-gaugesteelcabinetwith10-yeardesignlifebatteries. (Seewww.tripplite.comforruntimeandloadsupportdata.)

WALL-MOUNTED EXTERNAL MAINTENANCE BYPASS PANELS WITH KEYED SAFETY INTERLOCK SYSTEM

SU80KMBPKX MaintenancebypasspanelforSU80KX2only.Kirk-keyedsafetyinterlocksystempreventssequence

of operation errors.

SU120KMBPKX MaintenancebypasspanelforSU100KX2andSU120KX2.Kirk-keyedsafetyinterlocksystemprevents

sequence of operation errors.

WALL-MOUNTED PARALLEL DISTRIBUTION PANELS (Required for parallel connection of UPS systems.)

SUPCXMBP80KX ParalleldistributionpanelforparallelconnectionofSU80KXorSU80KX2models.(Xcanbe2,3or4)

SUPCXMBP120KX ParalleldistributionpanelforparallelconnectionofSU100KX2orSU120KX2models.(Xcanbe2,3or4)

POWER MANAGEMENT ACCESSORIES

SNMPWEBCARD AddsEthernetnetworkinterfacetoUPSsystemforremotemonitoringandcontrolviaSNMP,Webortelnet.

MODBUSCARD AddsModbusinterfacetoUPSsystemsforremotemonitoringandcontrolviaModbusprotocol.

RELAYIOCARD AddscontactclosureinterfacetoUPSsystemsandallowscommunicationofstatusviasixconfigurable

contact closure outputs.

ENVIROSENSE Monitors temperature and humidity. Monitors up to three additional sensors via contact closure interface.

Requires SNMPWEBCARD.

WARRANTIES AND SERVICES

Sitesurveyservices,start-upservices,preventivemaintenanceservices,extendedwarrantiesandon-sitewarrantiesareavailable.

Visitwww.tripplite.comorcontactyourTrippLitesalesrepresentativeformoreinformation.

6

Page 7: SmartOnline 3-Phase KX2 230V Series UPS System · PDF fileredundant control circuits eliminate a single point ... 3525 3162 8700 7803 5288 4743 11599 14499 ... Advanced high-utilization

INP

UT

MODEL SU80KX2 SU100KX2 SU120KX2

NOMINAL VOLTAGE User-selectable380Y/220V,400Y/230Vor415Y/240V(3ø,4-wire+ground)

VOLTAGE RANGE Fullload:300Y/173Vto477Y/276V(-25%/+20%@400Y/230V)

≤70%Load:208Y/120Vto477Y/276V(-48%/+20%@400Y/230V)

CURRENT THDi (Full Load) <4%

POWER FACTOR (On-line, Full Load) >0,99

FREQUENCY (Auto-Selectable) 50/60Hz

FREQUENCY TOLERANCE ±5%

NOMINAL CURRENT

(@ 380/400/415 VAC, Per Phase)

103/99/95A (121/115/111Amaxwithcharger)

129/123/116A (152/144/139Amaxwithcharger)

155/148/142A (182/173/167Amaxwithcharger)

OU

TPU

T

CAPACITY (kVA/kW) 80/64 100/80 120/96

POWER FACTOR 0,8PerPhase

NOMINAL VOLTAGE User-selectable380Y/220V,400Y/230Vor415Y/240V(3ø,4-wire+ground)

FREQUENCY 50/60Hz±0,05Hz

NOMINAL CURRENT

(@ 380/400/415 VAC, Per Phase) 121/115/111A 152/144/139A 182/173/167A

WAVEFORM (On-line or Battery) Pure Sine Wave

VOLTAGE THD (Linear Load) <3%

VOLTAGE REGULATION (Static) ±1%

VOLTAGE REGULATION (Dynamic) Maximum7%Deviation

OVERLOAD CAPACITY ≤125%for10minutes;≤150%for60seconds

BR

EA

KE

RS

RECTIFIER (3-Pole, 600 VAC)**

150A 200A 225ABYPASS (3-Pole, 600 VAC)**

RESERVE (3-Pole, 600 VAC) **

OUTPUT (3-Pole, 600 VAC)**

BATTERY BATTERY (± 240VDC, Max

Current Draw at Full Load)** 165A 206A 247A

RECOMMENDED MINIMUM OCPD RATING** 150A 200A 225A

GE

NE

RA

L

STANDARD INTERFACE LED/LCDControlPanel,RS-232,ContactClosure,EPO(LocalandRemote)

OPTIONAL INTERFACE SNMPWEBCARD,ENVIROSENSE,RELAYIOCARD,MODBUSCARD

UPS TOPOLOGY TrueOn-line,DoubleConversion;Voltage/FrequencyIndependent(VFI-SS-111) Operation; Complies with EU Directives (EN62040-3)

AGENCY APPROVALS CE(CompliantwithEN62040-1-2,EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5, IEC61000-4-6),RoHS

EFFICIENCY (AC-AC) NormalMode:Upto94%/EconomyMode:Upto97%

TRANSFER TIME (Normal Mode) 0ms

AMBIENT OPERATING TEMPERATURE 0°Cto40°C(32°Fto104°F)

ELEVATION 0to3000m(0to10000ft)

HUMIDITY (Non-Condensing) ≤90%

AUDIBLE NOISE (@ 1 m) <70dBA

TYPICAL RUNTIME* (Half/Full Load) 28/10+min. (WithBP480V55)

20/7.6+min (WithBP480V55)

15/5.9+min (WithBP480V55)

DIMENSIONS (Power Module)

Height 1697mm(66,8in)

Width 521mm(20,5in)

Depth 975mm(38,4in)

UNIT WEIGHT (Power Module) 319kg (703lb)

347,5kg (766lb)

379,2kg (836lb)

SHIPPING WEIGHT (Power Module) 411,5kg (907lb)

441,5kg (973lb)

473,2kg (1043lb)

*Runtime varies with load, battery condition and other factors. Runtime can be extended by connecting additional external battery cabinets, sold separately. ** Breakers sized to configured load. If adding modules, size accordingly.

TECHNICAL SPECIFICATIONS

7

Page 8: SmartOnline 3-Phase KX2 230V Series UPS System · PDF fileredundant control circuits eliminate a single point ... 3525 3162 8700 7803 5288 4743 11599 14499 ... Advanced high-utilization

Tripp Lite’s 3-Phase PDUs offer reliable power distribution and monitoring in

high-voltage, high-density applications requiring 3-phase power service and are

compatible with all 3-phase UPS systems.

• METERED PDUs support real-time local-monitoring of load level.

• MONITORED PDUs support real-time remote monitoring of load level,

voltage and frequency with options for environmental and

security monitoring.

• SWITCHED PDUs support remote individual outlet control, monitoring

of output load level per outlet or per load bank, input voltage and frequency

reporting with options for environmental and security monitoring.

TRIPP LITE 3-PHASE POWER DISTRIBUTION UNITS

ABOUT TRIPP LITESince1922,TrippLitehasestablishedaglobalreputationfor

qualitymanufacturing,superiorvalueandexcellentservice.

TrippLitemakesmorethan2500productstopower,protect

andconnectelectronicequipment,includingUPSsystems,

replacementbatteries,powerdistributionunits,racksystems,

surgesuppressors,KVMswitches,cables,laptopaccessories,

power strips and inverters. Learn more at www.tripplite.com.

Copyright © 2013 Tripp Lite. All trademarks are the sole property of their respective owners. Tripp Lite has a policy of continuous improvement.

Specifications are subject to change without notice. Photos may differ slightly from actual products. 13-06-040 95-33CE

TRIPP LITE WORLD HEADQUARTERS 1111W.35thStreet,Chicago,IL60609USA,+1.773.869.1212,www.tripplite.com

TRIPP LITE MIDDLE EAST +971.4.887.1633•[email protected]•TRIPP LITE ASIA PACIFIC+972.54.2057646•[email protected]

TRIPP LITE EASTERN EUROPE+36.1.203.7941•[email protected]•TRIPP LITE EAST/WEST AFRICA+254.731.137.202•[email protected]

TRIPP LITE SOUTH AFRICA+27.82.8099.043•[email protected]•TRIPP LITE WESTERN EUROPE+33.1.70.61.77.85•[email protected]

TRIPP LITE UNITED KINGDOM +44.01635.887396•[email protected]

COMPLETE DATA CENTER SOLUTIONSProtect, manage and power your application with complete solutions from a single, trusted source.

UPS Systems

• Network-grade power protection for large data centers

• On-line,double-conversionoperation with pure sine wave output

• N+1powermoduleredundancy, parallel capability and expandable runtime.

KVMs

• Consolidated,centralized device management with improved security and availability.

• Built-inLCD consoles, Cat5 cabling, IP remote access with multiuser support and other advanced features available.

• Ruggedmetalconstructionand simple installation.

Bypass Panels & Accessories

• Wall-mount manual bypass panels isolate UPS systems from connected loads for maintenance with no loss of network availability.

• IncludedKirk-Key interlock system enhances system reliability.

• Heavy-dutybusworkandthreebuilt-in circuit breakers.

• CompatiblewithTrippLite3-phase UPS systems.

3-PHASE PDU FEATURES BY GROUPING

MeteredPDUs MonitoredPDUs SwitchedPDUsDistributePowerto Multiple Devices (Multiple Outlets) • • •

LocallyViewPDULoad(Digital Load Meter) • • •

RemotelyViewPDULoadand Alarm Conditions (Network Interface/Software) • •

RemotelyControlIndividual Outlets (Network Interface/Software/Switchable Outlets) •