Sistema Rectificador Flatpack 2

76
> SISTEMA FLATPACK 2 José Rodas Utani Jefe de Servicios & Soporte Técnico Perú, Ecuador y Bolivia

Transcript of Sistema Rectificador Flatpack 2

Page 1: Sistema Rectificador Flatpack 2

>

SISTEMA FLATPACK 2

José Rodas Utani

Jefe de Servicios & Soporte Técnico

Perú, Ecuador y Bolivia

Page 2: Sistema Rectificador Flatpack 2

Slide 2 of 23 08.04.23

Page 3: Sistema Rectificador Flatpack 2

Slide 3 of 23 08.04.23

Generation 4Generation 4

Page 4: Sistema Rectificador Flatpack 2

Slide 4 of 23 08.04.23

Generation 1

Generation 3

Generation 4

1. Highest Power Density1. Highest Power Density

5W/in3

1995

2000

2005

SMPS 60/20

SMPS 1000

Flatpack 1800

2010

FP2 1800

10W/in3

15W/in3

20W/in3

25W/in3

FP2 2000

Flatpack 1500

Saves the customer money by :- More space for customer equipment and/or batteries- Thus less cabinets and less footprint in the location

33W/in3FP2 3000

Page 5: Sistema Rectificador Flatpack 2

Slide 5 of 23 08.04.23

1. Highest Power Density – FP2 2KW SHELF1. Highest Power Density – FP2 2KW SHELF

Modular Configuration 48 VDCModular Configuration 48 VDC

167A Maximum Per Shelf

125A Redundant

With four rectifiers installed

DimensionsDimensions

17.5” Wide –

brackets mount 19”, 21” or 23”

14.5” Deep

1U – 1.75” Height

Page 6: Sistema Rectificador Flatpack 2

Slide 6 of 23 08.04.23

1. Highest Power Density – FP2 3KW SHELF1. Highest Power Density – FP2 3KW SHELF

Modular Configuration 48 VDCModular Configuration 48 VDC

250A Maximum Per Shelf

187,5A Redundant

With four rectifiers installed

DimensionsDimensions

17.5” Wide –

brackets mount 19”, 21” or 23”

17” Deep

1U – 1.75” Height

Page 7: Sistema Rectificador Flatpack 2

Slide 7 of 23 08.04.23

2. Pequeño y ligero 2. Pequeño y ligero

< 1.9 Kg

- Personal de mantenimiento - especialmente como repuestos - Logística - un peso más ligero, significa menos costos de envío

41.5mm

109 mm

327 mm

Más fácil para dirigir :

Page 8: Sistema Rectificador Flatpack 2

Slide 8 of 23 08.04.23

3. Operación de los ventiladores3. Operación de los ventiladores

2 Fans – Front to back airflow - will work with only one

(Back to front version in design stage)

• Evitar las salidas de llamadas de prioridad (fuera de horas normales) - Da una alta eficacia del rectificador

Ahorros por costos de mantenimiento y operación por :

Page 9: Sistema Rectificador Flatpack 2

Slide 9 of 23 08.04.23

4. Controles digitales4. Controles digitales

2 controlador digital : Dan mas supervisión y control.

- Dando al operadores una información más en tiempo real del sistema

- El personal de mantenimiento sabe exactamente qué necesita hacer con las ayudas.

Ahorro de tiempo y dinero por :

Page 10: Sistema Rectificador Flatpack 2

Slide 10 of 23 08.04.23

5. Edge connectors5. Edge connectors

Edge-connector technology

- Módulos intercambiables en caliente.- Reduce fallas de interconexión.

Ahorra tiempo (y dinero) :

AC Input

Communications

DC Output

Page 11: Sistema Rectificador Flatpack 2

Slide 11 of 23 08.04.23

6. Amplio Rango de entrada CA 6. Amplio Rango de entrada CA

85V 185 290

650W

0W

NominalInput

Red LED Yellow LED Red LEDGreen LED

1800W2000W

850W

300

Output Power vs. Input voltage

Page 12: Sistema Rectificador Flatpack 2

Slide 12 of 23 08.04.23

6. Large AC input range6. Large AC input range

Mains derating

0

20

40

60

80

100

120

0 50 100 150 200 250 300 350

Voltage (Vac)

Ou

tpu

t P

ow

er (

%)

FP2 48/2000 FP2 48/3000

> Derating below 176Vac (185Vac on 2kW module)

> 1382W (46%) at 85Vac

Page 13: Sistema Rectificador Flatpack 2

Slide 13 of 23 08.04.23

7. Temperatura De-rating7. Temperatura De-rating

+45o

2000W

1400W

0W+75o

Yellow LED Red LEDGreen LED

1800W

1200W

Temperatura ambiente (max full carga de salida)

LinearDe-rating Zone

Page 14: Sistema Rectificador Flatpack 2

Slide 14 of 23 08.04.23

7. Temperature De-rating7. Temperature De-rating

> Derating above 45 oC

> 2100W (67%) at 75 oC

> Delivers 50A at 65 oC

> Operating down to -40 oC

Temperature derating

0

20

40

60

80

100

120

0 10 20 30 40 50 60 70 80

Ambient temperature

Ou

tpu

t P

ow

er (

%)

FP2 48/2000 FP248/3000

Page 15: Sistema Rectificador Flatpack 2

Slide 15 of 23 08.04.23

8. Excelente protección en AC/DC8. Excelente protección en AC/DC

Mains fuse: 2x15 A (fast) in Live and Neutral

Varistor across the lines for transient

protection

Hi -ohmic disconnect above 290V / 300V AC

(with auto reconnect when in range)

DC Output· Short circuit proof

(constant current)

· Single or double fan blockage/failureDC output : Blocking Diode

Page 16: Sistema Rectificador Flatpack 2

Slide 16 of 23 08.04.23

9. Highly Efficient – 2 KW9. Highly Efficient – 2 KW

MaxEfficiency

Zone

2000W rectifier : Efficiency at 230Vac input

90

90,5

91

91,5

92

92,5

93

0 200 400 600 800 1000 1200 1400 1600 1800 2000

Pout(W)

Eff.

(%)

Page 17: Sistema Rectificador Flatpack 2

Slide 17 of 23 08.04.23

9. Highly Efficient – 3 KW9. Highly Efficient – 3 KW

> Efficiency above 93% at 40-80% load, 92.4% at 100% load

> 10% loss reduction on system level

> Low load efficiency also improved

86

87

88

89

90

91

92

93

94

0 10 20 30 40 50 60 70 80 90 100

Load (%)

Eff

icie

ncy

(%)

3000W

2000W

Page 18: Sistema Rectificador Flatpack 2

Slide 18 of 23 08.04.23

9. Highly Efficient – 2 KW HE9. Highly Efficient – 2 KW HE

Page 19: Sistema Rectificador Flatpack 2

Slide 19 of 23 08.04.23

Technical Data – 24V 2000 WTechnical Data – 24V 2000 W

Page 20: Sistema Rectificador Flatpack 2

Slide 20 of 23 08.04.23

Technical Data – 48 V 1800 WTechnical Data – 48 V 1800 W

Page 21: Sistema Rectificador Flatpack 2

Slide 21 of 23 08.04.23

Technical Data – 48 V 2000 WTechnical Data – 48 V 2000 W

Page 22: Sistema Rectificador Flatpack 2

Slide 22 of 23 08.04.23

Technical Data – 48 V 3000 WTechnical Data – 48 V 3000 W

Page 23: Sistema Rectificador Flatpack 2

Slide 23 of 23 08.04.23

Technical Data – 48 V 2000 W HETechnical Data – 48 V 2000 W HE

Page 24: Sistema Rectificador Flatpack 2

Slide 24 of 23 08.04.23

Procedimiento de instalaciónProcedimiento de instalación

Handle in locked

positionHole to release

the handle’s spring

mechanism

Handle in unlocked position

Page 25: Sistema Rectificador Flatpack 2

Slide 25 of 23 08.04.23

Panel FrontalPanel Frontal

Dual Fan Cooling RED Alarm LED

YELLOWYELLOW Warning LEDGREENGREEN Power LED

Page 26: Sistema Rectificador Flatpack 2

Slide 26 of 23 08.04.23

Panel FrontalPanel Frontal

Power (green) ON Rectifier is powered

 Flashing

Smartpack controller accessing information on the rectifier

 OFF Mains are unavailable

Page 27: Sistema Rectificador Flatpack 2

Slide 27 of 23 08.04.23

Panel FrontalPanel Frontal

Warning (yellow)

ON

      Rectifier is in Derating Mode (reduced output power) high internal temperature (+65 to 70 C) orlow input voltage (lower than 176VAC) or

single fan failure      The remote Battery Current Limit is activated

     AC input voltage is out of range       Rectifier in stand-alone mode (or loss of

communication with the Smartpack controller

 Flashing Rectifier is in Over-voltage Protection Mode

 OFF No abnormal situation is present

Page 28: Sistema Rectificador Flatpack 2

Slide 28 of 23 08.04.23

Panel FrontalPanel Frontal

Alarm (red)

ON

      Rectifier is in Shut-down Mode due to low mains (0 – 85VAC) or

high internal temperature (+75 C or higher) orhigh output voltage (higher than 59.5 VDC)

     Internal rectifier failure (malfunction)      Fan failure (double fan malfunction)      Low output voltage (0 to 43.5VDC)

      CAN bus failure

 OFF No alarm situation is present

Page 29: Sistema Rectificador Flatpack 2

Slide 29 of 23 08.04.23

Unidad de ControlUnidad de Control

> Scaleable y modular, control flexible para la gama entera de productos Eltek

Page 30: Sistema Rectificador Flatpack 2

Slide 30 of 23 08.04.23

Unidad de ControlUnidad de Control> Front panel backlit LCD (2x16) and key pad

> USB for PC connection and easy FW uploading

> CAN bus para comunicacion con modulos Eltek

> 6 entradas digitales programables

> 6 relay de salidas configurables

> Latched contactor control

> Monitoreo y test de baterias

> Compensacion de carga por temperatura

> 8 symmetry measurements

> log de eventos(10000) con hora y fecha.

> Windows-based PC communication software

Page 31: Sistema Rectificador Flatpack 2

Slide 31 of 23 08.04.23

Pequeño pero de gran alcance Pequeño pero de gran alcance

44mm

109 mm

144 mm

< 300g

Page 32: Sistema Rectificador Flatpack 2

Slide 32 of 23 08.04.23

Smartpack Vista Frontal

> ”Top-level alarms” scrolls on display when active• Battery, Load, Rectifier, Control System & Mains

> Alarm LED (red) = Major Alarm active

> Warning LED (yellow) = Minor Alarm active

> Power LED (green) = Normal status active

Page 33: Sistema Rectificador Flatpack 2

Slide 33 of 23 08.04.23

Panel TraseroCAN BusPanel TraseroCAN Bus

CAN bus

Part No : 242100.110(RoHS compliant)

•ID based serial bus communications

•Max 8 Smartpack

•Max 50 Rectifiers

Page 34: Sistema Rectificador Flatpack 2

Slide 34 of 23 08.04.23

Panel TraseroMonitoreo de BateríasPanel TraseroMonitoreo de Baterías

Monitoreo de Baterías

Part No : 242100.110(RoHS compliant)

Con 4 : StandardCon 3 : Extended

• Symmetry measurement

• 8 strings mid point or2 strings 12V block

• Sensor de Temp.

Page 35: Sistema Rectificador Flatpack 2

Slide 35 of 23 08.04.23

ConectividadBateríaConectividadBatería

> CON3 & CON4 – Conexiones de baterías

Cable Sensor de Temperatura

Pin Function

1 Symmetry I/P 1

2 Symmetry I/P 2

3 Symmetry I/P 3

4 Symmetry I/P 4

5 Symmetry I/P 5

6 Symmetry I/P 6

7 Symmetry I/P 7

8 Symmetry I/P 8

9-10 Con 3 : Temp sense 2

Con 4 : Temp sense 1

11 - 14 Con 3 – 2nd batt current, batt fuse

Con 4 : Not used

Page 36: Sistema Rectificador Flatpack 2

Slide 36 of 23 08.04.23

Conectividad - Batería> CON3 & CON4 – Conexión de batería

Page 37: Sistema Rectificador Flatpack 2

Slide 37 of 23 08.04.23

> Symmetry measurement options

ConectividadSymmetryConectividadSymmetry

Page 38: Sistema Rectificador Flatpack 2

Slide 38 of 23 08.04.23

Panel TraseroSistema internoPanel TraseroSistema interno

Sistema Interno

Part No : 242100.110(RoHS compliant)

System measurements

Unit Power

2xLVD control (Latched)

Battery fuse fail

Page 39: Sistema Rectificador Flatpack 2

Slide 39 of 23 08.04.23

Conectividad SistemaConectividad Sistema

> CON5 – Conexión del sistemaPin Function

1 Positive Input

2 Negative Input

3 Batt Current +ve

4 Batt Current -ve

5 Batt Fuse +ve

6 Batt Fuse -ve

7 Load Fuse Fail

8 LVD1 Active

9 LVD1 Common

10 LVD2 Active

11 LVD2 Common

System Connection Card. Art 200625

Page 40: Sistema Rectificador Flatpack 2

Slide 40 of 23 08.04.23

ConectividadSistemaConectividadSistema

> Sistema de Configuración de la tarjeta

JP1-48v system = 1-2 +24v system = 2-3

JP2-48v system = ‘Neg’+24v system = ‘Pos’

Page 41: Sistema Rectificador Flatpack 2

Slide 41 of 23 08.04.23

Panel TraseroAlarmas I/OPanel TraseroAlarmas I/O

Alarma I/O

Part No : 242100.110(RoHS compliant)

Con 1 (standard):-

2 + 2 relay input / output

Con 2 (extended):-

4 + 4 relay input / output

Page 42: Sistema Rectificador Flatpack 2

Slide 42 of 23 08.04.23

ConectividadExterna y Alarm I/OConectividadExterna y Alarm I/O

> CON1 & CON2 – I/O Conexiones Pin Function

1 - 2 Alarm input 1 ( + / -)

3 – 4 Alarm input 2 ( + / -)

5 - 7 Alarm output 1 ( NO /C / NC)

8 - 10 Alarm output 2 ( NO /C / NC)

1 - 2 Alarm input 3 ( + / -)

3 - 4 Alarm input 4 ( + / -)

5 - 6 Alarm input 5 ( + / -)

7 - 8 Alarm input 6 ( + / -)

9 - 11 Alarm output 3 ( NO /C / NC)

12 - 14 Alarm output 4 ( NO /C / NC)

15 - 17 Alarm output 5 ( NO /C / NC)

18 - 20 Alarm output 6 ( NO /C / NC)

Alarm Output & Input CardArt 105954

Page 43: Sistema Rectificador Flatpack 2

Slide 43 of 23 08.04.23

RS-232 OpcionesRS-232 Opciones

RS-232 mounted

Part No : 242100.111(RoHS compliant)

•Enables connection of Standalone Webpower or modem

•Rear position : Replaces extended Battery symmetry card

Part No : 242100.112(RoHS compliant)

Page 44: Sistema Rectificador Flatpack 2

Slide 44 of 23 08.04.23

Smartpack

Smartpack Extended RS232

Page 45: Sistema Rectificador Flatpack 2

Slide 45 of 23 08.04.23

Panel TraseroWebpower incluidoPanel TraseroWebpower incluido

Embedded

WebPower

Part No : 242100.113(RoHS compliant)

Ethernet interface of remote monitoring of SmartpackIs possible to “tunnel” Powersuite remotely also.

Page 46: Sistema Rectificador Flatpack 2

Slide 46 of 23 08.04.23

Smartpack

Smartpack SNMP/Webpower

Page 47: Sistema Rectificador Flatpack 2

Slide 47 of 23 08.04.23

EscalabilidadEscalabilidad

Smartpack MasterSmartpack Slave n

System functionalityVoltage input 1

Symmetry inputs 8 (2x4x12V)

Current inputs 2

Temperature inputs 2

General purpose inputs 6

Load fuse input 1

Batt fuse input 2

Relay outputs 6

Contactor control 2+

System functionalityVoltage inputs 2

Symmetry inputs 16 (4x4x12V)

Current inputs 4

Temperature inputs 4

General purpose inputs 12

Load fuse input 2

Batt fuse input 4

Relay outputs 12

Contactor control 4+

System functionality with 8 modulesVoltage inputs 8

Symmetry inputs 64 (16x4x12V)

Current inputs 2x8

Temperature inputs 2x8

General purpose inputs 6x8

Load fuse input 1x8

Batt fuse input 2x8

Relay outputs 6x8

Contactor control 2+x8

Smartpack Slave 1

CAN/Power bus

Page 48: Sistema Rectificador Flatpack 2

Slide 48 of 23 08.04.23

ConectividadLatched ContactorsConectividadLatched Contactors

A latching contactor changes state only when a reversed pulse voltage is applied to the coil.

Protection Diode

Page 49: Sistema Rectificador Flatpack 2

Slide 49 of 23 08.04.23

> Explorer oriented easy to use PC SW

> USB gives simple access.

> Wide functionality with clear graphic presentation.

PowerSuitePowerSuite

Page 50: Sistema Rectificador Flatpack 2

Slide 50 of 23 08.04.23

Smartpack Front / Power SuiteContent

> Front menu

> Password levels

> Alarm ”monitor”

> AlarmGroups and output (relay) mapping

> ”Programmable” inputs

> Event log

> Operational mode and ”Critical” conditions

> Low Voltage Disconnect (LVD)

> Battery functions• Battery discharge test• Test results• Battery tables• Temp. comp & Charge curr. limitation• Test results• Special monitors• Boost• Symmetry

> Calibration & shunt Scaling

> Rectifier ID’s

> Mains measurement

> PowerSuite installation and basic introduction

Page 51: Sistema Rectificador Flatpack 2

Slide 51 of 23 08.04.23

Niveles de acceso

> Smartpack/PowerSuite password• 4 digit pin-code

> Nivel de usuario• No password

> Novel de Servicio• Password: ”0003” (default)

> Nivel de Fabrica • Password:

> Si perdió la contraseña de servicio, envíe el numero de serie a fabrica, para poder enviar ”PUK-code” de retorno.

Page 52: Sistema Rectificador Flatpack 2

Slide 52 of 23 08.04.23

Smartpack menu frontal

Option Description

NomVolt Nominal output voltage

BoostVolt Battery boost-charging voltage

LowBatt1 Voltage limit for MinorLow Battery Alarm

LowBatt2 Voltage limit for MajorLow Battery Alarm

HighBatt1 Voltage limit for MinorHigh Battery Alarm

HighBatt2 Voltage limit for MajorHigh Battery Alarm

LVBD Voltage limit for Low Voltage Battery Disconnect (LVBD)

LVLD 1.1 Voltage limit for Low Voltage Load Disconnect (LVLD)

> VoltageInfo - details

Page 53: Sistema Rectificador Flatpack 2

Slide 53 of 23 08.04.23

Smartpack menu frontal

> RectifierInfo - details

Option Description

NoOfRects. Number of rectifiers installed in the system.

RectCurrent Rectifier current

RectSerialNumber Rectifier ID and serial number

Rect.PrimaryVolt Rectifier input mains voltage

Rectifier Status Rectifier status

Rectifier Temp Rectifier temperature

Page 54: Sistema Rectificador Flatpack 2

Slide 54 of 23 08.04.23

Alarm ”monitor” cont’

Page 55: Sistema Rectificador Flatpack 2

Slide 55 of 23 08.04.23

Entradas programables

> 6 entradas digitales programables.

Page 56: Sistema Rectificador Flatpack 2

Slide 56 of 23 08.04.23

Entradas programables> Input ”Monitor”

• Event is selectable in ”drop-down-list”- Not all activates a function (yet...)

• Description may be changed

> Description and Event text listed in Event log

Page 57: Sistema Rectificador Flatpack 2

Slide 57 of 23 08.04.23

Log de Eventos

> Smartpack front: ”DisplayMessages”

> PowerSuite: “Event Log”

> El Smartpack controlador puede almacenar hasta 1000 eventos cronológicos. Cuando el registro esta lleno, se sobre escribe el más viejo evento.

> El registro se almacena en EEPROME

Ejemplo• 27-09-2005 (Date ”dd-mm-yyyy”)

• 17:15 (Time ”hh:mm”)

• Battery Voltage (Monitor name/Description)

• MinorLow: ON (Event status in monitor)

Page 58: Sistema Rectificador Flatpack 2

Slide 58 of 23 08.04.23

Desconexión por bajo voltaje (LVD)

> Se toma la acción de desconexión cuando el sistema está en “crítico” y:

- El voltaje de la batería esta debajo del limite.

- Delay time ha expirado, si es activo.

> Volver a conectar se toma cuando el sistema “NO es crítico” y:

- El voltaje de la batería está sobre límite.

> Default hysteresis entre reconexión y desconexión es de 4V

Page 59: Sistema Rectificador Flatpack 2

Slide 59 of 23 08.04.23

Funciones de Batería Test de Descarga

> Smartpack Tiene dos tipos de test batería.• Normal – usa la tabla de batería

• Simplificado – usa el voltaje final y el tiempo a criterio- Si se alcanza el tiempo de la prueba las baterías son buenas- Si se alcanza el voltaje final de las baterías primero son malas

> Tres diferentes modos de test son posibles (para ambos tipos)• Manual: Empiezo y parada por una entrada manual

• Periódico/Intervalo: Programado por tiempo, fecha y el intervalo de periodos.

Page 60: Sistema Rectificador Flatpack 2

Slide 60 of 23 08.04.23

Funciones de BateríaResultado del Test

> Hasta 10 diferentes resultados de la prueba de descarga almacenados en la EEPROM• Empiezo Fecha [mm/dd/yyyy]• Tiempo Final [hh:mm]• Tipo de Test [Manual/Periodic/Automatic]• Tabla de batería• Duración del Test [m]• Corriente de descarga [Ah]• Voltaje final [V]• Calidad Calculada [%]• Resultado del Test

> Datos Registardos• Corriente de bateria(1 & 2)• Voltaje de bateria• Temperatura(1 & 2)• Voltaje de simetria (8)

> Los Resulatados pueden ser vistos haciendo click en el icono de batería en la columna del resultado de la prueba• First 10 min and last 10 min logging are done every minute• In between every

- 10 min (test duration < 300 min) - 20 min (300 min < test duration < 600 min)- 40 min (600 min < test duration < 1200 min)

Page 61: Sistema Rectificador Flatpack 2

Slide 61 of 23 08.04.23

Funciones de Batería Tabla de Batería

> Smartpack puede almacenar dos tablas de batería definida por el usuario con:• Tiempo [min]• Corriente de Bateria 1.9V/cell Voltaje final alto [A]• Corriente de Bateria 1.75V/cell Voltaje final bajo [A]

> NOTE. Muchas tablas de batería pueden ser almacenadas en la PC y facil de uploaded al Smartpack con PowerSuite

> What is Eltek Std?• Es el promedio de valores no cambiables de los diferentes tipos de

fabricantes de baterías.

Page 62: Sistema Rectificador Flatpack 2

Slide 62 of 23 08.04.23

Funciones de Batería Tabla de Batería

> Configuración de la tabla de baterías por Powersuite

Page 63: Sistema Rectificador Flatpack 2

Slide 63 of 23 08.04.23

Funciones de Batería Tabla de Batería

Page 64: Sistema Rectificador Flatpack 2

Slide 64 of 23 08.04.23

Funciones de Batería Temp. Comp. & Curr. Lim.

> Compensacion por temperatura• Slope

• Ref. temp

• Min comp. volt

• Max comp. volt

> Limitación corriente de batería• Dos limitación configurables (v1.02)

• Planta generadora, indicando con una entrada digital.

Page 65: Sistema Rectificador Flatpack 2

Slide 65 of 23 08.04.23

Funciones de Batería Temp. Comp. & Curr. Lim.

52,5

53

53,5

54

54,5

55

55,5

Temperature T [oC]

Ou

tpu

t V

olt

age

[Vd

c]

Min Comp, volt Max Comp, Volt

Slope

Page 66: Sistema Rectificador Flatpack 2

Slide 66 of 23 08.04.23

Funciones de Batería Temp. Comp. & Curr. Lim.

Mains

Ba

tte

ry C

urr

en

t (A

)

Float current

Battery current limit [A] = 0.3*C10

Mains OK Mains OK, RechargeMains failure Mains OK

Load current

Page 67: Sistema Rectificador Flatpack 2

Slide 68 of 23 08.04.23

Rectifier ID’s cont’

> Reset number of rectifiers

Page 68: Sistema Rectificador Flatpack 2

>

Soluciones de SistemasSoluciones de Sistemas

Cuanta potencia usted necesita ?

Page 69: Sistema Rectificador Flatpack 2

Slide 70 of 23 08.04.23

4 across a 19” rack

1U

Mas densidad de potenciaMas densidad de potencia

Up to 8000W per 1PR shelf

370mm deep

Page 70: Sistema Rectificador Flatpack 2

Slide 71 of 23 08.04.23

Montaje FlexibleMontaje Flexible

Smartpack mounting options

Smartpack in PR Smartpack in Distribtuion

Page 71: Sistema Rectificador Flatpack 2

Slide 72 of 23 08.04.23

Incluye (up to) :

Soluciones IntegradasSoluciones Integradas

1U Distribucion + 1 PR

8000W (166A@48V)

Smartpack

2 x 100A Breakers de Bateria

6 x 2–32A Breakers de Carga

2 x LVD (150A)

Soluciones Integradas 2U

5 kg (exc rectifiers)

Page 72: Sistema Rectificador Flatpack 2

Slide 73 of 23 08.04.23

Incluye (up to) :

Soluciones IntegradasSoluciones Integradas

4U Distribucion + 1-4 PR

32000W (660A@48V)

Smartpack

6 x 100A Breakers de Bateria*

18 x 2–63A Breakers de carga*

2 x LVD (up to 600A)* Verficar en datasheet por otra for otra

configuracion disponible

Solucion Integrada 5 - 8U

8 kg (exc rectifiers)

Page 73: Sistema Rectificador Flatpack 2

Slide 74 of 23 08.04.23

Soluciones IntegradasSoluciones Integradas

FP2NX-48-9U power system block

Battery Tray #4

Battery Tray #3

Battery Tray #2

Battery Tray #1Battery Disconnect #1

Battery Disconnect #2

Battery Disconnect #3

Battery Disconnect #4

23” EIA Seismic Equipment Rack

7U available equipment space

Page 74: Sistema Rectificador Flatpack 2

Slide 75 of 23 08.04.23

GabinetesGabinetes

> 8 - 96 kW en un solo Gabinete

> Max 2000A@48V = 96kW

(CAN bus limitation)

> Típicamente hasta 4PR por sistema con baterías.

> Variedad de gabientes disponibles

Example 32 kW

Page 75: Sistema Rectificador Flatpack 2

Slide 76 of 23 08.04.23

Solución Gabinete 96kW Solución Gabinete 96kW

• Input 230V/400V 3-phase

• FP2 2kW rectifiers

• Max Output 48V 2000A

• Cabinet dimensions: 600x2000x600mm

• 2 SmartPacks (Master-Slave)

Page 76: Sistema Rectificador Flatpack 2

Slide 77 of 23 08.04.23

Gracias!!