Siemens Safety Engineering in SIMATIC S7.pdf

download Siemens Safety Engineering in SIMATIC S7.pdf

of 162

Transcript of Siemens Safety Engineering in SIMATIC S7.pdf

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    1/162

    SIMATIC Safety Engineering in SIMATIC S7

     ______________  ______________ 

     ______________ 

     ______________ 

     ______________  ______________ 

     ______________ 

     ______________ 

     Preface

    Overview of Fail-safe

    Systems

    1

    Configurations and Help with

    Selection

    2

    Comm unication O ptions

    3

    Safety in F-Systems

    4

    Achievable Safety Classes

    with F-I/O

    5

    Configuring F-Systems

    6

    Programming F-Systems

    7

    Monitoring and Response

    Times of F-Systems

    A

    SIMATIC

    Safety Engineering in SIMATIC S7

    System M anual

    08/2005

    A5E00109529-04

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    2/162

     

    afety Guidelines

    This manual contains notices you have to observe in order to ensure your personal safety, as well as to preventdamage to property. The notices referring to your personal safety are highlighted in the manual by a safety alertsymbol, notices referring only to property damage have no safety alert symbol. These notices shown below aregraded according to the degree of danger.

    Danger

    indicates that death or severe personal injury will result if proper precautions are not taken.

    Warning

    indicates that death or severe personal injury may  result if proper precautions are not taken.

    Caution

    with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.

    Caution

    without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.

    Notice

    indicates that an unintended result or situation can occur if the corresponding information is not taken intoaccount.

    If more than one degree of danger is present, the warning notice representing the highest degree of danger willbe used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating toproperty damage.

    Qualified Personnel

    The device/system may only be set up and used in conjunction with this documentation. Commissioning andoperation of a device/system may only be performed by qualified personnel. Within the context of the safety notesin this documentation qualified persons are defined as persons who are authorized to commission, ground andlabel devices, systems and circuits in accordance with established safety practices and standards.

    Prescribed U sage

    Note the following:

    Warning

    This device may only be used for the applications described in the catalog or the technical description and only inconnection with devices or components from other manufacturers which have been approved or recommendedby Siemens. Correct, reliable operation of the product requires proper transport, storage, positioning andassembly as well as careful operation and maintenance.

    Trademarks

    All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in thispublication may be trademarks whose use by third parties for their own purposes could violate the rights of the

    owner.

    Disclaimer o f Liability

    We have reviewed the contents of this publication to ensure consistency with the hardware and softwaredescribed. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, theinformation in this publication is reviewed regularly and any necessary corrections are included in subsequenteditions.

    Siemens AG

    Automation and DrivesPostfach 48 4890437 NÜRNBERGGERMANY

    Order No.: A5E00109529-04

    Edition 08/2005

    Copyright © Siemens AG 2005.

    Technical data subject to change

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    3/162

     

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 iii 

    Preface

    Purpose of System Description

    This system description provides an overview of the S7 Distributed Safety and S7 F/FHSystems fail-safe automation systems. It identifies the similarities and differences betweenS7 Distributed Safety and S7 F/FH Systems and presents detailed technical informationapplicable to both S7 Distributed Safety and S7 F/FH Systems.

    The system description helps you to decide which fail-safe system is best suited for yourautomation task. It is intended as starting information for decision makers and as a source oftechnical information on S7 Distributed Safety and S7 F/FH Systems fail-safe automationsystems for service and commissioning personnel (e.g., detailed information on monitoringand response times of S7 Distributed Safety and S7 F/FH Systems is provided in theappendix).

    Scope of System Description

    This system description applies to the S7 Distributed Safety, S7 F Systems, and S7 FHSystems fail-safe systems.

    In addition, this system description addresses integration of the following

    fail-safe I/O devices in S7 Distributed Safety and S7 F/FH Systems:• S7-300 fail-safe signal modules

    • ET 200S fail-safe modules

    • ET 200pro fail-safe modules

    • ET 200eco fail-safe I/O module

    • Fail-safe DP standard slaves / I/O standard devices

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    4/162

    Preface

    Safety Engineering in SIMATIC S7iv  System Manual, 08/2005, A5E00109529-04

    What's New?

    The following table summarizes the most important technical changes in the add-onpackages S7 Distributed Safety V 5.4  and S7 F Systems V5.2 SP2  and higher. Thesechanges have been taken into account in this system description.

    Change Affects:echnical Change

    S7 Distributed

    Safety

    S7 F/FH

    Systems

    Support for PROFINET IO with:

    • CPU 416F-2 (6ES7 416-2FK04-0AB0) as of firmwareversion V 4.1 with CP 443-1 Advanced

    • CPU 315F-2 PN/DP

    • CPU 317F-2 PN/DP

    • ET 200S fail-safe modules

    • ET 200pro fail-safe modules

    Fail-safe I/O standard devices

    x -

    Safety-related CPU-CPU communication has been expanded toinclude I-slave-slave communication

    x -

    Channel-specific passivation when channel errors occur:

    • S7-300 fail-safe signal modules

    • ET 200S fail-safe modules

    • ET 200pro fail-safe modules

    • ET 200eco fail-safe I/O module

    x -

    New F-library blocks - x

    Safety Data Write - x

    ET 200pro fail-safe modules x -

    Fail-safe I/O standard devices x -

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    5/162

      Preface

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 v 

    Position in the Information Landscape

    Depending on your application, you will need the documentation listed below when workingwith S7 Distributed Safety or S7 F/FH Systems:

    This system description makes reference to these documents where appropriate.

    Docum entation Brief Description of Relevant Contents

    • The Programmable Controllers S7 F/FH Systems  manualdescribes the tasks required to create and commission anS7 F/FH Systems fail-safe system.

    For the fail-safe system S7F/FH Systems

    • The S7-400 Hardware and Installation  installation manualdescribes the assembly and wiring of S7-400 systems.

    • The Automation System S7-400H Fault-Tolerant Systems  manual describes the CPU 41x-H central modules and the tasksrequired to create and commission an S7-400H fault-tolerantsystem.

    • The CFC for S7 Continuous Function Chart manual/online help

    provides a description of programming with CFC.The following elements are described in the S7 Distributed Safety,Configuring and Programming  operator manual and online help:

    • Configuration of the F-CPU and the F-I/O

    • Programming of the F-CPU in F-FBD or F-LAD

    For the fail-safe system S7Distributed Safety

    Depending on which F-CPU you are using, you will need thefollowing documentation:

    • The operating manual S7-300, CPU 31xC and CPU 31x:Installation  describes the installation and wiring of S7-300systems.

    • The CPU 31xC and CPU 31x, Technical Data  product manualdescribes the CPUs 315-2 DP and PN/DP and CPUs 317-2 DP

    and PN/DP.• The Automation System S7-400 Hardware and Installation  

    installation manual describes the assembly and wiring of S7-400systems.

    • The Automation System S7-400 CPU Specifications  referencemanual describes CPU 416-2.

    • The ET 200S IM 151-7 CPU Interface Module  manual describesthe IM 151-7 CPU.

    • Each F-CPU that can be used has its own product information.The product information only describes the deviations from therespective standard CPUs.

     Automation System S7-300

    Fail-safe Signal Modules  

    manual

    Describes the hardware of the S7-300 fail-safe signal modules(including installation, wiring, and technical specifications)

    ET 200S Distributed I/O

    System Fail-Safe Modules  operating instructions

    Describes the hardware of the ET 200S fail-safe modules (includinginstallation, wiring, and technical specifications)

    ET 200pro Distributed I/O

    Device Fail-Safe Modules  operating instructions

    Describes the hardware of the ET 200pro fail-safe modules(including installation, wiring, and technical specifications)

    ET 200eco Distributed I/O

    Station Fail-safe Signal

    Module  manual

    Describes the hardware of the ET 200eco fail-safe signal module(including installation, wiring, and technical specifications)

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    6/162

    Preface

    Safety Engineering in SIMATIC S7vi  System Manual, 08/2005, A5E00109529-04

    Docum entation Brief Description of Relevant Contents

    STEP 7  manuals• The Configuring Hardware and Communication Connections with

    STEP 7 V5.x  manual describes how to operate the STEP 7  standard tools.

    The LAD for S7-300/400  manual describes the standard LadderDiagram programming language in STEP 7 .

    • The FBD for S7-300/400  manual describes the standard FunctionBlock Diagram programming language in STEP 7 .

    • The System Software for S7-300/400 System and StandardFunctions  reference manual describes functions for distributedI/O access and diagnostics for distributed I/O/CPU.

    • The Programming with STEP 7 V 5.x  manual describes theprocedure for programming with STEP 7 .

    STEP 7  online help • Describes the operation of STEP 7  standard tools

    • Contains information about how to configure and assignparameters for modules and intelligent slaves with HW Config  

    • Contains a description of the FBD and LAD programming

    languagesPROFINET System

    Description  system manual• Describes the basics for PROFINET IO

    PCS 7  manuals • Describe operation of the PCS 7  process control system(necessary when the F-system is integrated in a higher-levelcontrol system)

    The complete collection of SIMATIC S7 documentation is available on CD-ROM.

    Guide

    The following topics are covered in the system description:

    • Overview of fail-safe automation systems in general, and in SIMATIC S7, in particular• Comparison of system performance of S7 Distributed Safety and

    S7 F/FH Systems

    • Description of the configuration variants for S7 Distributed Safety and S7 F/FH Systems

    • Information to help you decide which F-system represents the best solution for yourrequirements

    • Comparison of the similarities and differences between the communication options forS7 Distributed Safety and S7 F/FH Systems

    • Overview of the safety mechanisms in S7 Distributed Safety and S7 F/FH Systems thatare apparent to the user

    • Standards upon which the S7 Distributed Safety and S7 F/FH Systems F-systems arebased

    • Overview of configuring S7 Distributed Safety and S7 F/FH Systems

    • Overview of programming S7 Distributed Safety and S7 F/FH Systems

    Configuring and programming are described in more detail in the respective programmingand configuration manuals for S7 Distributed Safety and S7 F/FH Systems.

    • Configuration of F-related monitoring times for F-systems

    • Calculating the maximum response time of the safety functions in S7 Distributed Safetyand S7 F/FH systems

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    7/162

      Preface

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 vii 

    Conventions

    The terms "safety engineering" and "fail-safe engineering" are used synonymously in thissystem description. The same applies to the terms "fail-safe" and "F-".

    "Safety program" refers to the fail-safe portion of the user program and is used instead of"fail-safe user program," "F-program," etc.

    "S7 Distributed Safety " and "S7 F System " in italics refer to the add-on packages for"S7 Distributed Safety" and"S7 F/FH Systems".

    Additional Support

    For any unanswered questions about the use of products presented in this manual, contactyour local Siemens representative:

    ht t p: / / www. s i emens. com/ aut omat i on/ par t ner  

    Training Center

    We offer courses to help you get started with the S7 automation system. Contact yourregional training center or the central training center in D-90327 Nuremberg, FederalRepublic of Germany.

    Phone: +49 (911) 895-3200

    ht t p: / / www. si t r ai n. com

    H/F Competence Center

    The H/F Competence Center in Nuremberg offers special workshops on SIMATIC S7 fail-

    safe and fault-tolerant automation systems. The H/F Competence Center can also provideassistance with onsite configuration, commissioning, and troubleshooting.

    Phone: +49 (911) 895-4759

    Fax: +49 (911) 895-5193

    For questions about workshops, etc., contact: hf - cc @nbgm. si emens. com

    Technical Support

    Technical support is available for all A&D products

    • using the Web form for a support requesthttp://www.siemens.de/automation/support-request 

    • Phone: + 49 180 5050 222

    • Fax: + 49 180 5050 223

    You can find additional information about our technical support athttp://www.siemens.de/automation/service 

    http://www.siemens.com/automation/partnerhttp://www.sitrain.com/http://www.siemens.de/automation/support-requesthttp://www.siemens.de/automation/support-requesthttp://www.siemens.de/automation/servicehttp://www.siemens.de/automation/servicehttp://www.siemens.de/automation/support-requesthttp://www.sitrain.com/http://www.siemens.com/automation/partner

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    8/162

    Preface

    Safety Engineering in SIMATIC S7viii  System Manual, 08/2005, A5E00109529-04

    Service Support on the Internet

    In addition to our documentation, we offer our complete knowledge base on the Internet at:

    ht t p: / / www. s i emens. com/ aut omat i on/ ser vi ce&suppor t  

    There, you will find the following information:• Newsletters providing the latest information on your products

    • Relevant documentation for your application via the search function in Service & Support

    • A forum where users and experts from all over the world exchange ideas

    • Our contacts database where you can find your local Automation & Drives representative

    • Information on local service, repairs, and replacement parts and much more can be foundunder "Services."

    Important Information for Preserving the Operational Safety of your System

    Note

    The operators of systems with safety-related characteristics must adhere to operationalsafety requirements. The supplier is also obliged to comply with certain actions whenmonitoring the product. To keep you informed, a special newsletter is therefore availablecontaining information on product developments and properties that are important (orpotentially important) for operating systems where safety is an issue. By subscribing to theappropriate newsletter, you will ensure that you are always up-to-date and able to makechanges to your system, when necessary. Go to the Internet addresshttp://my.ad.siemens.de/myAnD/guiThemes2Select.asp?subjectID=2&lang=de 

    and register for the following newsletters:

    • SIMATIC S7-300• SIMATIC S7-400

    • Distributed I/O

    • SIMATIC Industrial Software

    Select the "Updates" check box for each newsletter.

    http://www.siemens.com/automation/service&supporthttp://my.ad.siemens.de/myAnD/guiThemes2Select.asp?subjectID=2&lang=dehttp://my.ad.siemens.de/myAnD/guiThemes2Select.asp?subjectID=2&lang=dehttp://my.ad.siemens.de/myAnD/guiThemes2Select.asp?subjectID=2&lang=dehttp://www.siemens.com/automation/service&support

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    9/162

     

    Safety Engineering in SIMATIC S7

    System Manual, 08/2005, A5E00109529-04 ix 

    Table of contents

    Pre face ...................................................................................................................................................... iii

    1 Ov erview of Fail safe System s ............................................................................................................... 1 1

    1.1 Introduction ................................................................................................................................ 1-1

    1.2 Safety Integrated - the Integrated Safety Concept by Siemens ................................................ 1-2

    1.3 Fail-safe Systems in SIMATIC S7.............................................................................................. 1-31.3.1 Areas of Application of S7 Distributed Safety and S7 F/FH Systems........................................ 1-5

    1.3.2 Performance Characteristics of S7 Distributed Safety and S7 F/FH Systems.......................... 1-7

    1.4 Components of S7 Distributed Safety and S7 F/FH Systems ................................................. 1-101.4.1 Hardware Components ............................................................................................................ 1-111.4.2 Software Components ............................................................................................................. 1-15

    1.5 Guide to Working with F-Systems............................................................................................ 1-17

    2 Configura tions and He lp with Se lection .................................................................................................. 2 1

    2.1 Introduction ................................................................................................................................ 2-1

    2.2 Configuration of F-Systems ....................................................................................................... 2-22.2.1 S7 Distributed Safety Fail-safe System ..................................................................................... 2-22.2.2 S7 F Systems Fail-safe System................................................................................................. 2-5

    2.2.3 S7 FH Systems Fail-safe and Fault-Tolerant System................................................................ 2-62.2.4 Coexistence of Standard and Fail-safe Components ................................................................ 2-7 

    2.3 Configuration Variants for Fail-safe Systems According to Availability Requirements.............. 2-92.3.1 Single-channel I/O (S7 Distributed Safety).............................................................................. 2-102.3.2 Single-channel I/O (S7 F Systems).......................................................................................... 2-152.3.3 Single-channel Switched I/O (S7 FH Systems only)................................................................ 2-182.3.4 Redundant Switched I/O (S7 FH Systems Only)..................................................................... 2-20

    2.4 S7 Distributed Safety or S7 F/FH Systems – Selection Guide ................................................ 2-22

    3 Co mm unica tion Op tions ......................................................................................................................... 3 1

    3.1 Introduction ................................................................................................................................ 3-1

    3.2 Overview of Safety-Related Communication............................................................................. 3-2

    3.3 Communication between Standard User Program and Safety Program................................... 3-33.3.1 Communication between Standard User Program and Safety Program in

    S7 Distributed Safety ................................................................................................................. 3-43.3.2 Communication between Standard User Program and Safety Program in

    S7 F/FH Systems....................................................................................................................... 3-4

    3.4 Communication between F-Runtime Groups............................................................................. 3-5

    3.5 Communication between F-CPU and F-I/O............................................................................... 3-63.5.1 Safety-Related Communication ................................................................................................. 3-63.5.2 Accessing F-I/O in S7 Distributed Safety................................................................................... 3-73.5.3 Safety-Related I-Slave-Slave Communication in Distributed Safety ......................................... 3-83.5.4 Accessing F-I/O in S7 F/FH Systems ...................................................................................... 3-103.5.5 Standard Communication ........................................................................................................ 3-11

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    10/162

    Table of contents

    Safety Engineering in SIMATIC S7x  System Manual, 08/2005, A5E00109529-04

    3.6 Safety-Related CPU-CPU Communication.............................................................................. 3-133.6.1 S7 Distributed Safety: Safety-related Master-Master Communication ....................................3-13 3.6.2 S7 Distributed Safety: Safety-related Master-I-Slave Communication .................................... 3-15 3.6.3 S7 Distributed Safety: Safety-Related I-Slave-I-Slave Communication .................................. 3-16 3.6.4 S7 Distributed Safety: Safety-Related Communication via S7 Connections ........................... 3-18 

    3.6.5 S7 F/FH Systems: Safety-Related Communication via S7 Connections................................. 3-20 

    4 Safe ty in F-Sy stem s................................................................................................................................ 4-1 

    4.1 Introduction ................................................................................................................................ 4-1 

    4.2 Safety Mode ............................................................................................................................... 4-3 

    4.3 Fault Reactions .......................................................................................................................... 4-5 

    4.4 Restart of F-System ................................................................................................................... 4-6 

    4.5 Password Protection for F-Systems........................................................................................... 4-7 

    4.6 Acceptance Test of System ....................................................................................................... 4-7 

    4.7 Standards and Approvals........................................................................................................... 4-8 

    4.8 Safety Requirements................................................................................................................ 4-12 

    5 Achie vable Safe ty Classes with F-I/O ..................................................................................................... 5-1 

    5.1 Introduction ................................................................................................................................ 5-1 

    5.2 Safety Functions for Achieving Safety Classes for F-I/O with Inputs ........................................5-2 5.2.1 1oo1 Evaluation for F-I/O with Digital Inputs.............................................................................. 5-3 5.2.2 1oo2 Evaluation for F-I/O with Inputs......................................................................................... 5-5 

    5.3 Safety Functions for Achieving Safety Classes for F-I/O with Outputs.................................... 5-12

    6 Configuring F-Sy stems ........................................................................................................................... 6-1

    6.1 Introduction ................................................................................................................................ 6-1

    6.2 Configuring the F-CPU............................................................................................................... 6-2

    6.3 Configuring the F-I/O.................................................................................................................. 6-4

    6.4 Configuring Fail-safe DP Standard Slaves and Fail-safe I/O Standard Devices ....................... 6-5

    7 Prog ram ming F-Sy stem s ........................................................................................................................ 7-1

    7.1 Introduction ................................................................................................................................ 7-1

    7.2 Programming Languages for F-Systems ................................................................................... 7-3

    7.3 Structure of the Safety Program in S7 Distributed Safety..........................................................7-4

    7.4 Structure of Safety Program in S7 F/FH Systems ..................................................................... 7-9

    A Mo nitoring and Respon se Time s of F-Sy stem s ......................................................................................A-1

    A.1 Introduction ................................................................................................................................A-1

    A.2 Configuring the Monitoring Times ..............................................................................................A-2

    A.3 F-Related Monitoring Times for S7 Distributed Safety ..............................................................A-3A.3.1 Minimum Monitoring Time for F-Cycle Time..............................................................................A-4A.3.2 Minimum Monitoring Time for Safety-related Communication between the F-CPU and

    F-I/O or between I-Slave and Slave via PROFIBUS DP............................................................A-5A.3.3 Minimum Monitoring Time for Safety-Related Master-Master Communication .........................A-6A.3.4 Minimum Monitoring Time for Safety-Related Master-I-Slave Communication.........................A-7A.3.5 Minimum Monitoring Time for Safety-Related I-Slave-I-Slave Communication.........................A-7A.3.6 Minimum Monitoring Time for Safety-Related Communication via S7 Connections .................A-7A.3.7 Monitoring Time for Safety-Related Communication between F-Runtime Groups....................A-8

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    11/162

      Table of contents

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 xi 

    A.4 F-Related Monitoring Times for S7 F/FH Systems....................................................................A-8A.4.1 Minimum Monitoring Time for F-Cycle Time..............................................................................A-9A.4.2 Minimum Monitoring Time for Safety-Related Communication between F-CPU and

    F-I/O.........................................................................................................................................A-11A.4.3 Minimum Monitoring Time for Safety-Related Communication between F-CPUs...................A-13

    A.4.4 Minimum Monitoring Time for Safety-Related Communication between F-Runtime Groups.. A-14

    A.5 Response Times of Safety Functions ......................................................................................A-15

    Glossary ..................................................................................................................................... Glossary-1

    Inde x................................................................................................................................................ Index-1

    Tables

    Table 1-1 Performance Characteristics of F-Systems ............................................................................... 1-7 

    Table 1-2 Memory Configuration of F-CPUs.............................................................................................. 1-9

    Table 1-3 Hardware Components ............................................................................................................ 1-11Table 1-4 Use of Interface Modules with ET 200S Fail-safe Modules..................................................... 1-13

    Table 1-5 Optional Packages for Configuration and Programming ......................................................... 1-15

    Table 1-6 Programming Languages......................................................................................................... 1-16

    Table 1-7 Sequence of Steps Ranging from Selection of Hardware to Maintenance of F-Systems ....... 1-18

    Table 2-1 Configuration Options for Fail-safe Systems According to Availability ...................................... 2-9

    Table 2-2 Selection Citeria for an F-system............................................................................................. 2-22

    Table 3-1 Communication Options............................................................................................................. 3-2

    Table 3-2 Accessing F-I/O in S7 Distributed Safety................................................................................... 3-7

    Table 3-3 Overview of Communication between F-CPUs ....................................................................... 3-13

    Table 3-4 Safety-Related CPU-CPU Communication.............................................................................. 3-20

    Table 4-1 Meaning of the risk parameters in accordance with IEC 61508-5 ........................................... 4-13

    Table 4-2 Safety Integrity Level in Accordance with IEC 61508.............................................................. 4-13

    Table 4-3 Probability Values for Individual Components of S7 Distributed Safety andS7 F/FH Systems..................................................................................................................... 4-15

    Table 4-4 Calculation Example for the Contribution of the F-System to the Failure Probabilityof a Safety Function................................................................................................................. 4-16

    Table 5-1 Achievable Safety Classes for F-I/O with Digital Inputs ............................................................ 5-2

    Table 5-2 Achievable Safety Classes for F-I/O with Analog Inputs ........................................................... 5-2Table 5-3 Achievable Safety Classes for F-I/O with Outputs................................................................... 5-12

    Table 7-1 Fail-safe Blocks of an F-Runtime Group.................................................................................... 7-6

    Table 7-2 Fail-safe Blocks of the Distributed Safety F-Library (V1)........................................................... 7-7

    Table 7-3 Fail-safe Blocks of Failsafe Blocks F-Library (V1_2) ............................................................... 7-10

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    12/162

    Table of contents

    Safety Engineering in SIMATIC S7xii  System Manual, 08/2005, A5E00109529-04

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    13/162

     

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 1-1 

    Overview o f Fail-safe Systems

    1

    1.1

    1.1

    Introduction

    Objective of Safety Eng ineering

    The objective of safety engineering is to minimize danger to humans and the environment asmuch as possible through use of safety-oriented technical installations without restrictingindustrial production and the use of machines and chemical products any more thannecessary.

    What are Fail-safe Automation Systems?

    Fail-safe automation systems (F-systems) are used to control processes that can achieve asafe state immediately as a result of a shutdown. That is, F-systems control processes inwhich an immediate shutdown does not endanger humans or the environment.

    Fail-safe systems go beyond conventional safety engineering to enable far-reachingintelligent systems that extend all the way to the electrical drives and measuring systems.

    F-systems are used in systems with advanced safety requirements. Improved fault detectionand localization in F-systems through detailed diagnostic information enables production tobe resumed quickly following a safety-related interruption.

    Overview

    This chapter provides an introduction to safety engineering in SIMATIC S7.S7 Distributed Safety and S7 F/FH Systems are introduced along with their areas ofapplication. The important similarities and differences between the two fail-safe systems arealso presented.In the last part of the chapter, we introduce the user to the basic procedure to be followedwhen working with the fail-safe systems S7 Distributed Safety and S7 F/FH Systems.

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    14/162

    Overview of Fail-safe Systems

    1.2 Safety Integrated - the Integrated Safety Concept by Siemens

    Safety Engineering in SIMATIC S71-2  System Manual, 08/2005, A5E00109529-04

    1.2 1.2Safety Integrated - the Integrated Sa fety Concept by Siemens

    Safety Integrated

    Safety Integrated is the integrated safety concept for automation and drives by Siemens.

    Proven technologies and systems from automation engineering are used for safetyengineering. Safety Integrated covers the entire chain of safety from sensors and actuatorsdown to the controller, including safety-related communication over standard field buses.

    In addition to their functional tasks, drives and controllers also take on safety tasks. Aparticular feature of Safety Integrated is that is ensures not only reliable safety, but also ahigh level of flexibility and productivity.

    Safety-Related Input and Output Signals

    Safety-related input and output signals form the interface to the process. This enables, forexample, direct connection of single-channel and two-channel I/O signals from devices suchas emergency STOP buttons or light barriers. Safety-related signals are redundantlycombined internally. Safety-related input signals are read redundantly (e.g., 2 times) andcompared. The unified read result is passed on to the central processing unit in a fail-safemanner for further processing. Safety-related actuators are driven based on redundantANDing without any additional action on the part of the user. Interconnection of the inputsand outputs is also greatly simplified.This eliminates the need for some of the individually mounted hardware switching devices,resulting in a simplified control cabinet design.

    Fail-safe D istributed I/O S ystems

    Implementation of fail-safe distributed I/O systems enables conventional safety engineeringdesigns to be replaced by PROFIBUS DP components. This includes replacement ofswitching devices for emergency STOP, protective door monitors, two-hand operation, etc.

    Advantages of Integrating Safety Engineering into Standard Automa tion Systems

    Integration of safety engineering into standard automation systems has the followingimportant advantages:

    • An automation system with integrated fail-safe engineering is more flexible thanelectromechanical solutions.

    • Integration entails less complicated wiring solutions.

    • Integration requires less engineering effort, as standard engineering tools are used forconfiguring and programming.

    • Only one CPU is required, as safety-related sections of the program can be executedalongside standard sections in the CPU.

    • Simple communication between safety-related and standard program components.

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    15/162

      Overview of Fail-safe Systems

    1.3 Fail-safe Systems in SIMATIC S7

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 1-3 

    1.3 1.3Fail-safe Systems in SIMATIC S7

    What fail-safe systems are available in SIMATIC S 7?

    Two fail-safe systems are available for integrating safety engineering into SIMATIC S7automation systems:

    1. The S7 D istributed Safety  system is available to implement safety concepts for machineand operator protection (e.g., for emergency STOP devices for operation of machinetools and processing machinery) and the process industry (e.g., for protection functionsfor instrumentation and control protective devices and burners).

    2. The fail-safe and, in particular, the optionalS7 F/FH Systems

     fault-tolerant automationsystem is well-suited for process engineering and oil industry applications.

    Fail-safe and Fault-Tolerant S7 FH System s

    To increase availability of an automation system and, thus, to prevent process failures due tofaults in the F-system, fail-safe S7 F Systems can be optionally equipped with a fault-tolerantfeature (S7 FH Systems). Increased availability is achieved through component redundancy(power supply, central processing unit, communication, and I/O).

    Achievable Safety Requirements

    S7 Distributed Safety and S7 F/FH Systems F-systems can satisfy the following safetyrequirements:

    • Safety class (Safety Integrity Level) SIL1 to SIL3 in accordance with IEC 61508

    • Category 2 to Category 4 in accordance with EN 954-1

    Principle of Safety Functions in S7 Distributed Safety and S 7 F/FH Systems

    Functional safety is implemented principally through safety functions in the software. Safetyfunctions are executed by S7 Distributed Safety or S7 F/FH Systems to restore or maintain asafe state in a system when a dangerous event occurs. Safety functions are containedmainly in the following components:

    • In the safety-related user program (safety program) in the fail-safe CPU (F-CPU)

    • In the fail-safe inputs and outputs (F-I/O)

    The F-I/O ensures safe processing of field information (emergency STOP buttons, lightbarriers, motor control). They have all of the required hardware and software components forsafe processing, in accordance with the required safety class. The user only programs theuser safety function.

    The safety function for the process can be provided through a user safety function or a faultreaction function. In the event of a fault, if the F-system can no longer execute its actual usersafety function, it executes the fault reaction function; for example, the associated outputsare deactivated, and the F-CPU switches to STOP mode, if necessary.

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    16/162

    Overview of Fail-safe Systems

    1.3 Fail-safe Systems in SIMATIC S7

    Safety Engineering in SIMATIC S71-4  System Manual, 08/2005, A5E00109529-04

    Exam ple of User Safety Functions and Fault Reaction Functions

    In the event of overpressure, the F-system opens a valve (user safety function). If a

    dangerous fault occurs in the F-CPU, all outputs are deactivated (fault reaction function),whereby the valve is opened and the other actuators also attain a safe state. If the F-systemis intact, only the valve would be opened.

    PROFIBUS DP or PR OFINET IO with PROFIsafe Bus Profile

    Safe communication between the safety program in the F-CPU and the fail-safe inputs andoutputs takes place via the "standard" PROFIBUS DP or "standard" PROFINET IO withsuperimposed PROFIsafe safety profile.The user data of the safety function plus the safety measures are transmitted within astandard data frame.

    Advantages:

     

    • Because both standard and safety-related communication takes place on the standardPROFIBUS DP or standard PROFINET IO, no additional hardware components arerequired.

    • Safety-related communication tasks can be solved without resorting to previousconventional solutions (such as permanent wiring of emergency stop devices) or specialbuses. This enables safety-related distributed applications, for example in automobilechassis construction with presses and robots, burner management, passengertransportation on cable railway, and process automation.

    • Fail-safe DP standard slaves can be integrated in S7 Distributed Safety and S7 F/FHSystems F-systems (sensors/actuators with bus capability and safety devices ofPROFIBUS partner companies that are DP standard slaves with PROFIsafe capability).

    Fail-safe I/O standard devices can be integrated in S7 Distributed Safety F-systems(sensors/actuators with bus capability and safety devices of PROFIBUS partnercompanies that are I/O standard devices with PROFIsafe capability).

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    17/162

      Overview of Fail-safe Systems

    1.3 Fail-safe Systems in SIMATIC S7

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 1-5 

    1.3.1 Areas of Application of S7 Distributed Safety and S7 F/FH System s

    Use of S 7 Distributed Safety

    The primary uses of S7 Distributed Safety fail-safe systems are for machine and operatorprotection (e.g., for emergency STOP devices for operation of machine tools and processingmachinery) and the process control industry (e.g., for protection functions for instrumentationand control protective devices and burners).

    Integration options for S7 Distributed Safety fail-safe systems at the plant automation levelare shown below.

    PROFIBUS

    PC

    ET 200SET 200M

    ET 200M

    ET 200S

    F-SMs

    ET 200S

    ET 200S

    ET 200pro

    ET 200S

    F-SMs

    ET 200M

    ET 200pro

    ET 200eco

     Figure 1-1 Use of S7 Distributed Safety

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    18/162

    Overview of Fail-safe Systems

    1.3 Fail-safe Systems in SIMATIC S7

    Safety Engineering in SIMATIC S71-6  System Manual, 08/2005, A5E00109529-04

    Use of S7 F/FH Systems

    S7 F/FH Systems fail-safe systems are used primarily in process engineering and

    instrumentation and control applications in which a safe state can be attained by disablingthe fail-safe outputs.

    Integration options for S7 F Systems andS7 FH Systems in process automation systems using PCS 7 are shown below.

    PC

    PC

    • •

    PC PC

    ET 200M

    ET 200M ET 200M

    ET 200S ET 200S

    S7-400H

    ET 200eco

     Figure 1-2 Use of S7 F/FH Systems

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    19/162

      Overview of Fail-safe Systems

    1.3 Fail-safe Systems in SIMATIC S7

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 1-7 

    1.3.2 Performance Characteristics of S7 Distributed Safety and S7 F/FH System s

    Com mon C haracteristics of S7 Distributed Safety and S7 F/FH Systems

    S7 Distributed Safety and S7 F/FH Systems have the following important characteristics incommon:

    • Integration in S7-300 or S7-400 automation systems; the automation task determines thesystem design, and fail-safe engineering is integrated into the system

    • Execution of standard control functions and protection functions on the same system(standard system with fail-safe capability, which eliminates the need for dedicated fail-safe solutions)

    • Connection of distributed I/O via PROFIBUS DP with PROFIsafe

    • Use of standard PROFIBUS components (copper and fiber-optic cable technology)

    • Configuration integrated in STEP 7 , same as for standard automation systems

    • Creation of safety program using standard programming languages of STEP 7  

    • Flexible adaptation to the task requirements by providing a wide range of fail-safe I/O

    Com parison of System Performance of S7 Distributed Safety and

    S7 F/FH Systems

    The following table identifies the differences between the fail-safe systems with regard toimportant performance characteristics.

    Table 1-1 Performance Characteristics of F-Systems

    Performance Characteristic S7 Distributed Safety S7 F/FH Systems

    Achievable safety classes SIL3/Category 4 SIL3/Category 4

    Fault tolerance featureavailable

    No Yes

    Development stage Fail-safe system Fail-safe system

    Fail-safe and fault-tolerant system

    Connection of fail-safe I/O • Centralized and decentralizedvia PROFIBUS DP

    • Distributed via PROFINET IO(ET 200S and ET 200pro

    F-modules)

    • Distributed via PROFIBUS DP

    Minimum response time ofF-system (dependent onconfiguration)

    50 ms 100 ms

    Typical response time ofF-system

    100 ms to 200 ms 200 ms to 500 ms

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    20/162

    Overview of Fail-safe Systems

    1.3 Fail-safe Systems in SIMATIC S7

    Safety Engineering in SIMATIC S71-8  System Manual, 08/2005, A5E00109529-04

    Performance Characteristic S7 Distributed Safety S7 F/FH Systems

    Communication Safety-related master-mastercommunication

    Safety-related master-I-slavecommunication

    Safety-related I-slave-I-slavecommunication

    Safety-related I-slave-slavecommunication

    Safety-related communication viaS7 connections (IndustrialEthernet only)

    Safety-related communication viaS7 connections (via PROFIBUS,MPI, Industrial Ethernet, etc.)

    Creation of safety program In standard LAD or FBDlanguages in STEP 7  

    In CFC (optional software forSTEP 7 )

    via safety matrixModification of safetyprogram in the F-CPU inRUN mode

    Currently possible in deactivatedsafety mode, however, transitionto safety mode possible only byswitching the F-CPU to STOPmode

    Currently possible in deactivatedsafety mode or via Safety DataWrite; change of operating modeof F-CPU not required fortransition to safety mode

    Fault reactions in the safetyprogram

    Passivation of channels or F-I/O

    F-CPU in STOP mode

    Passivation of channels or F-I/O

    F-CPU does not go to STOPmode; instead, the safetyprogram or faulty F-runtime groupis shut down

    Main areas of application Operator and machine protection

    Burner control

    Instrumentation and control andprocess industries

    (can be integrated in thePCS 7 process control system)

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    21/162

      Overview of Fail-safe Systems

    1.3 Fail-safe Systems in SIMATIC S7

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 1-9 

    Table 1-2 Memory Configuration of F-CPUs

    F-System Applicable

    F-CPU

    Memory configuration (RAM)

    IM 151-7 F-CPU

    (6ES7 151-7FA01-0AB0)

    96 Kbytes (of which 64 Kbytes is forstandard user program)

    CPU 315F-2 DP

    (6ES7 315-6FF01-0AB0)

    192 Kbytes

    CPU 315F-2 PN/DP

    (6ES7 315-2FH10-0AB0)

    192 Kbytes

    CPU 317F-2 DP

    (6ES7 317-6FF00-0AB0)

    512 Kbytes

    CPU 317F-2 PN/DP

    (6ES7 317-2FJ10-0AB0)

    512 Kbytes

    CPU 416F-2(6ES7 416-2FK02-0AB0)

    800 Kbytes for program +

    800 Kbytes for data

    S7 Distributed Safety

    CPU 416F-2(6ES7 416-2FK04-0AB0)

    1.4 Mbytes for program +

    1.4 Mbytes for data

    CPU 414-4H

    (6ES7 414-4HJ00-0AB0)

    384 Kbytes for program +

    384 Kbytes for data

    CPU 414-4H

    (6ES7 414-4HJ04-0AB0)

    700 Kbytes for program +

    700 Kbytes for data

    CPU 417-4H

    (6ES7 417-4HL00-0AB0)

    (6ES7 417-4HL01-0AB0)

    2 Mbytes for program, can be expandedto 10 Mbytes + 2 Mbytes for data, can

    be expanded to 10 Mbytes

    S7 F/FH Systems

    CPU 417-4H

    (6ES7 417-4HL04-0AB0)

    10 Mbytes for program +

    10 Mbytes for data

    Support for PROFINET IO (as of

    S7 Distributed Safety V 5 4

    ):

    The following F-CPUs and F-I/O support PROFINET IO:

    • CPU 315F-2 PN/DP

    • CPU 317F-2 PN/DP

    • CPU 416F-2 (6ES7 416-2FK04-0AB0) as of firmware version V 4.1 with

    CP 443-1 Advanced• ET 200S fail-safe modules

    • ET 200pro fail-safe modules

    • Fail-safe I/O standard devices

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    22/162

    Overview of Fail-safe Systems

    1.4 Components of S7 Distributed Safety and S7 F/FH Systems

    Safety Engineering in SIMATIC S71-10  System Manual, 08/2005, A5E00109529-04

    1.4 1.4Com ponents of S7 Distributed Safety and S7 F/FH Systems

    Hardware and Software Components of F-Systems

    An overview of the hardware and software components required for configuring andoperating S7 Distributed Safety and S7 F/FH Systems F-systems is shown below.

     

     

     

     

     

     

     

     Figure 1-3 Overview of Hardware and Software Components of an F-System

    Interaction of Compo nents

    To configure a fail-safe system, certain software and hardware components have to becombined.

    Wiring Fail-safe I/O

    The user wires the F-I/O to the sensors and actuators so as to be able to achieve therequired safety class.

    Configuring Hardware

    The user configures the F-CPU and the F-I/O in STEP 7HW Config . This configuration must match the hardware configuration; that is, the circuitdiagram of the F-I/O must reflect the parameter settings.

    Creating Safety Program

     The user creates the safety program using a programming language in STEP 7.

    For S7 Distributed Safety

    , the user creates fail-safe blocks in F-FBD or F-LAD. Theassociated F-block library provides fail-safe blocks that the user can use in his safetyprogram. For the most part, the F-I/O is linked in the background without user involvement.

    For S7 F/FH Systems

    , the user assigns parameters for the fail-safe blocks of the associatedF-block library and interconnects them in CFC. Special F-driver blocksare available to link the F-I/O. These driver blocks must also be parameterized andinterconnected.

    For both F-systems, safety checks are performed and additional F-blocks for fault detectionare incorporated automatically when the executable safety program is compiled.

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    23/162

      Overview of Fail-safe Systems

    1.4 Components of S7 Distributed Safety and S7 F/FH Systems

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 1-11 

    1.4.1 Hardware Components

    Components

    An F-system consists in part of hardware components that fulfill particular safetyrequirements:

    Table 1-3 Hardware Components

    F-System F-CPU Fail-safe I/O

    S7

    Distributed

    Safety 

    • IM 151-7 F-CPU

    • CPU 315F-2 DP

    • CPU 315F-2 PN/DP

    • CPU 317F-2 DP

    • CPU 317F-2 PN/DP• CPU 416F-2

    • F-signal modules in ET 200M (decentralizedconfiguration)

    • F-signal modules in S7-300 station (localconfiguration with a CPU 3xxF)

    F-electronic modules in ET 200S (DP master orintelligent DP slave with an IM 151-7 F-CPU )

    • F-electronic modules in ET 200S (DP slave with an IM151-1 HIGH FEATURE)

    • F-electronic modules in ET 200S (PROFINET IOdevice with 151-3 PN HIGH FEATURE)

    • ET 200pro F-modules

    • ET 200eco fail-safe I/O module

    • Fail-safe DP standard slaves

    • Fail-safe I/O standard devices

    S7 F/FH

    Systems • CPU 414-4H

    • CPU 417-4H

    (each with F-runtimelicense)

    • F-signal modules in ET 200M (decentralizedconfiguration)

    • F-electronic modules in ET 200S (DP slave with an IM151-1 HIGH FEATURE)

    • ET 200eco fail-safe I/O module

    • Fail-safe DP standard slaves

    In addition, the F-system can be expanded using standard components of the S7-300 andS7-400.

    F-CPU

    A CPU with fail-safe capability is a central processing unit that is approved for use in S7Distributed Safety and S7 F/FH Systems.

    For S7 F/FH systems

    , the F-runtime license allows the central processing unit to be used asan F-CPU. That is, a safety program can be run on it.

    For S7 Distributed Safety

    , an F-runtime license is not required.

    A standard user program can also be run in the F-CPU.It is possible for a standard program and a safety program to coexist because unintentionalinterference of the safety program by the standard user program can be prevented.

    Safety-related portions of the user program must be password-protected againstunauthorized access in the F-CPU and the programming device or ES. In addition, the F-CPU applies highly effective measures to detect and eliminate faults.

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    24/162

    Overview of Fail-safe Systems

    1.4 Components of S7 Distributed Safety and S7 F/FH Systems

    Safety Engineering in SIMATIC S7

    1-12  System Manual, 08/2005, A5E00109529-04

    Warning

    You can use the following F-CPUs in S7 Distributed Safety : IM 151-7 F-CPU, CPU 315F-2

    DP, CPU 315F-2 PN/DP, CPU 317F-2 DP, CPU 317F-2 PN/DP and CPU 416F-2. Note thatthese F-CPUs cannot be used in S7 F/FH Systems.

    You can use the following F-CPUs in S7 F/FH Systems : CPU 414-4H and CPU 417-4H.Note that these F-CPUs can not  be used in S7 Distributed Safety.

    Fail safe I/O

    The following fail-safe I/O are available:

    For S7 Distributed Safety and S7 F/FH Systems: 

    • S7-300 fail-safe signal modules (F-SMs)

    • ET 200S fail-safe power and electronic modules (ET 200S F-modules)

    • ET 200eco fail-safe I/O module (ET 200eco F-module)

    • Fail-safe DP standard slaves

    For S7 Distributed Safety: 

    • ET 200pro fail-safe electronic modules

    • Fail-safe I/O standard device

    S7 300 Fail safe Signal Modules

    The following fail-safe signal modules (F-SMs) are available:

    • Fail-safe digital input modules:

     – SM 326; DI 8 ☓ NAMUR, with diagnostic interrupt

     – SM 326; DI 24 ☓ 24 VDC, with diagnostic interrupt

    • Fail-safe digital output modules:

     – SM 326; DO 10 ☓ 24 VDC/2 A, with diagnostic interrupt

     – SM 326; DO 8 ☓ 24 VDC/2 A, with diagnostic interrupt

    • Fail-safe analog input module: SM 336; AI 6 ☓ 13 bits, with diagnostic interrupt

    F-SMs can also be used as standard SMs with standard CPUs in standard applications.

    From a user standpoint, the F-SMs can be distinguished from most standard SMs in thatthey have diagnostic interrupt capability.

    In S7 Distributed Safety , the F-SMs can be operated as decentralized modules in ET 200Mand as centralized modules in an S7-300 station.

    In S7 F/FH Systems , the F-SMs can generally be operated only in the ET 200M distributedI/O system.

    Exception: The SM 326; DO 8 ☓ DC 24V/2A can only be operated as a fail-safe signalmodule. You can, however, installed it centrally with all F-CPUs of the S7-300 spectrum with:

    • CPU 315F-2 DP (6ES7 315-6FF01-0AB0) beginning with firmware version V 2.0.9 and

    • CPU 315F-2 DP (6ES7 317-6FF00-0AB0) beginning with firmware version V 2.1.4.

    The module can be operated in a distributed configuration in in S7 Distributed Safety.

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    25/162

      Overview of Fail-safe Systems

    1.4 Components of S7 Distributed Safety and S7 F/FH Systems

    Safety Engineering in SIMATIC S7

    System Manual, 08/2005, A5E00109529-04 1-13 

    Restrictions on the Use of S 7-300 Standard SM s

    The restrictions for fault-tolerant systems are applicable to the use of S7-300 standard SMs

    in S7 F/FH Systems (see Automation System S7-400H Fault-Tolerant Systems  manual).For the restrictions for S7-300 standard SMs in safety mode of F-SMs, refer to the Automation System S7-300 Fail-safe Signal Modules  manual.

    ET 20 0S Fail-safe Electronic Modules

    The following fail-safe electronic modules (F-modules) are available in ET 200S:

    • PM-E F pm 24 VDC PROFIsafe power module with 2 additional fail-safe digital outputs

    • PM-E F pp 24 VDC PROFIsafe power module

    • PM-D F 24 VDC PROFIsafe power module

    • 4/8 F-DO 24 VDC PROFIsafe digital electronic module• 4 F-DO 24 VDC/2 A PROFIsafe digital electronic module

    F-modules can no t be used with standard CPUs in standard applications.

    Interface M odules for ET 200S w ith Fail-safe Modules

    One interface module is required for each ET 200S. The F-system determines whichinterface module can be used:

    Table 1-4 Use of Interface Modules with ET 200S Fail-safe Modules

    Interface Modu le Order Num ber or higher) Applicable Optional Packag e

    in ET 200S

    Version or

    higher)

    S7 Distributed Safety V5.1IM 151-1 HIGH

    FEATURE

    6ES7 151-1BA00-0AB0

    6ES7 151-1BA01-0AB0S7 F Systems   V5.2

    IM 151-7 F-CPU 6ES7 151-7FA01-0AB0 S7 Distributed Safety   V5.2

    IM 151-3 PN HIGH

    FEATURE

    6ES7 151-3AB00-0AB0 S7 Distributed Safety   V 5.4

    Note

    Unlike IM 151-1 HIGH FEATURE, for example, the IM 151-7 F-CPU  is an intelligentpreprocessing device (intelligent DP slave) and can also be used as a DP master. An IM151-7 F/CPU can therefore exercise full and, if necessary, independent control over atechnological functional unit and can be used as a stand-alone CPU or F-CPU. The IM 151-7F-CPU represents an addition to the line of F-CPUs for S7 Distributed Safety.

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    26/162

    Overview of Fail-safe Systems

    1.4 Components of S7 Distributed Safety and S7 F/FH Systems

    Safety Engineering in SIMATIC S71-14  System Manual, 08/2005, A5E00109529-04

    ET 200p ro Fail-safe Modules

    The following fail-safe electronic modules (F-modules for short) are available for an

    ET 200pro:• 8/16 F-DI DC24V PROFIsafe Digital Electronic Module

    • 4/8 F-DI/4 F-DO DC24V/2A PROFIsafe Digital Electronic Module

    ET 200eco Fa il-safe I/O Module

    The following fail-safe I/O modules (F-modules) are available in ET 200eco:

    • 4/8 F-DI 24 VDC PROFIsafe

    Fail-safe DP S tandard Slaves

    Fail-safe DP standard slaves are standard slaves that are operated on PROFIBUS with theDP protocol and the PROFIsafe bus profile. Their behavior must comply with IEC 61784-1:2002 Ed1 CP 3/1 and the PROFIsafe bus profile.

    Fail-safe DP standard slaves that are used in a mixed configurations on PROFIBUS DP andPROFINET IO after IE/PB links, must support the PROFIsafe bus profile in the V2 mode.

    A GSD file is used to configure fail-safe DP standard slaves.

    Fail-safe IO Standard Devices

    Fail-safe I/O standard slaves are standard devices that are operated on PROFINET with theI/O protocol and the PROFIsafe (V2 mode) bus profile. They must behave in accordance

    with IEC 61784-1:2002 Ed1 CP 3/3 and the PROFIsafe bus profile (V2 MODE). A GSDMLfile is used to configure them.

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    27/162

      Overview of Fail-safe Systems

    1.4 Components of S7 Distributed Safety and S7 F/FH Systems

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 1-15 

    1.4.2 Software Com ponents

    Introduction

    The software components of an F-system include the following:

    • Optional package on the programming device or ES for configuring and programming theF-system

    • Safety program in the F-CPU

    You also need the STEP 7  basic software on the programming device or ES for configuringand programming the standard automation system.

    Für ForS7 F/FH systems

    , you also need the CFC  and S7-SCL add-on software for STEP 7  and, when applicable, PCS 7 .

    Optional Packages for Configuring and Programm ing F-Systems

    The two optional packages are available for configuring and programming F-systems asshown in the following table.

    Table 1-5 Optional Packages for Configuration and Programming

    Optional Package Order Number For F-System Scope

    S7 Distributed

    Safety  6ES7 833-1FC02-0YX0

    S7 Distributed

    Safety Configuration and programming softwarewith F-block library for:

    • IM 151-7 F-CPU, CPU 315F-2 DP,CPU 315F-2 PN/DP, CPU 317F-2 DP,CPU 317F-2 PN/DP, CPU 416F-2

    • ET 200S F-modules

    • ET 200pro F-modules

    • ET 200eco F-module

    • S7-300 F-SMs

    • Fail-safe DP standard slaves

    • Fail-safe I/O standard devices

    S7 F Systems   6ES7 833-1CC00-0YX0

    S7 F/FH

    Systems Configuration and programming softwarewith F-block library for:

    • CPU 414-4H, CPU 417-4H

    • ET 200S F-modules

    • ET 200eco F-module• S7-300 F-SMs

    • Fail-safe DP standard slaves

    The user receives the following with these optional packages:

    • Support for configuring the F-I/O in STEP 7  with HW Config .

    • F-library with fail-safe blocks for creating safety programs

    • Support for creating the safety program and integrating fault detection functions in thesafety program

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    28/162

    Overview of Fail-safe Systems

    1.4 Components of S7 Distributed Safety and S7 F/FH Systems

    Safety Engineering in SIMATIC S71-16  System Manual, 08/2005, A5E00109529-04

    Programming Language

    Different programming languages are used to create safety programs:

    Table 1-6 Programming Languages

    F-System Programming

    Language

    Description

    S7

    Distributed

    Safety 

    F-LAD, F-FBD • The primary difference between the F-LAD and F-FBDprogramming languages and the standard LAD and FBDlanguages in STEP 7  lies in the limitations in the instruction setand data types.

    • F-application blocks from the Distributed Safety  F-library orcustom F-libraries can be used.

    S7 F/FH

    Systems CFC • Use of optional CFC software in STEP 7  

    • Special F-blocks in the Failsafe Blocks  F-library must be used.

    Creating a Safety Program for S7 Distributed Safety

    The user creates safety programs with F-FBD or F-LAD in fail-safe FBs and FCs. TheF-library provided contains F-application blocks that the user can incorporate into his safetyprogram.

    The user also has the option of creating his own F-libraries for S7 Distributed Safety (customF-libraries).

    Creating a Safety Program for S7 F/FH Systems

    The user creates safety programs with CFC by interconnecting fail-safe blocks in theF-library provided with the S7 F Systems  optional package.

    Additional Information

    For detailed information on configuring S7 Distributed Safety and S7 F/FH Systems, refer to"Configuring F-Systems" . Programming of F-systems is described in "ProgrammingF-Systems" .

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    29/162

      Overview of Fail-safe Systems

    1.5 Guide to Working with F-Systems

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 1-17 

    1.5 1.5Guide to Working with F-Systems

    Introduction

    This section describes the basic procedure for working with fail-safe systems. Only therelevant steps for F-systems that differ from the standard procedure are presented.

    Planning tasks that depend on the process, such as creating a flowchart or process tag list,defining a structure, etc., are not described here.

    Examp le Projects

    You will find introductory example projects for configuration and programming of:

    • S7 Distributed Safety in S7 Distributed Safety Getting Started  

    • S7 Distributed Safety in S7 Distributed Safety Configuring and Programming  manual

    • S7 F/FH Systems in Programmable Controllers S7 F/FH  manual

    • S7 F/FH Systems in step7\Examples  directory

    Planning a System

    When planning a system, the planner specifies the applicable safety class (SIL/Category) foreach required safety function based on a risk assessment. This is then used to determinethe component requirements for implementing the safety functions (programmable logiccontrollers, sensors, actuators). These decisions influence additional activities such ashardware design, configuration, and programming.

    Note

    A functional division of standard and safety functions is important for planning.

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    30/162

    Overview of Fail-safe Systems

    1.5 Guide to Working with F-Systems

    Safety Engineering in SIMATIC S71-18  System Manual, 08/2005, A5E00109529-04

    Sequence of Steps R anging from Selection of Com ponents to Maintenance of F-Systems

    The following table provides references to manuals for obtaining information. The relevantproduct information sheets provide additional information on the F-CPUs.

    Table 1-7 Sequence of Steps Ranging from Selection of Hardware to Maintenance of F-Systems

    Step Procedure Reference

    1.

     Plan system:

     • Specify safety functions with appropriate safety

    classes (SIL/Category).• Specify S7 Distributed Safety, S7 F Systems,

    or S7 FH Systems; select hardware andsoftware components.

    Safety Engineering  system description,"Overview of Fail-safe Systems"  sectionProduct catalog

    2.

     Configure hardware in STEP 7:

     • Configure F-CPU and assign parameters for

    safety program.• Configure and assign parameters for fail-safe

    I/O (F-SMs, F-modules) according to safetyclass and wiring diagram.

    • Integrate and assign parameters for fail-safeDP standard slaves and I/O standard devices.

    Safety Engineering  system description,"Configuring F-Systems"  sectionS7 Distributed Safety: S7 DistributedSafety, Configuring and Programming  

    S7 F/FH Systems: S7 F/FH AutomationSystems  ET 200S: ET 200S, Fail-safe Modules  ET 200pro: ET 200pro, Fail-safeModules  ET 200eco: ET 200eco, Fail-safe I/OModule  F-SMs S7-300, Fail-safe SignalModules  

    3.   Set up hardware:• Set the PROFIsafe addresses on the ET 200S,

    ET 200pro, ET 200eco, and S7-300 F-SMs viaswitch.

    • Install modules.• Wire modules according to required wiring

    diagram.

    ET 200S: ET 200S, Fail-safe Modules  ET 200pro: ET 200pro, Fail-safeModules  ET 200eco: ET 200eco, Fail-safe I/OModule  F-SMs S7-300, Fail-safe SignalModules  

    4.

     Create safety program in STEP 7:

     • Create F-blocks or select them from F-library;

    position, interconnect, and assign parametersfor F-blocks.

    • Compile safety program and download it to theF-CPU.

    • Test safety program.• If necessary, modify safety program.• Document configuration and safety program.

    Safety Engineering  system description,"Programming F-Systems"  sectionS7 Distributed Safety: S7 DistributedSafety, Configuring and Programming  S7 F/FH Systems: S7 F/FH AutomationSystems  

    5.   Commission system: • If necessary, arrange for acceptance testing of

    safety-related parts by the relevant authoritiesbefore starting safety mode.

    • Commission system.

    S7 Distributed Safety: S7 DistributedSafety, Configuring and Programming  S7 F/FH Systems: S7 F/FH AutomationSystems  

    6.

     Perform system maintenance:

     • Replace hardware and software components.• Update operating system.• Uninstall F-system.

    S7 Distributed Safety: S7 DistributedSafety, Configuring and Programming  S7 F/FH Systems: S7 F/FH AutomationSystems  

    See also

    Introduction (Page 6-1) 

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    31/162

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    32/162

    Configurations and Help with Selection

    2.2 Configuration of F-Systems

    Safety Engineering in SIMATIC S72-2  System Manual, 08/2005, A5E00109529-04

    2.2 2.2Configuration of F-Systems

    Basic Configurations

    This chapter describes the three basic configurations for F-systems:

    • S7 Distributed Safety fail-safe system

    • S7 F Systems fail-safe system

    • S7 FH Systems fail-safe and fault-tolerant system

    2.2.1 S7 Distributed Safety Fail-safe System

    Com ponents of S7 Distributed Safety System

    S7 Distributed Safety

     refers to a fail-safe automation system consisting of at least thefollowing components:

    • A central processing unit with fail-safe capability, such as CPU 315F-2 DP, on which asafety program is executed

    • Fail-safe I/O, for example:

     – Fail-safe signal modules (F-SMs) in a centralized configuration with CPU 315F-2 DP

     – Fail-safe signal modules (F-SMs) in an ET 200M distributed I/O system

     – Fail-safe modules in an ET 200S distributed I/O system – Fail-safe modules in an ET 200pro distributed I/O device

     – ET 200eco fail-safe I/O module

     – Fail-safe DP standard slaves/standard I/O devices

    Warning

    You can use the following F-CPUs in S7 D istributed Safety : IM 151-7 F-CPU, CPU 315F-2 DP, CPU 315F-2 PN/DP, CPU 317F-2 DP, CPU 317F-2 PN/DP and CPU 416F-2. Notethat these F-CPUs

    cannot

     be used in S7 F/FH Systems.

    You can use the following F-CPUs in S7 F/FH Systems: CPU 414-4H and CPU 417-4H.Note that these F-CPUs cannot

     be used in S7 Distributed Safety.

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    33/162

      Configurations and Help with Selection

    2.2 Configuration of F-Systems

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 2-3 

    Configuration Exam ples for S7 Distributed Safety F-System s

    The following figures illustrate three examples of S7 Distributed Safety F-systems.

    Example 1 for PROFIBUS DP:The S7-300 station with CPU 315F-2 DP is the DP master.The F-CPU exchanges safety-related data with the fail-safe I/O in the centralizedconfiguration and in the DP slaves.

    The F-system can be expanded with additional fail-safe I/O, any number of "standard" DPslaves and standard modules.

    PROFIBUS DP

     

     Figure 2-1 Example 1: F-System S7 Distributed Safety with PROFIBUS DP

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    34/162

    Configurations and Help with Selection

    2.2 Configuration of F-Systems

    Safety Engineering in SIMATIC S72-4  System Manual, 08/2005, A5E00109529-04

    Example 2 for PROFIBUS DP:

    The S7-400 station with CPU 416F-2 is the DP master. TheF-CPU exchanges safety-related data with the IM 151-7 F-CPU in ET 200S.The IM 151-7 F-CPU acts as an intelligent preprocessing device (I-slave).

    The F-system can be expanded with additional fail-safe I/O, any number of "standard" DPslaves and standard modules.

     Figure 2-2 Example 2: F-System S7 Distributed Safety with PROFIBUS DP

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    35/162

      Configurations and Help with Selection

    2.2 Configuration of F-Systems

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 2-5 

    Example 3 for PROFINET IO:

    The S7-300 station with CPU 315F-2 PN/DP is the I/Ocontroller The F-CPU exchanges safety-relevant data with the fail-safe modules ofET 200pro, ET 200S and fail-safe I/O standard devices.

    The fail-safe system can be expanded by any number of "standard" I/O devices.

    PROFINET IO

     

     

    Figure 2-3 Example 3: F-System S7 Distributed Safety with PROFINET IO

    2.2.2 S7 F System s Fail-safe System

    Components of S7 F Systems

    S7 F Systems

     refers to a fail-safe automation system consisting of at least the followingcomponents:

    • A central processing unit with fail-safe capability, such as CPU 417-4 H with an F-runtime

    license, on which a safety program is executed• Fail-safe I/O, for example:

     – Fail-safe signal modules (F-SMs) in an ET 200M distributed I/O system (with optionalredundancy)

     – Fail-safe modules in an ET 200S distributed I/O system

     – ET 200eco fail-safe I/O module

     – Fail-safe DP standard slaves

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    36/162

    Configurations and Help with Selection

    2.2 Configuration of F-Systems

    Safety Engineering in SIMATIC S72-6  System Manual, 08/2005, A5E00109529-04

    Configuration Exam ple for an S7 F Systems F-System

    The following figure illustrates an example of an S7 F Systems F-system.

    The S7-400 station with CPU 417-4H is the DP master. The F-CPU exchanges safety-related data with the fail-safe I/O in the DP slaves. The F-system can be expanded withadditional fail-safe I/O, any number of "standard" DP slaves and standard modules.

     

     Figure 2-4 S7 F Systems Fail-safe System

    2.2.3 S7 FH System s Fail-safe and Fault-Tolerant System

    Components of S7 FH Systems

    S7 FH Systems  refers to a fail-safe and fault-tolerant automation system consisting of atleast the following components:

    • S7-400H fault-tolerant system (master and standby) on which a safety program isexecuted

    • Fail-safe signal modules (F-SMs) in an ET 200M distributed I/O system as switched I/O(with optional redundancy)

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    37/162

      Configurations and Help with Selection

    2.2 Configuration of F-Systems

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 2-7 

    Configuration Exam ple for an S7 FH Systems F-System

    The following figure illustrates an example of an S7 FH Systems system with redundant F-

    CPU and shared, switched distributed I/O, as well as connection to a redundant system bus.

     Figure 2-5 S7 FH Systems Fail-safe System

    2.2.4 Coexistence of Standard and Fail-safe Com ponents

    Coexistence Is Possible

    Standard, fault-tolerant (H-), and fail-safe (F-) components and systems can be used incombination as follows:

    Standard systems, H-systems, F-systems, and FH systems can coexist in a system .• In an F-system :

     – Distributed I/O devices and systems can be operated with standard and fail-safe I/O,such as ET 200S, ET 200pro and ET 200eco.

     – S7-300 standard and fail-safe signal modules can be operated in safety mode both ascentralized modules (in S7 Distributed Safety only) and as decentralized modules inET 200M.

    • In an F-system or FH-system, a standard user program can be executed along with thesafety program.

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    38/162

    Configurations and Help with Selection

    2.2 Configuration of F-Systems

    Safety Engineering in SIMATIC S72-8  System Manual, 08/2005, A5E00109529-04

    Advantages

    Coexistence of F-components, H-components, and standard components has the followingadvantages:

    • It is possible to configure a totally integrated automation system that takes advantage ofstandard CPU innovation. At the same time, fail-safe components are implementedindependently of standard components such as FMs or CPs. The entire system isconfigured and programmed with standard tools such as HW Config , FBD, LAD, or CFC.

    • The coexistence of standard and fail-safe program parts in one F-CPU reduces the costof acceptance tests because program parts not required to be fail-safe can be swappedout to the standard user program. This reduces the size of the safety program, that is, thepart of the program that must pass an acceptance test.

    Maintenance costs can also be reduced if as many functions as possible are moved tothe standard user program, since the standard user program can be modified duringoperation.

    Boundary C onditions for Coexistence

    Warning

    For applications with safety classSIL2/Category 3

     and lower, physical contact protectionmeasures for standard components are sufficient (see the manuals for the F-CPU and F-I/Oyou are using).

    Applications with safety class SIL3/Category 4 require certain measures beyond physicalcontact protection to prevent hazardous overvoltages of F-circuits via the power supply andbackplane bus, even in the event of a fault. Therefore, the following are provided forprotection from backplane bus influence:

    • Safety protector for centralized and decentralized configuration of S7-300 F-SMs• For S7 F/FH Systems, PROFIBUS DP with fiber-optic cable design

    • ET 200S fail-safe modules and ET 200eco fail-safe I/O module exhibit a 250 VAC isolationinternally.

    To protect against influence by the power supply, configuration rules for power supplies,standard I/O, and fail-safe I/O are available (see Fail-safe I/O manuals ).

    Rules for Using the S afety Protector

    The safety protector protects the F-SMs from possible overvoltages in the event of a fault.

    Warning

    The safety protector must be used for SIL3/Category 4 applications:• Generally, when the F-SMs are used as centralized modules in an S7-300

    • Generally, when PROFIBUS DP is configured with copper cable

    • When PROFIBUS DP is configured with fiber-optic cable and combined operation of standard andfail-safe SMs in one ET 200M is required

    For a detailed description of the safety protector, refer to the Automation System S7-300Fail-safe Signal Modules  manual.

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    39/162

      Configurations and Help with Selection

    2.3 Configuration Variants for Fail-safe Systems According to Availability Requirements

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 2-9 

    2.3 2.3Configuration Variants for Fail-safe Systems A ccording to Availability

    Requirements

    Options for Increasing Availability

    To increase availability of an automation system and, thus, to prevent process failures due tofaults in the F-system, S7 F Systems fail-safe systems can be configured optionally as fault-tolerant systems (S7 FH Systems). This increased availability can be achieved bycomponent redundancy (F-CPU, communication connections, and F-I/O).

    For S7 F Systems, availability can be increased without fault-tolerant configuration. Fail-safesignal modules (F-SMs) can be used redundantly in one ET 200M or in several ET 200Ms.

    The following section includes a description of how to achieve increased availability throughredundancy of the F-CPU and F-I/O in S7 FH Systems.

    Note

    Availability of the fail-safe CPUs in S7 Distributed Safety and S7 F Systems cannot beincreased by using the "SW Redundancy" software package.

    Configuration Op tions in Safety Mode

    Fail-safe systems can be configured three different ways, as follows:

    Table 2-1 Configuration Options for Fail-safe Systems According to Availability

    System Configuration

    Option

    Description Availability

    S7Distributed

    Safety

    S7 FSystems

    • Single-channelI/O

    Single-channel and fail-safe (F-CPU and F-I/Oare not redundant)

    Standardavailability

    • Single-channelswitched I/O

    Single-channel switched and fail-safe (F-CPUis redundant, F-I/O is not redundant; in the

    event of a fault, the system switches over tothe other F-CPU)

    Increasedavailability

    S7 FHSystems

    • Redundantswitched I/O

    Multichannel and fail-safe (F-CPU, PROFIBUSDP, and F-I/O are redundant)

    Highestavailability

    Typical configuration examples are presented below. A different level of availability ofprocess data is achieved for each configuration variant.

    Additional Information about Increased Availability

    Communication between F-CPUs in S7 FH Systems is described in the Safety-Related CPU- CPU Communication  section of this manual. For information about S7-400H fault-tolerantsystems, refer to the Automation System S7-400H Fault-Tolerant Systems  manual.

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    40/162

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    41/162

      Configurations and Help with Selection

    2.3 Configuration Variants for Fail-safe Systems According to Availability Requirements

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 2-11 

    Configuration Exam ple of S7 D istributed Safety: Single-channel I/O (Stand-alone IM 151-7 F-CPU )

     

    Figure 2-7 S7 Distributed Safety with Single-channel I/O (Stand-Alone IM 151-7 F-CPU)

    Distributed Configuration of S7 Distributed Safety and PRO FIBUS DP w ith Copper Cable

    The following are required for distributed configuration with copper cable:

    • One CPU 416F-2, CPU 31xF-2 DP, CPU 31xF-2 PN/DP or IM 151-7 F-CPU

    • One PROFIBUS DP line

    • Fail-safe I/O, for example:

     – One ET 200M with:IM153-2, F-SMs, and, if necessary, standard SMs,safety protector (required for SIL3/Category 4 applications only)

     – One ET 200S with:IM 151-1 HIGH FEATURE or IM 151-7 F-CPU,fail-safe modules, and, if necessary, ET 200S standard modules

     – One ET 200pro with:IM 154-2 HIGH FEATURE,fail-safe modules, and, if necessary, ET 200pro standard modules

     – ET 200eco fail-safe I/O module

     – Fail-safe DP standard slaves

    • Bus connector for connecting the F-CPU and fail-safe I/O to the PROFIBUS DP

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    42/162

    Configurations and Help with Selection

    2.3 Configuration Variants for Fail-safe Systems According to Availability Requirements

    Safety Engineering in SIMATIC S72-12  System Manual, 08/2005, A5E00109529-04

    Configuration E xample of S7 Distributed Sa fety: Single-channel I/O (Distributed Configuration with

    Copper Cable)

    PROFIBUS DP

     

     Figure 2-8 S7 Distributed Safety with Single-channel I/O (PROFIBUS DP, Copper Cable)

    Distributed Configuration of S7 D istributed Safety and PRO FIBUS DP w ith Fiber-optic Cable

    The following are required to configure PROFIBUS DP with fiber-optic cables:

    • One CPU 416F-2, CPU 31xF-2 DP, CPU 31xF-2 PN/DP or IM 151-7 F-CPU

    • One PROFIBUS DP line

    • Fail-safe I/O, for example:

     – One ET 200M with:IM153-2 FO, F-SMs, and, if necessary, standard SMs,safety protector (required for SIL3/Category 4 applications only if F-SMs and standardSMs are used together in an ET 200M)

     – One ET 200S with:IM 151-1 HIGH FEATURE or IM 151-7 F-CPU,fail-safe modules, and, if necessary, ET 200S standard modules

     – One ET 200pro with:IM 154-2 HIGH FEATURE,fail-safe modules, and, if necessary, ET 200pro standard modules

    • Components for connecting the F-CPU and fail-safe I/O to the fiber-optic cable, forexample, OLM/OBT

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    43/162

      Configurations and Help with Selection

    2.3 Configuration Variants for Fail-safe Systems According to Availability Requirements

    Safety Engineering in SIMATIC S7System Manual, 08/2005, A5E00109529-04 2-13 

    Configuration E xample of S7 Distributed Safety: Single-channel I/O (Distributed Configuration with

    Fiber-optic Cable)

    OLM/OBT

    OLM/OBT

    PROFIBUS DP

     Figure 2-9 S7 Distributed Safety with Single-channel I/O (PROFIBUS DP, Fiber-optic Cable)

    Distributed Configuration of S7 Distributed Safety and PR OFINE T IO

    The following are required to set up PROFINET IO:

    • One CPU 31xF-2 PN/DP or CPU 416F-2 (as of firmware version V 4.1) with CP 443-1Advanced

    • One PROFINET IO line

    • Fail-safe I/O for PROFINET IO, for example:

     – One ET 200pro with:

    IM 154-4 PN HIGH FEATURE

    Fail-safe modules and ET 200pro standard modules, if necessary

     – One ET 200S with:

    IM 151-3 PN HIGH FEATUREFail-safe modules and ET 200S standard modules, if necessary

    • Fail-safe I/O standard devices

    • Components for configuring PROFINET

     – Passive network components (cables, plugs)

     – Active network components (switches, routers, etc.) if necessary

  • 8/18/2019 Siemens Safety Engineering in SIMATIC S7.pdf

    44/162

    Configurations and Help with Selection

    2.3 Configuration Variants for Fail-safe Systems According to Availability Requirements

    Safety Engineering in SIMATIC S72-14  System Manual, 08/2005, A5E00109529-04

    Configuration Exam ple of S7 Distributed Safety and PRO FINET IO

    PROFINET IO

     Figure 2-10 S7 Distributed Safety with Single-channel I/O (PROFINET IO)

    Limits of Availability with Single-channel I/O

    In the event of a fault, the I/O are no longer available. The F-I/O is passivated.Possible fault causes:

    • Failure of F-I/O

    • Failure of interface module in an ET 200M, ET 200S or ET 200pro

    • Failure of the entire ET 200M, ET 200S, ET 200pro or ET 200eco

    • Fai