Series Generator,Shunt generators and

compound generators

Page 2: SERIES, SHUNT AND COMPOUND GENERATORS

Series Generator- the armature coils and the series field coils are connected in series.

In this generator, because field windings are in series with the armature, they carry full armature current Ia. As Ia is increased, flux and hence generated e.m.f. is also increased.

Page 3: SERIES, SHUNT AND COMPOUND GENERATORS

Curve Oa - is the O.C.C

ab - the extra exciting current necessary to neutralize the weakening effect of armature reaction at full load.

ordinate bc = gh = armature voltage drop, then point c lies on the external characteristic

point c- lies on the external characteristic

Page 4: SERIES, SHUNT AND COMPOUND GENERATORS

It will be noticed that a series generator has rising voltage characteristic i.e. with increase in load, its voltage is also increased. But it is seen that at high loads, the voltage starts decreasing due to excessive demagnetising effects of armature reaction. In fact, terminal voltage starts decreasing as load current is increased as shown by the dotted curve. For a load current OC′, the terminal voltage is reduced to zero as shown.

Page 5: SERIES, SHUNT AND COMPOUND GENERATORS

Example 1. In a 220 V supply system, a series generator, working on a linear portion of its magnetisation characteristic is employed as a booster. The generator characteristic is such that induced e.m.f. increases by 1 volt for every increase of 6 amperes of load current through the generator. The total armature resistance of the generator is 0.02 ΟΗΜ. If supply voltage remains constant, find the voltage supplied to the consumer at a load current of 96 A. Calculate also the power supplied by the booster itself.

Solution. Voltage increase for 6 amperes = 1 V Voltage increase for 96 A = 96/6 = 16 V Voltage drop in series coils = 96 (0.02) = 1.9 V Net Voltage rise due to booster = 16 −1.9 = 14.1V Voltage at consumer end = 220 + 14.1 = 234.1 V

Power supplied by booster itself = 14.1(96) = 1354W = 1.354 kW

Page 6: SERIES, SHUNT AND COMPOUND GENERATORS

Compound-wound Generator

Page 7: SERIES, SHUNT AND COMPOUND GENERATORS

Compound-wound Generator

is unsuitable where constancy of terminal voltage is essential, because its terminal voltage decreases as the load on it increases. This decrease in V is particularly objectionable for lighting circuit where even slight change in the voltage makes an appreciable change in the candle power of the incandescent lamps.

may be made to supply substantially constant voltage (or even a rise in voltage as the load increases) by adding to it a few turns joined in series with either the armature or the load.

shunt generator

These turns are so connected as to aid to shunt turns when the generator supplies load.

Page 8: SERIES, SHUNT AND COMPOUND GENERATORS

Types of Compound-wound Generator

long shunt compound generatorthe series field coils are connected in series with the armature coils while the shunt field coils are connected across the series

combination.

Page 9: SERIES, SHUNT AND COMPOUND GENERATORS

the the series field coils are connected in series with the load while the shunt field coils are connected across armature coils

short shunt compound generator

Page 10: SERIES, SHUNT AND COMPOUND GENERATORS

As the load current increases, the current through the series windings also increase thereby increasing the flux. Due to the increase in flux, induced e.m.f. is also increased. By adjusting the number of series turns (or series amp-turns), this increase in e.m.f. can be made to balance the combined voltage drop in the generator due to armature reaction and the armature drop. Hence, V remains practically constant which means that field current is also almost unchanged

three causes which decrease the terminal voltage of a shunt generator

1. flat-compounded – if the series field amp-turns are such as to produce the same voltage at rated load as at no-load.

2. Over-compounded – if the series field amp-turns are such that the rated-load voltage is greater than the no load voltage.

3. under-compounded – if the rated-lad voltage is less than the no- load.This generators are seldom used.

Page 11: SERIES, SHUNT AND COMPOUND GENERATORS

For short distances such as in hotels and office buildings, flat-compound generators are used because the loss of voltage over small lengths of the feeder is negligible. But when it is necessary to maintain a constant voltage then an over-compounded generator, which combines the functions of a generator and a booster, is invariably used.

Page 12: SERIES, SHUNT AND COMPOUND GENERATORS

are used for ordinary lighting and power supply purposes. They are also used for charging batteries because their terminal voltages are almost constant or can be kept constant.

Shunt generators with field regulators

Uses of D.C. Generators

Page 13: SERIES, SHUNT AND COMPOUND GENERATORS

Series generatorsare not used for

power supply because of their rising

characteristics. However, their rising

characteristic makes them suitable for being used

as boosters in certain types of

distribution systems particularly in railway

service.

Page 14: SERIES, SHUNT AND COMPOUND GENERATORS

Compound generators – is a machine having both shunt and series excitation where the series field is wound directly over the shunt field

is the most widely used d.c. generator because its external characteristic can be adjusted for compensating the voltage drop in the line resistance.

cumulatively-compound generator

differential-compound generator

has an external characteristic similar to that of a shunt generator but with large demagnetization armature reaction. Hence, it is widely used in arc welding where larger voltage drop is desirable with increase in current.