Secondary Unit Substations
Transcript of Secondary Unit Substations
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog14-40
14SW
ITCH
GEAR
For more information, please visit http://automation.usa.siemens.com/consultant/ or contact your local sales office.
Siemens / Speedfax Previous folio: 13-49
Secondary Unit SubstationsOverview GeneralSiemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically and electrically connected to and coordinated in design with one or more switchgear or switchboard assemblies. A secondary unit substation is defined as a unit substation whose outgoing section is rated below 1000 volts.
A typical secondary unit substation consists of three sections:n Primary: an incoming section that
accepts incoming high voltage (2400 to 13,800 volts) line
n Transformer: section that transforms incoming voltage down to utilization voltage (600 volts or less)
n Secondary: an outgoing section that distributes power to outgoing feeders and provides protection for these feeders (600 volts and less)
Standard secondary unit substations consist of:n Medium Voltage Primaryn Transformern Low Voltage Secondary
Siemens also offers low voltage unit substations with:n Low Voltage Primaryn Transformern Low Voltage Secondary
The primary reason for using a secondary unit substation is to bring power as close as possible to the center of the loads. Another reason is that it provides a system design concept incorporating a wide variety of components that permits tailoring equipment to the needs of the application. A secondary unit substation providesn Reduced power lossesn Better voltage regulationn Improved service continuityn Increased functional flexibilityn Lower installation costn Efficient space utilization
Every component and assembly of secondary unit substations are designed and engineered as an integral part of a complete system.
PrimarySwitch
PrimarySwitch
PrimarySwitch
LiquidFilledTransformer
LiquidFilledTransformer
SwitchboardwithWLEncasedSystemsBreakers
TypeSB3SwitchboardwithFusibleSwitches
TypeWLLowVoltageSwitchgear
DryTypeTransformer
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 14-41
14SW
ITCHGEAR
Siemens Unit Substation Solutions5–27.6 kV Type SIMOSEC Metal-Enclosed Load Interrupter Primary Switch
Dimensions
Cable switch CS Fused switch FS Duplex switch
WidthSinglecableorfuseThreecablesordouble-barrelfuseTwocables+SAor3-barrelfuse
14.8”(375mm)19.7”(500mm)29.6”(750mm)
14.8”(375mm)19.7”(500mm)29.6”(750mm)
19.7”(500mm)+19.7”(500mm)29.6”(750mm)+19.7”(500mm)
Depth 48.4”(1,230mm)
Height 88.6-100.4”(2,250-2,850mm)dependingonarrangement
Technical DataRatedvoltage 5kV 8.25kVand15kV 27.6kV
Ratedfrequency 50/60Hz 50/60Hz 50/60Hz
Ratedshort-durationpower-frequencywithstandvoltage 19kV 36kV 60kV
Ratedlightning-impulsewithstandvoltage(BIL) 60kV 95kV 125kV
Ratedshort-timewithstandcurrent,twoseconds Upto25kA Upto25kA Upto20kA
Fusedshort-circuitcurrentrating(FSpanelsonly)SinglefuseFS-1DoublefuseFS-2TriplefuseFS-3
63kA(to450E)63kA(totwo350E)63kA(tothree200E)
63kA(to200E)63kA(totwo200E)63kA(tothree200E)
20kA20kA20kA
Maximumfusedcontinuouscurrent(notequaltofuseErating)
SinglefuseFS-1 325A 165A 65A
DoublefuseFS-2 575A 305A 117A
TriplefuseFS-3 600A 430A 156A
SwitchdisconnectorContinuous 600A 600A 600A
Interrupting 600A 600A 600A
Mainbuscontinuouscurrentrating 1,200A 1,200A 1,200A
n Standard capacitive voltage indicators to show whether the cable side is energized or not
n Integrated mechanical interlockingn Animated mimic diagram (mimic bus)n Main bus at top or bottom to suit
applicationn Configurations: individual feeder switches,
transformer primary switches and switch line-ups
n Ideal for utility, construction and industrial applications
n Over 20 years of field experience with more than 350,000 switch-disconnector units installed
n Switch-disconnector contacts maintenance free and sealed for life.
n Main bus continuous current rating” (row title) (blank 2nd column from left) and “1,200 A” in each of three columns on right
SIMOSEC Specificationsn Extremely compact footprintn Meets ANSI/IEEE C37.20.3n UL or C-UL listing availablen Seismic compliant up to IBC 2003n High switching capacity - 100 operations
at 600A - five times higher than ANSI requirements
n Gas-insulated, three-position switch\disconnector, hermetically sealed for life inside a stainless steel vessel
n Switch-disconnector combines the functions of a load-interrupter switch(with CLOSED-OPEN indication) and an optional grounding switch (with OPEN-GROUND indication)
n Front accessible fuses and outgoing cables, which means type SIMOSEC switches can be placed against the wall and maximize the use of available space
n Convenient viewing window for visible verification of primary contact position (visible break)
Siemens / Speedfax Previous folio: New page from TRSA-SIMOSC-0810 SS 2/08/11
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog14-42
14SW
ITCH
GEAR
High-voltage (HV) Fuse Selection Table
Allowable continuous current (A)
Maximum voltage (kV) Fuse typeE -rating (open air) FS-1 FS-2 FS-3
5.5 55GDMSJ10ES 10E 10
5.5 55GDMSJ15E 15E 15
5.5 55GDMSJ20ES 20E 20
5.5 55GDMSJ25ES 25E 25
5.5 55GDMSJ30ES 30E 30
5.5 55GDMSJ40ES 40E 40
5.5 55GDMSJ50ES 50E 50
5.5 55GDMSJ65ES 65E 65
5.5 55GDMSJ80ES 80E 80
5.5 55GDMSJ100ES 100E 100
5.5 55GDMSJ125ES 125E 120
5.5 55GFMSJ150ES 150E 150
5.5 55GFMSJ175ES 175E 164
5.5 55GFMSJ200ES 200E 183 327
5.5 55GFMSJ250ES 250E 220 390
5.5 55GFMSJ300ES 300E 241 429 598
5.5 55GFMSJ350ES 350E 269 478 600
5.5 55GFMSJ400ES 400E 302 536 600
5.5 55GFMSJ450ES 450E 325 575 600
17.5 175GDMSJ10ES 10E 10
17.5 175GDMSJ15ES 15E 15
17.5 175GDMSJ20ES 20E 20
17.5 175GDMSJ25ES 25E 25
17.5 175GDMSJ30ES 30E 30
17.5 175GFMSJ40ES 40E 40
17.5 175GFMSJ50ES 50E 50
17.5 175GFMSJ65ES 65E 59
17.5 175GXMSJ80ES 80E 73
17.5 175GXMSJ100ES 100E 85
17.5 175GXQSJ125ES 125E 112 207
17.5 175GXQSJ150ES 150E 123 238 336
15.5 155GXQSJ175ES 175E 167 310 420
15.5 155GXQSJ200ES 200E 165 305 430
Siemens Unit Substation SolutionsHigh-voltage (HV) Fuse Selection Table General
Siemens / Speedfax Previous folio: New page from TRSA-SIMOSC-0810 SS 2/08/11
Example:n 5,000 kVA, 12.47 kV transformern Full-load current 231.5 An Multiplier 1.33n Current for fuse-size selection =
1.33 x 231.5 A - 308 An Multiplier of 1.33 for transformer with fan-cooled rating
125% of self-cooled rating (adjust multiplier for differing fan-cooled transformer capability)
n Fuse rating = 2 x 175E/phase (FS-2).
FS-1:Onefusebarrelperphase FS-2:Twofusebarrelsperphase FS-3:Threefusebarrelsperphase
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 14-43
14SW
ITCHGEAR
Siemens offers a wide variety of unit substation designs to meet virtually any customer requirement. A unit substation consists of one or more transformers mechanically and electrically connected to, and coordinated with, one or more switchgear or switchboard assemblies. A secondary unit substation is defined as a unit substation whose outgoing section is rated below 1,000 volts.
A typical secondary unit substation consists of three sections:n Primary: depending on the specific
application, this section accepts medium voltage (2,400 to 27,600 volts) incoming power
n Transformer: reduces incoming voltage to utilization voltage (600 volts or less)
n Secondary: distributes power to, and provides protection for, outgoing feeders (600 volts and less).
The key benefit of a secondary unit substation is that it economically brings power as close as possible to the loads, minimizing power loss and maximizing voltage regulation. It also enhances flexibility, using a system design concept that integrates a wide variety of components to tailor the equipment to the specific needs of each application.
Every component or assembly utilized in secondary unit substations is engineered to be an integral part of a complete system.
A secondary unit substation helps you:n Reduce power lossesn Enhance voltage regulationn Improve service continuityn Increase functional flexibilityn Lower installation costsn Minimize space utilization.
SIMOSEC Primary Switch Dry-Type Transformer Type SB3 Switchboard
SIMOSEC Primary Switch Liquid Filled Type Transformer Type SB3 Switchboard
Siemens Unit Substation SolutionsOverview
Siemens / Speedfax Previous folio: New page from TRSA-SIMOSC-0810 SS 2/08/11
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog14-44
14SW
ITCH
GEAR
Siemens Unit Substation SolutionsTransformers: Dry Type — VPI/VPE
N.P.
Plan view
W
Fancontrol
when req.
18 in.(457 mm)
Std.
LVair
terminalchamber(optional)
HVair
terminalchamber(optional)
Front viewindoor
18 in.(457 mm)
Std.
D
H
Danger
Front
Fancontrolpanel
Groundbus
W
Front viewoutdoor
HV-terminal
4 in. 4 in.
Siemens / Speedfax Previous folio: New page from TRSA-SIMOSC-0810 SS 2/08/11
Type = VPI/VPE
Primary Volts = 2400-13800
Sec_Volts = 208-600
Temperature Rise = 150C for Aluminum Windings, 80/115C for Copper Windings
Standard kV BIL (HV/LV) = 60/30 for Aluminum Windings, 95/30 for Copper Windings
Table 1 Low Voltage Switchgear or Switchboard Coordination
Winding Material KVAHeight(Inches)
Width(Inches)
Depth(Inches)
Weight(Pounds)
Aluminum 300 90 90 54 4600Aluminum 500 90 90 54 4800Aluminum 750 90 90 54 5800Aluminum 1000 90 102 60 7000Aluminum 1500 96 102 60 9200Aluminum 2000 102 102 60 11000Aluminum 2500 108 112 60 12200Aluminum 3000 108 118 60 14100Aluminum 3750 112 126 66 15800Aluminum 5000 118 132 66 17000Copper 300 90 90 54 6000Copper 500 90 96 60 6400Copper 750 90 102 60 8000Copper 1000 96 102 60 9700Copper 1500 102 108 60 13200Copper 2000 108 112 60 17400Copper 2500 118 126 60 19000Copper 3000 118 132 60 22000Copper 3750 126 132 66 27000Copper 5000 132 138 66 30000
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 14-45
14SW
ITCHGEAR
Siemens Unit Substation SolutionsTransformers: Dry Type — Cast Coil
Siemens / Speedfax Previous folio: New page from TRSA-SIMOSC-0810 SS 2/08/11
Type = Cast Coil
Primary Volts = 2400-13800
Sec_Volts = 208-600
Temperature Rise = 80/115C for Both Aluminum & Copper Windings
Standard kV BIL (HV/LV) = 60/30 for Aluminum Windings, 95/30 for Copper Windings
Table 2 Low Voltage Switchgear or Switchboard Coordination
Winding Material KVAHeight(Inches)
Width(Inches)
Depth(Inches)
Weight(Pounds)
Aluminum 300 90 90 54 5500Aluminum 500 90 90 54 6300Aluminum 750 90 96 60 7800Aluminum 1000 96 102 60 9500Aluminum 1500 102 108 60 11500Aluminum 2000 108 112 60 13800Aluminum 2500 112 126 60 16200Aluminum 3000 118 132 60 19200Aluminum 3750 126 138 66 25000Aluminum 5000 132 144 66 28000Copper 300 90 90 60 6200Copper 500 90 96 60 7000Copper 750 90 102 60 9100Copper 1000 96 112 60 10600Copper 1500 102 118 60 14300Copper 2000 108 118 66 18200Copper 2500 118 126 66 19500Copper 3000 126 132 66 23500Copper 3750 126 144 66 28000Copper 5000 132 160 66 35000
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog14-46
14SW
ITCH
GEAR
Siemens Unit Substation SolutionsTransformers: Liquid Filled Type
X3X2X1X0
H3
H2
H1
D
C
J
H
G
B
A
8
E F
Top view Elevation
Weights,gallonsoffluidanddimensionsareforreferenceonly,andnotforconstruction.PleasecontactSiemensIndustryInc.forexactdimensions
Siemens / Speedfax Previous folio: New page from TRSA-SIMOSC-0810 SS 2/08/11
Aluminum Windings Copper Windings
Drawing Dimensions (in.) Gallons Of Fluid
Approx. Total Weight (lbs.) (With Fluid)
Gallons Of Fluid
Approx. Total Weight (lbs.) (With Fluid)kVA A B C D E F G H J
500 66 51 26 52 45 45 30 60 35 300 5600 310 5900750 75 59 26 52 55 55 34 68 35 360 7000 370 7400
1000 75 67 26 52 55 55 38 76 35 420 8400 430 88001500 75 59 59 80 55 55 34 68 35 400 9500 420 100002000 85 67 67 90 55 55 38 76 39 520 12000 500 128002500 85 75 68 92 55 55 42 84 41 570 14600 590 149003750 85 75 70 120 65 65 42 84 45 790 20500 830 215005000 99 87 72 144 65 65 48 96 49 1050 26000 1090 280007500 99 95 74 148 75 75 52 104 53 1320 35000 1360 37000
10,000 99 103 76 152 75 75 56 112 57 1740 43000 1780 4500012,000 99 103 82 164 75 75 56 112 61 1850 49000 1880 50000
Unit Type Substation Transformer Primary Volts = 25kV and below, Secondary Voltage = 5kV and below
Table 3 Liquid-Filled 55/65 °C Rise
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 14-47
14SW
ITCHGEAR
Siemens Unit Substation SolutionsType WL Low Voltage Switchgear Substation Secondaries
Siemens type WL low-voltage, metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of the type WL low voltage switchgear is the world class Siemens type WL breaker. Siemens type WL low-voltage switchgear can be utilized in the following applications:n Industrial n Institutionaln Critical powern Utility and co-generationn Commercial.
Product Scopen Equipment ratings:
635 Vac maximum
Three-phase, three-wire
Three-phase, four-wire
50/60 Hz
6,000 A maximum horizontal bus
5,000 A maximum vertical bus.n Enclosure options:
NEMA 1 indoor
NEMA 3R outdoor walk-in
NEMA 3R outdoor non walk-in.
Exclusive featuresGenerator/utility protection sets24/7/365 power availability is critical for some systems. On-site generation capabilities are becoming more and more common. Type WL digital electronic trip units allow the system designer to precisely tailor trip settings for the most demanding requirements.
The Siemens type WL 776 trip unit allows one set of trip settings for a fully loaded utility feed and, with a simple contact closure, the trip unit toggles to a second trip set tailored to provide optimal generator protection. The wide range of settings allows the type WL to provide protection for a minimal generator capacity for only essential loads, through full backup for an entire facility. This dual utility/generator protection capability in a single circuit breaker allows the system designer unparalleled, cost effective flexibility.
Extended instantaneous protection (EIP)This patent pending type WL trip unit feature allows the system designer to achieve full selective trip coordination up to the short-time rating of the frame, while also allowing application of the circuit breaker up to the interrupting rating of the frame. EIP allows the type WL breaker to be applied up to the full withstand rating of the circuit breaker, for complete coordination, with a minus 0% short-time band tolerance up to 85 kA on Frame Size II and 100 kA on Frame Size III.
Above fault currents of 20-percent higher than the full short-time rating, the type WL circuit breaker is self-protecting, and the EIP function will trip the circuit breaker instantly to protect the frame and the system from these extremely high currents (as high as 150 kA on Frame Size III). An added benefit is that arc flash energy is greatly reduced in this high- current region due to EIP’s instantaneous trip response.
Industry standardsType WL switchgear with power circuit breakers are designed, tested and constructed in accordance with: n UL 1558—Metal-Enclosed Low-
Voltage Power Circuit Breaker Switchgear
n ANSI C37.20.1—Metal-Enclosed Low- Voltage Power Circuit Breaker Switchgear.
Type WL drawout circuit breakers are designed for continuous operation at 100-percent of their current rating without the need for external heat sinks, and are in accordance with:n UL 1066—Low-Voltage AC and DC
Power Circuit Breakers Used in Enclosures
n ANSI C37.13—Low-Voltage AC Power Circuit Breakers Used in Enclosures.
Switchgear SecondaryNote: See Pages 14-52 to 14-61 for complete details concerning WL Low Voltage Switchgear unit substation secondaries.
Siemens / Speedfax Previous folio: New page from TRSA-SIMOSC-0810 SS 2/08/11
For more information, visit our web site at: www.usa.siemens.com/switchgear.
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog14-48
14SW
ITCH
GEAR
Siemens Unit Substation SolutionsSwitchboard Substation Secondaries
Siemens / Speedfax Previous folio: New page from TRSA-SIMOSC-0810 SS 2/08/11
Product OverviewSiemens modular front connected switchboard design provides a broad range of features and capabilities for a wide range of applications.
Every aspect of design of Siemens switchboards has been aimed at improving layout convenience, reducing installation costs and minimizing the impact and cost of changes to the system.
Siemens switchboards provide a rugged design and the flexibility necessary in electrical systems for all types of applications, some examples are:
n Industrial plantsn High-rise complexesn Hospitalsn Commercial buildings
Standards and CertificationsSiemens switchboards are designed, tested and constructed in accordance with:
n UL891 – Switchboardsn NEMA PB-2n Seismially qualifiedn Other equipment is UL listed as
applicable
Features & BenefitsSiemens switchboards ratings and features include:
n Up to 6000 ampere main bus ratingn Up to 600 volts ACn Bus bracing up to 200KAICn Copper or aluminum bussingn Temperature or density rated bussingn Type 1 and Type 3R enclosuresn Main and branch circuit breakers and
fusible switchesn Thermal magnetic and solid state
circuit breakersn Surge protective devicesn Utility metering provisions
n ACCESS power monitoring on mains and branches
n Ground fault protection on mains and branches
n Busway and transformer connectionsn Protective relayingn Two and three device autothrowover
scheme
Further Switchboard InformationSee Section 13 for complete details concerning SB3 front-connected switchboard unit substation secondaries.
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 14-49
14SW
ITCHGEAR
Transformer
38.0 38.0
AreaRestricted
conduitTop and bottom
48.4
19.7 W
�
D 58.0�
Section #1 Section #2
Unit space
38" (965 mm)
Type SB3 switchboard digital meter type SPD module
90" (2,286 mm)
38" (965 mm)
19.7" (500 mm)
100.4" (2,550 mm)
PrimaryluglocationSeepage5fortransformerdimensions.
PrimarySwitchrequiresfrontaccessfortopcableentryterminations.Transformerrequiresaccessfromthefrontand12”(305mm)onthebacksideforventilationspace.
Plan view
Front view
Siemens Unit Substation SolutionsIndoor Dry Type Transformer Sketch Page
Siemens / Speedfax Previous folio: New page from TRSA-SIMOSC-0810 SS 2/08/11
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog14-50
14SW
ITCH
GEAR
Plan view
Front view
Siemens Unit Substation SolutionsIndoor Liquid Filled Transformer Sketch Page
Section #2 Section #3 Section #1
Primary Switch requires front access for top cable entry terminations. Transformer requires access from the front and 12" (305 mm) on the back side for ventilation space.
Liquid filledtransformer 100.4”
(2,550 mm)
Main breaker
Metering/SPD
X3
X2
X1
X0H1
H2
H3
19.7”(500 mm)
48.4”(1,229 mm)
spac
e in
top
or
bott
om
for
cust
omer
's c
able
s.
Max
imu
m a
vaila
ble
Space for secondary leads from above.
31.5” (800 mm)
Space for secondary leads from above.
for
cust
omer
's c
able
s.sp
ace
in t
op o
r bo
ttom
M
axim
um
ava
ilabl
e
Space for secondary leads from above.
Space for secondary leads from below.
spac
e in
top
or
bott
om
for
cust
omer
's c
able
s.
Max
imu
m a
vaila
ble
Space for secondary leads from below.
Space for secondary leads from below.
�
32.0”(813 mm)
22.0”(559 mm)
22.0”(559 mm)
D
Transformer
W
� 70.0”(1,778 mm)
102.2”(2,596 mm)
31.5” (800 mm)
31.5” (800 mm)
32.0”(813 mm)
22.0”(559 mm)
22.0”(559 mm)
Primaryluglocations.Seepage6fortransformerdimensions.
PrimarySwitchrequiresfrontaccessfortopcableentryterminations.Transformerrequiresaccessfromthefrontand12”(305mm)onthebacksideforventilationspace.
Siemens / Speedfax Previous folio: New page from TRSA-SIMOSC-0810 SS 2/08/11
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 14-51
14SW
ITCHGEAR
Section #1
103.1”(2,619 mm)
Outdoor type
SIMOSEC switch
30.2”(767 mm)
76.8”(1,951 mm)
W
Walk-in aisle Door
113.9”(2,893 mm)
Door
Section #2 Section #3
X0
X1
X2
X3H1
H2
H3H3
H2
H1
42.7”(1,085 mm)
59.9”(1,521 mm)
Allow 6” clearancefor door swing
124.0”(3,150 mm)
Low voltage switchgear
�
D
Liquid filledtransformer
�
Primaryluglocations.Seepage6fortransformerdimensions.
Plan view
Front view
Siemens Unit Substation SolutionsOutdoor Liquid Type Transformer Sketch Page
Siemens / Speedfax Previous folio: New page from TRSA-SIMOSC-0810 SS 2/08/11