SC200 System Controller Operation Handbooknanapowerinc.com/DC Power...

129
SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue Date: May 2011 Eaton Corporation Telecommunications Power Solutions www.eaton.com/telecompower [email protected]

Transcript of SC200 System Controller Operation Handbooknanapowerinc.com/DC Power...

Page 1: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 System Controller

Operation Handbook

Issue: IPN 997-00012-50G

Issue Date: May 2011

Eaton Corporation

Telecommunications Power Solutions

www.eaton.com/telecompower

[email protected]

Page 2: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

The product discussed in this literature is subject to terms and conditions outlined in Eaton selling policies. The sole source governing the rights and remedies of any purchaser of this equipment is the relevant Eaton selling policy.

No warranties, express or implied, including warranties of fitness for a particular purpose or merchantability, or warranties arising from course of dealing or usage of trade, are made regarding the information, recommendations and descriptions contained herein.

In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein.

The information contained in this literature is subject to change without notice.

Subject to the right to use its equipment, Eaton Corporation does not convey any right, title or interest in its intellectual property, including, without limitation, its patents, copyrights and know-how.

No part of this literature may be reproduced or transmitted in any form, by any means or for any purpose other than the Purchaser’s personal use, without the express written permission of Eaton Corporation.

Eaton®, Matrix, Powerware

®, Intergy

TM, CellSure

TM, SiteSure

TM, PowerManagerII

TM and DCTools

TM are trade

names, trademarks, and/or service marks of Eaton Corporation or its subsidiaries and affiliates. Unless otherwise noted, brands, product names, trademarks or registered trademarks are the property of their respective holders.

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

Page 3: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

About This Guide

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 i

About This Guide

Scope

This guide covers operation of the SC200 system controller with embedded software Version 3.0 or later.

See SC200 Identity Information on page 14 to determine the version of the embedded software.

Audience

This guide is intended for use by:

Installers competent in:

installing and commissioning dc power systems

safe working practices for ac and dc powered equipment

the relevant local electrical safety regulations and wiring standards

Operators and maintenance staff competent in:

operation of dc power systems

safe working practices for ac and dc powered equipment

Related Information

PowerManagerII Online Help

DCTools Online Help

SiteSure-3G Installation and Operation Guide – IPN 997-00012-51

CellSure Installation Guide – IPN 997-00012-20

Reporting Problems with this Guide

Please use this email address to report any problems you find in this guide:

Eaton DC Product Marketing Communications

EMAIL: [email protected]

For Further Information and Technical Assistance

For further information and technical assistance see Worldwide Support on page 115.

Third Party Software

Software code in the SC200 system controller includes the following third party software:

Eric Young is the author of the parts of the library

Page 4: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

ii Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Page 5: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Table of Contents

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 iii

Table of Contents

About This Guide Scope ........................................................................................................................................... i Audience ..................................................................................................................................... i Related Information .................................................................................................................. i Reporting Problems with this Guide ...................................................................................... i For Further Information and Technical Assistance .............................................................. i Third Party Software ................................................................................................................. i

Chapter 1 General Description Overview ................................................................................................................................... 1 SC200 System Controller ......................................................................................................... 2 Input/Output Board ................................................................................................................ 2 Connections ............................................................................................................................... 3 Compatible Software ............................................................................................................... 4

Chapter 2 SC200 Operation Overview ................................................................................................................................... 5 Starting the SC200 .................................................................................................................... 6

Main Screen Shortcut Keys ............................................................................................................. 6 SC200 Operation using the Keypad and Screen ................................................................... 6

Soft Keys ........................................................................................................................................... 7 Navigation Keys .............................................................................................................................. 7 Main Menu Navigation .................................................................................................................. 8 Sub-menu Tabs ................................................................................................................................ 9 Changing a Configuration Setting using the Keypad ............................................................... 10 Keypad Access Security ................................................................................................................ 10 Display Settings ............................................................................................................................. 11 Main Screen Parameters ............................................................................................................... 11 Display Time-out ........................................................................................................................... 12 Alarm Indicators ............................................................................................................................ 12

SC200 Operation Using a PC/Laptop ................................................................................. 13 SC200 Identity Information ................................................................................................... 14 SC200 Internal Clock .............................................................................................................. 14 Language Options .................................................................................................................. 16

Language selection ........................................................................................................................ 16 SC200 Firmware Upgrade ..................................................................................................... 17 Configuration File .................................................................................................................. 17 Backup and Restore ............................................................................................................... 18

Page 6: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

iv Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Chapter 3 System Operation Overview .................................................................................................................................. 19 Voltage Control ....................................................................................................................... 20

Float Voltage ................................................................................................................................... 20 Active Voltage Control (AVC) ..................................................................................................... 21 Battery Current Limit (BCL) ......................................................................................................... 21 Battery Test ..................................................................................................................................... 22 Equalize ........................................................................................................................................... 24 Fast Charge ..................................................................................................................................... 25 Temperature Compensation ......................................................................................................... 27

Rectifiers ................................................................................................................................... 28 Identify a Rectifier .......................................................................................................................... 29 Rectifier Comms Lost Alarm ........................................................................................................ 30 Rectifier Shutdown ........................................................................................................................ 30

Low Voltage Disconnect (LVD) ............................................................................................ 32 Typical LVD Arrangements .......................................................................................................... 33 LVD Operation ............................................................................................................................... 34 LVD Setup ....................................................................................................................................... 35 Smart Alarm Disconnect ............................................................................................................... 38

Alarms ...................................................................................................................................... 39 Types of Alarms ............................................................................................................................. 39 Active Alarm Indications .............................................................................................................. 40 Common Alarm Parameters ......................................................................................................... 41 System Alarm Configuration ....................................................................................................... 42 System Overload Alarm ................................................................................................................ 42 Smart Alarms .................................................................................................................................. 44

Batteries .................................................................................................................................... 49 Batteries Configuration ................................................................................................................. 50 Battery Mid-point Monitoring (MPM) ........................................................................................ 50 Battery Time Remaining ............................................................................................................... 54 Reverse Battery Detection ............................................................................................................. 58

Generator Control Option ...................................................................................................... 60 Configuration ................................................................................................................................. 61

Input/Output (I/O) ................................................................................................................ 62 Identify an I/O Board .................................................................................................................... 62 Analog System Values ................................................................................................................... 63 Analog Inputs ................................................................................................................................. 63 System States .................................................................................................................................. 65 Digital Inputs .................................................................................................................................. 66 Digital Outputs ............................................................................................................................... 67

Data Logging ........................................................................................................................... 68 Event Log ........................................................................................................................................ 68 Data Log .......................................................................................................................................... 69 PC Log ............................................................................................................................................. 70

Page 7: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Table of Contents

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 v

Chapter 4 Communications Overview ................................................................................................................................. 71 Communications Options ..................................................................................................... 72 Direct (USB) Communications ............................................................................................. 72 Ethernet Communications .................................................................................................... 72

DCTools or PowerManagerII Communications Setup (if required) ....................................... 73 Communication via Web Browser .............................................................................................. 74 Communication via a Network Management System using SNMP....................................... 75 Modbus-TCP Communications ................................................................................................... 77

Serial (RS232) Communications ........................................................................................... 78 PSTN Modem Communications .................................................................................................. 78 GSM Modem Communications ................................................................................................... 80 Serial Server .................................................................................................................................... 83

Communications Security ..................................................................................................... 83 Serial Communications (USB/RS232/Ethernet) Security ........................................................ 84 Web Access Security ..................................................................................................................... 85

CSP ........................................................................................................................................... 86

Chapter 5 Maintenance Overview ................................................................................................................................. 87 Troubleshooting ..................................................................................................................... 88 Replacing the System Controller or I/O Board .................................................................. 92

Appendix A Specifications SC200 system controller ........................................................................................................ 93 IOBGP-00, -01 I/O Board ...................................................................................................... 93

Appendix B Alarm Descriptions

Appendix C Connector Pin-outs System Controller Connector Pin-outs .............................................................................. 101 I/O Board (IOBGP-00, -01) Connector Pin-outs ............................................................... 103

Appendix D System Event Types

Appendix E SC200 Mappings I/O Board Mapping ............................................................................................................. 109 Digital Output (Relay) Activation ...................................................................................... 111

Equipment Incident Report

Worldwide Support

Index

Page 8: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

vi Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Page 9: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Chapter 1

General Description

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 1

C h a p t e r 1 General Description

Overview

Topic Page

SC200 System Controller 2

Input/Output Board 2

Connections 3

Compatible Software 4

Page 10: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

2 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

SC200 System Controller

The SC200 system controller is an advanced control and monitoring solution which provides a full suite of communications options, including built-in Ethernet interface, Web server, and SNMP agent.

Alarm notifications may be by SNMP traps, SMS text messaging, dial-out to PowerManagerII remote monitoring software, or relay contact closures.

Power on LED (green)

Minor alarm LED (yellow)

Critical/Major alarm LED (red)

Color LCD

Soft keys (2)

Navigation keys (4)

USB 1.1 connector (12Mb/s)

Retaining screw

Power and system communications connector

RS232 connector

Ethernet connector and status LEDs

The SC200 is supplied pre-configured with either a default configuration file, or with one factory customized for a particular application. Some configuration file changes can be made with the keypad, or all settings can be changed via a PC connected to the USB interface (see details on page 17).

For connector pin-outs see details on page 101. See Troubleshooting on page 88 for details of SC200 alarm LEDs.

Input/Output Board

The input/output (I/O) board provides the I/O interfaces and connections for the SC200 system controller.

The I/O board includes a range of sense inputs for dc power system control and monitoring. It also allows real time data collection from building services and other external devices, and relay outputs for alarm signals or control of external devices.

Page 11: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

General Description

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 3

The I/O functions are:

Sensors: Current - 3, Bus voltage - 1, Temperature - 2, Battery Mid-point - 4

Input/Output: Digital inputs: 4 pre-defined system functions, 6 user-defined Relay outputs: 6 (one also used as Monitor OK alarm) LVD contactor outputs: 2

For input and output specifications see details on page 93. For connector pin-outs see details on page 103.

Bus voltage sense input - XH9

Power/Comms OK LED (green)

Digital inputs D1-D6 (6 user defined) - XH15A, XH15B

Digital (relay) outputs RY1-RY6 (6) - XH16-XH21

LVD contactor 2 status LED (green)

LVD contactor 2 connector - XH5

LVD contactor 1 status LED (green)

LVD contactor 1 connector - XH4

LVD power input connector - XH8

Power and RXP comms input - YH11

Current sense inputs (3) - XH6

Temperature sense inputs (2) - XH7

Battery Mid-point Monitoring sense inputs - XH12

DC power system digital inputs (4 pre-defined: Load Fuse Fail, Battery Fuse Fail, AC Distribution Fan Fail, AC Distribution MOV Fail) - YH3

See Troubleshooting on page 88 for details of I/O board LED signals.

Connections

The following diagram shows the connections between the SC200, the I/O board, the other dc power system components and external devices.

Page 12: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

4 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

SC200 system controller

I/O board

Voltage feed module

USB communications

Ethernet communications

RS232 communications

Digital relay outputs (6) to external devices and/or alarm indication system

Digital inputs (6) from external voltage-free switches or relay contacts

Connection to additional I/O board(s) and/or SiteSure-3G I/O module(s)

Connection to dc common bus

Connection to dc live bus

Communications to rectifiers

DC power system digital inputs (Load Fuse Fail, Battery Fuse Fail, AC Distribution Fan Fail, AC Distribution MOV Fail)

Connections for battery mid-points (4)

Connection for temperature sensors (2)

Connection for current sensors (3)

Connection for LVD contactor and auxiliary switch

Connection for LVD contactor and auxiliary switch

Bus voltage sense and LVD power connections

I/O and system controller power and RXP comms connections

For connector pin-outs see details on page 103. For input and output specifications see details on page 93.

Compatible Software

The following software is compatible with the SC200 system controller:

DCTools Configuration Software. Latest version is available free from www.powerquality.eaton.com/downloads.

PowerManagerII Remote Control and Monitoring Software. Contact your Eaton dc product supplier for further information (see Worldwide Support on page 115).

Recommended web browsers: Microsoft Internet Explorer 8 (IE6 is compatible but with reduced performance), Mozilla Firefox 3.0.

Page 13: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Chapter 2

SC200 Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 5

C h a p t e r 2 SC200 Operation

Overview

Topic Page

Starting the SC200 6

SC200 Operation using the Keypad and Screen 6

SC200 Operation Using a PC/Laptop 13

SC200 Identity Information 14

SC200 Internal Clock 14

Language Options 16

SC200 Firmware Upgrade 17

Configuration File 17

Backup and Restore 18

Page 14: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

6 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Starting the SC200

When dc power is applied to the SC200 (via the RXP connector YS11) the start-up sequence begins.

Approx.

120s

Start-up screen Main screen Menu screen

The values shown are configurable, see details on page 11. All active Critical, Major,

Minor and Warning alarms are displayed.

See navigation details on page 8.

If Logon is required see Keypad Access Security on page 10.

Main Screen Shortcut Keys

Key Function

From the Main Screen go directly to the Alarms screen.

From the Main Screen go directly to the Settings screen.

From the Main Screen go directly to the Control Processes screen.

From the Main Screen go directly to the Analogs screen.

SC200 Operation using the Keypad and Screen

LCD

Soft key 1 label

Soft key 1

Navigation keys (Up - Down - Left - Right)

Soft key 2

Soft key 2 label

Page 15: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 7

Soft Keys

The function of the soft keys is indicated by the corresponding labels on the LCD screen. The following table shows the most common labels and key functions.

Label Key function

Go to menu screen. See details on page 8.

Go back to parent menu screen.

Go to sub-menu or configuration screen*.

Save a new configuration setting*.

Ignore a new configuration setting*.

* See Changing a Configuration Setting on page 10.

Navigation Keys

Key Function

Move up/down in the menu screen. See details on page 8.

Move up/down in a list (hold to go to the top or bottom of the list).

Select options in a configuration screen.

Increase/decrease a value in a configuration screen.

Move left/right in the menu screen. See details on page 8.

Move left/right between tabs in Rectifiers, Alarms, Battery or Settings menus.

Move left/right between segments of a multiple segment value in a configuration screen.

Page 16: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

8 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Main Menu Navigation

At each menu screen press Enter to access the associated configuration menu screen(s).

These menus have multiple configuration menu screens. See details on page 9.

Page 17: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 9

Sub-menu Tabs

The following menu screens have sub-menus accessed via tabs at the top of the screens.

Rectifiers Sub-menus

List of registered rectifiers.

Rectifier settings.

Alarms Sub-menus

List of active alarms. Alarm settings.

Battery Sub-menus

Battery settings. LVD settings. Mid-point monitoring

settings.

Settings Sub-menus

SC200 settings. Registered

input/output boards.

Page 18: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

10 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Changing a Configuration Setting using the Keypad

For the configuration settings that can be changed using the keypad, the keys have the following functions.

Press to change the setting or activate a control process.

Press to change the value. Hold key to change at a faster rate.

Use these keys for values with multiple segments (for example an IP address).

Press to save the new value.

Or

Press to leave the value unchanged.

Keypad Access Security

This feature prevents accidental or unauthorized changes to settings from the SC200 keypad.

All access to change an SC200's settings will be lost if:

All communications are disabled (see S3P Access on page 84 and HTTP/HTTPS Access on page 85), and

Keypad access is Read Only, or PIN Protected and the keypad access PIN is lost.

The SC200 will continue to function, but no configuration changes can be made. Contact your Eaton dc product supplier or Eaton for advice (see Worldwide Support on page 115).

► To use DCTools/Web to enable/disable keypad access

In DCTools/Web go to Communications > Front Panel.

Set Access to:

Unprotected - keypad access is allowed to view and change parameters, or

Read Only - keypad access is allowed to view parameters only, or

PIN Protected - keypad access is allowed to view and change parameters if the correct 4-digit number is typed in the Access PIN field. Otherwise, Read Only access is allowed.

► To use the SC200 when access is set to PIN Protected

At the Main Screen press Menu. The Logon screen appears.

If the Access PIN is not known then press Skip to use the SC200 with Read Only access.

If the Access PIN is known:

Use the Left and Right keys to access each digit position. Use the Up and Down keys to change the digits.

When the correct digits are entered, press Logon.

Keypad access will return to PIN Protected mode when the display returns to the Main Screen.

Page 19: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 11

Display Settings

► To change the display contrast

Use the keypad to go to: Settings > Setup > Contrast > Edit.

► To change the display language

See Language Options on page 16.

► To change the display orientation (horizontal/vertical)

Either:

Use the keypad to go to: Settings > Setup > Orientation > Edit.

Select the required orientation (vertical, horizontal-left or horizontal-right). Press Save.

Or:

In DCTools/Web go to: Configuration > Communications > Front Panel.

Select the required orientation (vertical, horizontal-left or horizontal-right). Click Save Changes.

The functions of the navigations keys also change to suit the new display orientation.

Main Screen Parameters

The parameters displayed on the SC200 main screen are configurable.

To be updated.

(default parameters are Bus Voltage and Rectifier Current).

Top value

Bottom value

► To change the parameters displayed on the main screen

Either:

Use the keypad to go to: Settings > Setup > Top Value and/or Bottom Value > Edit.

Select the required parameters (see Note 1) for Top Value and/or Bottom Value.

If Analog Input is selected then also select a value for Top Value Index and/or Bottom Value Index. See Note 2.

Or:

In DCTools/Web go to: Configuration > Communications > Front Panel.

Select the required parameter (see Note 1) for Top Value and/or Bottom Value.

If Analog Input is selected then also select a value for Top Value Index and/or Bottom Value Index. See Note 2.

Page 20: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

12 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Notes:

1 The parameters available are: Bus Voltage, Rectifier Current, Load Current, Battery Current, Battery Temperature, Load Power, System Power, or Analog Input.

2 If Analog Input is selected then also select a value for Top Value Index and/or Bottom Value Index. This value is the number of the AI from the Analog Inputs table. To view the table in DCTools/Web go to: Analog Inputs.

Display Time-out

If there is no keypad activity for 60 seconds the display will go back to the main screen.

Alarm Indicators

Visual indicators

Power on LED (green)

Minor Alarm LED (yellow)

Critical/Major Alarm LED (red)

??? The system value cannot be displayed because of a failed, disconnected or unconfigured sensor.

Audible indicator

One beep – indicates an invalid key press

Three beeps every 2 seconds – refer to the alert message on the display

One beep every 2 seconds – Minor alarm is active

Continuous sound – Critical/Major alarm is active

Critical/Major alarms always override Minor alarms.

► To stop the audible indicator

Press any key

The audible indicator will restart at the next active alarm or alert message.

► To enable/disable the audible alarm indicator

Either:

Use the keypad to go to: Alarms > Alarm Settings > Audible Alarms > Edit.

Or:

In DCTools/Web go to: Alarms > Alarm Configuration.

When Disabled, the audible indicator will still indicate an invalid key press.

Page 21: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 13

SC200 Operation Using a PC/Laptop

DCTools is configuration software for editing a system controller's configuration file (on-line) and monitoring the operation of Eaton's dc power systems. It is available free from www.powerquality.eaton.com/downloads.

DCTools can be run on a PC/laptop connected to the SC200's USB port.

DCTools can also be run on a remote PC/laptop connected to the SC200's RS232 serial port (via a modem) or Ethernet port. For remote PC/laptop connection details see Communications Options on page 72.

Before you start you will need:

The latest version of DCTools available from www.powerquality.eaton.com/downloads.

A PC/laptop with USB port and USB A/B cable (RadioShack 55010997, Jaycar WC7700, or equivalent).

► To connect a PC/laptop to the SC200:

1 Download the latest version of DCTools from www.powerquality.eaton.com/downloads.

2 Install DCTools on the PC/laptop.

3 Connect a USB A/B cable from a USB port on the PC/laptop to the USB port on the SC200.

See the diagram on page 2 for location of the USB port.

4 DCTools will now connect to the SC200.

If connection is not successful refer to DCTools Help (press F1) or Troubleshooting on page 88.

5 For details of the SC200 control and monitoring functions available via DCTools see System Operation on page 19.

For help using DCTools press F1.

Page 22: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

14 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

SC200 Identity Information

The following identity information is stored in the SC200.

Parameter Description Where to find:

Serial Number The SC200 serial number (factory set). SC200: Info

DCTools/Web: Configuration > Identity

Software Version (App Version)

The version of the embedded software in the SC200 (factory set).

If required, the following site specific information can be stored in the SC200 to assist site management.

Parameter Description Where to find:

System Manufacturer

The manufacturer of the dc power system.

DCTools/Web: Configuration > Identity

System Type The dc power system model number.

System Serial Number

The dc power system serial number.

System Location Location of dc power system at the site.

Site Name Name of the site.

Site Address Address of the site.

Site Notes Any notes relevant to site access, location or other matters.

Contact Contact name, phone number, and so on.

Configuration Name

Reference name of the configuration file in the SC200.

SC200 Internal Clock

The SC200 has a battery-backed clock for time stamping of log entries and Control Processes.

The time and date is factory set. It can also be set manually using a web browser or can be synchronized (either to a PC clock using DCTools or to an SNTP reference time server).

Page 23: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 15

► To view the SC200 time

Either:

Use the keypad to go to: Info.

This time is set to Universal Coordinated Time (UTC). DCTools, Web and PowerManagerII convert local PC time to/from UTC for the SC200. For practical purposes UTC is equivalent to Greenwich Mean Time (GMT).

Or:

In DCTools go to: Configuration > Identity.

This time is set to the SC200 time adjusted to the time zone set in the PC.

Or:

In Web go to: Configuration > Time.

This time is set to the SC200 time adjusted to the time zone set in the PC.

► To set the time

1 Connect to the SC200 via a web browser. (See Ethernet Communications on page 72.)

2 Go to Configuration > Time.

3 Click on the time-date field to select the text.

4 Select the time or date text to be changed and type the correct time/date.

5 Press Enter on the keyboard. Then select Apply in the Changes window.

Time Synchronization

If required, the SC200 time can be synchronized either to the internal time of a PC or laptop, or to a reference time server using SNTP protocol (SC200 must have access to the server).

► To synchronize the SC200 time using DCTools or PowerManagerII

1 Ensure the time on the PC is correct before synchronizing.

PowerManagerII can be set to automatically synchronize SC200 clocks.

2 Connect to the SC200 with DCTools/PowerManagerII. (See Communications Options on page 72.)

3 Go to Configuration >Identity > Time Synchronization

4 Click Synchronize to synchronize the SC200 time to the PC/laptop time.

DCTools, Web and PowerManagerII convert local PC time to/from UTC for the SC200.

► To synchronize the SC200 time using SNTP

For more information on SNTP, including a list of public SNTP servers, visit www.ntp.org http://www.ntp.org.

Ensure that your network has an internal SNTP server or allows access to an external server. It may be necessary to configure access through your network's firewall.

1 Connect to the SC200 via DCTools/Web.

2 Either: In DCTools go to Configuration > Configuration > SNTP, or In Web go to Configuration > Time > SNTP.

Page 24: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

16 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

3 Set the following parameters:

Primary Address IP address of primary SNTP server.

Backup Address IP address of backup SNTP server.

UDP Port Assigned by the time server administrator.

Poll Interval The time between synchronizations.

The time will update a few seconds after any SNTP parameter change.

Language Options

The SC200 system controller language default is English. Text on the LCD and web pages (see details on page 74) can be shown in other languages by loading the appropriate Translation File (SC200-xx-Vyyy.icp) into the SC200.

Contact Eaton for available Translation Files (see Worldwide Support on page 115).

This process does not change the language in DCTools.

► To add a new SC200 display/web page language:

1 Obtain the appropriate Translation File (SC200-xx-Vyyy.icp) from Eaton.

2 Save the file.

3 Connect to the SC200 via an Ethernet connection. See Communications Options on page 72.

4 Open a web browser and browse to the SC200 IP address.

5 Go to Tools > Firmware Upgrade.

6 Click on Browse and select the Translation File (SC200-xx-Vyyy.icp).

7 Click on Next then follow the prompts to add the language.

Language selection

An SC200 can hold multiple language files and any of these can be selected for the LCD and Web pages.

► To see which languages are loaded into an SC200

Either:

On the SC200 keypad go to: Settings > Language > Edit.

Or:

Connect to the SC200 via an Ethernet connection. See Communications Options on page 72.

On the Log On web page, there is a flag icon for each language option available.

► To select a new language for the Web pages

On the Log On web page, click on the flag icon for the language you require.

The web pages will change to this language.

Page 25: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 17

► To select a new language for the SC200 display

Either:

On the SC200 keypad go to: Settings > Language > Edit.

Select the required language and press Save.

Or:

In DCTools/Web go to Communications > Front Panel.

Type the two letter language code in the Language Code field.

This code is the "xx" in the file name of the Translation File (SC200-xx-Vyyy.icp). For example: zh = Chinese. Clear the Language Code field (blank entry) to revert to English.

Click Apply Changes. The display language will change.

The message "Waiting for database to become available for update ..." may display for a few seconds. If an incorrect or unavailable language code is used the display language will remain/revert to English.

SC200 Firmware Upgrade

If required, the embedded software (firmware) in the SC200 can be upgraded from a PC/laptop via a web browser.

► To use a web browser for a Firmware Upgrade

1 Connect to the SC200 via a web browser. (For details see Ethernet Communications on page 72.)

2 Check the SC200 internal clock shows the correct time. If necessary set the correct time. See SC200 Internal Clock on page 14.

3 Go to Tools.

4 Select Firmware Upgrade: Launch.

5 Select the file (*.icp). Click Next, then click Proceed.

Configuration File

The operational settings of the dc power system are stored in a configuration file loaded into the SC200 system controller.

The SC200 is supplied pre-loaded with a configuration file. If this configuration file has been customized for the site then no further configuration changes will be necessary.

Otherwise, it is important that the settings of this configuration file are checked and changed as required for site-specific conditions. In particular, settings that may affect the performance and life expectancy of the battery must be checked and set according to the battery manufacturer’s recommendations.

Some settings in the configuration file can be edited using the system controller's keypad (see details on page 6), or all settings can be edited using a PC/laptop with DCTools/Web (see details on page 13) or remotely, see Communications Options on page 72.

The configuration file settings in the SC200 can be saved to (Backup) or loaded from (Restore) a PC/laptop using DCTools/Web. See Backup and Restore on page 18.

Page 26: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

18 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Backup and Restore

The configuration file settings in the SC200 can be saved to (Backup) or loaded from (Restore) a PC/laptop using DCTools/Web.

Backup and Restore can be used to:

Load a standard (master) configuration file into an SC200 for customization.

Copy a customized configuration file from one SC200 to others (at similar sites).

Save a copy of a customized configuration file. This is recommended in case the SC200 has to be replaced.

► To use DCTools for Backup and Restore

1 Connect to the SC200 with DCTools. See Communications Options on page 72.

2 In DCTools go to File > ICE Backup/Restore and follow the prompts.

The saved file does not include site specific settings including Site Identity, IP Address, S3P Address, battery characterization data.

► To use a web browser for Backup

1 Connect to the SC200 via a web browser. For details see Ethernet Communications on page 72.

2 Go to Tools.

3 Select Backup Tool.

4 Select the file type:

System Snapshot (*.dcs): Configuration file including site specific settings.

Configuration (*.dcc): Configuration file without site specific settings - Site Identity, IP Address, S3P Address, battery characterization data).

5 Click Proceed to Backup the configuration.

► To use a web browser for Restore

1 Connect to the SC200 via a web browser. For details see Ethernet Communications on page 72.

2 Go to Tools.

3 Select Restore Tool.

4 Select the file type:

System Snapshot (*.dcs): Configuration file including site specific settings.

Configuration (*.dcc): Configuration file without site specific settings - Site Identity, IP Address, S3P Address, battery characterization data).

Fragment (*.dcf): Restore part of a configuration file (such as battery characterization data).

5 Click Next, and then select a file name to Restore a configuration.

Page 27: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Chapter 3

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 19

C h a p t e r 3 System Operation

Overview

Topic Page

Voltage Control 20

Rectifiers 28

Low Voltage Disconnect (LVD) 32

Alarms 39

Batteries 49

Generator Control Option 60

Input/Output (I/O) 62

Data Logging 68

Page 28: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

20 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Voltage Control

The output voltage of the rectifiers is controlled by a number of control processes. The following diagram shows the various control processes, measured values and operating values that determine the rectifier output voltage.

If ac fails then any active control process stops. No control process can start until the ac supply is restored.

Float Voltage

Configuration

Set the following parameter.

Parameter Description Where to find:

Float Voltage Set to the voltage required to maintain optimum battery charge (at the nominal ambient temperature*) as specified by the battery manufacturer. The bus voltage may be adjusted above or below this value by the System Control Processes.

*This is the same as the Reference Temperature used by Temperature Compensation. See details on page 27.

SC200: Control Processes > Voltage Control > Float Voltage

DCTools/Web: Control Processes > Voltage Control

The system voltage is limited by maximum and minimum values. The values are viewable in DCTools/Web at Control Processes > Voltage Control. These values are not configurable.

Page 29: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 21

Active Voltage Control (AVC)

Active Voltage Control maintains a constant float voltage under varying load current by monitoring the bus voltage and adjusting the rectifier output voltage to compensate for any voltage drop. This prevents undercharging the batteries during high load demand.

► To enable Active Voltage Control

Use the SC200 keypad to go to: Control Processes > Voltage Control > AVC.

Or, in DCTools/Web go to: Control Processes > Voltage Control > Active Voltage Control.

Active Voltage Control is normally enabled. Only disable if there are particular reasons.

Information

The following information is available about AVC.

Parameter Description Where to find:

State Indicates if AVC is active or inactive.

DCTools/Web: Control Processes > Active Voltage Control

Target Voltage AVC will set the Base Voltage to attempt to maintain the bus voltage to this value.

Voltage Offset The difference between the Base Voltage and the Target Voltage.

Battery Current Limit (BCL)

Battery Current Limit automatically limits the battery recharge current to:

Prevent excessive battery charge current in under-loaded systems

Minimize gas release in VRLA batteries

Reduce the load on a standby generator.

Two current limit values can be set (both are a percentage of the C10 rating of the battery):

Battery Current Limit (Normal Limit):

BCL value for use when utility ac is available.

Engine Run Limit (optional): BCL value for use when ac is supplied by a standby generator. This reduces the load on the generator and allows a smaller generator to be used.

Engine Run Limit is activated by a signal from an ac standby generator.

► To enable BCL

Use the SC200 keypad to go to: Control Processes > Battery Current Limit.

Or, in DCTools/Web go to: Control Processes > Battery Current Limit.

► To activate Engine Run BCL

Connect a voltage free relay contact (that will operate when the standby generator starts) to a Digital Input.

In DCTools/Web go to Digital Inputs.

Configure the selected Digital Input and set Function to Engine Run.

In DCTools/Web go to Control Processes > Battery Current Limit and set the Engine Run Limit.

Page 30: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

22 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Information

The following information is available about BCL.

Parameter Description Where to find:

State Indicates if BCL is active or inactive. SC200: Control Processes > Battery Current Limit.

DCTools/Web: Control Processes > Battery Current Limit

Engine Run State Indicates if Engine Run BCL is active. DCTools/Web: Control Processes > Battery Current Limit

Voltage Offset The bus voltage adjustment made by Battery Current Limit is applied to the Operating Voltage to produce the Target Voltage. Target Voltage is used as the input to the AVC function.

Configuration

Set the following parameters.

Parameter Description Where to find:

Battery Capacity Set to the rated 10 hour capacity of the installed battery strings. Zero means no battery is installed.

SC200: Battery > Battery > Battery Capacity

DCTools/Web: Batteries

Current Limit BCL maintains the battery current below this value, which is a percentage of the installed C10 Battery Capacity.

DCTools/Web: Control Processes > Battery Current Limit

Engine Run Limit The Battery Current Limit setting when Engine Run is active. BCL maintains the battery current below this value when the engine run digital input is active (engine run is enabled). This limit is expressed as a percentage of the installed C10 Battery Capacity.

Battery Test

Battery Test is a preventative maintenance tool that monitors the discharge capabilities to ensure that the condition of the battery has not deteriorated over time.

The SC200 temporarily reduces the output voltage of the rectifiers to just below the bus voltage for a set duration. The battery then supplies power to the load. A battery test passes if the battery voltage remains above a predetermined level for the duration of the test.

Battery Tests can be scheduled to occur at regular intervals, and/or can be started/stopped manually, and/or can be started by an external relay contact or switch.

Battery Test does NOT function during a Fast Charge or Equalize, or during the lock-out period after an ac supply failure.

If a Digital Input has the function "Start Battery Test" then a Battery Test will start when the Digital Input becomes active.

► To enable Battery Test (or to start or stop a test manually)

Use the SC200 keypad to go to: Control Processes > Battery Test.

Or, in DCTools/Web go to: Control Processes > Battery Test

Page 31: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 23

► To use an external relay contact to activate a Battery Test (optional)

Connect a voltage free relay contact or switch to any Digital Input.

In DCTools/Web go to Digital Inputs.

Configure the selected Digital Input and set Function to Start Battery Test.

Information

The following information is available about Battery Test.

Parameter Description Where to find:

State Indicates if Battery Test is disabled, locked-out, active or inactive.

SC200: Control Processes > Battery Test

DCTools/Web: Control Processes > Battery Test

Next Start Time The start time of the next scheduled Battery Test.

Time shown on SC200 is UTC. Time on PC running DCTools/Web is local time. See SC200 Internal Clock on page 14.

Remaining Time The time to the end of the currently active Battery Test.

Battery Test Lockout Remaining

The time remaining until a Battery Test can be started. Battery Tests cannot be started within 48 hours of an ac supply failure.

Voltage Offset The adjustment to the bus voltage being applied due to the Battery Test. While a Battery Test is running, the rectifiers are turned down to force the battery to carry the load.

Configuration

Set the following parameters.

Parameter Description Where to find:

First Start Time The date and time that the first battery test cycle will occur. Subsequent tests will occur at every Battery Test Interval after that.

SC200: Control Processes > Battery Test

DCTools/Web: Control Processes > Battery Test

Interval The time between scheduled battery tests. The interval period begins at the start of a battery test. Zero disables scheduled battery tests. Zero also disables the 48 hour lockout following an ac supply failure, allowing an immediate manual test.

Test Duration The maximum time a Battery Test process will be active. The battery test will pass if the bus voltage remains above the Battery Test Termination Voltage for the duration of the test.

Termination Voltage

If the bus voltages drops below this value during a Battery Test, then the test fails.

Page 32: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

24 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Equalize

Equalize charges batteries at a higher voltage after they have been fully charged to ensure that all individual cell voltages are the same, that electrolyte is distributed evenly, and that sulfate crystal buildup on the plates is reduced.

Equalize can be scheduled to occur at regular intervals and/or can be started/stopped manually.

Refer to the battery manufacturer's instructions before using Equalize.

If a Digital Input has the function "Start Equalize" then a manual equalize cycle will start when the Digital Input becomes active.

If Equalize cannot start at the scheduled time (for example when there is no ac supply) then its state will be Pending and it will start as soon as conditions allow. Use Stop Equalize to cancel a Pending Equalize.

► To enable Equalize (or to start or stop Equalize manually)

Use the SC200 keypad to go to: Control Processes > Equalize.

Or, in DCTools/Web go to: Control Processes > Equalize.

► To use an external relay contact to activate an Equalize (optional)

Connect a voltage free relay contact or switch to any Digital Input.

In DCTools/Web go to: Digital Inputs.

Configure the selected Digital Input and set Function to Start Equalize.

Information

The following information is available about Equalize.

Parameter Description Where to find:

State Indicates if Equalize is Disabled, Active, Inactive or Pending.

SC200: Control Processes > Equalize

DCTools/Web: Control Processes > Equalize

Next Start Time The start time of the next scheduled Equalize.

Time shown on SC200 is UTC. Time on PC running DCTools/Web is local time. See SC200 Internal Clock on page 14.

Remaining Time The time to the end of the currently active Equalize.

Voltage Offset The adjustment to the bus voltage being applied due to the Equalize.

Page 33: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 25

Configuration

Set the following parameters.

Parameter Description Where to find:

First Start Time The date and time that the first scheduled Equalize will occur. Subsequent Equalize will occur at every Equalize Interval after that.

SC200: Control Processes > Equalize

DCTools/Web: Control Processes > Equalize

Interval The time between scheduled Equalize. The interval period begins at the start of an Equalize. Zero disables scheduled Equalizes.

Duration The duration of a scheduled Equalize. Use the value recommended by the battery manufacturer.

Equalize Voltage The bus voltage maintained during an Equalize cycle. Use the value recommended by the battery manufacturer. The bus voltage is further adjusted by Temperature Compensation.

Equalize may also be used to trigger the Generator Enable alarm. See details on page 60.

Fast Charge

After an ac supply failure, Fast Charge automatically increases the float voltage of the power system to recharge the batteries as quickly as possible.

Enable Fast Charge if the site experiences frequent ac supply failures.

Fast Charge does NOT function during a Battery Test, Equalize or if the battery current sensor fails.

If Fast Charge is used then Battery Current Limit (BCL) should also be used. See Battery Current Limit on page 21 for details.

If Fast Charge cannot start at the scheduled time (for example when there is no ac supply) then its state will be Pending and it will start as soon as conditions allow. Use Stop Fast Charge to cancel a Pending Fast Charge.

► To enable Fast Charge (or to stop Fast Charge manually)

Use the SC200 keypad to go to: Control Processes > Fast Charge.

Or, in DCTools/Web go to: Control Processes > Fast Charge.

Page 34: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

26 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Information

The following information is available about Fast Charge.

Parameter Description Where to find:

State Indicates if Fast Charge is Disabled, Active, Inactive or Pending.

SC200: Control Processes > Fast Charge

DCTools/Web: Control Processes > Fast Charge

Ah Discharged The current level of battery discharge. A Fast Charge cycle is started if this value is above the Ah Threshold.

See also Reset Battery State.

Maximum Time Remaining

The maximum time to the end of the currently active Fast Charge.

Voltage Offset The adjustment to the bus voltage being applied due to the Fast Charge.

Configuration

Set the following parameters.

Parameter Description Where to find:

Voltage Threshold If the bus voltage drops below this value during an ac supply failure, then Fast Charge starts when the ac supply is restored. Fast charge can also be started based on the Ah Threshold.

SC200: Control Processes > Fast Charge

DCTools/Web: Control Processes > Fast Charge

Ah Threshold If Ah Discharged exceeds this value during an ac supply failure, then Fast Charge starts when the ac supply is restored. The threshold is given as a percentage of installed C10 battery capacity. Fast charge can also be started based on the Voltage Threshold.

Maximum Duration

The maximum duration of a Fast Charge as recommended by the battery manufacturer.

Recharge Percentage (%)

The ratio of ampere-hours recharged to the ampere-hours discharged. Fast Charge stops either when the Ah recharged equals the Ah discharged x Fast Charge Recharge Percentage, or after Maximum Duration.

Fast Charge Voltage

The bus voltage maintained during a Fast Charge.

Battery Capacity The rated 10 hour capacity of the installed battery strings. Zero means no battery is installed.

Fast Charge may also be used to trigger the Generator Enable alarm. See details on page 60.

Page 35: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 27

Temperature Compensation

As the ambient temperature of a battery drops (or rises) the voltage required to maintain full charge increases (or decreases). Temperature Compensation automatically varies the float voltage to cancel the effects of changing temperature.

Enable Temperature Compensation for optimum battery life and battery capacity over a wider temperature range.

Temperature Compensation does NOT function during a Battery Test.

► To enable Temperature Compensation

Use the SC200 keypad to go to: Control Processes > Temp. Compensation > Enable.

Or, in DCTools/Web go to: Control Processes > Temperature Compensation.

Information

The following information is available about Temperature Compensation.

Parameter Description Where to find:

State Indicates if Temperature Compensation is active or inactive.

SC200: Control Processes > Temp. Compensation > Enable

DCTools/Web: Control Processes > Temperature Compensation

Voltage Offset The adjustment to the bus voltage being applied due to the Temperature Compensation. Offset is zero when the battery temperature equals the reference temperature.

Battery Temperature

The temperature measured by the battery temperature sensor.

SC200: Analogs > Battery Temperature

DCTools/Web: Batteries

Configuration

Set the following parameters.

Parameter Description Where to find:

Cells Per String The number of 2V cells per battery string (for example: 24 in a 48V nominal system).

SC200: Battery > Battery

DCTools/Web: Batteries

Slope Bus voltage adjustment rate. Use the value recommended by the battery manufacturer.

SC200: Control Processes > Temp. Compensation > Enable

DCTools/Web: Control Processes > Temperature Compensation

Reference Temp The temperature where no voltage adjustment is applied. Refer also to Float Voltage on page 20.

Upper Limit No additional voltage adjustment is made above this temperature.

Lower Limit No additional voltage adjustment is made below this temperature.

Page 36: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

28 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Rectifiers

The SC200 registers all rectifier modules as they are inserted into the dc power system.

Information

The following information is available from rectifiers.

Parameter Description Where to find:

State Registered - communicating with the SC200. Un-registered - there is a rectifier compatibility or communications problem.

SC200: Rectifiers > Enter (Use Left and Right keys to scroll to other rectifiers)

DCTools/Web: Rectifiers

Serial Number (S/N)

Rectifier serial number.

AC Voltage The ac voltage measured by the rectifier (single-phase rectifiers only).

Phase Voltages The ac phase voltages measured by the rectifier (three-phase rectifiers only).

Voltage Rectifier's dc output voltage.

Current Rectifier's output current.

Heatsink Temp The measured rectifier heatsink temperature.

Max Power (Limit) Rectifier's maximum output power (factory set).

Power Rectifier output power as a percentage of Max. Power Limit.

DCTools/Web: Rectifiers Max Current Limit The maximum current limit value of the rectifier.

Adjust Rectifier Current Limit to set a lower operating current limit.

Status Information about rectifier alarms.

Type Rectifier manufacturer's model number. SC200: Rectifiers > Enter (Use Left and Right keys to scroll to other rectifiers) Software Version Version of rectifier embedded software.

Page 37: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 29

Common Rectifier Configuration

The following parameters (common to all rectifiers) can be configured.

Parameter Description Where to find:

Rectifier (DC) Current Limit

The output current limit of the rectifier. If set to zero, then the output current limit is maximum.

SC200: Rectifiers > Rect. Settings

DCTools/Web: Rectifiers

AC Rectifier Current Limit

The input current limit of the rectifier. If set to zero, then the input current limit is maximum.

Rectifier Current Share

Current Share ensures that the total output power of the power system is evenly shared between all rectifiers.

Set to Enabled unless there is a specific reason to disable.

OVSD Set Point Over Voltage Shut Down. A rectifier will shut down if its output voltage exceeds this value.

Recommended value is 59.2V for 48V nominal systems, 28.6V for 24V nominal systems.

DCTools/Web: Rectifiers

Ramp Up Slope The ramp-up slope of the rectifier, as a percentage of the rectifier rated current.

Enable Rectifier Shutdown

Set to Enabled to allow rectifier shut down.

Load Based Rectifier Shutdown is not available with APR48-3G, EPR48-3G, APR24-3G and CR48-3G rectifiers.

Start Up Delay The delay from ac turn-on before the rectifier output turns on.

See Voltage Control on page 20 for details of the rectifier's output voltage control.

Identify a Rectifier

The rectifier's registration number does not correspond to a physical position in the dc power system.

► To identify a rectifier

Either:

On SC200 keypad go to: Rectifiers > Rectifier number. Press Enter.

The rectifier details screen appears. Use to scroll to other rectifiers.

All LEDs on the selected rectifier will flash for 60 seconds, or press Esc to stop.

Or:

In DCTools/Web go to: Configuration > RXP > RXP Devices.

DCTools: select Identify Device or Web: click on Start Identifying.

All LEDs on the selected rectifier will flash for 60 seconds.

Rectifier serial numbers are printed on a label on the front of each rectifier.

Page 38: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

30 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Rectifier Comms Lost Alarm

When a rectifier is removed (or a fault interrupts rectifier communications), the SC200 will display an alert message and sound an alert alarm (if Audible Alarms are enabled). After the Alarm Recognition Period, a Rectifier Comms Lost alarm will activate.

A Multiple Rectifier Comms Lost alarm will activate (after the Alarm Recognition Period) if more than one rectifier is affected.

► To prevent a Rectifier Comms Lost alarm when a rectifier is removed

Press any key within the Alarm Recognition Period, to cancel the alert.

Rectifier Shutdown

Manual Rectifier Shutdown

► To shut down a rectifier

In DCTools/Web go to: Rectifiers > Configuration.

Set Rectifier Shutdown to Enabled.

In the Rectifiers table select the Shutdown check box (DCTools) or click Shutdown (Web).

The rectifier will shut down and the yellow LED will be on.

The SC200 will restart any shutdown rectifiers if: ac has failed, or more than one rectifier has failed, or the bus voltage is below the Low Load threshold, or Rectifier Shutdown is disabled.

Shutdown rectifiers will restart if Load Based Rectifier Shutdown is enabled.

Rectifier Restart

► To restart all shutdown rectifiers

Use the SC200 keypad to go to: Rectifiers > Rect. Settings (tab) > Restart All Rectifiers.

Or

In DCTools/Web go to: Rectifiers. Click Restart All Rectifiers.

► To restart individual rectifiers

In DCTools/Web go to: Rectifiers.

For each rectifier clear the Shutdown check box (DCTools) or click Startup (Web).

The rectifier(s) will then resume normal operation.

The SC200 will restart any shutdown rectifiers if: ac has failed, or more than one rectifier has failed, or the bus voltage is below the Low Load threshold, or Rectifier Shutdown is disabled.

Page 39: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 31

Load Based Rectifier Shutdown

Load Based Rectifier Shutdown is not available with APR48-3G, EPR48-3G, APR24-3G and CR48-3G rectifiers.

If Load Based Rectifier Shutdown (LBRS) is enabled then the SC200 automatically shuts down rectifiers when the total load current is significantly less than the total rectifier capacity.

This raises the average load on the remaining rectifiers which will then operate at a higher efficiency. This results in a decrease in system power consumption.

The run time of all rectifiers is recorded and balanced to ensure even aging.

The SC200 will progressively restart rectifiers if the load increases.

Rectifiers shut down by LBRS will have the yellow LED on.

At least two rectifiers will always be on to maintain N+1 rectifier redundancy. Therefore, LBRS has no effect in dc power systems with only one or two rectifiers.

The SC200 will automatically restart all rectifiers if ac supply has failed, or more than one rectifier has failed, or the bus voltage is below the Low Load threshold, or Battery Test / Equalize / Fast Charge are active.

► To enable Load Based Rectifier Shutdown

Use the SC200 keypad to go to: Control Processes > Load Based Rectifier Shutdown.

Or, in DCTools/Web go to: Rectifiers > Load Based Rectifier Shutdown

Ensure that Rectifier Start Up Delay is less than 30 seconds. See information on page 29. LBRS will not function correctly if the start up delay is more than 30 seconds.

LBRS Info SC200

Information

The following information is available about Load Based Rectifier Shutdown.

Parameter Description Where to find:

State Indicates if LBRS is Enabled or Disabled. SC200: Control Processes > LBRS

DCTools/Web: Rectifiers > Load Based Rectifier Shutdown

Run Time The run time of each rectifier DCTools/Web: Rectifiers

Page 40: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

32 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Configuration

The following parameters must be configured to set Load Based Rectifier Shutdown.

Parameter Description Where to find:

Reset Run Time Sets the run time of all rectifiers to zero.

SC200: Control Processes > LBRS

DCTools/Web: Rectifiers > Load Based Rectifier Shutdown

High Threshold LBRS restarts all rectifiers if the load is more than this percentage of the total rectifier capacity. Typical: 80%.

Low Threshold LBRS shuts down rectifiers if the load is less than this percentage of the total rectifier capacity. Typical: 60%.

Interval The time interval in minutes that the SC200 will cycle rectifiers when the LBRS process is active.

Restart All Rectifiers

Press to temporarily restart all rectifiers shut down by LBRS.

Disable LBRS to permanently restart all rectifiers.

Low Voltage Disconnect (LVD)

Low Voltage Disconnects may be connected either as load disconnect or battery disconnect depending on the dc power system model. They have two purposes:

to protect a VRLA battery from deep discharge and premature failure, and/or

to reduce the load on a battery under discharge so that high priority equipment operates for a longer time after an ac supply failure.

The SC200 has 16 independent LVD control channels (LVD 1 to LVD 16). Each channel can control one or more of up to 16 contactors, with coil voltages from 12V to 48V nominal.

There are two contactor connectors on an IOBGP input/output board. Additional contactors are controlled by additional IOBGP-01 input/output boards. If required, refer to the dc power system Installation and Operation Guide for details on how to connect additional IOBGP-01 input/output boards to the SC200.

LVD Disconnect Modes

The LVD control channels can have any combination of the following modes of operation:

1 Voltage Based Disconnect: The LVD control channel will disconnect its contactor(s) based on the bus voltage.

2 AC Timer Based Disconnect: The LVD control channel will disconnect its contactor(s) after a specified period of ac supply failure.

3 Smart Alarm Disconnect: The LVD control channel will disconnect its contactor(s) according to the state of a specified Smart Alarm. See Smart Alarm Disconnect on page 38.

CAUTION: An unnecessary LVD disconnection may occur if the Smart Alarm uses a sensor or other input device which becomes faulty or disconnected.

Page 41: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 33

If Chained to Previous is enabled, the LVD control channel will only disconnect its contactor(s) if one of its disconnect conditions is True, and the preceding control channel has been disconnected for the Recognition Time.

Chained to Previous does not apply to LVD 1.

LVD Default and Custom Configuration

If factory-fitted in the dc power system, the LVD contactors will be characterized and the LVD control channels will have default configuration settings for Voltage Based Disconnect. Custom configuration will only be necessary if:

contactors are connected to the dc power system on site (see LVD Characterization on page 34 and LVD Setup on page 35)

different disconnect conditions are required (see LVD Configuration on page 37).

Typical LVD Arrangements

The simplest use of an LVD is a single battery disconnect contactor.

The following diagram shows a typical arrangement of two LVDs. This arrangement allows lower priority loads to be disconnected first (contactor controlled by control channel LVD 1), either at a specified battery voltage or a specified time interval after an ac supply failure. This then prolongs battery power for the highest priority loads (contactor controlled by control channel LVD 2). The battery will be disconnected when the battery voltage reaches its minimum preset voltage.

Contactor controlled by LVD 1 - low priority load disconnect (disconnects first).

Contactor controlled by LVD 2 - battery disconnect (only disconnects after LVD 1)

Connections to high priority loads (for example transmission equipment).

Connections to low priority loads.

Connection to the SC200 system controller via the I/O board.

More complex arrangements with up to 16 contactors and a selection of disconnection criteria, are possible with the SC200 system controller. The exact arrangement(s) used in a particular Eaton dc power system will be described in the Installation and Operation Guide.

Page 42: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

34 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Characterization

If auxiliary contacts are fitted to the LVD contactor(s)*, then the LVD Characterization process determines the optimum operating voltages to suit the contactor(s) coil voltage. These values are stored in the SC200 and on the I/O board.

An LVD Characterization Error alarm will be activated if the SC200 detects that the characterization values stored in the SC200 and on the I/O board are different. This happens when:

The SC200 is replaced. To clear the alarm, on the SC200 select Use IOB Values.

The I/O Board is replaced. To clear the alarm, on the SC200 select Use SC Values.

Both the SC200 and the I/O Board are replaced. In this case, re-characterize the contactor(s).

When a contactor is re-characterized it will disconnect and re-connect several times. Refer to Maintenance in the dc power system Installation and Operation Guide for full instructions.

Factory-fitted contactors will be characterized at the factory. If an existing contactor is replaced, characterize the new contactor from the SC200.

In this case, there will be no LVD Characterization Error alarm.

LVD Operation

► To allow access to LVD functions from the SC200 keypad

In DCTools/Web go to: Control Processes > LVD.

Select the Allow Front Panel LVD Control check box.

If the check box is cleared LVD functions can only be accessed using DCTools/Web.

► To manually connect or disconnect an LVD control channel

Use the SC200 keypad to go to: Battery > LVDs > LVD 1 - LVD 16 > Details > Manual Control.

Select Connect or Disconnect to connect or disconnect the channel (and all mapped contactors).

The contactor(s) will remain in the selected state until another state or Auto is selected.

Select Auto to return the LVD control channel to automatic operation.

Page 43: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 35

Information

The following information is available about LVD control channels and contactors.

Parameter Description Where to find:

LVD Control Channel State

Connected: all of the channel's disconnect conditions are false. All mapped contactors are connected (contacts closed).

Disconnected: one of the channel's disconnect conditions is true. All mapped contactors are disconnected (contacts open).

Manual: The LVD is under manual control from the SC200 keypad (see previous section).

No Contactors: there are no contactors mapped to this channel.

Idle: The LVD has not yet connected or disconnected.

SC200: Battery > LVDs

DCTools/Web: Control Processes > LVD

LVD Control Channel Inhibited

Indicates if the LVD cannot change state due to the Inhibit Period.

Contactor State Disabled: contactor cannot be operated

Connected: contactor is connected (contacts closed)

Disconnected: contactor is disconnected (contacts open)

Failed: contactor is not connected to the I/O board or is faulty.

Conflict: two contactors are mapped to the same I/O board connector.

Not Characterized: the contactor must be characterized (see details on page 34).

LVD Setup

Use the following procedures to enable or add an LVD control channel.

For SC200s upgraded from software v2.57 or earlier only: The software upgrade preserves the original LVD1 and LVD2 alarms (for backwards compatibility). However, these alarms will not operate with LVD 3 or higher. Before adding LVD 3, 4 and so on., enable and configure the generic LVD alarms (LVD Manual, LVD Fail, LVD Disconnected, LVD Characterization) and disable the specific LVD1 and LVD2 alarms.

Page 44: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

36 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

► To Enable (Add) an LVD control channel using the SC200 keypad

Control and configuration of LVDs and contactors is only available from the SC200 keypad if Allow Front Panel LVD Control is TRUE. See LVD Operation on page 34.

1 Go to: Battery > LVDs.

2 If there are no LVD control channels (LVD 1, LVD 2, ...) listed then go to Step 4.

3 For each LVD control channel select Details. Note the contactors operated by each channel.

The contactor numbers (1-1, 1-2, ...) indicate the existing IOB Number - IOB Connector Number combinations.

4 Go to: Battery > LVDs > Add LVD.

5 From the list of registered I/O boards, select a board connected to a contactor to be operated by this LVD control channel. Select Next.

6 For IOBGP I/O boards (see Input/Output Board on page 2) select:

1, if the contactor is connected to XH4

2, if the contactor is connected to XH5.

Warning: Do not select an existing IOB Number - IOB Connector Number combination (see Step 3). This will cause a conflict.

7 Select Next.

8 Select contactor type:

Normally Open if contacts are open when coil voltage is zero.

Normally Closed if contacts are closed when coil voltage is zero.

9 Characterize the contactor (see LVD Characterization on page 34).

10 To add additional contactors to the LVD control channel, go to Battery > LVDs > LVD x > Add Contactor. Repeat Steps 5-9.

► To Enable an LVD control channel using DCTools/Web

1 In DCTools/Web go to: Control Processes > LVD. Expand the Logical LVDs table:

2 Select a spare LVD control channel and configure as required. See LVD Configuration on page 37.

3 Expand the Physical Contactors table.

4 Select and configure the contactor(s) to be operated by the LVD control channel. See Contactor Configuration on page 38.

General Configuration Settings

Parameter Description Where to find:

Inhibit Period The minimum time an LVD stays connected or disconnected before it can change state. Does not apply to manual operation.

SC200: Battery > LVDs

DCTools/Web: Control Processes > LVD

Allow Front Panel LVD Control

Disables LVD control from the system controller front panel.

DCTools/Web: Control Processes > LVD

Page 45: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 37

Control Channel Configuration

Parameter Description Where to find:

Voltage Based Disconnect

If Enabled, the LVD will disconnect if the bus voltage has been below the Disconnect Voltage for the Recognition Time and reconnect if the bus voltage has been above the Reconnect Voltage for the Recognition Time.

SC200: Battery > LVDs > LVD x > Settings

DCTools/Web: Control Processes > LVD > Logical LVDs

Disconnect Voltage See Voltage Based Disconnect.

Reconnect Voltage* See Voltage Based Disconnect.

Recognition Time See Voltage Based Disconnect and Chained To Previous.

AC Timer Based Disconnect

If Enabled, then during an ac supply failure the LVD will disconnect after the AC Timer Delay, even if the Disconnect Voltage has not been reached.

AC Timer Delay See AC Timer Based Disconnect.

Smart Alarm Based Disconnect

If Enabled, the LVD will disconnect when the Smart Alarm specified by Smart Alarm Index becomes active.

See Smart Alarm Disconnect on page 38.

Smart Alarm Index See Smart Alarm Based Disconnect.

Chained To Previous (Chaining)

If Enabled, the LVD channel will only disconnect if one of its disconnect conditions is true and the preceding LVD channel has been disconnected for the Recognition Time. This applies in reverse when reconnecting.

Does not apply to LVD 1.

* If the LVD channel operates contactors used as a load-disconnect, ensure the Reconnect Voltage is set higher than the expected open-circuit recovery voltage of the discharged batteries.

Page 46: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

38 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Contactor Configuration

Parameter Description Where to find:

LVD Num Set to the number of the LVD control channel that will operate this contactor.

In DCTools/Web, number is from first column of the Logical LVDs table. SC200: See LVD Setup on

page 35.

DCTools/Web: Control Processes > LVD > Physical Contactors

Enable Set to Enabled for this contactor to be operated (connected and disconnected).

If a connected contactor (contacts closed) is Disabled, it will remain connected unless the coil is disconnected from the I/O board or the I/O board loses power.

IOB Number (On IOB)

Set to the number of the I/O board from the I/O Board to Serial Number Mapping table.

See I/O Board Mapping on page 109.

SC200: Battery > LVDs > LVD x > Contactors (x-1, x-2, ...) > Edit

DCTools/Web: Control Processes > LVD > Physical Contactors

IOB LVD Number (LVD Connector)

For IOBGP I/O boards, set to:

1, if the contactor is connected to XH4

2, if the contactor is connected to XH5.

See Input/Output Board on page 2.

Type Set according to the type of contactor:

Normally Open if contacts are open when coil voltage is zero.

Normally Closed if contacts are closed when coil voltage is zero.

Smart Alarm Disconnect

An LVD control channel can be set to disconnect if a specified Smart Alarm becomes active. For example, a battery LVD can be set to disconnect if the battery temperature is too high, or a load LVD can be set to disconnect when Ah Discharged exceeds a defined value.

An unnecessary LVD disconnect may occur if Smart Alarm Disconnect uses a sensor

which becomes faulty or disconnected.

Page 47: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 39

► To configure a Smart Alarm Disconnect

1 In DCTools/Web go to: Alarms > Smart Alarms. Configure a Smart Alarm as described on page 45.

2 Note the SA Number (first column of the Smart Alarm States table).

3 Go to: Control Processes > LVD.

4 For the required LVD control channel:

Set Smart Alarm Index to the SA Number (first column of the Smart Alarm States table).

Set Smart Alarm based Disconnect to Enabled.

The LVD control channel will disconnect its contactor(s) if the Smart Alarm becomes active.

Except, if Chained to Previous is enabled then the preceding LVD control channel must be disconnected first.

Alarms

An SC200 supplied with a standard configuration file (see details on page 17) has a standard set of alarms configured and enabled. This will be sufficient for standard dc power system operation.

For specific alarm arrangements all SC200 alarms can be individually enabled or disabled and are configurable.

Types of Alarms

The SC200 provides five types of alarms:

Alarm type Description Configuration

System alarms Generated by the operating values of dc power system (voltages, currents, temperatures, and so on) and the operation of power system modules (rectifiers, circuit breakers, fuses, and so on). The SC200 system alarms are listed in Alarm Descriptions on page 97.

See details on page 42.

Analog Input (AI) High alarms

Activated when the input value of an AI is above the alarm threshold.

See details on page 63.

Analog Input (AI) Low alarms

Activated when the input value of an AI is below the alarm threshold.

See details on page 63.

Digital Input (DI) alarms

Activated when a DI is in its active state. See details on page 66.

Smart Alarms Software simulation of logic gates to allow the logical combination of other alarms, time schedules and/or system values.

See details on page 44.

Page 48: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

40 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Active Alarm Indications

All alarms have a configured Severity:

Critical Major Minor Warning Control

The Severity determines how an active alarm is indicated:

Severity Alarm indications Details

SC200 Major alarm LED will turn on. See details on page 12.

SC200 Minor alarm LED will turn on. See details on page 12.

If the SC200 audible indicator is enabled, it will sound until a key is pressed.

See details on page 12.

The alarm name and severity icon will be displayed on the SC200 main screen.

See details on page 6.

The Event Log will record the alarm activation. See details on page 68.

If configured, an SMS text message will be sent to one or more cell phones.

See details on page 82.

If configured, PowerManagerII control and monitoring software will be notified by modem callback. PowerManagerII can initiate various actions when it receives an alarm notification.

Refer to the PowerManagerII online Help.

In DCTools/Web (if connected), the alarm name and severity icon will be displayed in the Alarms list on the System page.

See DCTools screen on page 13, Web screen on page 74.

If configured, an SNMP Trap will be sent to a network management system (NMS).

See details on page 75.

If configured, a note will be displayed on the SC200 and included in the SNMP trap (if used).

Refer to the alarm's configuration details.

If configured, one or two digital outputs (relays) will be operated.

Refer to the alarm's configuration details.

► To view a list of active alarms

Use the SC200 keypad to go to: Alarms.

Or, in DCTools/Web go to System.

Page 49: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 41

Common Alarm Parameters

The following parameters are common to multiple alarms.

Parameter Description Where to find:

Enable Audible Alarm Indication

Enable or disable the audible alarm indicator.

SC200: Alarms > Alarm Settings > Global Settings

DCTools/Web: Alarms > Alarm Configuration

Alarm Recognition Period

All alarms (except those listed below) are activated only after the alarm condition is present for this period.

These alarms have individual recognition periods: AC Fail, System Overload, Generator Fail.

These alarms do not have recognition periods: Battery Test Fail, Configuration Error, Generator Enable, Missing Hardware, Standby Mode, String Fail, Unknown Hardware, Unmapped IOB Found, and all LVD alarms.

Page 50: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

42 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

System Alarm Configuration

The following system alarm parameters can be configured.

Parameter Description Where to find:

Severity Set to the required alarm priority. This determines how the alarm is indicated. See details on page 40.

If set to Disabled then the alarm will not activate.

SC200: Alarms > Alarm Settings > System Alarm. Select an alarm.

Use to scroll to other alarms.

DCTools/Web: Alarms > Alarm States

DO Mapping A If required, select a digital output (relay) that will be operated when the alarm is active.

DO Mapping B If required, select a second digital output (relay) that will be operated when the alarm is active.

Send Trap An SNMP Trap will be sent for this alarm, if Send Trap is True and the alarm's Severity matches the setting of the SNMP Trap Level (see details on page 76).

Notes Type any required description. When the alarm is active the text will be displayed on the SC200 and included in the SNMP trap (if used).

Recognition Period The following alarms have individual recognition periods: AC Fail, System Overload, Generator Fail.

All other system alarms either use the standard Alarm Recognition Period or do not have a recognition period. See details on page 41. SC200: Alarms > Alarm

Settings > System Alarm. Select an alarm.

Use to scroll to other alarms.

DCTools/Web: Alarms > Alarm Configuration

High or Low Threshold

The following alarms have a high or low threshold: High Float, Low Float, High Load, Low Load, Battery Temperature High, Battery Temperature Low.

The alarm will be activated if the measured value is above or below this value, as applicable.

Enable High Float Tracking

If enabled, the High Float alarm threshold will be increased when the operating voltage is increased by a voltage control process.

Enable Low Float Tracking

If enabled, the Low Float alarm threshold will be decreased when the operating voltage is decreased by a voltage control process.

The following system alarms have particular configuration settings:

System Overload alarm. See details on page 42.

Battery Mid-point monitoring. See details on page 50.

System Overload Alarm

The System Overload alarm activates if the total system load exceeds a percentage of the installed rectifier capacity for a specified period. This indicates that additional rectifiers need to be installed. This is useful at sites where there is ongoing installation of additional load equipment.

Page 51: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 43

► To enable System Overload

In DCTools/Web go to: Alarms > Alarm States. Enable and configure System Overload alarm. See System Alarm Configuration on page 42.

Go to: Alarms > Alarm Configuration. Configure the System Overload alarm parameters. See details on page 43.

Information

The following information is available about System Overload.

Parameter Description Where to find:

System Power The output power of the system as a percentage of the total nominal power the system is capable of supplying.

SC200: Analogs

DCTools/Web: Analog Inputs

Configuration

Set the following parameters.

Parameter Description Where to find:

System Overload alarm parameters

See System Alarm Configuration on page 42. DCTools/Web: Alarms > Alarm States

System Overload Threshold

The System Overload alarm activates if the load is above this threshold continuously for the System Overload Recognition Period. Measured as a percentage of total rectifier capacity.

DCTools/Web: Alarms > Alarm Configuration

System Overload Recognition Period

The System Overload alarm activates if the load is above the threshold continuously for this time. It is normally set to several hours so that the alarm does not operate during a normal battery recharge.

System Overload Type

The System Overload alarm can be based on either Total Capacity or Redundancy.

If the system overload type is based on Total Capacity then the alarm will trigger when the load is above the System Overload Threshold for the System Overload Recognition Period.

If the system overload type is Redundancy then the alarm will trigger when the load is above the total current capacity of the system minus the current capacity of the largest rectifier, for the System Overload Recognition Period.

An alarm will always activate if the system overload type is set to Redundancy when there is only one rectifier installed.

Page 52: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

44 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Smart Alarms

Smart Alarms are a software simulation of logic gates to allow the logical combination of other alarms, time schedules and/or system values. Up to 32 Smart Alarms can be configured.

A single Smart Alarm is the equivalent of a multi-input AND, OR or XOR logic gate. More complex logic arrangements are created by using one Smart Alarm as an input into another. For example:

Two input AND gate:

SAx = Sa AND Sb

Three input OR gate:

SAy = Sa OR Sb OR Sc

Multi-gate logic:

SAz = SAx OR NOT Sd

One input is Smart Alarm SAx (output from another gate). The other input is negated. This is available with Alarm Sources only.

Key:

SAx, SAy, SAz are Smart Alarms (entered in the Smart Alarms table).

Sa, Sb, Sc, Sd are the Sources (entered in the Alarm Sources, Schedule Sources or System Value Sources tables).

Smart Alarms also have optional activation and deactivation delays. When activated they can cause alarm indications (unless Severity is set to Control) and can activate one or two digital outputs (in the same way as other alarms).

For more information and application examples contact your Eaton DC product supplier and request Eaton Application Note AN0106, SC200 Version 3 Advanced Alarm Features.

Page 53: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 45

Sources

The inputs to Smart Alarms are called Sources.

Sources can be any combination of:

Alarm Sources (up to 64):

System Alarms, Analog Input High alarms, Analog Input Low alarms, Digital Input alarms, Other Smart Alarms

Alarm Sources can either use the alarm’s recognition period,or be triggered immediately. Alarm Sources can also be triggered either when the source alarm becomes active or when it becomes inactive.

Time Schedules (up to 20)

Time schedules can repeat for a fixed number of times, or indefinitely.

System Values (up to 20):

Bus Voltage, Rectifier Current, Load Current, Battery Current, Battery Temperature, Load Power, System Power, Ah Discharged, Number Of Rectifiers Failed, Number Of Rectifiers Comms Lost.

System Value Sources are active either when the system value is above or below a defined threshold value.

Configuration

Information

The following information is available about Smart Alarms and Sources.

Parameter Description Where to find:

Smart Alarm State The present state of the Smart Alarm. If Enabled and active, this will be the alarm's Severity. If Disabled, or Enabled but inactive, the state is shown as "-".

DCTools/Web: Alarms > Smart Alarms > Smart Alarm States

Source Triggered The present state of the source:

= Enabled and active "-" = Disabled, or Enabled but inactive.

= There is an invalid dependency, or the source Index is invalid.

DCTools/Web: Alarms > Smart Alarms > Sources

Next Activation The date and time this schedule will next activate. DCTools/Web: Alarms >

Smart Alarms > Schedule Sources Schedule End The date and time this schedule will activate for

the last time.

Page 54: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

46 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

► To create a Smart Alarm

1 Determine the equivalent logic gate arrangement for the Smart Alarm.

Smart Alarms can be regarded as logic gates. Each gate (AND, OR or XOR) is an entry in the Smart Alarm States table. The gate inputs are entries in the Alarm Sources, Scheduled Sources or System Value Sources tables.

2 Configure the Smart Alarm(s):

In DCTools/Web go to: Alarms > Smart Alarms.

Expand the Smart Alarm States table and configure a Smart Alarm and configure the following parameters.

To change a setting, double-click and select from drop down list or edit the text.

Parameter Setting

Name Type the name of the alarm.

Severity Set to the required alarm priority. This determines how the alarm is indicated. See details on page 40.

If set to Disabled then the alarm will not activate.

Operator Determines how the sources will be logically combined (AND, OR or XOR).

Recognition Period The alarm will activate when the logical combination of the sources has been true for this period.

Deactivation Recognition Period

The alarm will deactivate when the logical combination of the sources has been false for this period.

Digital Output Mapping A

If required, select a relay that will be operated when the alarm is active.

Digital Output Mapping B

If required, select a second relay that will be operated when the alarm is active.

Send Trap An SNMP Trap will be sent for this alarm, if Send Trap is True and the alarm's Severity matches the setting of the SNMP Trap Level (see details on page 76).

Trap Origin Sent in the Trap Origin field.

Group Set to 0 unless using Groups in PowerManagerII. See PowerManagerII online help for details.

Notes Type any required description. When the alarm is active the text will be displayed on the SC200 and included in the SNMP trap (if used).

Page 55: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 47

► To configure the Source(s) for a Smart Alarm

Configure the following parameters for the source(s) for each Smart Alarm.

Every Smart Alarm must have at least one Source assigned to it.

Alarm Sources

Parameter Setting

SA Num Type the number (from the Smart Alarm States table) of the Smart Alarm for which this source is an input.

Status Set to Enabled.

Logic Set to either:

EQUAL - the Alarm Source will become active when the source alarm is Triggered or Active.

NOT - the Alarm Source will become active when the source alarm is Inactive.

Trigger When Source Is

Set to either:

Triggered - the Alarm Source will become active immediately when the conditions for this alarm become true (or false when Logic is set to NOT). The alarm does not have to be Enabled.

Do not use Triggered when Type is set to Smart Alarm.

Active - the Alarm Source will become active when the alarm becomes active (or inactive when Logic is set to NOT), after the alarm recognition time, and only if the alarm is Enabled.

Type Set to the appropriate source type: System Alarm, Analog Input High, Analog Input Low, DI, Smart Alarm.

Index Identify the alarm:

Source Type = System Alarm: DCTools - type the alarm number from the Alarm States table. Web - select the name of the system alarm from the list.

Source Type = AI High/AI Low - type the alarm number from the Analog Input High Alarms or the Analog Input Low Alarms table.

Source Type = DI - type the alarm number from the Digital Input Alarms table.

Source Type = Smart Alarm - type the alarm number from the Smart Alarm States table.

Page 56: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

48 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Scheduled Sources

Parameter Setting

SA Num Type the number (from the Smart Alarm States table) of the Smart Alarm for which this source is an input.

Status Set to Enabled.

First Date / Time Set to the date and time for the first activation of the Schedule Source.

Duration Set the time the Schedule Source will be active.

Interval Set the time between activations.

Number of Activations

Set the number of activations.

If set to zero then there is no limit to the number of activations.

System Value Sources

Parameter Setting

SA Num Type the number (from the Smart Alarm States table) of the Smart Alarm for which this source is an input.

Status Set to Enabled.

System Value Set to the required value (Bus Voltage, Rectifier Current, Load Current, Battery Current, Battery Temperature, Load Power, System Power, Ah Discharge, Number Of Rectifiers Failed, Number Of Rectifiers Comms Lost).

Threshold Type Set to either:

High - the System Value Source will be true when the System Value goes above the Threshold.

Low – the System Value Source will be true when the System Value goes below the Threshold.

Threshold The System Value Source will be true when the System Value goes above or below (depending on the Threshold Type) this value.

Hysteresis Determines when an active System Value Source will become false:

If Threshold Type is set to Low the System Value Source will become false when the System Value goes above Threshold + Hysteresis.

If Threshold Type is set to High the System Value Source will become false when the System Value goes below Threshold - Hysteresis.

Latched Smart Alarm

A Smart Alarm can be latched so that once it become active it must be cleared manually.

► To Create a latched Smart Alarm

1 Configure a Smart Alarm with the following parameter settings:

Operator: OR

Severity: Select the level for the required alarm indications (see details on page 40).

Page 57: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 49

Set other parameters as required (see details on page 45).

2 Configure an Alarm Source with the following parameter settings:

SA Num: The number of the Smart Alarm configured in step 1.

Status: Enabled

Logic: EQUAL

Trigger When Source Is: Active

Type: Smart Alarm

Index: The number of the Smart Alarm configured in step 1.

3 Configure a second source (Alarm Source, Schedule Source or System Value Source) with the following parameter settings:

SA Num: The number of the Smart Alarm configured in step 1.

Status: Enabled

Set other parameters as required (see details on page 45).

The Smart Alarm will activate when the source (configured in step 3) becomes active. The Smart Alarm will then remain active until it is manually cleared (see next), even if the source is deactivated.

► To Clear a latched Smart Alarm

Either:

Use SC200 keypad to go to: Alarms. Select the active alarm. Press Details > Clear.

Or:

In DCTools/Web go to: Alarms > Smart Alarms. Click the Clear button.

Batteries

The following information is available about the batteries connected to the dc power system.

Parameter Description Where to find:

Battery Charge State

Charge - the battery current is above the Battery State Threshold.

Discharge - the battery current is below -1 * Battery State Threshold.

Floating - the battery current is between ± Battery State Threshold.

Unavailable - the battery current is not available.

See SC200 or DCTools/Web displays ??? or N/A on page 89.

SC200: Battery > Battery

DCTools/Web: Batteries

Battery Temperature

The temperature measured by the battery temperature sensor.

Ah Discharged The current level of battery discharge.

See also Reset Battery State.

Page 58: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

50 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Batteries Configuration

The following battery parameters must be configured.

Parameter Description Where to find:

Cells Per String The number of 2V cells per battery string (for example: 24 in a 48V nominal system). SC200: Battery > Battery

(tab)

DCTools/Web: Batteries Battery Capacity Set to the rated 10 hour capacity of the installed battery strings.

Battery State Threshold

Used to determine the Battery Charge State. See Battery Charge State on page 49.

DCTools/Web: Batteries

Battery Type An optional text field for the name or type of battery.

Battery Current Sensor Fail Recognition Period

An optional battery current sensor fail delay.

Set if momentary battery current sensor fail conditions stop battery related control processes.

Battery Mid-point Monitoring (MPM)

Battery Mid-point Monitoring provides a cost-effective method for the early detection of internal battery faults. The voltages of the two halves of a battery string are measured and the system controller generates an alarm signal if a voltage imbalance is detected.

A voltage imbalance is an indication that one or more cells has an internal fault. Further investigation can then isolate the faulty cell(s) and action can be taken to correct the problem and prevent a total battery failure.

To connect Battery Mid-point Monitoring see details in the dc power system installation guide. If a String Fail alarm is generated see Troubleshooting on page 88.

To ensure reliable operation Mid-point Monitoring operates only when the battery is in float charge and after a configurable lockout period since the last battery discharge, Fast Charge, Equalize or Battery Test.

Page 59: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 51

► To enable Battery Mid-point Monitoring (MPM)

If any of the mid-point monitoring analog inputs are used for Reverse Battery Detection (see details on page 58) then they are not available for MPM.

1 Connect the mid-point monitoring sense wires to the batteries. Refer to the dc power system Installation and Operation Guide.

There are four mid-point monitoring analog inputs on an IOBGP input/output board (for four battery strings). Up to 20 additional battery strings can be monitored if additional IOBGP input/output boards are connected. Refer to the dc power system Installation and Operation Guide for details on how to connect additional IOBGP input/output boards to the SC200.

2 In DCTools/Web go to Batteries.

3 Set Cells Per String to the number of 2V cells per string (for example: 24 for 48V nominal system).

4 Expand the Mid-point Monitoring table.

5 Set MPM Enable to Enabled and check the configuration settings (see details on page 53).

6 Go to Analog Inputs and Enable the mid-point monitoring analog inputs (one per battery string) as required.

Battery strings 1-4 will be connected to IOB Number 1, IOB AI Numbers 2-5. Battery strings 5-8 will be connected to IOB Number 2, IOB AI Numbers 2-5. And so on, as required up to string 24.

7 Go to Alarms > Alarm States. Enable and configure the String Fail alarm. See System Alarm Configuration on page 42.

► To clear a String Fail alarm

1 In DCTools/Web go to Batteries > Mid-point Battery Monitoring (expand the table).

2 Click on Clear String Fail.

Page 60: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

52 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Information

The following information is available about Battery Mid-point Monitoring.

Parameter Description Where to find:

MPM State Disabled: MPM is Disabled.

Unable To Start: MPM is Enabled but either: Cells per String is zero; the bus voltage sensor has failed; ac supply has failed; the battery is in discharge state; Fast Charge, Equalize or Battery Test is active; or the battery fuse has failed.

Locked Out: MPM is within the MPM Lockout Period. No String Fail alarm will become active in this period.

Converging: MPM is outside the MPM Lockout Period but is within MPM Convergence Period.

Stable: MPM is outside the MPM Convergence Period.

SC200: Battery > MPM

DCTools/Web: Batteries > Mid-point Monitoring

Time In This State The time period MPM has been in the current state.

Current MPM Threshold

When MPM state is Converging this value is between MPM Start Threshold and MPM Stable Threshold. When MPM state is Stable this value is the MPM Stable Threshold.

Reference Voltage The calculated mid-point reference voltage (50% of the bus voltage for even number of cells).

String State OK: MPM is in the state Converging or Stable and the string's Imbalance is below the current threshold.

Unavailable: The MPM is not in state Converging or Stable, or the string's mid-point voltage is unavailable.

Pending Fail: The string's Imbalance is above the current threshold, but has not yet been so continuously for the String Fail Recognition Period.

Fail: The string's Imbalance has been above the Current MPM Threshold for longer than the String Fail Recognition Period. This will activate a String Fail alarm.

Not Configured: No analog input is mapped to this string.

Mid-point Voltage Shows the mid-point voltage reading for the string or N/A if no analog input channel is mapped to this string.

Imbalance The percentage imbalance of the Mid-point Voltage.

Page 61: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 53

Configuration

Set the following parameters.

Parameter Description Where to find:

String Fail alarm parameters

See System Alarm Configuration on page 42. DCTools/Web: Alarms > Alarm States

MPM Enable Enable/disable Mid-point Monitoring.

SC200: Battery > MPM > Settings

DCTools/Web: Batteries > Mid-point Monitoring

MPM Lockout Period*

Time from when MPM is able to start until the start of the MPM Convergence Period.

MPM Convergence Period*

Time from the end of the MPM Lockout Period until MPM State is Stable. During this period the Current MPM Threshold is calculated using linear interpolation between Start Threshold and Stable Threshold and the MPM State is defined as Converging. After this period the MPM State is defined as Stable and the MPM Stable Threshold applies.

String Fail Recognition Period

If the mid-point Imbalance percent of a battery string exceeds the MPM Threshold for this period of time the String State is set to Fail and the String Fail alarm is activated.

MPM Start Threshold*

Mid-point Imbalance percent threshold at the start of the MPM Convergence Period.

MPM Stable Threshold*

Mid-point Imbalance percent threshold after the convergence period.

* A dynamic alarm threshold is used to give the best possible battery fault detection:

1 After the end of a discharge, Fast Charge or Equalize cycle, MPM does not start until the end of the MPM Lockout Period, to ensure the system is in float charge.

2 At this point, the battery cell voltages are expected to be widely spread, so the alarm threshold is set high (MPM Start Threshold).

3 The alarm threshold is then progressively reduced over the MPM Convergence Period.

4 After the end of the MPM Convergence Period, cell imbalance is assumed to be stable, and a fixed threshold is used (MPM Stable Threshold).

Page 62: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

54 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Battery Time Remaining

The SC200 obtains characterization data from every full battery discharge, to a specified end voltage.

During a battery discharge, the SC200 uses this characterization data to calculate an estimated time until the battery will reach the specified end voltage.

If a battery disconnect LVD is fitted then the end voltage will usually be the voltage at which the LVD disconnects the battery.

Battery Time Remaining is designed for a constant power load. The accuracy of the time remaining calculation will be reduced if the dc power system is connected to a predominantly resistive (constant current) load.

The time remaining calculation will not be correct if a non-essential load is disconnected during the battery discharge.

The following information is available about Battery Time Remaining.

Parameter Description Where to find:

Battery Time Remaining*

During a battery discharge, this is the estimated time until the battery voltage will be equal to the End Voltage, at the present battery current. Time Remaining will be re-calculated if the load current varies during discharge (for example, when a load disconnect LVD operates).

SC200: Menu > Controls > Batt Time Remaining

DCTools/Web: Batteries

Estimated State of Charge (SOC)*

The estimated charge left in the battery (Ah).

*Values of Battery Time Remaining and SOC are only available during a discharge and if the battery has been characterized. The values will be N/A when the Battery Charge State is Floating or Charge, or if the battery has not been characterized. See Battery Characterization.

Page 63: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 55

Configuration

It will take at least 10 hours to characterize a battery.

When a battery is characterized it is discharged. The bus voltage will gradually reduce to the battery end voltage. Ensure that this will not affect the operation of any equipment connected to the dc power system.

Use the following procedure to configure Battery Time Remaining for the first time, or if a previously characterized battery is changed.

Battery Characterization is not necessary if a previously saved battery characterization data file is available. Refer to Characterization Data Management on page 58. Only use characterization data for an identical type and size of battery.

► To configure Battery Time Remaining

1 Check that all battery strings are connected and all LVD contactors (if any) are connected.

During a battery characterization, LVD contactor disconnection is inhibited. If any LVD contactor is configured to connect during a battery discharge then set it to Manual Connect to prevent operation during the battery characterization.

2 Check that all battery strings are fully charged.

When a battery is fully charged, the Battery Charge State will be Float and Ah Discharged will be zero. See Batteries on page 49.

3 Check that all battery parameters are set to the correct values. See Batteries Configuration on page 50.

4 Check that the load current is at least 2% of the C10 capacity of the batteries (Battery Capacity) and 150% of the Battery State Threshold. See Batteries Configuration on page 50.

If the load current is less than 10% of the C10 capacity of the batteries, then Battery Characterization will take longer than 10 hours.

5 Either, in DCTools/Web go to Batteries > Battery Time Remaining, or use the SC200 keypad to go to Battery. Set End Voltage to the voltage per cell when the battery is regarded as fully discharged.

In general set the end voltage to the same value as for the LVD Disconnect Voltage (see LVD Configuration on page 37). End Voltage must be at least 0.02V/Cell above the Minimum System Voltage (per cell). The Minimum System Voltage is viewable in DCTools/Web at Control Processes. It is not configurable.

6 Enable Battery Current Limit (see details on page 21).

Page 64: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

56 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

► To Characterize the Battery

1 Either:

Manually start a Characterization: On the SC200 go to: Battery > Characterize > Start. Or, in DCTools/Web go to: Battery > Battery Time Remaining. Click Characterize.

If "Characterize" is not present on the SC200 or the "Characterize" button is inactive in DCTools/Web, then check all configuration settings. In DCTools/Web, the hover text will indicate why the characterization cannot start.

Or, use Automatic Characterization to start a characterization automatically when all conditions are correct and stable: In DCTools/Web go to: Battery > Battery Time Remaining. Set Automatic Characterization to Enabled and set Automatic Characterization Delay to the required time that the conditions must be stable.

2 The characterization process will take at least 10 hours, depending on the load current.

During characterization the rectifier output voltage is varied to maintain a constant power discharge.

3 When the characterization has finished, the Characterization Result will be Updated.

If any other Characterization Result is shown, refer to BTR Operation on page 57.

4 The rectifiers will return to float voltage and the battery will start to recharge. If required, start a manual Equalize (see details on page 24) to reduce the battery recharge time.

5 Restore any changed LVD operation back to the original settings. If no longer required, disable Battery Current Limit.

Battery Time Remaining is now operational. During any battery discharge an estimate of time remaining will be displayed.

Page 65: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 57

Operation

The following information is available about Battery Time Remaining.

Parameter Description Where to find:

Time Remaining During a battery discharge, this is the estimated time until the battery voltage will be equal to the End Voltage, at the present battery current. Time remaining will be re-calculated if the load current varies during discharge (for example, when a load disconnect LVD operates).

Time Remaining is only available when Battery Time Remaining State is Active.

SC200: Battery

DCTools/Web: Batteries

Battery State Of Health

The approximate battery capacity measured during the last battery characterization, as a percentage of the configured Battery Capacity.

DCTools/Web: Batteries

State Inoperative: The battery characterization data is not loaded, End Voltage is below the characterization end point, or the bus voltage or battery current is unavailable.

Inactive: Battery Charge State is Float or Charge.

See Battery Charge State on page 49.

Characterizing: Battery characterization is in progress.

Active: The battery has been characterized and Battery Charge State is Discharge.

See Battery Charge State on page 49.

SC200: Battery

DCTools/Web: Batteries > Battery Time Remaining

Lowest End Voltage

The end voltage used for the last battery characterization.

Characterization Result

Not Yet Run: The battery has not been characterized since the last restart of the SC200.

Active: The SC200 is collecting the characterization data.

Complete: The SC200 has collected the characterization data and is updating its database.

Updated: The SC200 has updated its database.

Sensor Failed: Data from the last characterization was not saved because the bus voltage sensor failed or the battery current became unavailable.

Not Fully Charged: Characterization did not start because the battery was not fully charged when discharge started.

Unstable Battery Current Pending: The battery current has varied more than the tolerance for an accurate characterization. Characterization will continue if the battery current is in tolerance within one minute. Otherwise, data from this discharge will not be saved.

Unstable Battery Current: Data from the last characterization was not saved because the battery current varied more than the tolerance,

Page 66: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

58 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

for more than one minute.

Voltage Step Detected: Data from the last characterization was not saved because of a change in the bus voltage (possibly caused by a load disconnect).

Canceled: Data from the last characterization was not saved because the characterization was stopped manually.

Characterization Data Management

Battery characterization data can be saved to file for later use. This is useful if several sites use batteries of the same type and size. However, characterization of each battery will provide the most accurate estimate of Time Remaining.

► To save characterization data to a file

1 In Web go to Batteries > Battery Time Remaining.

2 When the battery characterization is completed, click on Characterization Data: Download.

3 Click Save. Type a file name (*.dcf) and browse to the required location. Click Save.

► To load battery characterization data into the SC200

Use Web to restore the *.dcf (configuration fragment) file previously saved. Refer to Backup and Restore on page 18.

Reverse Battery Detection

If Reverse Battery Detection is enabled and a battery is connected with the incorrect polarity, the SC200 will:

activate a Wrong Battery Polarity alarm, and

prevent any LVD from connecting.

Reverse Battery Detection uses the battery mid-point monitoring (MPM) analog inputs on an IOBGP input/output board. Any of the mid-point monitoring analog inputs used for Reverse Battery Detection are not available for MPM (see details on page 50).

Page 67: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 59

► To enable Reverse Battery Detection

1 Before the batteries are connected to the dc power system, connect the mid-point monitoring sense wires to the battery sides of the battery fuses/disconnect devices (leave the fuses/disconnect devices open). Refer to the dc power system Installation and Operation Guide.

There are four mid-point monitoring analog inputs on an IOBGP input/output board (for four battery fuses/disconnect devices). Up to 20 additional battery fuses/disconnect devices can be connected if additional IOBGP-01 input/output boards are connected. Refer to the dc power system Installation and Operation Guide for details on how to connect additional IOBGP-01 input/output boards to the SC200.

2 In DCTools/Web go to Analog Inputs and for each mid-point monitoring analog inputs used (one per battery fuses/disconnect devices) set the following parameters.

To change a setting, double-click and select from drop down list or edit the text.

Parameter Setting

Status Set to Enable.

Name Set to: Battery Polarity Detect 1, Battery Polarity Detect 2, ...

Function Set to Reverse Battery Detection.

Units Set to Volts.

IOB Number Set to 1 for battery fuses/disconnect devices 1-4.

Set to 2 for battery fuses/disconnect devices 5-8.

...

IOB AI Number Set to 2 for battery fuses/disconnect devices 1, 5, 9 ...

Set to 3 for battery fuses/disconnect devices 2, 6, 10 ...

...

Gain Set to 1.

Offset Set to 0.

Group Set to 0 unless using Groups in PowerManagerII. See PowerManagerII online help for details.

Wrong Battery Polarity Alarm

If Reverse Battery Detection is connected and enabled, the SC200 will activate a Wrong Battery Polarity alarm if it detects that one or more of the batteries are connected with the wrong polarity.

Page 68: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

60 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Generator Control Option

Generator Control is used to delay the start of standby ac generators until the batteries are partially discharged (rather than immediately after the ac supply fails). This can save fuel by preventing generators running during short ac supply failures. It can also be used to control a generator in a hybrid power system (cyclic charge/discharge).

Generator Control uses a digital output (relay) which is connected in series with the generator run signal of the generator controller. The relay is controlled by the Generator Enable alarm. The relay contacts interrupt the generator run signal until the Generator Enable alarm is active.

The Generator Enable alarm is activated when the ac supply fails and either the Fast Charge or Equalize control process starts (depending on the setting of the Generator Start Trigger).

The Generator Enable alarm stays active (and the generator running) until the ampere-hours recharged is enough for the battery to be fully charged, or until the maximum fast charge duration is reached.

A Generator Fail alarm is activated if the SC200 does not detect that the ac supply is present (rectifiers have turned on) after the Generator Fail Alarm Recognition Period following Generator Enable becoming active.

Single line diagram

AC utility supply

Generator

AC change-over switch

Rectifiers

Generator control panel

Normally open (NO) relay contacts on I/O board interrupt Generator Run signal.

Page 69: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 61

Typical operation

AC Supply

Battery Discharge

Generator Run

Generator Fuel Savings

AC supply failure. Battery starts to discharge.

AC supply restored. Battery begins to recharge. Battery discharge did not reach the Ah Threshold. Generator Enable was not active (relay contacts did not close) so the generator did not run.

AC supply failure. Battery starts to discharge.

Battery discharge reaches the Ah Threshold. Generator Enable becomes active and the relay contacts close. The Generator Run circuit is completed allowing the generator to start. Battery begins to recharge.

Battery recharge is complete. Generator Enable becomes inactive and the relay contacts open. The Generator Run circuit is interrupted causing the generator to stop. Battery begins to discharge.

AC supply restored. Battery begins to recharge. Battery discharge did not reach the Ah Threshold. Generator Enable was not active (relay contacts did not close) so the generator did not run.

Configuration

1 In DCTools/Web go to Alarms > Alarm States (expand the Alarms table).

See Alarms on page 39.

2 Set the Severity of the Generator Enable alarm to enable it.

3 In the Alarm DO Mapping A column select a spare digital output (relay).

4 In DCTools/Web go to Digital Outputs and configure the digital output as Active State Energized. See Digital Outputs on page 67.

5 Connect from the normally open (NO) contacts of the digital output relay on the I/O board to the generator run circuit.

6 Go to Control Processes > Generator Control.

7 Set Generator Start Trigger to either Fast Charge Only or Fast Charge and Equalize as required.

8 Go to Control Processes > Fast Charge.

9 Check that Fast Charge is enabled, and check the following configuration settings.

Page 70: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

62 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Parameter Description Where to find:

Battery Capacity Set to the rated 10 hour capacity of the installed battery strings.

SC200: Battery > Battery

DCTools/Web: Batteries

Ampere-Hour Threshold

If Ah Discharged is above this value, then the Generator Enable alarm will be active. The threshold is given as a percentage of installed C10 battery capacity.

Generator Enable alarm can also be triggered based on the Voltage Threshold.

SC200: Control Processes > Fast Charge

DCTools/Web: Control Processes > Fast Charge

Voltage Threshold If the bus voltage drops below this value then Generator Enable alarm will be active. Generator Enable alarm can also be triggered based on the Ampere-Hour Threshold.

Recharge Percentage

The ratio of ampere-hours recharged to the ampere-hours discharged. Fast Charge stops either when the Ah recharged equals the Ah discharged x Fast Charge Recharge Percentage, or after Maximum Duration.

Maximum Duration

The maximum duration of a Fast Charge as recommended by the battery manufacturer.

Generator Fail Alarm Recognition Period

A Generator Fail alarm is activated after this time if Generator Enable is active but the SC200 does not detect that the ac supply is present (rectifiers have turned on).

SC200: Alarms > Alarm Settings > System Alarms > Generator Fail

DCTools/Web: Alarms > Alarm Configuration

Input/Output (I/O)

The following section describes the I/O functions available with a single IOBGP I/O board.

Also see I/O Board Mapping on page 109.

Optional SiteSure-3G input/output (I/O) modules or additional IOBGP I/O boards can be connected to the SC200 to provide additional I/O to monitor and control external devices. For details refer to the SiteSure-3G Installation Guide (see Related Information on page i).

Identify an I/O Board

Input/Output (I/O) boards and SiteSure-3G modules are referenced by their serial numbers.

► To identify a particular I/O board or SiteSure-3G module

Either:

On SC200 keypad go to: Settings > IOBs and select a module or board. Press Enter.

The I/O board details screen appears. Use to scroll to other I/O boards.

The Power-on LED on the selected I/O board or SiteSure-3G module will flash for 60 seconds (or press Esc to stop).

Page 71: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 63

Or:

In DCTools/Web go to: Configuration > RXP > RXP Devices.

DCTools: select Identify Device or Web: click on Start Identifying.

The Power-on LED on the selected I/O board or SiteSure-3G module will flash for 60 seconds.

Analog System Values

The SC200 provides access to the following system analog values.

Parameter Description Where to find:

Bus Voltage The average of all analog inputs configured as Bus Voltage. Otherwise, the system bus voltage is determined from the rectifier output voltages.

SC200: Analogs

DCTools/Web: Analog Inputs > System Values

Load Current The sum of any analog inputs configured as Load Current. Otherwise, if Battery Current is available, the Load Current is calculated as Rectifier Current - Battery Current. Otherwise it is unavailable.

Battery Current The sum of any analog inputs configured as Battery Current. Otherwise, if Load Current is available, the Battery Current is calculated as Rectifier Current - Load Current. Otherwise it is unavailable. If positive, the battery is being charged.

Battery Temperature

The average of all analog inputs configured as Battery Temperature.

Rectifier Current The sum of any analog inputs configured as Rectifier Current. Otherwise, if there are Battery and Load Currents, the Rectifier Current is calculated as Battery Current + Load Current. Otherwise, Rectifier Current is determined as the sum of all reported rectifier output currents.

Load Power The power being supplied to the load. Load Current x Bus Voltage.

System Power The output power of the system as a percentage of the total nominal power of the registered rectifiers.

AC Voltage The average of the ac voltage measured by single-phase rectifiers.

Or, if 3-phase rectifiers are fitted then the average of the ac phase voltages is shown.

Analog Inputs

The analog inputs (AI) monitor variable dc voltages (bus voltage sense, general purpose analog inputs, current sensors or temperature sensors). See Specifications on page 93 for details.

Generally, the system analog inputs (as indicated by the "Function" field) are configured at the factory and do not need to be changed.

Page 72: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

64 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

► To configure an analog input

1 In DCTools/Web go to Analog Inputs. Expand the Analog Inputs table.

The table shows the maximum number of analog inputs. The actual number of analog inputs available depends on the number of I/O boards or modules connected.

2 Select an Analog Input. The analog inputs are mapped to specific I/O connectors and are of three types (voltage/general purpose, current or temperature). See mapping tables on page 109.

If needed, more than one analog input can be mapped to the same connector so that the sensor can trigger more than one Analog Input High and/or Low Alarm. In this case, no more than one analog input can be assigned to a system function.

3 Configure the following parameters to suit the application.

To change a setting, double-click and select from drop down list or edit the text.

Parameter Setting

Status Set to Enabled.

Name Type the name of the input or use the default value.

Function Set to User Defined. Or to a particular system function if the input is to be associated with that function.

Units Select the units to match the type of analog value.

IOB Number The number of the I/O board or module.

Generally, do not change this mapping. See point 2.

IOB AI Number The number of the AI on the I/O board or module.

Generally, do not change this mappings. See point 2.

Gain A scaling factor applied to the raw measured value.

Offset A fixed value added to the raw measured value (after any Gain is applied).

Group Set to 0 unless using Groups in PowerManagerII. Refer to PowerManagerII online help.

Analog Input High and Low Alarms

Any analog input that is Enabled in the Analog Inputs table can activate a high and/or low alarm.

The Alarm Recognition Period (see details on page 41) applies to analog input alarms.

Configure the following parameters in the Analog Input High Alarms and/or Analog Input Low Alarms tables to suit the application.

To change a setting, double-click and select from drop down list or edit the text.

Page 73: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 65

Parameter Setting

Severity Set to the required alarm priority. This determines how the alarm is indicated. See details on page 40.

If set to Disabled then the alarm will not activate.

Threshold An analog input high/low alarm is activated if the scaled input is greater than/less than or equal to this value.

Hysteresis The amount of hysteresis applied to the input before an active alarm is deactivated.

Digital Output Mapping A

If required, select a relay that will be operated when the alarm is active.

Digital Output Mapping B

If required, select a second relay that will be operated when the alarm is active.

Send Trap An SNMP Trap will be sent for this alarm, if Send Trap is True and the alarm's Severity matches the setting of the SNMP Trap Level (see details on page 76).

Notes Type any required description. When the alarm is active the text will be displayed on the SC200 and included in the SNMP trap (if used).

System States

The SC200 monitors the following system states to provide an overview of the dc power system's operation. States displayed will depend on the dc power system model.

Name Description Where to find:

Fan Indicates if any digital input with Function set to "ACD Fan Fail" is active (only used in systems with ac distribution fans).

SC200: Digitals

DCTools/Web: Digital Inputs

Cabinet Fan Indicates if any digital input with Function set to "Cabinet Fan Fail" is active (only used in systems with cabinet fans).

Mains Fail Indicates if any digital input with Function set to "AC Fail" is active.

MOV Fail Indicates if any digital input with Function set to "MOV Fail" is active (only used in systems with MOV surge protection).

Load Fuse Fail Indicates if any digital input with Function set to "Load Fuse Fail" is active.

Battery Fuse Fail Indicates if any digital input with Function set to "Battery Fuse Fail" is active.

Phase Fail Indicates if any digital input with Function set to "Phase Fail" is active.

Notes:

1 See the related Alarm Descriptions on page 97.

2 A value of Unavailable indicates that a System State is not configured for this dc power system.

3 A value of Missing indicates that the I/O board has been disconnected or is faulty, or the connector mapping is incorrect.

Page 74: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

66 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Digital Inputs

The input/output (I/O) board is fitted with a number of configurable digital inputs (DI) which can monitor external voltage-free relay contacts or switches. See Input/Output Board on page 2 for details.

► To configure a digital input

1 In DCTools/Web go to Digital Inputs. Expand the Digital Inputs table.

2 Digital Input 1-6 are available for configuration.

Digital Input 7-10 (on I/O board 1) are used for system alarms.

If additional I/O boards and/or SiteSure-3G modules are connected there will be more configurable Digital Inputs. See details in the dc power system installation guide.

The last four digital inputs are the pre-assigned Digital System States (see details on page 65). Do not change these settings.

3 Select a configurable Digital Input.

4 Configure the following parameters to suit the application.

To change a setting, double-click and select from drop down list or edit the text.

Parameter Setting

Status Set to Enabled.

Name Type the name of the input.

Function Set to User Defined.

IOB Number The number of the I/O board (or SiteSure-3G module if connected). Do not change.

IOB DI Number The number of the DI on the I/O board (or SiteSure-3G module if connected). Do not change.

Active State Select the state of the input that will activate the DI.

Group Set to 0 unless using Groups in PowerManagerII. See PowerManagerII online help for details.

Digital Input Alarms

Any digital input that is Enabled in the Digital Inputs table can activate an alarm.

Configure the following parameters in the Digital Input Alarms table to suit the application.

To change a setting, double-click and select from drop down list or edit the text.

Page 75: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 67

Parameter Setting

Severity Set to the required alarm priority. This determines how the alarm is indicated. See details on page 40.

If set to Disabled then the alarm will not activate.

Recognition Period The alarm will activate only after the digital input is active for this period.

Deactivation Recognition Period

The alarm will deactivate only after the digital input is inactive for this period.

Digital Output Mapping A

If required, select a relay that will be operated when the alarm is active.

Digital Output Mapping B

If required, select a second relay that will be operated when the alarm is active.

Send Trap An SNMP Trap will be sent for this alarm, if Send Trap is True and the alarm's Severity matches the setting of the SNMP Trap Level (see details on page 76).

Notes Type any required description. When the alarm is active the text will be displayed on the SC200 and included in the SNMP trap (if used).

Digital Outputs

The input/output (I/O) board is fitted with a number of digital outputs (relays) which can control external equipment or alarm systems. See Input/Output Board on page 2 for details.

Digital outputs are operated by a mapping from a digital input alarm (see details on page 66), an analog input high or low alarm (see details on page 63), or a system alarm (see details on page 39).

► To manually control a digital output

Either:

In DCTools/Web go to Digital Outputs:

Expand the Digital Outputs table.

In the Control State column of the required digital output, select Active or Inactive.

Or, use the SC200 keypad to go to Digital Outputs:

Select the required digital output. Press Edit.

Select Active or Inactive. Press Save.

The DO Manual alarm (if enabled) will activate.

The corresponding digital output will Energize or De-Energize, as selected in the Active State column of the Digital Outputs table.

While Active or Inactive is selected, the DO will not be operated by any active alarms mapped to it. Set Control State back to Automatic to allow mapped alarms to operate the digital output.

Page 76: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

68 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

► To set the state of a digital output from PowerManagerII

In DCTools, set the Group of one or more digital outputs to a non-zero value.

Only digital outputs with a non-zero Group are visible in PowerManagerII

In PowerManagerII select the SiteManager group item.

Click on the Realtime tab.

From the drop down list beside the digital output select Active Manual or Inactive Manual.

The DO Manual alarm (if enabled) will activate.

The corresponding digital output will Energize or De-Energize, according to its Active State.

While Active Manual or Inactive Manual is selected, the DO will not be operated by any active alarms mapped to it. Set Control State back to Automatic to allow mapped alarms to operate the digital output.

► To configure a digital output

1 In DCTools/Web go to Digital Outputs. Expand the Digital Outputs table.

2 Select a Digital Output (1-6*).

Other Digital Outputs will be available if additional I/O boards and/or SiteSure-3G modules are connected. See details in the dc power system installation guide.

3 Configure the following parameters to suit the application.

To change a setting, double-click and select from drop down list or edit the text.

Parameter Setting

Control State Set to Automatic.

Status Set to Enabled.

Name Type the name of the output.

IOB Number The number of the I/O board (or SiteSure-3G module). Do not change.

IOB DO Number The number of the DO on the I/O board (or SiteSure-3G module). Do not change.

Active State Select the state of the output when the DO is active*.

Group Set to 0 unless using Groups in PowerManagerII. See PowerManagerII online help for details.

* Digital Output 6 is also used as the Monitor Fail alarm relay. It will de-energize if the I/O board loses power or loses communication with the SC200.

Data Logging

The SC200 has the following data logging functions.

Event Log

The Event Log records every system event. See System Event Types on page 107 for a description of event log entries.

The most recent Event Log entries are shown by the SC200 web view, on the Log screen. See Communication via Web Browser on page 74.

Page 77: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

System Operation

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 69

► To view and save the Event Log

To view the log entries, either:

In DCTools go to: Controller Log > Data Log , or

In Web go to Logs > Log Management and click Event Log (CSV): Download to view the log entries in a new browser window.

Wait for the log entries to download from the SC200.

To save the log to a file, either:

In DCTools click on Save to File ... , or

In Web go to File > Save As...

Type a file name, select a file type, and browse to a location to save the file.

► To configure the size of the Event Log

Either:

In DCTools go to: Controller Log > Configuration, or

In Web go to Logs > Event Log Config.

Type the required number of Event Log entries (up to 10,000). Memory will be allocated for at least this number of entries. When the memory is full the oldest record will be over-written.

► To clear the Event Log

In Web go to Logs > Log Management or in DCTools go to Controller Log > Configuration > Log Management.

Click Clear Logs.

This will also clear the Data Log.

Data Log

The Data Log records several system parameters (AC Voltage, Bus Voltage, Load Current, Rectifier Current, Battery Current, Battery Temperature) at specified intervals. The rate of recording increases (interval is reduced) when the bus voltage differs from the float voltage by more than a specified value.

Data log entries are also written whenever a system event occurs (as for the Event Log).

► To view and save the Data Log

To view the log entries, either:

In DCTools go to: Controller Log > Event Log , or

In Web go to Logs > Log Management and click Data Log (CSV): Download to view the log entries in a new browser window.

Wait for the log entries to download from the SC200.

To save the log to a file, either:

In DCTools click on Save to File ... , or

In Web go to File > Save As...

Type a file name, select a file type, and browse to a location to save the file.

► To configure the Data Log

Either:

In DCTools go to: Controller Log > Configuration, or

In Web go to Logs > Data Log Config.

The following parameters must be configured.

Page 78: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

70 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Parameter Description Where to find:

Normal Interval The time between each data log record when the Bus Voltage differs from the Float Voltage by less than the Off-Normal Offset Voltage.

Web: Logs > Data Log Config

DCTools: Controller Log > Configuration > Data Log Config

Off-Normal Interval

The time between each log record when the Bus Voltage differs from the Float Voltage by more than the Data Log Off-Normal Offset Voltage.

Off-Normal Offset Voltage

The Off Normal Log Interval will apply when bus voltage is outside the range: Float Voltage ± Off-Normal Offset Voltage. Off-normal condition transitions are recognized within 10 seconds.

Maximum Number of Log Entries

Memory will be allocated for at least this number of Data Log entries (up to 10,000). When the memory is full the oldest record will be over-written.

► To clear the Data Log

In Web go to Logs > Log Management or in DCTools go to Controller Log > Configuration > Log Management.

Click Clear Logs.

This will also clear the Event Log.

PC Log

The PC Log allows a continuous streaming of system data (Bus Voltage, Load Current, Battery Current, Battery Temperature, Rectifier Current, Load Power, System Power) from the SC200 directly into a specified file.

► To configure and activate the PC Log

1 In DCTools go to PC Log.

2 At File Name, click on the button to type a file name, select a file type, and browse to a location to save the file.

3 Select the required interval between log entries (from 5s to 60 minutes).

4 Click on Start to begin the log.

5 Click on Stop to end the log.

Page 79: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Chapter 4

Communications

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 71

C h a p t e r 4 Communications

Overview

Topic Page

Communications Options 72

Direct (USB) Communications 72

Ethernet Communications 72

Serial (RS232) Communications 78

Communications Security 83

CSP 86

Page 80: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

72 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Communications Options

The SC200 system controller has a standard USB interface, a standard RS232 serial interface (XS1) and an Ethernet 10BaseT interface (XS31) for communication with a local or remote PC or laptop, or a Network Management System (NMS). See the diagrams on page 2 for locations of these connectors.

The standard communications options for an SC200 system controller are described in the following sections. For other communications options contact your Eaton dc product supplier or Eaton (see Worldwide Support on page 115).

Direct (USB) Communications

See SC200 Operation Using a PC/Laptop on page 13.

Ethernet Communications

Connections

SC200 system controller

PC/laptop with:

PowerManagerII and/or DCTools (see details on page 73), and/or

Web browser (see details on page 74), and/or

Network Management System using SNMP (see details on page 75), and/or

Building management System using Modbus-TCP (see details on page 77).

Communications network. Protocol: TCP/IP

MAC Address

► To view the MAC Address of the SC200

Either:

Use the SC200 keypad to go to: Info

Or:

In DCTools/Web go to: Configuration > Communications > Ethernet

The Media Access Control (MAC) address is the SC200’s unique Ethernet address assigned by the manufacturer.

Page 81: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Communications

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 73

SC200 Setup

The network administrator must assign a unique IP address to each SC200 to be connected to the TCP/IP network.

► To configure an SC200 for Ethernet communications from the keypad

Go to Settings > Setup

Enter the IP Address, Subnet Mask and Gateway Address assigned by the network administrator.

If required, set HTTP Access to Enabled for web browser access, or set HTTPS Access to Enabled for secure web access.

► To configure an SC200 for Ethernet communications using DCTools

Connect using USB (see details on page 13).

In DCTools go to Configuration > Communications.

Under Ethernet, type the IP Address, Subnet Mask and Gateway Address assigned by the network administrator.

If required, under HTTP (Web), set HTTP Access to Enabled for web browser access, or set HTTPS Access to Enabled for secure web access.

DCTools or PowerManagerII Communications Setup (if required)

► To connect to the SC200 with DCTools or PowerManagerII:

1 Install DCTools/PowerManagerII on the PC/laptop.

2 Double-click the DCTools/PowerManagerII icon to open the connection manager.

3 Go to Connection > New to open a new connection dialog box.

4 Enter:

Connection Name: <as required>

Comms Enabled: True

Protocol: S3P

Connect Using: Ethernet

S3P Address: 0 (0 = Broadcast, 1-65279 = individual address)

Server IP Address: Allocated by network administrator

Server Port: Allocated by network administrator

Telnet Cleared

5 Press OK. DCTools/PowerManagerII will now connect to the SC200.

6 See System Operation on page 19 for details of the SC200 control and monitoring functions available via DCTools.

For help using DCTools press F1.

7 If required, access to the SC200 via DCTools or PowerManagerII can be password controlled. See Write Access Password on page 84.

Page 82: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

74 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Communication via Web Browser

The SC200 system controller has an in-built web server. This allows a PC/laptop with a standard web browser to control and monitor the SC200 via an IP network.

► To connect to the SC200 with web browser:

1 Set up Ethernet communications and connect the SC200 to the IP network. See Ethernet Communications on page 72.

2 Open a web browser window.

Recommended web browsers: Microsoft Internet Explorer 8 (IE6 is compatible but with reduced performance), Mozilla Firefox 3.0.

3 Type the IP Address of the SC200 into the address bar of the browser.

If HTTPS Access has been enabled and you wish to use secure web communication (see details on page 85) then type "https://" before the IP Address.

4 The SC200 web server Log On page will appear.

5 If required, type a Logon ID and Password. Otherwise select Default User.

Administration of Logon IDs and Passwords is available in DCTools/Web. See Web Access Security on page 85.

6 Click Log On. The SC200 web system page will be displayed.

Page 83: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Communications

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 75

7 Go to the Forms for details of the SC200 control and monitoring functions available via the web.

8 To change a setting click the text field, type the new value, then press Enter on the PC keyboard. Then click Apply in the Changes window.

Hold the mouse pointer over any field for help.

9 Click Log Off (top right of window) to log out.

Communication via a Network Management System using SNMP

The SC200 system controller can be configured to allow access by a Network Management System (NMS), and/or to send alarms as SNMP traps to up to eight different SNMP trap receivers on an NMS.

► To allow NMS access to the SC200

1 Set up Ethernet Communications (see details on page 72).

2 In DCTools/Web go to Configuration > Communications > SNMP.

3 Set the following parameters:

SNMP Access: Disabled: NMS access to the SC200 is not allowed.

All: the NMS has full access to the SC200.

Read Only: the NMS has read only access to the SC200.

V3 Only: SNMP v3 access is allowed.

Read Community, Write Community:

Do not change the default settings unless requested by the network administrator.

Authentication Password (SHA):

Only used with SNMP v3. Set if the NMS requires an authentication password.

Privacy Password (DES): Only used with SNMP v3 and if an authentication password is set. Set if the NMS uses encryption.

System Object ID: This is a unique Object Identifier that allows the NMS to identify the type of device (in this case a power system) on the network. Objects are named in the iso.org.dod.internet.private.enterprises (1.3.6.1.4.1) sub-tree for enterprise-specific objects. The default Object Identifier for an SC200-based dc power system is: 1.3.6.1.4.1.1918.2.13 A network administrator can specify a new Object Identifier within the (1.3.6.1.4.1) sub-tree, if required.

Do not enter the sub-tree integers 1.3.6.1.4.1 into the System Object ID field.

► To send alarms as SNMP traps

1 Set up Ethernet Communications (see details on page 72).

2 In DCTools go to Configuration > Communications > SNMP.

Page 84: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

76 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

3 Set the following parameters:

System Object ID: See: To Allow NMS Access to a SC200 on page 75.

Trap Version: Set to SNMP V1, V2, V3 as required.

Trap Format: Set to Eaton or X.733 as appropriate .

"Eaton" format uses different trap numbers according to the alarm source. X.733 format uses a single trap number for all alarm sources.

Enable Generic Traps, Trap Repeat and Trap Repeat Rate

Configure as appropriate.

4 For each SNMP trap receiver (up to 8) , configure the following parameters.

Parameter Configuration Guidelines

Name Type the name of the SNMP trap receiver (20 bytes maximum).

This allows 20 ASCII characters, but less for languages with multi-byte characters.

Level SNMP Trap Level – controls reporting of specific events for each receiver:

Select All Alarms And Warnings to receive Critical, Major and Minor alarms, and Warnings. (Typically Warnings are status messages such as Equalize Active.)

Select Minor And Above to receive Critical, Major and Minor alarms.

Select Major And Above to receive only Critical and Major alarms.

Select Critical Only to receive only Critical alarms.

Select Disabled to disable notifications to the receiver.

To prevent an SNMP Trap for an individual alarm, set Send Trap to False in the alarm's configuration.

IP Address IP address of the trap receiver assigned by the network administrator.

Port The default setting is 162. Do not change this setting, unless requested by the network administrator.

Trap Community

A form of password. Use public, unless the network administrator has assigned a new password.

Mode Select:

Normal Traps for sending traps to any network management system, except PowerManagerII

Acknowledged Summary Trap for sending traps to PowerManagerII only

Page 85: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Communications

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 77

Modbus-TCP Communications

Modbus-TCP* Connections

The SC200 only accepts one Modbus-TCP connection at a time, on the reserved Modbus-TCP port of 502.

SC200 system controller

PC/laptop with Building Management System using Modbus-TCP.

Communications network. Protocol: TCP/IP

SC200 Setup

1 Setup Ethernet Communications (see details on page 72).

2 Set the following Modbus-TCP* parameters:

Parameter Description Where to find:

Modbus Access Set to Enabled. SC200: Settings > Modbus

DCTools/Web: Configuration > Communications > Remote Access Protocols > Modbus

Address Set to 1 for Modbus-TCP.

* The SC200 also supports Modbus-RTU via the RS232 serial port (XS1). For details request Application Note AN0107 from your Eaton dc product supplier.

Page 86: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

78 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Diagnostics

The following diagnostic information is available.

Parameter Description Where to find:

Bus Message Count Number of messages. Does not include messages with bad CRC.

DCTools/Web: Communications > Modbus > Diagnostics

Bus Communication Error Count

Number of CRC errors.

Slave Exception Error Count

Number of exception errors.

Slave Message Count

Number of messages to the SC200.

Slave No Response Count

Number of messages received for which no response was sent.

Bus Character Overrun Count

Number of messages received with more than 256 characters.

All counts are since the last SC200 restart or since counter was reset.

Serial (RS232) Communications

The parameters of the RS232 serial port can be configured, if required for a specific RS232 device. However, for most applications use the default settings.

Parameter Description Where to find:

Baud Rate Default: 19200 SC200: Settings > Serial Port Settings

DCTools/Web: Configuration > Communications > Serial > Port Settings

Parity Default: None

Stop Bits Default: One

PSTN Modem Communications

Connections

The PC modem may be external to the PC (as shown) or internal.

SC200 system controller

PC/laptop with PowerManagerII and/or DCTools.

RS232 modem cable (straight-thru). If access to XS1 is restricted use a DB9 ribbon cable extension (Farnell part number 869-6411).

PSTN modem

PSTN network.

Page 87: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Communications

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 79

SC200 Setup

Not all modems are suitable. If your modem does not operate correctly check the modem setup string. Contact your Eaton dc product supplier or Eaton for further assistance. See Worldwide Support on page 115.

► To enable modem communications

1 Connect to the SC200 with DCTools (see details on page 13).

2 Go to Communications.

3 Click on + to expand Serial. Configure the following settings:

Enable Modem: Enabled

Modem Power Reset: Optional. If this is enabled, then the SC200 will attempt to reset a non-operating modem by turning its power supply off and on using digital output 2.

Modem Set Up String: The string sent to the modem on reset.

The modem AT command should not be included as it is automatically sent. The Auto-Answer Rings parameter is also sent, so it does not need to be included here. For complete details of appropriate commands, consult your modem documentation.

Modem Auto Answer Rings: Number of rings before an incoming call is answered.

Setting this parameter to zero disables incoming calls (the modem can still be used for alarm reporting).

4 If the SC200 is to report alarms to PowerManagerII then click on + to expand PowerManager Callback. Configure the following settings:

Alarm Report: Select the type of event(s) that will initiate the dial-out process.

Report Maximum Retries: Set to the number of times the SC200 is to try to connect with a remote modem, if the first attempt fails.

After this number of retries the SC200 will try the next number in the Dial Out Numbers table.

Dialing will stop if none of the numbers in the Dial Out Number Table connect.

Report Retry Interval: Set to the required interval between retries.

Dial Out Number(s): Type the telephone number(s) to be called.

Consult the modem documentation for appropriate dial modifiers.

DCTools or PowerManagerII Communications Setup

► To connect to the SC200 with DCTools or PowerManagerII:

1 If not already installed, install the PC modem (hardware and software) according to the manufacturer's instructions.

2 Install DCTools/PowerManagerII on the PC/laptop.

3 Double-click the DCTools/PowerManagerII icon to open the Connection Manager window.

4 Go to Connection > New to open a new connection dialog box.

Page 88: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

80 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

5 Enter:

Connection Name: <as required>

Comms Enabled: True

Protocol: S3P

Connect Using: Select the COM port used by the modem (if external) or the modem name.

S3P Address: 0 (0 = Broadcast, 1-65279 = individual address)

Phone Number: The number of the PSTN line used by the modem.

Modem Logon: Clear if a logon script is not required for the modem.

Select if a logon script is required. Click Logon Script to define.

For more details, see DCTools/PowerManagerII online help (press F1).

6 Press OK. DCTools/PowerManagerII will now connect to the SC200.

7 See System Operation on page 19 for details of the SC200 control and monitoring functions available via DCTools.

For help using DCTools press F1.

8 If required, access to the SC200 via DCTools or PowerManagerII can be password controlled. See Write Access Password on page 84.

GSM Modem Communications

Connections

The PC modem may be external to the PC (as shown) or internal.

SC200 system controller

PC/laptop with PowerManagerII and/or DCTools.

RS232 modem cable (straight-thru). If access to XS1 is restricted use a DB9 ribbon cable extension (Farnell part number 869-6411).

GSM modem

Modem

Optional:

SMS text capable GSM cell phone or SMS-Email Gateway (if available)

SMS text message "P" or "p"

Power status text messages

Alarm text messages

Page 89: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Communications

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 81

SC200 Setup

Not all modems are suitable. If your modem does not operate correctly check the modem setup string. Contact your Eaton dc product supplier or Eaton for further assistance. See Worldwide Support on page 115.

► To enable modem communications

1 Connect to the SC200 with DCTools (see details on page 13).

2 Go to Communications.

3 Click on + to expand Serial. Configure the following settings:

Enable Modem: Enabled

Modem Power Reset: Optional. If this is enabled, then the SC200 will attempt to reset a non-operating modem by turning its power supply off and on using digital output 2.

Modem Set Up String: The string sent to the modem on reset.

The modem AT command should not be included as it is automatically sent. The Auto-Answer Rings parameter is also sent, so it does not need to be included here. For complete details of appropriate commands, consult your modem documentation.

Modem Auto Answer Rings: Number of rings before an incoming call is answered.

Setting this parameter to zero disables incoming calls (the modem can still be used for alarm reporting).

4 If the SC200 is to report alarms to PowerManagerII then click on + to expand PowerManager Callback. Configure the following settings:

Alarm Report: Select the type of event(s) that will initiate the dial-out process.

Report Maximum Retries: Set to the number of times the SC200 is to try to connect with a remote modem, if the first attempt fails.

After this number of retries the SC200 will try the next number in the Dial Out Numbers table.

Dialing will stop if none of the numbers in the Dial Out Number Table connect.

Report Retry Interval: Set to the required interval between retries.

Dial Out Number(s): Type the telephone number(s) to be called.

Consult the modem documentation for appropriate dial modifiers.

DCTools or PowerManagerII Communications Setup

► To connect to the SC200 with DCTools or PowerManagerII:

1 If not already installed, install the PC modem (hardware and software) according to the manufacturer's instructions.

2 Install DCTools/PowerManagerII on the PC/laptop.

3 Double-click the DCTools/PowerManagerII icon to open the Connection Manager window.

4 Go to Connection > New to open a new connection dialog box.

Page 90: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

82 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

5 Enter:

Connection Name: <as required>

Comms Enabled: True

Protocol: S3P

Connect Using: Select the COM port used by the modem (if external) or the modem name.

S3P Address: 0 (0 = Broadcast, 1-65279 = individual address)

Phone Number: The number of the PSTN line used by the modem.

Modem Logon: Clear if a logon script is not required for the modem.

Select if a logon script is required. Click Logon Script to define.

For more details, see DCTools/PowerManagerII online help (press F1).

6 Press OK. DCTools/PowerManagerII will now connect to the SC200.

7 See System Operation on page 19 for details of the SC200 control and monitoring functions available via DCTools.

For help using DCTools press F1.

8 If required, access to the SC200 via DCTools or PowerManagerII can be password controlled. See Write Access Password on page 84.

SMS Text Messaging Setup (if required)

For additional information see Application Note AN0112. To receive application notes see Worldwide Support on page 115.

► To enable SMS alarm messages

1 Connect to the SC200 with DCTools/Web.

2 Go to Configuration > Communications > Serial.

3 Click on to expand SMS Notifications.

4 For each cellphone to receive SMS alarm messages set the Phone Number and other details as required.

5 Type the required Prefix string if alarm messages are to be sent to an email address.

This requires a GSM-Email Gateway connected to the GSM network. Contact the GSM network operator for details of the Prefix string required at the beginning of the SMS message.

► To check the dc power system status using SMS

1 From any cellphone write a SMS (text) message starting with "P" or "p" (any following characters are ignored).

2 Send the message to the SC200 GSM modem telephone number.

The SC200 will reply with a dc power system status message. This will include: Number of active alarms, bus voltage, load current, ac voltage, battery current, battery temperature, battery time remaining (if available).

Page 91: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Communications

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 83

Serial Server

The SC200's Serial Server function makes the SC200's RS232 port available to any software via Ethernet. For example, use Serial Server to connect DCTools to a CellSure Battery Controller (CBC) connected to the SC200.

For information refer to the CellSure Installation Guide (see Related Information on page i).

► SC200 Setup

1 Configure the SC200 for Ethernet communications. See details on page 72.

2 Either:

On the SC200 keypad go to Settings > Setup > Serial Server. Select Enabled. Or:

Use DCTools/Web to go to Configuration > Communications > Remote Access Protocols > Serial Server.

Set Access to Enabled.

DCTools or PowerManagerII Setup

Use similar settings for other software.

1 Install DCTools/PowerManagerII on the PC/laptop.

2 Double-click the DCTools/PowerManagerII icon to open the connection manager.

3 Go to Connection > New to open a new connection dialog box.

4 Enter:

Connection Name: <as required>

Comms Enabled: True

Protocol: S3P

Connect Using: Local Network

S3P Address: 0 (0 = Broadcast, 1-65279 = individual address)

Server IP Address: The IP Address of the SC200. Allocated by network administrator.

Server Port: 15000

Telnet Cleared

5 Press OK. DCTools/PowerManagerII will now connect to the device connected to the SC200's RS232 port.

Communications Security

SC200 settings cannot be changed if:

All communications are disabled (see S3P Access on page 84 and HTTP/HTTPS Access on page 85), and

Keypad access (see details on page 10) is Read Only, or PIN Protected and the keypad access PIN is lost.

In this situation the SC200 will continue to function, but no configuration changes can be made. Contact your Eaton dc product supplier or Eaton for advice (see Worldwide Support on page 115).

Page 92: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

84 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Serial Communications (USB/RS232/Ethernet) Security

S3P Access

S3P is the serial communications protocol used by the SC200 to communicate with DCTools or PowerManagerII via the USB, RS232 or Ethernet port.

S3P Protocol is not used by the web server.

► To Enable/Disable S3P access

On the SC200 keypad go to Settings > Setup > S3P. Select Enabled or Disabled.

Or:

1 Connect to the SC200 with a web browser (see details on page 72).

2 Go to Configuration > Communications > Remote Access Protocols > S3P.

3 Set Access to Enabled or Disabled.

Write Access Password

The Write Access Password prevents unauthorized changes to the SC200 configuration (using DCTools or PowerManagerII).

When a Write Access Password is set serial communications access to the SC200 (using DCTools or PowerManagerII) is read only. The password must be entered before any setting can be changed.

If a Write Access Password is lost, clear it from the SC200 keypad and type a new password in DCTools, or change it via the Web.

► To set a Write Access Password

1 Connect to the SC200 with DCTools/Web (see details on page 72).

2 Go to Configuration > Communications > Remote Access Protocols > S3P

3 Type a password into the Write Access Password field.

Passwords are case sensitive, maximum 32 characters.

4 Click the Apply Changes button.

► To clear or change a Write Access Password

1 Connect to the SC200 with DCTools/Web (see details on page 72).

2 Go to Configuration > Communications > Remote Access Protocols > S3P

3 Type a new password into the Write Access Password field or leave the field blank for no password control.

4 Click the Apply Changes button.

5 DCTools only: Type the old password.

► To clear a Write Access Password from the SC200

1 Use SC200 keypad to go to Settings > Setup > Clear Write Access Password

2 Press Enter.

The password is now permanently cleared. If required, reset the password with DCTools/Web.

Page 93: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Communications

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 85

Web Access Security

Server Access

Access to the SC200 web server can be disabled or set for secure access using Secure Sockets Layer (SSL) protocol.

SSL is a protocol for transmitting encrypted data over the Internet. URLs that require an SSL connection start with https: instead of http:. If the network is insecure, Eaton recommends that you disable HTTP Access.

► To change access to the web server

Set the following parameters as required.

Parameter Description Where to find:

HTTP Access Enable to allow un-encrypted access to the SC200 web server.

Disable to prevent un-encrypted access to the SC200 web server.

SC200: Settings > Setup

DCTools/Web: Communications > HTTP (Web)

HTTPS Access Enable to allow encrypted access to the SC200 web server.

HTTPS access will be slower than HTTP because of the encryption process.

Disable to prevent encrypted access to the SC200 web server.

Page 94: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

86 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

User Setup

► To setup specific users and control their access levels

For each user, set the following parameters as required.

If there are no active users then web access is disabled. Use DCTools to set up an active user.

Parameter Description Where to find:

User Name This is not used in the login process (except for "Default User"). It is displayed at the top-right of the Web view screen.

DCTools/Web: Communications > HTTP (Web)

Logon ID* The logon name of the user.

Password* The password of the user.

Lost passwords cannot be recovered. If a password is lost then set a new password.

Read Allows the user to view configuration settings only.

Write Allows the user to change configuration settings.

Backup Allows the user to download configuration or snapshot files.

Restore Allows the user to upload configuration or snapshot files.

Execute Commands

Allows the user to stop and start control processes.

Upgrade Firmware Allows the user to upgrade firmware.

Edit User List Allows the user to edit the user list and change user access settings.

*Leave both fields blank to allow Default User (anonymous) log on.

CSP

These are parameters for specific protocols. Contact Eaton for further details.

If these protocols are not used then leave the parameters at their default values.

Page 95: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Chapter 5

Maintenance

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 87

C h a p t e r 5 Maintenance

Overview

The dc power system contains hazardous voltages and hazardous energy levels. Before

undertaking any maintenance task refer to the Warnings in the dc power system installation guide.

If a maintenance task must be performed on a "live" system then take all necessary precautions to avoid short-circuits or disconnection of the load equipment, and follow any "live-working" instructions applicable to the site.

Only perform the maintenance tasks described in the Maintenance chapter. All other tasks are classified as Servicing. Servicing must only be performed according to specific instructions and only by personnel authorized by Eaton. This includes disassembly and/or servicing of any modules.

For further information on Servicing contact your local Eaton dc product supplier, or refer to the contact details on page 115.

Topic Page

Troubleshooting 88

Replacing the System Controller or I/O Board 92

Page 96: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

88 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Troubleshooting

Use the table to troubleshoot minor installation and operational problems. For additional assistance see contact details on page 115. Return items for replacement or repair with a completed Equipment Incident Report on page 113.

Problem Possible Cause Required Action

SC200 displays a dc power system alarm message.

See Alarm Descriptions on page 97.

SC200 LCD is blank and green Power On LED is off.

RXP/power cable is disconnected from the SC200.

Connect cable from connector YS11 to the dc power system voltage feed module (see Connections on page 3). Wait for start-up to complete.

The ac supply is off and the batteries are not connected because the Low Voltage Disconnect (LVD) has disconnected.

None. The power system including the SC200 will return to normal operation when the ac supply is within its specified voltage range.

Faulty Voltage Feed Module (VFM) or faulty SC200.

Replace faulty unit.

SC200 LCD is blank and green Power On LED is on.

SC200 is in start-up mode Wait for start-up to complete. See Starting the SC200 on page 6.

Faulty SC200 Replace faulty SC200.

SC200 Red LED or Yellow LED is on.

An alarm is active. Check the type of alarm on the LCD or with DCTools/Web or PowerManagerII. See Alarm Descriptions on page 97.

Unable to change settings from SC200 keypad.

Keypad access is set to Read Only or PIN Protected.

See Keypad Access Security on page 10.

Rectifier does not shutdown when LBRS is enabled.

Load Based Rectifier Shutdown is not available with APR48-3G, EPR48-3G, APR24-3G and CR48-3G rectifiers.

See Load Based Rectifier Shutdown on page 31.

Monitor OK relay (RLY6) is de-energized.

An active alarm, digital input or analog input is mapped to this relay.

Check relay mapping. See Digital Outputs on page 67.

Problem with power or communications to I/O board.

Check all connections (see Connections on page 3).

SC200 or I/O board software corrupt or hardware fault.

Replace faulty unit.

Incorrect battery or load current readings.

Bus voltage sense polarity is incorrect.

Check the bus voltage sense polarity and correct if necessary.

Incorrectly configured shunt inputs.

Check shunt mapping and gain is correct.

Current is within the Battery State Threshold. See details on page 50.

None, normal operation.

Page 97: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Maintenance

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 89

Problem Possible Cause Required Action

SC200 or DCTools/Web displays ??? or N/A

Failed, disconnected or unconfigured sensor.

Replace, connect or configure sensor.

Faulty or disconnected voltage feed module.

Replace or connect voltage feed module.

Incorrect I/O board mapping. Check I/O board mapping. See details on page 109.

DCTools connection problem (Target Failed to Respond error)

Connection problem Refer to following communications problems.

Modem/RS232 communications problem.

Incorrect, disconnected or faulty cable.

Check an RS232 straight-thru cable is plugged into XS1 and the modem.

Replace faulty cable.

Access to RS232 connector XS1 is restricted.

Use a DB9 ribbon cable extension (Farnell part number 869-6411).

Incorrect communications settings.

See PSTN Modem Communications on page 78 or GSM Modem Communications on page 80.

Incorrect modem setup string. Refer to the AT command section in the modem's manual.

Modem not powered or other modem problem.

Refer to the modem's manual.

Incompatible modem. Contact your Eaton dc product supplier or Eaton for advice. See Worldwide Support on page 115.

Password required to change settings.

See Write Access Password on page 84.

Serial communications are disabled

S3P Access is disabled. Set S3P Access to Enabled. See details in the System Controller Operation Handbook.

Ethernet communications problem

Incorrect, disconnected or faulty cable.

Check a network patch cable is connected from XS31 to a live network outlet.

Replace faulty cable.

Ethernet link is not active. On the Ethernet connector (XS31) check:

Yellow LED is continuously lit to show link is active.

Green LED flashes to show traffic is reaching the SC200.

See the diagrams on page 2 for position of the Ethernet connector.

Incorrect communications settings.

See Ethernet Communications on page 72.

SC200 serial communications are disabled.

Check S3P Access is enabled. See details on page 84.

Password required to change settings (using DCTools or PowerManagerII).

See Write Access Password on page 84.

Page 98: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

90 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Problem Possible Cause Required Action

Web communications problem

Ethernet communications problem.

See previous entry.

Cannot connect to web server. Check IP address and other settings in SC200 are correct. Check correct IP address is used in web browser address bar. See Ethernet Communications on page 72.

Check HTTP Access or HTTPS Access is enabled. See Web Access Security on page 85.

Cannot log on to web server. Incorrect Logon ID or Password, or no active users setup.

Use DCTools to set up an active user. See Web Access Security on page 85.

Web communications lost (Comms Lost error message).

Check that the SC200 is operating.

Check the Ethernet communications connections. See previous entry.

Check web browser type and version. See Compatible Software on page 4.

Lost Logon ID and/or Password.

Use DCTools to set up a new Logon ID and/or Password. See Web Access Security on page 85.

Default User log on is not available.

Default User is not setup or not active.

Use DCTools to set up a Default User. See Web Access Security on page 85.

A user cannot change settings, Backup or Restore, Execute Commands, Upgrade Firmware, or Edit User List.

Check the user's access levels. See Web Access Security on page 85.

USB communications problem

Incorrect, disconnected or faulty cable.

Check a USB A/B cable is plugged into the USB port and a PC USB port.

Replace faulty cable.

SC200 serial communications are disabled.

Check S3P Access is enabled. See details on page 84.

DCTools not installed on PC or wrong version.

Install latest version of DCTools. Download from www.powerquality.eaton.com/downloads.

Password required to change settings.

See Write Access Password on page 84.

Page 99: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Maintenance

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 91

Problem Possible Cause Required Action

SC200 time/date is incorrect Time/date is different on SC200 compared to DCTools/Web.

None. Time shown on SC200 is UTC. Time on PC running DCTools/Web is local time.

Time needs to be set. See SC200 Internal Clock on page 14.

SC200 time can be set, but is incorrect when SC200 restarts.

Internal battery is dead. Return SC200 for service. (If removed, the battery must be disposed of according to the manufacturer's instructions.)

String Fail Alarm The Battery Mid-point Monitoring system has detected a voltage imbalance in one of the battery strings.

See Battery Mid-point Monitoring in the dc power system installation guide.

A Battery Mid-point Monitoring sense wire is disconnected.

Check the sense wires.

I/O board Power/Comms OK LED is off

I/O board is not powered or faulty.

Check connection to YH3 on I/O board. See Connections on page 3.

Replace I/O board if faulty.

I/O board Power/Comms OK LED is flashing.

I/O board is responding to an Identify command from the SC200.

None, this is normal operation. See details on page 62.

LVD Status LED(s) (on I/O board) are on.

LVD contactor is energized. None, this is normal operation.

LVD Status LED(s) are off (I/O board Power On LED is on).

LVD contactor is de-energized. None, this is normal operation.

LVD Status LED(s) flashing. The contactor is in the wrong state (SC200 internal state does not match signal from contactor auxiliary switch).

Check the electrical and mechanical operation of the contactor and auxiliary switch.

Check all wiring and connectors. See Connections on page 3.

LVD Type setting is incorrect. Check LVD Type setting.

LVD contactor(s) not operating.

LVD settings incorrect. Check LVD is enabled and set to correct values. See details on page 37.

Check that the LVD manual control is set to AUTO. See details on page 34.

Check that the contactor is correctly configured and mapped to the I/O board. See details on page 38.

Contactor is disconnected. Check the control and dc power cables are connected. See details on page 3.

Page 100: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

92 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Problem Possible Cause Required Action

System has no dc output (rectifiers are on).

Load fuse or disconnect device open.

Check for open fuse or disconnect device.

LVD contactor has disconnected the load.

Use DCTools/Web to check LVD is enabled and set to correct values. (LVD status LED on the I/O board is on when contactor is energized.)

Check that the I/O board is connected (Power LED is on).

Check that the LVD control and power cables connections on page 3.

Check the connections from the load bus to the LVD.

System has no battery input Battery disconnect device or fuse open.

Check for open battery disconnect device or fuse.

LVD has disconnected the battery because ac supply is off and the battery is fully discharged.

None. The battery will be automatically reconnected when the ac supply is restored.

LVD contactor is open. Use DCTools/Web to check LVD is enabled and set to correct values. (LVD status LED on the I/O board is on when contactor is energized.)

Check that the I/O board is connected (Power LED is on).

Check that the LVD control and power cables are connected. See Connections on page 3.

Check the connections from the battery bus to the LVD.

Replacing the System Controller or I/O Board

The SC200 system controller or the I/O board can be replaced without switching off the dc power system and disconnecting the equipment it powers.

The specific procedures depend on the system configuration. Refer to the dc power system Installation and Operation Guide.

Page 101: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Appendix A

Specifications

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 93

A p p e n d i x A Specifications

SC200 system controller

Communications

USB Version:

Connector:

1.1 (12Mbits/s)

USB B (female)

RS232 Interface:

Connector:

RS232 (DTE)

DB9M

Ethernet Interface:

Connector:

Protocols:

10baseT

RJ45

TCP/IP, SNMP, S3P over IP, http (Web), https (secure Web), SNTP, Modbus-TCP, Serial Server

MAC Address: See details on page 72.

Web browser: Microsoft Internet Explorer 8 (IE6 is compatible but with reduced performance), Mozilla Firefox 3.0.

External modem options Type:

Operation:

PSTN or GSM

Dial in/Dial out on alarm*

* Can operate as a backup for Ethernet communications.

IOBGP-00, -01 I/O Board

The following specifications apply to a single IOBGP-00, -01 I/O board connected to the SC200 system controller.

Digital Outputs/Alarm Relays (IOBGP)

Number of Digital Outputs/Relays 6 (one also used for Monitor OK alarm)*

Contact Arrangement One changeover contact per relay

Contact Rating 0.1A @ 60V dc maximum

Connectors Screwless terminal blocks

Wire Size 0.5 - 2.0mm2 [20 - 14 AWG]

Isolation Relay connections are isolated to 500V dc from all

other circuitry, earth and system common.

* Digital Output 6 is also used as the Monitor Fail alarm relay. It will de-energize if the I/O board loses power or loses communication with the SC200.

Page 102: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

94 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Battery Mid-point Monitoring

Number of Strings Standard:

Maximum: 4 24 (with additional IOBGP-01 I/O boards)

Range –35V to +35V

Resolution <30mV

Accuracy ±0.5% at 25°C [77°F], ±1% over rated temperature

range

Digital Inputs (IOBGP)

Number of Digital Inputs 6

Connectors Screwless terminal blocks

Wire Size 0.5 - 2.0mm2 [20 - 14 AWG]

Input Types Voltage-free switch or relay contacts only

Input Range Live Bus to Live Bus + 5V

Input Common Same bus as used for current shunts (Live bus is

standard)

Input Protection Protected against damage from short circuit to live

or common bus

Temperature Sense Inputs (IOBGP)

Number of Temperature Sense Inputs 2

One only connected as standard. Second input available (requires additional temperature sensor).

Range 2.53V to 3.43V (-20 to +70°C [-4 to +158°F])

Resolution < 0.01V (< 1°C [1.8°F])

Accuracy ±1°C [1.8°F] at 25°C [77°F], ±2°C [3.6°F] over rated

temperature range

Maximum Cable Length 20m (65 feet)

Connector RJ45

Current Sense Inputs (IOBGP)

Number of Current Sense Inputs 3

Range –50 to +50mV

Resolution <50µV

Accuracy ±0.5% at 25°C [77°F], ±1% over rated temperature

range

Connector RJ45

Page 103: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Specifications

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 95

Bus Voltage Sense Input (IOBGP)

Number of Bus Voltage Sense Inputs 1

Range –60V to +60V

Resolution 30mV

Accuracy ±0.5% at 25°C [77°F], ±1% over rated temperature

range

Connector MTA156 (2-way)

Low Voltage Disconnect (IOBGP)

Number of contactor connections 2 per IOBGP I/O board

Number of LVD channels 16

Contactor Type Normally Open (NO) with auxiliary contacts only.

Contactor Coil Voltage (nominal) 12V, 24V or 48V

Maximum Hold-in Current 1.2A (per contactor)

Connector MTA156 (4-way)

Page 104: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

96 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Page 105: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Appendix B

Alarm Descriptions

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 97

A p p e n d i x B Alarm Descriptions

AC Fail All rectifiers report ac supply failure or a digital input with Function set to "AC Fail" is active.

ACD Fan Fail The ac distribution cooling system or fan controller has failed (indicated by an active digital input with Function set to "ACD Fan Fail".

Auxiliary Sensor Fail An I/O board has an analog input with Function User Defined and the input is either out of range or unavailable.

Battery Current Limit Battery Current Limit (BCL) is active. See Battery Current Limit on page 21.

Battery Fuse Fail A battery fuse has blown or a battery disconnect device has operated (indicated by an active digital input with Function "Battery Fuse Fail").

Battery Temperature High

The analog input with Function set to "Battery Temperature" has a value above the Battery Temperature High Threshold.

This alarm indicates either thermal runaway of the batteries or that the batteries are operating at a temperature that may cause reduced battery life.

Battery Temperature Low

The analog input with Function set to "Battery Temperature" has a value below the Battery Temperature Low Threshold.

This alarm indicates a risk to the standby power system battery as lower temperatures reduce the battery capacity.

Battery Test The Battery Test control process is active. See Battery Test on page 22.

Battery Test Fail The batteries do not have the required capacity or are not fully charged. See Battery Test on page 22.

Cabinet Fan Fail A cabinet fan has failed (indicated by an active digital input with Function set to "Cabinet Fan Fail").

Configuration Error One of the following is true:

The Rectifier Current Limit is set higher than the Maximum Current Limit of all the registered rectifiers. See details on page 29.

The OVSD Set Point is out of the range of any registered rectifiers. See details on page 29.

More than one digital output are mapped to the same relay on an I/O board or SiteSure-3G Module. See details on page 67.

An LVD contactor is in Conflict state. See details on page 38.

Smart Alarm Based Disconnect is Enabled, but the corresponding Smart Alarm is Disabled. See details on page 38.

A Smart Alarm source has an invalid Source Triggered setting.

DO Manual A digital output is set to manual control (control state is set to Active or Inactive). See Digital Outputs on page 67.

Equalize The Equalize control process is active. See Equalize on page 24.

Fast Charge The Fast Charge control process is active. See Fast Charge on page 25.

Generator Enable The Generator Control process is active and Ah Discharged has exceeded the Ampere-Hour Threshold or the bus voltage is below the Voltage Threshold. See Generator Control on page 60.

Generator Fail Generator Enable is active but the SC200 has not detected that the ac supply is present (rectifiers have not turned on) after the Generator Fail Alarm Recognition Period.

High Float The bus voltage is above its normal range (set by the High Float Threshold).

Page 106: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

98 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

High Load The bus voltage is higher than the safe range for the load and/or battery (set by the High Load Threshold).

In Discharge Battery Charge State is Discharge (see details on page 49).

Load Fuse Fail A load fuse has blown or a load disconnect device has operated (indicated by an active digital input with Function "Load Fuse Fail").

Low Float The bus voltage is below its normal range (set by the Low Float Threshold).

Low Load The bus voltage is lower than the safe range for the load and/or battery (set by the Low Load Threshold).

LVD Characterization Error An LVD contactor must be characterized. See Low Voltage Disconnect on page 34.

LVD Disconnected An LVD contactor has disconnected the battery or load. See Low Voltage Disconnect on page 34.

LVD Fail An LVD contactor is faulty or the control cable from the I/O board is disconnected. See Low Voltage Disconnect on page 34.

LVD Manual An LVD is set to MANUAL CONNECT or MANUAL DISCONNECT. See Low Voltage Disconnect on page 34.

Missing Hardware The SC200 has lost communication with a mapped I/O board or SiteSure-3G module. Or, an input or output is mapped to an invalid I/O board or SiteSure-3G module. See I/O Board Mapping on page 109.

MOV Fail One or more MOV cartridges have failed and must be replaced (indicated by an active digital input with Function set to "MOV Fail").

Multiple Rectifier Comms Lost

More than one rectifier has lost communications. See also Rectifier Comms Lost on page 98.

Multiple Rectifier Fail Multiple rectifiers are faulty or their ac supply has failed without causing partial or total ac supply failure.

Partial AC Fail A digital input with Function set to "Phase Fail" is active, or more than 20% of single-phase rectifiers are reporting ac supply failure, or all 3-phase rectifiers are reporting loss of the same phase.

Rectifier Comms Lost Normally this alarm indicates that a rectifier has been removed during routine maintenance. However, faulty rectifier communications or losing the rectifier communications bus can also trigger this alarm. If removing multiple rectifiers triggers this alarm, reset it from the keypad before it triggers an external alarm.

Rectifier Current Limit Rectifier(s) in current limit.

Rectifier Fail A rectifier is faulty or its ac supply has failed without causing partial or total ac supply failure.

Rectifier No Load The total rectifier current is less than 2% of the maximum system output current or is less than 2A.

Rectifier Over Temperature

Rectifier(s) operating in temperature turndown mode, because of high ambient temperature or low ac supply voltage.

Sensor Fail The current, temperature or voltage sensing system is faulty, or the I/O board mapping is incorrect.

Standby Mode The SC200 is on but inactive. Another system controller controls the dc power system. If the other system controller fails or is disconnected then the SC200 in Standby Mode will become active (after a short delay).

String Fail There is a voltage imbalance in one of the battery strings. See Battery Mid-point Monitoring on page 50.

Page 107: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Alarm Descriptions

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 99

System Overload The power system is operating close to its maximum capacity and more rectifiers are needed. The System Overload threshold is configurable. See System Overload Alarm on page 42.

Unknown Hardware The SC200 has detected an unknown type of device on the RXP bus. Contact your Eaton DC product supplier for advice.

Unmapped IOB Found An I/O board or SiteSure-3G module is connected to the SC200, but its serial number is not in the I/O Board to Serial Number Mapping table. See I/O Board Mapping on page 109.

Wrong Battery Polarity An analog input with Function set to "Reverse Battery Detect" has a value above the Bus Voltage.

This alarm indicates the battery is connected with wrong polarity. See Reverse Battery Detection on page 58.

Page 108: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

100 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Page 109: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Appendix C

Connector Pin-outs

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 101

A p p e n d i x C Connector Pin-outs

System Controller Connector Pin-outs

Connector Type Purpose Pin Description

XS1 DB9M RS232 Serial Interface 1 -

2 RD (Receive Data)

3 TD (Transmit Data)

4 DTR (Data Terminal Ready)

5 Common (Ground)

6 -

7 RTS (Request to Send)

8 -

9 -

XS31

RJ45 Ethernet Interface 1 Rx

2 Rx

3 Tx

4 -

5 -

6 Tx

7 -

8 -

YS11 RJ45 RXP System Communications

1 +24/48V (System bus voltage)

2 +24/48V (System bus voltage)

3 -

4 RS485-A

5 RS485-B

6 -

7 0V

8 0V

USB

USB B USB Serial Interface 1 VCC (+5 V dc)

2 Data -

3 Data +

4 Ground

Page 110: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

102 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

8

1

1 8

RS232 D9M and RJ45 connector pin-outs RJ45 plug pin-outs

Page 111: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Connector Pin-outs

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 103

I/O Board (IOBGP-00, -01) Connector Pin-outs

See input and output specifications on page 93.

Connector Type Purpose Pin Description

XH4 MTA 156

LVD 1 Interface 1 Coil -

2 Coil +

3 LVD 1 auxiliary switch

4 Auxiliary switch common

XH5 MTA 156

LVD 2 Interface 1 Coil -

2 Coil +

3 LVD 2 auxiliary switch

4 Auxiliary switch common

XH6 RJ45 Current Sense Inputs 1 Current Input 1 Common

2 Current Input 1

3 +12V out

4 Current Input 2 Common

5 Current Input 2

6 0V out

7 Current Input 3 Common

8 Current Input 3

XH7 RJ45 Temperature Sense Inputs 1 -

2 -

3 -

4 Temp Sense 1+

5 Temp Sense 1-

6 -

7 Temp Sense 2+

8 Temp Sense 2-

XH8 MTA 156

LVD Power 1 Bus live

2 Common

XH9 MTA 156

Bus Voltage Sense Input 1 Controller reference (Live)

2 Controller sense (Com)

XH12A MTA 156

Battery Mid-point Monitoring sense inputs

1 String 1 Mid-point

2 String 2 Mid-point

3 String 3 Mid-point

4 String 4 Mid-point

XH15A Digital inputs D1-D3 1 D1 input

2 0V

Page 112: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

104 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Connector Type Purpose Pin Description

3 D2 input

4 0V

5 D3 input

6 0V

XH15B Digital inputs D4-D6 1 D4 input

2 0V

3 D5 input

4 0V

5 D6 input

6 0V

XH16/XH17 Digital relay outputs 1-2 1 Relay 1 normally closed (NC)

2 Relay 1 normally open (NO)

3 Relay 1 Common (COM)

4 Relay 2 normally closed (NC)

5 Relay 2 normally open (NO)

6 Relay 2 Common (COM)

XH18/XH19 Digital relay outputs 3-4 1 Relay 3 normally closed (NC)

2 Relay 3 normally open (NO)

3 Relay 3 Common (COM)

4 Relay 4 normally closed (NC)

5 Relay 4 normally open (NO)

6 Relay 4 Common (COM)

XH20/XH21 Digital relay outputs 5-6* 1 Relay 5 normally closed (NC)

2 Relay 5 normally open (NO)

3 Relay 5 Common (COM)

4 Relay 6 normally closed (NC)

5 Relay 6 normally open (NO)

6 Relay 6 Common (COM)

YH3 RJ45 DC power system digital inputs

1 Load Fuse Fail

2 Battery Fuse Fail

3 +12V out

4 AC Distribution Fan Fail

5 AC Distribution MOV Fail

6 0V out (system live - protected)

7 -

8 System common - protected

Page 113: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Connector Pin-outs

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 105

Connector Type Purpose Pin Description

YH11 RJ45 RXP System Communications

1 +24/48V (System bus voltage)

2 +24/48V (System bus voltage)

3 -

4 RS485-A

5 RS485-B

6 -

7 0V

8 0V

* Digital Output 6 is also used as the Monitor Fail alarm relay. It will de-energize if the I/O board loses power or loses communication with the SC200.

8

1

1 8

RJ45 connector pin-outs RJ45 plug pin-outs

Page 114: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

106 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Page 115: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Appendix D

System Event Types

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 107

A p p e n d i x D System Event Types

Event Type Description Additional Event Information

AI High Activation An analog input high threshold alarm has become active.

Analog input number (DCTools) or name (Web).

AI High Deactivation An analog input high threshold alarm has become inactive.

Analog input number (DCTools) or name (Web).

AI Low Activation An analog input low threshold alarm has become active.

Analog input number (DCTools) or name (Web).

AI Low Deactivation An analog input low threshold alarm has become inactive.

Analog input number (DCTools) or name (Web).

Alarm Activation An alarm has become active. Alarm number (DCTools) or name (Web).

Alarm Deactivation An alarm has become inactive. Alarm number (DCTools) or name (Web).

Clock Change From

The clock was changed to this new Event Log Time from the old Event Information time. When the clock is changed, two event log entries are recorded. The first is the Clock Change To event and the second is the Clock Change From event.

Clock Change To

The clock was changed to the new Event Information time from the old Event Log Time. When the clock is changed, two event log entries are recorded. The first is the Clock Change To event and the second is the Clock Change From event.

Configuration Change The configuration database was changed.

DI Activation A digital input alarm has become active.

Digital input number (DCTools) or name (Web).

DI Deactivation A digital input alarm has become inactive.

Digital input number (DCTools) or name (Web).

DO Control Activation A digital output has been manually activated.

Digital output number (DCTools) or name (Web).

DO Control Deactivation

A digital output has been manually deactivated.

Digital output number (DCTools) or name (Web).

Logs Cleared The event and data logs have been cleared.

Rectifier Restart A rectifier was started manually.

Page 116: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

108 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Event Type Description Additional Event Information

This excludes events where a rectifier starts due to Load-Based Rectifier Shutdown or after the removal of a fault condition.

Rectifier Shutdown A rectifier was shut down manually. This excludes events where a rectifier shuts down due to Load-Based Rectifier Shutdown or a fault condition.

Start Up Records when the controller started running.

Smart Alarm Activation A smart alarm has become active. Smart Alarm number (DCTools) or name (Web).

Smart Alarm Deactivation

A smart alarm has become inactive.

Smart Alarm number (DCTools) or name (Web).

Page 117: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Appendix E

SC200 Mappings

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 109

A p p e n d i x E SC200 Mappings

The SC200 uses mappings to allow it to associate internal functions, alarms and physical I/O devices.

A default mapping is set at the factory before delivery. Usually this default mapping will not need to be changed.

I/O Board Mapping

The serial numbers of an I/O board and SiteSure-3G modules, and the physical connectors on the board/modules are mapped to logical numbers in the SC200. This allows the physical inputs and outputs (including LVD contactors) to be recognized by the SC200.

I/O Board serial number mapping

Each I/O board serial number must be mapped to a logical IOB Number.

Usually, I/O board serial number mappings only need to be changed if:

The I/O board is changed or added. See details on page 92.

The SC200 is changed and/or a new configuration file is loaded into the SC200. See details on page 92.

This mapping is not included in configuration files and must be set if an SC200 is changed or loaded with a new configuration file. Input/output, sensors and most voltage control processes are only available if this mapping is set.

► To map I/O boards

Either:

Use the SC200 keypad to go to: Settings > IOBs. The serial numbers of registered input/output boards are displayed.

Select an unmapped Input/Output board (identified as New). Press Enter. Identity information is displayed and the I/O board LED will flash.

Press Map and select an unused IOB Number (or one marked as Missing, if replacing an I/O board). Press Enter.

Or:

In DCTools/Web go to: Configuration > RXP

Copy the I/O board serial number(s) from the RXP Devices table to the I/O Board to Serial Number Mapping table to map an IOB Number to each I/O board (overwrite an existing serial number if required).

If multiple SiteSure-3G modules are installed use the I/O board Identify function to physically identify each board. See details on page 62.

Page 118: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

110 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

I/O connector mapping

Each I/O connector (analog input, digital input and digital output) on an I/O board must be mapped to a logical IOB Number and IOB AI, IOB DI or IOB DO Number.

► To map I/O connectors

See Analog Inputs on page 63, Digital Inputs on page 66 and Digital Outputs on page 67.

The following tables show the default connector mappings:

Analog Input

Name Function* IOB Number

IOB AI Number

Connector

1 IOBGP 1 Bus Voltage Bus Voltage 1 1 XH9

2 IOBGP 1 Mid-point 1 Battery Mid-point 1 2 XH12A

3 IOBGP 1 Mid-point 2 Battery Mid-point 1 3 XH12A

4 IOBGP 1 Mid-point 3 Battery Mid-point 1 4 XH12A

5 IOBGP 1 Mid-point 4 Battery Mid-point 1 5 XH12A

6 Battery Current Battery Current 1 6 XH6

7 Current 2 User Defined 1 7 XH6

8 Current 3 User Defined 1 8 XH6

9 Battery Temperature Battery Temperature

1 9 XH7

10 Temperature 2 User Defined 1 10 XH7

Digital Input

Name Function* IOB Number

IOB DI Number

Connector

1 Digital Input 1 User Defined 1 1 XH15A

2 Digital Input 2 User Defined 1 2 XH15A

3 Digital Input 3 User Defined 1 3 XH15A

4 Digital Input 4 User Defined 1 4 XH15B

5 Digital Input 5 User Defined 1 5 XH15B

6 Digital Input 6 User Defined 1 6 XH15B

7 Load Fuse Fail Load Fuse Fail 1 7 YH3

8 Battery Fuse Fail Battery Fuse Fail 1 8 YH3

9 ACD Fan Fail ACD Fan Fail 1 9 YH3

10 MOV Fail MOV Fail 1 10 YH3

* Function is an internal analog or digital input value used by the SC200 for voltage control processes, and/or to generate System States, and/or to generate system alarms.

Page 119: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Mappings

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 111

Digital Output

Name IOB Number

IOB DO Number

Connector

1 Summary Non Urgent 1 1 XH16

2 Low/High Load 1 2 XH17

3 Rectifier Fail 1 3 XH18

4 AC Fail 1 4 XH19

5 Load/Batt Disconnect 1 5 XH20

6 IOBGP 1 RY6/Mon OK 1 6 XH21

Digital outputs are activated by mappings from alarms (see Digital Output (Relay) Mapping on page 111) or by a test (see Digital Outputs on page 67).

LVD connector mappings

For details refer to LVD Configuration on page 37.

Digital Output (Relay) Activation

Any alarm can activate one or two digital outputs (A and B).

► To map digital outputs

See System Alarms on page 42, Smart Alarms on page 44, Analog Inputs on page 63, Digital Inputs on page 66 and Digital Outputs on page 67.

Page 120: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

112 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Page 121: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 113

Equipment Incident Report

EQUIPMENT INCIDENT REPORT

Please enter as much information as you can. Send the completed form, together with the item for repair to your nearest authorized service agent. NOTE: Only one fault to be recorded per form.

For further information contact your local Eaton dc product supplier or Eaton (see contact details on page 115). Or email: [email protected]

Date: ________________

Customer Information

Company: _______________________________________________________________________

Postal Address: _______________________________________________________________________

_______________________________________________________________________

Return Address: (Not PO Box)

_______________________________________________________________________

_______________________________________________________________________

Telephone: _______________ Fax: _______________ Email: _________________

Contact Name: _______________________________________________________________________

Location of Failure

Product code: ___________ Serial number: __________ Document number: _____________

System type installed in: _________________________ Serial number: _____________

Site name or location: __________________________________________________________

Fault discovered Delivery Unpacking Installation

Initial test Operation after _____ years Other _______________

Failure source Design Manufacturing Documentation

Transportation Installation Handling

______________

Effect on system operation None Minor Major _______________________

INFORMATION (fault details, circumstances, consequences, actions)

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

Internal use only.

Reference No: __________ RMA: __________ NCR: __________ Signature: _________________ Date: _______________

Page 122: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

114 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

INFORMATION continued (fault details, circumstances, consequences, actions)

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

SG/03 ISS06

Page 123: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Worldwide Support

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 115

Worldwide Support

For product information and a complete listing of worldwide sales offices, visit Eaton's website at: www.eaton.com/telecompower or email: [email protected]

For technical support contact either your local Eaton dc product representative, the closest office from the following list, telephone (+64) 3 343-7448, or email [email protected]

Australia: 1300 877 359

Canada: 1-800-461-9166

Central America: +52 55 9000 5252

China: +86-571-8848-0166

+86-571-8848-0366

Europe / Middle East / Africa: +44-1243-810-500

Hong Kong / Korea / Japan: +852-2745-6682

India: +91-11-4223-2325

New Zealand 0800 DC Power (0800 327-693)

Singapore / South East Asia: +65 6825 1668

South America: +54-11-4124-4000

South Pacific: +64-3-343-7448

Taiwan: +886-2-6600-6688 or free call 0800-038-168

United States of America (Toll Free): 1-800-843-9433 - option 2 - option 6

Page 124: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

116 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Page 125: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Index

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 117

Index

?

??? on SC200 Display • 12, 89

A

AC Rectifier Current Limit • 29

AC Supply

AC Fail Alarm • 41, 65, 97

AC Voltage • 28, 63

ACD Fan Fail Alarm • 65, 97, 109

Low AC Threshold • 28

ACD Fan Fail Alarm • 65, 97, 109

Active Voltage Control • 20, 21

Ah Discharged • 26, 49

Alarms • 39

Alarm Configuration • 39, 41

Alarm Descriptions • 97

Alarm Tracking • 42

Analog Input Alarms • 39, 63

Audible Alarm Indication • 12, 40

Digital Input Alarms • 39, 66

LEDs (SC200) • 2, 12, 88

LVD Status LED • 2, 91

Mappings • 109

Monitor OK Alarm • 2, 88

Rectifier Alarms • 97

Rectifier Comms Lost Alarm • 30, 98

Relays • See Digital Outputs (Relays)

SC200 Alarms • 12, 39, 88

Severity • 40

Smart Alarms • 44

Sound • See Audible Alarm Indication

System Alarms • 39, 97

System Overload Alarm • 41, 42, 99

Analog Inputs • 11, 63

Analog Input Alarms • 39, 63

Mappings • 109

Audible Alarm Indication • 12, 40

Auxiliary Sensor Fail Alarm • 97

AVC • See Active Voltage Control

B

Battery • 49

Ah Discharged • 26, 49

Battery Capacity • 49

Battery Charge State • 49

Battery Current • 11, 63, 88, 109

Battery Current Sensor Fail • 49

Battery Fuse Fail Alarm • 65, 97, 109

Battery Fuses • 92

Battery Temperature • 11, 27, 49

Battery Temperature High Alarm • 41, 97

Battery Temperature Low Alarm • 41, 97

Battery Test • 20, 21, 22, 25, 27

Battery Test Alarms • 97

Cells Per String • 27, 49

CellSure • 83

Equalize • 20, 22, 24

Fast Charge • 20, 22, 25

In Discharge Alarm • 98

Mid-Point Monitoring (MPM) • 50, 94

Number of Cells • See Cells Per String

Reverse Polarity • 58, 99

String Fail Alarm • 50, 51, 91, 98

Temperature Compensation • 20, 27

Temperature Sensor • 2, 3, 63, 94, 109

Time Remaining • 54

Battery Circuit Breakers • 92

Battery Fuse Fail Alarm • 65, 97, 109

Battery Current Limit (BCL) • 20, 21, 25

Battery Current Limit Alarm • 97

Engine Run BCL • 21

BCL • See Battery Current Limit (BCL)

Browsers (recommended) • 4

Bus Voltage • 63

Bus Voltage Sense • 2, 21, 109

High Load Alarm • 41, 98

Low Load Alarm • 41, 98

C

Cabinet Fan Fail Alarm • 97

Cells Per String • 27, 49

CellSure • 83

Page 126: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

118 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Characterization of LVD • 34

Circuit Breakers

Battery Circuit Breakers • 92

Battery Fuse Fail Alarm • 65, 97, 109

Load Circuit Breakers • 92

Load Fuse Fail Alarm • 65, 98, 109

Communications • 72, 93

Browsers (recommended) • 4

Communications Options • 72

Connector • 2, 3

CSP • 86

DCTools • 4, 13, 72, 78, 80

Ethernet Communications • 72, 89

GSM Modem Communications • 80, 89

HTTP/HTTPS • 85

Loss of Communications • 83

MAC Address • 72

Modbus • 77

Problems • See Troubleshooting

PSTN Modem Communications • 78, 89

Security • 83

Serial Server • 83

SNMP • 75

USB Communications • 13, 90

Web Access Security • 85, 90

Web Server • 74, 90

Write Access Password • 84, 89

Configuration File • 17, 39

Backup and Restore • 18

Changing a Configuration Setting • 10

Contrast • See Display Settings

Control • See Voltage Control

CSP • 86

Current

Battery Current • 11, 63, 88, 109

Load Current • 11, 63, 88

No Load Alarm • 98

Rectifier Current • 6, 11, 63

Current Limit

Battery Current Limit (BCL) • 20, 21, 25

Rectifier Current Limit • 29

Current Sense • 2, 3, 63, 94, 109

D

Data Logging • 68

Data Log • 69

Event Log • 68

PC Log • 70

System Event Types • 107

DCTools • 4, 13, 72, 78, 80

N/A (in DCTools/Web) • 89

Software Versions • 4

Target Failed to Respond Error • 89

Write Access Password • 84, 89

Digital Inputs • 66, 94, 109

Connectors • 2, 3, 103

Digital Input Alarms • 39, 66

Mappings • 109

System States • 65

Digital Outputs (Relays) • 40, 67, 93

Connectors • 2, 3, 103

Relay Mapping • 41, 66, 67, 111

Remote Control State • 67

Test Digital Outputs • 67

Display Settings • 11

Language • 16

E

Email Alarm Messages • 82

Engine Run BCL • 21

Equalize • 20, 22, 24

Equalize Active Alarm • 97

Ethernet

Connector • 2, 3

Ethernet Communications • 72, 89

MAC Address • 72

Problems • See Troubleshooting

Event Log • 68

System Event Types • 107

F

Fast Charge • 20, 22, 25

Fast Charge Active Alarm • 97

Float Voltage • 20, 28

High Float Alarm • 41, 97

Low Batt Temp Alarm • 41, 98

Function • 65, 66

Fuse

Battery Fuses • 92

Page 127: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Index

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 119

Load Fuses • 92

G

Generator

Generator Control Option • 60

Generator Enable Alarm • 97

Generator Fail Alarm • 41, 60, 97

GSM Modem Communications • 80, 89

H

Heatsink Temperature • 28

High Float Alarm • 41, 97

High Load Alarm • 41, 98

Horizontal/Vertical Setting of Display • See Display Settings

HTTP/HTTPS • 85

I

Identify a Rectifier • 29

Identify an I/O Board • 62

Identity Information • 14

In Discharge Alarm • 98

Input/Output (I/O) Board

Additional I/O • See SiteSure-3G I/O module

Analog Inputs • 11, 63

Connections to other system components • 3

Connector Pin-outs • 103

Description • 2

Digital Inputs • 66, 94, 109

I/O Board Mapping • 109

Identify an I/O Board • 62

LVD Status LED • 2, 91

Power On LED • 2, 91

Repair and Return • 113

Replacing the Input/Output Board • 92

Internal Clock • 14, 91

K

Keypad

Keypad Access Security • 10, 88

L

Language • 16

LCD • 6, 88

Display Settings • 11

Language • 16

LEDs

LEDs (SC200) • 2, 12, 88

LVD Status LED • 2, 91

Power On LED • 2, 91

Troubleshooting • 88

Load Circuit Breakers • 92

Load Fuse Fail Alarm • 65, 98, 109

Load Current • 11, 63, 88

Load Fuse Fail Alarm • 65, 98, 109

Load Fuses • 92

Load Power • 11, 63

Load-Based Rectifier Shutdown • 31

Locate Rectifier • See Identify a Rectifier

Log • See Data Logging

Logon (SC200) • 10

Logon ID (Web) • 85

Low AC Threshold • 28

Low Batt Temp Alarm • 41, 98

Low Load Alarm • 41, 98

Low Voltage Disconnect (LVD) • 34

Characterization of LVD • 34

Connectors • 2, 3, 103

LVD Alarms • 98, See Troubleshooting

LVD Status LED • 2, 91

Mappings • 109

Problems • 91

LVD • See Low Voltage Disconnect (LVD)

M

MAC Address • 72

Main Screen • 6, 11

Main Screen Items • 11

Mains Fail Alarm • See AC Fail Alarm

Mappings • 109

Mid-Point Monitoring (MPM) • 50, 94

String Fail Alarm • 50, 51, 91, 98

Missing Hardware Alarm • 98

Modbus • 77

Modem (PSTN, GSM) • See Communications

Monitor OK Alarm • 2, 88

MOVs

MOV Fail Alarm • 65, 98, 109

MPM • See Mid-Point Monitoring (MPM)

Page 128: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

SC200 Handbook

120 Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011

Multiple Rectifier Comms Lost Alarm • 98

Multiple Rectifier Fail Alarm • 98

N

N/A (in DCTools/Web) • 89

Network Management System (NMS) • See SNMP

No Load Alarm • 98

Number of Cells • See Cells Per String

O

Output Voltage and Current • 20, 28, 63

Over Voltage Shut Down (OVSD) • 29

P

Partial AC Fail Alarm • 98

Password

Web Access Security • 85, 90

Write Access Password • 84, 89

PC Log • 70

PC/Laptop (Connection via USB) • See USB Communications

Polarity

Reverse Polarity • 58, 99

Power

Load Power • 11, 63

System Power • 11, 63

PowerManagerII • 4, 40

Problems • See Troubleshooting

Protection • See Security

PSTN Modem Communications • 78, 89

R

Ramp Up Slope • 29

Rectifiers

AC Rectifier Current Limit • 29

Heatsink Temperature • 28

Identify a Rectifier • 29

Load Power • 11, 63

Load-Based Rectifier Shutdown • 31

Locate Rectifier • See Identify a Rectifier

Output Voltage and Current • 20, 28, 63

Over Voltage Shut Down (OVSD) • 29

Problems • See Troubleshooting

Ramp Up Slope • 29

Rectifier Alarms • 97

Rectifier Comms Lost Alarm • 30, 98

Rectifier Current • 6, 11, 63

Rectifier Current Limit • 29

Registration • 28

Repair and Return • 113

Restart Rectifier(s) • 30

Serial Number • 28, 29

Shutdown • 29, 30, 88

Start Up Delay • 29

System Overload Alarm • 41, 42, 99

System Power • 11, 63

Voltage Control • 20

Relays • See Digital Outputs (Relays)

Monitor OK Alarm • 2, 88

Relay Mapping • 41, 66, 67, 111

Remote Control State • 67

Repair and Return • 113

Restart Rectifier(s) • 30

Reverse Polarity • 58, 99

RS232 • 78

Connector • 2, 3

Modem (PSTN, GSM) • See Communications

Serial Server • 83

S

SC200 system controller

??? on SC200 Display • 12, 89

Alarm Descriptions • 97

Changing a Configuration Setting • 10

Configuration File • 17, 39

Connections to other system components • 3

Connector Pin-outs • 101, 103

Description • 2

Display Settings • 11

Firmware Upgrade • 17

Identity Information • 14

Internal Clock • 14, 91

Keypad • 6, 88

Language • 16

LEDs (SC200) • 2, 12, 88

Main Menu • 8

Main Screen • 6, 11

Mappings • 109

Page 129: SC200 System Controller Operation Handbooknanapowerinc.com/DC Power Manual/50_G_SC200_Handbook_LTR.pdf · SC200 System Controller Operation Handbook Issue: IPN 997-00012-50G Issue

Index

Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.

IPN 997-00012-50G May 2011 121

N/A (in DCTools/Web) • 89

Problems • See Troubleshooting

Repair and Return • 113

Replacing the System Controller • 92

SC200 Alarms • 12, 39, 88

Security • See Keypad Access Security

Startup • 6

Security • 83

Keypad Access Security • 10, 88

Web Access Security • 85, 90

Write Access Password • 84, 89

Sensor Fail Alarm • 98

Auxiliary Sensor Fail Alarm • 97

Serial Server • 83

Servicing • 113, 115

Severity • 40

Shutdown • 29, 30, 88

Load-Based Rectifier Shutdown • 31

Over Voltage Shut Down (OVSD) • 29

Restart Rectifier(s) • 30

SiteSure-3G I/O module • 62

Smart Alarms • 44

SMS Text Messaging • See GSM Modem Communications

SNMP • 75

SNTP • See Internal Clock

Software Versions • 4

Sound • See Audible Alarm Indication

Specifications • 93

Standby Mode • 98

Start Up Delay • 29

String Fail Alarm • 50, 51, 91, 98

System Alarms • 39, 97

System Overload Alarm • 41, 42, 99

System Power • 11, 63

System States • 65

T

Target Failed to Respond Error • 89

Technical Assistance • 115

Temperature

Battery Temperature • 11, 27, 49

Battery Temperature High Alarm • 41, 97

Battery Temperature Low Alarm • 41, 97

Heatsink Temperature • 28

Temperature Compensation • 20, 27

Temperature Sensor • 2, 3, 63, 94, 109

Test Digital Outputs • 67

Text Messaging (SMS) • See GSM Modem Communications

Time • See Internal Clock

Time Remaining • 54

Transient Voltage Protection

MOV Fail Alarm • 65, 98, 109

Translation • 16

Troubleshooting • 88

Repair and Return • 113

Servicing • 113, 115

Technical Assistance • 115

U

Unknown Hardware Alarm • 99

USB

Connector • 2, 3

Problems • See Troubleshooting

USB Cable • 13

USB Communications • 13, 90

V

Vertical/Horizontal Setting of Display • See Display Settings

Voltage (Bus) • 63, See Bus Voltage Sense

Voltage Control • 20

Active Voltage Control • 20, 21

Bus Voltage Sense • 2, 21, 109

Voltage Feed Module • 3

W

Web

Browsers (recommended) • 4

Language • 16

Web Access Security • 85, 90

Web Server • 74, 90

Write Access Password • 84, 89