S3 Lec 6 (Air Distribution) Note
-
Upload
no-suhaila -
Category
Education
-
view
1.097 -
download
2
description
Transcript of S3 Lec 6 (Air Distribution) Note
SUPPLY DEVICES AND ROOM AIR DISTRIBUTION
SUPPLY DEVICES AND ROOM AIR DISTRIBUTION
• Heating, Ventilation and Air Conditioning
• Provides comfort for people
• Allows humans to exist under adverse conditions.
Comfort
• Comfort is primary intent of HVAC systems.
• Productivity• Building Durability• Health
• Mold
Supply Devices and Room Air Distribution
• One way to condition air is to use a fan to move the air over the conditioning space.
• The components that make up the forced-air system are : Blower (fan) Air supply system Filter Balancing damper Return air system Grillers And registers where the circulated air enters the room and returns to
the conditioning equipment
Basic HVAC Equipment
• Fans / Blowers• Furnace / Heating unit• Filters• Compressor• Condensing units• Evaporator (cooling coil)• Control System• Air Distribution System
Types of fans
• The fan or blower as it is sometimes called, can be described as a device that produces airflow or movement.
• The fan provides the pressure difference to force the air into the duct system, through grilles and registers and into a room.• Several different types of fans produce this
movement such as propeller fan, axial-flow fans and centrifugal fans.
THE PROPELLER FAN
• The propeller fan is used in exhaust-fan and condenser-fan applications.
• It will handle large volumes of air at low pressure differentials.
• The propeller fan can be cast iron, aluminum or stamped steel and is set into a housing called a venturi to encourage airflow in a straight line from one side of the fan to the other(Figure above).
• The propeller fan makes more noise than the centrifugal fan so it is normally used where noise is not a factor.
THE CENTRIFUGAL FAN
• The centrifugal fan has characteristics that make it desirable for duct work.
• It builds more pressure from the inlet to the outlet and moves more air against more pressure.
• This fan has a forward curved blade and a cutoff to shear the air spinning around the fan wheel (Figure above).
• The centrifugal fan is very quiet when properly applied.
AXIAL FAN
• The axial-flow fans have blades that force air to move parallel to the shaft about which the blades rotate.
• Axial fans blow air along the axis of the fan, linearly, hence their name. • This type of fan is used in a wide variety of applications, ranging from
small cooling fans for electronics to the giant fans used in wind tunnels• Axial flow fans are applied for air conditioning and industrial process
applications. • Standard axial flow fans have diameters from 300-400 mm or 1800 to
2000 mm and work under pressures up to 800 Pa.
System Types and Common Terms• Packaged Rooftop
Unit
• Split System
• Heat Pump
• Geothermal
• Air to Air
• Hydronic (water)• PTAC / PTHP
Constant Volume
Variable Volume
Indoor Air Quality
Direct Expansion
Packaged Rooftop Units
FURNACE
A/C UNIT
Ductwork
Heating and Cooling Equipment
Temperature &Humidity Controls
Split System
Heat Pump
• Operate on simple refrigeration cycle
• Reversing the cycle provides heating
• Temperature limitations
• Air to air• Water source• Geothermal• Lake coupled
Geothermal Heat Pump Systems
Variable Air Volume
T T
Variable Speed Return Fan
Re
turn
Air
Return Ducts
Zone Thermostat
Reheat Coil
VAV Box
Supply DuctsVariable Speed Supply Fan
Filt
ers
Co
ol C
oil
w/T
emp
Res
et
He
at
Co
il w
/Tem
p
Re
set
HVAC-16
Terminal Units
Variable volume: Parallel
Constant volume: Series
Hydronic systems
• Pumps• Piping• Valves
Control Devices
• Thermostats– Manual
– Programmable
• Optimum Start
• DDC Systems
• Variable Speed Drives
• Automatic Valves and Dampers
• Outdoor Sensors
Major Equipment
• Chillers
• Boilers
• Cooling Towers
Economizers
Air Side Water Side
Economizers
Free cooling source: When available, use cool outdoor air instead of mechanically cooled air.
55 oF
80 oF
Minimum supply of outside air
Normal OperationOutside air dampers are positioned to provide the minimum outside air
Economizer OperationOutside air dampers are fully open. Maximum outside air is provided
80 oF
55 oF and up
85%outside air
85%exhaust
HVAC-22
Zoning and Economizers
• Economizers provide “free cooling” when outdoor conditions are optimal
• Proper orientation & zoning yields comfort & efficiency
N
S
W ECore
HVAC-23
Air Distribution
• Ductwork– Metal– Flexible– Ductboard
• Grilles, Louvers, & Registers
• Dampers– Shut off– Fire– Smoke
• Sealants• Supports
Return Plenum Problems
HVAC-25
Additional Equipment
• Energy Recovery Units• Desiccant Systems
Additional Equipment
• Heat Exchangers• Humidifiers• Silencers
Mechanical Dehumidification
Return air is mixed with ventilation air
Cold coil condenses moisture
Heat is added back (electric or gas) so that room air is not over cooled- Reheat
Filt
er
Historical Minimum Ventilation Rates (cfm/person)
0
10
20
30
40
50
60
70
Tredgold 1836
Nightengale 1865
Billings 1895
Flugge 1905
Yaglou 1938
ASHRAE 62-73
ASHRAE 62-81
Smoking 62-81
ASH- RAE 62-89
Smoking 62-89
Improved Ventilation Effectiveness
• Mechanically provide filtered and dehumidified outdoor air to the breathing space
• Vary ventilation based on the number of occupants and process loads - changes in occupancy can be measured by CO2 sensors
• Consider designs that separate ventilation and space conditioning
• Utilize heat recovery systems to reduce system size and ventilation energy costs
Improved Ventilation Effectiveness
• Effective mixing of ventilation air within space
• Net positive pressure in the southeast; exhaust from appropriate spaces
• Provide clean outdoor air, avoid:– loading docks – exhaust vents– plumbing stacks– waste collection– stagnant water
Additional Information / Resources
• ASHRAE – The American Society of Heating, Refrigerating and Air-Conditioning Engineers– www.ashrae.org
• Southface Energy Institute www.southface.org• Geothermal heat pump consortium
www.geoexchange.org• www.buildingscience.com• www.energycodes.gov