SUPPLY AIR DUCT SYSTEM The supply duct system distributes air to the terminal units, registers or diffusers into the conditioned space. Starting at the fan outlet, the duct can be fastened to the fan housing directly or have a fireproof vibration eliminator between the fan and the ductwork. The duct system must be designed to allow air moving toward the conditioned space to move as freely as possible but the duct must not be oversized. Duct systems can be plenum, extended plenum, reducing plenum or perimeter loop ( Figure 1 and Figure 2).

description

Semester 5 Lec 7 (air flow rate) CB503 Ventilation And Airconditioning

Transcript of S3 Lec 7 (air flow rate)

Page 1: S3 Lec 7 (air flow rate)

SUPPLY AIR DUCT SYSTEM• The supply duct system distributes air to the terminal

units, registers or diffusers into the conditioned space.

• Starting at the fan outlet, the duct can be fastened to the fan housing directly or have a fireproof vibration eliminator between the fan and the ductwork.

• The duct system must be designed to allow air moving toward the conditioned space to move as freely as possible but the duct must not be oversized.

• Duct systems can be plenum, extended plenum, reducing plenum or perimeter loop ( Figure 1 and Figure 2).

Page 2: S3 Lec 7 (air flow rate)

SUPPLY AIR DUCT SYSTEM

Figure 1 :DUCT SYSTEM LAYOUT

Page 3: S3 Lec 7 (air flow rate)

SUPPLY AIR DUCT SYSTEM

Figure 2 : (A) Plenum system. (B) Extended plenum system.

(C) Reducing extended plenum system. (D) Perimeter loop system.

Whitman,Johnson,Tomczyk.Refrigeration and Air Conditioning Tech.

Page 4: S3 Lec 7 (air flow rate)

PLENUM SYSTEM• It has an individual supply system that makes it

well suited for a job in which the room outlets are all close to the unit (Figure 2A).

• This system is economical from a first cost standpoint and can be installed easily with minimum experience.

• The supply diffusers are normally located on the inside walls and are used for heating system with very warm or hot air as the heating source.

• The return air system can be a single return located at the air handler which makes materials economical.

Page 5: S3 Lec 7 (air flow rate)

EXTENDED PLENUM SYSTEM

• This system can be applied to a long structure such as the ranch-style house.

• This system takes the plenum closer to the farthest point.

• The extended plenum is called the trunk duct and can be round, square or rectangular (Figure 2B).

• The system uses small ducts called branches to complete the connection to the terminal units.

Page 6: S3 Lec 7 (air flow rate)

REDUCING PLENUM SYSTEM

• The reducing plenum system reduces the trunk duct size as branch ducts are added.

• This system has the advantage of saving materials and keeping the same pressure from one end of the duct system to the other when it is properly sized.

• This ensures that each branch duct has approximately the same pressure and velocity pushing air into its takeoff from the trunk duct (Figure 2C).

Page 7: S3 Lec 7 (air flow rate)

PERIMETER LOOP SYSTEM

• The perimeter loop duct system is particularly well suited for installation in a concrete floor in a colder climate.

• The loop can be run under the slab close to the outer walls with the outlets next to the wall.

• The loop has a constant pressure around the system and provides the same pressure to all outlets (Figure 2D).

Page 8: S3 Lec 7 (air flow rate)

RETURN AIR DUCT

• The return air duct is constructed in much the same manner as the supply duct except that some installations are built with central returns instead of individual room returns.

• Individual return air systems have a return air grille in each room that has a supply diffuser.

• The individual return air system will give the most positive return air system, but they are expensive. The return air duct is normally sized at least slightly larger than the supply duct so there is less resistance to the airflow in the return system than in the supply system.

Page 9: S3 Lec 7 (air flow rate)

AIR FILTERS

• The purpose of an air filter is to free the air of as much of the airborne contaminants as is practicable.

• The main types of filters are :• Dry : in which the contaminants are collected in

the filter medium• Viscous or Impingement : in which the

contaminants adhere to a special type of oil.• Electrostatic : in which the contaminants are

positively charged with electricity and collected on negative earthed plates.

Page 10: S3 Lec 7 (air flow rate)

DRY FILTERS

• These use materials such as cotton wool, glass fiber, cotton fabric, treated paper, foamed polyurethane as the cleaning medium. • The efficiency of the filter depends largely upon the area of medium offered to the air stream and for this reason the filter can be arranged in a ‘V’ formation which increases the area (Figure 3, 4 and 5).

Page 11: S3 Lec 7 (air flow rate)

DRY FILTERS

Figure 3 :

Dry cell filter arranged in Vee-formation.

Figure 4 :

Vee-type dry fabric (plan).

Page 12: S3 Lec 7 (air flow rate)

DRY FILTERS

Figure 5 :View of Vee fabric filter.

Frederick E Hall. Building Services & Equipment

Page 13: S3 Lec 7 (air flow rate)

DRY FILTERS • In the case of an automatic roller type filter, when the filter is dirty, a pressure switch will switch on an electric motor which will turn the dirty spool and allow clean fabric to enter the filter chamber. (Figure 6 and Figure 7). • One type of dry filter is made up of a square cell of sizes from 254mm by 254mm to 600mm by 600mm. • The filter medium which either 25mm or 50mm thick is held in a metal or cardboard frame. Figure 8 shows a view of a disposable or what is often called ‘a throw away dry cell type filter’.

Page 14: S3 Lec 7 (air flow rate)

DRY FILTERS

Figure 6 : Vertical sections of automatic roll type filter.

Figure 7: View of automatic roll type filter

Page 15: S3 Lec 7 (air flow rate)

DRY FILTERS Figure 8 :

Throw-away dry cell type filter.

Figure 9 : Cell type viscous filter.Frederick E Hall. Building Services & Equipment.

Page 16: S3 Lec 7 (air flow rate)

ABSOLUTE FILTERS • These are of dry fabric type and are very efficient in moving even the smaller particles from the air. • This high performance is obtained by close packing of a very large number of small diameter fibers but this unfortunately results in a high resistance to air passing through the filter.

Page 17: S3 Lec 7 (air flow rate)

VISCOUS FILTERS

• These have a large dust-holding capacity and are therefore often used in industrial areas where there is a high degree of atmospheric pollution.

• The filter medium is coated with a non-inflammable, non-toxic and odorless oil, which the contaminants adhere to as they pass through the filter.

• There are two types of viscous filters such as cell type and automatic type (Figure 10 and 11).

Page 18: S3 Lec 7 (air flow rate)

VISCOUS FILTERS

Figure 10 :Automatic revolving viscous. Frederick E Hall. Building

Services & Equipment.

Page 19: S3 Lec 7 (air flow rate)

Electrostatic Filters• These types of filters have three main

components : ionizer, metal collector and electrostatic power pack.

• The various air contaminants are given a positive electrostatic charge by an ionizer screen which is the first part of the filter.

• The screen consists of a series of fine wires possessing an electrostatic charge produced by a direct current potential of 13 kV.

• The wires are spaced alternatively with rods or tubes which are at earth potential.

Page 20: S3 Lec 7 (air flow rate)

Electrostatic Filters• The air containing these positively charged

contaminants then passes through a metal collector, which consists of a series of parallel plates about 6mm apart, arranged alternatively so that one plate which is earthed, is next to a plate which is charged with a positive direct current potential of 6 kV.

• The positively charged air contaminants passing through the collector are repelled by the plates of similar polarity ( which are positive) and are attracted by the negative earthed plates (Figure 11).

Page 21: S3 Lec 7 (air flow rate)

VISCOUS FILTERS

Figure 11 : Electrostatic filter. Frederick E Hall. Building Services

& Equipment.

Page 22: S3 Lec 7 (air flow rate)

BALANCING DAMPERS

• A well-designed system will have balancing dampers in the branch ducts to balance the air in the various parts of the system.

• Balancing the air with dampers enables the technician to direct the correct volume of air to the correct run of duct for better room temperature control.

Page 23: S3 Lec 7 (air flow rate)

BALANCING DAMPERS

• The dampers should be located as close as practical to the trunk line, with the damper handles uncovered if the duct is insulated.

• The place to balance the air is near the trunk so if there is any air velocity noise, it will be absorbed in the branch duct before it enters the room.

• A damper consists of a piece of metal shaped like the inside of the duct with a handle protruding through the side of the duct. The handle allows the damper to be turned at an angle to the air stream to slow the air down.

Page 24: S3 Lec 7 (air flow rate)

ROOM AIR DISTRIBUTION

• The supply air enters a room either through a grille, register or diffuser.

• A supply grille has adjustable vanes for controlling the direction of the air entering a room.

• A register is a grille that also has a damper behind it so that the amount as well as the direction of the air entering a room can be controlled.

Page 25: S3 Lec 7 (air flow rate)

ROOM AIR DISTRIBUTION• When registers are mounted on upper walls, they

are designed to throw the air about three-quarters the distance across the room (Figure 12).

• When registers are mounted in the floor, they are usually aimed up and thus are suitable only for small spaces (Figure 13).

• When air is supplied from the ceiling, it has to be mixed rapidly with the room air to prevent discomfort for the occupants and consequently a diffuser is used.

• Diffusers can be round, rectangular or linear. • Supply can also be diffused with large perforated

ceiling panels.

Page 26: S3 Lec 7 (air flow rate)

ROOM AIR DISTRIBUTION

Figure 12 : Cooling air distribution through upside wall.

Figure 13 :

Diffusers spread and distribute the air through the floor

Page 27: S3 Lec 7 (air flow rate)

ROOM AIR DISTRIBUTION

Figure 14 : Heating air distribution through low side wall. Whitman,Johnson,Tomczyk. Refrigeration and Air

Conditioning Tech.

Page 28: S3 Lec 7 (air flow rate)

ROOM AIR DISTRIBUTION• The location of supply air outlets is very

important for the comfort of the occupants. • The goal is to gently circulate all of the air in a

room so that there are neither stagnant nor draftly areas.

• Make sure too that beams or other objects do not block the air supply from reaching all parts of a room.

• Where heating is the major problem, the outlets should be paced lower (Figure 14).

• In large theaters good airflow is often achieved by supplying air all across the ceiling and returning it all across the floor under the seats.

Page 29: S3 Lec 7 (air flow rate)

ROOM AIR DISTRIBUTION

Return air generally leaves a room through a grille but it can also leave through lighting fixtures, perforated ceiling panels or undercut doors (Figure 15). The location of the return air grille has almost no effect on room air motion if supply outlets are properly located (Figure 16). However, to prevent short-circuiting of the air, do not place return openings right next to supply outlets. Also avoid floor return grilles because dirt and small objects fall into them.

Page 30: S3 Lec 7 (air flow rate)

ROOM AIR DISTRIBUTION

Figure 15 : Different types of grills.Figure 16 : : Diffusers and registers.

Whitman, Johnson, Tomczyk. Refrigeration and Air Conditioning Tech.

Page 31: S3 Lec 7 (air flow rate)

AIR FLOW RATE

When determining air flow rates for rooms that are air conditioned, the following procedure should be adopted;1. Calculate heat gains.2. Complete psychometric chart.3. Determine mass flow rate of supply air from the following;

m = H / (Cp x (tr –ts))where;

H = Sensible heat gain (kW)m = mass flow rate of air (kg/s) Cp = Specific heat capacity of air (1.005 kJ/kg K)tr = room temperature (oC)ts = supply air temperature (oC) from

psychometric chart.

Page 32: S3 Lec 7 (air flow rate)

AIR FLOW RATE4. Convert mass flow rate to a volume flow rate:

Volume flow rate (m3/s) = mass flow rate (kg/s) / density of air (kg/m3)

5. Convert this to an Air Change rate for comparison.

Volume flow rate (m3/h) = Volume flow rate (m3/s) x 3600

Supply Air Rate (AC/h) = Volume Flow Rate (m3/h) / Room Volume (m3)

6. Check out the recommended air flow rate from CIBSE Guide B2 (Ventilation and Air Conditioning) Section 3 - Requirements.

Use the higher value of air change rate for design purposes.