RT-PRC028-EN_03222013.28-29
Click here to load reader
-
Upload
mecanico-2000 -
Category
Documents
-
view
4 -
download
0
description
Transcript of RT-PRC028-EN_03222013.28-29
28 RT-PRC028-EN
General Data
Table 5. General data—25 ton standard efficiency
25 Tons Downflow & Horizontal Units
TS*300F3,4,W,K YS*300F3,4,W,K
Cooling Performance(a)
Gross Cooling Capacity 296,400 296,400EER (Downflow/Horizontal)(b) 10 10Nominal Airflow CFM / ARI Rated CFM 10,000 / 8,000 10,000 / 8,000ARI Net Cooling Capacity 272,000 272,000 Integrated Energy Efficiency Ratio (IEER) (One Speed Fan / Multi or Variable Speed Fan)(c) 10.4/12.0 10.4/12.0
Percent Capacity @ part load (Stage 1/Stage 2) 50/100 50/100
System Power (kW) 27.20 27.20
CompressorNumber/Type 2 / Scrolls 2 / Scrolls
SoundOutdoor Sound Rating (BELS)(d) 9.4 9.4
Outdoor CoilType Microchannel MicrochannelCoil Width (in.) 1.0 1.0Face Area (sq. ft.) 35.2 35.2Rows/FPI 1 / 20 1 / 20
Indoor CoilType Hi-Performance Hi-PerformanceTube Size (in.) ID 0.3125 0.3125Face Area (sq. ft.) 26.00 26.00 Rows/FPI 4 / 15 4 / 15Refrigerant Control Short Orifice Short OrificeDrain Connection Number/Size (in.) 1/1.00 NPT 1/1.00 NPT
Outdoor FanType Propeller PropellerNumber Used/Diameter (in.) 2 / 28 2 / 28Drive Type/No. Speeds Direct / 1 Direct / 1cfm 16,100 16,100Number Motors/hp 2 / 1.0 2 / 1.0Motor rpm 1125 1125
Indoor FanType FC Centrifugal FC CentrifugalNumber Used/Diameter (in.) 1 / 18x18 1 / 18x18Drive Type/No. Speeds Belt / 1 Belt / 1Number Motors 1 1Motor hp (Standard/Oversized) 7.5 / N/A 7.5 / N/AMotor rpm (Standard/Oversized) 3,470 / N/A 3,470 / N/AMotor Frame Size (Standard/Oversized) 184T / N/A 184T / N/A
RT-PRC028-EN 29
General Data
FiltersType Furnished(e) Throwaway ThrowawayNumber Size RecommendedDownflow (4)20x20x2 (4)20x25x2 (4)20x20x2 (4)20x25x2Horizontal (8)20x25x2 (8)20x25x2
Refrigerant Charge (Pounds of R-410A)(f)
Downflow/Horizontal 10.5 / 10.5 10.5 / 10.5
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360-93.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 360.(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.(e)An optional 2-inch pleated filter is also available.(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instruc-
tions.* Indicates both downflow and horizontal units.
Table 5. General data—25 ton standard efficiency (continued)
25 Tons Downflow & Horizontal Units
TS*300F3,4,W,K YS*300F3,4,W,K
Table 6. General data—heating—25 tons
25 Tons Downflow & Horizontal Units
Heating Performance(a) (Gas/Electric Only)
Heating Models Low HighModulating Turn
Down = 5:1
Heating Input (Btu/h) 250,000 400,000 350,000
1st Stage (Btu) 175,000 300,000 80,000
Heating Output (Btu/h) 203,000 324,000 283,500
1st Stage (Btu) 142,000 243,000 64,800
AFUE%(b)
Downflow/Horizontal 80.2 / 81.0 79.8 / 79.7 79.8 / 79.7
Steady State Efficiency% 81.0 81.0 81.0
No. Burners 1 1 1
No. Stages 2 2 N/A
Gas Supply Line Pressure (in. wc) 2.5 / 14.0 2.5 / 14.0 2.5 / 14.0
Natural or LP (minimum/maximum) Natural or LP Natural or LP Natural Only
Gas Connection Pipe Size (in.) ½ ¾ ¾
(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.