ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3...

20
ROM and ROMpak Range Quarter-Turn Direct Drive Electric Actuators Keeping the World Flowing

Transcript of ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3...

Page 1: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

ROM and ROMpak Range

Quarter-Turn Direct DriveElectric Actuators

Keeping the World Flowing

A4 US

US

A4

US

A4

A4 US

Page 2: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

2 ROM and ROMpak Range

Keeping the World Flowing

RELIABILITY IN FLOW CONTROL

CRITICAL APPLICATIONS

Reliable operation when it matters

Assured reliability for critical applications and environments.

Whether used 24/7 or infrequently, Rotork products will operate reliably and efficiently when called upon.

Low cost of ownership

Long-term reliability prolongs service life.

Rotork helps to reduce long term cost of ownership and provides greater efficiency to process and plant.

Quality-driven global manufacturing

Products designed with 60 years of industry and application knowledge.

Research and development across all our facilities ensures cutting edge products are available for every application.

Customer-focused service worldwide support

Solving customer challenges and developing new solutions.

From initial enquiry through to product installation, long-term after-sales care and Client Support Programmes (CSP).

pantah61tbz

A4US

US

A4

US A4

US

A4

Page 3: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

Keeping the World Flowing 3

Corporate social responsibility

A responsible business leads to being the best business.

We are socially, ethically, environmentally responsible and committed to embedding CSR across all our processes and ways of working.

Market leader technical innovator

The recognised market leader for 60 years.

Our customers have relied upon Rotork for innovative solutions to safely manage the flow of liquids, gases and powders.

Global presence local service

Global company with local support.

Manufacturing sites, service centres, sales offices and Centres of Excellence throughout the world provide unrivalled customer services and fast delivery.

Comprehensive product range serving multiple industries

Improved efficiency, assured safety and environmental protection.

Rotork products and services are used throughout industry inclusive of Power, Oil & Gas, Water & Wastewater, HVAC, Marine, Mining, Pulp & Paper, Food & Beverage, Pharmaceutical and Chemical industries around the world.

Section Page Section Page

Rotork – Keeping the World Flowing 2

Product Overview 4

Design Features 6

Performance Data 8

ROM and ROMpak 8

ROMH and ROMpakH 9

Circuit Diagram and Optional Extras 10

ROM 10

ROMpak 3-Phase 11

ROMpak 1-Phase 12

Dimensional Data 13

Client Support and Site Services 18

ROM and ROMpak Range

pantah61tbz

A4 US

US

A4

US

A4

A4 US

Page 4: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

4 ROM and ROMpak Range

Product Overview

Compact, lightweight and cost effective Rotork solution to suit your application

Proven reliable design

Continuous position indication at all times, even without power

Analogue and Network compatibility for complete site system integration

Watertight and dustproof to IP68 10m for 100 hours

Manual override for emergency operation

Backed by Rotork Global Support

1-phase, 3-phase and DC power supplies

Guaranteed operating direction with automatic phase rotation correction

Integral local controls for enhanced local operation

Dependable mechanical end of travel protection

Self-locking and high speed solutions

As one of the world’s leading manufacturers of actuation products, Rotork has built up an enviable reputation as the supplier of reliable and durable equipment.

With over 60 years of valve automation experience, Rotork has evolved a design of uncompromising reliability. The ROM and ROMpak range of actuators are designed to provide a simple and reliable Rotork solution for small part-turn valves.

A4US

US

A4

US A4

US

A4

Page 5: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

Keeping the World Flowing 5

A4 US

US

A4

US

A4

A4 US

Page 6: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

6 ROM and ROMpak Range

ROM and ROMpak actuators provide quiet and reliable operation for all kinds of small ball valves and butterfly valves, as well as dampers and ventilation louvres. They provide local indication and manual override options together with a wide range of voltages.

Features:

ROM ROMpak

Enclosure IP68Waterproof - Dustproof

IP68Waterproof - Dustproof

Material Aluminium Alloy Aluminium Alloyand plastic

Finish Dry powder coated Dry powder coated and wet spray

Motor

• Standard duty cycle induction motor - S3. Class F insulation for all ROM and ROMpak actuators

Position Indicator

• All models have continuous position indication on the actuator top cover

Manual Override

• Non-clutch design, the manual operation can be operated without any lever, clutch or brake upon power outage

• When the electric motor is operating, the manual override will not rotate except on ROMH-1 to ROMH-3, ROM-1 & ROM-A

Gear Train

• High alloy steel gear trains provide self-locking function to avoid valve back drive*

• ROM-1 and ROM-A designs incorporate an efficient spur gear train which can back drive in certain applications

• Gear trains are factory lubricated with a wide temperature rated lubricant

Mechanical Stops

• Externally adjustable mechanical stops*

Working Conditions

• Ambient temperature: -30 to +70 ºC (-22 to 158 ºF)†

• Humidity: 30% to 95%

Various Options

• Anti-condensation heater

• Additional limit switches

• Conduit entries M20 x 1.5p

• Torque switches*

Certificates

• ISO 9001, CE, CSA, BV

† 12/24 VDC units are -30 to +65 ºC (-22 to +149 ºF)

* ROM and ROMpak 2, 3, 4, 5, 6 & 7 actuators only

Design Features

ROM Actuator ROMpak Actuator

A4US

US

A4

US A4

US

A4

Page 7: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

Keeping the World Flowing 7

Design Features

The ROMpak

The ROM range of actuators can be enhanced with the addition of a self contained control package to create a ROMpak actuator. This adds local controls, status indication relays, isolated control circuits and support for Rotork control options such as Folomatic, PakscanTM and other bus systems.

• Small, compact & lightweight

• Manual override

• Externally adjustable mechanical stops*

• Local control unit (local/remote, on/off)

• Status relays

• Phase rotation correction

• IP68 (10m / 100 hours)

• 12/24 VDC, 110/220 VAC 1-phase and 220/380/440 VAC 3-phase, 50 Hz and 60 Hz

• Position indication via local mechanical indicator and LEDs

• -30 to +70 ºC (-22 to 158 ºF)† operation

† 12/24 VDC units are -30 to +65 ºC (-22 to +149 ºF)

* ROM and ROMpak 2, 3, 4, 5, 6 & 7 actuators only

Various Options:

• Bus communications including: PakscanTM, Profibus®, Modbus® and Foundation Fieldbus®

• Current position transmitter & Folomatic

The ROMH

The ROMH actuator has been designed for high-speed applications. This actuator is also available with the self-contained control package (ROMpakH). All features from the ROM and ROMpak are also available on the ROMH and ROMpakH.

• Small, compact, lightweight and high speed

• 4.5 and 5.5 seconds operating times

• Manual override

• Bus communications including: PakscanTM, Profibus®, Modbus® and Foundation Fieldbus®

• Analogue control and feedback

• DC and 1-phase options

ROMpak Actuator

A4 US

US

A4

US

A4

A4 US

Page 8: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

ROM and ROMpak Range8

Performance Data

A4US

US

A4

US A4

US

A4

ROM and ROMpakMechanical Data Model ROM

Weight (kg)ROMpak

Weight (kg)Manual override

Output Drive (mm)

TorqueNm (lbf.ft)

Mounting Flange

ISO 5211 MSS SP-101

ROM-1* 2 4 Hexagonal Drive 14 / 11 / 9 35 (26) F03/F05 FA03/FA05

ROM-A* 3 5 Hexagonal Drive 17 / 14 50 (37) F05/F07 FA05/FA07

ROM-2 11 13 Handwheel 22 / 17 90 (67) F07 FA07

ROM-3 11 13 Handwheel 22 / 17 150 (111) F07 FA07

ROM-4 22 24 Handwheel 36 / 35 400 (295) F10 FA10

ROM-5 22 24 Handwheel 36 / 35 500 (369) F10 FA10

ROM-6 22 24 Handwheel 36 / 35 650 (479) F10 FA10

ROM-7 26 28 Handwheel 36 / 35 800 (590) F12 FA12

NOTE: Weight data based on 1-phase 50Hz supply.*Not suitable for butterfly valves which may back drive.

Electrical Performance Data12V/24V*

Model Torque (Nm)

Operating Time (sec)

Motor Power (W)

12 VDC/VAC CURRENT (A) Run Lock

24 VDC/VAC CURRENT (A) Run Lock

ROM-1 35 20 4.2 1.2 2.2 0.6 1.2

ROM-A 50 30 4.2 1.2 2.2 0.6 1.2

ROM-2 90 17 43 2.5 20 1.1 11

ROM-3 150 28 43 3.2 20 1.5 11

ROM-4 400 23 92 11 42 5.5 21

ROM-5 500 30 92 11 42 5.5 21

ROM-6 650 38 92 11 42 5.5 21

ROM-7 800 46 92 11 42 5.5 21

*12/24 VAC not available for ROMpak.

1-Phase

Model Torque (Nm)

Operating Time (sec) 50 Hz 60 Hz

Motor Power (W)

110 V CURRENT (A) Run Lock

220 V CURRENT (A) Run Lock

ROM-1 35 15 13 5 0.36 0.4 0.23 0.25

ROM-A 50 22 19 5 0.36 0.4 0.23 0.25

ROM-2 90 17 15 43 1.0 1.7 0.65 1.0

ROM-3 150 28 24 43 1.0 1.7 0.65 1.0

ROM-4 400 20 17 105 1.9 5.0 0.85 2.3

ROM-5 500 26 22 105 1.9 5.0 0.85 2.3

ROM-6 650 33 28 105 1.9 5.0 0.85 2.3

ROM-7 800 40 34 105 1.9 5.0 0.85 2.3

Page 9: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

Keeping the World Flowing 9

Performance Data

A4 US

US

A4

US

A4

A4 US

3-Phase

Model Torque (Nm)

Operating Time (sec) 50 Hz 60 Hz

Motor Power (W)

220 V Current Run Lock

380 V CURRENT (A) Run Lock

440 V CURRENT (A) Run Lock

ROM-2 90 16 14 46 1.3 1.8 0.45 0.83 0.58 0.80

ROM-3 150 26 22 46 1.3 1.8 0.45 0.83 0.58 0.80

ROM-4 400 20 17 105 2.45 4.5 0.7 2 0.63 1.77

ROM-5 500 26 22 105 2.45 4.5 0.7 2 0.63 1.77

ROM-6 650 33 28 105 2.45 4.5 0.7 2 0.63 1.77

ROM-7 800 40 34 105 2.45 4.5 0.7 2 0.63 1.77

Operating Voltages:

12 VDC

24 VDC

12 VAC

24 VAC

110 V/1

220 V/1

220 V/3

380 V/3

440 V/3

ROM-A

ROM-1

ROM-2,3

ROM-4,5,6&7

12 VDC

24 VDC

12 VAC

24 VAC

110 V/1

220 V/1

220 V/3

380 V/3

440 V/3

ROMpak-A

ROMpak-1

ROMpak-2,3

ROMpak-4,5,6&7

ROMH and ROMpakHMechanical Data

Model ROMH Weight (kg)

ROMpakH Weight (kg)

Manual override

Output Drive (mm)

TorqueNm (lbf.ft)

Mounting Flange

ISO 5211 MSS SP-101

ROMH-1* 2 4 Hexagonal Drive 14 / 11 / 9 35 (26) F03/F05 FA03/FA05

ROMH-2* 3 5 Hexagonal Drive 17 / 14 50 (37) F05/F07 FA05/FA07

ROMH-3* 11 13 Handwheel 22 / 17 90 (67) F07 FA07

*Not suitable for butterfly valves which may back drive.

Electrical Performance Data12V/24V*

Model Power Supply

Torque (Nm)

Operating Time (sec)

Motor Power (W)

Current (A) Run Lock

ROMH-112 VDC 8 5.5 4.75 1.2 2.2

24 VAC 8 4.5 4.75 0.65 1.2

ROMH-2 24 VDC 10 4.5 4.75 0.65 1.2

1-Phase

Model Power Supply

Torque (Nm)

Operating Time (sec) 50Hz 60Hz

Motor Power (W)

Current (A) Run Lock

ROMH-3110 V 13 4.5 4.3 6.5 0.36 0.4

220 V 13 4.5 4.3 6.5 0.23 0.25

Operating Voltages:

12 VDC

24 VDC

12 VAC

24 VAC

110 V/1

220 V/1

220 V/3

380 V/3

440 V/3

ROMH-1

ROMH-2

ROMH-3

12 VDC

24 VDC

12 VAC

24 VAC

110 V/1

220 V/1

220 V/3

380 V/3

440 V/3

ROMpakH-1

ROMpakH-2

ROMpakH-3

Page 10: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

ROM and ROMpak Range10

Circuit Diagram and Optional Extras

ROM Wiring Diagram

7

6

5

4

3

1

A

B

C

E

F

1011

12

SMOTOR

7 6 5 4 3 2 1

RY1 RY2

F RY2 RY1

LED 1

LED 2

HEATER

LS1

LS2

LS3

LS4

OPEN CLOSED

CLOSE

OPENOFF

SELECTORSWITCH

FULLY OPEN

FULLY CLOSED

MCB

12/24V AC/DC SUPPLY

(1) S CONNECTS TO 3 FOR“OPEN”, S CONNECTS TO 4FOR "CLOSE"

(2) HEATER,LS3,LS4,ANDPOTENTIONMETER AREOPTIONS.ROM 1 & ROM A

7

6

5

4

3

1

A

B

C

E

F

1011

12

HEATER

LS1

LS2

LS3

LS4

OPEN

ROM 1 & ROM A

CLOSED

CLOSE

OPENOFF

FULLY OPEN

FULLY CLOSED

(1) L CONNECTS TO 3 FOR“OPEN”, L CONNECTS TO 4

(2) HEATER,LS3,LS4 AND,POTENTIONMETER AREOPTIONS.

M1

N

LSELECTORSWITCH

MCB 110/220V AC1-PHASE

SINGLE PHASE

FOR "CLOSE"

SUPPLY

M1

7

6

5

4

3

1

A

B

C

D

E

F

1011

12

LS1

LS2

LS3

LS4

OPEN

ROM 2 3 4 5 6 7

CLOSED

CLOSE

OPENOFF

SELECTORSWITCH

FULLY OPEN

FULLY CLOSED

MCB

(1) L CONNECTS TO 3 FOR “OPEN”, L CONNECTS TO 4FOR "CLOSE"

(2) HEATER,LS3,LS4,TS1,TS2AND POTENTIONMETERARE OPTIONS.

N

L

110/220V AC1-PHASE

SINGLE PHASESUPPLY

TS1

TS2

HEATER

7

6

5

4

3

1

A

B

C

D

E

F

1011

12

P

SMOTOR

7 6 5 4 3 2 1

RY1 RY2

F RY2 RY1

LED 1

LED 2

HEATER

TS2

TS1 LS1

LS2

LS3

LS4

OPEN

ROM 2 3 4 5 6 7

CLOSED

CLOSE

OPENOFF

SELECTORSWITCH

FULLY OPEN

FULLY CLOSED

MCB Refer to table below

12/24V AC/DC SUPPLY

(1) S CONNECTS TO 3 FOR“OPEN”, S CONNECTS TO 4FOR "CLOSE"

(2) HEATER,LS3,LS4,TS1,TS2AND POTENTIONMETER AREOPTIONS.

9

8

6

5

A

B

C

3

W

V

U

4

1

LS3

HEATER

110/220V AC

LS1

LS2

TS1

TS2

M3 R

ST

L

N

MCB

MCB

FULLY OPEN

FULLY CLOSED

OPEN

CLOSEC 0

(1) 1 CONNECTS WITH 3 FOR “OPEN”,1 CONNECTS WITH 4 FOR“CLOSE”.

(2) IF THE ACTUATOR IS REVERSED

E

F

1011

12OPEN CLOSED

LS4

ROM 2 3 4 5 6 7THREE PHASE SUPPLY

(3) HEATER,LS3,LS4,TS1,TS2 ANDPOTENTIONMETER ARE OPTIONS.

OPERATION,PLEASE CHANGE TWO OF U,V AND W AT WILL.

Actuator Power supply P S 12V DC + - 24V DC + - 12V AC N L 24V AC N L

PRefer to table

below

Actuator Power supply P S 12V DC + - 24V DC + - 12V AC N L 24V AC N L

Wiring Diagram ( ROM 1/A/2/3/4/5/6 ) Issue No: 4

3-PHASE SUPPLY

Optional Extras:

Torque Switches

Cam activated torque switches to provide torque overload protection ROM-2, 3, 4, 5, 6 & 7.

Anti-condensation Heater

This heater is available for all sizes.

A4US

US

A4

US A4

US

A4

Page 11: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

Keeping the World Flowing 11

Circuit Diagram and Optional Extras

ROMpak 3-Phase Wiring Diagram

V

E

W

HeaterU 1

2

3

4

LOCALCONTROLPCB

CLOSE-OPEN

STOPREMOTE-LOCAL

4

65

3

12

C1 C2

Z

XYMOTOR

U

V

YX Z

U

W

V

THREE PHASE

SUPPLY

CIRCUIT DRAWN WITHPOWER SUPPLY OFF

LIMITTORQUE

AND POSITIONSENSING

TRANSFORMER TAPPING

TAP

352-484 396-517

NOM 50/60HZ220/230380/400440/460

176-242304-418 342-446

198-25960HZ50HZ

SIR

1R

ELAY

1

3

5

SIR

2R

ELAY

2

4

6

NOTE

TO BE MINIMUM 'ON' 14V DC AT 1mA MAXIMUM 'OFF'=3V

MINIMUM CONTROL SIGNAL DURATIONTO BE 300mS.

CONTROL SIGNAL IS 5mA ON 24V DC CURRENT DRAWN FROM EACH REMOTE

MAX EXTERNAL LOAD ON S1/S2 RELAYS TO BE 5A. MAX VOLTAGE 120V AC/DC

NOT USED

CONTROL SIGNAL THRESHOLD VOLTAGES:MAX 60V DC

MONITOR

REMOTE SELECTED

SK.5

SK.17

SK.3

SK.8

1

2

3

4

5

OPEN

STOP/MAINTAIN

CLOSE

NOMINAL +VE 20-32V DC SUPPLY

6

7

8

9

10

OPEN COMMON

STOP/MAINTAIN COMMON

CLOSE COMMON ESD ESD COMMON

0V DC SUPPLY

SK.1

SK.1 SK.2

SK.24123456

1 2 3 4 SK.7

W

VOLTAGE SELECTOR

FS1FS1 - See ROMPAK E672E Installation and Maintenance Manual

S1

S2

FOR TYPICAL REMOTE CONTROLINDICATING,MONITORING AND ALARMCIRCUITS SEE PUBLICATION E621E

LS3 / LS4MAXIMUM CURRENT 3A MAXIMUMVOLTAGE 120V AC/DC

ACTUATOR CONFIGURATION VIA DIL SWITCH SW2

ROM1 DOES NOT SUPPORT TORQUE LIMIT

REFER TO INSTALLATION INSTRUCTIONS FOR DIL SWITCH SELECTION

MAX EXTERNAL LOAD ON TERMINAL27 & 28 TO BE 3W

LS3

LS4

7 8 9

10 11 12

5 6

13 14 15 16 17 18

19 20 21 22 23 24 25 26 27 28

A4 US

US

A4

US

A4

A4 US

Page 12: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

ROM and ROMpak Range12

Circuit Diagram and Optional Extras

ROMpak 1-Phase Wiring Diagram

FOR TYPICAL REMOTE CONTROLINDICATING,MONITORING AND ALARMCIRCUITS SEE PUBLICATION DOC862

NOTE

TRANSFORMER TAPPING

NOM 50/60HZ

220/230110/120

176-24292-135

60HZ50HZ

CONTROL SIGNAL THRESHOLD VOLTAGES:

TO BE MINIMUM 'ON' 14V DC AT 1mAMAXIMUM 'OFF'= 3VMINIMUM CONTROL SIGNAL DURATIONTO BE 300mS.

CONTROL SIGNAL IS 5mA ON 24V DCCURRENT DRAWN FROM EACH REMOTE

MAX EXTERNAL LOAD ON S1/S2 RELAYSTO BE 5A. MAX VOLTAGE 120V AC/DC

LS3 / LS4MAXIMUM CURRENT 3A MAXIMUMVOLTAGE 120V AC/DC

FS1 - SEE ROMPAK PUB008-006 INSTALLATIONAND MAINTENANCE MANUAL

92-135176-242

VOLTAGE SELECT SWITCH SW1,MUST BE CONFIGUREDCORRECTLY BEFORE APPLYINGPOWER.

ACTUATOR CONFIGURATIONVIA DIL SWITCH SW2

ROM1 AND ROMA DO NOTSUPPORT TORQUE LIMIT

REFER TO INSTALLATIONINSTRUCTIONS FOR DILSWITCH SELECTION

MAX EXTERNAL LOAD ON TERMINAL27 & 28 TO BE 3W

MAX 60V DC

LOCALCONTROLPCB

CLOSE-OPEN

STOPREMOTE-LOCAL

CIRCUIT DRAWN WITHPOWER SUPPLY OFF

LIMIT ANDTORQUESENSING

SIR1

RELAY

1

3

5

SIR2

RELAY

2

4

6

S1

S2

LS3

LS4

MONITOR

REMOTESELECTED

SK.5 7 8 9

10 11 12

5 6

13 14 15 16 17 18

SK.17

SK.3

SK.8

1

2

3

4

5

OPEN

STOP/MAINTAIN

CLOSE6

7

8

9

10

OPEN COMMON

STOP/MAINTAIN COMMON

CLOSE COMMONESDESD COMMON

19 20 21 22 23 24 25 26 27 28

SK.1

SK.1 SK.2

SK.241

3

5

2

4

6

1 2 3 4 SK.71 2 3 4 SK.10

UX WZ

A B C D

1 2 3 4SK.52

MOTOR

N

ACW

CW

HEATER

MOTORRUNCAP.

E 4

LN

115

230

VOLTAGESELECTOR

FS1

NOMINAL +VE 20-32V DC SUPPLY0V DC SUPPLY

SINGLEPHASESUPPLY

A4US

US

A4

US A4

US

A4

Page 13: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

Keeping the World Flowing 13

20mm Deep

M6 x1.0p10mm Deep4 Positions(ISO5211 F05)

M8x1.25p12mm Deep4 Positions(ISO5211 F07)

P.C.D 50

P.C.D 70

45°17 17

20mm Deep

Option for output shaft

14

11

170.

5

102

106

2 off M20 x1.5pConduit Entries

123

37

60

114 32 CTS

Conduit Entries

8

Manual overridemechanism

ROM-A

106102

123

114

32 CTSConduit Entries

2 off M20 x1.5pConduit Entries

M5 x0.8p9mm Deep4 Positions(ISO5211 F03)

M6 x1.0p10mm Deep4 Positions(ISO5211 F05)

60

136.

5(H

*)37

15mm Deep

P.C.D 36

P.C.D 50

45°

8

1414

20mm Deep 9

12

P.C.D 42

M5 x0.8p12mm Deep4 Positions(ISO5211 F04)

Option 2 for output shaft

H*=140

11

1420mm Deep

Option 1 for output shaft

H*=140

ROM-1ROMH-1ROMH-2ROMH-3

Flange type

F07 / F05

Flange type

F05 / F03

Dimensional Data

A4 US

US

A4

US

A4

A4 US

Page 14: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

ROM and ROMpak Range14

ROM-2/3

ROM-4/5/6

Flange type

F07

Flange type

F10

209

180

196

115

M8 x1.25p10mm Deep4 Positions(ISO5211 F07)

70.00 P.C.D

45°

2 off M20 x1.5pConduit Entries

32 CTSConduit Entries

86.5

25mm Deep

345

246

252

H=/3

12*

22

22

110V, 220V AC 1-Phase

220V, 380V, 440V AC 3-Phase

213=HCD/CA V42 ,V21

ROM-2/3*H=252

140

22

25mm Deep

Option for output shaft17

*ROM-2/3

110 V, 220 V AC 1-PhaseH=252

220 V, 380 V, 440 V AC three-phase

12 V, 24 V AC/DC H=312

32 CTSConduit Entries

40mm Deep

268

102

228Ø

217Ø

318 (with torque limit switches) 249 (without torque limit switches)

434 (with torque limit switches) 365 (without torque limit switches)

160

Ø

327

45°

M10 x1.5p20mm Deep4 Positions(ISO5211 F10)

Ø 102.00 P.C.D

2 off M20 x1.5pConduit Entries 17

2

Option for output shaft

35 35

40mm Deep36

36

119

232

Dimensional Data

A4US

US

A4

US A4

US

A4

Page 15: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

Keeping the World Flowing 15

32 CTSConduit Entries

40mm Deep

279

106

252240

339 (with torque limit switches) 280 (without torque limit switches)

465 (with torque limit switches) 406 (without torque limit switches)

160

356

45°

M12 x1.75p20mm Deep4 Positions(ISO5211 F12)

125.00 P.C.D

2 off M20 x1.5pConduit Entries

36

36

184

Option for output shaft

35 35

40mm Deep

20mm Deep

M8x1.25p12mm Deep4 Positions(ISO5211 F07)

M6 x1.0p10mm Deep4 Positions(ISO5211 F05)

P.C.D 70

P.C.D 50

45°

17 17

20mm Deep

Option for output shaft

14

11

170.

5

161

102106

215

225.

5

63

37

114

8

194

Manual overridemechanism

ROM-7

ROMpak-A

Flange type

F12

Flange type

F07 / F05

Dimensional Data

A4 US

US

A4

US

A4

A4 US

Page 16: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

ROM and ROMpak Range16

ROMpak-2/3

209

180

196

252

H=/3

12*

115

M8 x1.25p10mm Deep4 Positions(ISO5211 F07)

70.00 P.C.D

45°

86.5

25mm Deep

246

438

246

22

22

110V, 220V AC 1-Phase H=252

220V, 380V, 440V AC 3-Phase

12V, 24V AC/DC

*ROMpak 2/3H=312

140

22

25mm Deep

Option for output shaft17

Flange type

F07*ROMpak-2/3

110 V, 220 V AC 1-Phase H=252

220 V, 380 V, 440 V AC three-phaseH=312

12 V, 24 V AC/DC

Dimensional Data

106

102

114

136.

5(H

*)37

15mm Deep

8

M5 x 0.8p9mm Deep4 Positions(ISO5211 F03)M6 x 1.0p10mm Deep4 Positions(ISO5211 F05)

215

63

161

225.

5

1414

P.C.D 50.00

P.C.D 36.00

45°

20mm Deep 9

12

P.C.D 42

M5 x 0.8p12mm Deep4 Positions(ISO5211 F04)

Option 2 for output shaft

H*=140

11

1420mm Deep

Option 1 for output shaft

H*=140

ROMpak-1, ROMpakH-1, ROMpakH-2, ROMpakH-3

Flange type

F05 / F03

A4US

US

A4

US A4

US

A4

Page 17: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

Keeping the World Flowing 17

ROMpak-4/5/6

ROMpak-7

Flange type

F10

Flange type

F12

40mm Deep

268

102

228Ø

217Ø

318 (with torque limit switches)249 (without torque limit switches)

160

Ø

327

45°

M10 x1.5p20mm Deep4 Positions(ISO5211 F10)

Ø 102.00 P.C.D

527 (with torque limit switches )458 (without torque limit switches )

172

Option for output shaft

35 35

40mm Deep

3636

279

119

232

40mm Deep

279

106

252240

339 (with torque limit switches)280 (without torque limit switches)

160

356

45°

M12 x1.75p20mm Deep4 Positions(ISO5211 F12)

125.00 P.C.D

559 (with torque limit switches )499 (without torque limit switches )

273

36

36

184

Option for output shaft

35 35

40mm Deep

Dimensional Data

A4 US

US

A4

US

A4

A4 US

Page 18: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

ROM and ROMpak Range18

Rotork actuators are recognised as the best in the world for reliability and safety in the most demanding applications. To maintain this hard-earned leadership position, Rotork Site Services is committed to helping clients to maximise the continuous, fault-free operation and working life of all their actuators.

With established operations and worldwide service centres we are able to offer same-day or next-day service to all our customers. Our Rotork factory trained engineers have skills in both multi-purpose and industry specific applications and carry with them spare parts and specialist test equipment. Our operations utilise a documented Quality Management system established in accordance with ISO9001.

Rotork Site Services aims to be your number one choice for taking care of fault diagnosis, service repairs, scheduled maintenance and system integration needs.

Rotork has expertise and specialist knowledge of every aspect of flow control.

Our service solutions increase plant efficiency and reduce maintenance costs.

Workshop services return equipment to as-new condition.

Client Support and Site Services

A4US

US

A4

US A4

US

A4

Page 19: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

Keeping the World Flowing 19

Global Service and Support

Rotork understands the value of prompt and punctual customer site services and aim to supply our customers with superior flow control solutions, by providing high quality, innovative products and superior service – on time, every time.

Whether you have an actuator requiring on-site servicing, a custom design service requirement or a new actuator installation, we can deliver the fastest turnaround with the least plant disruption.

Accreditation and Assurance

Rotork Site Services is accredited with all major safety authorities around the world, providing our clients with reassurance and peace of mind.

Rotork's engineering teams are experts in the design and implementation of actuation solutions for all circumstances and environments. Our knowledge base draws upon previous installations and environmental situations from all around the world.

Our track record of undertaken engineering projects is second to none. Rotork is trusted by major utility and industrial companies throughout the world to design, install and maintain their actuation stock. We keep their plants operating at peak efficiency, helping them to be more profitable and at the same time meet ever tightening industry watchdog requirements.

We have the knowledge and expertise to design, build and install any standard or custom installation for you, anywhere throughout the world.

Asset Management

Rotork is a corporate member of the Institute of Asset Management, the professional body for whole life management of physical assets.

Actuator Workshop Overhaul

• Supporting all Rotork and non-Rotork products

• Workshop facilities including torque testing and re-coating

• Large OEM stock in all workshops

• Fully trained and experienced service engineers

• Fleet of well stocked service vehicles

• Loan actuator facilities

Field Support

• Site repairs

• Commissioning

• Upgrades

• Fault finding

• Maintenance

• Call-out

• Fully equiped service vehicles

Rotork Client Support Programme (CSP)

• Enables users to select a level of service precisely tailored for their individual asset management requirements

• Designed to provide the maximum reliability and availability of actuators over the life of the product – thereby improving production throughput

• Designed to reduce the cost of maintenance year on year

• Designed to allow customers to manage the problem of ‘Risk vs Budget’ in maintenance operations

• Designed to be flexible – you choose the level of cover you want

• Reports generated on agreed frequency to demonstrate cost savings and performance improvements

Turnaround, Shutdown and Outage Support

• Preventative maintenance

• Full on-site overhaul and testing facilities

• OEM spares and support

• Support for Rotork and non-Rotork products

• Commissioning support to achieve shutdown time targets

• Project management and supervision of your plant overhaul and return to service dates

Valve Automation Centres

• On Site – Manual Valve Automation

• On Site – Actuator Replacement

• Off Site – New Valve Automation

Giving You Peace of Mind, Guaranteed Quality and

Improving Your Site Efficiency

Client Support and Site Services

A4 US

US

A4

US

A4

A4 US

Page 20: ROM and ROMpak Range · 10 11 12 MOTOR S 7654321 RY1 RY2 F RY2 RY1 LED 1 LED 2 HEATER LS1 LS2 LS3 LS4 OPEN CLOSED CLOSE OPEN OFF SELECTOR SWITCH FULLY OPEN FULLY CLOSED MCB 12/24V

Rotork plcBrassmill Lane, Bath, UK

tel +44 (0)1225 733200fax +44 (0)1225 333467email [email protected]

As part of a process of on-going product development, Rotork reserves the right to amend and change specifications without prior notice. Published data may be subject to change. For the very latest version release, visit our website at www.rotork.com

The name Rotork is a registered trademark. Rotork recognises all registered trademarks. The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks by Rotork is under license. Published and produced in the UK by Rotork Controls Limited. POWJB0518

www.rotork.com

A full listing of our worldwide sales and service network is available on our website.

Rotork is a corporate member of the Institute of Asset Management

PUB008-001-00Issue 07/18

A4US

US

A4

US A4

US

A4