Building Services Engineers
Level 2, 121 Walker Street North Sydney NSW 2060
02 9922 5200
Return Services Brief Clarke Street, Riverstone 14 -28 Residential
Development
Prepared For:
Elite International Development Pty Ltd
Suite 302, 1 Richardson Place, North Ryde, NSW 2113
Prepared By:
Building Services Engineers Document Issue 2 Project Number 20180054 Document Date Friday, 27 April 2018
20180054 Return Services Brief [2] Page 2 of 23
Status
Document Title Return Services Brief Clarke Street, Riverstone 14 -28 Residential Development
File Location S:\Projects\20180054 Clarke Street, Riverstone 14 -28 Residential Development\Reports & Briefs\20180054 Return Services Brief [2].docx
Project Manager: Michael Yan
Document Author: MY/JD/KM/PM
Revision Revision Date Reviewer
1 13/04/18 SJ
2 27/04/18 SJ
Issued To: Elite International Development Pty Ltd
DEM (Aust) Pty Ltd
20180054 Return Services Brief [2] Page 3 of 23
Contents
Status ....................................................................................................................................................................... 2
Contents .................................................................................................................................................................. 3
Introduction ..................................................................................................................................................... 5
Project Description ................................................................................................................................. 5
Services Scope ...................................................................................................................................... 5
Mechanical Services ....................................................................................................................................... 6
Design compliance standards ................................................................................................................ 6
Carpark Ventilation Systems .................................................................................................................. 6
Air conditioning and ventilation for retail areas ....................................................................................... 7
Air conditioning for apartments ............................................................................................................... 7
Ventilation for apartments ...................................................................................................................... 7
Exhaust to apartment wet areas ............................................................................................................. 7
Ventilation for common areas ................................................................................................................. 8
Electrical Services ........................................................................................................................................... 9
Design compliance standards ................................................................................................................ 9
Extent of works ....................................................................................................................................... 9
Substation .............................................................................................................................................. 9
Consumer Mains .................................................................................................................................. 10
Main Switchboard ................................................................................................................................. 10
Metering ............................................................................................................................................... 10
Submains and Cable Reticulation ........................................................................................................ 10
Distribution boards ............................................................................................................................... 11
General power distribution ................................................................................................................... 11
General lighting ................................................................................................................................ 12
3.10.1. Lighting control systems .............................................................................................................. 12
Emergency and exit lighting ............................................................................................................. 12
Communication Cabling and Facilities ............................................................................................. 13
MATV / PayTV Systems ................................................................................................................... 13
Intercom and Access Control System .............................................................................................. 13
CCTV System .................................................................................................................................. 14
Apartment General Lighting and Outlet Allowance .......................................................................... 14
Photovoltaic System......................................................................................................................... 15
Hydraulic Services ........................................................................................................................................ 16
Design compliance standards .............................................................................................................. 16
20180054 Return Services Brief [2] Page 4 of 23
Extent of works ..................................................................................................................................... 16
Potable water service ........................................................................................................................... 16
Hot water service .................................................................................................................................. 17
Sanitary drainage and plumbing ........................................................................................................... 17
Stormwater and roof drainage .............................................................................................................. 17
Natural gas service ............................................................................................................................... 18
Metering ............................................................................................................................................... 18
Fire Services ................................................................................................................................................. 19
Design compliance standards .............................................................................................................. 19
Extent of works ..................................................................................................................................... 19
Fire hydrant system .............................................................................................................................. 19
5.3.1. Fire Service Water Provision and Pumps .................................................................................... 19
Fire hose reels ...................................................................................................................................... 20
Automatic fire alarm & detection system .............................................................................................. 20
Portable fire extinguishers .................................................................................................................... 20
Testing, commissioning, maintenance and certifications...................................................................... 20
Vertical Transportation .................................................................................................................................. 21
Design compliance standards .............................................................................................................. 21
Extent of works ..................................................................................................................................... 21
Appendix - Services spatial markups ............................................................................................................ 23
20180054 Return Services Brief [2] Page 5 of 23
Introduction
The Return Services Brief has been prepared to describe BSE’s understanding of the services requirements for
review and approval by the Client and/or authorised representative.
This document is intended to outline the following with respect to the building services associated with the proposed development:
• Proposed connections to power, communications, water, gas and sewer
• Building services options and recommendations
• Building services design assumptions
This document is intended to be “fluid” allowing its development from the Engineer and other members of the
design and user team to confirm the requirements for the proposed development.
Project Description
The development is a residential building with 2 levels of basement carpark, ground floor retail and 3 levels of
apartments above . The site has a fall from eastern side street level to Clarke Street side.
The development comprises:
• Ground floor neighbourhood shops
• 5 x studios including dual key units
• 3 x 1 bedroom units
• 19 x 2 bedroom units including dual key units
• 1 x 3 bedroom units
Services Scope
The purpose of this document is to detail the required new services as related to BSE’s scope of work and the
services provisions.
This document discusses the following engineering services:
• Mechanical services
• Electrical, communications and security services
• Hydraulic services
• Fire protection services
• Vertical transportation services
20180054 Return Services Brief [2] Page 6 of 23
Mechanical Services
The mechanical services that require spatial consideration for the proposed development generally consist of the
following:
• Carpark ventilation systems
• Air conditioning and ventilation for retail areas
• Air conditioning for apartments
• Ventilation for apartments
• Exhaust to apartment wet areas
• Ventilation for common areas
Dimensions indicated are approximate only at this stage.
Design compliance standards
The latest Australian Standards having jurisdiction over the works and materials within this development, in
particular:
• AS 1668.2 - The use of mechanical ventilation and air-conditioning in buildings - Mechanical ventilation for
acceptable indoor-air quality
• AS/NZS 1668.1 - The use of ventilation and air conditioning in buildings – Fire and smoke control in multi-
compartment buildings
Carpark Ventilation Systems
Mechanical ventilation serving the carpark comprises fans, ductwork, grilles and controls, etc. Supply and
exhaust air fans can utilise compact axial fans to save plant space. The fans and ductwork will be provided with
noise treatment to meet acoustic requirements.
Supply and exhaust air ductwork design will be coordinated with the structural slabs/beams to achieve the
required minimum head room clearance within the carpark.
Exhaust air is ducted to the discharge louvres with minimum separation distance of 6m from any natural
ventilation openings or mechanical outside air intakes.
Supply air will be drawn by fans from louvres in external wall on the south façade of ground floor. Some makeup
air will be provided via the main entry. If any roller shutter is installed at the entry, it should be perforated with
minimum 40% open area ratio.
Fan speed controls
Ventilation fans are to be fitted with variable speed controllers (VSDs) linked to carbon monoxide (CO) monitoring
system. VSDs fan controls will save energy and operational cost while maintaining atmospheric contaminant
levels in the carpark to AS1668.2 requirements.
Fire mode operation
The carpark mechanical ventilation system shall operate at full ventilation rate once activated for fire mode
operation. Supply air fans shall shut down upon the detection of smoke in the supply air.
20180054 Return Services Brief [2] Page 7 of 23
Potential alternative jet fan solution
An alternative carpark jet fan solution to the carpark ventilation may be suitable and can be developed in future
design phases. The jet fan solution will require CFD modelling to verify it can achieve equivalent ventilation
performance.
Once the CFD modelling is complete, a fire safety engineer will be required to complete an assessment to
confirm that this option can be accepted as a performance solution.
Air conditioning and ventilation for retail areas
Refrigerant pipework risers and roof plant areas should be allowed for future air conditioning (AC) equipment
serving the retail areas.
A fire rated kitchen exhaust shaft from ground floor to the roof are proposed at each of the three lift core areas for
future food retailers.
If the tenancy doors and windows remain closed during business hours, facade louvres will be required as part of
makeup air provision for the kitchen exhaust. Façade louvres will also be required for ducted outside air supply
where natural ventilation is unavailable to the tenancy areas.
We understand the air conditioning and ventilation systems serving the retail areas will be part of the future
tenancy fitout.
Air conditioning for apartments
Split ducted air conditioning units concealed within the ceiling bulkhead are recommended for the apartments. The sizes of each split AC unit are approx. 1.3m wide x 1m long x 0.35m high. The supply air will be reticulated from the unit to each room with flexible ductwork and side blow bar grilles.
Each AC unit will be provided with an air-cooled condensing unit located on the roof/plant area. The sizes of each condensing unit are approx. 1.2m high x 1m wide x 0.4m deep. The condensing units will require 1m clearance at the front, 0.3m at the rear and 0.3m on the sides.
The refrigerant pipe riser shall have a minimum space of 150mm wide x 100mm deep for each split air conditioning system. Refrigerant pipework risers are located in the common corridor areas. This allows for any future replacement or maintenance access.
Multi-head split AC systems may be provided to the apartments where the distance from indoor AC unit to the roof condensing unit does not exceed piping length limits.
Ventilation for apartments
The apartments require either natural ventilation or mechanical ventilation for each occupied space to meet BCA
F4.6 ventilation requirements.
The opening area of the natural ventilation device (e.g. operable window) is required to be 5% of the floor area as
a minimum. Where natural ventilation is not achievable, a ducted outside air supply system will be provided as
part of mechanical ventilation to each apartment.
Exhaust to apartment wet areas
20180054 Return Services Brief [2] Page 8 of 23
The domestic kitchen rangehood exhaust and bathroom/laundry exhaust can be ducted horizontally to the façade
louvres of each apartment.
Ductwork from the apartments to the façade will be concealed within the ceiling and require approximately 0.2m
high ceiling space. Make-up air for the exhaust is via. external door/window openings.
Ventilation for common areas
Outside air supply will be ducted to the enclosed common areas where natural ventilation is unavailable.
Mechanical exhaust will be provided to the enclosed gas meter cupboards.
Both supply and relief air will be provided to the main switch room for code compliance and temperature control.
Supply air will be drawn from the louvres on ground floor and relief air from the switch room can be discharged
into the carpark.
Toilet exhaust system
A separate toilet exhaust will be provided to the public toilet areas on ground floor. We recommend the exhaust
discharge louvres to be located at eastern façade high level on ground floor next to the garbage room and holding
area.
Grease arrestor room exhaust
Mechanical exhaust system will be provided to the grease arrestor room.
Garbage room exhaust
Mechanical exhaust to the ground floor garbage room and holding area is recommended, although natural
ventilation by openable entry door satisfies code requirements. Mechanical exhaust controls odour more
effectively than natural ventilation.
Mechanical exhaust to the basement garbage room and the ground floor garbage room shall consist of fans,
ductwork, grilles and exhaust discharge louvres.
20180054 Return Services Brief [2] Page 9 of 23
Electrical Services
Design compliance standards
The electrical services installation shall be designed to comply with the following statutory compliance standards
and codes:
• The latest Australian Standards having jurisdiction over the works and materials within this development, in
particular
− Wiring Rules [AS/NZS 3000]
− Selection of Cables [AS 3008]
− Interior Lighting [AS 1680]
− Emergency Lighting and Exit Signage [AS/ NZS 2293]
− Public lighting [AS 1158]
• New South Wales Service and Installation Rules
• The requirements of the National Construction Code
• Industrial safety code regulations including Workplace Health & Safety regulations
• Regulations and requirement of Supply Authority
Extent of works
The extent of electrical works associated with the project shall encompass:
• Substation
• Consumer mains
• Main Switchboard
• Metering
• Submains and cable reticulation
• Distribution boards
• General power distribution
• General Lighting
• Emergency and exit lighting
• Telecommunications
• MATV/PayTV
• Intercom and access control
• CCTV
• Apartment general power and lighting allowances
• Photovoltaic system
Substation
The supply to the development will be taken from an off-site Padmount substation located on the opposite side of
the proposed road to the project site. This will require easements allocated on the adjacent site in favour of the
project site. The Padmount substation easement dimensions are 5500 (W) x 2750 (D). The Padmount substation
requires a 2000 (W) easement from the site boundary to the kiosk substation for HV cabling and 24hr, 7 day a
week unimpeded 27 ton truck access with dimensions 3500 (W) x 4400 (H).
20180054 Return Services Brief [2] Page 10 of 23
The Padmount substation itself is approx. 1400 (W) x 3200 (L) x 1600 (H) and must not be located within;
• 1:100 flood level or in stormwater paths
• 10000 of an external fire hydrant/fire pumps etc
• 6000 of any ventilation opening
• 3000 of any part of a building unless it is 180/180/180 FRL & 2kPa blast
• 3000 from site boundary unless provided with 180/180/180 FRL & 2kPa blast wall
• 3000 of any glazing and fire exits
The above will need to be coordinated and agreed with the proposed design of the adjacent structures.
Consumer Mains
Consumer mains will be sized to match the building maximum demand of 327 A/phase plus a spare capacity of
20%.
The consumer mains will commence from the proposed substation low voltage board, and reticulate via inground
conduits across the road, then on cable tray through the carpark to the main switchboard.
The consumer mains will be fire rated copper cable installed on fire rated cable trays in accordance with the
requirements of the Wiring Rules (AS3000).
Main Switchboard
A main switchboard will be installed in a main switchroom at the basement 1. This room will contain the main
switchboard, authority meters, power factor correction equipment, and a house services distribution board.
The main switchboard will be designed in accordance with Endeavour Energy’s supply standards, the
requirements of AS3000 and AS3439.1 and will comprise service protection device, main switch, moulded case
circuit breakers and surge protection device.
Metering
We propose that retail, house and residential authority meters are located within the main switchroom. This
means that the main switchroom is required to be larger, but the risers through the residential levels are much
smaller.
In addition to the authority metering, private energy monitoring shall be provided in accordance with NCC section
J8 for house services, including:
• Life safety services
• Lifts
• Mechanical plant
• Hydraulic plant
• Fire protection plant
• Artificial lighting
• General power
Submains and Cable Reticulation
20180054 Return Services Brief [2] Page 11 of 23
Sub-main reticulation between the main switchboard, distribution boards and apartment distribution boards will be
through the electrical risers and on cable trays at high level through the carpark and in ceilings along the
corridors. This will be coordinated with the communication cabling systems and other services.
Sub-mains will be fire rated for life safety services or XLPE/PVC with Copper conductors for others.
The size and type of sub-main cables will be based on AS3000, AS3008, NCC and Supply Authority requirement
with appropriate diversity incorporated in the design.
Sub-mains will be sized for connected load with an additional 20% spare capacity at time of design.
Distribution boards
House distribution boards will be provided in the main switchroom.
The distribution boards will be wall mounted IP42 split chassis proprietary manufacture type. Lighting and power
outlet sub-circuits will be provided as required with combination circuit breaker / RCD devices as per current code
requirements. Single pole sized units will be specified maintaining spatial capacity within the distribution boards.
There will be 20% spare capacity allowed in the design of the distribution boards.
Retail tenancies shall be provided with a dedicated distribution board located within that tenancy.
Each residential apartment shall be provided with individual distribution boards installed in a cupboard above
fridge or recessed into the wall for adaptable apartments. Residential apartments shall be provided with the
following circuits as a minimum:
• General power
• General lighting
• Laundry power
• Kitchen power
• Oven
• Air conditioning
General power distribution
General power and cleaner’s outlets will be provided throughout as required.
Special purpose power outlets/supplies will be provided for plant.
Outlets of appropriate IP rating will be provided to wet areas or where exposed.
House power dedicated outlets will be provided for electrical equipment/appliances including:
• Security system
• Hydraulic services pumps
• Fire services pumps
• Fire detection system
• Access control system
• Lift service
• Hot Water Units
20180054 Return Services Brief [2] Page 12 of 23
General lighting
Lighting for the common areas shall be as follows:
Table 3-1 Lighting System
3.10.1. Lighting control systems
Automatic operation of the common area lighting systems (e.g. carpark, circulation spaces) shall be by
occupancy sensors with a 30min run-on timer and some 24hr lighting for safety. Plant rooms shall be controlled
solely by occupancy sensors with a 30min run-on timer. Lighting in fire stairs shall be controlled by occupancy
sensors and dim down to 10% when not in use.
External lighting shall be controlled by timer and daylight sensor.
Emergency and exit lighting
Emergency luminaires will consist of recessed LED luminaires and Exit luminaires located in accordance with the
NCC and AS2293.
All exit signs will be fitted with “running man” decals.
All exit and emergency lights shall be the single point self-contained type with the batteries, charger and inverter
contained within the fittings.
Fire stairs, storage room, garbage room, carpark and similar areas will utilise integral battery/charger packs to the
general lighting.
Description of Area Type of Luminaire Level
Carpark Surface mounted diffused vandal resistant LED batten luminaires with additional LED lowbay type luminaires at carpark entry
80lx loading bays
800lx first 15m, 160lx next 4m
40lx parking spaces and aisles
Corridors, Covered Walkway
Recessed LED down lights 160lx entrances and lobbies
40lx corridors
Communal Open Space, Open Walkway
Bollard/weatherproof wall mounted LED luminaire/LED brick lights. Some LED pole mounted luminaires shall be provided in the landscaped area in conjunction with the landscape plan.
We understand that the external landscaped area shall have low nighttime activity and low risk of crime. As such, we propose AS1158.3.1 category P4 generally and P3 within the large landscaped area
Fire Stairs, services areas
Surface mounted diffused LED batten luminaire
80lx stairs, toilets, stairs and general plant rooms
160lx control panels
Retail tenancies Surface mounted diffused LED batten luminaire
22W/m2 for Retail space
20180054 Return Services Brief [2] Page 13 of 23
Emergency lighting test switch and control systems will be provided on the house services distribution boards.
Communication Cabling and Facilities
NBN connection is currently available for the site. The communications services installation will be designed in
accordance with the requirements of NBN and will include the following systems:
• Conduits for lead in cables
• Adequate spatial clearance as per NBN’s requirements in Basement 1 communications cupboard for main
communications equipment
• Dedicated riser as per NBN’s requirements for each core
• Cable pathways through the whole building consisting of cable trays and conduits in slab from riser to retail
tenancy/residential apartment
• Space for NTD’s in wardrobe of each apartment
• Space for NTD’s in each retail tenancy
• Power supply (GPO) for NBN equipment in each apartment, communications riser and communications
cupboard
• Patch panel and Cat 6 cable from NTD to each outlet in the apartments
• Coordinate the position of the connection point, pits and conduits with NBN
• Dedicated outlets for lift, FIP, Security, Gas and Water Meters
Supply and installation of fibre optic cabling and equipment shall be by NBN and coordinated by the electrical
contractor.
MATV / PayTV Systems
A dedicated digital MATV system will be provided for the building. The system will be capable of receiving all free
to air commercial and Pay TV channels. The system in the building will consist of:
• Digital Aerial on the roof for analogue and digital colour Free-to-Air TV reception.
• Foxtel compliant TV cable connection by underground cable or by satellite plate into the building.
• Headend amplifiers and associated equipment positioned to suit the system in the building. This could be in
the Basement 1 communications cupboard or elsewhere to suit the riser cables.
• Backbone cabling for MATV system including Pay TV ready cables – 5 backbone cables.
• Splitters, switchers in communications riser at floors for individual connections to each apartment.
• Cables from splitters to each apartment TV outlet.
Intercom and Access Control System
An intercom and access control system shall be provided consisting of:
• Wall mounted audio/video intercom within each residential apartment with pedestrian door release, vehicle
entry open and lift call facilities
• Wall recessed weatherproof audio/video intercom at each pedestrian entry with a separate resident proximity
card reader. Pedestrian entry doors shall be provided with electric strikes or magnetic locks
• Bollard mounted weatherproof audio/video intercom at each vehicle entry with a separate resident long range
proximity card reader. Automatic egress control on carpark roller shutter by induction loop.
20180054 Return Services Brief [2] Page 14 of 23
• Proximity card reader within each lift allowing access for residents to their block and level plus communal
spaces only.
• Door monitors (reed switches) with alarms for monitoring perimeter doors.
We understand that retail tenancies will be key lockable. Staff will be able to access the carpark via proximity card
reader.
CCTV System
A CCTV system shall be provided to the building consisting of:
• IP based weatherproof and vandal resistant CCTV cameras at the pedestrian and vehicle entries to the
building
• DVR digital video recorder and monitors within the main communications cupboard with 30 days storage
Apartment General Lighting and Outlet Allowance
The apartments within the development will be provided with the following services:
Room Lights Power Outlets Phone/Data Other
Main bedroom LED Downlights 2 DGPO
2
(1 for PayTV)
MATV and PayTV, two way switching
Main bedroom ensuite
IP44 LED Downlights
1 DGPO Dedicated switch for exhaust fan
Other bedroom LED Downlights 2 DGPO
Bathroom IP44 LED Downlights
1 DGPO Dedicated switch for exhaust fan
Laundry IP44 LED Downlights
1 DGPO on dedicated circuit
Dedicated switch for exhaust fan
Dining LED Downlights 1 DGPO Audio/video intercom
Kitchen
LED Downlights
Fridge x1 GPO
Microwave x1 GPO
Dishwasher x1 GPO
Bench top x2 DGPO
Range hood x1 GPO
Cooktop x1 GPO
Oven Fixed Outlet x1
20180054 Return Services Brief [2] Page 15 of 23
Table 3-2 Apartment General Lighting and Outlet Allowance
Photovoltaic System
A 5kW photovoltaic system shall be provided to the building consisting of:
• A matrix of Photovoltaic panels located on the roof top facing north and fixed on mounting racks to achieve
an angle no less than 15 degrees in horizontal.
• Panels shall be connected to an inverter located on the roof.
• The inverter shall be connected to the main switchboard via cabling within the electrical risers.
Living LED Downlights 3 DGPO
2
(1 for PayTV)
MATV and PayTV
Study LED Downlights 1 DGPO 1
20180054 Return Services Brief [2] Page 16 of 23
Hydraulic Services
Design compliance standards
The Hydraulic Services installations shall be designed and installed to comply with the following standards and
codes:
The latest Australian Standards having jurisdiction over the works and materials within this project, in particular
• National Plumbing and Drainage Codes Parts 1-5 [AS/NZS 3500]
• The requirements of the Building Code of Australia
• Industrial Safety code regulations including Workplace Health & Safety regulations.
Extent of works
The extent of hydraulic works associated with the development is generally as follows:
• Potable water service
• Hot water service
• Sanitary drainage and plumbing
• Stormwater drainage
• Natural gas service
• Metering
Potable water service
Supply of the potable water service to all fixtures used for washing, cooking, drinking, personal hygiene shall be designed in accordance with National Construction Code and AS 3500.1.
Cold water isolation valves shall be provided to each fixture group.
Hose taps with required backflow prevention devices shall be installed within all plant, garbage and trade waste areas to comply with AS3500.1, the National Construction Code (NCC) and local Council requirements.
A cold water isolation valve and Sydney Water meter shall be provided at the property boundary to monitor usage of the development and remote reading capability by Authorities (Sydney Water).
Building will be connected to the planned water main in the Riverstone Street. Meter cupboard will be located on the eastern side of the building next to the gas boundary regulator and meter set and grease arrestor fixed pump out connection point.
Cold water meters are required for each apartment/tenancy to monitor usage within that apartment/tenancy. Refer to the metering clause in this section for spatial requirements associated with the apartment/tenancy metering.
Sydney water will monitor water consumption remotely. Each cold water meter will be equipped with integrated radio transmitter that sends the signal to the central unit connected to SW with mobile connection (SIM card).
A domestic cold water booster pump will be required to provide adequate pressures for the correct operation of fixtures and appliances. The final pump selection (e.g. duties) will be subject to the available pressure and flow within Sydney Waters water main.
20180054 Return Services Brief [2] Page 17 of 23
Hot water service
Supply of the potable hot water service to all fixtures used for washing, cooking, drinking and personal hygiene
shall be designed in accordance with the National Construction Code and AS 3500.4.
The new building shall be designed with independent gas hot water heaters for each apartment in the building.
Continuous flow gas heaters will be located on the apartment balconies and will be equipped with flue diverters.
Additional dedicated electric hot water storage units shall be provided for grease arrestor room, sewer pump out pit room and each bin room. These are approximately 1m wide x 1m long x 1m high each.
Reduced pressure zone devices (RPZDs) will be provided to prevent backflow of water in Bin rooms and in
grease arrestor room.
Hot water reticulation pipework would be constructed of copper tube with 25mm thick thermal insulation.
Tempering valves shall be provided to all resident’s rooms and all sanitary fixtures used primarily for personal
hygiene.
Circulated hot water flow and return system will be applied in the apartments where apartment heaters to the fixtures dead legs exceed 12m in length.
Sanitary drainage and plumbing
Sanitary Drainage and Plumbing is to be provided to all waste fixtures and faucets to comply with AS3500.2, National Construction Code 2016 and Sydney Water Corporation requirements.
The Sanitary drainage system shall connect to the planned Authority Sewer Main which will be built in the Riverstone Street.
Sanitary drainage of levels above the B1 slab will be drained by gravity, however the trade waste lines from GF, grease arrestor outlet and all fixtures from B1 and B2 will be drained towards the sewer pump out pit located in the B2 services room. The B2 Sewer pump out pit and the Grease arrestor needs to be vented directly to the atmosphere. Grease arrestor will be located in the B2 for the 3 tenancies (minimum 1000L per tenancy). There will be fixed pump out spot next to the gas meter to allow the cleaning of the GA by the maintenance company.
System venting is to be via conventional atmospheric type and local venting.
The sanitary drainage system (vertical stacks) serving building upper levels will be designed to the fully vented modified system in accordance with the above mentioned Australian standards.
S-trapped tundishes will be provided to receive condensate water from local air-conditioning drains where
connecting direct to the sanitary system and not via a floor waste.
Floor wastes will also be provided to all apartment meter cupboards. Each floor waste will be connected to a trap
priming device to maintain the water seal in accordance with AS3500.
Stormwater and roof drainage
Building stormwater drainage encompassing the roof and balconies above ground level shall be provided in
accordance with AS3500 and local Council requirements.
Buildings roofs will be drained in to the Rain water harvesting tank (size still to be confirmed) that will overflow in to
the OSD tank (by Civil engineer).
Downpipes shall be concealed where possible, however will not be cast into the structural columns.
20180054 Return Services Brief [2] Page 18 of 23
Balcony rainwater outlets shall be cast within the concrete slab. Final detail and arrangement shall be coordinated
with the project Structural Engineer.
Overflows to all balconies shall be built into the balcony hobs. BSE shall document rainwater outlets to balconies
only. Hob details for overflow provision shall be included as part of the architectural package.
All building stormwater drainage (balconies, roofed areas etc.) shall discharge to the site Civil stormwater drainage system. BSE shall coordinate with the project Civil Engineer for building stormwater connection locations.
The ground, basement and site stormwater system shall be completed by the Civil Engineer.
Natural gas service
The natural gas service and appliances are to be installed in accordance with AS 5601 and Jemena Gas fitting
rules.
The connection to the existing high pressure gas main in the Clark street requires boundary regulator for the
pressure drop from 1050 KPa. However, at this stage, we are proposing to connect to the planned main in the
Riverstone Street. The gas pipework is to extend to the site Boundary Meter set where pressure will be reduced
and is to reticulate to and throughout the building.
A metered gas connection shall be provided to each apartment. A gas connection shall be provided to gas cook
tops and HW Heaters .
Metering
Tenancy/apartment individual meters for Potable water services are to be located within a common area (corridor, lobby etc.) to ensure unrestricted access to the meters. Hot water meters are not required because the hot water system will be individual for each apartment.
The meter cupboards will also contain the Gas, Potable water rising mains and rainwater downpipes from the roofs and should be vertically aligned.
Gas isolation valves for apartments shall be located within the meter cupboards.
20180054 Return Services Brief [2] Page 19 of 23
Fire Services
Design compliance standards
The fire services installations shall be designed to comply with the following statutory compliance standards and
codes:
• The latest Australian Standards having jurisdiction over the works and materials within this development, in
particular
− Portable Fire Extinguishers and Fire Blankets [AS 2444-2001]
− Installation of Fire Hose Reels [AS 2441-2005]
− Fire Hydrant System [AS2419-2005]
− Fire Detection, Warning, Control and Intercom Systems [AS 1670.1, AS 1670.3, AS1670.4-2015]
• The requirements of the Nation Construction Code 2016.
• Industrial safety code regulations including Workplace Health & Safety regulations.
Extent of works
The extent of the fire services works shall encompass:
• Fire hydrant compliance
• Fire hose reel compliance
• Portable fire extinguishers
• Automatic fire detection and warning system
Fire hydrant system
The development shall be supplied and equipped with a Fire Hydrant System in accordance with the BCA Section
E1.3 and AS2419 – 2005. The fire hydrant system shall serve all levels of the development.
The Fire Hydrant System shall be subject to the requirements of Clause 3.2.3 of AS2419.1 and associated
clauses such that the development shall comprise of internal hydrants throughout the building to provide full
coverage from a 10m hose stream issued from a 30m hose. Fire Hydrants shall not obstruct egress routes.
Fire hydrants will be located within the fire stair landings on each floor and will be directly connected to the riser
pipe within the fire stairs in the building. Where coverage from the fire stair is insufficient to cover an area
completely, additional fire hydrants will be provided in readily accessible areas to provide the coverage.
5.3.1. Fire Service Water Provision and Pumps
The fire protection services shall be accommodated with a city municipal water supply provided that the source of
water for the fire hydrant installations shall be not less than that necessary to satisfy the minimum flow
requirements of the hydrant system. Connection to the reticulated water supply shall comprise of a single
compression ignition engine fire pump and comply with the requirements of AS2941-2013.
Provided that the fire pump/s are located internally of the development and building not sprinklered, the
pumproom shall have a door opening to a road or open space, or a door opening to fire-isolated passage or stair
which leads to a road or open space.
20180054 Return Services Brief [2] Page 20 of 23
Final assessments shall be validated once Sydney Water’s flow and pressure information is available for the
development.
Fire hose reels
The development shall be supplied and equipped with a Fire Hose Reel System in accordance with the BCA
section E1.4 and AS2441-2005.
Fire hose reels will be located within 4m of fire exits within the building. Where coverage from the fire exits is
insufficient to cover an area completely additional fire hose reels will be provided to provide the coverage. The fire
hose reels will be connected to a metered water supply.
Automatic fire alarm & detection system
The development shall be supplied and equipped with an Automatic Fire Alarm & Detection System in
accordance with BCA section E2.2a and AS1670.1-2015. The building shall comprise of a fire detection system
connected to a new Fire Indicator Panel located at the main entrance on ground level. Smoke detection shall be
located throughout the ground level commercial tenancies and residential suites. A new private provider call out
facility will be connected to the new Fire Indicator Panel for fire brigade notification.
The new system will be an addressable system and will use fire signatures or multiple detection criteria to
eliminate false alarms.
Portable fire extinguishers
The new development shall be supplied and equipped with Portable Fire Extinguishers. Assessment of the
building by the BCA Consultant shall confirm locations and areas where required.
Portable fire extinguishers will be mounted on walls or in cupboards/alcoves within 4m of fire stairs on the
apartment floors and next to hose reels on the commercial and basement floor levels.
AB(E) type portable fire extinguishers will be located adjacent to each hose reel. CO2 type portable fire
extinguishers will be located at all significant switchboards and essential services boards. Portable fire
extinguishers will be located in plantrooms and the like.
Testing, commissioning, maintenance and certifications
Testing, commissioning, 12 months warranty and maintenance will be provided as part of the scope of works.
Essential Services certifications will be provided at practical completion and at the end of the 12 months warranty
and maintenance period.
20180054 Return Services Brief [2] Page 21 of 23
Vertical Transportation
Design compliance standards
The Vertical Transportation Services installations shall be designed and installed to comply with the following
standards and codes:
The latest Australian Standards having jurisdiction over the works and materials within this project, in particular:
• AS SAA Lift Code;
• AS 1735. Lifts, Escalators and Moving Walks;
• AS 1735.1 General Requirements;
• AS 1735.2 Passenger and goods lift – Electric;
• AS 1735.11 Fire-rated landing doors;
• AS 1735.12 Facilities for persons with disabilities;
• AS 4431. Guidelines for Safe Working on New Lift Installations in New Constructions;
• Building Code of Australia;
• National Construction Code;.
Extent of works
The extent of works include the supply, installation and commissioning of four (4) passenger (MRL) motor-room-
less lifts. Each lift has a speed of 1/ms, a simplex orientation and serves a total of up to 6 levels. Each lift has
dimensions as follows:
Item Details
Duty (Passenger Rating) 1150kg (15 passengers)
Car Details
Clear Internal Car Width 1400mm
Clear Internal Car Depth 2000mm
Clear Internal Car Height 2400mm
Entrance Details
Entrance Width 1000mm
Entrance Height 2100mm
Shaft Details
Clear Internal Shaft Width 2200mm
Clear Internal Shaft Depth 2400mm
Pit Depth 1400mm
Overrun 3900mm
Lifts will also be provided with:
• Proximity card reader.
• Wiring provision for digital CCTV cameras.
• Emergency lowering units.
• Low level interfaces with the access control system (BMS).
• Low level interfaces with the Automatic fire detection system.
20180054 Return Services Brief [2] Page 22 of 23
All Lifts shall include Variable Voltage Variable Frequency (VVVF) motor drives with Regenerative Drive features
which allows the elevator to generate power back into the electricity grid when the out of balance load is assisting
the direction of travel.
Additional equipment features that will be specified to reduce the power consumption of the lift system include:
• High efficiency permanent gearless motors.
• LED down lights.
• Motion sensing / timing devices to turn off elevator car lighting and ventilation fans when the elevator is not in
use.
• Halogen free cables.
• Signalisation dimming- timing devices to turn off elevator car and landing signalization to preserve energy.
• Regenerative Systems would recover excess braking energy from the elevator and converts it for use.
20180054 Return Services Brief [2] Page 23 of 23
Appendix - Services spatial markups
ar--1200
1:100
-07
24/04/18Basement 2 Floor Plan
landscape architecture, interior design
planning, urban design, architecture,proj no.
rev no.drwg no.
date
dem
dem
documents, advice or other material prepared by any other party.
limited. (aust) pty limited expressly takes no responsibility for any
or information and does not constitute a representation by (aust) pty
the sole representation of the party who prepared the report drawings, advice
prepared and/or provided by any other party, including the client/principal, is
any reports, drawings, advice or information included or referenced that is
demC copyright of (aust) pty limited abn 92 085 486 844. 24/04/18 VIpplotted: plotted by:
po box 5036 west chatswood nsw 1515p:
t: (02) 8966 6000
www.dem.com.auw:
nominated architects: Rudi Valla BArch (Hons) nsw reg no 6582 Jon Pizey BArch nsw reg no 6567
4465-00
scale @ A1
DA DRAFT14 CLARKE STREET RIVERSTONE MIXED-USE DEVELOPMENT
2500
1:20
2800
RESIDENTIAL CAR PARK
COM
CORE
RESI
CORE
RESI
CORE
2600
8800
RESI
CORE
1:40RL 26.107
1000
25002500
1:11
RESIDENTIAL CAR PARK
RL 27.142
RL 27.152 RL 27.757
BULKY/
RECYCLE
ITEMS
STORE
GARBAGE
R
GG G
R
R
R
R
R
R
R
GG G GG G G
G GG GGGG G G G
8960
6250
4310
1:20
2800
7400 8110
RL 26.547
26002600
5500
7000
5500
8142
1976
978
3976
1832
3870
6770
GG G
SHUTTER
ROLLER
R1R2R3R4
1000
R11R12R13R14R15R16R17R18R19
STORE
4M3
4M
34
M3
4M3
4M3
4M3
3.5M3
4.7
4 M
3
1250
1250
1000
3M3
H
FHR
LOW WALL
FHR
260025001000 30026002600
ST ST ST ST ST ST ST ST ST
ST
ST
ST
ST
ST
ST
ST
ST
R20R21R22R23R24R25R26R27R28R29R30R31
3M3
3M3
4.5 M
3
280028002800 260026002600 28002800 2400
3050 28002400 25002400
ST
2800
V4V5V6C3C4C5
280028002800 247524752475
5800
9710
RL 26.790
2870
2620
PLANT ROOM
PLANT ROOM
1317019340
Height Limit 12M
FSR N/A
Dwelling Density
Planning Requirements Based on SEPP
(sydney region growth centres 2006)
R3 (Medium Density Residential)
25/HA
Allowance UsesNeighbourhood Shops
Shop Top Housing
Residential Flat Building
SEPP65 COMPLIANCE
Solar Access
Cross Ventilation
Required Achieved
Min 70%
Min 60%
Max 15%No Direct Sunlight
Deep Soil Planting Min 7%
Required Achieved
TABLE 4-10: Key controls for residential flat buildings, manor homes and shop top housing
(Blacktown City Council Growth Centre Precincts DCP 2016)
Site coverage (maximum)
Landscaped area (minimum)
Communual open space
Principal POS
Front setback (minimum)
Cnr lots secondary street
setback (minimum)
Side setback (minimum)
Rear setback (minimum)
50% of site area
30% of site area
15% of site area
where the
development includes
≥ 4 dwellings
Determined by ground
floor setback
2M
6M
4M (excluding garages)
6M
37% of site area
6M
6M
8.4M
44% of site area
Zoning
Communal Open Space
Min. 8m² per dwelling
with min. dimension
of 2.0m
Min 25%
Min. dimension of 2m for
all balconies with larger
balconies to the north
26% of site area
UrinalsUser Group Closet Pans Washbasins
Male Employees
Female Employees
1
3 -
2 2
2
1 1Unisex accessible
Sanitary Facilities calculated on the basis of Normal Retail Shops (85 Male and 85 Female)
Ground
Level 1
Level 2
Total
1B 2B 3B Total
11
6
2814
Level 3
- - -
6
6 11
3
1
-
12
-
-
-2 1
1 2 1
5 1
3.6%17.9% 10.7%
-
2B
(dual key)
Studio
(dual key)
2
2
1
5
17.8%
Car Parking Requirement as per BCC DCP
Ratio 1 1 211
1B 2B 3B Total2B
(dual key)
Studio
(dual key)
5 3 5 14 2 29
Vistor Ratio 0.4 space per dwelling 28x 0.4 = 11
50%
Unit Mix (numbers of sole occupancy units)
Retail 1 Space Per 22Sq.m GFA 519/ 22 = 24
64Total
Total
65
Car space provided
Basement 1 Basement 2
3233
BCA Compliance: Part F2 Sanitary & Other Facilities Deemed-to
Satisfy Provisions
Required
8%
85% (24 apts)
67.8% (19apts)
7%(2apts)
28%
5007
arsk
1
5008
arsk
2
5009
arsk
3
FH FH
FHR FHR
FIRE SERVICE NOTES:
FIRE EXTINGUISHERS/BLANKETS SHALL COMPLY TO THE REQUIREMENTS OFAS2444-2001.
FIRE HOSE REELS TO BE LOCATED THROUGHOUT THE CARPARK LEVELS AND TOSERVE ALL COMMERCIAL/ RETAIL TENANCIES AREAS.900W x 450DALL LEVELS WITHIN 4m OF FIRE EXITS/COMMON EXITSCENTER FHR HEIGHT ABOVE FFL BETWEEN 1.5m - 2.4mCABINETS OR CUPBOARDS TO HOUSE FHR's ARE OPTIONAL.ADDTIONAL SUPPLEMENTARY FHR's MAY BE REQUIRED SUBJECT TO 36m TRAVELDISTANCES.
FIRE HYDRANTS ARE TO BE LOCATED WITHIIN ALL FIRE STAIRS AT EACH LEVEL.750mm ABOVE FFL.ACCESS/EGRESS PATH WITHIN FIRE STAIR TO CLEAR LANDING VALVES.TO BE PROVIDED ON LANDINGS OF ALL FIRE STAIRS AT ALL LEVELS.1m CLEAR SPACE IN FRONT AND 300mm CLEARANCE AROUND EACH VALVEREQUIRED.SUPPLEMENTARY FH's MAY BE REQUIRED SUBJECT TO 30m HOSE TRAVELDISTANCES.
FIRE PUMP ROOM - FINAL REQUIREMENTSSUBJECT TO PRESSURE AND FLOW INWATER MAIN.
FIRE PUMPS TO BE PROVIDED TO THEREQUIREMENTS OF AS2941 - 2013.
FIRE PUMP ROOM TO HAVE MIN SPACE OF5.5m (L) x 3.5m (W) x 2.1m (H). PUMP ROOMTO HAVE DIRECT ACCESS TO ROAD OROPEN SPACE VIA A FIRE ISOLATED STAIROR PASSAGE.
WE DON'T EXPECT FIRE STORAGE TANKSARE REQUIRED. HOWEVER,REQUIREMENTS SHOULD BE CONFIRMEDONCE SYDNEY WATER AND FLOWINFORMATION IS AVAILABLE.
FHR
FIR
E P
UM
P
FIR
E P
UM
P
FHR
Ex Ex Ex
2,000L SEWER PUMP OUT PIT.
PUMP OUT PIT NEEDS TOCATER FOR:GREASE WASTE LINE FROM 3RETAIL SHOPS THAT WILL BEDRAINED TOWARDS THEGREASE ARRESTOR ON B2.B2 BIN ROOMS ANDPLANTROOMS DRAINAGE.B1 RESTAURANT ANDPLANTROOMS AREAS.CONTROL PANEL TO BELOCATED ON SERVICES ROOMWALL WITH VISUAL ALARM.
3000L GREASE ARRESTOR 3 X 1000 L PER RETAIL SHOP.2.8m x 1.3m x 1.6m HIGH WITH 1mCLEARANCE AROUND TANK TO BE WITHIN ROOM. TANK TO HAVE MIN1.6m CLEAR SPACE DIRECTLY ABOVEFOR MAINTENANCE. GREASE TRAPTO BE INSTALLED ON A 100mmCONCRETE PLINTH. ROOM TO BEMECHANICALLY VENTILATED.
GREASE ARRESTOR ANDSEWER PUMP PIT CHAMBERVENTS TO BE TERMINATEDABOVE ROOF LEVEL 2 X 100mm VENT PIPE.250 x 300 mm RISER REQUIREDFROM B1 UP TO ABOVE THETOP LEVEL
HWU
TYPICAL WATER DRAINAGEARRANGEMENT FOR GAROOM, BIN ROOMS, SERVICESPLANT ROOMS:
50L ELECTRIC STORAGE HOTWATER UNIT.HOT AND COLD WATER TAPSTO BE PROVIDED FORWASHING. RPZD TO BE INSTALLED ONTHE CW FEED LINE.BTFW FOR THE FLOORDRAINAGE.TUNDISH TO BE INSTALLEDBELOW THE RPZD.SPACE REQUIRED1m x 1m x 1m HIGH.
100 mm GREASE ARRESTOR FIXEDPUMP OUT CONNECTION LINE TO BEINSTALLED FROM THE GAVERTICALLY UP TO THE SUCTIONCONNECTION POINT ON GF NEXT TOTHE GAS AND WATER METERS.THIS PUMP OUT CONNECTION ISUSED FOR THE GREASE ARRESTORCLEANING PURPOSES.OVERALL LENGTH OF THE SUCTIONLINE IS APPROX. 6 METERS FROMTHE GA.
SEWER PUMPOUT PITPRESSURE LINE TO BECONNECTED TO THEHORIZONTAL SEWER LINE ATH/L B1.
300x300 Internal clearanceGarbage riser to above
600x300
DG
650x300 Internal clearancecarpark supply riser from above
700x300 Internal clearancecarpark exhaust riser to above
Carpark exhaust ductwork athigh level, to be coordinatedwith structural slab/beams.-Typical
700x300 Internal clearancecarpark exhaust riser to above
Carpark exhaust ductwork athigh level, to be coordinatedwith structural slab/beams.-Typical
650x300 Internal clearancecarpark supply riser from above
Carpark supply ductwork at highlevel, to be coordinated withstructural slab/beams.-Typical
300x200 Internal clearancegrease arrestor exhaust riser toabove
Building Services Engineers Pty Ltd
Date..27/04/2018...
By...myan,SAluague, RDruce.
FOR INFORMATION ONLY
ar--1201
1:100
-07
24/04/18
Basement 1 Floor Plan
Retail/Mix Use Option 6B landscape architecture, interior design
planning, urban design, architecture,proj no.
rev no.drwg no.
date
dem
dem
documents, advice or other material prepared by any other party.
limited. (aust) pty limited expressly takes no responsibility for any
or information and does not constitute a representation by (aust) pty
the sole representation of the party who prepared the report drawings, advice
prepared and/or provided by any other party, including the client/principal, is
any reports, drawings, advice or information included or referenced that is
demC copyright of (aust) pty limited abn 92 085 486 844. 24/04/18 VIpplotted: plotted by:
po box 5036 west chatswood nsw 1515p:
t: (02) 8966 6000
www.dem.com.auw:
nominated architects: Rudi Valla BArch (Hons) nsw reg no 6582 Jon Pizey BArch nsw reg no 6567
4465-00
scale @ A1
DA DRAFT14 CLARKE STREET RIVERSTONE MIXED-USE DEVELOPMENT
1:8 1:201:8
RL 30.300
2620
3870
62530
1:20
COMMERCIAL CAR PARK
COM
CORERESI
CORE
1
9300
2900 24002400 2600
13810
29
30
RESI
CORE
2400
22002800
2600
1:8
RL 30.068 RL 29.377
RL 28.531
5
878
1000
3000
1:8
RESI
CORE
RL 30.757
1:40 1:20
5500
7000
5500
PLANT
ROOM
5500
RL 33.675
60187000162902000
RL 35.000
1:5
9120
6770
5500
RL 34.500
RL 35.000
1050C16C17C20C21
1250
1000
CONVEX
MIRRORCONVEX
MIRROR
C19C23V7V8V9V10
C24
2500
SHUTTER
ROLLER
1000
RL 29.064
RL 30.300 RL 34.850
RL 34.550 RL 30.550
5500
7000
5500
C1C2C3C4C5C6C7C8C9C10C11C12C13C14C15 V1V2V3V4V5V6
28002800 260026002600 250025002500 28002800280028002800
2600260026002600
C18
ST ST STSTSTST ST ST
28002800
C21
ST
5800
2800
2475247524752800 280028002800
25502550
OSD ABOVE RAMP DOTTED RWT
ABOVE
RAMP
DOTTED
PLANT
ROOM
PLANT
ROOM
Height Limit 12M
FSR N/A
Dwelling Density
Planning Requirements Based on SEPP
(sydney region growth centres 2006)
R3 (Medium Density Residential)
25/HA
Allowance UsesNeighbourhood Shops
Shop Top Housing
Residential Flat Building
SEPP65 COMPLIANCE
Solar Access
Cross Ventilation
Required Achieved
Min 70%
Min 60%
Max 15%No Direct Sunlight
Deep Soil Planting Min 7%
Required Achieved
TABLE 4-10: Key controls for residential flat buildings, manor homes and shop top housing
(Blacktown City Council Growth Centre Precincts DCP 2016)
Site coverage (maximum)
Landscaped area (minimum)
Communual open space
Principal POS
Front setback (minimum)
Cnr lots secondary street
setback (minimum)
Side setback (minimum)
Rear setback (minimum)
50% of site area
30% of site area
15% of site area
where the
development includes
≥ 4 dwellings
Determined by ground
floor setback
2M
6M
4M (excluding garages)
6M
37% of site area
6M
6M
8.4M
44% of site area
Zoning
Communal Open Space
Min. 8m² per dwelling
with min. dimension
of 2.0m
Min 25%
Min. dimension of 2m for
all balconies with larger
balconies to the north
26% of site area
UrinalsUser Group Closet Pans Washbasins
Male Employees
Female Employees
1
3 -
2 2
2
1 1Unisex accessible
Sanitary Facilities calculated on the basis of Normal Retail Shops (85 Male and 85 Female)
Ground
Level 1
Level 2
Total
1B 2B 3B Total
11
6
2814
Level 3
- - -
6
6 11
3
1
-
12
-
-
-2 1
1 2 1
5 1
3.6%17.9% 10.7%
-
2B
(dual key)
Studio
(dual key)
2
2
1
5
17.8%
Car Parking Requirement as per BCC DCP
Ratio 1 1 211
1B 2B 3B Total2B
(dual key)
Studio
(dual key)
5 3 5 14 2 29
Vistor Ratio 0.4 space per dwelling 28x 0.4 = 11
50%
Unit Mix (numbers of sole occupancy units)
Retail 1 Space Per 22Sq.m GFA 519/ 22 = 24
64Total
Total
65
Car space provided
Basement 1 Basement 2
3233
BCA Compliance: Part F2 Sanitary & Other Facilities Deemed-to
Satisfy Provisions
Required
8%
85% (24 apts)
67.8% (19apts)
7%(2apts)
28%
FH FH
FHR FHR
FH
R
FIRE SERVICE NOTES:
FIRE EXTINGUISHERS/BLANKETS SHALL COMPLY TO THE REQUIREMENTS OFAS2444-2001.
FIRE HOSE REELS TO BE LOCATED THROUGHOUT THE CARPARK LEVELS AND TOSERVE ALL COMMERCIAL/ RETAIL TENANCIES AREAS.900W x 450DALL LEVELS WITHIN 4m OF FIRE EXITS/COMMON EXITSCENTER FHR HEIGHT ABOVE FFL BETWEEN 1.5m - 2.4mCABINETS OR CUPBOARDS TO HOUSE FHR's ARE OPTIONAL.ADDTIONAL SUPPLEMENTARY FHR's MAY BE REQUIRED SUBJECT TO 36m TRAVELDISTANCES.
FIRE HYDRANTS ARE TO BE LOCATED WITHIIN ALL FIRE STAIRS AT EACH LEVEL.750mm ABOVE FFL.ACCESS/EGRESS PATH WITHIN FIRE STAIR TO CLEAR LANDING VALVES.TO BE PROVIDED ON LANDINGS OF ALL FIRE STAIRS AT ALL LEVELS.1m CLEAR SPACE IN FRONT AND 300mm CLEARANCE AROUND EACH VALVEREQUIRED.SUPPLEMENTARY FH's MAY BE REQUIRED SUBJECT TO 30m HOSE TRAVELDISTANCES.
Ex
Ex Ex
POTABLE COLD WATERPUMP 2.5m (L) x 2.5m (W).PUMP TO HAVE MIN 1mCLEARANCE IN FRONTOF PUMPSET.
IRRIGATION PLANT.SUCTION LINE FROMTHE RW HARVESTINGTANK TO BECONNECTED TO THEIRRIGATION FILTER ANDPUMP SET.
GREASE ARRESTOR ANDSEWER PUMP PIT CHAMBERVENTS TO BE TERMINATEDABOVE ROOF LEVEL 2 X 100mm VENT PIPE.250 x 300 mm RISER REQUIREDFROM B1 UP TO ABOVE THETOP LEVEL
100mm GREASE ARRESTOR FIXEDPUMP OUT CONNECTION LINE TO BEINSTALLED FROM THE GAVERTICALLY UP TO THE SUCTIONCONNECTION POINT ON GF NEXT TOTHE GAS AND WATER METERS.THIS PUMP OUT CONNECTION ISUSED FOR THE GREASE ARRESTORCLEANING PURPOSES.OVERALL LENGTH OF THE SUCTIONLINE IS APPROX. 6 METERS FROMTHE GA.
HWU
TYPICAL WATER DRAINAGEARRANGEMENT FOR GAROOM, BIN ROOMS, SERVICESPLANT ROOMS:
50L ELECTRIC STORAGE HOTWATER UNIT.HOT AND COLD WATER TAPSTO BE PROVIDED FORWASHING. RPZD TO BE INSTALLED ONTHE CW FEED LINE.BTFW FOR THE FLOORDRAINAGE.TUNDISH TO BE INSTALLEDBELOW THE RPZD.SPACE REQUIRED1m x 1m x 1m HIGH.
MAIN COMMUNICATIONS CUPBOARDWITH 2 DOUBLE DOORS COMPRISES NBNEQUIPMENT, CCTV RECORDING DEVISE.3m(W) x 0.9m(D).ENSURE CUPBOARD DOORS IS NOTOBSTRUCTED BY PARKING SPACE.
E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
INDICATIVE CABLE TRAY ROUTE FORELECTRICAL CABLING RETICULATION
EE
EE
EE
EE
E
EEEEE
EE
E
EEE
INDICATIVE LOCATION OFCOMMS RISER 700mm (W) x300mm (D)FOR FLOORTRANSITION IN BASEMENTS
INDICATIVE LOCATION OFELECTRICAL RISER 700mm (W)x 300mm (D)FOR FLOORTRANSITION IN BASEMENTS
T
TTTT
MAIN SWITCHROOM COMPRISES MSBHOUSE SERVICES DISTRIBUTION BOARDAND METERING AND REQUIRES 2HR FIRERATING AND TWO ENTRANCES (ONEDOUBLE DOORS) ON OPPOSITE SIDES OFTHE ROOM. 4.2m x 2.5m.ENSURE ROOM EXIT IS NOT OBSTRUCTEDBY PARKING SPACE.
CT
LD
VR
300x300 Internal clearanceGarbage riser from belowto above
200x200 Internal clearanceExhaust riser to above
200x200 Internal clearancesupply riser from above
300x150 ExternalDimension SidewallBargrille
250x250 External DimensionExhaust Ductwork
700x300 Internal clearance carparkexhaust riser from below
1200x350 Internal clearancecarpark supply riser from above
650x300 Internal clearancecarpark supply riser to below
1200x500 Internal clearancecarpark exhaust riser to above
700x300 Internal clearance carparkexhaust riser from below
Carpark exhaust ductwork athigh level, to be coordinatedwith structural slab/beams.-Typical
1200x350 Internal clearancecarpark supply riser from above
Carpark supply air fan at highlevel of the plant room.
-Typical
650x300 Internal clearancecarpark supply riser to below
Carpark supply air fan at highlevel of the plant room.
-Typical
Building Services Engineers Pty Ltd
Date..27/04/2018...
By...myan,SAluague, RDruce.
FOR INFORMATION ONLY
ar--1202
1:100
-08
24/04/18Ground Floor Plan
landscape architecture, interior design
planning, urban design, architecture,proj no.
rev no.drwg no.
date
dem
dem
documents, advice or other material prepared by any other party.
limited. (aust) pty limited expressly takes no responsibility for any
or information and does not constitute a representation by (aust) pty
the sole representation of the party who prepared the report drawings, advice
prepared and/or provided by any other party, including the client/principal, is
any reports, drawings, advice or information included or referenced that is
demC copyright of (aust) pty limited abn 92 085 486 844. 24/04/18 VIpplotted: plotted by:
po box 5036 west chatswood nsw 1515p:
t: (02) 8966 6000
www.dem.com.auw:
nominated architects: Rudi Valla BArch (Hons) nsw reg no 6582 Jon Pizey BArch nsw reg no 6567
4465-00
scale @ A1
DA DRAFT14 CLARKE STREET RIVERSTONE MIXED-USE DEVELOPMENT
RL 32.900
RL 33.100
RL 3
3.1
00
RL 33.500
1000 1000 2200
LANDSCAPE AREA
RL 35.000
1560
RESI
CORE
RESI
CORE
RESI
CORE
COM
CORE
1200
59 Sq. m
46 Sq. m
GR
G
G
G
G
G
G
G
G
G
G
G
G
G
R
R
R
R
R
R
R
C C
C C
6 Sq. m
BULKY/
RECYCLE
ITEMS
STORE
G
G
G
RETAIL GARBAGE
ROOM & HOLDING
AREA
RES
LOBBY 1 RES
LOBBY 1
RES
LOBBY 3
48 Sq. m
61 Sq. m
RL 32.900
66 Sq. m
RL 33.100
23 Sq. m
RL 34.100
RL 33.500 RL 33.500 RL 33.500
MALE
75 Sq. m 61 Sq. m
6000
3770
1270
LE
TT
ER B
OX
LE
TT
ER B
OX
3770
1270
FEMALE1000
FE
MA
LE
576511725
1500
RL 31.000 )(OLD
RL 31.500 )(OLD
RL 30.750 )(OLD
FUTURE RL 32.027
96 Sq. m
G
G
RL 34.500 EX
RL 35.000 EX
RL 34.850
1 IN 14 RAMP
1 IN 14 RAMP
RL 34.310
RL 34.310
RL 33.500
CL
AR
K S
TR
EE
T
ACC.
GA
S
CO
MM
NEIGHBOURHOOD
SHOP 1
NEIGHBOURHOOD
SHOP 2
NEIGHBOURHOOD
SHOP 3
NEIGHBOURHOOD
SHOP 4
NEIGHBOURHOOD
SHOP 5
NEIGHBOURHOOD
SHOP 6
NEIGHBOURHOOD
SHOP 7
8680
RL 34.120
1900
2000
1500
1500
1500
RL 33.900
1100
1500
RL 35.307
RL 34.675
RL 3
3.1
00
RL 34.143
1IN 10
STEP
RAMP
9 Sq. m9 Sq. m9 Sq. m
5.87w x 3.0h
3.13w x 3.0h
5.36w x 3.0h
5.7w x 3.0h
5.5w x 3.0h
5.5w x 3.0h
1.00w x 3.0h
LE
TT
ER B
OX
1.39w x 2.85h
WA
TE
R
G
G
GG
1 in 20
RL 34.650
1 I
N 1
4 R
AM
P
1900
1 in 25 fall
MAX
OSD BELOW
DOTTED
RWT
BELOW
DOTTED
BA
SE
ME
NT O
UT
LIN
E D
OT
TE
D
BA
SE
ME
NT O
UT
LIN
E D
OT
TE
D
BASEMENT OUTLINE DOTTED
BASEMENT OUTLINE DOTTED
BASEMENT OUTLINE DOTTED
BA
L.
OV
ER D
AS
HE
D
AWNING. OVER DASHED AWNING. OVER DASHEDAWNING. OVER DASHED
RL 33.675 RL 34.550
RL 34.850
1:201:81:5
2200
1.17w x 3.0h
7.5w x 3.0h
1.92w x 2.85h 4.18w x 2.85h
2.73w x 3.0h
8.56w x 3.0h
3.97w x 3.0h
6000
6006
2002
6370
1.00wx 3.0h 1.00wx 3.0h 1.00wx 3.0h
2500
4729
8372
AW
NIN
G.
OV
ER D
AS
HE
D
AWNING. OVER DASHED
AW
NIN
G.
OV
ER D
AS
HE
D
BAL. OVER DASHED BAL. OVER DASHED
BUILDING. OVER DASHED
BAL. OVER DASHED BAL. OVER DASHED
2200 1000 1000220010001000
1810
LOUVRE AT HIGH LEVEL
BAL. OVER DASHED
BAL. OVER DASHEDBAL. OVER DASHEDBAL. OVER DASHED
32.00
FUTURE RL 32.237
FUTURE RL 32.132
EX RL 34.00EX RL 33.50EX RL 33.00EX RL 32.50EX RL 32.00
EX RL 31.50EX RL 31.00
FUTURE RL 32.077
FUTURE RL 32.027
SSL 34.075
SSL 34.675 SSL 35.307
RL 33.855 RL 34.105 RL 34.300
RL 34.500
RL 35.000
Height Limit 12M
FSR N/A
Dwelling Density
Planning Requirements Based on SEPP
(sydney region growth centres 2006)
R3 (Medium Density Residential)
25/HA
Allowance UsesNeighbourhood Shops
Shop Top Housing
Residential Flat Building
SEPP65 COMPLIANCE
Solar Access
Cross Ventilation
Required Achieved
Min 70%
Min 60%
Max 15%No Direct Sunlight
Deep Soil Planting Min 7%
Required Achieved
TABLE 4-10: Key controls for residential flat buildings, manor homes and shop top housing
(Blacktown City Council Growth Centre Precincts DCP 2016)
Site coverage (maximum)
Landscaped area (minimum)
Communual open space
Principal POS
Front setback (minimum)
Cnr lots secondary street
setback (minimum)
Side setback (minimum)
Rear setback (minimum)
50% of site area
30% of site area
15% of site area
where the
development includes
≥ 4 dwellings
Determined by ground
floor setback
2M
6M
4M (excluding garages)
6M
37% of site area
6M
6M
8.4M
44% of site area
Zoning
Communal Open Space
Min. 8m² per dwelling
with min. dimension
of 2.0m
Min 25%
Min. dimension of 2m for
all balconies with larger
balconies to the north
26% of site area
UrinalsUser Group Closet Pans Washbasins
Male Employees
Female Employees
1
3 -
2 2
2
1 1Unisex accessible
Sanitary Facilities calculated on the basis of Normal Retail Shops (85 Male and 85 Female)
Ground
Level 1
Level 2
Total
1B 2B 3B Total
11
6
2814
Level 3
- - -
6
6 11
3
1
-
12
-
-
-2 1
1 2 1
5 1
3.6%17.9% 10.7%
-
2B
(dual key)
Studio
(dual key)
2
2
1
5
17.8%
Car Parking Requirement as per BCC DCP
Ratio 1 1 211
1B 2B 3B Total2B
(dual key)
Studio
(dual key)
5 3 5 14 2 29
Vistor Ratio 0.4 space per dwelling 28x 0.4 = 11
50%
Unit Mix (numbers of sole occupancy units)
Retail 1 Space Per 22Sq.m GFA 519/ 22 = 24
64Total
Total
65
Car space provided
Basement 1 Basement 2
3233
BCA Compliance: Part F2 Sanitary & Other Facilities Deemed-to
Satisfy Provisions
Required
8%
85% (24 apts)
67.8% (19apts)
7%(2apts)
28%
FHBV
FIP
FH
R
FHR
FH
R
FH
R
FH
R
FH
RFHR
FH
R
FH
R
FIRE SERVICE NOTES:
FIRE EXTINGUISHERS/BLANKETS SHALL COMPLY TO THE REQUIREMENTS OFAS2444-2001.
FIRE HOSE REELS TO BE LOCATED THROUGHOUT THE CARPARK LEVELS AND TOSERVE ALL COMMERCIAL/ RETAIL TENANCIES AREAS.900W x 450DALL LEVELS WITHIN 4m OF FIRE EXITS/COMMON EXITSCENTER FHR HEIGHT ABOVE FFL BETWEEN 1.5m - 2.4mCABINETS OR CUPBOARDS TO HOUSE FHR's ARE OPTIONAL.ADDTIONAL SUPPLEMENTARY FHR's MAY BE REQUIRED SUBJECT TO 36m TRAVELDISTANCES.
FIRE HYDRANTS ARE TO BE LOCATED WITHIIN ALL FIRE STAIRS AT EACH LEVEL.750mm ABOVE FFL.ACCESS/EGRESS PATH WITHIN FIRE STAIR TO CLEAR LANDING VALVES.TO BE PROVIDED ON LANDINGS OF ALL FIRE STAIRS AT ALL LEVELS.1m CLEAR SPACE IN FRONT AND 300mm CLEARANCE AROUND EACH VALVEREQUIRED.SUPPLEMENTARY FH's MAY BE REQUIRED SUBJECT TO 30m HOSE TRAVELDISTANCES.
DFH
FIP TO BE LOCATED WITHIN ENTRY LOBBY. PROVIDECABINET ENCLOSURE WHERE NECESSARY.
LOCATION TO BE COORDINATED:
FIRE HYDRANT BOOSTER VALVE ASSEMBLY WILL REQUIRE A SPACE OF 2.5m (L) X 1m (W) X 2.1m (H). BOOSTERVALVE ASSEMBLY SHALL BE INSTALLED AGAINST FIRE RATED WALL EXTENDING 2m EITHER SIDE AND 3mABOVE BOOSTER ASSEMBLY. ALTERNATIVELY A PERFORMANCE SOLUTION MAY BE OBTAINED FOR AREDUCED RADIANT WALL PROTECTION REQUIREMENT. A PERFORMANCE SOLUTION WILL ALSO BE REQUIREDTO SATISFY THE LOCATION NOT BEING WITHIN SITE OF THE BUILDINGS MAIN ENTRANCE.
EXTERNAL DUAL FIRE HYDRANT TO BE INSTALLED WITHIN FHBV ENCLOSURE, 1m (W).ACCESS DIRECT TO OUTSIDE.
CLEAR ACCESS IS REQUIRED DIRECTLY INFRONT OF BOOSTER VALVE ASSEMBLIES FOR EASYIDENTIFICATION AND ACCESS BY FRNSW. FINAL LOCATION TO BE CONFIRMED.
6,43
3 m
m
ExEx
Ex
Ex
Ex
RETAILGREASE WASTE AND VENTCONNECTION POINT.TO BE DRAINED TOWARDS3000 L GREASE ARRESTOR INB2.
SW
C S
EW
ER
SW
C S
EW
ER
SW
C S
EW
ER
PLANNED SYDNEY WATER SEWER MAIN. TBC.
SWC SEWER SWC SEWER SWC SEWER
PROPOSED SEWERCONNECTION TO THESYDNEY WATER MAIN.BOUNDARY TRAP.
ePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCW
GAS BOUNDARYREGULATOR AND METERSET.ASSEMBLY 2.5m x 1m x2.1m HIGH. ACCESS REQUIREDDIRECT FROM STREET.ROOM TO BE WELLVENTILATED.
WATER METERASSEMBLYWITHBACKFLOWPREVENTION.2.6m x 0.6m
PLEASE NOTE THAT THE SHOWN LOCATION OF THEGAS AND THE WATER METERS IS IDEAL ONLY IFCONNECTIONS FROM RIVERSTONE ROAD WILL BEPOSSIBLE.THE CONNECTION TO THE EXISTING HIGHPRESSURE GAS MAIN IN THE CLARK STREETREQUIRES BOUNDARY REGULATOR FOR THEPRESSURE DROP FROM 1050 KPa.
PLEASE NOTE THAT IFGREASE ARRESTORCONNECTIONS WILL BEPROVIDED IN THE RETAILAREAS BETWEEN GRIDLINES1 AND 3 GRAVITY DRAINAGETOWARDS GA ON LEVEL B1CAN'T BE ACHIEVEDTHEREFORE THE GA NEEDSTO BE ON B2. HOWEVER IFTHE GA CONNECTIONS AREPROVIDED ONLY IN THEAREAS BETWEEN GRIDLINESBETWEEN 4 TO 10 GA CAN BELOCATED ON B1.
GREASE ARRESTORFIXED PUMP OUTCONNECTION POINT.THIS PUMP OUTCONNECTION IS USEDFOR THE GREASEARRESTOR CLEANINGPURPOSES.OVERALL LENGTH OFTHE SUCTION LINE ISAPPROX. 6 METERSFROM THE GA.
LANDSCAPE PLANTERBOXES AND DRAINAGE FROMTHE PAVED AREAS FROMTHIS LEVEL WILL BEDRAINED DIRECTLYTOWARDS TO OSD TANK(LOCATION TO BECONFIRMED)
HWU
TYPICAL WATER DRAINAGEARRANGEMENT FOR GAROOM, BIN ROOMS, SERVICESPLANT ROOMS:
50L ELECTRIC STORAGE HOTWATER UNIT.HOT AND COLD WATER TAPSTO BE PROVIDED FORWASHING. RPZD TO BE INSTALLED ONTHE CW FEED LINE.BTFW FOR THE FLOORDRAINAGE.TUNDISH TO BE INSTALLEDBELOW THE RPZD.SPACE REQUIRED1m x 1m x 1m HIGH.
Potential requirements of facadelouvres for mechanical outside airand makeup air to the tenancy areas
EE
EE
EE
EE
EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE
EE
EE
EE
EE
E E E
NTD
NT
D
NTD
NTD NTD NTD
NTD
INDICATIVE LOCATION OFCOMMS RISER 700mm (W) x300mm (D)FOR FLOORTRANSITION TO ALL LEVELSABOVE GROUND FLOOR
INDICATIVE LOCATION OFELECTRICAL RISER 700mm (W)x 300mm (D)FOR FLOORTRANSITION TO ALL LEVELSABOVE GROUND FLOOR
INDICATIVE LOCATION OFCOMMS RISER 700mm (W) x300mm (D)FOR FLOORTRANSITION TO ALL LEVELSABOVE GROUND FLOOR
INDICATIVE LOCATION OFELECTRICAL RISER 700mm (W)x 300mm (D)FOR FLOORTRANSITION TO ALL LEVELSABOVE GROUND FLOOR
INDICATIVE LOCATION OFCOMMS RISER 700mm (W) x300mm (D)FOR FLOORTRANSITION TO ALL LEVELSABOVE GROUND FLOOR
INDICATIVE LOCATION OFELECTRICAL RISER 700mm (W)x 300mm (D)FOR FLOORTRANSITION TO ALL LEVELSABOVE GROUND FLOOR
TT
TT
TT
TT
TT
TT
TT
TT
T T T T T T
INDICATIVE CABLE TRAY ROUTE FORTELECOMMUNICATION CABLINGRETICULATION
RETAIL TENANT DISTRIBUTION BOARD 600mm (L) x 900mm (H) x 200mm (D).ENSURE AT LEAST 600mm ACCESS CLEARANCE INFRONT OF OPEN DOORTYPICAL TO ALL
RETAIL NBN NETWORK TERMINATION DEVICE ANDPOWER SUPPLY UNIT. 400mm (L) x 600mm (H) x 200mm (D).TYPICAL TO ALL
INDICATIVE CABLE TRAY ROUTE FORELECTRICAL CABLING RETICULATION
EE
E
EEEE
EE
EE
EE
E
TT
TT
TT
T
T T T T T
T
UC
300x200
DG
300x200
DG
600x400 External dimensionweather proof exhaust louvre.
Min.2m separated fromwindow openings above(exhaust air flow < 300 l/s)
UC
UC
UC
UC
300x250 External dimensionweather proof outside airintake louvre
200x200 Internal clearancesupply riser to below
600x400 External dimensionweather proof exhaust louvre2m2 face area weather proof
outside air intake louvre athigh level
2m2 face area weather proofoutside air intake louvre athigh level
4m2 face area carparkexhaust weather proofexhaust louvre at high level
1200x350 Internal clearancecarpark supply riser to below
1200x400 Internal clearancecarpark exhaust riser from below
Carpark exhaust air fan withaccess from the corridor
HYD OFFSET RISERS 300x800mm
HYD OFFSET RISERS 300x800mm
HYD OFFSET
RISERS 300x800mm
HYD OFFSET RISERS 300x800mm
HYD OFFSET RISERS 300x800mm
HYD OFFSET RISERS 300x800mm. TYPICALFOR THIS FLOOR IN THERETAILS.SEWER AND STOEMWATERPIPE WORK FROM ABOVEWILL OFFFSET IN THECEILINGS OF THIS FLOORAND NEEDS TO TRANSFERVERTICALLY TO THE CEILINGOF LEVEL BELOW.
GAS AND COLD WATERMETERS FOR RETAIL600mmWIDE 400mm DEEP.
GAS AND COLD WATERMETERS FOR RETAIL600mmWIDE 400mm DEEP.
GAS AND COLD WATERMETERS FOR RETAIL600mmWIDE 400mm DEEP.
T T T T T T T T T T T T T T T T T T T T T T T T T T
TT
RAIN WATER HARVESTING TANK.SIZE AND THE LOCATION OF THE TANK TOBE CONFIRMED.
RAIN WATER HARVESTING OUTLET ANDINLET PIPES SHOULD BE COORDINATEDWITH PIPE LEVELS OF OSD TANKTHEREFORE THE HARVESTING TANKSHOULD BE AS HIGH AS POSSIBLE ONLEVEL B1.
THE OUTLET (OVERFLOW) PIPE FROM THEHARVESTING TANK SHOULD BE ABOVETHE DESIGNED LEVELS OF INLET PIPE OFOSD TANK.
Building Services Engineers Pty Ltd
Date..27/04/2018...
By...myan,SAluague, RDruce.
FOR INFORMATION ONLY
ar--0200 -02
11/04/18 1:200
200 SCALE 1:
SITE PLAN
200 SCALE 1:
DEMOLITION PLAN
SITE PLAN
& DEMOLITION PLAN
landscape architecture, interior design
planning, urban design, architecture,proj no.
rev no.drwg no.
date
dem
dem
documents, advice or other material prepared by any other party.
limited. (aust) pty limited expressly takes no responsibility for any
or information and does not constitute a representation by (aust) pty
the sole representation of the party who prepared the report drawings, advice
prepared and/or provided by any other party, including the client/principal, is
any reports, drawings, advice or information included or referenced that is
demC copyright of (aust) pty limited abn 92 085 486 844. 11/04/18 VIpplotted: plotted by:
po box 5036 west chatswood nsw 1515p:
t: (02) 8966 6000
www.dem.com.auw:
nominated architects: Rudi Valla BArch (Hons) nsw reg no 6582 Jon Pizey BArch nsw reg no 6567
4465-00
scale @ A1
DA DRAFT14 CLARKE STREET RIVERSTONE MIXED-USE DEVELOPMENT
EXISTING
LIGHT
POLE
EXISTING
ELE. POLE
EXISTING
ELE. POLE
EXISTING FENCE DOTTED TO BE DEOLISH
BOUNDARY
BO
UN
DA
RY
BOUNDARY
EXISTING DRIVEWAY
TO BE DEMOLISHED
EXISTING BUILDING
DOTTED TO
DEMOLISHED
CL
AR
K S
TR
EE
T
RIVERSTONE ROAD
EXISTING SHED
DOTTED TO
DEMOLISHED
14 Clark Street
SIT
E B
OU
ND
AR
Y
RIVERSTONE ROAD
CL
AR
K S
TR
EE
T
14 Clark StreetSITE AREA 2166m2
EXISTING 2 STOREY
RESIDENTIAL
BUILDINGS
16 & 18 Clark
Street
FUTURE TWO
STOREY
COMMERCIAL
SUITES
PROPOSED
SUBSTATION FOR TOP
SHOP RESIDENTIAL
GA
S
3331
A
4 651 7
6000
6018
B
C
8802
8000
8020
98324595107604450445010760
1044504450107604595
SW
C S
EW
ER
SW
C S
EW
ER
SW
C S
EW
ER
SW
C S
EW
ER
SW
C S
EW
ER
SW
C S
EW
ER
SW
C S
EW
ER
SW
C S
EW
ER
SW
C S
EW
ER
SW
C S
EW
ER
SW
C S
EW
ER
SW
C S
EW
ER
SW
C S
EW
ER
NG
NG
NG
NG
NG
NG
NG
NG
NG
NG
NG
NG
NG
NG
NG
NG
NG
NG
ePC
WeP
CW
ePC
WeP
CW
ePC
WeP
CW
ePC
WeP
CW
ePC
WeP
CW
ePC
WeP
CW
ePC
WeP
CW
ePC
W
EXISTING 1050 KPa 200mm JEMENA SECONDARY GAS LINE.
EXISTING 525mm PP SYDNEYWATER SEWER MAIN.
EXISTING SYDNEY WATER COLDWATER MAIN.
SW
C S
EW
ER
SW
C S
EW
ER
ePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCW
PLANNED SYDNEY WATER SEWER MAIN. TBC.
PROPOSED/PLANNED SYDNEY WATER SEWER MAIN. TBC.
PROPOSED/PLANNED SYDNEY WATER COLD WATER MAIN.TBC.
SWC SEWER SWC SEWER
PROPOSED SEWERCONNECTION TO THESYDNEY WATER MAIN.BOUNDARY TRAP.
ePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCWePCW
GAS BOUNDARYREGULATOR AND METERSET.ASSEMBLY 2.5m x 1m x2.1m HIGH. ACCESS REQUIREDDIRECT FROM STREET.ROOM TO BE WELLVENTILATED.
WATER METERASSEMBLYWITHBACKFLOWPREVENTION.2.6m x 0.6m
PLEASE NOTE THAT THE SHOWN LOCATION OF THEGAS AND THE WATER METERS IS IDEAL ONLY IFCONNECTION FROM RIVERSTONE ROAD WILL BEPOSSSILE.THE CONNECTION TO THE EXISTING HIGHPRESSURE GAS MAIN IN THE CLARK STREETREQUIRES BOUNDARY REGULATOR SET FOR THEPRESSURE DROP FROM 1050 KPa.
LV CONDUITS FORCONSUMER MAINS TO MAINSWITCHROOM
PADMOUNT SUBSTATION EASEMENT OF 5.5m (L) x 2.75m(W). PADMOUNT SUBSTATION MUST NOT BE LOCATEDWITHIN: •1:100 FLOOD LEVEL OR IN STORMWATER PATHS•10000 OF AN EXTERNAL FIRE HYDRANT/FIRE PUMPS ETC•6000 OF ANY VENTILATION OPENING•3000 OF ANY PART OF A BUILDING UNLESS IT IS180/180/180 FRL & 2KPA BLAST•3000 FROM SITE BOUNDARY UNLESS PROVIDED WITH180/180/180 FRL & 2KPA BLAST WALL•3000 OF ANY GLAZING AND FIRE EXITS
Building Services Engineers Pty Ltd
Date..13/04/2018...
By...myan.
FOR INFORMATION ONLY
Building Services Engineers Pty Ltd
Date..27/04/2018...
By...myan,SAluague, RDruce.
FOR INFORMATION ONLY
ar--1203
1:100
-07
24/04/18LEVEL 1 & LEVEL 2 FLOOR PLAN
landscape architecture, interior design
planning, urban design, architecture,proj no.
rev no.drwg no.
date
dem
dem
documents, advice or other material prepared by any other party.
limited. (aust) pty limited expressly takes no responsibility for any
or information and does not constitute a representation by (aust) pty
the sole representation of the party who prepared the report drawings, advice
prepared and/or provided by any other party, including the client/principal, is
any reports, drawings, advice or information included or referenced that is
demC copyright of (aust) pty limited abn 92 085 486 844. 24/04/18 VIpplotted: plotted by:
po box 5036 west chatswood nsw 1515p:
t: (02) 8966 6000
www.dem.com.auw:
nominated architects: Rudi Valla BArch (Hons) nsw reg no 6582 Jon Pizey BArch nsw reg no 6567
4465-00
scale @ A1
DA DRAFT14 CLARKE STREET RIVERSTONE MIXED-USE DEVELOPMENT
1B
BED 1
LDY
KITCHEN
LIVING
1800
2B
74 Sq. m
2B
BED 1
BED 2ENS
LDY
KITCHENKITCHEN
LIVING LIVING
1800
2B
71 Sq. m
BED 1
LIVING
BED 2
KITCHEN
LD
Y
BATH BATH
2B
LDY
KITCHEN
LIVING
1800
BATH
RESI
CORE
2400
2200
RESI
CORE
RESI
CORE
2400
2200
77 Sq. m
BED 1 BED 2
78 Sq. m
LDY
1800
BATHENS
BED 1
7942
ENS
BED 1
74 Sq. m
STUDIO
LIVING
2BKITCHEN
LD
Y
BED 2
BATH
LD
Y
35 Sq. m 56 Sq. m
7940
5000
6000
6000
L1 FFL 37.350
L2 FFL 40.450
2B73 Sq. m
BED 2
KITCHEN
BED 1
LIVING
TOILET
2250
1000
1000
1550
LDY
1540
1550
L1 FFL 37.350
L2 FFL 40.450
L1 FFL 37.350
1.8X4.3
PRIMARY BAL. PRIMARY BAL.
2.4X4.3
PRIMARY BAL. PRIMARY BAL.
2.2X4.0
PRIMARY BAL.
2.0X4.4 1.5X4.2
BAL. BAL.
1.5X2.8
2.4X4.3
PRIMARY BAL.
2.4X4.3
PRIMARY BAL.
2.4X4.3
PRIMARY BAL.
2.2X4.6
5000
101A
103
104
105
106 107
108
201A
203204
205
206 207
208
ST 1.2m3
2B
71 Sq. m
ENS
BED 1
LIVING
BED 2
KITCHEN
LD
Y
BATH
PRIMARY BAL.
2.2X4.0
102
202
0.8
m3
C E C EC E
ST 3.4m3
1.4m3
3.1m3
1.0m3
1.0m3
3.1m3
2.2m3 2.2m3
BED 1
BATH
74 Sq. m
LIVING
2B KITCHEN
LD
Y
BED 2
8372
PRIMARY BAL.
2.0X4.4
ST 3.4m3
L2 FFL 40.450
ST 1.2m3
STUDIO
BATH
LD
Y
35 Sq. m
1.8X4.3
PRIMARY BAL.
0.8
m3
3.6m3 3.6m3
ENS
BATH109A
209A
FE FE FE
109B
209B
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST ST
BATH
300
1000
6106
5806
R1000X480 1000X480
R1000X480
R
K
K K
201B
101B2500
2500
LINE OF AWNING BELOW
LIN
E O
F A
WNIN
G B
EL
OW
LINE OF AWNING BELOW
LINE OF AWNING BELOW DOTTEDLINE OF AWNING BELOW DOTTED LINE OF AWNING BELOW DOTTED
LINE OF AWNING BELOW
1000
Height Limit 12M
FSR N/A
Dwelling Density
Planning Requirements Based on SEPP
(sydney region growth centres 2006)
R3 (Medium Density Residential)
25/HA
Allowance UsesNeighbourhood Shops
Shop Top Housing
Residential Flat Building
SEPP65 COMPLIANCE
Solar Access
Cross Ventilation
Required Achieved
Min 70%
Min 60%
Max 15%No Direct Sunlight
Deep Soil Planting Min 7%
Required Achieved
TABLE 4-10: Key controls for residential flat buildings, manor homes and shop top housing
(Blacktown City Council Growth Centre Precincts DCP 2016)
Site coverage (maximum)
Landscaped area (minimum)
Communual open space
Principal POS
Front setback (minimum)
Cnr lots secondary street
setback (minimum)
Side setback (minimum)
Rear setback (minimum)
50% of site area
30% of site area
15% of site area
where the
development includes
≥ 4 dwellings
Determined by ground
floor setback
2M
6M
4M (excluding garages)
6M
37% of site area
6M
6M
8.4M
44% of site area
Zoning
Communal Open Space
Min. 8m² per dwelling
with min. dimension
of 2.0m
Min 25%
Min. dimension of 2m for
all balconies with larger
balconies to the north
26% of site area
UrinalsUser Group Closet Pans Washbasins
Male Employees
Female Employees
1
3 -
2 2
2
1 1Unisex accessible
Sanitary Facilities calculated on the basis of Normal Retail Shops (85 Male and 85 Female)
Ground
Level 1
Level 2
Total
1B 2B 3B Total
11
6
2814
Level 3
- - -
6
6 11
3
1
-
12
-
-
-2 1
1 2 1
5 1
3.6%17.9% 10.7%
-
2B
(dual key)
Studio
(dual key)
2
2
1
5
17.8%
Car Parking Requirement as per BCC DCP
Ratio 1 1 211
1B 2B 3B Total2B
(dual key)
Studio
(dual key)
5 3 5 14 2 29
Vistor Ratio 0.4 space per dwelling 28x 0.4 = 11
50%
Unit Mix (numbers of sole occupancy units)
Retail 1 Space Per 22Sq.m GFA 519/ 22 = 24
64Total
Total
65
Car space provided
Basement 1 Basement 2
3233
BCA Compliance: Part F2 Sanitary & Other Facilities Deemed-to
Satisfy Provisions
Required
8%
85% (24 apts)
67.8% (19apts)
7%(2apts)
28%
FH
FIRE SERVICE NOTES:
FIRE EXTINGUISHERS/BLANKETS SHALL COMPLY TO THE REQUIREMENTS OFAS2444-2001.
FIRE HOSE REELS TO BE LOCATED THROUGHOUT THE CARPARK LEVELS AND TOSERVE ALL COMMERCIAL/ RETAIL TENANCIES AREAS.900W x 450DALL LEVELS WITHIN 4m OF FIRE EXITS/COMMON EXITSCENTER FHR HEIGHT ABOVE FFL BETWEEN 1.5m - 2.4mCABINETS OR CUPBOARDS TO HOUSE FHR's ARE OPTIONAL.ADDTIONAL SUPPLEMENTARY FHR's MAY BE REQUIRED SUBJECT TO 36m TRAVELDISTANCES.
FIRE HYDRANTS ARE TO BE LOCATED WITHIIN ALL FIRE STAIRS AT EACH LEVEL.750mm ABOVE FFL.ACCESS/EGRESS PATH WITHIN FIRE STAIR TO CLEAR LANDING VALVES.TO BE PROVIDED ON LANDINGS OF ALL FIRE STAIRS AT ALL LEVELS.1m CLEAR SPACE IN FRONT AND 300mm CLEARANCE AROUND EACH VALVEREQUIRED.SUPPLEMENTARY FH's MAY BE REQUIRED SUBJECT TO 30m HOSE TRAVELDISTANCES.
FH
FH
450mm Internal clearancefor bulkhead area-Typical
UC
UC
UC
UC
UC
UC
UC
UC
AP
900mm Wide x 200mm High Externalface dimension or equal linear bargrille-Typical
AP
UC
UC
300mm Wide x 150mm Highexternal face dimension or equalkitchen exhaust ductwork-Typical
250mm Wide x 200mm High externalface dimension or equal weatherproof exhaust louvre-Typical
250mm Wide x 200mm Highexternal face dimension or equalexhaust ductwork-Typical
300mm High x 1000mm Wide x 700mmDeep External dimension ceiling mountAC unit-Typical
AP
AP
AP
AP
HYDRAULIC CUPBOARD - 3 APARTEMENTS
ROOF DRAINAGE DOWNPIPEGAS RISER AND METERSWATER RISERS AND METERSCUPBOARD SEWER DRAIN
APARTMENTS3 x GAS METERS3 x COLD WATER METERS
METER CUPBOARD SIZE1.0m W x 0.6m DEEP.
HYDRAULIC CUPBOARD - 3 APARTEMENTS
ROOF DRAINAGE DOWNPIPEGAS RISER AND METERSWATER RISERS AND METERSCUPBOARD SEWER DRAIN
APARTMENTS3 x GAS METERS3 x COLD WATER METERS
METER CUPBOARD SIZE1.0m W x 0.6m DEEP.
HYDRAULIC CUPBOARD - 3 APARTEMENTS
ROOF DRAINAGE DOWNPIPEGAS RISER AND METERSWATER RISERS AND METERSCUPBOARD SEWER DRAIN
APARTMENTS3 x GAS METERS3 x COLD WATER METERS
METER CUPBOARD SIZE1.0m W x 0.6m DEEP.
HW HW
HW HW
HWHW HW HW
HW
CONTINUOUS FLOW GAS HEATER WITH FLUEDIVERTER.TYPICAL FOR EACH APARTMENT.
PLEASE NOTE THAT THERE ARE GAS CODEREQUIREMENTS ON THE ALLOWED DISTANCESFROM THE FLUE TO THE DOORS AND WINDOWS.
HYDRAULIC NOTES:
1. HYDRAULIC RISERS REQUIRED WITHINAPARTMENTS FOR SANITARYDRAINAGE/STACKS (H/R) 800mm X 350mm.RISERS REQUIRED FOR BATHROOMS ANDKITCHENS.
2. ALL BALCONY'S TO HAVE DOWNPIPEAND RAINWATER OUTLETS INSTALLEDAND OVERFLOW PROVISION IN BALCONYEDGE.
COMMS RISER CUPBOARD, 900mm (W) x600mm (D). CUPBOARD TO BENON-COMBUSTIBLE OR SMOKE SEALED.ENSURE AT LEAST 600mm ACCESSCLEARANCE IN FRONT OF OPEN DOOR
ELECTRICAL RISER CUPBOARD, 700mm (W) x 600mm (D). CUPBOARD TO BENON-COMBUSTIBLE OR SMOKE SEALED.ENSURE AT LEAST 600mm ACCESSCLEARANCE IN FRONT OF OPEN DOOR
COMMS RISER CUPBOARD, 900mm (W) x600mm (D). CUPBOARD TO BENON-COMBUSTIBLE OR SMOKE SEALED.ENSURE AT LEAST 600mm ACCESSCLEARANCE IN FRONT OF OPEN DOOR
ELECTRICAL RISER CUPBOARD, 900mm (W) x 600mm (D). CUPBOARD TO BENON-COMBUSTIBLE OR SMOKE SEALED.ENSURE AT LEAST 600mm ACCESSCLEARANCE IN FRONT OF OPEN DOOR
COMMS RISER CUPBOARD, 900mm (W) x600mm (D). CUPBOARD TO BENON-COMBUSTIBLE OR SMOKE SEALED.ENSURE AT LEAST 600mm ACCESSCLEARANCE IN FRONT OF OPEN DOOR
ELECTRICAL RISER CUPBOARD, 700mm (W) x 600mm (D). CUPBOARD TO BENON-COMBUSTIBLE OR SMOKE SEALED.ENSURE AT LEAST 600mm ACCESSCLEARANCE IN FRONT OF OPEN DOOR
NTD UC
HWHW
DPDP
DP DP
DP
DP DP
DPDP
DP
DPDP
DPDP
DP
DPBALCONY DOWNPIPES.RW OUTLETS FROM THEBALCONIES CONNECTEDTO RW DOWNPIPES.TYPICAL.RW OUTLET65mm CASTIN THE BALCONY SLAB.
DP
200mm x 200mm outside air intakeriser from above to below.
400mm x 600mm (or equal)refrigerant pipework riser fromabove to below.
200mm x 200mm outside air intakeriser from above to below.
400mm x 600mm (or equal)refrigerant pipework riser fromabove to below.
Building Services Engineers Pty Ltd
Date..27/04/2018...
By...myan,SAluague, RDruce.
FOR INFORMATION ONLY
ar--1204
1:100
-07
24/04/18Level 3 Floor Plan
landscape architecture, interior design
planning, urban design, architecture,proj no.
rev no.drwg no.
date
dem
dem
documents, advice or other material prepared by any other party.
limited. (aust) pty limited expressly takes no responsibility for any
or information and does not constitute a representation by (aust) pty
the sole representation of the party who prepared the report drawings, advice
prepared and/or provided by any other party, including the client/principal, is
any reports, drawings, advice or information included or referenced that is
demC copyright of (aust) pty limited abn 92 085 486 844. 24/04/18 VIpplotted: plotted by:
po box 5036 west chatswood nsw 1515p:
t: (02) 8966 6000
www.dem.com.auw:
nominated architects: Rudi Valla BArch (Hons) nsw reg no 6582 Jon Pizey BArch nsw reg no 6567
4465-00
scale @ A1
DA DRAFT14 CLARKE STREET RIVERSTONE MIXED-USE DEVELOPMENT
1B
59 Sq. m
8372
7942
5000
6000
6000
6106
FFL 43.800 RL 43.800
ROOF TERRACE BELOW
ACC.
KITCHEN
LD
Y
88 Sq. m
KITCHEN
LD
Y
PRIMARY BAL.
4.7X2.4
PRIMARY BAL.
2.2X4.0
A/C CONDENSER
21 Sq. m
BED 2 BED 3
ENS
BATH
ENSBED 1
ST 5.6m3
ST 2.5
m3
301 302 303
304A
305
304B
300
0.9w x 1.5h
SILL 0.9
0.9w x 1.5h
SILL 0.9
(AW AT 1.8)
SD4.08w x 2.4h
2w x 1.5h
SILL 0.9 (FULL AW)
1.2w x 0.6h (AW AT 1.8)
2w x 1.5h
SILL 0.9 (FULL AW)
4.7w x 2.4h SD
2w x 1.5h
SILL 0.9 (FULL AW)(FULL AW)
2w x 1.5h
SILL 0.9
(FULL AW)(AW AT 1.8)
(FULL A/W)
2w x 1.5h
SILL 0.9 (FULL A/W)
2w x 1.5h
SILL 0.9 (FULL A/W)
SD3.3w x 2.4h
SD
(FULL A/W)3.07w x 2.4h
3.07w x 2.4h SD
3.66w x 2.4h SD
SD
1.6w
x 2.4h GD
1.05w x 2.4h(1.05w x1.5h
AW at SILL 0.9 )
1.05w x 2.4h(1.05w x1.5h
AW at SILL 0.9 )
1.2w x 2.4h (1.2w x1.5h AW
at SILL 0.9 )
(1.2w x1.5h AW
at SILL 0.9 )
1.2w x 2.4h
(FULL AW)
4.18w x 2.4h
2.2w x 1.5h
SILL 0.9
2w x 1.5h
SILL 0.9
2w x 1.5h
SILL 0.9
1.2w x 0.6h
5806
5007
arsk
1
5008
arsk
2
5009
arsk
3
A
4 651 7
4370
6000
4388
B
C
8802
8000
8020
9832
62257795743089958650836088506225
LDY LDY
2B
71 Sq. m
BED 1
LIVING
BED 2
KITCHEN
LD
Y
RESI
CORE
2400
2200
RESI
CORE
2B73 Sq. m
BED 2
KITCHEN
BED 1
LIVING
TOILET
2250
1000
1000
1550
LDY
1540
1550
PRIMARY BAL.
2.2X4.0
PRIMARY BAL.
2.2X4.6
C EC E
1.0m3
1.0m3
BED 1
BATH
74 Sq. m
LIVING
2B KITCHEN
LD
Y
BED 2PRIMARY BAL.
2.0X4.4
ST 3.4m3
ST 1.2m3
STUDIO
BATH
LD
Y
35 Sq. m
1.8X4.3
PRIMARY BAL.
0.8
m3
3.6m3
ENS
BATH
FE FE
ST
ST
ST
ST
ST
300
1000X480R
1000X480R
K
K
LINE OF AWNING BELOW DOTTED LINE OF AWNING BELOW DOTTED
LOUNGE SEATING
AREA
COMMUNAL PERGOLA/ BBQ SEATING AREA
SYNTHETIC TURF &
PROPOSED DECK CHAIRS
LOUNGE SEATING
AREA
FIRE ESCAPE
SERVICES
LIFTSQUIET
SEATING
SPACE
Height Limit 12M
FSR N/A
Dwelling Density
Planning Requirements Based on SEPP
(sydney region growth centres 2006)
R3 (Medium Density Residential)
25/HA
Allowance UsesNeighbourhood Shops
Shop Top Housing
Residential Flat Building
SEPP65 COMPLIANCE
Solar Access
Cross Ventilation
Required Achieved
Min 70%
Min 60%
Max 15%No Direct Sunlight
Deep Soil Planting Min 7%
Required Achieved
TABLE 4-10: Key controls for residential flat buildings, manor homes and shop top housing
(Blacktown City Council Growth Centre Precincts DCP 2016)
Site coverage (maximum)
Landscaped area (minimum)
Communual open space
Principal POS
Front setback (minimum)
Cnr lots secondary street
setback (minimum)
Side setback (minimum)
Rear setback (minimum)
50% of site area
30% of site area
15% of site area
where the
development includes
≥ 4 dwellings
Determined by ground
floor setback
2M
6M
4M (excluding garages)
6M
37% of site area
6M
6M
8.4M
44% of site area
Zoning
Communal Open Space
Min. 8m² per dwelling
with min. dimension
of 2.0m
Min 25%
Min. dimension of 2m for
all balconies with larger
balconies to the north
26% of site area
UrinalsUser Group Closet Pans Washbasins
Male Employees
Female Employees
1
3 -
2 2
2
1 1Unisex accessible
Sanitary Facilities calculated on the basis of Normal Retail Shops (85 Male and 85 Female)
Ground
Level 1
Level 2
Total
1B 2B 3B Total
11
6
2814
Level 3
- - -
6
6 11
3
1
-
12
-
-
-2 1
1 2 1
5 1
3.6%17.9% 10.7%
-
2B
(dual key)
Studio
(dual key)
2
2
1
5
17.8%
Car Parking Requirement as per BCC DCP
Ratio 1 1 211
1B 2B 3B Total2B
(dual key)
Studio
(dual key)
5 3 5 14 2 29
Vistor Ratio 0.4 space per dwelling 28x 0.4 = 11
50%
Unit Mix (numbers of sole occupancy units)
Retail 1 Space Per 22Sq.m GFA 519/ 22 = 24
64Total
Total
65
Car space provided
Basement 1 Basement 2
3233
BCA Compliance: Part F2 Sanitary & Other Facilities Deemed-to
Satisfy Provisions
Required
8%
85% (24 apts)
67.8% (19apts)
7%(2apts)
28%
FH
FH
FH
FIRE SERVICE NOTES:
FIRE EXTINGUISHERS/BLANKETS SHALL COMPLY TO THE REQUIREMENTS OFAS2444-2001.
FIRE HOSE REELS TO BE LOCATED THROUGHOUT THE CARPARK LEVELS AND TOSERVE ALL COMMERCIAL/ RETAIL TENANCIES AREAS.900W x 450DALL LEVELS WITHIN 4m OF FIRE EXITS/COMMON EXITSCENTER FHR HEIGHT ABOVE FFL BETWEEN 1.5m - 2.4mCABINETS OR CUPBOARDS TO HOUSE FHR's ARE OPTIONAL.ADDTIONAL SUPPLEMENTARY FHR's MAY BE REQUIRED SUBJECT TO 36m TRAVELDISTANCES.
FIRE HYDRANTS ARE TO BE LOCATED WITHIIN ALL FIRE STAIRS AT EACH LEVEL.750mm ABOVE FFL.ACCESS/EGRESS PATH WITHIN FIRE STAIR TO CLEAR LANDING VALVES.TO BE PROVIDED ON LANDINGS OF ALL FIRE STAIRS AT ALL LEVELS.1m CLEAR SPACE IN FRONT AND 300mm CLEARANCE AROUND EACH VALVEREQUIRED.SUPPLEMENTARY FH's MAY BE REQUIRED SUBJECT TO 30m HOSE TRAVELDISTANCES.
UC
AP
450mm Internal clearancefor bulkhead area-Typical
900mm Wide x 200mm High Externalface dimension or equal linear bargrille-Typical
300mm Wide x 150mm Highexternal face dimension or equalkitchen exhaust ductwork-Typical
400mm Wide x 250mm High externalface dimension or equal weatherproof kitchen exhaust louvre-Typical
300mm High x 1000mm Wide x 700mmDeep External dimension ceiling mountAC unit-Typical
Condensing units forapartments andretails, includingspare spaces
HYDRAULIC CUPBOARD - 3 APARTEMENTS
ROOF DRAINAGE DOWNPIPEGAS RISER AND METERSWATER RISERS AND METERSCUPBOARD SEWER DRAIN
APARTMENTS3 x GAS METERS3 x COLD WATER METERS
METER CUPBOARD SIZE1.0m W x 0.6m DEEP.
HW
CONTINUOUS FLOW GAS HEATER WITH FLUEDIVERTER.TYPICAL FOR EACH APARTMENT.
PLEASE NOTE THAT THERE ARE GAS CODEREQUIREMENTS ON THE ALLOWED DISTANCESFROM THE FLUE TO THE DOORS AND WINDOWS.
HW
HW
HW
HWHW
LOCATIONS OF THE RAIN WATERDOWNPIPE RISERS STARTING FLOORBELOW.
ROOF WILL BE DRAINED IN TO THE RWHARVESTING TANK OVERFLOWING INTO THE OSD TANK.
HATCHED AREAS ARE REPRESENTINGCORIDOR CEILING AREAS ON LEVELSBELOW ROOFS.
RAIN WATER OUTLETS ANDHORIZONTAL PIPES COULD BE RUN INTHOSE AREAS TO AVOID RUNNINGSTORMWATER PIPES TROUGHT THEAPARTMENTS.
DPDP
DP
DPDP
DP
DPDP
DP DP
DP
DP
DP
DP
DP DP
RAINWATER DOWNPIPESFROM LEVEL BELOW.IF THERE WILL BE NO RAINWATER HARWESTING THOSEDOWNPIPES CAN BE USED TODRAIN THE LANDSCAPE AREA.IF THERE
HYDRAULIC NOTES:
1. HYDRAULIC RISERS REQUIRED WITHINAPARTMENTS FOR SANITARYDRAINAGE/STACKS (H/R) 800mm X 350mm.RISERS REQUIRED FOR BATHROOMS ANDKITCHENS.
2. ALL BALCONY'S TO HAVE DOWNPIPEAND RAINWATER OUTLETS INSTALLEDAND OVERFLOW PROVISION IN BALCONYEDGE.
DPBALCONY DOWNPIPES.RW OUTLETS FROM THEBALCONIES CONNECTEDTO RW DOWNPIPES.TYPICAL.RW OUTLET65mm CASTIN THE BALCONY SLAB.
FH
R
COMMS RISER CUPBOARD, 900mm (W) x600mm (D). CUPBOARD TO BENON-COMBUSTIBLE OR SMOKE SEALED.ENSURE AT LEAST 600mm ACCESSCLEARANCE IN FRONT OF OPEN DOOR
ELECTRICAL RISER CUPBOARD, 700mm (W) x 600mm (D). CUPBOARD TO BENON-COMBUSTIBLE OR SMOKE SEALED.ENSURE AT LEAST 600mm ACCESSCLEARANCE IN FRONT OF OPEN DOOR
COMMS RISER CUPBOARD, 900mm (W) x600mm (D). CUPBOARD TO BENON-COMBUSTIBLE OR SMOKE SEALED.ENSURE AT LEAST 600mm ACCESSCLEARANCE IN FRONT OF OPEN DOOR
ELECTRICAL RISER CUPBOARD, 700mm (W) x 600mm (D). CUPBOARD TO BENON-COMBUSTIBLE OR SMOKE SEALED.ENSURE AT LEAST 600mm ACCESSCLEARANCE IN FRONT OF OPEN DOOR
Kitchen exhaustdischarge at thislocation (offset onlevel below)
200mm x 200mm outside air intakeriser from above to below.
400mm x 600mm (or equal)refrigerant pipework riser fromabove to below.
Building Services Engineers Pty Ltd
Date..27/04/2018...
By...myan,SAluague, RDruce.
FOR INFORMATION ONLY
ar--1204
1:100
-06
24/04/18Roof plan
landscape architecture, interior design
planning, urban design, architecture,proj no.
rev no.drwg no.
date
dem
dem
documents, advice or other material prepared by any other party.
limited. (aust) pty limited expressly takes no responsibility for any
or information and does not constitute a representation by (aust) pty
the sole representation of the party who prepared the report drawings, advice
prepared and/or provided by any other party, including the client/principal, is
any reports, drawings, advice or information included or referenced that is
demC copyright of (aust) pty limited abn 92 085 486 844. 24/04/18 VIpplotted: plotted by:
po box 5036 west chatswood nsw 1515p:
t: (02) 8966 6000
www.dem.com.auw:
nominated architects: Rudi Valla BArch (Hons) nsw reg no 6582 Jon Pizey BArch nsw reg no 6567
4465-00
scale @ A1
DA DRAFT14 CLARKE STREET RIVERSTONE MIXED-USE DEVELOPMENT
LIFT OVERRUN LIFT OVERRUN
A/C CONDENSER
A/C CONDENSER
A/C CONDENSER
BOX GUTTER
BOX GUTTER
SKYLIGHT
SKYLIGHT
RR RR
K
K
6018
3 d
eg F
ALL
3 d
eg F
ALL
METAL DECK ROOF
1w x 1w
FW
1w x 1w
FW
8372
6000
5007
arsk
1
5008
arsk
2
5009
arsk
3
A
4 651 7
4370
6000
4388
B
C
8802
8000
8020
9832
62257795743089958650836088506225
RL 43.800
ROOF TERRACE BELOW
A/C CONDENSER
21 Sq. m
8802
8000
8020
62257795743089958650836088506225
LDY LDY
LINE OF AWNING BELOW DOTTED
LOUNGE SEATING
AREA
COMMUNAL PERGOLA/ BBQ SEATING AREA
SYNTHETIC TURF &
PROPOSED DECK CHAIRS
LOUNGE SEATING
AREA
FIRE ESCAPE
SERVICES
LIFTSQUIET
SEATING
SPACE
Height Limit 12M
FSR N/A
Dwelling Density
Planning Requirements Based on SEPP
(sydney region growth centres 2006)
R3 (Medium Density Residential)
25/HA
Allowance UsesNeighbourhood Shops
Shop Top Housing
Residential Flat Building
SEPP65 COMPLIANCE
Solar Access
Cross Ventilation
Required Achieved
Min 70%
Min 60%
Max 15%No Direct Sunlight
Deep Soil Planting Min 7%
Required Achieved
TABLE 4-10: Key controls for residential flat buildings, manor homes and shop top housing
(Blacktown City Council Growth Centre Precincts DCP 2016)
Site coverage (maximum)
Landscaped area (minimum)
Communual open space
Principal POS
Front setback (minimum)
Cnr lots secondary street
setback (minimum)
Side setback (minimum)
Rear setback (minimum)
50% of site area
30% of site area
15% of site area
where the
development includes
≥ 4 dwellings
Determined by ground
floor setback
2M
6M
4M (excluding garages)
6M
37% of site area
6M
6M
8.4M
44% of site area
Zoning
Communal Open Space
Min. 8m² per dwelling
with min. dimension
of 2.0m
Min 25%
Min. dimension of 2m for
all balconies with larger
balconies to the north
26% of site area
UrinalsUser Group Closet Pans Washbasins
Male Employees
Female Employees
1
3 -
2 2
2
1 1Unisex accessible
Sanitary Facilities calculated on the basis of Normal Retail Shops (85 Male and 85 Female)
Ground
Level 1
Level 2
Total
1B 2B 3B Total
11
6
2814
Level 3
- - -
6
6 11
3
1
-
12
-
-
-2 1
1 2 1
5 1
3.6%17.9% 10.7%
-
2B
(dual key)
Studio
(dual key)
2
2
1
5
17.8%
Car Parking Requirement as per BCC DCP
Ratio 1 1 211
1B 2B 3B Total2B
(dual key)
Studio
(dual key)
5 3 5 14 2 29
Vistor Ratio 0.4 space per dwelling 28x 0.4 = 11
50%
Unit Mix (numbers of sole occupancy units)
Retail 1 Space Per 22Sq.m GFA 519/ 22 = 24
64Total
Total
65
Car space provided
Basement 1 Basement 2
3233
BCA Compliance: Part F2 Sanitary & Other Facilities Deemed-to
Satisfy Provisions
Required
8%
85% (24 apts)
67.8% (19apts)
7%(2apts)
28%
200mm x 200mm Internal clearanceoutside air intake riser to below
Kitchen exhaust roof discharge
Condensing units forapartments andretails, includingspare spaces.
Refrigerant piperoute fromcondensing units toindoor AC unit
LOCATIONS OF THE RAIN WATERDOWNPIPE RISERS STARTING FLOORBELOW.
ROOF WILL BE DRAINED IN TO THE RWHARVESTING TANK OVERFLOWING INTO THE OSD TANK.
HATCHED AREAS ARE REPRESENTINGCORIDOR CEILING AREAS ON LEVELSBELOW ROOFS.
RAIN WATER OUTLETS ANDHORIZONTAL PIPES COULD BE RUN INTHOSE AREAS TO AVOID RUNNINGSTORMWATER PIPES TROUGHT THEAPARTMENTS.
INDICATIVE PHOTOVOLTAIC PANELLOCATIONS AND DIRECTION.
LOCATION AND NUMBER OF PANLESSUBJECT TO FURTHERCOORDINATION
INDICATIVE INVERTER LOCATIONS
INVERTER
Kitchen exhaust roof discharge
DP
DPDP
DPDP
DP
DP
DPDP
RAINWATER DOWNPIPESFROM LEVEL BELOW.IF THERE WILL BE NO RAINWATER HARWESTING THOSEDOWNPIPES CAN BE USED TODRAIN THE LANDSCAPE AREA.IF THERE
HYDRAULIC NOTES:
1. HYDRAULIC RISERS REQUIRED WITHINAPARTMENTS FOR SANITARYDRAINAGE/STACKS (H/R) 800mm X 350mm.RISERS REQUIRED FOR BATHROOMS ANDKITCHENS.
2. ALL BALCONY'S TO HAVE DOWNPIPEAND RAINWATER OUTLETS INSTALLEDAND OVERFLOW PROVISION IN BALCONYEDGE.
DPBALCONY DOWNPIPES.RW OUTLETS FROM THEBALCONIES CONNECTEDTO RW DOWNPIPES.TYPICAL.RW OUTLET65mm CASTIN THE BALCONY SLAB.
Building Services Engineers Pty Ltd
Date..27/04/2018...
By...myan,SAluague, RDruce.
FOR INFORMATION ONLY