Canalis
Rising main KSRbusbar trunking
for multi-storey buildings
Selection guide
-
7/27/2019 Residential Busbar Distribution System
2/32
Canalis rising main busbar trunking
cuts installation costs in multi-storey buildings
2
The Canalis KSR rising main busbar trunking system launched byTelemecanique enables electrical distribution to be rapidly installed
in multi-storey buildings of all types, including office blocks, hotels,
hospitals and car parks. Canalis KSR improves safety, cuts
installation time and reduces the overall cost of installing
distribution systems.
Fire barriers at
each floor
Canalis KSR
incorporates a solid
fire barrier at each
floor, giving aminimum of two hours
fire protection. This
minimises the risk of
fire spreading in
multi-storey
buildings where
vertical ducting can
provide a path for
fumes, smoke and
fire. Canalis KSR
meets the most
stringent interpretation
of the Building
Regulations for fire
safety.
Rated at 400-800A,
Canalis KSR is the
first rising main
busbar trunking to use
aluminium conductors
as standard. The
system is lighter and
easier to handle on
site than conventional
copper busbar
trunking, allowing fastinstallation.
At around half the
weight of traditional
copper conductor
based busbar
trunking, Canalis KSR
can be fitted in many
installations by one
person. Its lightness
means it needs fewer
mechanical fixings,
making it even faster
to install.
Fast installation
allows contractors to
meet the extremely
short deadlines that
are becoming
increasingly common
in todays building
market.
Canalis KSR busbar
sections are linked by
joint kits bolted in
place, complete with
an expansion joint
that ensures a secure,
safe and easy-to-
make connection.
Silver-to-silver
contacts provide
excellent conductivity
at all joints.
This simple connection
method makes it
easier to install the
distribution system
safely, first time.
Canalis KSR is one of
the safest rising main
busbar trunking
systems available.
Interlocks on the
tap-off units prevent
live loads being
connected or
disconnected. The
busbar sections are
finger-safe to IP2X,
even when no tap-off
units are fitted. All of
which means that
tap-off units can besafely connected to a
live system if this is
unavoidable.
-
7/27/2019 Residential Busbar Distribution System
3/32
3
KSR issuitable formanyapplications
Canalis KSR is
designed for medium
power distribution with
high tap-off density in
multi-storey office
blocks and
commercial and
industrial buildings.
The range is availablein 3 ratings: 400A,
630A and 800A.
The standard IP54
degree of protection
makes KSR suitable
for many locations.
This is achieved by
the addition of dust
and damp proof
blanking plates on the
tap-off outlets and
joints. Connection is
via tap-off units.These units, from 25
to 400A, can be safely
removed while the
busbar trunking is
live because they
feature mechanical
and electrical
interlocks as
standard.
KSR riser can also be
fitted with any other
products from the
established CanalisKSA busbar trunking
range.
KSR rising main is aspecific version of
KSA busbar trunking
for energy distribution
to each floor of a
multi-storey building.
KSR retains all the
construction principles
of KSA trunking for
horizontal distribution,
in particular:
Aluminiumconducting bars
are equipped withbi-metal silvercopper laminatesaddles fitted atthe points ofcontact in the
joints and tap-offoutlets
The jointing blockwith spring-loadedcontacts, lockedby 1/4-turnfastening (thisblock, which also
absorbs theexpansion of theconductors,eliminates anymechanical stressat the fire barrier)
Tap-off outletswith automaticclosingshutters
Degree ofprotection is IP54
-
7/27/2019 Residential Busbar Distribution System
4/32
4
A
C
BB
G
D
F
G
Canalis KSR (400A to 800A)Description
Medium power busbar trunking
E
E
A
-
7/27/2019 Residential Busbar Distribution System
5/32
5
Canalis KSR (400A to 800A)Description
Medium power busbar trunking
ARiser distribution lengths
Connection components,
feed units and end covers
Fixings
Tap-off units
Accessories
Feeder lengths
Components for
changing direction
Page19
BPage19 - 21
CPage20
DPage22 - 23
EPage20
FPage20
GPage
21
APage6 - 7
BPage8
CPage9
DPage10
EPage11
FPage12
GPage
13
Product description Product selection
-
7/27/2019 Residential Busbar Distribution System
6/32
4
3
2
1
5
6
6
Canalis KSR (400A to 800A)Description
Medium power busbar trunking
Riser distribution lengths
The KSR length is equal to the height between 2 floors (floor-to-floor), ranging from2900 to 4840mm (standard length and made to measure fire barrier components).They are equipped with: 3 or 4 tap-off outlets, always positioned at the same height with respect to the
centre line of the lower floor slab
1 fire barrier, placed at the level of passage through the floor slab, eliminating
any risk of fire propagation from one floor to another via the trunking. The fire
barrier, which has been tested by the laboratory of the University of Gand(Belgium) conforms to the requirements of standard ISO834. According toreport 7296, the following results were obtained:
Thermal insulation : 120 minutes
Flame resistance : 120 minutes
Stability : 120 minutes
Straight distribution lengths
Straight lengths are designed to carry current and feed loads with low or mediumpower. The straight lengths form the structure of the run.
They comprise:
1 A casing of galvanised sheet steel which is crimped closed
This casing, shaped and ribbed by rolling, provides excellent resistance tobending and twisting. Two casing widths cover the whole range:
75mm wide sheet steel with RAL 7032 grey finish for 400A rating
113mm wide sheet steel with RAL 7032 grey finish for 630 and 800A
ratings
2 4 live conductors of the same cross-section:
Aluminium fitted with bi-metal silver-plated copper/aluminium laminate
riders electrically welded to junctions and tap-off positions for 400 to 800Aratings. The lamination is a patented process by which the copper andaluminium molecules are fused together under extreme pressure
3 Fibreglass reinforced polyester isolators at 250mm intervals.These hold the conductors securely within the casing
4 A special protected earth (PE) conductor of the same type as the liveconductors with a cross-section 1/2 of the phase cross-section. It isconnected to the casing at each junction
5 Tap-off outlets on the front face of the trunking at 500mm intervals.They are connected to the isolators to form a block, holding the bars.They have a shuttered outlet which is opened and closed automaticallywhen connectors or tap-off units are plugged in, or removed
6 A mechanical and electrical jointing device Electrical connection is via ablock with spring and silver graphite contacts. This block absorbs thedifferential conductor/casing expansion of each length equally.It simultaneously connects all the live conductors, ensures continuity of theprotective earth conductor and its connection with the casing.The electrical connection is made by a 1/4 screw turn for each conductor
A
-
7/27/2019 Residential Busbar Distribution System
7/32
7
Canalis KSR (400A to 800A)Description
Medium power busbar trunking
Fire barrier lengths
To enable to pass from floor to floor of a multi-story building. Fire resistance of thebarriers is 2 hours (A120) conforming to ISO834
Riser support fire barrier length
The first floor is a combined base support length for the complete riserincluding the fire barrier. This is a standard length 1150m.
Made to measure fire barrier length
Subsequent floor fire barriers are made to measure lengths to alter the lengthof a run between floor to floor heights.
These components are manufactured from 900mm to 2300mm in multiples of5mm. They do not have tap-off outlets.
215 13
103
290
450
70057
55
450
L = 900 - 2300
450 - 1850
-
7/27/2019 Residential Busbar Distribution System
8/32
8
Canalis KSR (400A to 800A)Description
Medium power busbar trunking
Connection components, feed units and end covers
To feed a KSR riser run by cables, or directly from a distribution panel.
Supply cable
The feed can be from one end (end feed) or along a run (centre feed). They can be connected by aluminium orcopper cables fitted with suitable cable lugs. There is an undrilled aluminium gland plate which will accept cableglands. This plate can be replaced by a plate fitted with 1-3 cable clamps depending on the rating (to be
ordered separately)
A End feed units - For bottom or top connection
B Centre feed unit - Through run type (1 cable feeds the right and left sections)It is mounted along the run, between 2 straight lengths
Direct supplyfrom switchboard
Using a connection unit with spreader bars mounted at the end of a horizontal run carried out using lengths
with or without additional tap-off outlets
C Flange feed unit - Fitted with splayed bars and a mounting plate. It is used for connection to adistribution panel. It can be mounted at either end of a component
KV-KSR connector
The KV-KSR connector is fitted with a KV end length at one end and a KSA end length at the other. Due to itsflexible design, it ensures direct connection from a feed run to a distribution run and reduces any risk caused by
alignment faults
D End cover
The end cover protects and isolates the ends of the conductors. It is mounted on the last length.Two products cover the entire KSR range: 400 and 800A.
D
B
C
A
B
-
7/27/2019 Residential Busbar Distribution System
9/32
9
Canalis KSR (400A to 800A)Description
Medium power busbar trunking
Fixings
Used to fix the riser run to the structure of the building, directly or via an adjustable universal guide.
Bottom support for riser
Equips the fire barrier first joint at the bottom of the rising main. Angle wall brackets are fixed to the wall by
standard fixings (supplied by others). This unit supports the complete rising main (for design guide see page 14)
Universal GuideThis bracket maintains the trunking in position at each floor. Two adjustable fixing straps are supplied to give a30mm depth adjustment from the supporting wall.
C
-
7/27/2019 Residential Busbar Distribution System
10/32
10
Canalis KSR (400A to 800A)Description
Medium power busbar trunking
Tap-off units BS88 fuse links
Tap-offs are provided by KSR tap-off units, either :
Switch fuse and Fuse switch tap-offs 32A to 400A fuses
100 to 400A moulded case circuit breaker
Standard KSA units with isolators and fuse carriers for 25 to 160A fuses
These fused tap-off units are designed to protect the tap-off by means
of fuses (not supplied).They can be fitted with carriers for the following fuses:
32 to 160A fused on-load tap-off unit, switch fuse on-load tap-off unit
250 to 400A fused off-load tap-off unit, fuse switch on-load tap-off unit
Tap-off units for Merlin Gerin circuit breaker
These units are designed to take Merlin Gerin Compact NS circuit breakers:
100 to 400A rating
Version N, H or L
With or without residual differential device
With rotary switch
For other types of circuit breaker, please consult your regional sales office.
Standard KSA units
These units can only be mounted on trunking which is installed horizontally on edge. To make installation easier,
it is performed in two stages:
The unit is hooked onto the trunking, then automatically located in front of the tap-off outlet by moving it
sideways
The fixing brackets are then locked and the mobile power block plugged in, using an internal device
Used for instant connection of loads or secondary runs (for example, for low power distribution).The connectors and tap-off units conform to installation standards and regulations whatever type of neutral
point connection is used (TT, IT, TNS or TNC).
They can be removed and moved whilst live, with no load
The tap-off outlets are opened and closed automatically when units are plugged in or removed
With the cover open, no live part can be accessed. Degree of protection IP2X Connectors and tap-off units are made in two versions
Protected version, degree of protection IP54, suitable for most industrial and commercial applications
Tap-off units with isolator for
modular equipment
All standard KSA tap-off units are available tobe fitted to the KSR busbar riser products.
A selection guide for the KSA range is availableupon request. Please contact Tel: 0870 608 8 608.
D
-
7/27/2019 Residential Busbar Distribution System
11/32
11
Medium power busbar trunking
Canalis KSR (400A to 800 A)Description
Accessories
To achieve the degree of protection, IP54, the following accessories are fitted to the riser.
Vertical and flat installation
1 Each tap-off outlet not being used, should be fitted with a sealed tap-off blanking plate
2 Each junction between components should be fitted with a jointing sleeve to maintain the IP54 projection
Various devices, for lead sealing in particular, can be used to complete the equipment of the
KSR rising main.
2
1
E
-
7/27/2019 Residential Busbar Distribution System
12/32
12
Canalis KSR (400 to 800A)Description
Medium power busbar trunking
Feeder lengths (with or without tap-off outlets)
These lengths, without tap-off outlets are used as feeders, running horizontally (generally in the basement or inthe utilities ducting) between the switchboard and the bottom of the distribution rising main.
Any complementary lengths required for this horizontal run (elbows, special lengths, fire barriers) can beselected for the KSA components from the Canalis Busbar Trunking and Power Applications catalogueavailable upon request. Please contact 0870 608 8 608.
F
-
7/27/2019 Residential Busbar Distribution System
13/32
13
Canalis KSR (400 to 800A)Description
Medium power busbar trunking
Components for changing direction
Edgewise elbow
One model for each size of casing for turning to left or right
Flat elbow
Two models for each size of casing (one ascending, one descending). Flat and edgewise elbows can bemanufactured upon request, with made to measure connection lengths, with multiple angles, withbuilt-in fire barrier, etc. for the KSA components from the Canalis Busbar Trunking and Power Applications
catalogue available upon request. Please contact 0870 608 8 608.
Edgewise tee and cross
For vertical branches on the main
G
-
7/27/2019 Residential Busbar Distribution System
14/32
14
Basement
Information required to design a KSR riser system
The types of load and their characteristics and floor locations
The power source and its characteristics and location
The structure of the premises (availability of fixing points for trunking)
Any influences external to the installation site. (ambient temperature, dust, water, etc)
Distribution run layout
The siting of rising main depends on the position of the loads, the location of the general power supply and theavailability of fixing points. A single supported KSR riser run can serve up to 12 floors (60 metres).
Selection of the trunking according to the rated operating current Ib
k1 = average demand coefficient Ib = total current x k1
Total current = sum of currents drawn by the loads on a run
Permissible current Iz according to the ambient temperature(at the installation site)
The nominal current Inc of the trunking is specified for an average daily ambient temperature of 35C(and a maximum of 40C). Depending on the actual temperature, an uprating or derating coefficient (f1) may beapplied to the nominal current Inc : see the characteristics on page 17.
Checking the voltage drop
The voltage drop in Canalis KS is given in V/100m/A in the characteristics table on page 17.
Polarity selection
Applications k1
Lighting, heating 1
Distribution
2 or 3 loads 0.9
4 or 5 loads 0.8
6...9 loads 0.7
10...40 loads 0.6
40 or more 0.5
Rated operating current Ib Selected trunking
0...100 A KS-10
100...160 A KS-16
160...250 A KS-25
315...400 A KS-40
400...500 A KS-50
500...630 A KS-63
630...800 A KS-80
4 tap-offs per floor
Canalis KSR (400 to 800A)Design guide
Medium power busbar trunking
3L + PE(IT-TT-TNS)
3L + N + PE(IT-TT-TNS)
3L + PE(IT-TT-TNS)
3L + N + PE(IT-TT-TNS)
3-pole distribution + N
+ PE (IT-TT-TNS)
KSA-D4
trunking3-pole + N + PE tap-offspossible, type 3-pole +PE or 3-pole + N + PE
3-pole distribution +
PEN (TNC)
KSA-ED4
trunking3-pole + PEN tap-offspossible, type 3-pole +PEN (TNC) or 3-pole +N + PE (TNS).
-
7/27/2019 Residential Busbar Distribution System
15/32
15
Canalis KSR : rating (A) 100 160 250 400 500 630 800
Type of NS100 N 25
Merlin Gerin H 25
circuit breaker (1) L 25
NS160 N 20 36
H 20 70
L 20 70
NS250 N 36 36
H 55 70
L 55 150
NS400 N 45 45
H 45 70
L 45 150
NS630 N 45 45 45
H 70 70 70
L 150 150 150
C801 N 40 50
H 40 50
L 55 50
C1001 N 50
H 50L 80
Protecting the trunking against overloads (1)
To enable it to be extended, prefabricated busbar trunking is generally protected to its nominal current Inc
(or to its permissible current Iz if the K1 coefficient is applied according to the ambient temperature).
Protection using fuses
Calculate the standard nominal current In of the fuse so that : In Inc
Select the circuit breaker setting current Ir so that : Ib Ir Inc
Note: Protecting trunking using a circuit breaker makes it possible to use the trunking at full capacity.
Protection using a circuit breaker
Select the circuit breaker setting current Ir so that : Ib Ir Inc
Note: Protecting trunking using a circuit breaker makes it possible to use the trunking at full capacity.
Electrodynamic protection against short-circuit currents
The electrodynamic withstand of the trunking should be taken into account when selecting a protective device
(permissible rated peak current).
Determine the 3-phase short-circuit current, prospective lcc 3 (KA) at the start of the Canalis KSR
Check the current limitation curve of the selected protective device, that this limits the peak current (kA) to a
value below the permissible rated peak current of the KSR trunking. Limited current Canalis current
Protection using a Merlin Gerin Compact circuit breaker
The circuit breaker/Canalis co-ordination table below gives the maximum short-circuit current for which theKSR trunking is protected, according to the type of circuit breaker.Prospective Icc 3, max (Ka rms) voltage 380/415V.
(1) By calculation or using graphs, pre-calculated tables, etc.
Note: To obtain details of the Merlin Gerin circuit breaker range, please refer to the circuit breaker brochure
available by phone from 0870 608 8 608
Canalis KSR (400 to 800A)Design guide
Medium power busbar trunking
k1
-
7/27/2019 Residential Busbar Distribution System
16/32
16
B
A
Canalis KSR (400 to 800A)Design guide
Medium power busbar trunking
External influences are taken into consideration when siting the installation.The IP54 degree of protection of Canalis KSR means that it is suitable forinstallation in most industrial and commercial locations.
Especially for locations or sites which may be subject to water splashes in anydirection, the degree of protection is achieved by installing sealed tap-off blankingplates and sealed jointing sleeves. (See page 20).
Selecting the power supply
A cable feed unit can be mounted at either end of a run, bottom or top
500 and 800A feed unit
Two types depending on position:
Bottom (right hand) mounting (fig. A)
Top (left hand) mounting (fig. B)
All types of neutral system. Connected by means of cable lugs.
Switchboard feed may be connected via cable or busbar interconnector.
Mounting position
Tap-off units
The complete range of tap-off units for KSR are IP54 dust and damp proof range,
for very dusty or damp environments.
Changing levels in horizontal distribution
The trunking is mounted vertically, the degree of protection at a junction isIP54. This is achieved by fitting a standard sealed jointing sleeve at each junction.
Selection of IP degree of protection
KSE = IP54
230
21 120 - 150
-
7/27/2019 Residential Busbar Distribution System
17/32
17
Canalis KSR (400 to 800A)Characteristics (1)
General characteristics (1)
4 4 4
A 400 630 800
Ui V 660 660 660
Ue V 660 660 660
F Hz 50/60 50/60 50/60
Number of conductors
Rated insulated voltage Conforming to IEC 158-1
Rated operating voltage
Rated frequency
KSA-40 KSA-63 KSA-80Type of trunking
Fault loop characteristics
Between live conductors
Rb1phph m/m 0.38 0.202 0.122
phN m/m 0.38 0.202 0.122
phPEN m/m 0.2613 0.1409 0.0929
Rb2phph m/m 0.45 0.239 0.144
phN m/m 0.45 0.239 0.144
phN m/m 0.3113 0.169 0.1101
Xbphph m/m 0.252 0.154 0.1475
phN m/m 0.2915 0.197 0.1895
phPEN m/m 0.2115 0.1433 0.1395
Between live conductor and PE
Rb1phPE m/m 0.304 0.167 0.128
Rb2phPE m/m 0.365 0.201 0.153
XbphPE m/m 0.303 0.225 0.226
Average resistance of loop
(thermal stabilisation temp. 01)
Average resistance of loop (1)
(short-circuit conventional temp.)
Average reactance loop
Average resistance of loop
(thermal stabilisation temp. 01)
Average resistance of loop (1)
(short-circuit conventional temp.)
Average reactance loop
KSA-40 KSA-63 KSA-80Type of trunking
(1) Conforming to international standard IEC 439-2 and European standard EN 60439.2
Medium power busbar trunking
Nominal rated current INC to 350C
-
7/27/2019 Residential Busbar Distribution System
18/32
18
Conductor characteristics
Live conductors (per conductor)
GE resistance, cold state Rboph(1) m/m 0.142 0.074 0.045
(ambient temperature 20C)
R1 average resistance at/nc Rb1ph(1) m/m 0.190 0.101 0.061
(ambient temperature 35C)
X1 average resistance at/nc Xbph(1) m/m 0.112 0.070 0.071
and at rated frequency (Hz)
Protective conductors
Average resistance, cold state m/m 0.105 0.061 0.061
(ambient temperature 35C)
KSA-40 KSA-63 KSA-80Type of trunking
Other characteristics
KSA-40 KSA-63 KSA-80Type of trunking
Destination of permissible current
Iz for a busbar trunking system,
according to ambient temperature
(1) Conforming to international standard IEC 439-2 and European standard EN 60439.2
Canalis KSR (100 to 800A)Characteristics (1)
Medium power busbar trunking
Short-circuit withstand capacity
Maximum thermal limit 12 t ph or N kA 354x106 1225x106 1758x106
PE kA 354x106 1225x106 1225x106
PEN kA 500x106 2000x106 2500x106
Permissible rated peak current Ipk kA 49.2x106 67.5x106 78.7x106
Degree of protection
IP54 With accessories.
Voltage drop Composite voltage drop, hot state, expressed in V/100 m/A
for 3 phase 50Hz current, with load
distributed along the run. Where the load is concentrated
at the end of a feed run, the voltage drops
are twice the values indicated in the table.
For a power factor Cos f=1.0 V/100 m/A 0.01645 0.00875 0.00528
For a power factor Cos f=0.9 V/100 m/A 0.01904 0.01051 0.00743
For a power factor Cos f=0.8 V/100 m/A 0.01898 0.01063 0.00792
For a power factor Cos f=0.7 V/100 m/A 0.01844 0.01045 0.00805
Derating or uprating factor to be applied to the rated
current of the trunking where the average daily ambient
temperature is other than 35C
Average ambient temperature C 15 20 25 30 35 40 45 50 55
Factor f1 1.11 1.08 1.06 1.03 1.00 0.97 0.94 0.91 0.87
-
7/27/2019 Residential Busbar Distribution System
19/32
Rising main busbar
19
Canalis KSR (400 to 800A)References
Rating A Length no. of tap-off outlets Catalogue number 3Ph Weight kg
(front face) +N+PE or 3Ph+PEN
400 2000 3 KSA40VD420 16
2500 4 KSA40VD425 20
630 2000 3 KSA63VD420 24
2500 4 KSA63VD425 30
800 2000 3 KSA80VD420 28
2500 4 KSA80VD425 35
Rating A Length Length of Length of part on Catalogue number 3Ph Weight kg
(L) top part measurement Y= +N+PE or 3Ph+PEN Min. Max.
400 900-2300(1) 450 450...1850 KSA40EF4B 8 20
630 900-2300(1) 450 450...1850 KSA63EF4B 12 30
800 900-2300(1) 450 450...1850 KSA80EF4B 14 35
Floor distribution lengths
Additional fire barrier lengths
Rating A Length Total supportable Catalogue number 3Ph Weight kg
height +N+PE or 3Ph+PEN
400 1150 60m (12 floors) KSA50VA412 (2) 20
630 and 800 1150 60m (12 floors) KSA80VA412 (2) 30
Riser base support length (bracket) including a fire barrier
Description Rating A Connection Type/Max Catalogue number 3Ph Weight kg
cross section +N+PE or 3Ph+PEN
Bottom end feed 400 Lugs/ 2x300mm2 (M12 screws) KSA50AB452 22.000
unit by cables
Bottom end feed 800 (630) Lugs/ 3x300mm2 (M12 screws) KSA80AB452 36.200
unit by cables
End cover 400 KSB50FA2 0.440
800 (630) KSB80FA2 0.510
End feed unit cable connector and end cover
(1) When ordering, state the required length in mm (in multiples of 5 mm) after the reference.
Example : KSA-40EF4B L = 1250 mm.
(2) Order 1 KSA00ZA1 per riser base support length
450
900 - 2300
Y= 450 - 1850
Fire
barrier
Fire
barrier
-
7/27/2019 Residential Busbar Distribution System
20/32
20
Rising main busbar
Canalis KSR (400 to 800A)References
Description Rating A Connection Type/Max Catalogue number 3Ph Weight kg
cross section +N+PE or 3Ph+PEN
Junction sleeve 400 KSE50YA2 2.250
630/800 KSE80YA2 2.600
End cover sleeve 400 KSE50YF2 2.280
630/800 KSE80YF2 2.600
Tap-off outlet shutter 400/630/800 KSE80YB2 0.080
Sealing device All KSA80YB3 0.080
IP54 - dust and damp proof accessories
Rating A Length mm Reference Weight kg
400 2500 KSA-40EA450 40.300
2500 KSA-40EA430 24.200
500 2500 KSA-50EA450 48.800
2500 KSA-50EA430 29.300
630 2500 KSA-63EA450 62.500
2500 KSA-63EA430 37.500
800 2500 KSA-80EA450 80.000
2500 KSA-80EA430 48.000
Straight lengths for switchboard interconnectionWithout tap-off outlets for horizontal runs
Rating A Length mm Reference Weight kg
500 (400) 500 to 1995 KSA-50ES4A (1) 15.000
800 (630) 500 to 1995 KSA-80ES4A (1) 19.600
Feeder straight lengths manufactured to required lengthWithout tap-off outlets for horizontal runs
Description Rating A Maximum height m Catalogue number 3Ph Weight kg
+N+PE or 3Ph+PEN
400 50 KSA00ZA1 8.200
630 50 KSA00ZA1 8.200
800 50 KSA00ZA1 8.200
Riser guiding bracket All KSA80ZM52(1bracket per floor) with
depth adjustment bracket
Fixings vertical riser
Riser base support
wall bracket
(used with Riser support length)
Description Rating A Mounting Type/Max Reference Weight kg
cross section
Bracket 500 (400) KSA-50EZ3 0.330
800 (630) KSA-80EZ3 0.400
Fixing device horizontal feeder lengths (order in multiples of 10)
(1) When ordering, state
the required length in
mm (in multiples of
5mm) after the
reference.
Example: KSA-80ES4A
L=1250mm.
-
7/27/2019 Residential Busbar Distribution System
21/32
21
Rising main busbar
Canalis KSR (400 to 800A)References
KSA-50AB452
Description Rating A Connection Mounting Unit reference Weight kg
Type/Max
cross section
Switched end feed 500 Lugs 1 x 300mm2 Bottom KSA50AB452SW 30.00
unit by cables isolator
bottom
Switched end feed 800 Lugs 2 x 300mm2
Bottom KSA80AB452SW 65.00unit by cables isolator OR
bottom Lugs 3 x 240mm2
End feed unit 500 (400) Lugs/2 x 300mm2 Top KSA50AB462 22.00
by cables top M12 screws
End feed unit 800 (630) Lugs/3 x 300mm2 Top KSA80AB462 36.20
by cables top M12 screws
Centre feed unit 500 (400) Lugs/2 x 300 mm2 Along the run KSA-50BT402 39.000
(M12 screw)
800 (630) Lugs/3 x 300 mm2 Along the run KSA-80BT402 40.000
(M12 screw)
Flange feed unit 500 (400) Bars Bottom or top KSA-50ER4 4.100
(M12 screw)
800 (630) Bars Bottom or top KSA-80ER4 6.150
(4 x M10 screw)
KV-KS connector 500 (400) Bottom or top KV0-50ER41001 23.800
800 (630) Bottom or top KV0-80ER41001 43.000
Connection components and feed units (2)
N
KV0-50ER41001
KSALP41
Description Rating A Mounting Type/Max Unit reference Weight kg
cross section
Elbows 500 (400) Edgewise KSA-50LC40 9.860
Flat upwards (1) KSA-50LP41 10.000
Flat downwards (1) KSA-50LP42 10.000
800 (630) Edgewise KSA-80LC40 15.000
Flat upwards (1) KSA-80LP41 13.700
Flat downwards (1) KSA-80LP42 13.700
Tee 500 (400) Edgewise KSA-50TC40 15.000
800 (630) Edgewise KSA-80TC40 18.240
Cross 500 (400) Edgewise KSA-50XC40 16.500
800 (630) Edgewise KSA-80XC40 20.000
Components for changing direction (2)
(1) IP54 achieved with sealing accessories. See page 20
(2) Other run components IP54 as standard, common to versions of 3L+N+PE and 3L+PEN straight lengths.
-
7/27/2019 Residential Busbar Distribution System
22/32
22
Medium power busbar trunking
Canalis KSR (400 to 800A)References
Rating A Fuse size Connection Continuous (1) Reference Reference Weight kg
AC 22/23 mm2 rating of device
A
32 BS88 (2) 10 32 KSE-03ST41 Twinbreak Switchfuse 9.0
63 BS88 (2) 35 63 KSE-06ST41 Twinbreak Switchfuse 10.5
100 BS88 (2) 70 90 KSE-10ST41 Twinbreak Switchfuse 10.5
125 BS88 (2) 150 100 KSE-12ST41 Twinbreak Switchfuse 11.0
160 BS88 (2) 240 120 KSE-16ST41 Twinbreak Switchfuse 11.0
250 BS88 (2) 240 200 KSE-25ST41 Fupact Fuseswitch 26.0
315 BS88 (2) 240 250 KSE-31ST41 Fupact Fuseswitch 26.5
400 BS88 (2) 240 250 KSE-40ST41 Fupact Fuseswitch 26.5
Tap-off units, switchfuse and fuseswitch
(1) In 350C ambient.
(2) BS 88 fuse links not provided.
-
7/27/2019 Residential Busbar Distribution System
23/32
23
Medium power busbar trunking
Canalis KSR (400 to 800A)References
KSE-16DB411SP3
KSE-16DB411
Number of conductors 3L + N + PE
Scheme (1) Trunking TT TNS
Tap-off TT TNS
Tap-off scheme
Rating A Type of circuit breaker Reference Weight kg
fitted
25 NS100N/TM25D KSE16DB411SP1 12.6
63 NS100N/TM63D KSE16DB411SP2 12.9
100 NS100N/TM100D KSE16DB411SP3 12.9
125 NS100N/TM125D KSE16DB411SP4 12.9
160 NS160N/TM160D KSE16DB411SP5 13.1
200 NS250N/TM200D KSE25DB411SP1 15.8
250 NS250N/TM250D KSE25DB411SP2 15.8
400 NS400N/STR23SE KSE40DB411SP3 19.5
Tap-off units for Merlin Gerin Compact NS fixed circuit breaker complete
Fully assembled fitted with N frame MCCB and door interlocked rotary handle
Rating A Type of circuit breaker Reference Weight kg
100 NS100 (either) N,H,L (1) KSE16DB411 (2) 11.0
160 NS160 (either) N,H,L (1) KSE16DB411 (2) 11.0
250 NS250 (either) N,H,L (1) KSE25DB411 (2) 13.5
400 NS400 (either) N,H,L(1)
KSE40DB411(3)
13.5
Empty tap-off units for Merlin Gerin Compact NS fixed circuit breaker
Standard extendable rotary handle (not included)
(1) Selection of moulded case circuit breaker, please refer to the Merlin Gerin circuit breaker brochure
available from 0870 608 8 608
(2) A standard extended rotary handle part No. 29338 needs to be fitted with the MCCB.
(3) A standard extended rotary handle Part No. 32598 needs to be fitted with the MCCB.
-
7/27/2019 Residential Busbar Distribution System
24/32
24
Medium power busbar trunking
Canalis KSR (400 to 800A)References
Trunking riser lengths 400, 600 and 800A
KSA-40VD, KSA-63VD, KSA-80VD
250
500
500
2000
250
500
500
500
2500
a
146
Rating A a
400/500 75
630/800 113
-
7/27/2019 Residential Busbar Distribution System
25/32
25
Medium power busbar trunking
Canalis KSR (400 to 800A)References
Trunking feeder lengths 400, 500, 630 and 800A
KSA-40ED, KSA-50ED, KSA-63ED, KSA-80ED
Fire barrier lengths 400, 600, 800A
Straight lengths manufactured to required length
KSA-ES4A
750100010001000
5000
1000250
2501000100010001000750
a
146
450
L = 900 - 2300
Y= 450 - 1850
(1) a
215 13
103
290
450
70057
55
120 - 150
Rating A a
400/500 75
630/800 113
Rating A a
400/500 75
630/800 113
(1) Minimum 500. Maximum 1995
-
7/27/2019 Residential Busbar Distribution System
26/32
26
Medium power busbar trunking
Canalis KSR (400 to 800A)Dimensions (mm)
Feed units for 400 and 800A trunking - KSA-BT402, KSA-AB42
B
B-20
170
300
177
660 100011
AA1
DD1
C
C-20
F
G
AB11
928
770
388
433 331
259
127
89
344
450
400
11
Rating A A A1 B
400/500 290 235 510
630/800 390 316 556
Rating A A B C D D1 F G
400/500 600 770 406 230 175 300 150
630/800 680 850 556 310 236 300 190
37
20
14
808080
143
315
370
340
290
170220250 7
N40
16
11
808080
166
338
370
340
290
210260290 7
N 72
40
Cable outlet
Cable outlet
1058
900
650
695 429
299
147
91
450
409
400
11
Flange feeder unit
KSA-50ER4 KSA-80ER4
KSA-BT402 KSA-AB42
KSA-80AB402SWKSA-50AB402SW
-
7/27/2019 Residential Busbar Distribution System
27/32
27
Medium power busbar trunking
Canalis KSR (400 to 800A)Dimensions (mm)
End covers
KSA-50ER4, KSA-80ER4
Elbows, tee and cross for 400 to 800A trunking
KSA-LC40 KSA-LP41 KSA-LP42
KSA-TC40 KSA-XC40
Rating A a
400/500 75
630/800 113
20
KV-KS connector
KV0-ER41001
146
2000
a
N 146
290
a
290
N
a
290
290
290
146
290 290
580
a
290 290
580
290
290
580
146
a
N
N
a
290
290
Rating A a
500 75
800 113
-
7/27/2019 Residential Busbar Distribution System
28/32
28
Medium power busbar trunking
Canalis KSR (400 to 800A)Dimensions (mm)
Fixing brackets
KSA-80ZM52 KSA-50EZ3 KSA-80EZ3
Sealing and joining kits
KSE-50YA2 KSE-80YA2
230
21 120-150
115 30
36
50
50 1
76
8x14
40
105
190
323
Tap-off blanking plate
KSE-80YB2
a
155
95
140
200
323
Dust and damp proof tap-off units with/without isolator for modular equipment
KSE-05DA KSE-10DA
270
183
507.5 modules (140 x 47)
70
113*
40
195
190
395
7.5 modules (140 x 47)
52
100
152 30
36
50
50 1
76
8x14
40
Rating A a
100/250 70
40/500 90
630 and 800 125
-
7/27/2019 Residential Busbar Distribution System
29/32
29
Medium power busbar trunking
Canalis KSR (400 to 800A)Dimensions (mm)
Dust and damp proof tap-off units for Merlin Gerin circuit breakers
KSE-16DB11 KSE-25DB11 KSE-40DB11
465
147
368
163
15
197
780
275
36818
163
325
590
207
15
163
368
257
Dust and damp proof tap-off units for fused switch disconnector
306
147
271 10
50
51
406
147
271 10
50
51
456
147
271 10
50
51
606
232
421 10
50
46
KSE-03ST41 KSE-06ST41
KSE-10ST41
KSE-12ST41
KSE-16ST41
KSE-25ST41
KSE-31ST41
KSE-40ST41
-
7/27/2019 Residential Busbar Distribution System
30/32
30
Second floor
First floor
Ground floor
End feeder box
Guide bracket
Guide bracket
Feeder busbar
Riser suppor bracket
Fire barrier
Feeder busbar
Fire barrier
250
500
500
500
450
450
250
500
500
Floor to floor height3500 - 4900
3500
505
2000
1150
2500
Medium power busbar trunking
4 tap-off outlets floor to floor 3500mm to 4900mm
Canalis KSR (400 to 800A)Riser system
-
7/27/2019 Residential Busbar Distribution System
31/32
31
Second floor
First floor
Ground floor
End feeder box
Guide bracket
Guide bracket
Feeder busbar
Riser suppor bracket
Fire barrier
Feeder busbar
Fire barrier
250
500
500
450
450
250
500
500
Floor to floor height2900 - 3495
3500
505
2000
1150
2000
3 tap-off outlets floor to floor 2900mm to 3495mm
Canalis KSR (400 to 800A)Riser system
Medium power busbar trunking
-
7/27/2019 Residential Busbar Distribution System
32/32
Merlin Gerin is a world leader in the manufacture and
supply of high, medium and low voltage products for the
distribution, protection, control and management of
electrical systems. Its quality products, solutions and
services are focused on the needs of both the commercial
and industrial sectors.
Modicon is a world leader in high technology
programmable controllers (PLCs) and motion control
systems used in industrial automation. Its international
catalogue includes PLCs, numerical controllers, terminals,
software, multiple fieldbus and ethernet communication
networks, and human machine interfaces (HMI).
Square D is a total quality organisation and its business
is to put electricity to work productively and effectively,
protecting people, buildings and equipment. Its low voltage
electrical distribution equipment, systems and services are
used extensively in residential and commercial applications.
Telemecanique is a UK market leader and world expert
in industrial control and automation. It provides complete
solutions, with its range of components, programmable
logic controllers, variable speed drives and communications
software. In addition, it offers power distribution through
prefabricated busbar trunking.
Schneider Electrics local support
Schneider Electric is committed to supporting its customers at every stage of a project. Our 180 sales engineers, the largest
dedicated sales force in the UK electrical industry, operate from 4 customer support centres.
Our sales engineers are skilled at assessing individual requirements and combined with the expert support of our product
specialists, will develop the most effective and economical answer taking relevant regulations and standards fully into account.
To access the expertise of the Schneider Electric group, please call 0870 608 8 608. Each customer support centre includes
facilities for demonstrations and training, and presentation rooms fully equipped with audio visual and video, providing
excellent meeting facilities.
Scotland
Schneider Electric Ltd
Unit 11000
Academy Business Park
Gower Street
Glasgow G51 1PR
South West
Schneider Electric Ltd
190 Aztec West
Park Avenue
Almondsbury
Bristol BS32 4TP
North West
Schneider Electric Ltd
8 Brindley Road
City Park Business Village
Cornbrook
Manchester M16 9HQ
Greater London
Schneider Electric Ltd
2nd Floor
408 Strand
London WC2R 0NE
Industrial systems and solutions product showroom
Schneider Electric Ltd, University of Warwick Science Park, Sir William Lyons Road, Coventry CV4 7EZ
Building systems and solutions product showroom
Schneider Electric Ltd, Fordhouse Road, Wolverhampton WV10 9ED
Energy and Infrastructure systems and solutions product showroom
Schneider Electric Ltd, 123 Jack Lane, Hunslet, Leeds LS10 1BS
Regional product showrooms
Local customer support centres
Fax 0870 608 8 606
0870 608 8 608
Nationwide support on one number -
call the Customer Information Centre on