Residential Busbar Distribution System

download Residential Busbar Distribution System

of 32

Transcript of Residential Busbar Distribution System

  • 7/27/2019 Residential Busbar Distribution System

    1/32

    Canalis

    Rising main KSRbusbar trunking

    for multi-storey buildings

    Selection guide

  • 7/27/2019 Residential Busbar Distribution System

    2/32

    Canalis rising main busbar trunking

    cuts installation costs in multi-storey buildings

    2

    The Canalis KSR rising main busbar trunking system launched byTelemecanique enables electrical distribution to be rapidly installed

    in multi-storey buildings of all types, including office blocks, hotels,

    hospitals and car parks. Canalis KSR improves safety, cuts

    installation time and reduces the overall cost of installing

    distribution systems.

    Fire barriers at

    each floor

    Canalis KSR

    incorporates a solid

    fire barrier at each

    floor, giving aminimum of two hours

    fire protection. This

    minimises the risk of

    fire spreading in

    multi-storey

    buildings where

    vertical ducting can

    provide a path for

    fumes, smoke and

    fire. Canalis KSR

    meets the most

    stringent interpretation

    of the Building

    Regulations for fire

    safety.

    Rated at 400-800A,

    Canalis KSR is the

    first rising main

    busbar trunking to use

    aluminium conductors

    as standard. The

    system is lighter and

    easier to handle on

    site than conventional

    copper busbar

    trunking, allowing fastinstallation.

    At around half the

    weight of traditional

    copper conductor

    based busbar

    trunking, Canalis KSR

    can be fitted in many

    installations by one

    person. Its lightness

    means it needs fewer

    mechanical fixings,

    making it even faster

    to install.

    Fast installation

    allows contractors to

    meet the extremely

    short deadlines that

    are becoming

    increasingly common

    in todays building

    market.

    Canalis KSR busbar

    sections are linked by

    joint kits bolted in

    place, complete with

    an expansion joint

    that ensures a secure,

    safe and easy-to-

    make connection.

    Silver-to-silver

    contacts provide

    excellent conductivity

    at all joints.

    This simple connection

    method makes it

    easier to install the

    distribution system

    safely, first time.

    Canalis KSR is one of

    the safest rising main

    busbar trunking

    systems available.

    Interlocks on the

    tap-off units prevent

    live loads being

    connected or

    disconnected. The

    busbar sections are

    finger-safe to IP2X,

    even when no tap-off

    units are fitted. All of

    which means that

    tap-off units can besafely connected to a

    live system if this is

    unavoidable.

  • 7/27/2019 Residential Busbar Distribution System

    3/32

    3

    KSR issuitable formanyapplications

    Canalis KSR is

    designed for medium

    power distribution with

    high tap-off density in

    multi-storey office

    blocks and

    commercial and

    industrial buildings.

    The range is availablein 3 ratings: 400A,

    630A and 800A.

    The standard IP54

    degree of protection

    makes KSR suitable

    for many locations.

    This is achieved by

    the addition of dust

    and damp proof

    blanking plates on the

    tap-off outlets and

    joints. Connection is

    via tap-off units.These units, from 25

    to 400A, can be safely

    removed while the

    busbar trunking is

    live because they

    feature mechanical

    and electrical

    interlocks as

    standard.

    KSR riser can also be

    fitted with any other

    products from the

    established CanalisKSA busbar trunking

    range.

    KSR rising main is aspecific version of

    KSA busbar trunking

    for energy distribution

    to each floor of a

    multi-storey building.

    KSR retains all the

    construction principles

    of KSA trunking for

    horizontal distribution,

    in particular:

    Aluminiumconducting bars

    are equipped withbi-metal silvercopper laminatesaddles fitted atthe points ofcontact in the

    joints and tap-offoutlets

    The jointing blockwith spring-loadedcontacts, lockedby 1/4-turnfastening (thisblock, which also

    absorbs theexpansion of theconductors,eliminates anymechanical stressat the fire barrier)

    Tap-off outletswith automaticclosingshutters

    Degree ofprotection is IP54

  • 7/27/2019 Residential Busbar Distribution System

    4/32

    4

    A

    C

    BB

    G

    D

    F

    G

    Canalis KSR (400A to 800A)Description

    Medium power busbar trunking

    E

    E

    A

  • 7/27/2019 Residential Busbar Distribution System

    5/32

    5

    Canalis KSR (400A to 800A)Description

    Medium power busbar trunking

    ARiser distribution lengths

    Connection components,

    feed units and end covers

    Fixings

    Tap-off units

    Accessories

    Feeder lengths

    Components for

    changing direction

    Page19

    BPage19 - 21

    CPage20

    DPage22 - 23

    EPage20

    FPage20

    GPage

    21

    APage6 - 7

    BPage8

    CPage9

    DPage10

    EPage11

    FPage12

    GPage

    13

    Product description Product selection

  • 7/27/2019 Residential Busbar Distribution System

    6/32

    4

    3

    2

    1

    5

    6

    6

    Canalis KSR (400A to 800A)Description

    Medium power busbar trunking

    Riser distribution lengths

    The KSR length is equal to the height between 2 floors (floor-to-floor), ranging from2900 to 4840mm (standard length and made to measure fire barrier components).They are equipped with: 3 or 4 tap-off outlets, always positioned at the same height with respect to the

    centre line of the lower floor slab

    1 fire barrier, placed at the level of passage through the floor slab, eliminating

    any risk of fire propagation from one floor to another via the trunking. The fire

    barrier, which has been tested by the laboratory of the University of Gand(Belgium) conforms to the requirements of standard ISO834. According toreport 7296, the following results were obtained:

    Thermal insulation : 120 minutes

    Flame resistance : 120 minutes

    Stability : 120 minutes

    Straight distribution lengths

    Straight lengths are designed to carry current and feed loads with low or mediumpower. The straight lengths form the structure of the run.

    They comprise:

    1 A casing of galvanised sheet steel which is crimped closed

    This casing, shaped and ribbed by rolling, provides excellent resistance tobending and twisting. Two casing widths cover the whole range:

    75mm wide sheet steel with RAL 7032 grey finish for 400A rating

    113mm wide sheet steel with RAL 7032 grey finish for 630 and 800A

    ratings

    2 4 live conductors of the same cross-section:

    Aluminium fitted with bi-metal silver-plated copper/aluminium laminate

    riders electrically welded to junctions and tap-off positions for 400 to 800Aratings. The lamination is a patented process by which the copper andaluminium molecules are fused together under extreme pressure

    3 Fibreglass reinforced polyester isolators at 250mm intervals.These hold the conductors securely within the casing

    4 A special protected earth (PE) conductor of the same type as the liveconductors with a cross-section 1/2 of the phase cross-section. It isconnected to the casing at each junction

    5 Tap-off outlets on the front face of the trunking at 500mm intervals.They are connected to the isolators to form a block, holding the bars.They have a shuttered outlet which is opened and closed automaticallywhen connectors or tap-off units are plugged in, or removed

    6 A mechanical and electrical jointing device Electrical connection is via ablock with spring and silver graphite contacts. This block absorbs thedifferential conductor/casing expansion of each length equally.It simultaneously connects all the live conductors, ensures continuity of theprotective earth conductor and its connection with the casing.The electrical connection is made by a 1/4 screw turn for each conductor

    A

  • 7/27/2019 Residential Busbar Distribution System

    7/32

    7

    Canalis KSR (400A to 800A)Description

    Medium power busbar trunking

    Fire barrier lengths

    To enable to pass from floor to floor of a multi-story building. Fire resistance of thebarriers is 2 hours (A120) conforming to ISO834

    Riser support fire barrier length

    The first floor is a combined base support length for the complete riserincluding the fire barrier. This is a standard length 1150m.

    Made to measure fire barrier length

    Subsequent floor fire barriers are made to measure lengths to alter the lengthof a run between floor to floor heights.

    These components are manufactured from 900mm to 2300mm in multiples of5mm. They do not have tap-off outlets.

    215 13

    103

    290

    450

    70057

    55

    450

    L = 900 - 2300

    450 - 1850

  • 7/27/2019 Residential Busbar Distribution System

    8/32

    8

    Canalis KSR (400A to 800A)Description

    Medium power busbar trunking

    Connection components, feed units and end covers

    To feed a KSR riser run by cables, or directly from a distribution panel.

    Supply cable

    The feed can be from one end (end feed) or along a run (centre feed). They can be connected by aluminium orcopper cables fitted with suitable cable lugs. There is an undrilled aluminium gland plate which will accept cableglands. This plate can be replaced by a plate fitted with 1-3 cable clamps depending on the rating (to be

    ordered separately)

    A End feed units - For bottom or top connection

    B Centre feed unit - Through run type (1 cable feeds the right and left sections)It is mounted along the run, between 2 straight lengths

    Direct supplyfrom switchboard

    Using a connection unit with spreader bars mounted at the end of a horizontal run carried out using lengths

    with or without additional tap-off outlets

    C Flange feed unit - Fitted with splayed bars and a mounting plate. It is used for connection to adistribution panel. It can be mounted at either end of a component

    KV-KSR connector

    The KV-KSR connector is fitted with a KV end length at one end and a KSA end length at the other. Due to itsflexible design, it ensures direct connection from a feed run to a distribution run and reduces any risk caused by

    alignment faults

    D End cover

    The end cover protects and isolates the ends of the conductors. It is mounted on the last length.Two products cover the entire KSR range: 400 and 800A.

    D

    B

    C

    A

    B

  • 7/27/2019 Residential Busbar Distribution System

    9/32

    9

    Canalis KSR (400A to 800A)Description

    Medium power busbar trunking

    Fixings

    Used to fix the riser run to the structure of the building, directly or via an adjustable universal guide.

    Bottom support for riser

    Equips the fire barrier first joint at the bottom of the rising main. Angle wall brackets are fixed to the wall by

    standard fixings (supplied by others). This unit supports the complete rising main (for design guide see page 14)

    Universal GuideThis bracket maintains the trunking in position at each floor. Two adjustable fixing straps are supplied to give a30mm depth adjustment from the supporting wall.

    C

  • 7/27/2019 Residential Busbar Distribution System

    10/32

    10

    Canalis KSR (400A to 800A)Description

    Medium power busbar trunking

    Tap-off units BS88 fuse links

    Tap-offs are provided by KSR tap-off units, either :

    Switch fuse and Fuse switch tap-offs 32A to 400A fuses

    100 to 400A moulded case circuit breaker

    Standard KSA units with isolators and fuse carriers for 25 to 160A fuses

    These fused tap-off units are designed to protect the tap-off by means

    of fuses (not supplied).They can be fitted with carriers for the following fuses:

    32 to 160A fused on-load tap-off unit, switch fuse on-load tap-off unit

    250 to 400A fused off-load tap-off unit, fuse switch on-load tap-off unit

    Tap-off units for Merlin Gerin circuit breaker

    These units are designed to take Merlin Gerin Compact NS circuit breakers:

    100 to 400A rating

    Version N, H or L

    With or without residual differential device

    With rotary switch

    For other types of circuit breaker, please consult your regional sales office.

    Standard KSA units

    These units can only be mounted on trunking which is installed horizontally on edge. To make installation easier,

    it is performed in two stages:

    The unit is hooked onto the trunking, then automatically located in front of the tap-off outlet by moving it

    sideways

    The fixing brackets are then locked and the mobile power block plugged in, using an internal device

    Used for instant connection of loads or secondary runs (for example, for low power distribution).The connectors and tap-off units conform to installation standards and regulations whatever type of neutral

    point connection is used (TT, IT, TNS or TNC).

    They can be removed and moved whilst live, with no load

    The tap-off outlets are opened and closed automatically when units are plugged in or removed

    With the cover open, no live part can be accessed. Degree of protection IP2X Connectors and tap-off units are made in two versions

    Protected version, degree of protection IP54, suitable for most industrial and commercial applications

    Tap-off units with isolator for

    modular equipment

    All standard KSA tap-off units are available tobe fitted to the KSR busbar riser products.

    A selection guide for the KSA range is availableupon request. Please contact Tel: 0870 608 8 608.

    D

  • 7/27/2019 Residential Busbar Distribution System

    11/32

    11

    Medium power busbar trunking

    Canalis KSR (400A to 800 A)Description

    Accessories

    To achieve the degree of protection, IP54, the following accessories are fitted to the riser.

    Vertical and flat installation

    1 Each tap-off outlet not being used, should be fitted with a sealed tap-off blanking plate

    2 Each junction between components should be fitted with a jointing sleeve to maintain the IP54 projection

    Various devices, for lead sealing in particular, can be used to complete the equipment of the

    KSR rising main.

    2

    1

    E

  • 7/27/2019 Residential Busbar Distribution System

    12/32

    12

    Canalis KSR (400 to 800A)Description

    Medium power busbar trunking

    Feeder lengths (with or without tap-off outlets)

    These lengths, without tap-off outlets are used as feeders, running horizontally (generally in the basement or inthe utilities ducting) between the switchboard and the bottom of the distribution rising main.

    Any complementary lengths required for this horizontal run (elbows, special lengths, fire barriers) can beselected for the KSA components from the Canalis Busbar Trunking and Power Applications catalogueavailable upon request. Please contact 0870 608 8 608.

    F

  • 7/27/2019 Residential Busbar Distribution System

    13/32

    13

    Canalis KSR (400 to 800A)Description

    Medium power busbar trunking

    Components for changing direction

    Edgewise elbow

    One model for each size of casing for turning to left or right

    Flat elbow

    Two models for each size of casing (one ascending, one descending). Flat and edgewise elbows can bemanufactured upon request, with made to measure connection lengths, with multiple angles, withbuilt-in fire barrier, etc. for the KSA components from the Canalis Busbar Trunking and Power Applications

    catalogue available upon request. Please contact 0870 608 8 608.

    Edgewise tee and cross

    For vertical branches on the main

    G

  • 7/27/2019 Residential Busbar Distribution System

    14/32

    14

    Basement

    Information required to design a KSR riser system

    The types of load and their characteristics and floor locations

    The power source and its characteristics and location

    The structure of the premises (availability of fixing points for trunking)

    Any influences external to the installation site. (ambient temperature, dust, water, etc)

    Distribution run layout

    The siting of rising main depends on the position of the loads, the location of the general power supply and theavailability of fixing points. A single supported KSR riser run can serve up to 12 floors (60 metres).

    Selection of the trunking according to the rated operating current Ib

    k1 = average demand coefficient Ib = total current x k1

    Total current = sum of currents drawn by the loads on a run

    Permissible current Iz according to the ambient temperature(at the installation site)

    The nominal current Inc of the trunking is specified for an average daily ambient temperature of 35C(and a maximum of 40C). Depending on the actual temperature, an uprating or derating coefficient (f1) may beapplied to the nominal current Inc : see the characteristics on page 17.

    Checking the voltage drop

    The voltage drop in Canalis KS is given in V/100m/A in the characteristics table on page 17.

    Polarity selection

    Applications k1

    Lighting, heating 1

    Distribution

    2 or 3 loads 0.9

    4 or 5 loads 0.8

    6...9 loads 0.7

    10...40 loads 0.6

    40 or more 0.5

    Rated operating current Ib Selected trunking

    0...100 A KS-10

    100...160 A KS-16

    160...250 A KS-25

    315...400 A KS-40

    400...500 A KS-50

    500...630 A KS-63

    630...800 A KS-80

    4 tap-offs per floor

    Canalis KSR (400 to 800A)Design guide

    Medium power busbar trunking

    3L + PE(IT-TT-TNS)

    3L + N + PE(IT-TT-TNS)

    3L + PE(IT-TT-TNS)

    3L + N + PE(IT-TT-TNS)

    3-pole distribution + N

    + PE (IT-TT-TNS)

    KSA-D4

    trunking3-pole + N + PE tap-offspossible, type 3-pole +PE or 3-pole + N + PE

    3-pole distribution +

    PEN (TNC)

    KSA-ED4

    trunking3-pole + PEN tap-offspossible, type 3-pole +PEN (TNC) or 3-pole +N + PE (TNS).

  • 7/27/2019 Residential Busbar Distribution System

    15/32

    15

    Canalis KSR : rating (A) 100 160 250 400 500 630 800

    Type of NS100 N 25

    Merlin Gerin H 25

    circuit breaker (1) L 25

    NS160 N 20 36

    H 20 70

    L 20 70

    NS250 N 36 36

    H 55 70

    L 55 150

    NS400 N 45 45

    H 45 70

    L 45 150

    NS630 N 45 45 45

    H 70 70 70

    L 150 150 150

    C801 N 40 50

    H 40 50

    L 55 50

    C1001 N 50

    H 50L 80

    Protecting the trunking against overloads (1)

    To enable it to be extended, prefabricated busbar trunking is generally protected to its nominal current Inc

    (or to its permissible current Iz if the K1 coefficient is applied according to the ambient temperature).

    Protection using fuses

    Calculate the standard nominal current In of the fuse so that : In Inc

    Select the circuit breaker setting current Ir so that : Ib Ir Inc

    Note: Protecting trunking using a circuit breaker makes it possible to use the trunking at full capacity.

    Protection using a circuit breaker

    Select the circuit breaker setting current Ir so that : Ib Ir Inc

    Note: Protecting trunking using a circuit breaker makes it possible to use the trunking at full capacity.

    Electrodynamic protection against short-circuit currents

    The electrodynamic withstand of the trunking should be taken into account when selecting a protective device

    (permissible rated peak current).

    Determine the 3-phase short-circuit current, prospective lcc 3 (KA) at the start of the Canalis KSR

    Check the current limitation curve of the selected protective device, that this limits the peak current (kA) to a

    value below the permissible rated peak current of the KSR trunking. Limited current Canalis current

    Protection using a Merlin Gerin Compact circuit breaker

    The circuit breaker/Canalis co-ordination table below gives the maximum short-circuit current for which theKSR trunking is protected, according to the type of circuit breaker.Prospective Icc 3, max (Ka rms) voltage 380/415V.

    (1) By calculation or using graphs, pre-calculated tables, etc.

    Note: To obtain details of the Merlin Gerin circuit breaker range, please refer to the circuit breaker brochure

    available by phone from 0870 608 8 608

    Canalis KSR (400 to 800A)Design guide

    Medium power busbar trunking

    k1

  • 7/27/2019 Residential Busbar Distribution System

    16/32

    16

    B

    A

    Canalis KSR (400 to 800A)Design guide

    Medium power busbar trunking

    External influences are taken into consideration when siting the installation.The IP54 degree of protection of Canalis KSR means that it is suitable forinstallation in most industrial and commercial locations.

    Especially for locations or sites which may be subject to water splashes in anydirection, the degree of protection is achieved by installing sealed tap-off blankingplates and sealed jointing sleeves. (See page 20).

    Selecting the power supply

    A cable feed unit can be mounted at either end of a run, bottom or top

    500 and 800A feed unit

    Two types depending on position:

    Bottom (right hand) mounting (fig. A)

    Top (left hand) mounting (fig. B)

    All types of neutral system. Connected by means of cable lugs.

    Switchboard feed may be connected via cable or busbar interconnector.

    Mounting position

    Tap-off units

    The complete range of tap-off units for KSR are IP54 dust and damp proof range,

    for very dusty or damp environments.

    Changing levels in horizontal distribution

    The trunking is mounted vertically, the degree of protection at a junction isIP54. This is achieved by fitting a standard sealed jointing sleeve at each junction.

    Selection of IP degree of protection

    KSE = IP54

    230

    21 120 - 150

  • 7/27/2019 Residential Busbar Distribution System

    17/32

    17

    Canalis KSR (400 to 800A)Characteristics (1)

    General characteristics (1)

    4 4 4

    A 400 630 800

    Ui V 660 660 660

    Ue V 660 660 660

    F Hz 50/60 50/60 50/60

    Number of conductors

    Rated insulated voltage Conforming to IEC 158-1

    Rated operating voltage

    Rated frequency

    KSA-40 KSA-63 KSA-80Type of trunking

    Fault loop characteristics

    Between live conductors

    Rb1phph m/m 0.38 0.202 0.122

    phN m/m 0.38 0.202 0.122

    phPEN m/m 0.2613 0.1409 0.0929

    Rb2phph m/m 0.45 0.239 0.144

    phN m/m 0.45 0.239 0.144

    phN m/m 0.3113 0.169 0.1101

    Xbphph m/m 0.252 0.154 0.1475

    phN m/m 0.2915 0.197 0.1895

    phPEN m/m 0.2115 0.1433 0.1395

    Between live conductor and PE

    Rb1phPE m/m 0.304 0.167 0.128

    Rb2phPE m/m 0.365 0.201 0.153

    XbphPE m/m 0.303 0.225 0.226

    Average resistance of loop

    (thermal stabilisation temp. 01)

    Average resistance of loop (1)

    (short-circuit conventional temp.)

    Average reactance loop

    Average resistance of loop

    (thermal stabilisation temp. 01)

    Average resistance of loop (1)

    (short-circuit conventional temp.)

    Average reactance loop

    KSA-40 KSA-63 KSA-80Type of trunking

    (1) Conforming to international standard IEC 439-2 and European standard EN 60439.2

    Medium power busbar trunking

    Nominal rated current INC to 350C

  • 7/27/2019 Residential Busbar Distribution System

    18/32

    18

    Conductor characteristics

    Live conductors (per conductor)

    GE resistance, cold state Rboph(1) m/m 0.142 0.074 0.045

    (ambient temperature 20C)

    R1 average resistance at/nc Rb1ph(1) m/m 0.190 0.101 0.061

    (ambient temperature 35C)

    X1 average resistance at/nc Xbph(1) m/m 0.112 0.070 0.071

    and at rated frequency (Hz)

    Protective conductors

    Average resistance, cold state m/m 0.105 0.061 0.061

    (ambient temperature 35C)

    KSA-40 KSA-63 KSA-80Type of trunking

    Other characteristics

    KSA-40 KSA-63 KSA-80Type of trunking

    Destination of permissible current

    Iz for a busbar trunking system,

    according to ambient temperature

    (1) Conforming to international standard IEC 439-2 and European standard EN 60439.2

    Canalis KSR (100 to 800A)Characteristics (1)

    Medium power busbar trunking

    Short-circuit withstand capacity

    Maximum thermal limit 12 t ph or N kA 354x106 1225x106 1758x106

    PE kA 354x106 1225x106 1225x106

    PEN kA 500x106 2000x106 2500x106

    Permissible rated peak current Ipk kA 49.2x106 67.5x106 78.7x106

    Degree of protection

    IP54 With accessories.

    Voltage drop Composite voltage drop, hot state, expressed in V/100 m/A

    for 3 phase 50Hz current, with load

    distributed along the run. Where the load is concentrated

    at the end of a feed run, the voltage drops

    are twice the values indicated in the table.

    For a power factor Cos f=1.0 V/100 m/A 0.01645 0.00875 0.00528

    For a power factor Cos f=0.9 V/100 m/A 0.01904 0.01051 0.00743

    For a power factor Cos f=0.8 V/100 m/A 0.01898 0.01063 0.00792

    For a power factor Cos f=0.7 V/100 m/A 0.01844 0.01045 0.00805

    Derating or uprating factor to be applied to the rated

    current of the trunking where the average daily ambient

    temperature is other than 35C

    Average ambient temperature C 15 20 25 30 35 40 45 50 55

    Factor f1 1.11 1.08 1.06 1.03 1.00 0.97 0.94 0.91 0.87

  • 7/27/2019 Residential Busbar Distribution System

    19/32

    Rising main busbar

    19

    Canalis KSR (400 to 800A)References

    Rating A Length no. of tap-off outlets Catalogue number 3Ph Weight kg

    (front face) +N+PE or 3Ph+PEN

    400 2000 3 KSA40VD420 16

    2500 4 KSA40VD425 20

    630 2000 3 KSA63VD420 24

    2500 4 KSA63VD425 30

    800 2000 3 KSA80VD420 28

    2500 4 KSA80VD425 35

    Rating A Length Length of Length of part on Catalogue number 3Ph Weight kg

    (L) top part measurement Y= +N+PE or 3Ph+PEN Min. Max.

    400 900-2300(1) 450 450...1850 KSA40EF4B 8 20

    630 900-2300(1) 450 450...1850 KSA63EF4B 12 30

    800 900-2300(1) 450 450...1850 KSA80EF4B 14 35

    Floor distribution lengths

    Additional fire barrier lengths

    Rating A Length Total supportable Catalogue number 3Ph Weight kg

    height +N+PE or 3Ph+PEN

    400 1150 60m (12 floors) KSA50VA412 (2) 20

    630 and 800 1150 60m (12 floors) KSA80VA412 (2) 30

    Riser base support length (bracket) including a fire barrier

    Description Rating A Connection Type/Max Catalogue number 3Ph Weight kg

    cross section +N+PE or 3Ph+PEN

    Bottom end feed 400 Lugs/ 2x300mm2 (M12 screws) KSA50AB452 22.000

    unit by cables

    Bottom end feed 800 (630) Lugs/ 3x300mm2 (M12 screws) KSA80AB452 36.200

    unit by cables

    End cover 400 KSB50FA2 0.440

    800 (630) KSB80FA2 0.510

    End feed unit cable connector and end cover

    (1) When ordering, state the required length in mm (in multiples of 5 mm) after the reference.

    Example : KSA-40EF4B L = 1250 mm.

    (2) Order 1 KSA00ZA1 per riser base support length

    450

    900 - 2300

    Y= 450 - 1850

    Fire

    barrier

    Fire

    barrier

  • 7/27/2019 Residential Busbar Distribution System

    20/32

    20

    Rising main busbar

    Canalis KSR (400 to 800A)References

    Description Rating A Connection Type/Max Catalogue number 3Ph Weight kg

    cross section +N+PE or 3Ph+PEN

    Junction sleeve 400 KSE50YA2 2.250

    630/800 KSE80YA2 2.600

    End cover sleeve 400 KSE50YF2 2.280

    630/800 KSE80YF2 2.600

    Tap-off outlet shutter 400/630/800 KSE80YB2 0.080

    Sealing device All KSA80YB3 0.080

    IP54 - dust and damp proof accessories

    Rating A Length mm Reference Weight kg

    400 2500 KSA-40EA450 40.300

    2500 KSA-40EA430 24.200

    500 2500 KSA-50EA450 48.800

    2500 KSA-50EA430 29.300

    630 2500 KSA-63EA450 62.500

    2500 KSA-63EA430 37.500

    800 2500 KSA-80EA450 80.000

    2500 KSA-80EA430 48.000

    Straight lengths for switchboard interconnectionWithout tap-off outlets for horizontal runs

    Rating A Length mm Reference Weight kg

    500 (400) 500 to 1995 KSA-50ES4A (1) 15.000

    800 (630) 500 to 1995 KSA-80ES4A (1) 19.600

    Feeder straight lengths manufactured to required lengthWithout tap-off outlets for horizontal runs

    Description Rating A Maximum height m Catalogue number 3Ph Weight kg

    +N+PE or 3Ph+PEN

    400 50 KSA00ZA1 8.200

    630 50 KSA00ZA1 8.200

    800 50 KSA00ZA1 8.200

    Riser guiding bracket All KSA80ZM52(1bracket per floor) with

    depth adjustment bracket

    Fixings vertical riser

    Riser base support

    wall bracket

    (used with Riser support length)

    Description Rating A Mounting Type/Max Reference Weight kg

    cross section

    Bracket 500 (400) KSA-50EZ3 0.330

    800 (630) KSA-80EZ3 0.400

    Fixing device horizontal feeder lengths (order in multiples of 10)

    (1) When ordering, state

    the required length in

    mm (in multiples of

    5mm) after the

    reference.

    Example: KSA-80ES4A

    L=1250mm.

  • 7/27/2019 Residential Busbar Distribution System

    21/32

    21

    Rising main busbar

    Canalis KSR (400 to 800A)References

    KSA-50AB452

    Description Rating A Connection Mounting Unit reference Weight kg

    Type/Max

    cross section

    Switched end feed 500 Lugs 1 x 300mm2 Bottom KSA50AB452SW 30.00

    unit by cables isolator

    bottom

    Switched end feed 800 Lugs 2 x 300mm2

    Bottom KSA80AB452SW 65.00unit by cables isolator OR

    bottom Lugs 3 x 240mm2

    End feed unit 500 (400) Lugs/2 x 300mm2 Top KSA50AB462 22.00

    by cables top M12 screws

    End feed unit 800 (630) Lugs/3 x 300mm2 Top KSA80AB462 36.20

    by cables top M12 screws

    Centre feed unit 500 (400) Lugs/2 x 300 mm2 Along the run KSA-50BT402 39.000

    (M12 screw)

    800 (630) Lugs/3 x 300 mm2 Along the run KSA-80BT402 40.000

    (M12 screw)

    Flange feed unit 500 (400) Bars Bottom or top KSA-50ER4 4.100

    (M12 screw)

    800 (630) Bars Bottom or top KSA-80ER4 6.150

    (4 x M10 screw)

    KV-KS connector 500 (400) Bottom or top KV0-50ER41001 23.800

    800 (630) Bottom or top KV0-80ER41001 43.000

    Connection components and feed units (2)

    N

    KV0-50ER41001

    KSALP41

    Description Rating A Mounting Type/Max Unit reference Weight kg

    cross section

    Elbows 500 (400) Edgewise KSA-50LC40 9.860

    Flat upwards (1) KSA-50LP41 10.000

    Flat downwards (1) KSA-50LP42 10.000

    800 (630) Edgewise KSA-80LC40 15.000

    Flat upwards (1) KSA-80LP41 13.700

    Flat downwards (1) KSA-80LP42 13.700

    Tee 500 (400) Edgewise KSA-50TC40 15.000

    800 (630) Edgewise KSA-80TC40 18.240

    Cross 500 (400) Edgewise KSA-50XC40 16.500

    800 (630) Edgewise KSA-80XC40 20.000

    Components for changing direction (2)

    (1) IP54 achieved with sealing accessories. See page 20

    (2) Other run components IP54 as standard, common to versions of 3L+N+PE and 3L+PEN straight lengths.

  • 7/27/2019 Residential Busbar Distribution System

    22/32

    22

    Medium power busbar trunking

    Canalis KSR (400 to 800A)References

    Rating A Fuse size Connection Continuous (1) Reference Reference Weight kg

    AC 22/23 mm2 rating of device

    A

    32 BS88 (2) 10 32 KSE-03ST41 Twinbreak Switchfuse 9.0

    63 BS88 (2) 35 63 KSE-06ST41 Twinbreak Switchfuse 10.5

    100 BS88 (2) 70 90 KSE-10ST41 Twinbreak Switchfuse 10.5

    125 BS88 (2) 150 100 KSE-12ST41 Twinbreak Switchfuse 11.0

    160 BS88 (2) 240 120 KSE-16ST41 Twinbreak Switchfuse 11.0

    250 BS88 (2) 240 200 KSE-25ST41 Fupact Fuseswitch 26.0

    315 BS88 (2) 240 250 KSE-31ST41 Fupact Fuseswitch 26.5

    400 BS88 (2) 240 250 KSE-40ST41 Fupact Fuseswitch 26.5

    Tap-off units, switchfuse and fuseswitch

    (1) In 350C ambient.

    (2) BS 88 fuse links not provided.

  • 7/27/2019 Residential Busbar Distribution System

    23/32

    23

    Medium power busbar trunking

    Canalis KSR (400 to 800A)References

    KSE-16DB411SP3

    KSE-16DB411

    Number of conductors 3L + N + PE

    Scheme (1) Trunking TT TNS

    Tap-off TT TNS

    Tap-off scheme

    Rating A Type of circuit breaker Reference Weight kg

    fitted

    25 NS100N/TM25D KSE16DB411SP1 12.6

    63 NS100N/TM63D KSE16DB411SP2 12.9

    100 NS100N/TM100D KSE16DB411SP3 12.9

    125 NS100N/TM125D KSE16DB411SP4 12.9

    160 NS160N/TM160D KSE16DB411SP5 13.1

    200 NS250N/TM200D KSE25DB411SP1 15.8

    250 NS250N/TM250D KSE25DB411SP2 15.8

    400 NS400N/STR23SE KSE40DB411SP3 19.5

    Tap-off units for Merlin Gerin Compact NS fixed circuit breaker complete

    Fully assembled fitted with N frame MCCB and door interlocked rotary handle

    Rating A Type of circuit breaker Reference Weight kg

    100 NS100 (either) N,H,L (1) KSE16DB411 (2) 11.0

    160 NS160 (either) N,H,L (1) KSE16DB411 (2) 11.0

    250 NS250 (either) N,H,L (1) KSE25DB411 (2) 13.5

    400 NS400 (either) N,H,L(1)

    KSE40DB411(3)

    13.5

    Empty tap-off units for Merlin Gerin Compact NS fixed circuit breaker

    Standard extendable rotary handle (not included)

    (1) Selection of moulded case circuit breaker, please refer to the Merlin Gerin circuit breaker brochure

    available from 0870 608 8 608

    (2) A standard extended rotary handle part No. 29338 needs to be fitted with the MCCB.

    (3) A standard extended rotary handle Part No. 32598 needs to be fitted with the MCCB.

  • 7/27/2019 Residential Busbar Distribution System

    24/32

    24

    Medium power busbar trunking

    Canalis KSR (400 to 800A)References

    Trunking riser lengths 400, 600 and 800A

    KSA-40VD, KSA-63VD, KSA-80VD

    250

    500

    500

    2000

    250

    500

    500

    500

    2500

    a

    146

    Rating A a

    400/500 75

    630/800 113

  • 7/27/2019 Residential Busbar Distribution System

    25/32

    25

    Medium power busbar trunking

    Canalis KSR (400 to 800A)References

    Trunking feeder lengths 400, 500, 630 and 800A

    KSA-40ED, KSA-50ED, KSA-63ED, KSA-80ED

    Fire barrier lengths 400, 600, 800A

    Straight lengths manufactured to required length

    KSA-ES4A

    750100010001000

    5000

    1000250

    2501000100010001000750

    a

    146

    450

    L = 900 - 2300

    Y= 450 - 1850

    (1) a

    215 13

    103

    290

    450

    70057

    55

    120 - 150

    Rating A a

    400/500 75

    630/800 113

    Rating A a

    400/500 75

    630/800 113

    (1) Minimum 500. Maximum 1995

  • 7/27/2019 Residential Busbar Distribution System

    26/32

    26

    Medium power busbar trunking

    Canalis KSR (400 to 800A)Dimensions (mm)

    Feed units for 400 and 800A trunking - KSA-BT402, KSA-AB42

    B

    B-20

    170

    300

    177

    660 100011

    AA1

    DD1

    C

    C-20

    F

    G

    AB11

    928

    770

    388

    433 331

    259

    127

    89

    344

    450

    400

    11

    Rating A A A1 B

    400/500 290 235 510

    630/800 390 316 556

    Rating A A B C D D1 F G

    400/500 600 770 406 230 175 300 150

    630/800 680 850 556 310 236 300 190

    37

    20

    14

    808080

    143

    315

    370

    340

    290

    170220250 7

    N40

    16

    11

    808080

    166

    338

    370

    340

    290

    210260290 7

    N 72

    40

    Cable outlet

    Cable outlet

    1058

    900

    650

    695 429

    299

    147

    91

    450

    409

    400

    11

    Flange feeder unit

    KSA-50ER4 KSA-80ER4

    KSA-BT402 KSA-AB42

    KSA-80AB402SWKSA-50AB402SW

  • 7/27/2019 Residential Busbar Distribution System

    27/32

    27

    Medium power busbar trunking

    Canalis KSR (400 to 800A)Dimensions (mm)

    End covers

    KSA-50ER4, KSA-80ER4

    Elbows, tee and cross for 400 to 800A trunking

    KSA-LC40 KSA-LP41 KSA-LP42

    KSA-TC40 KSA-XC40

    Rating A a

    400/500 75

    630/800 113

    20

    KV-KS connector

    KV0-ER41001

    146

    2000

    a

    N 146

    290

    a

    290

    N

    a

    290

    290

    290

    146

    290 290

    580

    a

    290 290

    580

    290

    290

    580

    146

    a

    N

    N

    a

    290

    290

    Rating A a

    500 75

    800 113

  • 7/27/2019 Residential Busbar Distribution System

    28/32

    28

    Medium power busbar trunking

    Canalis KSR (400 to 800A)Dimensions (mm)

    Fixing brackets

    KSA-80ZM52 KSA-50EZ3 KSA-80EZ3

    Sealing and joining kits

    KSE-50YA2 KSE-80YA2

    230

    21 120-150

    115 30

    36

    50

    50 1

    76

    8x14

    40

    105

    190

    323

    Tap-off blanking plate

    KSE-80YB2

    a

    155

    95

    140

    200

    323

    Dust and damp proof tap-off units with/without isolator for modular equipment

    KSE-05DA KSE-10DA

    270

    183

    507.5 modules (140 x 47)

    70

    113*

    40

    195

    190

    395

    7.5 modules (140 x 47)

    52

    100

    152 30

    36

    50

    50 1

    76

    8x14

    40

    Rating A a

    100/250 70

    40/500 90

    630 and 800 125

  • 7/27/2019 Residential Busbar Distribution System

    29/32

    29

    Medium power busbar trunking

    Canalis KSR (400 to 800A)Dimensions (mm)

    Dust and damp proof tap-off units for Merlin Gerin circuit breakers

    KSE-16DB11 KSE-25DB11 KSE-40DB11

    465

    147

    368

    163

    15

    197

    780

    275

    36818

    163

    325

    590

    207

    15

    163

    368

    257

    Dust and damp proof tap-off units for fused switch disconnector

    306

    147

    271 10

    50

    51

    406

    147

    271 10

    50

    51

    456

    147

    271 10

    50

    51

    606

    232

    421 10

    50

    46

    KSE-03ST41 KSE-06ST41

    KSE-10ST41

    KSE-12ST41

    KSE-16ST41

    KSE-25ST41

    KSE-31ST41

    KSE-40ST41

  • 7/27/2019 Residential Busbar Distribution System

    30/32

    30

    Second floor

    First floor

    Ground floor

    End feeder box

    Guide bracket

    Guide bracket

    Feeder busbar

    Riser suppor bracket

    Fire barrier

    Feeder busbar

    Fire barrier

    250

    500

    500

    500

    450

    450

    250

    500

    500

    Floor to floor height3500 - 4900

    3500

    505

    2000

    1150

    2500

    Medium power busbar trunking

    4 tap-off outlets floor to floor 3500mm to 4900mm

    Canalis KSR (400 to 800A)Riser system

  • 7/27/2019 Residential Busbar Distribution System

    31/32

    31

    Second floor

    First floor

    Ground floor

    End feeder box

    Guide bracket

    Guide bracket

    Feeder busbar

    Riser suppor bracket

    Fire barrier

    Feeder busbar

    Fire barrier

    250

    500

    500

    450

    450

    250

    500

    500

    Floor to floor height2900 - 3495

    3500

    505

    2000

    1150

    2000

    3 tap-off outlets floor to floor 2900mm to 3495mm

    Canalis KSR (400 to 800A)Riser system

    Medium power busbar trunking

  • 7/27/2019 Residential Busbar Distribution System

    32/32

    Merlin Gerin is a world leader in the manufacture and

    supply of high, medium and low voltage products for the

    distribution, protection, control and management of

    electrical systems. Its quality products, solutions and

    services are focused on the needs of both the commercial

    and industrial sectors.

    Modicon is a world leader in high technology

    programmable controllers (PLCs) and motion control

    systems used in industrial automation. Its international

    catalogue includes PLCs, numerical controllers, terminals,

    software, multiple fieldbus and ethernet communication

    networks, and human machine interfaces (HMI).

    Square D is a total quality organisation and its business

    is to put electricity to work productively and effectively,

    protecting people, buildings and equipment. Its low voltage

    electrical distribution equipment, systems and services are

    used extensively in residential and commercial applications.

    Telemecanique is a UK market leader and world expert

    in industrial control and automation. It provides complete

    solutions, with its range of components, programmable

    logic controllers, variable speed drives and communications

    software. In addition, it offers power distribution through

    prefabricated busbar trunking.

    Schneider Electrics local support

    Schneider Electric is committed to supporting its customers at every stage of a project. Our 180 sales engineers, the largest

    dedicated sales force in the UK electrical industry, operate from 4 customer support centres.

    Our sales engineers are skilled at assessing individual requirements and combined with the expert support of our product

    specialists, will develop the most effective and economical answer taking relevant regulations and standards fully into account.

    To access the expertise of the Schneider Electric group, please call 0870 608 8 608. Each customer support centre includes

    facilities for demonstrations and training, and presentation rooms fully equipped with audio visual and video, providing

    excellent meeting facilities.

    Scotland

    Schneider Electric Ltd

    Unit 11000

    Academy Business Park

    Gower Street

    Glasgow G51 1PR

    [email protected]

    South West

    Schneider Electric Ltd

    190 Aztec West

    Park Avenue

    Almondsbury

    Bristol BS32 4TP

    [email protected]

    North West

    Schneider Electric Ltd

    8 Brindley Road

    City Park Business Village

    Cornbrook

    Manchester M16 9HQ

    [email protected]

    Greater London

    Schneider Electric Ltd

    2nd Floor

    408 Strand

    London WC2R 0NE

    [email protected]

    Industrial systems and solutions product showroom

    Schneider Electric Ltd, University of Warwick Science Park, Sir William Lyons Road, Coventry CV4 7EZ

    Building systems and solutions product showroom

    Schneider Electric Ltd, Fordhouse Road, Wolverhampton WV10 9ED

    Energy and Infrastructure systems and solutions product showroom

    Schneider Electric Ltd, 123 Jack Lane, Hunslet, Leeds LS10 1BS

    Regional product showrooms

    Local customer support centres

    Fax 0870 608 8 606

    0870 608 8 608

    Nationwide support on one number -

    call the Customer Information Centre on