REPORT - Appendix 4 - Busbar Configurations
-
Upload
mbsrajambsraja -
Category
Documents
-
view
219 -
download
2
Transcript of REPORT - Appendix 4 - Busbar Configurations
-
8/2/2019 REPORT - Appendix 4 - Busbar Configurations
1/13
Security Policy Review:Credible Event Management
Appendix 4 Busbar Configurations
December 2009
-
8/2/2019 REPORT - Appendix 4 - Busbar Configurations
2/13
Security Policy Review: Credible Event Management Page 2 of 13Appendix 4 Busbar Configurations
NOTICE
COPYRIGHT 2009 TRANSPOWER New Zealand LIMITED
ALL RIGHTS RESERVEDThe information contained in the report is protected by copyright vested in Transpower New ZealandLimited (Transpower). The report is supplied in confidence to you solely for your information. No part ofthe report may be reproduced or transmitted in any form by any means including, without limitation,electronic, photocopying, recording, or otherwise, without the prior written permission of Transpower. Noinformation embodied in the report which is not already in the public domain shall be communicated in anymanner whatsoever to any third party without the prior written consent of Transpower.
Any breach of the above obligations may be restrained by legal proceedings seeking remedies includinginjunctions, damages and costs.
LIMITATION OF LIABILITY/DISCLAIMER OF WARRANTYTranspower make no representation or warranties with respect to the accuracy or completeness of theinformation contained in the report. Unless it is not lawfully permitted to do so, Transpower specificallydisclaims any implied warranties of merchantability or fitness for any particular purpose and shall in noevent be liable for, any loss of profit or any other commercial damage, including but not limited to special,incidental, consequential or other damages.
Version Date Change
1 October 2009 Draft
2 December 2009 Final
-
8/2/2019 REPORT - Appendix 4 - Busbar Configurations
3/13
Security Policy Review: Credible Event Management Page 3 of 13Appendix 4 Busbar Configurations
TABLE OF CONTENTSAPPENDIX 4BUSBAR CONFIGURATIONS ............................................................................................................... 4
Summary of Busbar Configurations........................................................................................... 4220kV Busbar Configurations and Consequences.................................................................... 8110kV Busbar Configurations and Consequences.................................................................. 1066kV Busbar Configurations and Consequences.................................................................... 12
-
8/2/2019 REPORT - Appendix 4 - Busbar Configurations
4/13
Security Policy Review: Credible Event Management Page 4 of 13Appendix 4 Busbar Configurations
Appendix 4 Busbar Configurations
Summary of Busbar Configurations
Six different types of busbar configuration have been identified, each has differentlevel of asset redundancy accommodated and operational flexibility. As busbarterminology adopted by international transmission owners can vary, the terminologyused within this report is introduced in this appendix. The following busbarconfigurations are illustrated and described below.
Single Busbar or 2x Single Busbar(s)
Sectionalised Busbar
Meshed System
Breaker and a Half
Double Busbar
Double Breaker Double Busbar
Summary of Busbar Configurations
Configuration: Single Busbar
A single bus section to which all incomers and feeders are connected. Singlebusbars include those that have section disconnectors that are closed duringnormal operating conditions. Since there are no bus section circuit breakers all thecircuits connected the bus will be lost following the loss of the bus section.
Configuration: 2 x Single Busbar
Two single busbars or bus sections at a substation, incomers and feeders aredirectly connected to one bus section, without the flexibility of connecting directly tothe other. This arrangement includes two bus sections that are separated via anopen disconnector. Since there are no bus section circuit breakers all circuits
connected to a bus section will be lost following the loss of that bus section.
-
8/2/2019 REPORT - Appendix 4 - Busbar Configurations
5/13
Security Policy Review: Credible Event Management Page 5 of 13Appendix 4 Busbar Configurations
Summary of Busbar Configurations
Configuration: Sectionalised Busbar
The busbar may be split into more than one section by the operation of bus sectionbreakers. Where there is more than one bus section, the loss of a bus section maylead to the isolation of adjacent bus sections. Most busbars with this configurationhave bus zone protection that will trip the section breakers post-event and isolatethe affected bus section. All circuits connected to the affected bus section will belost following the loss of the bus section.
Configuration: Meshed System (4 sections)
The busbar may be split into more than one section by the operation of bus sectionbreakers. Where there is more than one bus section, the loss of a single bussectionwill not lead to the isolation of adjacent bus sections. Most busbars withthis configuration have bus zone protection that will trip the section breakers post-event and isolate the affected bus section. All circuits connected to the affected bussection will be lost following the loss of the bus section.
-
8/2/2019 REPORT - Appendix 4 - Busbar Configurations
6/13
Security Policy Review: Credible Event Management Page 6 of 13Appendix 4 Busbar Configurations
Summary of Busbar Configurations
Configuration: Double Busbar
The substation comprises of more than one busbar or bus section, incomers andfeeders may be connected to one of two bus section via the operation ofdisconnectors. For each feeder there is on average 1 circuit breaker. All circuitsconnected to the affected bus section will be lost following the loss of the bussection.
Configuration: Breaker and a Half
The substation comprises of more than one busbar or bus section, incomers andfeeders may be connected to one of two bus section via the operation of circuit
breakers. For each feeder there are on average 1.5 associated circuit breakers.Busbars with this configuration have bus zone protection that will trip the sectionbreakers post-event and isolate the affected bus section. All circuits connected tothe affected bus section will be transferred to the remaining bus section.
-
8/2/2019 REPORT - Appendix 4 - Busbar Configurations
7/13
Security Policy Review: Credible Event Management Page 7 of 13Appendix 4 Busbar Configurations
Summary of Busbar Configurations
Configuration: Double Breaker Double Busbar
The substation comprises of more than one busbar or bus section, incomers andfeeders may be connected to one of two bus sections via the operation of circuitbreakers. For each feeder there are on average 2 associated circuit breakers.Busbars with this configuration have bus zone protection that will trip the sectionbreakers post-event and isolate the affected bus section. All circuits connected tothe affected bus section will be transferred to the remaining bus section.
-
8/2/2019 REPORT - Appendix 4 - Busbar Configurations
8/13
Security Policy Review: Credible Event Management Page 8 of 13Appendix 4 Busbar Configurations
220kV Busbar Configurations and Consequences
Number of Substation Sites
220 kV BusbarConfiguration
IndirectLoss of
Load(costed)
Loss
ofLoad Loss ofGeneration NoIssues
Loss of
Load +Generation Total
Single busbar 2 6 7 1 0 16.00
2 x single busbar 0 0 1 6 0 7.00
Sectionalised singlebusbar 11 0 6 6 2 25.00
Double busbar 8 0 3 7 0 18.00
Breaker and a half 1 0 1 4 0 6.00
Meshed system 1 0 0 0 0 1.00Percentage of Substation Sites
220 kV BusbarConfiguration
Indirect
Loss ofLoad(costed)
LossofLoad
Loss ofGeneration
NoIssues
Loss ofLoad +Generation Total
Single busbar 2.74 8.22 9.59 1.37 0.00 21.92
2 x single busbar 0.00 0.00 1.37 8.22 0.00 9.59
Sectionalised singlebusbar 15.07 0.00 8.22 8.22 2.74 34.25
Double busbar 10.96 0.00 4.11 9.59 0.00 24.66
Breaker and a half 1.37 0.00 1.37 5.48 0.00 8.22
Meshed system 1.37 0.00 0.00 0.00 0.00 1.37
Event: Loss of a 220kV Busbar Section
Consequence: Direct Loss of Supply & Indirect Loss of Supply(Costed)
0
5
10
15
20
25
30
Single
busbar
2xsingle
busbar
Sectionalised
singlebusbar
Double
busbar
Breakerand
ahalf
Meshed
system
Busbar Configuration
NumberofSubstations
Indirect Loss of Load (costed) Loss of Load Loss of Generation No Issues Loss of Load + Generation
-
8/2/2019 REPORT - Appendix 4 - Busbar Configurations
9/13
Security Policy Review: Credible Event Management Page 9 of 13Appendix 4 Busbar Configurations
Event: Loss of a 220kV Busbar Section
Consequence: Indirect Loss of Supply(Costed), Direct Loss of Supply & No Issues
0.00
10.00
20.00
30.00
40.00
Single
busbar
2xsingle
busbar
Sectionalised
singlebusbar
Double
busbar
Breakerand
ahalf
Meshed
system
Busbar Configuration
PercentageofSubstations(%)
Indirect Loss of Load (costed) Loss of Load Loss of Generation No Issues Loss of Load + Generation
Event: Loss of a 220kV Busbar Section
32%
8%
25%
32%
3%
Indirect Loss of Load (costed)Loss of Load
Loss of Generation
No Issues
Loss of Load + Generation
-
8/2/2019 REPORT - Appendix 4 - Busbar Configurations
10/13
Security Policy Review: Credible Event Management Page 10 of 13Appendix 4 Busbar Configurations
110kV Busbar Configurations and Consequences
Number of Substation Sites
110 kV BusbarConfiguration
Indirect
Loss ofLoad(costed)
LossofLoad
Loss ofGeneration
NoIssues
Loss ofLoad +Generation Total
Single busbar 6 38 3 1 0 48
2 x single busbar 1 1 0 12 0 14
Sectionalised singlebusbar 3 5 2 8 1 19
Double busbar 3 0 0 2 1 6
Breaker and a half 0 0 0 0 0 0
Meshed system 0 0 0 0 0 0Percentage of Substation Sites
110 kV BusbarConfiguration
IndirectLoss ofLoad
(costed)
Lossof
LoadLoss of
GenerationNo
Issues
Loss ofLoad +
Generation Total
Single busbar 6.90 43.68 3.45 1.15 0.00 55.17
2 x single busbar 1.15 1.15 0.00 13.79 0.00 16.09
Sectionalised singlebusbar 3.45 5.75 2.30 9.20 1.15 21.84
Double busbar 3.45 0.00 0.00 2.30 1.15 6.90
Breaker and a half 0.00 0.00 0.00 0.00 0.00 0.00
Meshed system 0.00 0.00 0.00 0.00 0.00 0.00
Event: Loss of a 110kV Busbar Section
Consequence: Indirect Loss of Supply(Costed), Direct Loss of Supply & No Issues
0
10
20
30
40
50
60
Single
busbar
2xsingle
busbar
Sectionalised
singlebusbar
Double
busbar
Breakerand
ahalf
Meshed
system
Busbar Configuration
Num
berofSubstations
Indirect Loss of Load (costed) Loss of Load Loss of Generation No Issues Loss of Load + Generation
-
8/2/2019 REPORT - Appendix 4 - Busbar Configurations
11/13
Security Policy Review: Credible Event Management Page 11 of 13Appendix 4 Busbar Configurations
Event: Loss of a110kV Busbar Section
Consequence: Indirect Loss of Supply(Costed), Direct Loss of Supply & No Issues
0.00
10.00
20.00
30.00
40.00
50.00
60.00
Single
busbar
2xsingle
busbar
Sectionalised
singlebusbar
Double
busbar
Breakerand
ahalf
Meshed
system
Busbar Configuration
PercentageofSubstat
ions(%)
Indirect Loss of Load (costed) Loss of Load Loss of Generation No Issues Loss of Load + Generation
Event: Loss of a 110kV Busbar Section
15%
51%
6%
26%
2%
Indirect Loss of Load (costed)
Loss of Load
Loss of Generation
No Issues
Loss of Load + Generation
-
8/2/2019 REPORT - Appendix 4 - Busbar Configurations
12/13
Security Policy Review: Credible Event Management Page 12 of 13Appendix 4 Busbar Configurations
66kV Busbar Configurations and Consequences
Number of Substation Sites
66 kV BusbarConfiguration
IndirectLoss of
Load(costed)
Loss
ofLoad Loss ofGeneration NoIssues
Loss of
Load +Generation Total
Single busbar 0 15 1 0 4 20
2 x single busbar 0.5 0 0 1.5 0 2
Sectionalised singlebusbar 0 2 0 0 0 2
Double busbar 0.25 0.25 0 0.5 0 1
Breaker and a half 0 0 0 0 0 0
Meshed system 0 0 0 0 0 0Percentage of Substation Sites
66 kV BusbarConfiguration
Indirect
Loss ofLoad(costed)
LossofLoad
Loss ofGeneration
NoIssues
Loss ofLoad +Generation Total
Single busbar 0 60 4 0 16 80
2 x single busbar 2 0 0 6 0 8
Sectionalised singlebusbar 0 8 0 0 0 8
Double busbar 1 1 0 2 0 4
Breaker and a half 0 0 0 0 0 0
Meshed system 0 0 0 0 0 0
Event: Loss of a 66kV Busbar Section
Consequence: Indirect Loss of Supply(Costed), Direct Loss of Supply & No Issues
0
5
10
15
20
25
Single
busbar
2xsingle
busbar
Sectionalised
singlebusbar
Double
busbar
Breakerand
ahalf
Meshed
system
Busbar Configuration
N
umberofSubstations
Indirect Loss of Load (costed) Loss of Load Loss of Generation No Issues Loss of Load + Generation
-
8/2/2019 REPORT - Appendix 4 - Busbar Configurations
13/13
Security Policy Review: Credible Event Management Page 13 of 13Appendix 4 Busbar Configurations
Event: Loss of a 66kV Busbar Section
Consequence: Indirect Loss of Supply(Costed), Direct Loss of Supply & No Issues
0
10
20
30
40
50
6070
80
90
Single
busbar
2xsingle
busbar
Sectionalised
singlebusbar
Double
busbar
Breakerand
ahalf
Meshed
system
Busbar Configuration
PercentageofSubstations(%)
Indirect Loss of Supply (costed) Loss of Load Loss of Generation No Issues Loss of Load + Generation
Event: Loss of a 66kV Busbar Section
3%
69%
4%
8%
16%
Indirect Loss of Load (costed)
Loss of Load
Loss of Generation
No Issues
Loss of Load + Generation