Renovation of Substation – 2 including Replacement of Oil ...
Transcript of Renovation of Substation – 2 including Replacement of Oil ...
Tender No: 1800000055
Page 1 of 41
MAZAGON DOCK SHIPBUILDERS LIMITED (Formerly known as Mazagon Dock Ltd.)
CIN : U35100MH1934GOI002079 (A Government of India Undertaking)
Shipbuilders to the Nation Dockyard Road, Mazagon,
Mumbai 400 010. INDIA
Renovation of Substation – 2 including Replacement of Oil Type
transformers with Dry type Transformers at South Yard, MDL,
Mumbai.
VOLUME-IV
TECHNICAL SPECIFICATION &
PREFERRED MAKE
Tender No: 1800000055
Page 2 of 41
TECHNICAL SPECIFICATIONS OF
SUBSTATION & ASSOCIATED
ELECTRICAL WORKS
Tender No: 1800000055
Page 3 of 41
VOL IV - TABLE OF CONTENTS
Sr. No Description Page No
TECHNICAL SPECIFICATIONS FOR DRY TYPE TRANSFORMER 5
1 Scope of Work 5
2 Codes & Standards 8
3 Design Basis 9
4 SERVICES CONDITION 10
5 Other Design Parameters 10
6 Construction & Design 11
7 Fittings & Accessories for each of Transformer 15
8 Submittals 17
9 Submission of drawing to MDL/consultant approval prior to manufacturing 17
10 Inspection & testing during manufacturing of both transformers 17
11 Pre-dispatch inspection & testing of both transformers 18
12 Packaging 19
13 Annexure to be submitted along with technical bid 19
14 Deviations 19
15 Guarantee 19
16 Documents to be supplied at the time of delivery 19
17 QAP shall include following 19
18 Guaranteed technical particulars for distribution transformers 22
TECHNICAL SPECIFICATIONS FOR POINT WIRING 27
1 Scope of Work 27
2 Code & Standards 27
3 System of Wiring 27
4 General 27
5 Material 27
6 Switches 28
7 Socket 28
8 Inspection and testing 29
9 Method of measurement 29
10 Transport, delivery and storage 29
11 Guarantee and warranty 29
TECHNICAL SPECIFICATIONS FOR SUPPLY OF LIGHT FIXTURE 30
1 Scope of Work 30
2 Code & Standards 30
3 Technical requirements 30
4 LED Lamps 30
5 Luminaries 30
6 LED down lighter light (ip43) tech specs 31
7 Drawings & Information 31
8 Method of measurement 31
9 Guarantee and Warranty 31
10 Propeller Exhaust Fan 31
TECHNICAL SPECIFICATIONS FOR SUPPLY OF EARTHING SYSTEM 32
1 Scope of Work 32
2 Code & Standards 32
3 Installation of system 32
4 Plate Electrode Earthing 33
Tender No: 1800000055
Page 4 of 41
TECHNICAL SPECIFICATIONS FOR LT XLPE CABLES 35
1 Scope of Work 35
2 Code & Standards 36
3 Technical Requirements 36
4 Drawings & information 37
5 Inspection and testing 37
6 Routine test 38
7 Type Test 38
8 Method of measurement 38
9 Data sheet for cables 38
TECHNICAL SPECIFICATIONS FOR HT XLPE CABLES 39
1 Scope of Work 39
2 General Description 39
3 Material and Construction 39
4 Core identifications 39
5 Packing 39
6 Installation 40
MAKE OF MATERIAL 40
Tender No: 1800000055
Page 5 of 41
TECHNICAL SPECIFICATIONS FOR DRY TYPE TRANSFORMER
1.0 Scope of Work
1.1 Survey of site, design, manufacture, pre-dispatch testing conforming to relevant IS standards,
packing, forwarding, transportation & delivery at MDL, transportation to erection site &
properly unloading, on-site installation & testing, commissioning and setting to work of 2 nos.
2000 kVA rating, 11kV / 433V, 3 ph, copper winding, Cast resin, Air cooled , dry type
distribution Transformers conforming to IS 2026 & IS 11171 suitable for 11 kV, 50Hz distribution
system and indoor use.
1.2 All necessary works including the associated civil work (such as but not limited to foundation,
support railing for wheels, making of earth pits & earthing grid) & electrical works (such as but
not limited to disconnecting & removing existing HT cable, LT bus duct at both ends, supply,
laying and terminating new HT XLPE insulated, 300sqmm aluminum, armored power cable on
primary side (if required) and connection with existing bus duct including supply of additional
bus duct sections(if required) on LV side using palm connectors along with flexible links of thin
plates of copper (3 phase & neutral), earthing connection etc. for installation & commissioning
of both transformers shall be in supplier’s scope.
1.3 Offered transformers shall conform in all respects to high standards of engineering, design and
workmanship shall conform to relevant IS standards with latest amendments thereof and shall be capable of performing in continuous & satisfactory operation in the actual service
conditions at MDL’s site in a manner acceptable to MDL. Offered Transformer shall have
sufficiently long service life as per statutory requirements. The transformer shall be complete
with all components / parts necessary for their effective and trouble-free operation. Such
components / parts shall be deemed to be within the scope of bidder’s supply irrespective of
whether those are specifically brought out in this specification or not.
1.4 The transformers and accessories shall be designed to facilitate operation, inspection,
maintenance and repairs. The design shall incorporate every precaution and provision for the
safety of equipment as well as staff engaged in operation and maintenance of equipment.
1.5 Prior to bidding, firm’s representative shall visit the site of installation, take site measurements to
ensure that the offered transformer can be designed to accommodate & installed at the site,
considering the available space restrictions & compliance to statutory requirement as per
relevant & latest Indian Electricity Rules & CEA Regulations.
1.6 The requisite certification from Government Electrical Inspector with all arrangements, cost &
expenses shall be in the supplier’s scope.
1.7 Connection of both transformers to the existing LT bus ducts is in the suppliers’ scope. Supply &
installation of additional bus duct sections of same make & model of existing one &
connection to both transformers, to meet the statutory space requirement around each of the
offered HT transformers is also in the suppliers’ scope. The details of existing LT bus duct are as
follows:
Make Schneider Electric, Type: Non phase segregated sandwich type LT bus duct, System:
3P4W with 50% internal earth, Rated continuous current: 2500Amp, Rated 1 sec S.C. withstand
50kA, IP65, Bus bars: High conductivity electrolytic grade copper, Enclosure material:
Galvanized Steel, Provision for earthing on both side, paint shade: RAL 7032. Length: As per site
requirement to meet the statutory space requirement around each of the offered HT
transformers, taking into account the dimensions of the offered transformer & site restrictions.
1.8 Following Tests shall be carried out on both transformers prior to the energizing of Transformers
at installation site:
1. Insulation Resistance Value by HV Insulation Tester
2. Back charging of transformer from secondary side
Tender No: 1800000055
Page 6 of 41
1.9 OEM’s engineer shall supervise transformer energizing for 1 day for each transformer.
1.10 Disconnecting of existing 2 nos. transformers, associated old power cables (at both ends), LT
bus ducts also shall be in the supplier’s scope. Disconnected transformers shall be lifted &
shifted away from the site by Electrical Contractor as per instructions by MDL Authorities. Crane
facility for unloading, lifting & shifting of existing as well as new transformers shall be in
Electrical Contractor’s scope.
1.11 METHODOLOGY OF DISMANTLING EXISTING TRANSFORMER AND ERECTION OF NEW
TRANSFORMERS SHALL BE CARRIED OUT IN FOLLOWING STEPS:
i. Procurement of Dry Type Transformer-1 to MDL Site.
ii. Transfer the Load of Existing Transformer-1 to Transformer-2.
iii. Dismantling of existing Transformer before 7 days of delivery of New Transformer-1.
iv. Completion of Transformer room civil works as per approved drawing.
v. Installation of New Transformer-1.
vi. Transfer the Load of Existing Transformer-2 to Newly installed Transformer-1.
vii. Procurement of Transformer-2 to MDL site.
viii. Dismantling of existing Transformer before 7 days of delivery of New Transformer-2.
ix. Completion of Transformer room civil works as per approved drawing.
x. Installation of New Transformer-2.
xi. Transfer 50% Load on newly installed Transformer-2.
Delivery of both Transformers shall be planned according to above mentioned stepwise
procedure. Since there is Space constraint in MDL premises, Storage of Transformer is not
possible, Hence Installation of New Transformer shall be commenced on the same day of
receipt of transformer at MDL Site.
1.11.1 Dismantling of existing transformers:
The following are recommended steps for decommissioning a unit and taking out of service:
i. Shut down the low-voltage.
ii. Shut down the high-voltage.
iii. Secure the transformer to prevent incidental activation by unauthorized persons.
iv. Allow the transformer to cool down
v. Disconnect the connections on the low-voltage side from the transformer
vi. Disconnect the connections on the high-voltage side from the transformer
vii. Disconnect the connections on any provided additional components from the transformer viii. Disconnect the ground terminal from the transformer
Dismantling shall be planned according to Delivery of New Transformer. At first, Dismantling of
Transformer-1 shall be taken place, & the Load shall be transferred to Transfomer-2. Post
dismantling, the Transformer shall be shifted to desired location as per Client’s instructions. For
erection of new Transformer, Respective room shall be thoroughly cleaned, and all the
necessary civil works such as construction of Transformer foundation, Trench etc., shall be
completed as per the approved drawings & instructions of Client / Consultant representative.
1.11.2 At first, Transformer-1 shall be delivered to MDL site. Delivery of New Transformer-2 and
Dismantling of Existing Transformer-2 shall be planned in accordance with successful
installation & commissioning of Transformer-1 and shifting of Entire Load on newly Installed
Transformer. Dismantling of existing Oil type Transformer-2 shall be carried out before 7days of
delivery of Transformer-2. Following points shall be taken care at the time of Transformer
receipt at Site.
1) When a transformer arrives at site a careful external inspection must be made of the unit,
its cooling system and all sealed components, referring to the general arrangement
drawing and the shipping list.
i. Inspect all packing cases and loose components for damage or missing items.
Tender No: 1800000055
Page 7 of 41
ii. A record of damage must be prepared in conjunction with other participants and
supplier representative. Minor damage which may appear unimportant should also be
recorded.
iii. Confirm that case numbers match with the packing list. Check their contents tally with
the packing list if the packing case is damaged.
iv. Winding Temperature indicator shall be checked for any damage
v. Fill in the check list for external as well as internal inspections.
2) Unloading of transformers:
a) The following should be avoided during the unloading process
i. The transformer imbalance (Maximum 10 degree)
ii. Abrupt movements
iii. Impact against the ground
The transformer should be unloaded from trailer by using wooden sleepers and rails
for dragging the transformer to its plinth.
b) Considerations before unloading
i. Availability of access road between unloading point and plinth.
ii. Ensure overhead crane capacity for weight of main unit.
iii. Readiness of foundation
iv. Keep under base of main unit at least 300 – 400 mm above ground level by providing wooden slippers to facilitate jacking.
v. Remove lashing before unloading.
c) Unloading from Trailer
i. Unload main unit only on wooden slippers
ii. Jack the transformer at jacking pad only.
iii. Ensure simultaneous operation of all 4 jacks.
iv. Use only haulage lugs for hauling.
v. Ensure capacity of winches and wire ropes to be used for haulage.
vi. Do not use chain pulley block in place of winches.
3) Storage of transformers:
The transformer should be placed in a clean, dry room where a uniform temperature can
be maintained as best as possible because fluctuating temperatures can cause
condensation issues. The floor on which the transformer is being stored should be resistant to the upward migration of water vapor. Precautions should be taken to prevent storage in
an area that water could be present, such as roof leaks, windows, etc. Condensation or
absorption of moisture can be greatly reduced by the installation of space heaters
(optional). If the transformer is not furnished with internal space heaters, then external,
portable heaters can be used. A basic rule to mitigate condensation in the unit is to keep
the transformer enclosure 5-10 degrees above ambient temperature. Lamps or heaters
should never come in direct contact with the transformer coil insulation. If a transformer
has to be left outdoors, protective measures should be taken to prevent moisture and
foreign debris from entering the transformer. Also, if the transformer is to be stored for a
long period of time, then the transformer should be equipped with a suitable drying agent
such as silica gel. The energization of the space heaters (optional) is recommended to
prevent moisture collection inside the transformer due to condensation, etc. The unit
should be checked periodically for indications of condensation (i.e. Windings, coil support
blocks, core, core clamping system, bus/cable, etc.). Before the transformer is placed into
operation after being stored, the insulation should be checked for condensation by
performing an insulation resistance test (see “Testing”). If condensation is found a drying-
out procedure may be necessary. Space heaters are not adequate for drying.
1.11.3 Installation of new transformer
Installation of 2000KVA Dry type Transformer shall carried out in accordance with IS 10028 Part-
II, Indian Electricity rules and related statutory norms.
Tender No: 1800000055
Page 8 of 41
Once the transformer has been located on its permanent site, a thorough final inspection
should be made before any assembly is accomplished and the unit is energized. Before
energizing the unit, it's very important that to alert all personnel installing the transformer that
lethal voltages will be present inside the transformer enclosure as well as at all connection
points. The installation of conductors should be performed only by personnel qualified and
experienced in high-voltage equipment. Personnel should be instructed that should any
service work be required to the unit, the lines that power the transformer must be opened and
appropriate safety locks and tags applied.
Following points shall be checked prior to energizing the Transformer:
i. Make sure all connections to cables or bus bars are properly connected and well
positioned.
ii. Make sure that all connections at the tap change panel are firmly tightened and at the
same position in the three phases.
iii. Make sure the grounding mesh is correctly connected to the bolt provided for this
purpose.
iv. In case of transformers fitted with a thermal protective device, check the connections of
the circuit, making sure that the voltage is in accordance and that the alarm and shut-
off contacts are connected to their corresponding loops.
In Addition to above checks, All Pre-commissioning Test shall be carried out by the Contractor as mentioned above in item no-1.8 and shall be in accordance with IS 2026.
1.11.4 Energizing of Transformer
When energizing the transformer, slowly increase the load while monitoring current, voltage,
load levels, etc. If it is not possible to begin at no-load, full load may be applied with
caution. It is not recommended to load the unit above the maximum continuous load on the
nameplate. If there is any doubt about the load, voltage or current levels, or in any area,
contact the manufacturer immediately
All the procedure specified above for the dismantling of Existing Oil type Transformer-1 and
installation of New dry type Transformer-1, shall be repeated for installation of Transformer-2.
2.0 Codes & Standards
The offered transformers shall conform to IS 2026 & IS 11171 as amended up to date and materials, equipment’s & methods used in the manufacturing, testing of distribution
transformers shall conform to the latest amendments of below mentioned standards:
Indian
Standards
TITLE
IS 2026 Specifications for power transformers
IS 11171 Dry Type Power Transformers
IS 12444 Specification for Copper wire rod
IS 1271 Thermal evaluation and classification of electrical insulation
IS 5 Specification for colors for ready mixed paints
IS 104 Ready mixed paint, brushing zinc chromate, priming
IS 2099 Specification for High Voltage Bushing
IS 649 Testing for steel sheets & strips and magnetic circuits
IS 4257 Dimensions for clamping arrangements for bushings
IS 7421 Specification for Low Voltage Bushings
IS 3347 Dimensions for Porcelain Transformer bushings
IS 9335 Specification for Insulating Kraft Paper
IS 1576 Specification for Insulating Press Board
IS 2362 Determination of water content in oil for porcelain bushing of transformer
IS 6160 Rectangular Electrical conductor for electrical machines
IS 5561 Electrical power connector
Tender No: 1800000055
Page 9 of 41
Indian
Standards
TITLE
IS 10028 Selection, Installation & maintenance of transformers
IS 2705 Current Transformers
IS 3639 Fitting & Accessories of Power Transformers
IS 13947 LV switchgear & control gear – Part 1
Supplier shall strictly adhere to Indian Electricity Rules, Indian Electricity Act, CBIP Manual as
well as CEA Regulations 2016.
IEC Standards TITLE
IEC 60071 Co-ordination of Insulation
IEC 60445
Basic & safety principles for man-machine interface, marking and
identification – identification of equipment terminals and conductor
termination
IEC 60529 Degrees of protection provided by enclosures (IP code)
IEC 60551 Determination of Transformer & reactor sound levels
IEC 60606 Application Guide for Power Transformers
IEC 60616 Terminal & Tapping markings for power transformers
British Standards TITLE
BS 2562 Cable Boxes for Transformers & Reactors
In the event of direct conflict between various order documents, the precedence of authority of documents shall be as follows:
a. Guaranteed Technical Particulars (GTP)
b. This Specification
c. Indian Standards / IEC Standards
d. Approved Vendor Drawings
e. Other documents
3.0 Design Basis
The transformers shall be suitable for indoor installation with 3ph, 50 Hz, 11kV system in which
the neutral is effectively earthed and they shall be suitable for service with fluctuations in
supply voltage up to ±12.5%. The transformers shall conform to following specific parameters:
a. Highest System Voltage (HV side) : 12 kV
b. Rated Voltage HV : 11kV c. Highest System Voltage (LV side) : 460 Volts
d. Rated Voltage LV : 433 V
e. No Load Voltage Ratio : 11000/433 Volts
f. Standard kVA rating : 2000 kVA
g. Frequency : 50 Hz ± 3 %
h. Transient Condition : -20% or +10% combined variation of voltage & freq.
i. No. of phases : 3 ph
j. Connection HV : Delta
k. Connection LV : Star (Neutral brought out)
l. Vector Group : Dyn-11
m. Type : Dry Cast resin type
n. Type of cooling : AN as per IS 2026 (Part 2)
o. No Load Current : No Load Current shall not exceed 2% of the Full
Load Current and shall be measured by energizing
the transformer at rated voltage & frequency. p. Audible sound level: Shall not be more than 69db as per NEMA standard
Tender No: 1800000055
Page 10 of 41
4.0 SERVICES CONDITION:
a. Location : Indoor at MDL, Mumbai
b. Climatic Condition : Heavily polluted, salt laden, dusty, conducive to rust,
humid with possibility of condensation
c. Max. Altitude above sea level : 1000 meters
d. Max. Ambient air temperature : Highest 45 deg C,
e. Avg. Ambient Temp. : Average 40 deg C
f. Relative Humidity : 95% Max.
g. Rainfall : 2500 mm concentrated in four months
5.0 Other Design Parameters:
5.1 Insulation Levels: (as per IS:206)
5.2 Short Circuit withstand level :
a. 3 secs for 3 ph dead short circuit at secondary
terminal with rated voltage maintained on the
other side b. 3 secs for single ph short circuit at secondary
terminal with rated voltage maintained on the
other side
5.3 Overload Capability : Conforming to IS 6600
5.4 Harmonic Suppression : To be designed for suppression of 3rd, 5th & 7th
harmonic voltages and high freq. disturbances
5.5 Radio Influence Voltage : Maximum 250 microvolt
5.6 Partial Discharges : To be free from partial discharge upto 120% of rated
voltage as the voltage is reduced from150% of rated
voltage i.e. there shall be no significant rise above
background level
5.7 Parallel Operation : Offered transformers shall be designed to operate in
parallel, if need arises
5.8 % Impedance : At 75 deg C, it shall be 5%
5.9 Losses : Maximum Total Losses at rated voltage & freq. at 75
deg. C shall be as per IS 2026 & IS 11171
5.10 Temperature Rise : The permissible temperature-rise shall not exceed the
limits specified in the IS standard
5.11 Ref. Ambient Temp. for Temperature Rise : 40 deg C
5.12 Lightning Impulse withstand Voltage : 75kVpeak for nominal system voltage of 11kV
5.13 Power Freq. withstand Voltage : 28kVrms for nominal system voltage of 11kV & 3 kVrms
for nominal system voltage of 433V
5.14 Minimum Clearances for bushing : Min. clearances of bushing terminals for Transformer
with terminal boxes shall be as per IS 2026
Voltage (kV) Impulse Voltage
(kV peak)
Power Freq.
Voltage (kV)
0.433 -- 3
11 75 28
Tender No: 1800000055
Page 11 of 41
5.15 System Fault Level : HV side: 350 MVA & LV side: 35 MVA
5.16 System Earthing : Solidly earthed on HV & LV side
5.17 Tappings : Off circuit taps on HV winding, +5% to -10% in steps of
2.5% for variation of HV
5.18 Tapping Method : Tap changing shall be carried out by means of an
externally operated off circuit rotary tap switch, when
the transformer is in de-energized condition. Switch
position no. 1 shall correspond to the maximum plus
tapping. Each tap change shall result in variation of
2.5% in voltage. Provision shall be made for locking the
tapping switch handle in position. Suitable anodized
plate shall be fixed for tap changing switch to know the
position number of tap.
5.19 Rotary Tap switch operating voltage : 11 kV
5.20 Rotary Tap switch Current Rating : 150 Amp
6.0 Construction & Design:
6.1 Type Double Copper wound, three phase, Dry Cast resin
type with off circuit tap changer
Major Parts
6.2 Enclosure
6.2.1 Type Rectangular shape & non sealed type.
6.2.2 Material of Construction Prime quality mild steel plate without pitting and low carbon content.
6.3 CORE
6.3.1 Material High grade , non-ageing, low loss, high permeability,
grain oriented, cold rolled silicon steel lamination
coated on both sides with hot oil proof insulation,
bolted together to the frames firmly to prevent
vibration or noise. All core clamping bolts shall be effectively insulated.
6.3.2 Core Material Grade Premium Grade M4 or better
6.3.3 Core Design Features a) Magnetic circuit designed to avoid short circuit
paths within core or to the earthed clamping structures.
b) Magnetic circuit shall not produce flux components
at right angles to the plane of lamination to avoid local heating
c) Least possible air gap and rigid clamping to minimize core loss and noise generation
d) Adequately fitted to withstand bolted faults on
secondary terminals without mechanical damage
and damage/ displacement during transportation and positioning.
e) Percentage harmonic potential with the maximum
Nominal System
Voltage (kV) phase to phase
phase to
earth
11 130 mm 80 mm
0.433 25 mm 20 mm
Tender No: 1800000055
Page 12 of 41
flux density under any condition limited to avoid capacitor overloading in the system
f) All steel sections used for supporting the core shall
be thoroughly sand blasted after cutting, drilling, welding
g) Provision of lifting lugs for core coil assembly
6.4 WINDING
6.4.1 Material Electrolytic Grade Copper. Double paper covered
copper conductor shall be used for HV and LV
Winding
6.4.2 Maximum Current Density allowed (HV / LV)
Not more than 3.0 Amp per sq mm for copper conductor
6.4.3 Winding Insulating material Class A, non-catalytic & inert
6.4.4 Winding Insulation Uniform
6.4.5 Design features a) Stacks of winding to receive adequate shrinkage
treatment
b) Connections braced to withstand shock during transport, switching, short circuit, or other transients.
c) Minimum out of balance force in the transformer winding at all voltage ratios.
d) Conductor width on edge exceeding six times its thickness
e) Transposed at sufficient intervals.
f) Coil assembly shall be suitably supported between adjacent sections by insulating spacers + barriers
g) Winding leads rigidly supported
h) L.V. Neutral formation shall be at top
6.5 Bushings and Terminations
6.5.1 Type of HV side bushings Indoor , Epoxy Resin cast / Porcelain, 12kV voltage
class conforming to relevant IS
6.5.2 Type of LV side bushings Indoor, Epoxy resin cast / Porcelain, 1.1kV voltage
class conforming to relevant IS
6.5.3 Support insulators inside HV cable
box
Epoxy resin cast, 12kV voltage class
6.5.4 Termination on HV side bushings By bimetallic terminal connectors suitable for XLPE
Cable connection inside cable termination box.
6.5.5 Termination of LV side bushings By bimetallic terminal connectors suitable for
connecting with LT bus duct. Supply & installation of
rated Palm connectors (made of Brass & conforming
to type 1 of IS: 319-1974 or IS: 3488-1966 and tinned
finishing) along with rated flexible links of thin plates of
tinned copper (3 phase & neutral) suitable for LT bus duct connection.
6.5.6 Minimum creepage distance of all
bushings and support insulators
31 mm/kV
6.5.7 Protected creepage distance At least 50 % of total creepage distance
6.5.8 Continuous Current rating Minimum 20 % higher than the current corresponding
to the minimum tap of the transformer
Tender No: 1800000055
Page 13 of 41
6.5.9 Rated thermal short time current
a HV Bushing: 25 times rated current for 2 secs.
b LV Line & Neutral Bushing: 25 times rated current for 2 secs.
6.5.10 Atmospheric protection for clamp and fitting of iron and steel
Hot dip galvanizing as per IS 2633
6.6 HV & LV Termination boxes Supply & Installation required
6.6.1 Material & Construction a) Mild Steel min 2.5 mm thick
b) The parts shall be removable for cable / bus duct termination purposes.
c) Suitable nitrile/neoprene gasket of non-deteriorating
rubber braided cork sheet or similar type of material shall be provided at all joints to ensure tightness.
d) Each detachable part shall be earthed by routing a braided copper wire.
e) The end covers on the termination boxes shall be
provided with suitable fixed handles. The overall
dimensions shall not exceed the transformer dimensions specified by the firm.
f) The termination boxes shall be provided for Cable / Bus-duct termination.
g) Phase to phase clearance inside HV & LV box shall be min. 130mm & 25 mm respectively.
h) Phase to earth clearance inside HV & LV box shall be min. 80mm & 20 mm respectively.
6.6.2 HV Cable entry At bottom through detachable gland plate with cable clamps of non-magnetic material
6.6.3 XLPE Cable for HV supply
(Approx. Total Length: 62 meters, considering for both transformers)
Supply, digging, laying of XLPE Cables & end
terminations at both ends (on HT Panel & Transformer
HV side) also in scope of work. Firm shall use Raychem
make termination kit. Require ISI marked XLPE
insulated, 3Cx300sqmm stranded compact circular,
aluminum conductor, GI strip armoured, power cable
of 12kV Voltage class conforming to IS 7098 Pt. 2, Total
Length: As per site requirement for each of the transformer.
6.6.4 Connection of Bus Duct on LV side of both transformers
Connection of both transformers to the existing LT bus
ducts. Supply, installation & testing of additional bus
duct sections of same make & model of existing one, complete with all accessories & connect to both
transformers & existing bus ducts to meet the statutory
space requirement around each of the offered HT
transformers is in the suppliers’ scope.
6.6.5 Bus duct specifications a) Bus Duct sections of Make Schneider Electric, Type:
Non phase segregated sandwiched type LT bus
duct, System: 3P4W with 50% internal earth, Rated continuous current: 2500Amp, Rated 1 sec S.C.
withstand 50kA, IP65, Busbars: High conductivity
electrolytic grade copper, Enclosure material:
Galvanized Steel, Provision for earthing on both side, paint shade: RAL 7032.
b) Length: As per site requirement to meet the statutory
space requirement around each of the offered HT
transformers, taking into account the dimensions of
Tender No: 1800000055
Page 14 of 41
the offered transformer & site restrictions.
6.6.6 Bus Duct Entry Box for LV side a) Supply & Installation required for Bus Duct Entry Box made of Mild Steel min 2.5 mm thick.
b) Bus Duct entry shall be from Top side plate of Bus Duct Entry box.
c) It shall be installed on LV Terminal Box & shall be
suitable for detachment from LV Terminal Box.
d) Suitable gasket of non-deteriorating rubber braided
cork sheet or similar type of material shall be provided at all joints to ensure tightness.
6.6.7 Detachable Gland Plate material
for HV terminal box & LV bus duct
entry box
MS
6.6.8 Gland plate thickness for HV & LV
Bus duct terminal box
3mm
6.6.9 Cable gland for HV cable Nickel plated brass double compression weatherproof
cable gland and suitable for cable size as per 6.9.3
6.6.10 Cable lug for HV cable Long barrel heavy duty Copper Lug with Knurling on
inside surface and suitable for for cable size as per 6.9.3
6.6.11 Essential parts a. Doors shall be provided to access the Core coil assembly and removable cover for Termination box.
b. Tinned Copper Busbars of adequate size for Purchaser’s cable / busduct termination with busbar supports
c. Earthing boss for the termination box
c) Earthing link for the gasketted joints at two point for each joint
Earthing provision for cable Armour/ Screen
d) Danger / caution plate metallic fixed by rivet
6.7 Hardware
6.7.1 External Stainless Steel
6.7.2 Internal Cadmium plated except special hardware for frame
parts and core assembly as per manufacturer’s design
6.8 Cable routing on Transformer Control cables for accessories on transformer tank shall
be routed through perforated GI trays
6.8.1 Control cable specification PVC insulated, extruded PVC inner sheathed,
armoured, extruded PVC outer sheathed 1100 V grade
control cable as per latest edition of IS 1554 part 1
minimum 2.5 sq mm for signals with multi strand copper conductor
6.8.2 Specification of wires to be used
inside marshalling box
PVC insulated multi-strand flexible copper wires of
minimum 2.5 sq mm size, 1100 V grade as per latest edition of relevant IS
6.9 Terminal Blocks to be used by the
vendor
Nylon 66 material, minimum 4 sq mm, screw type for
control wiring and potential circuit
6.10 Cable glands to be used by the
vendor
Nickel plated brass double compression weatherproof
cable gland
6.10.1 Lugs for power cables Long barrel heavy duty Aluminium lug with knurling on inside surface
6.10.2 Lugs for Control Cables Tinned copper pre-insulated Pin, Ring, Fork type as
Tender No: 1800000055
Page 15 of 41
applicable
6.11 Painting of transformer,
marshalling box for CT, cable boxes etc.
6.11.1 Surface preparation By 7 tank pretreatment process or shot blasting method
6.11.2 Finish on inner surface of the
HV/LV terminal box & bus duct entry box
White Polyurethane paint anti condensation type two
coats, minimum dry film thickness 120 microns
6.11.3 Finish on inner & outer surface of
the transformer enclose, HV/LV terminal box & bus duct entry box
Battle ship Grey shade 632 Polyurethane paint two
coats , minimum dry film thickness 120 microns
6.11.4 Frame parts Battle ship grey shade 632 IS 5, 120 micron minimum dry
film thickness.
7.0 Fittings & Accessories for each of Transformer:
7.1 Rating and Diagram Plate Required
7.1.1 Material Anodized aluminum 16SWG
7.1.2 Background SATIN SILVER
7.1.3 Letters, diagram & border Black
7.1.4 Process Etching
7.1.5 Rating and Diagram Plate details Following details shall be provided on rating and
diagram plate as a minimum
a) Type/kind of transformer with winding material
b) Month and year of manufacture
c) Rated frequency in Hz
d) Rated voltages in kV
e) Number of phases
f) Rated power in kVA
g) Type of cooling (AN)
h) Rated currents in A
i) Vector group connection symbol
j) Power frequency withstand voltage in kV
k) Impedance voltage at rated current and frequency
in percentage at principal, minimum and maximum
tap
l) Load loss at rated current
m) No-load loss at rated voltage and frequency
n) Continuous ambient temperature at which ratings
apply in deg C
o) Winding temperature rise at rated load in deg C
p) Winding connection diagram with taps and table of
tapping voltage, current and power
q) Transport weight of transformer
r) Weight of core and windings
s) Total weight
t) Name of the purchaser
u) PO no and date
v) Guarantee period
w) Winding insulation level
Tender No: 1800000055
Page 16 of 41
7.2 Terminal marking Plate for
Bushing, anodized aluminium
black lettering on satin silver
background both inside cable
boxes near termination and on
cable box cover (all fixed by
rivet)
Required
7.3 Company Monogram Plate
fixed by rivet
Required
7.4 Lifting Lugs to lift complete
transformer
Required (minimum 4 nos. to body)
7.5 Lifting lugs for top cover Required (minimum 2 nos.)
7.6 Lashing Lugs Required
7.7 Jacking Pads with Haulage
hole to raise or lower complete
transformer
Required (4 nos.)
7.8 Detachable Bidirectional flat
roller Assembly
Required
7.8.1 Essential provision Roller dia 150 mm min., roller to be fixed in such a
way so that the lowermost part of the skid is
above ground by at least 100 mm when the transformer
is installed on roller
7.9 Earthing pad on enclosure for
transformer earthing complete
with non ferrous nut ., bolt,
washers, spring washers etc. with
metallic identification plate fixed
by rivet
Required
7.10 Earthing bridge by copper strip
jumpers on all gasketted joints at
at least two points for electrical
continuity
Required
7.11 Skid base welded type with
haulage hole
Required
7.12 Core , Frame to enclosure
Earthing
Required
7.13 Danger plate made of Anodized
aluminum with white letters on red
background on Transformer,
cable boxes (all fixed by rivet)
Required
7.14 Caution plate for Off Circuit
tap changer fixed by rivet.
Required
7.15 Winding Temperature Indicator (1
no.)
Required
7.16 WTI Scanner Box (IP 55) for
winding temperature indicator
Required
7.17 Base Channel (2 nos.) Required
7.18 Pulling Lugs 4 nos.
7.19 Make 4 nos. earth pits having
Copper earthing plate & 4 no’s of
GI earth pits & connect them in a grid with GI Strips
Total 8 nos. new earth pits required.
Connect installed transformers’ neutral & body to earth
pits using GI/Cu Strips.
Tender No: 1800000055
Page 17 of 41
8.0 Submittals:
8.1 Submittals required with Technical
Bid
a) Duly Filled up Guaranteed technical particulars
b) Descriptive literature giving full technical details of
equipment offered
c) Outline dimension drawing for each major
component, general arrangement drawing
showing component layout and general
schematic diagrams
d) Type test certificates and sample routine test
reports
e) Detailed reference list of customers already using
equipment offered during the last 5 years with
particular emphasis on units of similar design and
rating f) Details of manufacturer's quality assurance
program
g) Recommended spare parts and consumable
items for five years of operation with prices and
spare parts catalogue with price list for future
requirements
8.2 Submittals required at the final
hold
point prior to dispatch
a) Inspection and test reports carried
out in manufacturer’s works
b) Test certificates of all bought out items
c) Operation and maintenance instructions
manual as well as trouble shooting charts/
manual
d) Drawings of major components like Bushing
e) BOM
8.3 Drawing and document sizes Standard size paper A1, A2, A3, A4
9.0 Submission of drawing to mdl/consultant approval prior to manufacturing:
Prior to manufacture, a set of following drawings with all dimensions shall be submitted for MDL
approval within 1 month after order placement.
1. Rating & Marking Plate drawing
2. General Arrangement & Layout drawing for transformers’ installation at actual site 3. HV bushing assembly
4. LV bushing assembly
5. Terminal arrangements
6. HV & LV Terminal Box
7. Bus Duct Entry Box
8. Marshalling Box
9. Wiring schematic
10. GA drawing of offered Transformers
11. Busduct Layout (GA drawings) for termination at LV side & joining details with existing bus
duct for both transformers
12. Busduct sections’ dimensional details & technical ratings & details sheet
13. Busduct supporting arrangement (GA drawing) for both transformers
14. List of makes of all fittings and accessories
10.0 Inspection & testing during manufacturing of both transformers:
The supplier shall submit all the stage inspection Reports as per Quality Assurance Plan (QAP)
and Factory Acceptance Test Reports to MDL prior to the Pre-dispatch inspection & Testing
call.
Tender No: 1800000055
Page 18 of 41
11.0 Pre-dispatch inspection & testing of both transformers:
a) Below mentioned all Routine Tests & Type Tests shall be conducted on both the
transformers at Manufacturer’s Works in the presence of MDL’s representatives and/ OR
Consultant’s representatives. Some of the Routine tests & Type tests specifically
mentioned below in the scope shall be conducted at Manufacturer’s Works by
ERDA/CPRI personnel using ERDA / CPRI’s own equipments in the presence of MDL’s
representatives and / OR Consultant’s representatives. Original Test Certificates for the
tests carried out by ERDA/CPRI shall be issued by ERDA / CPRI and Original Test
Certificates for tests carried out by the Manufacturer shall be issued by the
manufacturer.
b) Supplier shall submit both the certificate sets to MDL and Electrical Consultant. Based on
the Test Reports, Dispatch Clearance shall be given from MDL office at Mumbai.
Inspection & Testing charges inclusive of ERDA / CPRI’s services, as well as
Manufacturer’s services shall be included in the cost of offered transformers at the time
of bidding.
c) Supplier shall issue pre-dispatch inspection & testing call 25 days in advance prior to the
inspection & testing schedule, with confirmation that both the transformers are complete
in all respect so as to be offered for the pre-dispatch inspection and testing. Supplier shall also forward the inspection & test schedule at the time of giving inspection & testing call.
All of these tests shall be conducted at a one go.
11.1 Following Routine Tests to be carried
out at Manufacturer’s Works by
manufacturer using their own
equipments in the presence of
MDL’s representatives and/ OR
Consultant’s representatives.
Measuring Instruments used for
testing shall have valid calibration certificates.
a) Visual and dimension check for completely
assembled transformer
b) Measurements of voltage ratio & check of phase displacement
c) Measurements of winding resistance at principal tap and two extreme taps.
d) Measurements of insulation resistance: It shall be carried out at 5kV for HV and 1 kV for LV.
e) Separate sources voltage withstand test
f) Induced voltage withstand test
g) Impedance measurement of principal tap (HV and LV) of the transformer.
h) Magnetic balance test
i) Power frequency voltage withstand test on all auxiliary circuits
11.2 Following Routine Tests to be carried
out at Manufacturer’s Works by
ERDA/CPRI personnel using ERDA /
CPRI’s own equipments in the
presence of MDL’s representatives
and/ OR Consultant’s representatives.
a) Measurement of iron losses and exciting current at
rated frequency and 90%, 100% and 110% rated voltage
b) Load losses measurement.
c) Vector Group and polarity test
d) Certification of all test results by ERDA / CPRI
11.3 Type Tests to be carried out at
Manufacturer’s Works by
ERDA/CPRI personnel using ERDA /
CPRI’s own equipments in the
presence of MDL’s representatives
and/ OR Consultant’s representatives.
a) Temperature Rise Test
11.4 Special Tests to be carried out at a) Measure of zero seq. impedance (Cl. 16.10 IS 2026
Tender No: 1800000055
Page 19 of 41
Manufacturer’s Works by
manufacturer using their own
equipments in the presence of
MDL’s representatives and/ OR Consultant’s representatives.
Part I)
b) Measurement of acoustic noise level (Cl. 16.12 of IS 2026 Part I)
c) Measurement of harmonic level on no load current.
11.5 OEM shall submit TEST Certificates of
the following raw materials as per
relevant IS amended up to date, to
MDL Representatives and
Consultant’s representatives at the
time of routine testing of fully assembled transformer.
a) Copper Conductor
b) Core
c) Porcelain Bushings
d) Electrical grade insulating Kraft Paper
12.0 Packaging
1 Packaging protection Against corrosion, dampness, heavy rains, breakage and vibration
2 Packaging for accessories
and spares
Robust wooden non-returnable packing case with all the
above protection
13.0 Annexures to be submitted along with technical bid
The bidder shall fill in & submit the following 2 nos. Annexures which shall be part of the
technical bid of the offer. If the duly filled in Annexures are not submitted with the technical
bid of the offer, then the offer shall be rejected.
Annexure 1: Confirmations by Seller for scope of Supply & Work for Both Transformers and
Technical Pre-Qualification Criteria.
Annexure 2: Confirmations by Seller for Guaranteed Technical Particulars.
Annexure 3: Data sheets of transformers.
14.0 Deviations:
Deviations from this Specification shall be clearly mentioned in the technical bid by reference
to the Specification clause no./GTP/Drawing and a description of the alternative offer. In
absence of such a statement, requirements of the Specification shall be met without
exception.
15.0 Guarantee:
Transformers supplied against this specification shall be guaranteed for the period of 12
months from the date of commissioning or for period of 18 months from the date of supply.
16.0 Documents to be supplied at the time of delivery:
1. Set of all the approved documents mentioned in the clause no. 9 of this specs.
2. Spare parts list/Bill of material in excel sheet format
3. Calibration certificates for all the gauges fitted on the transformer
4. Guarantee Certificates
5. Instruction & Operation Manual
6. Softcopies of documents listed above from 16.1 to 16.5 on 2 nos. DVDs
17.0 QAP shall include following,
Raw Material:
Tender No: 1800000055
Page 20 of 41
1 RAW MATERIAL
Sr.
No.
Material Component
Operations
Characteristic/ Inspection /
Testing
Bidder input
1 Conductor : P.C / enamel covered (Round & Strip
Bare & Paper Covering size
2 Insulating Papers : Nomex Thickness and size
3 Fiber glass sheets Thickness and size
4 Fiber glass cloth No physical damage
5 Varnish Viscosity & type
6 CRGO Lamination Thickness, Rust free, Grade
7 gaskets Thickness, Compressibility, &
Size
8 M.S.Sheets & Channel for enclosure &frames
Thickness , Size & Rust free
9 Brass stud for tap changing Dimensions
10 Bushings & epoxy insulators HV test / Crrpage
11 Neutral C. T. Pri/Sec ratio
12 Fiberglass tube, HT Sleeves,
Tape, blocks, spacers
Dimensions & Visual
13 Digital WTI (optional ) Alarm & Trip Checking
14
Enclosure ( for core-coil assembly
Dimensions & welding
Quality, door alignment &
Rollers.
In process inspection:
2 INPROCESS INSPECTION
Sr.
No.
Material
Component
Operations
Characteristic/ Inspection / Testing
Bidder input
1
Core Building
( steplap, mitred
construction)
i) Window Height & Width
ii)Number of sreps
iii) Diameter & diagonals
iv) Frame insulation
v) Araldite application On core limbs
vi) Anti Rust Protection
2 Winding
i) Bare Conductor Size & Nomex
covering size.
ii) ID, OD & Axial heights of HV & LV
iii) Continuity test
iv) Lead Positions for HV & LV winding
Tender No: 1800000055
Page 21 of 41
3
EPOXY casting of
individual winding
in casting plant
1) pouring the mixture under vacuum.
2) POSITION of tapping studs
4
Curing of
moulded winding
in oven
EPOXY material should be fully hard &
without any cracks
5 Assembly
i) Size of common blks. At top & bottom
end.
ii) Winding height
iii) HV & LV Clamping
iv) Cooling ducts
v) 1St Ratio Test Before casting
vi) 2nd Ratio test After casting
vii) Core / Frame & yoke stude insul.
Checking
viii) Core to frame earthing
ix) HV connections for delta / star
formation.
x) Brazing of current carrying joints
6
Tanking
i) Clearances between phases
ii) Clamping & tightness of fasteners
before tanking
iii) Straightness of top yoke lamination
iv) Ready for top cover & tightness of
connections & contact surface tinned
v) Air intel and outlet openings (
Ventilation )
vii) Terminal arrangement ( Cable box
/ Bus duct )
Final Testing & Dispatch:
3 FINAL TESTING & DISPATCH
Sr.
No.
Material
Component Operations
Characteristic/ Inspection / Testing Bidder/Consultant/clients input
1 Insulation
Resistance
I.R. Values in M. ohms @ ambient
2 Final Ratio Test Voltage Ratio at all tap positions
3 Winding resistance Resistance in Ohms / milliohm
4 Vector Group check
Vector Relationship
5 Separate Source
voltage withstand
Withstand test
6 iInduced over
voltage withstand
Withstand Test
7 No Load loss test Losses & % Excitation
Tender No: 1800000055
Page 22 of 41
8 Load loss & % Z
measurement
Losses & % Impedance
9 Temp. rise Test
(Type test)
wdg. Temp. rise
10 Acoustic Noise level test (Type test)
Sound level checking
11 Packing of Accessories
Visual check to avoid damage during transport
12 Finishing i) Terminal marking & Rating plate ii)
Paint Shade
13 Dispatch Supporting at Lorry base & lashing by
rope
18.0 Guaranteed technical particulars for distribution transformers
The bidder should fill up Technical particulars of Distribution Transformer in the following format)
The Bidder shall give his alternate offer for Oil cooled Transformer.
___________________________________________ (Bidder’s Name)
SR. NO. PARTICULARS Bidders input
1.0 General
1.1 Make
1.2 Type
1.3 Reference Standard
2.0 Rating
2.1 Rated output 2000 KVA
2.2 Type of cooling Air Cooled
2.3 Rated Voltage (kV)
H.V.
L.V.
11 KV
0.433 KV
2.4 Rated Current (Amps)
a) H.V.
b) L.V.
2.5 Guaranteed No Load current @ 100% rated voltage A H.V.
B L.V.
2.6 Guaranteed No Load current @ 110% rated voltage
H.V.
L.V.
2.7 No. of phases
2.8 No. of windings per phase
2.9 Rated Frequency ( Hz )
2.10 Vector Group reference
3.0 Temperature
3.1 Reference ambient temperature (deg C )
3.2 a)Temperature rise over reference Ambient
b) Winding by resistance ( deg C )
3.3 Maximum continuous overloading capacity of the
transformer without exceeding the specified winding
temperature
4.0 Tappings
Tender No: 1800000055
Page 23 of 41
SR. NO. PARTICULARS Bidders input
4.1 Type
4.2 Capacity
4.3 Range-Steps x % variation +7.5% to -7.5% in steps of
2.5%
4.4. Taps provided on H.V. windings
4.5 Details of Tappings
Tap Position HV Volts / LV Volts
1
2
3
4
5
4.6 Off load Tap Links
a) Operating Voltage ( kV )
b) Rated Current ( Amp )
c) Type
d) Reference Standard
e) Number of Poles
f) Defined features provided
(Please attach technical catalog giving details and
drawing)
Yes/No
5.0 Impedance at principal tap rated current and
frequency (%)
5.1 Impedance
5.2 Reactance
5.3 Resistance
5.4. Zero Sequence impedance
a) H.V.
b) L.V.
5.5 Resistance of the winding @ 75 Deg C
a) H.V.
b) L.V.
6.0 Guaranteed Losses at principal tap full load and 75
Deg C without any positive tolerance
6.1 No load losses (kW)
6.2 Load Losses (kW)
6.3 Total Losses (kW)
6.4 No Load loss at maximum permissible voltage and
frequency (approx.) kW.
7.0 Efficiency
7.1. Efficiency at 75 Deg C and unity power factor (%)
a) at 110% load
b) at 100% load
c) at 80% load
d) at 60% load
e) at 40% load
f) at 20% load
7.2 Efficiency @ 75deg C and 0.8 power factor lag ( % )
a) at 110% load
b) at 100% load
Tender No: 1800000055
Page 24 of 41
SR. NO. PARTICULARS Bidders input
c) at 80% load
d) at 60% load
e) at 40% load
f) at 20% load
Maximum efficiency (%)
Load and power factor at which it occurs
8.0 Regulation
Regulation at full load @75 Deg C
a) at Unity power factor
b) at 0.8 Power factor lagging
Regulation at 110% load @ 75 Deg C
a) at Unity power factor
b) at 0.8 Power factor lagging
9.0 No. load current (Amps)
At 100% voltage
a) H.V.
b) L.V
At 110 % voltage
a) H.V.
b) L.V
10.0 Maximum flux density (Lines/cm2 )
At 100% rated voltage
At 110% rated voltage
11.0 Maximum current density Amps/ cm2.
H.V. Winding
L.V. Winding
Withstand time and current as multiple of full load
current without injury for (Amps x Sec.)
Three phase dead short circuit at terminal with rated
voltage maintained on the other side.
Single phase short circuit at terminal with rated
voltage maintained on other side
12.0 Cooling System (if applicable)
Type of cooling
No. of cooling exhaust fans
Capacity of cooling exhaust fan
13.0 Core
Type/Core/or shell
Core Material
Thickness of lamination (mm)
Insulation of lamination (mm)
Equivalent cross section area ( mm2 )
14.0 Coils
14.1 Type of coils
a) H.V.
B) L.V
14.2 Conductor material
Gauge/area of cross section of conductor
a) H.V.
Tender No: 1800000055
Page 25 of 41
SR. NO. PARTICULARS Bidders input
b) L.V
14.3 Insulating material ( class H/180 Deg C or above )
a) H.V. Turn
b) L.V. Turn
c) L.V. Core
d) H.V – L.V.
14.4 Insulating material thickness (mm)
a) H.V. Turn
b) L.V. Turn
c) L.V. Core
d) H.V – L.V.
15.0 Minimum design clearance (mm)
H.V. to earth in air
L.V. to earth in air
Between H.V. & L.V. in air
Top Winding and Yoke
Bottom winding and yoke
16.0 Transformer impulse level (kV)
H.V. Winding
L.V. Winding
17.0 Bushing
Make
Type
Reference Standard
Voltage Class (kV)
Creepage distance factor (mm/kV)
Weight ( Kg )
Free space required for bushing removal (mm)
18.0 Terminal connections
H.V
L.V
L.V. Neutral
L.V. side to have Busduct provision
19.0 Accessories
Each Transformer furnished with fittings and
accessories as per Clause No.5.00.00 (Please attach
separate sheet giving details)
20.0 Drawings.
The Bidder shall submit the following drawings along
with offer:-
a. The overall schematic diagram with ratings
b. The physical arrangement lay out showing plan,
elevation and section for all equipments of CSS.
c. The foundation drawings showing civil work
requirement to install CSS.
21.0 Overall dimensions
Length (mm)
Breadth (mm)
Height (mm)
22.0 Weight Data Kg)
Tender No: 1800000055
Page 26 of 41
SR. NO. PARTICULARS Bidders input
Core and frame (Kg)
Core windings etc. (Kg)
Total Weight (Kg)
23.0 Shipping Data
Weight of heaviest package (Kg)
Dimensions of the largest package (L x B x H) (mm)
24.0 Tests
Routine tests as per IS:11171/1985
Core bolt withstand voltage for 1 minute
Type Test quoted:
Temperature rise test at ANAN rating
Impulse Test (kV peak)
(Add Sheets if necessary)
Partial Discharge Level:
Tender No: 1800000055
Page 27 of 41
TECHNICAL SPECIFICATIONS FOR POINT WIRING
1.0 Scope of Work
This section covers, definition of point wiring, system of wiring and supply, installation,
connection, testing and commissioning of point wiring for light points, convenience socket
outlet points, power socket outlet points etc. including fixing of light fixtures.
2.0 Code & Standards
The following standards and rules shall be applicable:
Sr.
No.
Item Relevant IS Relevant IEC
1 Code of practice for electrical wiring
installation (System voltage not exceeding
650 V)
IS: 732
2 Code of practice for fire safety of buildings
(General) Electrical installation.
IS: 1646
3 Rigid steel conduits for electrical wiring. IS: 9537 (Part - 2)
4 Fittings for rigid steel conduits for electrical
wiring.
IS: 2667
5 Flexible steel conduits for Electrical wiring. IS: 3480
6 Accessories for rigid steel conduit for
electrical wiring.
IS: 3837
7 PVC insulated cables. IS: 694
8 Rigid non-metallic conduits for electrical
wiring.
IS: 9537 (Part - 3)
9 Flexible (Pliable) non-metallic conduits for
electrical installation.
IS: 6946
10 3 pin plugs and sockets. IS: 1293
11 Specifications of conduits for electrical
installation.
IS: 8130
12 Switches for domestic purpose. IS: 3854
13 Fittings for rigid non-metallic conduits. IS: 3419
14 Guide for electrical layout in residential
buildings Indian electricity act and rules.
IS: 4648
3.0 System of Wiring
Unless otherwise mentioned on the drawings, the system of point wiring shall be as follows
The system of wiring shall consist of single core, FRLS insulated, 650/1100 volt grade, copper
conductor wires/cables laid through exposed (surface mounted) PVC conduits as directed &
wherever required, conduits shall be concealed in walls and slabs
4.0 General
Prior to laying of conduits, the contractor shall submit for approval, the shop drawing for
conduit layout indicating the route of the conduits, number and size of the conduits, location
of junction/inspection/pull/outlet boxes, size and location of switch boxes, number and size of
wires pulled through each conduit and all other necessary relevant details. Only after the
drawings are approved, the contractor shall proceed with the work of laying of conduits.
5.0 Material
5.1 PVC Conduit
Tender No: 1800000055
Page 28 of 41
All non-metallic PVC conduits shall conform to IS: 9537 (Part - 3). The conduit shall be planed
and of type as specified in IS: 9537 and shall be used with the corresponding accessories
(Refer IS: 3419 specification for fittings for rigid non-metallic conduits). PVC conduits shall be
rigid unplasticised, heavy gauge having 2.0 mm. wall thickness upto 20 mm. diameter conduit
and 2.5 mm. wall thickness for all sizes above 20 mm. diameter
5.2 Cables
1. The cables shall conform to IS: 697. For all internal wiring FRLS insulated cables of 650/1100
volts grade, single core shall be used.
2. The conductors shall be plain annealed copper conductors complying with IS: 1554.
3. The conductors shall be circular copper conductor.
4. The insulation shall be FRLS compound complying with the requirements of IS: 697. It shall be applied by an extrusion process and shall form a compact homogenous body.
5. The thickness of FRLS insulation shall be as set out in the relevant standards
6.0 Switches
1. Switches shall conform to IS: 3854, IS: 1293 and IS: 4615. The switches shall be single pole,
single or two way as shown on the drawings or as specified. They shall be of moulded type
rated for 250 volt, and of full 5/15 A capacity. They shall be provided with insulated dollies
and covers
2. The switches shall be rocker operated with a quiet operating mechanism with bounce free
snap action mechanism enclosed in an arc resistant chamber.
3. The switches shall have pure silver and silver cadmium contacts.
4. The switches shall be flush modular type.
5. The make of the switches shall be as indicated in the drawings or BOQ or make of material
or as suggested and approved by the client.
7.0 Socket
1. The sockets shall conform to IS: 1293. Each socket shall be provided with control switch of
appropriate rating. The sockets shall be moulded type, rated for 250 volts, and either of full
5 A or 15 A capacity, as mentioned on the drawings.
2. Sockets shall be of three pin type, the third in being connected to earth continuity
conductor.
3. The socket shall be flush modular type.
4. The finishing and make of all the sockets shall be same as light switch.
5. The socket shall have fully sprung contacts and solid brass shrouded.
6. Terminals to ensure positive electrical connections.
7. The sockets shall be provided with automatic shutters, which open only when earth pin of
the plug inserts in the socket.
8. The socket shall be provided with three pin plug top suitable to the socket and of the same
make as socket.
Tender No: 1800000055
Page 29 of 41
8.0 Inspection and testing
8.1 Insulation Resistance Test
The insulation resistance shall be measured by applying 500 volt megger with all fuses in
places, circuit breaker and all switches closed.
The insulation resistance in megohms of an installation, measured shall not be less than 50
megohms divided by the number of points on the circuit.
The insulation resistance shall be measured between
1. EARTH TO PHASE
2. EARTH TO NEUTRAL
3. PHASE TO NEURAL
4. PHASE TO PHASE
8.2 Earth Continuity Path
The earth continuity conductors shall be tested for electrical continuity and the electrical
resistance of the same along with the earthing lead but excluding any added resistance or earth leakage circuit-breaker, measured from the connection, with the earth electrode to any
point in the earth continuity conductor in the completed installation and shall not exceed one
ohm.
9.0 Method of measurement
All the items will be measured as mentioned in Bill of quantity.
10.0 Transport, delivery and storage
The wire shall be supplied in the actual length as per detailed purchase order
The wire shall be dispatched at client’s stores or at site as per detailed instructions given by
client at later stage.
The wire shall be loaded from the main vendor’s store and properly stacked as per instruction of client’s local representative. All such labour and transportation charges shall be clearly
mentioned in the offer.
11.0 Guarantee and warranty
The quotes values of parameters shall be within given tolerance for given period of service
life.
Tender No: 1800000055
Page 30 of 41
TECHNICAL SPECIFICATIONS FOR SUPPLY OF LIGHT FIXTURE AND EXHAUST FAN
1.0 Scope of Work
The scope of work shall cover the supply, installation and testing of various types of LED light
fixtures are used in the project.
2.0 Code & Standards
The following standards and rules shall be applicable:
IS 3646 (1960) Code of practice for interior illuminator.
IS 1913(1969) General and Safety requirements for electric lighting fittings.
Indian Electricity Act and Rules issued here under.
3.0 Technical requirements
3.1 General requirements
All fixtures shall be complete with accessories and fixings necessary for installation whether so
detailed under fixture description or not.
LED Surface type Industrial type luminaire are proposed. Fixture shall be corrosion resistant,
impact proof, surface mounting luminaire with PC housing & opal finish cover suitable for dusty
location with LEDs as light source. Housing shall be made up of corrosion resistant unbreakable
polycarbonate body. Cover shall be of High quality polycarbonate diffuser in opal finish for
glare free uniform light distribution, fixed to the housing with SS snap fit clamps. Lamp shall be High efficiency long life LED chip with Ra>70, lumen efficacy>125 lm/W & view angle 120°.
Optics Reflector made of LEF sheet which is pasted on Al. sheet (heat sink) to enhance the
lumen output of the fixture.
Electronic driver shall be powered by an in-built electronic driver (SMPS based constant
current supply) with THD. Mounting shall be on ceiling/ wall through 2 nos. slots using SS clamps
& screws provided with fixture.
Vendor shall be responsible for measuring the level of illumination after installation.
Lighting fixtures shall be designed for minimum glare and for continuous operation under
specified atmospheric condition.
4.0 LED Lamps:
LED lamp is a light-emitting diode (LED) product which is assembled into a lamp (or light bulb)
for use in lighting fixtures. LED lamps have a lifespan and electrical efficiency which are several
times longer than incandescent lamps, and significantly more efficient than most fluorescent
lamps.LEDs come to full brightness without need for a warm-up time; the life of fluorescent
lighting is also reduced by frequent switching on and off.
LEDs are “directional” light sources, which means they emit light in a specific direction, unlike
incandescent and compact fluorescent bulbs, which emit light and heat in all directions.
The LED bulbs require much less wattage than the CFL or Incandescent light bulbs.
5.0 Luminaires:-
LED Surface type Industrial type luminaire are proposed. Fixture shall be corrosion resistant,
impact proof, surface mounting luminaire with PC housing & opal finish cover suitable for dusty
location with LEDs as light source.
Tender No: 1800000055
Page 31 of 41
6.0 LED Industrial type batten light tech specs:-
Sytem power : 20 WATT LED SURFACE MOUNTED LUMINAIRE
LED Type : High Brightness Power LED
Color Temperature : 5000 - 6000K
CRI : >95
Lens : 95 Deg.
7.0 Drawings & Information
As per of the proposal the bidder furnish relevant descriptive and illustrative literature on lighting
fixtures and accessories and following drawings/ data for the respective lighting fixtures:-
1. Dimensional Drawings.
2. Mounting details cable entry facilities and weights.
8.0 Method of measurement
Supply of the fixture including transport to site, loading and unloading etc. as specified will be
treated as one unit for measurement and payment.
9.0 Guarantee and Warranty
The Bidder shall stand guarantee for the performance of entire fixtures and components for
twelve (12) months from the date of commissioning or eighteen (18) months from the date of
dispatch, whichever is earlier, as agreed up on and as reproduced in the purchase order
within the tolerance specified or as permitted by the relevant standards for the equipment in his scope of supply. The Purchaser also reserves the right to use the rejected equipment or part
thereof until the new equipment meeting the guaranteed performance is supplied by the
Bidder.
10.0 PROPELLER EXHAUST FAN
The Propeller fan shall be direct-driven, three or four blade type, mounted on a steel mounting
plate with orifice ring. Mounting Plate shall be of steel construction, square with streamlined
venturi inlet coated with baked enamel paint. Mounting plate shall be of standard size,
constructed of 12 to 16 gauge sheet steel depending upon the fan size. Orifice ring shall be
correctly formed by spinning or stamping to provide easy passage of air without turbulence and to direct the air stream. Fan blades and hub assembly shall be statically and dynamically
balanced at the manufacturer’s works. Motor shall be standard permanent split capacitor or
shaded pole for small sizes, totally enclosed with pre-lubricated sleeve or ball bearings,
designed for quiet operation with a maximum speed of 1000 rpm for fans 60 cm dia or larger
and 1440 rpm for fans 45 cm dia and smaller. Motors for larger fans shall be suitable for 415±6%
volts, 50 cycles 3 phase power supply, and for smaller fans shall be suitable for 220 ± 6% volts,
50 cycles single phase power supply. Motors shall be suitable for either horizontal or vertical
service. Wire guard on inlet side and bird screen at the outlet, Fixed or gravity louvers built into
a steel frame at the outlet., Regulator for controlling fan speed for single phase fan motor,
Single phase preventors for 3 phase fans shall be included in fan cost.
Tender No: 1800000055
Page 32 of 41
TECHNICAL SPECIFICATIONS FOR SUPPLY OF EARTHING SYSTEM
1.0 Scope of Work
Design, assembling, testing, painting, supply, delivery at site with all related accessories as per
the specifications as specified below. Compliance with the provisions of this specification shall
not relieve the Bidder of the responsibility of furnishing apparatus and accessories of proper
design, electrically and mechanically suited to meet the operating requirements under the
specified service conditions and be suitable for the purpose of which they are intended.
2.0 Code & Standards
The design, material, assembling, inspection and testing shall comply with all currently
applicable statutes, regulations and safety codes in the locality where the system will be
installed. The equipment shall also conform to the latest applicable standards and codes of
practice as mentioned below:
Sr. Item Relevant IS / IEC
1 Code of Practice for Earthing IS 3043
2 Insulation Co-ordination Application Guide IS 3716
3 Code of Practice for Protection of Buildings and Allied Structures against Lightning
IS 2309
4 Indian Electricity Rules, 1956
5 Indian Electricity Act, 1910
6 National Electrical Code
7 Low Voltage Electrical Installations-Part 5-54: Selection & Erection of
Electrical equipment- Earthing arrangement & protective conductors.
IEC 60364
8 Protection Against Lightning –Part 3: Protection of structures & life Hazards
IEC 62305
3.0 Installation of system
The plate/pipe electrode, as far as practicable, shall be buried below permanent moisture
level but in no case less than 3 M below finished ground level.
The plate/pipe electrode shall be kept clear of the building foundation and in no case, it shall
be nearer by less than 2 M from outer face of the respective building wall / column.
Construction of the earthling station shall in general be as shown in the drawing and shall
conform to the requirement on earth electrodes mentioned in the latest edition of Indian
Standard IS: 3043, Code of Practice for Earthling Installation.
The earth conductors ( Strips / Wires, Hot dip G.I. / copper ) inside the building shall properly be
clamped / supported on the wall with Galvanized Iron clamps and Hot Dip GI screws / bolts.
The conductors outside the building shall be laid at least 600 mm. below the finished ground
level.
The earth conductors shall either terminate on earthing socket provided on the equipment or
shall be fastened to the foundation bolt and / or on frames of the equipment. The earthing
connection to equipment body shall be done after removing paint and other oily substances
from the body and then properly be finished
Tender No: 1800000055
Page 33 of 41
Over lapping of earth conductors during straight through in joints, where required, shall be of
minimum 75mm. long and bitumen coated.
The earth conductors shall be in one length between the earthing grid and the equipment to
be earthed
Minimum distance of 2 mtr shall be maintained between other electric conductor, earthing
conductor and the conductor laid for the lightning protection system. Earthing and lightning
protection system conductors shall be bonded to each other to prevent side flashover in case
of non-availability of adequate clearance.
The earthing met conductors, risers, earthing cables, etc. passing through walls shall be
covered with galvanized iron sleeves for the passage through wall. Water stop sleeves shall
also be provided wherever the earthing conductor enters the building from outside.
4.0 Plate Electrode Earthing:
Earthing electrode shall consist of a Galvanized Cast Iron plate not less than 600 x 600 x 6
mm thick, or, 60 x 60 x 0.6 cm G.I. as called for in the drawings. The plate electrode shall be
buried as far as practicable below permanent moisture level but in any case not less than 3
mts. Below ground level. Wherever possible earth electrode shall be located as near the water tap, water drain or a down take pipe as possible. Earth electrodes shall not be installed
in proximity to a metal fence.
It shall be kept clear of the buildings foundations and in no case shall it be nearer than 1 meter
from the outdoor face of the wall. The earth plate shall be set vertically and surrounded with
150 mm thick layer of charcoal dust and salt mixture. 20 mm G.I. pipe shall run from the top
edge of the plate to the ground level. The top of the pipe shall be provided with a funnel and
a mesh for watering the earth through the earth. The main earth conductors shall be
connected to the electrode just below the funnel, with proper terminal lugs and checks
nuts. The funnel over the G.I. pipe and earth connections houses 300 mm wide and 300
mm deep. The masonry chamber shall be provided with a cast iron cover resting cover a C.I.
frame embedded in masonry.
Tender No: 1800000055
Page 34 of 41
Tender No: 1800000055
Page 35 of 41
TECHNICAL SPECIFICATIONS FOR LT XLPE CABLES
1.0 Scope of Work
This section shall cover supply, laying, testing and commissioning of medium voltage XLPE
cables.
This specification gives the general requirement of cables. However, it is the responsibility of
the vendor to take the joint measurement and obtain client’s approval before the placement
of orders to the main supplier / manufacturer.
1.1 LT Power Cables - General Description:
Electrolytic grade of Aluminium / high conductivity annealed copper conductor, as per IS :
7098, XLPE insulation, all sector shaped cores laid up with PP filler and PP tape (in case of
extruded PVC inner sheath), taped/ extruded PVC inner sheath as per IS : 5831, armoured as
per IS : 3975 and overall Flame Retardant ST2 PVC sheath as per IS:5831, 1100 Volts grade
cable as per IS : 7098 (I).
1.2 LT Control Cables - General Description:
Plain annealed electrolytic grade of Copper conductor, as per IS : 8130, PVC insulation as per IS : 5831, cores laid up, STI PVC inner sheath as per IS : 5831, armoured as per IS : 3975 and
overall STI PVC sheath as per IS : 5831, 1100 Volts grade cable as per IS : 1554 (I).
1.3 Conductor:
Conductor shall be stranded above 10 sqmm in case of Aluminium cables, and above 6
sqmm in case of copper cables, below which it shall be solid conductor. On customer
demand stranded conductor can be supplied. Stranded conductor are shaped and
compacted to reduce dimension and give a smoother profile.
Strand details shall be as below :
1.5 to 10 sqmm (CU) - 7 Strands
6 to 10 sqmm (AL) - 1 Strands
16 to 50 sqmm (CU/AL) - 7 Strands
70 to 150 sqmm (CU/AL) - 19 Strands 185 to 300 sqmm (CU/AL) - 37 Strands
400 to 630 sqmm (CU/AL) - 61 Strands
800 to 1000 sqmm (CU/AL) - 91 Strands.
1.4 Insulation :
Insulation shall be of cross linked polyethylene with IR value more than 100 Mega .ohm/km for
power cables and shall be of PVC type A with IR value more than 50 Mega Ohm/km for PVC
cables.
XLPE : Insulation having dielectric strength between (25 – 30 KV/MM)
PVC Type A : Insulation having dielectric strength between (30 – 36 KV/MM)
1.5 Inner sheath :
Inner sheath of ST-2 PVC along with Polypropylene (PP) fillers, in case of Taped Inner Sheath.
For extruded PVC inner sheath (if required) PP Fillers shall be provided with a binder of PP
Tape.
Tender No: 1800000055
Page 36 of 41
1.6 Armour :
ISI Marked armour, as per IS : 3975 should be provided over inner sheath to guard against
mechanical damage. Armour should be galvanized steel wire/ strip. In case of single core
cables used in A.C Systems, armouring should be non magnetic hard drawn aluminium wire/
strip. Round steel wire should be used where diameter over inner sheath is less than 13mm
and flat steel strip armour when diameter over inner sheath exceeds 13 mm. Round wire can
be provided on specific request.
Armour coverage to be more than 95% to achieve better mechanical projection and low
armour resistance.
1.7 Outersheath :
Outer sheath is of extruded ST-2 Flame Retardant PVC compound, black in colour as per IS :
5831. Having Oxygen index value of min 30%.
Outer sheath shall be resistant to terminate and rodent attack.
2.0 Code & Standards
The following standards and rules shall be applicable:
Sr.
No
Item Relevant IS Relevant IEC
1 XLPE insulated electric cables (heavy duty). IS : 7098 Part I
2 Recommended current ratings for cables. IS : 3961
3 Aluminium conductors for insulated cables IS : 8130 Indian Electricity Act and Rules.
3.0 Technical Requirements
3.1 General constructional features
The medium voltage cables shall be supplied, laid, connected, tested and commissioned in accordance with the drawings, specifications, relevant Indian Standards specifications,
manufacturer’s instructions. The cables shall be delivered at site in original drums with
manufacturer’s name, size, and type, clearly written on the drums.
3.2 Material
Medium voltage cable shall be XLPE insulated. PVC sheathed, aluminium or copper
conductor, armoured conforming to IS: 7098 Part I
3.3 Type
The cables shall be circular, multi core, annealed copper or aluminium conductor, XLPE
insulated and PVC sheathed, armoured or unarmoured.
3.4 Conductor
Uncoated, annealed copper / aluminium, of high conductivity upto 4 mm.² size, the
conductor shall be solid and above 4 mm.², conductors shall be concentrically stranded as
per IEC : 228.
3.5 Insulation
Tender No: 1800000055
Page 37 of 41
XLPE rated 70° c. extruded insulation.
3.6 Core Identification
Two core : Red and Black
Three cor : Red, Yellow and Blue
Four core : Red, Yellow, Blue and Black
Single core : Green, Yellow for earthing
Black shall always be used for neutral.
3.7 Assembly
Two, three or four insulated conductors shall be laid up, filled with non-hygroscopic material
and covered with an additional layer of thermoplastic material.
3.8 Armour:
Galvanised steel flat strip / round wires applied helicaly in single layers complete with covering
the assembly of cores.
For cable size upto 25 Sq. mm. : Armour of 1.4 mm dia G.I. round wire
For cable size above 25 Sq. mm. : Armour of 4 mm wide 0.8 mm thick G.I strip
3.9 Sheath
XLPE 70 deg.c. rated extruded.
Inner sheath shall be extruded type and shall be compatible with the insulation provided for
the cables.
Outer sheath shall be of an extruded type layer of suitable PVC material compatible with the
specified ambient temp. 50 deg. C and operating temperature of cables. The sheath shall be resistant to water, ultraviolet radiation, fungus, termite and rodent attacks. The colour of outer
sheath shall be black.
Sequential length marking required at every 1.0 mtr. interval on outer sheath
Vendor has to furnish resistance / reactance / capacitances of the cable.
3.10 Rating: Up to and including 1100 Volts.
4.0 Drawings & information
Contractor shall submit the as built drawing of the cable laying drawing.
HANDINGOVER DOCUMENTS
The supplier shall submit following: 1. Data sheet indicating results of tests
2. Test reports
5.0 Inspection and testing
All cables shall be adequately protected against any risk of mechanical damage to which
they may be liable in normal conditions of handling during transportation, loading, unloading
etc.
The cable shall be supplied in single length i.e. without any intermediate joint or cut unless
specifically approved by the client.
Tender No: 1800000055
Page 38 of 41
The cable ends shall be suitably sealed against entry of moisture, dust, water etc. with cable
compound as per standard practice.
6.0 Routine test
a) Conductor resistance test.
b) High voltage test.
c) Partial discharge test (for screened cable only)
(to be carried out on full drum length).
7.0 Type Test
a) Tests on conductor Annealing test for copper Tensile test (for aluminium) Wrapping test
(for aluminium) Resistance test.
b) Test for armoring wire/ strips Tensile strength & elongation at break Thickness of zinc
coating (Dip Test) Torsion/ Winding test Resistivity Test Mass of Zinc coating test.
c) Test for thickness of insulation and sheath.
d) Physical tests for insulation Tensile strength & elongation at break ageing in air oven hot
set test Shrinkage test Water absorption (gravimetric).
e) Physical test for outer sheath Tensile strength & elongation at break ageing in air oven
Shrinkage test Hot deformation. f) Insulation resistance (volume resistivity test)
g) High voltage test
h) Flammability test
i) Bleeding and blooming test (for outer sheath).
j) Partial discharge test.
k) Bending test.
l) Impulse withstand test.
m) Each core of cable shall be tested at room temperature at 3 KV A.C.
R.M.S. for duration of 5 minutes.
8.0 Method of measurement
The cables will be measured in meters. The unit rate shall include cutting the cable into
required lengths, packing, loading, unloading, insurance, transportation, delivery to stores/site
as per work order, stocking in stores, testing of cables at stores etc. of medium voltage cable.
Total quantity in meters shall be measured lug to lug basis.
9.0 Data sheet for cables
(Must be furnished along with the quotation for all cable of conductor size 50 Sq. mm and
above).
Sr. No. DESCRIPTION GUARANTEED PARTICULARS
1.0 Name of Manufacturer
2.0 Conductor
3.0 Form - circular/ segmented
4.0 Cross sectional area mm²
5.0 Whether cores identified by colours Yes/No
6.0 Overall dia. of finished cable
7.0
Critical Oxygen Index Value at 750oC when tested
for temperature index test as per ASTMD-2863
8.0
Total acid gas generation by weight when tested as
per IEC 7541
%
Tender No: 1800000055
Page 39 of 41
9.0 Percentage of light transmission under fire for
assessment of smoke generation when tested as per ASTM-D-2843.
%
10.0 Will cables offered pass the flammability tests as per:
a) Class-F3-Swedish Standard S5-424-1475
b) IEC 332-1
c) IEC 331-1
Yes/No
Yes/No
Yes/No
TECHNICAL SPECIFICATIONS FOR HT XLPE CABLES
1. Scope of Work
This section shall cover supply, laying, testing and commissioning of High voltage XLPE cables.
2. General Description:
All high voltage cables shall have a minimum rated voltage 33 KV (Earth Grade), cross-linked
polyethylene insulated, armoured and PVC sheathed. All cables shall be of 33 KV 3C
aluminum conductor, extruded shielded, cross-linked polyethylene (XLPE) insulated, semi-
conducting tape shielded, copper tape screened, assembled with non-hygroscopic fillers,
PVC separation sheathed, galvanized steel armoured and PVC outer sheathed power cable.
3. Material and Construction:
3.1 Conductor
The conductor shall consist of compacted circular (Class 2) stranded annealed plain
aluminum wires in accordance with IEC Pub 228.
The conductor shielding shall consist of extruded semi-conducting compound. A semi-
conducting separator tape may be applied between the conductor and the semi-
conducting compound layer at manufacturer’s discretion, if necessary.
3.2 Insulation
The insulation shall consist of extruded cross-linked polyethylene (XLPE).
The average thickness shall be not less than the specified nominal value. The
minimum thickness at any point shall not fall below the nominal value by more than
0.1mm plus 10% of the nominal value. The insulation shielding shall consist of a semi-
conducting tape applied with an overlap. Metallic screen shall consist of an
annealed plan copper tape applied with an overlap. The screened cores shall be
assembled together with non-hygroscopic fillers. The direction of lay shall be left
hand. A non-metallic binder tape(s) shall be applied over the assembled cores. The separation sheath shall consist of extruded black PVC. Minimum thickness at any
point shall not fall below 80% of the nominal value by more than 0.2mm. The armour
shall consist of one layer of galvanized steel wires; except for single core cables
which shall have aluminum sheathe and aluminum wire armouring. Nominal
diameter of each wire shall be 3.15mm. A suitable binder tape may be applied
over the armour at manufacturer’s discretion, if necessary. The outer sheath shall
consist of anti-termite treated and extruded red PVC compound. The minimum
thickness at any point shall not fall below the specified nominal value by more than
0.2mm plus 20% of the nominal value.
4. Core identification
The core identification shall be carried out by coloured narrow tapes longitudinally
applied over the insulation shielding. Colour: Red, Yellow and Blue.
Tender No: 1800000055
Page 40 of 41
5. Packing
The cable shall be wound onto non-returnable strong and seaworthy reel lagged
with wooden or steel battens.
6. Installation
This Contractor shall include for provision, installation, testing and commissioning of
all cables and accessories specified herein, shown on the Drawings and those
items not expressly specified but required to meet the design intent of this Section.
Although interfaces of this Contract are identified within the Contract Documents,
the Contractor should satisfy himself as to the extent of the cabling works involved,
and if unsure, should contact the Consultant before returning his tender.
MAKE OF MATERIAL
SR.NO. ITEM STANDARD MAKE
1 DRY TYPE TRANSFORMER VOLTAMP / CROMPTON GREAVES / KIRLOSKAR / ABB
2 HT XLPE CABLE POLYCAB / RPG / KEI
3 HT TERMINATION KIT RAYCHEM OR EQUIVALENT
4 HT JOINTING KIT RAYCHEM / MSEAL / OR EQUIVALENT
5 DISTRIBUTION BOARDS LEGRAND/HAGER /SCHNEIDER/C&S Electric
6 MEDIUM VOLTAGE CABLE POLYCAB/ FINOLEX / RRKABLE
7 CABLE TRAY INDIANA/OBO BETTERMAN/LEGRAND/PROFAB
8 LT SWITCHGEAR (ALL RANGE) SIEMENS / SCHNEIDER ELECTRIC / L & T / ABB
9 LT ACB SIEMENS / SCHNEIDER ELECTRIC / L & T / ABB
10 LT MCCB SIEMENS / SCHNEIDER ELECTRIC / L & T / ABB / LEGRAND
11 LT MCB, ELCB SIEMENS / SCHNEIDER ELECTRIC / HAGER /LEGRAND
12 LT SFU SIEMENS / SCHNEIDER ELECTRIC / L&T / ABB
13 LT CONTACTORS SIEMENS / SCHNEIDER ELECTRIC / L & T / ABB
14 CHANGE OVER SWITCH HPL / SOCOMEC
15 METERS (DIGITAL) AE / ENERCON / SCHNEIDER / MECO / NIPPEN
16 LOAD MANAGER ENERCON / NIPPEN/ L & T
17 RELAYS SIEMENS / SCHNEIDER ELECTRIC / GE / L & T
18 INDICATING LAMPS SIEMENS / SCHNEIDER ELECTRIC / L & T / ABB
19 ELECTRIC TIMER SIEMENS / EAPL
Tender No: 1800000055
Page 41 of 41
MAKE OF MATERIAL
SR.NO. ITEM STANDARD MAKE
20 SELECTOR SWITCH KEYCEE / SALZER
21 APFC RELAY ENERCON / L & T / TRINITY
22 LT CAPACITORS L & T / EPCOS
23 LUGS DOWELL’S / JAINSON / COMET
24 CABLE GLAND JAINSON / COMET
25 PVC CONDUITS AND
ACCESSORIES PRECISION / DIAMOND
26 CASING CAPING PRECISION / DIAMOND
27 M.S. CONDUIT AND ACCESSORIES AKG / BEC / STEELCRAFT
28 MODULAR SWITCHES, SOCKETS
& OTHER ACCESSORIES LEGRAND / SCHNEIDER / ABB
29 METAL CLAD SOCKET WITH MCB MDS / SIEMENS / LEGRAND
30 PVC JUNCTION BOX SINTEX / CLIPSAL / SPELSBERG
31 WIRES FOR INTERNAL WIRING POLYCAB/ FINOLEX / RRKABLE
32 FLEXIBLE WIRE POLYCAB/ FINOLEX / RRKABLE
33 MULTICORE FLEXIBLE CABLE POLYCAB/ FINOLEX / RRKABLE
34 CONNECTORS (COLOURS AS PER
PHASE & NEUTRAL) SALZER / ELEMEX / CONNECTWELL
35 LIGHT FIXTURES HAVELLS / WIPRO / PHILIPS / GEMINI GLOBAL
36 BATTERY EXIDE / AMCO
37 CEILING FAN / EXHAUST
FAN/WALL MOUNTED FAN CROMPTON / BAJAJ / ORIENT / HAVELLS