Retrofit of Drill
prepared for remote drilling
operation
M. Bähtz 08/09
2
CAN-Bus Topology
CAN-Bridge
ICN-VV
CAN-Master/
CAN-RC
CANopen
J1939
ICN-D2
ICN-D1
Engine J1939
3
Function of ControllerCAN-Master:
- Manage drill control
- RC-Interface
- ICN-D1:
- Manage digital in and outputs of switch panel
-CAN-Bridge:
- Manage analog sensors
- Translating J1939 to CANopen
- ICN-VV:
- PWM-Control and BangBang Control
- ICN-D2:
Drilling control
ICN-VVJ1939
CANopen
Mast
ICN-D2
J1939
CAN-Master
Drive control
CAN-Bridge ICN-D1
4
Wiring – Cab-Board
drill control, DCF/CPU1
RC interface, DCF/CPU2
drill control, ICN-D1
drill control, ICN-D2
5
Wiring – Valve-Board
drill control, ICN-V1
drill control, ICN-V2
drill control, DCF/IO
drill control, DCF/CPU
ICN-VV
DIGSY
CPU
6
Cab – New Controls
• Tablet-PC designed for rough & harsh applications, connected to the remote gateway bus (CANopen)
• functionality with Electronic Dashboard & Remote Service System,diagnostic port available
• electrical joysticks• “Murphy Gauge” for redundant engine data
Top View Side View
7
Dashboard – Drill Screen
• Pressure Gauges for drilling operation- rotation,- pull down,- system (aux),- bit air
• Icons between the gauges display drill states respectively interlocks
• Status of icon changes on input of prox. switch or logic
A detailed description of the interlocks is given in the:
SKS12 LAGUNAS NORTE OPERATIONAL INTERLOCKS GUIDE
8
How to measure on a CAN-Bus
Make a visual inspection of all CAN-Bus connections and components
Check on both sides of the CAN-Bus if the termination resistors are existing and connected properly
measure the resistance between CAN_H to ground and CAN_L to ground. Values which are below 10kOhm are suspicious and could be a sign for a high-Ohm connection between a bus line and ground
measure the resistance between CAN_H to supply voltage (Vbat) and CAN_L to supply voltage (Vbat). Values which are below 10kOhm are suspicious and could be a sign for a high-Ohm connection between a bus line and supply voltage
9
How to measure on a CAN-Busmeasure the resistance between CAN_H and CAN_L. So you can check if the termination resistors are existing and if they have the correct value or if there is a cable break or a short circuit. The value you measure should be in the range of 55…70 Ohms
disconnect either the CAN_H or CAN_L wire.
measure the resistance of the bus ring line including the termination resistors. The result gives you information if the termination resistors are existing and if they have the right value or if there is a cable break or short circuit somewhere.
10
CAN Bus monitor
Troubleshooting the CAN-Bus with a monitoring program
- shows messages of the devices
- every device (controller) is sending a „heartbeat“ cyclicly soon powered on
- heartbeat is on identifier 700 + Node ID
- Node IDs: 1, 2, 3, 4, 5, 6
- CAN-Bus baudrate is 250 kbps
11
How to reset ICN-ControllerWhile main power switch on:
- key switch on (ignition)
- change node ID with DIP switch to a valuegreater than 6
- key switch off/on
- reset node ID (old value)
- key switch off/on
-
=> Module/Controller is reseted and should start to communicate
DIP SwitchBaud rate
12
How to read the pin out for ICN-D
Pin out for ICN-D:
- X5.0 describes the Node ID and connector number (ID = 5, connector 0)
- Column for Inputs and Outputs
- Description for inputs and outputs
Number of connector
Pin
num
ber
13
How to read the pin out for DCF