Relion ® 650 series Line distance protection REL650 Product Guide

description

Relevador ABB

Transcript of REL650

  • Relion 650 series

    Line distance protection REL650Product Guide

  • Contents

    1. Description...........................................................32. Application...........................................................33. Available functions...............................................54. Impedance protection........................................125. Current protection..............................................146. Voltage protection..............................................167. Frequency protection.........................................178. Secondary system supervision..........................189. Control................................................................1810. Scheme communication....................................20

    11. Logic..................................................................2112. Monitoring.........................................................2213. Metering............................................................2414. Human Machine interface.................................2515. Basic IED functions...........................................2516. Station communication.....................................2617. Hardware description........................................2718. Connection diagrams........................................2919. Technical data...................................................3120. Ordering............................................................72

    Disclaimer

    The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumesno responsibility for any errors that may appear in this document.

    Copyright 2010 ABB AB.

    All rights reserved.

    Trademarks

    ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks orregistered trademarks of their respective holders.

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    2 ABB

  • 1. DescriptionLine distance protection IEDREL650

    The REL650 is designed for protection,monitoring and control of overhead lines andcables. The IED includes extensivefunctionality, with diverse applicationopportunities, as well as hardware, to meetspecific requirements. The powerful IEDprovides distance protection for all types ofoverhead lines, cables and power networkearthing.

    2. ApplicationThe REL650 is used for the protection,control and monitoring of overhead lines andcables in solidly or impedance earthednetworks. The IED can be used up to thehigh voltage levels. It is suitable for theprotection of heavily loaded lines and multi-terminal lines where the requirement for fastthree-pole tripping is wanted.

    The full scheme distance protection providesprotection of power lines with highsensitivity and low requirement on remoteend communication. The five zones havefully independent measuring and settingwhich gives high flexibility for all types oflines.

    The modern technical solution offers fastoperating time of typically 1.5 cycles.

    The auto-reclose includes priority features forsingle-breaker arrangements. It co-operates

    with the synchrocheck function with high-speed or delayed reclosing.

    High set instantaneous phase and earthovercurrent, four step directional or non-directional delayed phase and earthovercurrent, sensitive earth fault, thermaloverload and two step under and overvoltageprotection are examples of the availablefunctions allowing the user to fulfill anyapplication requirement.

    The distance and earth fault protection cancommunicate with remote end in anyteleprotection communication scheme.

    The advanced logic capability, where the userlogic is prepared with a graphical tool, allowsspecial applications.

    Disturbance recording and fault locator areavailable to allow independent post-faultanalysis after primary disturbances.

    Two packages has been defined for followingapplications:

    Five zone distance protection withquadrilateral characteristic (A01)

    Five zone distance protection with mhocharacteristic (A05)

    The packages are configured and ready fordirect use. Analogue and tripping IO hasbeen pre-defined for basic use.

    Add binary I/O as required for yourapplication at ordering. Other signals need tobe applied as required for each application.

    The graphical configuration tool ensuressimple and fast testing and commissioning.

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    Revision: A

    ABB 3

  • REL650 A01 Quad Distance Zones, Single Breaker 10AI (4I+1I+5U)

    SMB RREC79 0->1

    SMP PTRC94 1->0

    TCS SCBRCond

    SPVN ZBATCond

    Other configured functions

    OV2 PTOV59 U>

    PH PIOC50 3I>>

    CC RBRF50BF 3I> BF

    V MMXUMeter.

    QA1

    QB1 QB2

    QB9

    QC9

    QC2

    QC1

    WA1

    WA2

    V MSQIMeter.

    DRP RDRE Mont.

    V MMXUMeter.

    V MMXUMeter.

    EF PIOC50N IN>>

    CC RPLD52PD PD

    S SCBRCond

    L PTTR26 q>

    EF4 PTOC51N/67N IN>

    OC4 PTOC51/67 3I>

    BRC PTOC46 Iub

    UC2 PTUC37 2I

    GOP PDOP32 P>

    GUP PDUP37 P>

    CC RBRF50BF 3I> BF

    V MMXUMeter.

    QA1

    QB1 QB2

    QB9

    QC9

    QC2

    QC1

    WA1

    WA2

    V MSQIMeter.

    DRP RDRE Mont.

    V MMXUMeter.

    V MMXUMeter.

    EF PIOC50N IN>>

    CC RPLD52PD PD

    S SCBRCond

    L PTTR26 q>

    EF4 PTOC51N/67N IN>

    OC4 PTOC51/67 3I>

    BRC PTOC46 Iub

    UC2 PTUC37 2I

    GOP PDOP32 P>

    GUP PDUP37 P100 M, 500 V DC Protective bonding resistance IEC 60255-27

    Resistance

  • EMC compliance

    Table 20. EMC compliance

    Description Reference

    EMC directive 2004/108/EC

    Standard EN 50263 (2000)EN 60255-26 (2007)

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 41

  • Impedance protection

    Table 21. Distance measuring zone, Quad ZQDPDIS

    Function Range or value Accuracy

    Number of zones 5 with selectabledirection

    -

    Minimum operateresidual current

    (5-30)% of IBase 1,0 % of I r

    Minimum operate current,phase-to-phase and phase-to-earth

    (10-30)% of IBase 1,0 % of I r

    Positive sequenceimpedance reach forzones

    0.005 - 3000.000 2.0% static accuracy 2.0 degrees static angular accuracyConditions:Voltage range: (0.1-1.1) x UrCurrent range: (0.5-30) x IrAngle: at 0 degrees and 85 degrees

    Fault resistance, phase-to-earth

    (1.00-9000.00) /loop

    Fault resistance, phase-to-phase

    (1.00-3000.00) /loop

    Line angle for zones (0 - 180) degrees

    Magnitude of earth returncompensation factor KNfor zones

    0.00 - 3.00 -

    Angle for earth returncompensation factor KNfor zones

    (-180 - 180)degrees

    -

    Dynamic overreach

  • Table 22. Phase selection with load encroachment, quadrilateral characteristicFDPSPDIS

    Function Range or value Accuracy

    Minimum operate current (5-30)% of IBase 1.0% of Ir

    Reactive reach, positivesequence

    (0.503000.00) 2.0% static accuracy 2.0 degrees static angular accuracyConditions:Voltage range: (0.1-1.1) x UBaseCurrent range: (0.5-30) x IBaseAngle: at 0 degrees and 85 degrees

    Reactive reach, zerosequence, forward andreverse

    (0.50 - 3000.00)

    Fault resistance, phase-to-earth faults, forward andreverse

    (1.009000.00) /loop

    Fault resistance, phase-to-phase faults, forward andreverse

    (0.503000.00) /loop

    Load encroachmentcriteria:Load resistance, forwardand reverseSafety load impedanceangle

    (1.003000.00) /phase(5-70) degrees

    Reset ratio 105% typically -

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 43

  • Table 23. Full-scheme distance protection, Mho characteristic ZMOPDIS

    Function Range or value Accuracy

    Number of zones withselectable directions

    5 with selectabledirection

    -

    Minimum operate current (1030)% of IBase 2,0 % of Ir

    Positive sequenceimpedance

    (0.0053000.000) W/phase

    2.0% static accuracyConditions:Voltage range: (0.1-1.1) x UrCurrent range: (0.5-30) x IrAngle: at 0 degrees and 85 degrees

    Reverse positive sequenceimpedance

    (0.0053000.000) /phase

    Impedance reach forphase-to-phase elements

    (0.0053000.000) /phase

    Angle for positivesequence impedance,phase-to-phase elements

    (1090) degrees

    Reverse reach of phase-to-phase loop

    (0.0053000.000) /phase

    Magnitude of earth returncompensation factor KN

    (0.003.00)

    Angle for earthcompensation factor KN

    (-180180) degrees

    Dynamic overreach

  • Table 25. Phase preference logic PPLPHIZ

    Function Range or value Accuracy

    Operate value, phase-to-phase and phase-to-neutral undervoltage

    (10.0 - 100.0)% of UBase 0,5% of Ur

    Reset ratio, undervoltage < 105% -

    Operate value, residualvoltage

    (5.0 - 300.0)% of UBase 0,5% of Ur

    Reset ratio, residualvoltage

    > 95% -

    Operate value, residualcurrent

    (10 - 200)% of IBase 1,0% of Ir for I < Ir

    1,0% of I for I > Ir

    Reset ratio, residualcurrent

    > 95% -

    Timers (0.000 - 60.000) s 0,5% 10ms

    Operating mode No Filter, NoPrefCyclic: 1231c, 1321cAcyclic: 123a, 132a, 213a,231a, 312a, 321a

    Table 26. Power swing detection ZMRPSB

    Function Range or value Accuracy

    Reactive reach (0.10-3000.00) W

    2.0% static accuracyConditions:Voltage range: (0.1-1.1) x UrCurrent range: (0.5-30) x IrAngle: at 0 degrees and 85 degreesResistive reach (0.101000.00)W

    Timers (0.000-60.000) s 0.5% 10 ms

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 45

  • Table 27. Automatic switch onto fault logic, voltage and current based ZCVPSOF

    Parameter Range orvalue

    Accuracy

    Operate voltage, detection of dead line (1100)% ofUBase

    0.5% of Ur

    Operate current, detection of dead line (1100)% ofIBase

    1.0% of Ir

    Delay following dead line detectioninput before Automatic switch onto faultlogic function is automatically turned On

    (0.00060.000) s

    0.5% 10 ms

    Time period after circuit breaker closurein which Automatic switch onto faultlogic function is active

    (0.00060.000) s

    0.5% 10 ms

    Current protection

    Table 28. Instantaneous phase overcurrent protection PHPIOC

    Function Range or value Accuracy

    Operate current (5-2500)% of lBase 1.0% of Ir at I Ir 1.0% of I at I > Ir

    Reset ratio > 95% -

    Operate time 20 ms typically at 0 to 2 x Iset -

    Reset time 25 ms typically at 2 to 0 x Iset -

    Critical impulse time 10 ms typically at 0 to 2 x Iset -

    Operate time 10 ms typically at 0 to 10 x Iset -

    Reset time 35 ms typically at 10 to 0 x Iset -

    Critical impulse time 2 ms typically at 0 to 10 x Iset -

    Dynamic overreach < 5% at t = 100 ms -

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    46 ABB

  • Table 29. Four step phase overcurrent protection OC4PTOC

    Function Setting range Accuracy

    Operate current (5-2500)% of lBase 1.0% of Ir at I Ir 1.0% of I at I > Ir

    Reset ratio > 95% -

    Min. operating current (1-100)% of lBase 1.0% of IrIndependent time delay (0.000-60.000) s 0.5% 10 msMinimum operate timefor inverse characteristics

    (0.000-60.000) s 0.5% 10 ms

    Inverse characteristics,see table 77, table 78 andtable 79

    17 curve types See table 77, table 78 andtable 79

    Operate time,nondirectionalstartfunction

    20 ms typically at 0 to 2 x Iset -

    Reset time, nondirectionalstart function

    25 ms typically at 2 to 0 x Iset -

    Operate time, directionalstart function

    30 ms typically at 0 to 2 x Iset -

    Reset time, directionalstart funciton

    25 ms typically at 2 to 0 x Iset -

    Critical impulse time 10 ms typically at 0 to 2 x Iset -

    Impulse margin time 15 ms typically -

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 47

  • Table 30. Instantaneous residual overcurrent protection EFPIOC

    Function Range or value Accuracy

    Operate current (1-2500)% of lBase 1.0% of Ir at I Ir 1.0% of I at I > Ir

    Reset ratio > 95% -

    Operate time 20 ms typically at 0 to 2 x Iset -

    Reset time 30 ms typically at 2 to 0 x Iset -

    Critical impulse time 10 ms typically at 0 to 2 x Iset -

    Operate time 10 ms typically at 0 to 10 x Iset -

    Reset time 40 ms typically at 10 to 0 x Iset -

    Critical impulse time 2 ms typically at 0 to 10 x Iset -

    Dynamic overreach < 5% at t = 100 ms -

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    48 ABB

  • Table 31. Four step residual overcurrent protection EF4PTOC

    Function Range or value Accuracy

    Operate current (1-2500)% of lBase 1.0% of Ir at I Ir 1.0% of I at I > Ir

    Reset ratio > 95% -

    Operate current fordirectional comparison

    (1100)% of lBase 1.0% of Ir

    Timers (0.000-60.000) s 0.5% 10 msInverse characteristics,see table 77, table 78 andtable 79

    17 curve types See table 77, table 78 andtable 79

    Second harmonic restrainoperation

    (5100)% of fundamental 2.0% of Ir

    Relay characteristic angle (-180 to 180) degrees 2.0 degreesMinimum polarizingvoltage

    (1100)% of UBase 0.5% of Ur

    Minimum polarizingcurrent

    (2-100)% of IBase 1.0% of Ir

    Real part of source Zused for currentpolarization

    (0.50-1000.00) W/phase -

    Imaginary part of sourceZ used for currentpolarization

    (0.503000.00) W/phase -

    Operate time, startfunction

    30 ms typically at 0.5 to 2 x Iset -

    Reset time, start function 30 ms typically at 2 to x Iset -

    Critical impulse time 10 ms typically at 0 to 2 x Iset -

    Impulse margin time 15 ms typically -

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 49

  • Table 32. Sensitive directional residual overcurrent and power protection SDEPSDE

    Function Range or value Accuracy

    Operate level for 3I0cosjdirectional residualovercurrent

    (0.25-200.00)% of lBase At low setting:(2.5-10) mA(10-50) mA

    1.0% of Ir at I Ir 1.0% of I at I > Ir 0.5 mA1.0 mA

    Operate level for 3I03U0 cosj directional residualpower

    (0.25-200.00)% of SBase At low setting:(0.25-5.00)% of SBase

    1.0% of Sr at S Sr 1.0% of S at S > Sr 10% of set value

    Operate level for 3I0 and

    j residual overcurrent(0.25-200.00)% of lBase At low setting:(2.5-10) mA(10-50) mA

    1.0% of Ir at Ir 1.0% of I at I > Ir 0.5 mA1.0 mA

    Operate level for nondirectional overcurrent

    (1.00-400.00)% of lBase At low setting:(10-50) mA

    1.0% of Ir at I Ir 1.0% of I at I > Ir 1.0 mA

    Operate level for nondirectional residualovervoltage

    (1.00-200.00)% of UBase 0.5% of Ur at UUr 0.5% of U at U > Ur

    Residual release currentfor all directional modes

    (0.25-200.00)% of lBase At low setting:(2.5-10) mA(10-50) mA

    1.0% of Ir at I Ir 1.0% of I at I > Ir 0.5 mA 1.0 mA

    Residual release voltagefor all directional modes

    (1.00 - 300.00)% of UBase 0.5% of Ur at UUr 0.5% of U at > Ur

    Reset ratio > 95% -

    Timers (0.000-60.000) s 0.5% 10 msInverse characteristics,see table 77, table 78 andtable 79

    17 curve types See table 77, table 78 andtable 79

    Relay characteristic angleRCA

    (-179 to 180) degrees 2.0 degrees

    Relay open angle ROA (0-90) degrees 2.0 degrees

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    50 ABB

  • Table 32. Sensitive directional residual overcurrent and power protection SDEPSDE,continued

    Function Range or value Accuracy

    Operate time, nondirectional residual overcurrent

    35 ms typically at 0.5 to 2 Iset -

    Reset time, non directinalresidual over current

    40 ms typically at 1.2 to 0 Iset -

    Operate time,nondirectional residualovervoltage

    150 ms typically at 0.8 to 1.5 Uset -

    Reset time,nondirectional residualovervoltage

    60 ms typically at 1.2 to 0.8 Uset -

    Table 33. Time delayed 2-step undercurrent protection UC2PTUC

    Function Setting range Accuracy

    Low-set step of undercurrent limit, ILLow< 5.0-100.0% of Ibasein steps of 0.1%

    2.5 % of Ir

    High-set step of undercurrent limit, ILHigh< 5.0-100.0% of Ibasein steps of 0.1%

    2.5 % of Ir

    Time delayed operation of low-set step, tLow 0.000-60.000 s insteps of 1 ms

    0.5 % 10 ms

    Time delayed operation of high-set step, tHigh 0.000-60.000 s insteps of 1 ms

    0.5 % 10 ms

    Reset ratio > 106% typically

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 51

  • Table 34. Thermal overload protection, one time constant LPTTR

    Function Range or value Accuracy

    Reference current (0-400)% of IBase 1.0% of IrStart temperaturereference

    (0-400)C 1.0C

    Operate time:

    2 2

    2 2lnp

    b

    I It I It - = -

    EQUATION1356 V1 EN (Equation 1)

    I = actual measuredcurrentIp = load current before

    overload occursIb = base current, IBase

    Time constant t = (01000) minutes

    IEC 60255-8, class 5 + 200 ms

    Alarm temperature (0-200)C 2.0% of heat content tripTrip temperature (0-600)C 2.0% of heat content tripReset level temperature (0-600)C 2.0% of heat content trip

    Table 35. Breaker failure protection CCRBRF

    Function Range or value Accuracy

    Operate phase current (5-200)% of lBase 1.0% of Ir at I Ir 1.0% of I at I > Ir

    Reset ratio, phase current > 95% -

    Operate residual current (2-200)% of lBase 1.0% of Ir at I Ir 1.0% of I at I > Ir

    Reset ratio, residual current > 95% -

    Phase current level forblocking of contact function

    (5-200)% of lBase 1.0% of Ir at I Ir 1.0% of I at I > Ir

    Reset ratio > 95% -

    Timers (0.000-60.000) s 0.5% 10 msOperate time for currentdetection

    10 ms typically -

    Reset time for currentdetection

    15 ms maximum -

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    52 ABB

  • Table 36. Stub protection STBPTOC

    Function Range or value Accuracy

    Operating current (1-2500)% of IBase 1.0% of Ir at I Ir 1.0% of I at I > Ir

    Reset ratio > 95% -

    Operating time 20 ms typically at 0 to 2 x Iset -

    Resetting time 25 ms typically at 2 to 0 x Iset -

    Critical impulse time 10 ms typically at 0 to 2 x Iset -

    Impulse margin time 15 ms typically -

    Table 37. Pole discordance protection CCRPLD

    Function Range or value Accuracy

    Operate value, currentunsymmetry level

    (0-100) % 1.0% of Ir

    Reset ratio >95% -

    Operate current, currentrelease level

    (0100)% of IBase 1.0% of Ir

    Time delay (0.000-60.000) s 0.5% 10 ms

    Table 38. Broken conductor check BRCPTOC

    Function Range or value Accuracy

    Minimum phase currentfor operation

    (5100)% of IBase 1.0% of Ir

    Unbalance currentoperation

    (50-90)% of maximumcurrent

    1.0% of Ir

    Timer (0.00-6000.00) s 0.5% 10 ms

    Operate time for startfunction

    25 ms typically -

    Reset time for startfunction

    15 ms typically -

    Critical impulse time 15 ms typically -

    Impulse margin time 10 ms typically -

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 53

  • Table 39. Directional over/underpower protection GOPPDOP/GUPPDUP

    Function Range or value Accuracy

    Power level (0.0500.0)% of Sbase At low setting:(0.5-2.0)% of Sbase(2.0-10)% of Sbase

    1.0% of Sr at S < Sr 1.0% of S at S > Sr < 50% of set value< 20% of set value

    Characteristic angle (-180.0180.0) degrees 2 degrees

    Timers (0.010 - 6000.000) s 0.5% 10 ms

    Table 40. Negative sequence based overcurrent function DNSPTOC

    Function Range or value Accuracy

    Operate current (2.0 - 5000.0) % of IBase 1.0% of Ir at I Ir

    Reset ratio > 95 % -

    Low voltage level for memory (0.0 - 5.0) % of UBase < 0,5% of Ur

    Relay characteristic angle (-180 - 180) degrees 2,0 degrees

    Relay operate angle (1 - 90) degrees 2,0 degrees

    Timers (0.00 - 6000.00) s 0.5% 10 ms

    Operate time, nondirectional 25 ms typically at 0 to 2 x Iset15 ms typically at 0 to 10 x Iset

    -

    Reset time, nondirectional 30 ms typically at 2 to 0 x Iset -

    Operate time, directional 25 ms typically at 0.5 to 2 xIset15 ms typically at 0 to 10 x Iset

    -

    Reset time, directional 30 ms typically at 2 to 0 x Iset -

    Critical impulse time 10 ms typically at 0 to 2 x Iset2 ms typically at 0 to 10 x Iset

    -

    Impulse margin time 15 ms typically -

    Dynamic overreach < 10% at t = 300 ms -

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    54 ABB

  • Voltage protection

    Table 41. Two step undervoltage protection UV2PTUV

    Function Range or value Accuracy

    Operate voltage, low andhigh step

    (1100)% of UBase 0.5% of Ur

    Reset ratio Ur

    Reset ratio >95% -

    Inverse time characteristicsfor low and high step, seetable 81

    - See table 81

    Definite time delay, step 1 (0.00 - 6000.00) s 0.5% 10 ms

    Definite time delays, step 2 (0.000-60.000) s 0.5% 10 ms

    Minimum operate time,Inverse characteristics

    (0.000-60.000) s 0.5% 10 ms

    Operate time, start function 20 ms typically at 0 to 2 x Uset -

    Reset time, start function 25 ms typically at 2 to 0 x Uset -

    Critical impulse time 10 ms typically at 0 to 2 x Uset -

    Impulse margin time 15 ms typically -

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 55

  • Table 43. Two step residual overvoltage protection ROV2PTOV

    Function Range or value Accuracy

    Operate voltage, step 1 (1-200)% of Ubase 0.5% of Ur at U < Ur 0.5% of U at U > Ur

    Operate voltage, step 2 (1100)% of Ubase 0.5% of Ur at U < Ur % of U at U > Ur

    Reset ratio >95% -

    Inverse time characteristicsfor low and high step, seetable 82

    - See table 82

    Definite time setting, step 1 (0.006000.00) s 0.5% 10 ms

    Definite time setting, step 2 (0.00060.000) s 0.5% 10 ms

    Minimum operate time forstep 1 inverse characteristic

    (0.000-60.000) s 0.5% 10 ms

    Operate time, start function 20 ms typically at 0 to 2 x Uset -

    Reset time, start function 25 ms typically at 2 to 0 x Uset -

    Critical impulse time 10 ms typically at 0 to 2 x Uset -

    Impulse margin time 15 ms typically -

    Table 44. Loss of voltage check LOVPTUV

    Function Range or value Accuracy

    Operate voltage (0100)% of Ubase 0.5% of Ur

    Reset ratio

  • Frequency protection

    Table 45. Under frequency protection SAPTUF

    Function Range or value Accuracy

    Operate value, start function (35.00-75.00) Hz 2.0 mHz

    Operate value, restore frequency (45 - 65) Hz 2.0 mHz

    Operate time, start function 200 ms typically at fr to

    0.99 x fset

    -

    Reset time, start function 50 ms typically at 1.01 xfset to fr

    -

    Timers (0.000-60.000)s 0.5% + 10 ms

    Table 46. Over frequency protection SAPTOF

    Function Range or value Accuracy

    Operate value, start function (35.00-75.00) Hz 2.0 mHz at symmetricalthree-phase voltage

    Operate time, start function 200 ms typically at fr to

    1.01 x fset

    -

    Reset time, start function 50 ms typically at 1.01 xfset to fr

    -

    Timer (0.000-60.000)s 0.5% + 10 ms

    Table 47. Rate-of-change frequency protection SAPFRC

    Function Range or value Accuracy

    Operate value, start function (-10.00-10.00) Hz/s 10.0 mHz/s

    Operate value, restore enablefrequency

    (45.00 - 65.00) Hz

    Timers (0.000 - 60.000) s 0.5% + 10 ms

    Operate time, start function 100 ms typically -

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 57

  • Secondary system supervision

    Table 48. Current circuit supervision CCSRDIF

    Function Range or value Accuracy

    Operate current (5-200)% of Ir 10.0% of Ir at I Ir 10.0% of I at I > Ir

    Block current (5-500)% of Ir 5.0% of Ir at I Ir 5.0% of I at I > Ir

    Table 49. Fuse failure supervision SDDRFUF

    Function Range or value Accuracy

    Operate voltage, zero sequence (1-100)% of UBase 0.5% of Ur

    Operate current, zero sequence (1100)% of IBase 1.0% of Ir

    Operate voltage, negativesequence

    (1100)% of UBase 0.5% of Ur

    Operate current, negativesequence

    (1100)% of IBase 1.0% of Ir

    Operate voltage change level (1100)% of UBase 5.0% of Ur

    Operate current change level (1100)% of IBase 5.0% of Ir

    Table 50. Breaker close/trip circuit monitoring TCSSCBR

    Function Range or value Accuracy

    Operate time delay (0.020 - 300.000)s 0,5% 10ms

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    58 ABB

  • Control

    Table 51. Synchronizing, synchrocheck check and energizing check SESRSYN

    Function Range or value Accuracy

    Phase shift, jline - jbus (-180 to 180) degrees -Voltage ratio, Ubus/Uline 0.20-5.00 -

    Frequency difference limit betweenbus and line

    (0.003-1.000) Hz 2.0 mHz

    Phase angle difference limitbetween bus and line

    (5.0-90.0) degrees 2.0 degrees

    Voltage difference limit betweenbus and line

    (2.0-50.0)% of Ubase 0.5% of Ur

    Time delay output for synchrocheck (0.000-60.000) s 0.5% 10 ms

    Time delay for energizing check (0.000-60.000) s 0.5% 10 ms

    Operate time for synchrocheckfunction

    160 ms typically -

    Operate time for energizing function 80 ms typically -

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 59

  • Table 52. Autorecloser SMBRREC

    Function Range or value Accuracy

    Number of autoreclosing shots 1 - 5 -

    Autoreclosing open time:shot 1 - t1 3Ph

    (0.000-60.000) s

    0.5% 10 ms

    shot 2 - t2 3Phshot 3 - t3 3Phshot 4 - t4 3Phshot 5 - t5 3Ph

    (0.00-6000.00) s

    Autorecloser maximum wait time for sync (0.00-6000.00) s

    Maximum trip pulse duration (0.000-60.000) s

    Inhibit reset time (0.000-60.000) s

    Reclaim time (0.00-6000.00) s

    Minimum time CB must be closed before ARbecomes ready for autoreclosing cycle

    (0.00-6000.00) s

    CB check time before unsuccessful (0.00-6000.00) s

    Wait for master release (0.00-6000.00) s

    Wait time after close command beforeproceeding to next shot

    (0.000-60.000) s

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    60 ABB

  • Scheme communication

    Table 53. Scheme communication logic for distance or overcurrent protection ZCPSCH

    Function Range or value Accuracy

    Scheme type OffIntertripPermissive URPermissive ORBlocking

    -

    Co-ordination time forblocking communicationscheme

    (0.000-60.000) s 0.5% 10 ms

    Minimum duration of acarrier send signal

    (0.000-60.000) s 0.5% 10 ms

    Security timer for loss ofguard signal detection

    (0.000-60.000) s 0.5% 10 ms

    Operation mode ofunblocking logic

    OffNoRestartRestart

    -

    Table 54. Current reversal and weak-end infeed logic for distance protectionZCRWPSCH

    Function Range or value Accuracy

    Operating mode of WEIlogic

    OffEchoEcho & Trip

    -

    Detection level phase-to-neutral and phase-to-phase voltage

    (10-90)% of UBase 0.5% of Ur

    Reset ratio

  • Table 55. Scheme communication logic for residual overcurrent protection ECPSCH

    Function Range or value Accuracy

    Scheme type OffIntertripPermissive URPermissive ORBlocking

    -

    Communication schemecoordination time

    (0.000-60.000) s 0.5% 10 ms

    Minimum duration of asend signal

    (0.000-60.000) s 0.5% 10 ms

    Security timer for loss ofcarrier guard detection

    (0.000-60.000) s 0.5% 10 ms

    Table 56. Current reversal and weak-end infeed logic for residual overcurrent protectionECRWPSCH

    Function Range or value Accuracy

    Operating mode of WEIlogic

    OffEchoEcho & Trip

    -

    Operate voltage 3Uo for

    WEI trip

    (5-70)% of UBase 1.0% of Ur

    Reset ratio >95% -

    Operate time for currentreversal logic

    (0.000-60.000) s 0.5% 10 ms

    Delay time for currentreversal

    (0.000-60.000) s 0.5% 10 ms

    Coordination time forweak-end infeed logic

    (0.00060.000) s 0.5% 10 ms

    Logic

    Table 57. Tripping logic SMPPTRC

    Function Range or value Accuracy

    Trip action 3-ph -

    Minimum trip pulse length (0.000-60.000) s 0.5% 10 ms

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    62 ABB

  • Table 58. Configurable logic blocks

    Logic block Quantity withcycle time

    Range or value Accuracy

    5 ms 20ms

    100ms

    LogicAND 60 60 160 - -

    LogicOR 60 60 160 - -

    LogicXOR 10 10 20 - -

    LogicInverter 30 30 80 - -

    LogicSRMemory 10 10 20 - -

    LogicGate 10 10 20 - -

    LogicPulseTimer 10 10 20 (0.00090000.000) s 0.5% 10 ms

    LogicTimerSet 10 10 20 (0.00090000.000) s 0.5% 10 ms

    LogicLoopDelay 10 10 20

    Monitoring

    Table 59. Measurements CVMMXN

    Function Range or value Accuracy

    Frequency (0.95-1.05) fr 2.0 mHzConnected current (0.2-4.0) Ir 0.5% of Ir at I Ir

    0.5% of I at I > Ir

    Table 60. Event counter CNTGGIO

    Function Range or value Accuracy

    Counter value 0-10000 -

    Max. count up speed 10 pulses/s -

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 63

  • Table 61. Disturbance report DRPRDRE

    Function Range or value Accuracy

    Current recording - 1,0% of Ir at I Ir 1,0% of I at I > Ir

    Voltage recording - 1,0% of Ur at U

    Ur 1,0% of U at U >Ur

    Pre-fault time (0.053.00) s -

    Post-fault time (0.110.0) s -

    Limit time (0.58.0) s -

    Maximum number of recordings 100 -

    Time tagging resolution 1 ms See timesynchronizationtechnical data

    Maximum number of analog inputs 30 + 10 (external +internally derived)

    -

    Maximum number of binary inputs 96 -

    Maximum number of phasors in the TripValue recorder per recording

    30 -

    Maximum number of indications in adisturbance report

    96 -

    Maximum number of events in the Eventrecording per recording

    150 -

    Maximum number of events in the Eventlist

    1000, first in - first out -

    Maximum total recording time (3.4 srecording time and maximum number ofchannels, typical value)

    340 seconds (100recordings) at 50 Hz, 280seconds (80 recordings)at 60 Hz

    -

    Sampling rate 1 kHz at 50 Hz1.2 kHz at 60 Hz

    -

    Recording bandwidth (5-300) Hz -

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    64 ABB

  • Table 62. Fault locator LMBRFLO

    Function Value or range Accuracy

    Reactive and resistivereach

    (0.001-1500.000) /phase 2.0% static accuracy 2.0% degrees static angularaccuracyConditions:Voltage range: (0.1-1.1) x UrCurrent range: (0.5-30) x Ir

    Phase selection According to input signals -

    Maximum number of faultlocations

    100 -

    Table 63. Event list DRPRDRE

    Function Value

    Buffer capacity Maximum number of events inthe list

    1000

    Resolution 1 ms

    Accuracy Depending on timesynchronizing

    Table 64. Indications DRPRDRE

    Function Value

    Buffer capacity Maximum number of indications presentedfor single disturbance

    96

    Maximum number of recorded disturbances 100

    Table 65. Event recorder DRPRDRE

    Function Value

    Buffer capacity Maximum number of events in disturbance report 150

    Maximum number of disturbance reports 100

    Resolution 1 ms

    Accuracy Depending ontimesynchronizing

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 65

  • Table 66. Trip value recorder DRPRDRE

    Function Value

    Buffer capacity

    Maximum number of analog inputs 30

    Maximum number of disturbance reports 100

    Table 67. Disturbance recorder DRPRDRE

    Function Value

    Buffer capacity Maximum number of analog inputs 40

    Maximum number of binary inputs 96

    Maximum number of disturbance reports 100

    Maximum total recording time (3.4 s recording time andmaximum number of channels, typical value)

    340 seconds (100 recordings)at 50 Hz280 seconds (80 recordings) at60 Hz

    Table 68. Station battery supervision SPVNZBAT

    Function Range or value Accuracy

    Lower limit for the batteryterminal voltage

    (60-140) % of Ubat 0,5% of set battery voltage

    Reset ratio, lower limit 95 % -

    Timers (0.000-60.000) s 0.5% 10 ms

    Table 69. Insulation gas monitoring function SSIMG

    Function Range or value Accuracy

    Pressure alarm 0.00-25.00 -

    Pressure lockout 0.00-25.00 -

    Temperature alarm -40.00-200.00 -

    Temperature lockout -40.00-200.00 -

    Timers (0.000-60.000) s 0.5% 10 ms

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    66 ABB

  • Table 70. Insulation liquid monitoring function SSIML

    Function Range or value Accuracy

    Alarm, oil level 0.00-25.00 -

    Oil level lockout 0.00-25.00 -

    Temperature alarm -40.00-200.00 -

    Temperature lockout -40.00-200.00 -

    Timers (0.000-60.000) s 0.5% 10 ms

    Table 71. Circuit breaker condition monitoring SSCBR

    Function Range or value Accuracy

    RMS current setting belowwhich energy accumulationstops

    (5.00-500.00) A 1.0% of Ir at IIr 1.0% of I at I>Ir

    Alarm level for accumulatedenergy

    0.00-20000.00 < 5.0% of set value

    Lockout limit foraccumulated energy

    0.00-20000.00 < 5.0% of set value

    Alarm levels for open andclose travel time

    (0-200) ms 0.5% 10ms

    Setting of alarm for springcharging time

    (0.00-60.00) s 0.5% 10ms

    Time delay for gas pressurealarm

    (0.00-60.00) s 0.5% 10ms

    Time delay for gas pressurelockout

    (0.00-60.00) s 0.5% 10ms

    Metering

    Table 72. Pulse counter PCGGIO

    Function Setting range Accuracy

    Cycle time for report ofcounter value

    (13600) s -

    Table 73. Function for energy calculation and demand handling ETPMMTR

    Function Range or value Accuracy

    Energy metering kWh Export/Import,kvarh Export/Import

    Input from MMXU. No extra errorat steady load

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 67

  • Hardware

    IED

    Table 74. Degree of protection of flush-mounted IED

    Description Value

    Front side IP 40

    Rear side, connection terminals IP 20

    Table 75. Degree of protection of the LHMI

    Description Value

    Front and side IP 42

    Dimensions

    Table 76. Dimensions

    Description Type Value

    Width half 19" 220 mm

    Height half 19"

    Depth half 19" 249.5 mm

    Weight half 19" box

  • Inverse time characteristics

    Table 77. ANSI Inverse time characteristics

    Function Range or value Accuracy

    Operating characteristic:

    ( )1= + - P

    At B k

    I

    EQUATION1249-SMALL V1 EN (Equation 2)

    I = Imeasured/Iset

    k = 0.05-999 in steps of 0.01 unlessotherwise stated

    -

    ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 ANSI/IEEE C37.112,class 5 + 40 ms

    ANSI Very inverse A=19.61, B=0.491, P=2.0

    ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46

    ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02

    ANSI Long Time ExtremelyInverse

    A=64.07, B=0.250, P=2.0

    ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0

    ANSI Long Time Inverse k=(0.01-1.20) in steps of 0.01A=0.086, B=0.185, P=0.02

    Table 78. IEC Inverse time characteristics

    Function Range or value Accuracy

    Operating characteristic:

    ( )1= - P

    At kI

    EQUATION1251-SMALL V1 EN (Equation 3)

    I = Imeasured/Iset

    k = (0.05-1.10) in steps of 0.01 -

    IEC Normal Inverse A=0.14, P=0.02 IEC 60255-3, class 5+ 40 ms

    IEC Very inverse A=13.5, P=1.0

    IEC Inverse A=0.14, P=0.02

    IEC Extremely inverse A=80.0, P=2.0

    IEC Short time inverse A=0.05, P=0.04

    IEC Long time inverse A=120, P=1.0

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 69

  • Table 79. RI and RD type inverse time characteristics

    Function Range or value Accuracy

    RI type inverse characteristic

    10.2360.339

    = -

    t k

    IEQUATION1137-SMALL V1 EN (Equation 4)

    I = Imeasured/Iset

    k=(0.05-999) in steps of 0.01 IEC 60255-3, class 5+ 40 ms

    RD type logarithmic inversecharacteristic

    5.8 1.35= - tIInk

    EQUATION1138-SMALL V1 EN (Equation 5)

    I = Imeasured/Iset

    k=(0.05-1.10) in steps of 0.01 IEC 60255-3, class 5+ 40 ms

    Table 80. Inverse time characteristics for Two step undervoltage protection UV2PTUV

    Function Range or value Accuracy

    Type A curve:

    = < -

    t

    kU U

    UEQUATION1436-SMALL V1 EN (Equation 8)

    U> = UsetU = Umeasured

    k = (0.05-1.10) in steps of0.01

    Class 5 +40 ms

    Type B curve:

    2.0480

    32 0.5 0.035=

    - > - ->

    tk

    U UU

    EQUATION1437-SMALL V1 EN (Equation 9)

    k = (0.05-1.10) in steps of0.01

    Type C curve:

    3.0480

    32 0.5 0.035=

    - > - ->

    tk

    U UU

    EQUATION1438-SMALL V1 EN (Equation 10)

    k = (0.05-1.10) in steps of0.01

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 71

  • Table 82. Inverse time characteristics for Two step residual overvoltage protectionROV2PTOV

    Function Range or value Accuracy

    Type A curve:

    = - >>

    t

    kU U

    UEQUATION1436-SMALL V1 EN (Equation 11)

    U> = UsetU = Umeasured

    k = (0.05-1.10) insteps of 0.01

    Class 5 +40 ms

    Type B curve:

    2.0480

    32 0.5 0.035=

    - > - ->

    tk

    U UU

    EQUATION1437-SMALL V1 EN (Equation 12)

    k = (0.05-1.10) insteps of 0.01

    Type C curve:

    3.0480

    32 0.5 0.035=

    - > - ->

    tk

    U UU

    EQUATION1438-SMALL V1 EN (Equation 13)

    k = (0.05-1.10) insteps of 0.01

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    72 ABB

  • 20. OrderingGuidelinesCarefully read and follow the set of rules to ensure problem-free order management.Please refer to the available functions table for included application functions.

    To obtain the complete ordering code, please combine code from the tables, as given in the example below.

    Exemple code: REL650*1.0-A01X00-X00-B1A5-A-A-SA-A-RA3-AAXX-A. Using the code of each position #1-11specified as REL650*1-2 2-3-4 4-5-6-7 7-8-9 9-10 10 10 10-11

    # 1 - 2 - 3 - 4 - 5 6 - 7 - 8 - 9 - 10 - 11

    REL650* - - - - - . - - .

    Posi

    tion

    SOFTWARE #1 Notes and Rules

    Version number

    Version no 1.0

    Selection for position #1.

    Configuration alternatives #2 Notes and Rules

    Single breaker, 3-phase tripping, quadrilateral A01

    Single breaker, 3-phase tripping, mho A05

    ACT configuration

    ABB standard configuration X00

    Selection for position #2.

    Software options #3 Notes and Rules

    No option X00

    Selection for postition #3

    First HMI language #4 Notes and Rules

    English IEC B1

    Selection for position #4.

    Additional HMI language #4

    No second HMI language X0

    Chinese A5

    Selection for position #4.

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 73

  • Casing #5 Notes and Rules

    Rack casing, 6 U 1/2 x 19" A

    Selection for position #5.

    Mounting details with IP40 of protectionfrom the front

    #6 Notes and Rules

    No mounting kit included X

    Rack mounting kit for 6 U 1/2 x 19" A

    Wall mounting kit for 6U 1/2 x 19" D

    Flush mounting kit for 6U 1/2 x 19" E

    Rear wall mounting kit 6U 1/2 x 19" G

    Selection for position #6.

    Connection type for Power supply, Input/output and Communication modules

    #7 Notes and Rules

    Compression terminals S

    Ringlug terminals R

    Power supply

    Slot position:

    pPSM

    100-240V AC, 110-250V DC, 9BO A

    48-125V DC, 9BO B

    Selection for position #7.

    Human machine interface #8 Notes and Rules

    Local human machine interface, OL3000, IEC6U 1/2 x 19", Basic

    A

    Detached LHMI

    No detached mounting of LHMI X0

    Detached mounting of LHMI incl. ethernet cable, 1m B1

    Detached mounting of LHMI incl. ethernet cable, 2m B2

    Detached mounting of LHMI incl. ethernet cable, 3m B3

    Detached mounting of LHMI incl. ethernet cable, 4m B4

    Detached mounting of LHMI incl. ethernet cable, 5m B5

    Selection for position #8.

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    74 ABB

  • Connection type for Analog modules #9 Notes and Rules

    Compression terminals S

    Ringlug terminals R

    Analog system

    Slot position: p2

    Transformer module, 4I, 1/5A+1I, 0.1/0.5A+5U,100/220V

    A3

    Selection for position #9.

    Binary input/output module #10 Notes and Rules

    Slot position (rear view) p3

    p4

    p5

    p6

    Available slots in 1/2 case

    No board in slot X X

    Binary input/output module 9 BI, 3 NOTrip, 5 NO Signal, 1 CO Signal

    A A A A

    Selection for position #10. A A

    Communication and processing module #11 Notes and Rules

    Slot position (rear view)pCO

    M

    14BI, IRIG-B, Ethernet, LC optical D

    Selection for position #11.

    Accessories

    Configuration and monitoring tools

    Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA

    LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA

    LED Label special paper Letter, 1 pc Quantity: 1MRK 002 038-DA

    Manuals

    Note: One (1) IED Connect CD containing user documentation (Operation manual, Technical manual,Installation manual, Commissioning manual, Application manual, Communication protocol manual,DNP, Communication protocol manual, IEC61850, Type test certificate, Engineering manual and Pointlist manual, DNP3, Connectivity packages and LED label template is always included for each IED.

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 75

  • Rule: Specify additional quantity of IED Connect CD requested

    User documentation Quantity: 1MRK 003 500-AA

    Rule: Specify the number of printed manuals requested

    Operation manual IEC Quantity: 1MRK 500 088-UEN

    Technical manual IEC Quantity: 1MRK 506 304-UEN

    Commissioning manual IEC Quantity: 1MRK 506 307-UEN

    Application manual IEC Quantity: 1MRK 506 305-UEN

    Communication protocol manual, DNP3 Quantity: 1MRK 511 224-UEN

    Communication protocol manual, IEC 61850 Quantity: 1MRK 511 205-UEN

    Engineering manual Quantity: 1MRK 511 206-UEN

    Installation manual Quantity: 1MRK 514 013-UEN

    Point list manual, DNP3 Quantity: 1MRK 511 225-UEN

    Reference information

    For our reference and statistics we would be pleased to be provided with the following application data:

    Country: End user:

    Station name: Voltage level: kV

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    76 ABB

  • Related documents

    Documents related to REL650 Identity number

    Commissioning manual 1MRK 506 307-UEN

    Technical manual 1MRK 506 304-UEN

    Application manual 1MRK 506 305-UEN

    Product Guide, configured 1MRK 506 308-BEN

    Type test certificate 1MRK 506 308-TEN

    Documents related to Identity number

    Operation manual 1MRK 500 088-UEN

    Communication protocol manual, DNP3 1MRK 511 224-UEN

    Communication protocol manual, IEC 61850 1MRK 511 205-UEN

    Engineering manual 1MRK 511 206-UEN

    Installation manual 1MRK 514 013-UEN

    Point list manual, DNP3 1MRK 511 225-UEN

    Latest versions of the described documentation can be found onwww.abb.com/substationautomation

    Line distance protection REL650 1MRK 506 308-BEN AProduct version: 1.0 Issued: February 2010

    ABB 77

  • 78

  • Contact us

    ABB ABSubstation Automation ProductsSE-721 59 Vsters, SwedenPhone +46 (0) 21 34 20 00Fax +46 (0) 21 14 69 18www.abb.com/substationautomation

    1MRK

    506 3

    08-B

    EN A

    Co

    pyrig

    ht 20

    10 AB

    B. All

    rights

    rese

    rved.

    ContentsDescriptionApplicationAvailable functionsImpedance protectionCurrent protectionVoltage protectionFrequency protectionSecondary system supervisionControlScheme communicationLogicMonitoringMeteringHuman Machine interfaceBasic IED functionsStation communicationHardware descriptionConnection diagramsTechnical dataOrdering