Technical Data TD013001ENEffective July 2016Supersedes August 2015 Series NRX
ContentsDescription Page
General wiring notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Figure 1 . Zone interlock wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Figure 2 . Ground fault residual 3-phase, 4-wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Figure 3 . Source ground fault sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Figure 4 . Zero sequence ground fault sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Figure 5 . PXR alarm wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Figure 6 . Maintenance mode wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Figure 7 . INCOM communication module (ICAM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Figure 8 . MODBUS communication module (MCAM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Figure 9 . PROFIBUS communication module (PCAM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Figure 10 . ETHERNET communication module (ECAM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Figure 11 . Communication control (SR and ST wiring) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Figure 12 . Under voltage release . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Figure 13 . Circuit breaker control – type NF frame/IZMX16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Figure 14 . Circuit breaker control – type RF frame/IZMX40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Figure 15 . Series NRX mounted breaker (with external PT module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Figure 16 . Typical breaker master connection diagram – type NF frame/IZMZ16 . . . . . . . . . . . . . . . . . . 18Figure 17 . Typical breaker master connection diagram – type RF frame/IZMX40 . . . . . . . . . . . . . . . . . . . 19
Series NRX with PXR circuit breaker wiring diagrams
Instructions apply to:
UL489 series NRX RF frame IEC IZMX40
UL1066/ANSI, UL489 series NRX NF frame IEC IZMX16
2
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
General wiring notes1 . Each contact block on the Secondary Terminal Block contains
four independent contacts (Figure A) . A possible 14 terminal blocks will provide 56 contact points for the type NF frame . A possible 24 terminal blocks will provide 96 contact points for the type RF frame .
Figure A. Secondary terminal blocks.
2 . Drawout circuit breakers use Style 67C3246 contact blocks that mount onto an insulated support frame on the cassette .
3 . Fixed mounted circuit breakers use Style 67C3247 contact blocks that mount onto an insulated support frame . The cus-tomer tension connectors are at an angle .
4 . Customer wiring is done using a tension clamp termination on each contact .
5 . Contact blocks are individually mounted and hence contact positions may be empty depending on accessories and options ordered .
6 . The tension clamp terminals will support solid or flexible conduc-tors, #12/4 mm2 through #26/0 .5 mm2 AWG wire and are rated for 600 V, 10 A .
7 . The recommended wire strip length is 10-12 mm (0 .39 - 0 .47 in) .
8 . The tension clamp terminals also support finely stranded conduc-tors with wire-end ferrules and plastic collars DIN 46228/4, rated connection .
9 . The two-point blue plugs house two female crimp contacts (Style 67C3249), with the odd assigned numbers having the coded rib feature on the blue plug (Figure B) .
ote:N Note that the connector plug must be oriented as shown in Figure B before making the connection .
10 . For secondary contacts, odd numbers should be treated as posi-tive voltage for any accessory . This will not apply for AC ratings .
11 . Reference tool for removing leads from secondary contact con-nector plug – 68D3288H01 Extraction Tool (Figure C) .
Table 1. Customer wiring details.
Type of conductor Tension clamp connection
Recommended strip length or ferrule length
Solid cross section (min - max) 0.5 - 4 mm² 10 - 12 mm (0.39 - 0.47 in.)
Flexible cross section (min - max)
0.5 - 4 mm² 10 - 12 mm (0.39 - 0.47 in.)
American wire gauge - AWG (min - max)
26 - 12 AWG 10 - 12 mm (0.39 - 0.47 in.)
Flexible cross section with wire end ferrule without plastic sleeve - DIN 46228/1 (min - max)
0.5 - 2.5 mm² (26 - 14 AWG)
10 - 12 mm (0.39 - 0.47 in.)
Flexible cross section with wire end furrule with plastic sleeve - DIN 46228/4 (min - max)
0.5 - 1.5 mm² (26 - 16 AWG)
16 - 18 mm (0.63 - 0.71 in.)
Gauge to IEC 60947-1. A3
Figure B. Accessory plug and crimp contact.
Figure C. Extraction tool in use.
Fixed terminal block
Drawout terminal block
Secondary lead
Connector Plug
Terminal extraction tool
3
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
2423
21
PXR
2423
21
PXR
2423
21
PX
R
2423
21
PX
R
ote
s:N 1 .
Tw
iste
d to
geth
er A
WG
#14
to
#20
copp
er w
ire .
Rou
te t
he z
one
inte
rlock
wiri
ng
sepa
rate
fro
m p
ower
con
duct
ors .
D
O N
OT
GR
OU
ND
any
zon
e in
terlo
ck w
iring
.
2 .
The
max
imum
dis
tanc
e be
twee
n tw
o fa
rthe
st b
reak
ers
on d
iffer
ent
zone
s (f
rom
the
Z o
ut d
owns
trea
m t
o th
e Z i
n up
stre
am t
erm
inal
s) is
250
feet
(75
m) .
3 .
A m
axim
um o
f 20
bre
aker
s m
ay b
e co
ntai
ned
in p
aral
lel i
n on
e zo
ne .
4 .
Prov
ide
a se
lf in
terlo
ckin
g ju
mpe
r (o
n zo
ne 3
), if
coor
dina
tion
is d
esire
d w
ith o
ther
do
wns
trea
m b
reak
ers
not
prov
idin
g th
e Zo
ne In
terlo
ck fe
atur
e .
Fig
ure
1. Z
on
e in
terl
ock
wir
ing
.
4
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
Figure 2.
PXR
Series NRX Circuit Breaker
11
12
Ground fault residual 3-phase, 4-wire.
otes:N
1 . Sensor is customer wired to sense neutral currents . This is required for 3-phase, 4-wire residual ground fault (applicable for trip units having G protection) .
2 .
Series NRX frame Ground (earth) sensing method Sensor style IZMX type coding
NFResidual
5721B76G12 IZMX-CT16-N
RF 70C1718G11 IZMX-CT40-N
5
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
Figure 3. Source ground fault sensing.
PXR
Series NRX Circuit Breaker
ExternalSensor
ote:N
1 . Sensor NFGFSKIT (IZMX-EFS) is used to sense and detect ground fault currents . The part number is 70C1527G04 .
6
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
Figure 4.
Series NRX Circuit Breaker
PXR
Zero sequence ground fault sensing.
ote:N
1 . Sensor NFGFSKIT (IZMX-EFS) is used to sense and detect ground fault currents of 3-wire or 4-wire . The part number is 70C1527G04 .
7
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
Figure 5.
Series NRX Circuit Breaker
24VDC ±10%
13
14� � �
�
15
16
19
20
ALM-Com ALM1ALM2 ALM3
Control Power
PXR alarm wiring.
otes:N
1 . For the PXR20/25, the Alarm 1 is for Remote Indication/ Maintenance Mode indication . Contact rating 1 A @ 120 Vac, 1 A @ 24 Vdc, and 0 .5 A @ 230 Vac .
2 . For the PXR20/25, the Alarm 2 is for High Load alarm/Ground Fault alarm . Contact rating 1 A @ 120 Vac, 1 A @ 24 Vdc, and 0 .5 A @ 230 Vac .
3 . For the PXR20/25, the Alarm 3 is for Trip N .O . contact . Contact rating 1 A @ 120 Vac, 1 A @ 24 Vdc, and 0 .5 A @ 230 Vac .
4 . If the control voltage is +24 Vdc, the trip unit should be fed from a separate, galvanically isolated + 24 V voltage dc supply .
8
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
Ser
ies
NR
X C
ircu
it B
reak
erS
erie
s N
RX
Cir
cuit
Bre
aker
Alt
ern
ate
Cu
sto
mer
Wir
ing
(p
arti
al)
Mai
nte
nan
ce M
od
e W
irin
g
1319
22
2214
2020
ote
s:N 1 .
P
XR
20/2
5 ca
n lo
cally
be
plac
ed in
mai
nten
ance
mod
e vi
a a
two
posi
tion
switc
h lo
cate
d on
the
trip
uni
t . T
he f
unct
ion
can
be a
rmed
via
a r
emot
e sw
itch
as s
how
n .
In a
dditi
on, t
he f
unct
ion
can
be a
ctiv
ated
via
com
mun
icat
ion
mod
ules
. A
blu
e LE
D o
n th
e P
XR
ver
ifies
the
PX
R r
elea
se in
mai
nten
ance
mod
e .
2 .
The
reco
mm
ende
d se
lect
or s
witc
h fo
r th
is lo
w v
olta
ge a
pplic
atio
n is
Eat
on p
art
num
ber
1025
0T13
3-2E
whi
ch in
clud
es a
con
tact
blo
ck r
ated
for
logi
c le
vel a
nd
corr
osiv
e us
e .
3 .
The
max
imum
leng
th o
f th
is w
iring
to
rem
otel
y ar
m t
he s
witc
h (o
r al
tern
ate
rela
y co
ntac
t) is
9 .7
8 fe
et (3
m) .
Use
#20
AW
G w
ire o
r la
rger
.
4 .
A r
emot
e S
tack
Lig
ht A
nnun
ciat
or p
anel
or
othe
r re
mot
e in
dica
tion
devi
ce c
an b
e co
nnec
ted
to v
erify
tha
t P
XR
is in
the
mai
nten
ance
mod
e .
5 .
The
rela
y in
the
PX
R r
elea
se m
akes
whe
n in
mai
nten
ance
mod
e .
Con
tact
is r
ated
1 A
@ 1
20 V
ac, 1
A @
24
Vdc
, an
d 0 .
5 A
@ 2
30 V
ac .
6 .
The
PX
R r
elea
se c
an a
lso
be p
lace
d re
mot
ely
in it
s m
aint
enan
ce m
ode
via
a ge
nera
l pur
pose
rel
ay (i
ce c
ube
type
with
logi
c le
vel c
onta
cts)
and
act
ivat
ed b
y a
rem
ote
cont
rol s
witc
h . A
rec
omm
ende
d ty
pe is
IDE
C r
elay
RY
22 .
Cho
ose
the
volta
ge a
s de
sire
d .
7 .
If a
com
mun
icat
ion
mod
ule
is u
sed,
see
Fig
ures
6, 7
8, a
nd 9
for
diff
eren
t w
iring
. Th
e co
mm
unic
atio
n m
odul
e w
ill r
equi
re 2
4 V
dc p
ower
and
will
pro
vide
isol
ated
po
wer
to
the
PX
R r
elea
se
in t
he c
ircui
t br
eake
r . If
a c
omm
unic
atio
n m
odul
e is
not
use
d, t
he P
XR
rel
ease
tha
t re
quire
s au
xilia
ry v
olta
ge f
or a
larm
s w
hich
sho
uld
be fe
d fr
om a
gal
vani
cally
isol
ated
, 24
Vdc
sup
ply .
Fig
ure
6. M
ain
ten
ance
mo
de
wir
ing
.
9
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
otes:N
1 . The Series NRX communication module is a separate device that mounts on a DIN rail bracket . A separate harness is required to remotely mount and wire the module .
2 . The communications module voltage requirement is 24 Vdc ± 10% and should be sourced from a high quality supply (6 watts is the burden of the CAM) .
3 . INCOM communication cable is a two conductor with shield type wire in “daisy chain” configuration . The recommended cable (Belden “Blue Hose” # 9643 or equivalent) has a twisted-pair of wires (# 20 AWG stranded 7 x 28 conductors with PVC insulation) having an aluminum/mylar foil shield with drain wire . The maximum system capacity is 10,000 feet (3048 m) of communications cable and 1,000 devices on the INCOM network . Make sure that the twisted-pair wire is recommended for INCOM network use . Use shielded twisted-pair wire to connect each slave to the INCOM network, daisy-chain style . The polarity of the twisted-pair is not important . Ground the shield at the host computer (device) .
4 . Set the jumper on the module to enable or disable the communications control as desired .
5 . Connectors are UL/CSA rated 300 V, VDE rated 250 V . The recommended connector is Weidmuller # BL 3 .5/90/5 BK, oriented for 90° lead exit . However, other lead orientations are possible . Wire gauge # 18 AWG/0 .82 mm2 .
6 . The final device in the daisy-chain configuration must have a 100 ohm termination resistor installed across terminals #1 and #2 on TB2 .
Figure 7.
PXR
�
��
�
�
�
19 25 27
20 26 28
INCOM communication module (ICAM).
10
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
otes:N
1 . The Series NRX communication module is a separate device that mounts on a DIN rail bracket . A separate harness is required to remotely mount and wire the module .
2 . The communications module voltage requirement is 24 Vdc ± 10% and should be sourced from a high quality supply (6 watts is the burden of the CAM) .
3 . MODBUS communication cable is a three conductor with shield type wire in “daisy chain” configuration . The recommended cable has a twisted-pair of wires (# 24 AWG stranded 7 x 32 conductors with PVC insulation) having an aluminum/mylar foil shield with drain wire . The maximum system capacity is 4,000 feet (1219 m) of communications cable and 32 unit loads on the MODBUS RTU net-work . Make sure that the twisted-pair wire is recommended for MODBUS RTU network use . Use shielded twisted-pair wire to con-nect each slave to the MODBUS RTU network, daisy-chain style . The polarity of the twisted-pair is not important . Ground the shield at the host computer (device) .
4 . Set the jumper on the module to enable or disable the communications control as desired .
5 . Connectors are UL/CSA rated 300 V, VDE rated 250 V . The recommended connector is Weidmuller # BL 3 .5/90/5 BK, oriented for 90° lead exit . However, other lead orientations are possible . Wire gauge # 18 AWG/0 .82 mm2 .
6 . The final device in the daisy-chain configuration must have a 121 ohm termination resistor installed across terminals #1 and #2 on TB2 .
Figure 8.
PXR
Series NRX Circuit Breaker
��
�
�
�
�
19
20 26 28
25 27
MODBUS communication module (MCAM).
11
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
Figure 9.
CommunicationsModule
TB2-6 TB2-3 TB2-8
390 ohm 390 ohm220 ohm
TB2-5
TB 29 pinD Sub
Female
53 4 68
Dat
a B
Dat
a A D
GN
D
CN
TR
-P/R
TS
VP
SH
IELD
(SH
ELL
)S
CR
EW
�
�
�
��
PXR
Series NRX Circuit Breaker
�
19
20 26 28
25 27
� �
PROFIBUS communication module (PCAM).
otes:N
1 . The Series NRX communication module is a separate device that mounts on a DIN rail bracket . A separate harness is required to remotely mount and wire the module .
2 . Communication module voltage requirement is 24 Vdc ± 10% and should be sourced from reliable service (6 watts is the burden of the CAM) .
3 . PROFIBUS DP communication cable uses a five conductor flexible cable with shield type wire in “daisy chain” configuration . The maximum cable length depends on Baud rate and can link up to 32 unit loads on the network . Ground the shield at host computer (device) . For further connection information, see PROFIBUS Order No . 2 .142 .
4 . Set jumper on the module to enable or disable communications control as desired .
5 . Connector TB1 is UL/CSA rated 300 V, VDE rated 250 V . Recommended: Weidmuller (BL 3 .5/90/5 BK) oriented for 90° lead exit, but other lead orientations are possible . Wire gauge: #18 AWG / 0 .82 mm2 .
6 . The final device on each end of the network in the daisy-chain configuration must have termination resistors installed as shown on TB2 .
12
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
otes:N
1 . The Series NRX communication module is a separate device that mounts on a DIN rail bracket . A separate harness is required to remotely mount and wire the module .
2 . The communications module voltage requirement is 24 Vdc ± 10% and should be sourced from a high quality supply (6 watts is the burden of the CAM) . A shielded CAT5, CAT5e, or CAT6 cable for 10/100 Mb/s ETHERNET is recommended .
3 . The shielded cable is recommended for the best communication reliability in industrial environments . The metal jack provides a ground to the housing on the ETHERNET communications adapter module, which is grounded to the breaker housing via the CAM ground pin . Be sure to ground the breaker housing per the instructions in the breaker IL .
4 . Set the jumper on the module to enable or disable the communications control as desired .
5 . Use shielded ETHERNET cable .
Figure 10.
�
�
�
�
PXR
Series NRX Circuit Breaker
�
19
20 26 28
25 27
ETHERNET communication module (ECAM).
13
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
otes:N
1 . The spring release and shunt trip wiring as shown for optional communication close or open capability .
2 . Choose the spring release coil voltage rating as desired if communications is required .
3 . Choose the shunt trip rating to be the same as spring release rating if communication is required .
4 . The control power rating must match the ST and SR coil rating .
5 . Close duration is two seconds on communication activation .
6 . The communication control jumper must be in the enable position for communications opening or closing .
7 . The spring release terminals are 43 & 44 for NF Frame/IZMX16 only . For RF Frame/IZMX40 breakers, the terminals are 55 & 56 .
Figure 11.
Series NRX Circuit Breaker
43 (NF/IZMX16)55 (RF/IZMX40)
44 (NF/IZMX16)56 (RF/IZMX40)
CommunicationsModule
����
���
�
�
�
Communication control (SR and ST wiring).
14
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
Figure 12.
Series NRX Circuit Breaker
Under voltage release.
ote:N
1 . Treated as the positive voltage for DC ratings .
15
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
Legend:
MOT – Motor operator for charging closing spring
ST – Shunt trip
SR – Spring release
Description of operation:
1 . The motor is energized and runs, charges closing spring, and is cut off by switch .
2 . When the spring is charged, the SC closes and the green indicating light will illuminate (if applicable) .
3 . Closing the CS-C contact energizes the spring release coil and closes the circuit breaker . The spring release internal electronics pulse the SR coil and then provides a high impedance circuit . This provides anti-pumping .
4 . When the spring discharges its energy, the motor switch will re-energize the charging motor until the spring is charged again .
5 . To detect the presence of voltage (Health Light), use Omron Red indicator LED Port # C22-L-R-120 for 120 Vac application . For 230 Vac application, use C22-L-R-230 . For 24 Vdc application, use C22-L- R-24 . Remove the white (22 mm [0 .89 in .]) diameter pilot light) Light Diffuser from the assembly to give better indication of voltage present . Activate the push-button to trip the circuit breaker . See Eaton for other voltages .
6 . For secondary contacts, odd numbers should be treated as positive for any accessory . This will not apply to AC ratings .
7 . Reference Figure 16 for internal circuit breaker wiring .
Figure 13.
Series NRX Circuit Breaker
43
44
41
42
40
Circuit breaker control – type NF Frame/IZMX16.
16
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
Figure 14.
Series NRX Circuit Breaker
253555
4565
Circuit breaker control – type RF Frame/IZMX40.
Legend:
MOT – Motor operator for charging closing spring
ST – Shunt trip
SR – Spring release
Description of Operation:
1 . The motor is energized and runs, charges the closing spring, and is cut off by the switch .
2 . When the spring is charged, SC closes and the green indicating light will illuminate (if applicable) .
3 . Closing the CS-C contact energizes spring release coil and closes circuit breaker . The spring release internal electronics pulse the SR coil and then provides a high impedance circuit . This provides anti-pumping .
4 . When the spring discharges its energy, the motor switch will re-energize the charging motor until the spring is charged again .
5 . To detect presence of voltage (Health Light), use Omron Red indicator LED Port # C22-L-R-120 for 120 Vac application . For 230 Vac application, use C22-L-R-230 . For 24 Vdc application, use C22-L- R-24 . Remove the white (22 mm [0 .89 in .]) diameter pilot light) Light Diffuser from the assembly to give better indication of voltage present . Activate the push-button to trip the circuit breaker . See Eaton for other voltages .
6 . For secondary contacts, odd numbers should be treated as positive for any accessory . This will not apply to AC ratings .
7 . Reference Figure 17 for internal circuit breaker wiring .
17
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
Figure 15.
LA
LB
LC
PTMODULE
BREAKER
A
0-600 L-L INPUT
B C
To additionalbreakers (16 max)
SecondaryContacts1
N
3 5
30 PTVB29 PTVA
31 PTVC
TP2
32 PTVN
LN
LA
LB
LC
PTMODULE
BREAKER
A
0-600 L-L INPUT
B C
To additionalbreakers (16 max)
SecondaryContacts1 3 5
30 PTVB29 PTVA
31 PTVC
TP2
32
Series NRX Mounted Breakers - 3 pole - 3 wire
Series NRX Mounted Breakers - 3 pole or 4 pole - 4 wire
Series NRX mounted breaker (with external PT module).
18
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
N:set
o
1.
Sec
onda
ry p
ositi
ons
and
labe
ls p
er 6
6B26
66 -
Mas
ter
NR
X s
econ
dary
map
.
2.
See
66B
2666
for
AC
CY
1-A
CC
Y7
optio
ns.
Sec
on
dar
y T
erm
inal
s
TA
MC
RS
eco
nd
ary
Ter
min
als
Tri
p U
nit
Bo
ard
Fram
e M
od
ule
Cir
cuit
Bre
aker
13
24
65
7
1614
13
ALM3
ALM1
ALMC
15ALM2
AB
CN 2 6 1 2 1 55 2 6 1 5 2 6 1 5
UV
R
34
UV1+
UV2-
ST
12
ST1+
ST2-
SR
4344
SR1
SR2
M
42
E01+
E02-
41
SC 40
40 P
ins
Co
nn
ecto
r
JP1
JP6
Au
x B
ox
Tra
y
5655
54
A4
C4
B4
46 A1
45 C1
47 B1
48 B2
49 C2
50 A2
52 A3
51 C3
53 B3
89
75
64
23
12931
3032
2627
2422 10
2821
3435
33
PTVC
PTVN
CMM3
ARMSIN
CMM4
MODBA
MODBB
PTVA
PTVB
CMM2
ZOUT
ZCOM
MODBG
ZIN
CMM1 25
1112
23
1415
1317
1816
JP1
21
VAUX-
VAUX+
45
23
1 VBUS
Data+
Data-
GND
US
B
J1J2
Au
x P
ow
er
JP5
21
43
57
6820
1918
17
+24V
G1
AGND
MCR2
TA-
TA+
JP4
8R
og
o C
oils
2G
rou
nd
Fau
lt (
G21
,G22
)
3V3
1.2V
Ref
SP
I5
5V 5.1V
_Sta
rt
3V_B
AT
VA
UX
_EX
VA
UX
1
ST
2
ST
-
Rel
ay_D
R3
5 OT1C
6 OT1M
7 OT1B
8 ACCY1
10 ACCY3
9 ACCY2
36 ACCY4
11N
1
12N
2
To
Fra
me
Mo
du
le J
P4
11 N1
12 N2
MCR1
G2
37 ACCY5
39 ACCY7
38 ACCY6
6
JP2
JP3
1 2 3 4
RO
G
CT
RO
G
CT
1 2 3 4
RO
G
4C
T
31 2
RO
G
CT
1 2 3 4
Fig
ure
16.
Typ
ical
bre
aker
mas
ter
con
nec
tio
n d
iag
ram
– t
ype
NF
Fram
e/IZ
MX
16.
19
Technical Data TD013001ENEffective July 2016
Series NRX with PXR circuit breaker wiring diagrams
EATON www.eaton.com
Fig
ure
17.
Typ
ical
bre
aker
mas
ter
con
nec
tio
n d
iag
ram
– t
ype
RF
Fram
e/IZ
MX
40.
ote
s:N 1.
S
econ
dary
pos
ition
s an
d la
bels
per
66B
2666
- M
aste
r N
RX
sec
onda
ry m
ap.
Au
x B
ox
Tra
y
Cir
cuit
Bre
aker
To
Fra
me
Mo
du
le J
P4
Tri
p U
nit
Bo
ard
Sec
on
dar
y T
erm
inal
s 1
TA
MC
R
Sec
on
dar
y T
erm
inal
s 1
Fram
e M
od
ule
13
24
65
71314
16
ALMC
ALM1
ALM3
15ALM2
AB
CN 2 6 1 2 1 55 2 6 1 5 2 6 1 5
UV
R
34
UV1+
UV2-
ST
12
ST1+
ST2-
1112
N1
N2
40 P
ins
Co
nn
ecto
r
JP1
JP6
89
75
64
23
12931
3032
2627
2422 10
1282
3435
33
PTVC
PTVN
CMM3
ARMSIN
CMM4
MODBA
MODBB
PTVA
PTVB
CMM2
ZOUT
ZCOM
MODBG
ZIN
CMM1 25
1112
23
1415
1317
1816
JP1
21
VAUX-
VAUX+
45
23
1 VBUS
Data+
Data-
GND
US
B
J1J2
Au
x P
ow
er
JP5
21
43
57
6820
1918
17
+24V
G1
AGND
MCR2
TA-
TA+
JP4
8R
og
o C
oils
2G
rou
nd
Fau
lt (
G21
,G22
)
3V3
1.2V
Ref
SP
I5
5V 5.1V
_Sta
rt
3V_B
AT
VA
UX
_EX
VA
UX
1
ST
2
ST
-
Rel
ay_D
R3
5 OT1C
6 OT1M
7 OT1B
8 OT2B
10 OT2M
9 OT2C
36 2CMM2
11N
1
12N
2
MCR1
G2
37 2CMM3
39 2CMM1
38 2CMM4
6
JP2
JP3
1 2 3 4
RO
G
CT
RO
G
CT
1 2 3 4
RO
G
4C
T
31 2
RO
G
CT
1 2 3 4
40 ARCON1
41 ARCON2
42ARCON3
43 RR1
44 RR2
4546
4748
6867
66
A4
C4
B4
58 A1
57 C1
59 B1
60 B2
61 C2
62 A2
64 A3
63 C3
65 B3
MS
R
8079
78
A8
C8
B8
70 A5
69 C5
71 B5
72 B6
73 C6
74 A6
76 A7
75 C7
77 B7
9291
90
A12
C12
B12
82 A981 C9
83 B9
84 B10
85 C10
86 A10
88 A11
87 C11
89 B11
4950
5153
5556
54
LCM
EO1+
EO2-
LCC
LCB
SR1
SC 52
SR2
S
eco
nd
ary
Ter
min
als
293
9495
96
Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton .com
© 2016 EatonAll Rights ReservedPrinted in USAPublication No . TD013001EN / TBG01219Part Number: TD013001ENH03July 2016
Eaton is a registered trademark.
All other trademarks are property of their respective owners.
Series NRX with PXR circuit breaker wiring diagrams
Technical Data TD013001ENEffective July 2016
Disclaimer of warranties and limitation of liability
The information, recommendations, descriptions, and safety nota-tions in this document are based on Eaton’s experience and judg-ment . This instructional literature is published solely for information purposes and should not be considered all-inclusive . If further information is required, you should consult an authorized Eaton sales representative .
The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between the parties . This literature is not intended to and does not enlarge or add to any such contract . The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton .
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS, AND DESCRIPTIONS CONTAINED HEREIN.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and description contained herein .
The information contained in this manual is subject to change without notice .