Technical Data TD013001EN Effective July 2016 Supersedes August 2015 Series NRX Contents Description Page General wiring notes 2 Figure 1 Zone interlock wiring 3 Figure 2 Ground fault residual 3-phase, 4-wire 4 Figure 3 Source ground fault sensing 5 Figure 4 Zero sequence ground fault sensing 6 Figure 5 PXR alarm wiring 7 Figure 6 Maintenance mode wiring 8 Figure 7 INCOM communication module (ICAM) 9 Figure 8 MODBUS communication module (MCAM) 10 Figure 9 PROFIBUS communication module (PCAM) 11 Figure 10 ETHERNET communication module (ECAM) 12 Figure 11 Communication control (SR and ST wiring) 13 Figure 12 Under voltage release 14 Figure 13 Circuit breaker control – type NF frame/IZMX16 15 Figure 14 Circuit breaker control – type RF frame/IZMX40 16 Figure 15 Series NRX mounted breaker (with external PT module) 17 Figure 16 Typical breaker master connection diagram – type NF frame/IZMZ16 18 Figure 17 Typical breaker master connection diagram – type RF frame/IZMX40 19 Series NRX with PXR circuit breaker wiring diagrams Instructions apply to: UL489 series NRX RF frame IEC IZMX40 UL1066/ANSI, UL489 series NRX NF frame IEC IZMX16

Transcript of PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON...

Page 1: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

Technical Data TD013001ENEffective July 2016Supersedes August 2015 Series NRX

ContentsDescription Page

General wiring notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Figure 1 . Zone interlock wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Figure 2 . Ground fault residual 3-phase, 4-wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Figure 3 . Source ground fault sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Figure 4 . Zero sequence ground fault sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Figure 5 . PXR alarm wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Figure 6 . Maintenance mode wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Figure 7 . INCOM communication module (ICAM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Figure 8 . MODBUS communication module (MCAM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Figure 9 . PROFIBUS communication module (PCAM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Figure 10 . ETHERNET communication module (ECAM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Figure 11 . Communication control (SR and ST wiring) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Figure 12 . Under voltage release . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Figure 13 . Circuit breaker control – type NF frame/IZMX16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Figure 14 . Circuit breaker control – type RF frame/IZMX40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Figure 15 . Series NRX mounted breaker (with external PT module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Figure 16 . Typical breaker master connection diagram – type NF frame/IZMZ16 . . . . . . . . . . . . . . . . . . 18Figure 17 . Typical breaker master connection diagram – type RF frame/IZMX40 . . . . . . . . . . . . . . . . . . . 19

Series NRX with PXR circuit breaker wiring diagrams

Instructions apply to:

UL489 series NRX RF frame IEC IZMX40

UL1066/ANSI, UL489 series NRX NF frame IEC IZMX16

Page 2: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

2

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

General wiring notes1 . Each contact block on the Secondary Terminal Block contains

four independent contacts (Figure A) . A possible 14 terminal blocks will provide 56 contact points for the type NF frame . A possible 24 terminal blocks will provide 96 contact points for the type RF frame .

Figure A. Secondary terminal blocks.

2 . Drawout circuit breakers use Style 67C3246 contact blocks that mount onto an insulated support frame on the cassette .

3 . Fixed mounted circuit breakers use Style 67C3247 contact blocks that mount onto an insulated support frame . The cus-tomer tension connectors are at an angle .

4 . Customer wiring is done using a tension clamp termination on each contact .

5 . Contact blocks are individually mounted and hence contact positions may be empty depending on accessories and options ordered .

6 . The tension clamp terminals will support solid or flexible conduc-tors, #12/4 mm2 through #26/0 .5 mm2 AWG wire and are rated for 600 V, 10 A .

7 . The recommended wire strip length is 10-12 mm (0 .39 - 0 .47 in) .

8 . The tension clamp terminals also support finely stranded conduc-tors with wire-end ferrules and plastic collars DIN 46228/4, rated connection .

9 . The two-point blue plugs house two female crimp contacts (Style 67C3249), with the odd assigned numbers having the coded rib feature on the blue plug (Figure B) .

ote:N Note that the connector plug must be oriented as shown in Figure B before making the connection .

10 . For secondary contacts, odd numbers should be treated as posi-tive voltage for any accessory . This will not apply for AC ratings .

11 . Reference tool for removing leads from secondary contact con-nector plug – 68D3288H01 Extraction Tool (Figure C) .

Table 1. Customer wiring details.

Type of conductor Tension clamp connection

Recommended strip length or ferrule length

Solid cross section (min - max) 0.5 - 4 mm² 10 - 12 mm (0.39 - 0.47 in.)

Flexible cross section (min - max)

0.5 - 4 mm² 10 - 12 mm (0.39 - 0.47 in.)

American wire gauge - AWG (min - max)

26 - 12 AWG 10 - 12 mm (0.39 - 0.47 in.)

Flexible cross section with wire end ferrule without plastic sleeve - DIN 46228/1 (min - max)

0.5 - 2.5 mm² (26 - 14 AWG)

10 - 12 mm (0.39 - 0.47 in.)

Flexible cross section with wire end furrule with plastic sleeve - DIN 46228/4 (min - max)

0.5 - 1.5 mm² (26 - 16 AWG)

16 - 18 mm (0.63 - 0.71 in.)

Gauge to IEC 60947-1. A3

Figure B. Accessory plug and crimp contact.

Figure C. Extraction tool in use.

Fixed terminal block

Drawout terminal block

Secondary lead

Connector Plug

Terminal extraction tool

Page 3: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

3

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

2423

21

PXR

2423

21

PXR

2423

21

PX

R

2423

21

PX

R

ote

s:N 1 .

Tw

iste

d to

geth

er A

WG

#14

to

#20

copp

er w

ire .

Rou

te t

he z

one

inte

rlock

wiri

ng

sepa

rate

fro

m p

ower

con

duct

ors .

D

O N

OT

GR

OU

ND

any

zon

e in

terlo

ck w

iring

.

2 .

The

max

imum

dis

tanc

e be

twee

n tw

o fa

rthe

st b

reak

ers

on d

iffer

ent

zone

s (f

rom

the

Z o

ut d

owns

trea

m t

o th

e Z i

n up

stre

am t

erm

inal

s) is

250

feet

(75

m) .

3 .

A m

axim

um o

f 20

bre

aker

s m

ay b

e co

ntai

ned

in p

aral

lel i

n on

e zo

ne .

4 .

Prov

ide

a se

lf in

terlo

ckin

g ju

mpe

r (o

n zo

ne 3

), if

coor

dina

tion

is d

esire

d w

ith o

ther

do

wns

trea

m b

reak

ers

not

prov

idin

g th

e Zo

ne In

terlo

ck fe

atur

e .

Fig

ure

1. Z

on

e in

terl

ock

wir

ing

.

Page 4: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

4

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

Figure 2.

PXR

Series NRX Circuit Breaker

11

12

Ground fault residual 3-phase, 4-wire.

otes:N

1 . Sensor is customer wired to sense neutral currents . This is required for 3-phase, 4-wire residual ground fault (applicable for trip units having G protection) .

2 .

Series NRX frame Ground (earth) sensing method Sensor style IZMX type coding

NFResidual

5721B76G12 IZMX-CT16-N

RF 70C1718G11 IZMX-CT40-N

Page 5: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

5

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

Figure 3. Source ground fault sensing.

PXR

Series NRX Circuit Breaker

ExternalSensor

ote:N

1 . Sensor NFGFSKIT (IZMX-EFS) is used to sense and detect ground fault currents . The part number is 70C1527G04 .

Page 6: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

6

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

Figure 4.

Series NRX Circuit Breaker

PXR

Zero sequence ground fault sensing.

ote:N

1 . Sensor NFGFSKIT (IZMX-EFS) is used to sense and detect ground fault currents of 3-wire or 4-wire . The part number is 70C1527G04 .

Page 7: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

7

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

Figure 5.

Series NRX Circuit Breaker

24VDC ±10%

13

14� � �

15

16

19

20

ALM-Com ALM1ALM2 ALM3

Control Power

PXR alarm wiring.

otes:N

1 . For the PXR20/25, the Alarm 1 is for Remote Indication/ Maintenance Mode indication . Contact rating 1 A @ 120 Vac, 1 A @ 24 Vdc, and 0 .5 A @ 230 Vac .

2 . For the PXR20/25, the Alarm 2 is for High Load alarm/Ground Fault alarm . Contact rating 1 A @ 120 Vac, 1 A @ 24 Vdc, and 0 .5 A @ 230 Vac .

3 . For the PXR20/25, the Alarm 3 is for Trip N .O . contact . Contact rating 1 A @ 120 Vac, 1 A @ 24 Vdc, and 0 .5 A @ 230 Vac .

4 . If the control voltage is +24 Vdc, the trip unit should be fed from a separate, galvanically isolated + 24 V voltage dc supply .

Page 8: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

8

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

Ser

ies

NR

X C

ircu

it B

reak

erS

erie

s N

RX

Cir

cuit

Bre

aker

Alt

ern

ate

Cu

sto

mer

Wir

ing

(p

arti

al)

Mai

nte

nan

ce M

od

e W

irin

g

1319

22

2214

2020

ote

s:N 1 .

P

XR

20/2

5 ca

n lo

cally

be

plac

ed in

mai

nten

ance

mod

e vi

a a

two

posi

tion

switc

h lo

cate

d on

the

trip

uni

t . T

he f

unct

ion

can

be a

rmed

via

a r

emot

e sw

itch

as s

how

n .

In a

dditi

on, t

he f

unct

ion

can

be a

ctiv

ated

via

com

mun

icat

ion

mod

ules

. A

blu

e LE

D o

n th

e P

XR

ver

ifies

the

PX

R r

elea

se in

mai

nten

ance

mod

e .

2 .

The

reco

mm

ende

d se

lect

or s

witc

h fo

r th

is lo

w v

olta

ge a

pplic

atio

n is

Eat

on p

art

num

ber

1025

0T13

3-2E

whi

ch in

clud

es a

con

tact

blo

ck r

ated

for

logi

c le

vel a

nd

corr

osiv

e us

e .

3 .

The

max

imum

leng

th o

f th

is w

iring

to

rem

otel

y ar

m t

he s

witc

h (o

r al

tern

ate

rela

y co

ntac

t) is

9 .7

8 fe

et (3

m) .

Use

#20

AW

G w

ire o

r la

rger

.

4 .

A r

emot

e S

tack

Lig

ht A

nnun

ciat

or p

anel

or

othe

r re

mot

e in

dica

tion

devi

ce c

an b

e co

nnec

ted

to v

erify

tha

t P

XR

is in

the

mai

nten

ance

mod

e .

5 .

The

rela

y in

the

PX

R r

elea

se m

akes

whe

n in

mai

nten

ance

mod

e .

Con

tact

is r

ated

1 A

@ 1

20 V

ac, 1

A @

24

Vdc

, an

d 0 .

5 A

@ 2

30 V

ac .

6 .

The

PX

R r

elea

se c

an a

lso

be p

lace

d re

mot

ely

in it

s m

aint

enan

ce m

ode

via

a ge

nera

l pur

pose

rel

ay (i

ce c

ube

type

with

logi

c le

vel c

onta

cts)

and

act

ivat

ed b

y a

rem

ote

cont

rol s

witc

h . A

rec

omm

ende

d ty

pe is

IDE

C r

elay

RY

22 .

Cho

ose

the

volta

ge a

s de

sire

d .

7 .

If a

com

mun

icat

ion

mod

ule

is u

sed,

see

Fig

ures

6, 7

8, a

nd 9

for

diff

eren

t w

iring

. Th

e co

mm

unic

atio

n m

odul

e w

ill r

equi

re 2

4 V

dc p

ower

and

will

pro

vide

isol

ated

po

wer

to

the

PX

R r

elea

se

in t

he c

ircui

t br

eake

r . If

a c

omm

unic

atio

n m

odul

e is

not

use

d, t

he P

XR

rel

ease

tha

t re

quire

s au

xilia

ry v

olta

ge f

or a

larm

s w

hich

sho

uld

be fe

d fr

om a

gal

vani

cally

isol

ated

, 24

Vdc

sup

ply .

Fig

ure

6. M

ain

ten

ance

mo

de

wir

ing

.

Page 9: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

9

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

otes:N

1 . The Series NRX communication module is a separate device that mounts on a DIN rail bracket . A separate harness is required to remotely mount and wire the module .

2 . The communications module voltage requirement is 24 Vdc ± 10% and should be sourced from a high quality supply (6 watts is the burden of the CAM) .

3 . INCOM communication cable is a two conductor with shield type wire in “daisy chain” configuration . The recommended cable (Belden “Blue Hose” # 9643 or equivalent) has a twisted-pair of wires (# 20 AWG stranded 7 x 28 conductors with PVC insulation) having an aluminum/mylar foil shield with drain wire . The maximum system capacity is 10,000 feet (3048 m) of communications cable and 1,000 devices on the INCOM network . Make sure that the twisted-pair wire is recommended for INCOM network use . Use shielded twisted-pair wire to connect each slave to the INCOM network, daisy-chain style . The polarity of the twisted-pair is not important . Ground the shield at the host computer (device) .

4 . Set the jumper on the module to enable or disable the communications control as desired .

5 . Connectors are UL/CSA rated 300 V, VDE rated 250 V . The recommended connector is Weidmuller # BL 3 .5/90/5 BK, oriented for 90° lead exit . However, other lead orientations are possible . Wire gauge # 18 AWG/0 .82 mm2 .

6 . The final device in the daisy-chain configuration must have a 100 ohm termination resistor installed across terminals #1 and #2 on TB2 .

Figure 7.

PXR

��

19 25 27

20 26 28

INCOM communication module (ICAM).

Page 10: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

10

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

otes:N

1 . The Series NRX communication module is a separate device that mounts on a DIN rail bracket . A separate harness is required to remotely mount and wire the module .

2 . The communications module voltage requirement is 24 Vdc ± 10% and should be sourced from a high quality supply (6 watts is the burden of the CAM) .

3 . MODBUS communication cable is a three conductor with shield type wire in “daisy chain” configuration . The recommended cable has a twisted-pair of wires (# 24 AWG stranded 7 x 32 conductors with PVC insulation) having an aluminum/mylar foil shield with drain wire . The maximum system capacity is 4,000 feet (1219 m) of communications cable and 32 unit loads on the MODBUS RTU net-work . Make sure that the twisted-pair wire is recommended for MODBUS RTU network use . Use shielded twisted-pair wire to con-nect each slave to the MODBUS RTU network, daisy-chain style . The polarity of the twisted-pair is not important . Ground the shield at the host computer (device) .

4 . Set the jumper on the module to enable or disable the communications control as desired .

5 . Connectors are UL/CSA rated 300 V, VDE rated 250 V . The recommended connector is Weidmuller # BL 3 .5/90/5 BK, oriented for 90° lead exit . However, other lead orientations are possible . Wire gauge # 18 AWG/0 .82 mm2 .

6 . The final device in the daisy-chain configuration must have a 121 ohm termination resistor installed across terminals #1 and #2 on TB2 .

Figure 8.

PXR

Series NRX Circuit Breaker

��

19

20 26 28

25 27

MODBUS communication module (MCAM).

Page 11: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

11

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

Figure 9.

CommunicationsModule

TB2-6 TB2-3 TB2-8

390 ohm 390 ohm220 ohm

TB2-5

TB 29 pinD Sub

Female

53 4 68

Dat

a B

Dat

a A D

GN

D

CN

TR

-P/R

TS

VP

SH

IELD

(SH

ELL

)S

CR

EW

��

PXR

Series NRX Circuit Breaker

19

20 26 28

25 27

� �

PROFIBUS communication module (PCAM).

otes:N

1 . The Series NRX communication module is a separate device that mounts on a DIN rail bracket . A separate harness is required to remotely mount and wire the module .

2 . Communication module voltage requirement is 24 Vdc ± 10% and should be sourced from reliable service (6 watts is the burden of the CAM) .

3 . PROFIBUS DP communication cable uses a five conductor flexible cable with shield type wire in “daisy chain” configuration . The maximum cable length depends on Baud rate and can link up to 32 unit loads on the network . Ground the shield at host computer (device) . For further connection information, see PROFIBUS Order No . 2 .142 .

4 . Set jumper on the module to enable or disable communications control as desired .

5 . Connector TB1 is UL/CSA rated 300 V, VDE rated 250 V . Recommended: Weidmuller (BL 3 .5/90/5 BK) oriented for 90° lead exit, but other lead orientations are possible . Wire gauge: #18 AWG / 0 .82 mm2 .

6 . The final device on each end of the network in the daisy-chain configuration must have termination resistors installed as shown on TB2 .

Page 12: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

12

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

otes:N

1 . The Series NRX communication module is a separate device that mounts on a DIN rail bracket . A separate harness is required to remotely mount and wire the module .

2 . The communications module voltage requirement is 24 Vdc ± 10% and should be sourced from a high quality supply (6 watts is the burden of the CAM) . A shielded CAT5, CAT5e, or CAT6 cable for 10/100 Mb/s ETHERNET is recommended .

3 . The shielded cable is recommended for the best communication reliability in industrial environments . The metal jack provides a ground to the housing on the ETHERNET communications adapter module, which is grounded to the breaker housing via the CAM ground pin . Be sure to ground the breaker housing per the instructions in the breaker IL .

4 . Set the jumper on the module to enable or disable the communications control as desired .

5 . Use shielded ETHERNET cable .

Figure 10.

PXR

Series NRX Circuit Breaker

19

20 26 28

25 27

ETHERNET communication module (ECAM).

Page 13: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

13

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

otes:N

1 . The spring release and shunt trip wiring as shown for optional communication close or open capability .

2 . Choose the spring release coil voltage rating as desired if communications is required .

3 . Choose the shunt trip rating to be the same as spring release rating if communication is required .

4 . The control power rating must match the ST and SR coil rating .

5 . Close duration is two seconds on communication activation .

6 . The communication control jumper must be in the enable position for communications opening or closing .

7 . The spring release terminals are 43 & 44 for NF Frame/IZMX16 only . For RF Frame/IZMX40 breakers, the terminals are 55 & 56 .

Figure 11.

Series NRX Circuit Breaker

43 (NF/IZMX16)55 (RF/IZMX40)

44 (NF/IZMX16)56 (RF/IZMX40)

CommunicationsModule

����

���

Communication control (SR and ST wiring).

Page 14: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

14

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

Figure 12.

Series NRX Circuit Breaker

Under voltage release.

ote:N

1 . Treated as the positive voltage for DC ratings .

Page 15: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

15

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

Legend:

MOT – Motor operator for charging closing spring

ST – Shunt trip

SR – Spring release

Description of operation:

1 . The motor is energized and runs, charges closing spring, and is cut off by switch .

2 . When the spring is charged, the SC closes and the green indicating light will illuminate (if applicable) .

3 . Closing the CS-C contact energizes the spring release coil and closes the circuit breaker . The spring release internal electronics pulse the SR coil and then provides a high impedance circuit . This provides anti-pumping .

4 . When the spring discharges its energy, the motor switch will re-energize the charging motor until the spring is charged again .

5 . To detect the presence of voltage (Health Light), use Omron Red indicator LED Port # C22-L-R-120 for 120 Vac application . For 230 Vac application, use C22-L-R-230 . For 24 Vdc application, use C22-L- R-24 . Remove the white (22 mm [0 .89 in .]) diameter pilot light) Light Diffuser from the assembly to give better indication of voltage present . Activate the push-button to trip the circuit breaker . See Eaton for other voltages .

6 . For secondary contacts, odd numbers should be treated as positive for any accessory . This will not apply to AC ratings .

7 . Reference Figure 16 for internal circuit breaker wiring .

Figure 13.

Series NRX Circuit Breaker

43

44

41

42

40

Circuit breaker control – type NF Frame/IZMX16.

Page 16: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

16

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

Figure 14.

Series NRX Circuit Breaker

253555

4565

Circuit breaker control – type RF Frame/IZMX40.

Legend:

MOT – Motor operator for charging closing spring

ST – Shunt trip

SR – Spring release

Description of Operation:

1 . The motor is energized and runs, charges the closing spring, and is cut off by the switch .

2 . When the spring is charged, SC closes and the green indicating light will illuminate (if applicable) .

3 . Closing the CS-C contact energizes spring release coil and closes circuit breaker . The spring release internal electronics pulse the SR coil and then provides a high impedance circuit . This provides anti-pumping .

4 . When the spring discharges its energy, the motor switch will re-energize the charging motor until the spring is charged again .

5 . To detect presence of voltage (Health Light), use Omron Red indicator LED Port # C22-L-R-120 for 120 Vac application . For 230 Vac application, use C22-L-R-230 . For 24 Vdc application, use C22-L- R-24 . Remove the white (22 mm [0 .89 in .]) diameter pilot light) Light Diffuser from the assembly to give better indication of voltage present . Activate the push-button to trip the circuit breaker . See Eaton for other voltages .

6 . For secondary contacts, odd numbers should be treated as positive for any accessory . This will not apply to AC ratings .

7 . Reference Figure 17 for internal circuit breaker wiring .

Page 17: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

17

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

Figure 15.

LA

LB

LC

PTMODULE

BREAKER

A

0-600 L-L INPUT

B C

To additionalbreakers (16 max)

SecondaryContacts1

N

3 5

30 PTVB29 PTVA

31 PTVC

TP2

32 PTVN

LN

LA

LB

LC

PTMODULE

BREAKER

A

0-600 L-L INPUT

B C

To additionalbreakers (16 max)

SecondaryContacts1 3 5

30 PTVB29 PTVA

31 PTVC

TP2

32

Series NRX Mounted Breakers - 3 pole - 3 wire

Series NRX Mounted Breakers - 3 pole or 4 pole - 4 wire

Series NRX mounted breaker (with external PT module).

Page 18: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

18

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

N:set

o

1.

Sec

onda

ry p

ositi

ons

and

labe

ls p

er 6

6B26

66 -

Mas

ter

NR

X s

econ

dary

map

.

2.

See

66B

2666

for

AC

CY

1-A

CC

Y7

optio

ns.

Sec

on

dar

y T

erm

inal

s

TA

MC

RS

eco

nd

ary

Ter

min

als

Tri

p U

nit

Bo

ard

Fram

e M

od

ule

Cir

cuit

Bre

aker

13

24

65

7

1614

13

ALM3

ALM1

ALMC

15ALM2

AB

CN 2 6 1 2 1 55 2 6 1 5 2 6 1 5

UV

R

34

UV1+

UV2-

ST

12

ST1+

ST2-

SR

4344

SR1

SR2

M

42

E01+

E02-

41

SC 40

40 P

ins

Co

nn

ecto

r

JP1

JP6

Au

x B

ox

Tra

y

5655

54

A4

C4

B4

46 A1

45 C1

47 B1

48 B2

49 C2

50 A2

52 A3

51 C3

53 B3

89

75

64

23

12931

3032

2627

2422 10

2821

3435

33

PTVC

PTVN

CMM3

ARMSIN

CMM4

MODBA

MODBB

PTVA

PTVB

CMM2

ZOUT

ZCOM

MODBG

ZIN

CMM1 25

1112

23

1415

1317

1816

JP1

21

VAUX-

VAUX+

45

23

1 VBUS

Data+

Data-

GND

US

B

J1J2

Au

x P

ow

er

JP5

21

43

57

6820

1918

17

+24V

G1

AGND

MCR2

TA-

TA+

JP4

8R

og

o C

oils

2G

rou

nd

Fau

lt (

G21

,G22

)

3V3

1.2V

Ref

SP

I5

5V 5.1V

_Sta

rt

3V_B

AT

VA

UX

_EX

VA

UX

1

ST

2

ST

-

Rel

ay_D

R3

5 OT1C

6 OT1M

7 OT1B

8 ACCY1

10 ACCY3

9 ACCY2

36 ACCY4

11N

1

12N

2

To

Fra

me

Mo

du

le J

P4

11 N1

12 N2

MCR1

G2

37 ACCY5

39 ACCY7

38 ACCY6

6

JP2

JP3

1 2 3 4

RO

G

CT

RO

G

CT

1 2 3 4

RO

G

4C

T

31 2

RO

G

CT

1 2 3 4

Fig

ure

16.

Typ

ical

bre

aker

mas

ter

con

nec

tio

n d

iag

ram

– t

ype

NF

Fram

e/IZ

MX

16.

Page 19: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

19

Technical Data TD013001ENEffective July 2016

Series NRX with PXR circuit breaker wiring diagrams

EATON www.eaton.com

Fig

ure

17.

Typ

ical

bre

aker

mas

ter

con

nec

tio

n d

iag

ram

– t

ype

RF

Fram

e/IZ

MX

40.

ote

s:N 1.

S

econ

dary

pos

ition

s an

d la

bels

per

66B

2666

- M

aste

r N

RX

sec

onda

ry m

ap.

Au

x B

ox

Tra

y

Cir

cuit

Bre

aker

To

Fra

me

Mo

du

le J

P4

Tri

p U

nit

Bo

ard

Sec

on

dar

y T

erm

inal

s 1

TA

MC

R

Sec

on

dar

y T

erm

inal

s 1

Fram

e M

od

ule

13

24

65

71314

16

ALMC

ALM1

ALM3

15ALM2

AB

CN 2 6 1 2 1 55 2 6 1 5 2 6 1 5

UV

R

34

UV1+

UV2-

ST

12

ST1+

ST2-

1112

N1

N2

40 P

ins

Co

nn

ecto

r

JP1

JP6

89

75

64

23

12931

3032

2627

2422 10

1282

3435

33

PTVC

PTVN

CMM3

ARMSIN

CMM4

MODBA

MODBB

PTVA

PTVB

CMM2

ZOUT

ZCOM

MODBG

ZIN

CMM1 25

1112

23

1415

1317

1816

JP1

21

VAUX-

VAUX+

45

23

1 VBUS

Data+

Data-

GND

US

B

J1J2

Au

x P

ow

er

JP5

21

43

57

6820

1918

17

+24V

G1

AGND

MCR2

TA-

TA+

JP4

8R

og

o C

oils

2G

rou

nd

Fau

lt (

G21

,G22

)

3V3

1.2V

Ref

SP

I5

5V 5.1V

_Sta

rt

3V_B

AT

VA

UX

_EX

VA

UX

1

ST

2

ST

-

Rel

ay_D

R3

5 OT1C

6 OT1M

7 OT1B

8 OT2B

10 OT2M

9 OT2C

36 2CMM2

11N

1

12N

2

MCR1

G2

37 2CMM3

39 2CMM1

38 2CMM4

6

JP2

JP3

1 2 3 4

RO

G

CT

RO

G

CT

1 2 3 4

RO

G

4C

T

31 2

RO

G

CT

1 2 3 4

40 ARCON1

41 ARCON2

42ARCON3

43 RR1

44 RR2

4546

4748

6867

66

A4

C4

B4

58 A1

57 C1

59 B1

60 B2

61 C2

62 A2

64 A3

63 C3

65 B3

MS

R

8079

78

A8

C8

B8

70 A5

69 C5

71 B5

72 B6

73 C6

74 A6

76 A7

75 C7

77 B7

9291

90

A12

C12

B12

82 A981 C9

83 B9

84 B10

85 C10

86 A10

88 A11

87 C11

89 B11

4950

5153

5556

54

LCM

EO1+

EO2-

LCC

LCB

SR1

SC 52

SR2

S

eco

nd

ary

Ter

min

als

293

9495

96

Page 20: PXR - Wiring diagrams · 2020. 8. 21. · Series NRX with PXR circuit breaker wiring diagrams EATON www .eaton .com Figure 2. PXR Series NRX Circuit Breaker 11 12 Ground fault residual

Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton .com

© 2016 EatonAll Rights ReservedPrinted in USAPublication No . TD013001EN / TBG01219Part Number: TD013001ENH03July 2016

Eaton is a registered trademark.

All other trademarks are property of their respective owners.

Series NRX with PXR circuit breaker wiring diagrams

Technical Data TD013001ENEffective July 2016

Disclaimer of warranties and limitation of liability

The information, recommendations, descriptions, and safety nota-tions in this document are based on Eaton’s experience and judg-ment . This instructional literature is published solely for information purposes and should not be considered all-inclusive . If further information is required, you should consult an authorized Eaton sales representative .

The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between the parties . This literature is not intended to and does not enlarge or add to any such contract . The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton .

NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS, AND DESCRIPTIONS CONTAINED HEREIN.

In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and description contained herein .

The information contained in this manual is subject to change without notice .